Académique Documents
Professionnel Documents
Culture Documents
2, APRIL 2001
I. INTRODUCTION
(1)
where
is time, the independent variable,
Fig. 3. Instrumentation. is the load current in per unit, a forcing function
variable,
to increase the loading to near-rated or above, all three of the is the ambient temperature, a second forcing func-
parallel transformers were removed from service during each tion variable,
178 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 16, NO. 2, APRIL 2001
Fig. 4. July 34 recorded test data. Measured load currentlight line; measured top oil temperatureupper heavy line; measured ambient temperaturebottom
heavy line.
is the top oil temperature, the solution variable, Initial values for the sought parameters are guessed at and a
is the ratio of copper loss to iron loss at rated load univariate search technique [3] is used. Each parameter is varied
( ), one at a time until the objective function is minimized in that
is the rated top oil temperature rise above ambient, direction. Then a new search is carried out in the nest parameter
is the top oil time constant, and direction starting from the previous minimum. This is repeated
is an exponent due to the nonlinear heat transfer over all three parameter directions until no further minimization
relationship. of the objective function takes place.
The corresponding difference equation, also from the com- The starting value for , that is , is set equal to
panion paper, is the measured value of at the start of the 24-hour test period.
Incidentally, it turns out that the results are quite insensitive to
this value.
When (3) cannot further be minimized, the optimum values
(2) of the parameters , , and have been found and can be
where used for any ambient temperature or loading condition, provided
is the small difference operator. that the pumps and fans are on, and that the tap position is not
If no parameters are known, then the last four items of the too far off (discussed below).
foregoing list of eight above, are to be found. For this study,
one of the parameters was known accurately a priori: the load- C. Results for July Test
loss-to-no-load-loss ratio from factory tests. The optimization procedure yielded the following values:
Thus the three parameters to be determined are C
which can be compared with the factory test value, days hours
which was not measured at the factory, and .
which might be presumed unity, but not assumed so Fig. 5 shows the top oil temperature measured and calculated
here, as a matter of interest. curves. They are so close that it is difficult to distinguish them
at this scale resolution.
B. Parameter Estimation Method It was surprising that was 0.9 rather than 1.0, which is the
The parameter estimation procedure is based on a nonlinear usual assumption for directed-flow oil cooling, as was the case
integral-squared error objective function [2] defined by here. The optimization minimum occurred for ,
for both tests, so there is little doubt about the validity. The im-
(3) plication is that the cooling is not as effective as one might as-
sume, for this transformer. The cooling is, however, adequate,
where since the top oil rise agrees well with the factory value, as men-
is a vector whose elements are the three parameters tioned below.
listed above,
is the top oil temperature at each time step as calcu- D. Application to the Conditions of the February Test
lated from (2), The very good fit of the previous section is all very well, but
is the measured top oil temperature at each time there needs to be a check under other conditions. Ideally, these
step, and would be overload conditions, but that was not easily possible
is the index for each 3-minute time step over the because of system loading conditions at the time of the tests. In-
24-hour period. stead, a comparison is made under drastically different ambient
SWIFT et al.: A FUNDAMENTAL APPROACH TO TRANSFORMER THERMAL MODELINGPART II: FIELD VERIFICATION 179
Fig. 5. Measured (jagged trace) and Model (smoother trace) top oil temperature.
Fig. 6. July TestFebruary Test comparison. Upper curves: July Measured (jagged) and Model (smooth). Lower curves: February Measured (jagged) and Model
(smooth) using July parameters.