Vous êtes sur la page 1sur 5

Capacitor Banks In Power System (part three)

electrical-engineering-portal.com/capacitor-banks-in-power-system-part-three

03/03/2012

Low Voltage Power Capacitor

Continued from part two Capacitor Banks In Power System (part two)

Maximum Permissible Current


Capacitor units shall be suitable for continuous operation at an RMS current of 1.30 times the current that occurs at
rated sinusoidal voltage and rated frequency, excluding transients. Taking into account the capacitance tolerances of
1.1 CN, the maximum permissible current can be up to 143 IN.

These overcurrent factors are intended to take care of the combined eects of harmonics and overvoltages up to
and including1.10 UN, according to IS 13340.

Top

Discharge Device
Each capacitor unit or bank shall be provided with a directly connected discharge device. The discharge device
shall reduce the residual voltage from the crest value of the rated value UN to 50 V or less within 1 min, after the
capacitor is disconnected from the source of supply. There must be no switch, fuse or any other isolating device

1/5
between the capacitor unit and the discharge device.

A discharge device is not a substitute for short-circuiting the capacitor terminals together and to earth before
handling.

Where:

t = time for discharge from UN Jr to UR(s),


R = equals discharge resistance
C = rated capacitance (pF) per phase,
UN = rated voltage of unit (V),
UR = permissible residual voltage
k = coecient depending on both resistance and capacitor unit connections, Value of k to be taken as per IS13340

Top

Conguration of Capacitor bank


A delta-connected bank of capacitors is usually applied to voltage classes of 2400 volts or less.

In a three-phase system, to supply the same reactive power, the star connection requires a capacitor with a
capacitance three times higher than the delta connected capacitor. In addition, the capacitor with the star connection
results to be subjected to a voltage 3 lower and ows through by a current 3 higher than a capacitor inserted and
delta connected.

For Three Phase STAR Connection

Capacity of the capacitor bank C = Qc / (2F rUr2)


Rated current of the components IRC = 2FrCUr / 3
Line current I = IRC

Three Phase Delta Connection

Capacity of the capacitor bank C = Qc / (2F rUr2.3)


Rated current of the components IRC = 2FrCUr
Line current I = IRC / 3

Where,

Ur = rated voltage, which the capacitor must withstand indenitely;


F r = rated frequeny
Qc = generally expressed in kVAR ( reactive power of the capacitor bank)

While deciding the size of capacitor bank on any bus it is necessary to check the voltage rise due to installation of
capacitors under full load and light load conditions. It is recommended to limit the voltage rise to maximum of 3% of
the bus voltage under light load conditions. The voltage rise due to capacitor installation may be worked out by the
following expression.

Top

Voltage Drop/Rise Due to Switching


2/5
Switching on or o a large block of load causes voltage change. The approximate value can be estimated by:

Voltage change load in MVA/fault level in MVA

Switching a capacitor bank causes voltage change, which can be estimated by:

Voltage change capacitor bank rating in MVA /system fault level in MVA

Where,

% VC = % voltage change or rise due to capacitor


% X = % Reactance of equipment e.g. Transformer

If the capacitor bank is STAR connected than the required value of C will be higher in comparison to the value of C
in DELTA connection for the same value of required kVAR. Higher value of C will cause higher voltage rise of the
system causing nuisance tripping of the equipment provided with over voltage protection.

It is common practice to leave the star-connected capacitor banks ungrounded (there are separate reason for
leaving it ungrounded) when used in the system or use delta-connected banks to prevent the ow of third harmonic
currents into the power system through the grounded neutral.

Large capacitor banks can be connected in STAR ungrounded, STAR grounded or delta. However, the wye
ungrounded connection is preferable from a protection standpoint. For the STAR ungrounded system of connecting
single capacitor units in parallel across phase-to-neutral voltage the fault current through any incomer fuse or
breaker of capacitor bank is limited by the capacitors in the two healthy phases. In addition the ground path for
harmonic currents is not present for the ungrounded bank.

For STAR grounded or delta-connected banks, however, the fault current can reach the full short circuit value from
the system because the sound phases cannot limit the current.

Top

Detuning of Capacitor Banks


In an industrial plant containing power factor correction capacitors, harmonics distortions can be magnied due to
the interaction between the capacitors and the service transformer. This is referred to as harmonic resonance or
parallel resonance. It is important to note that capacitors themselves are not main cause of harmonics, but only
aggravate potential harmonic problems. Often, harmonic-related problems do not show up until capacitors are
applied for power factor correction.

In de-tuned systems, reactors are installed in series with the capacitors and prevent resonance conditions by
shifting the capacitor/network resonance frequency below the rst dominant harmonic (usually the 5th).

Impedance of the capacitor decreases with increase in frequency. Capacitor capacity to cancel out harmonic
decreases with increase in frequency. This oer the low impedance path to harmonic currents. These harmonic
currents added to the fundamental current of capacitors can produce dangerous current overloads on capacitor.
Each of the harmonic currents causes the voltage drop across the capacitor. This voltage drop is added to the
fundamental voltage. Thus in presence of harmonics higher voltage rating of capacitor is recommended. This
overvoltage can be much above permissible 10% value when resonance is present.

Another important aspect is resonance which can occur when p.f. capacitors forms the series or parallel resonant
circuit with impedance of supply transformer. If the resonance frequency of this LC circuit coincides with one of the
harmonic present, the amplitude of the harmonic current owing through LC circuit is multiplied several times

3/5
damaging the capacitors, supply transformer and other network components.

Top

Precautions to be taken while switching ON a capacitor bank


Make sure that there is adequate load on the system. The normal current of the capacitor to be switched ON at 440
volts is say 100 amps. Therefore the minimum load current at which the capacitor should be switched ON is 130-
150 amps.

If one capacitor unit is already on and a second one is to be added then minimum load current on this bus system
must be equal to or more than the combined capacitor current of the two banks by at least a factor of 1.35 to 1.5.

After switching o the capacitor wait for at least one minute before switching it on. Earth all the live terminals only
after waiting for one minute before touching these with spanner etc. If above precautions are not observed, this
could lead to dangerous situations both for plant and personnel.

Switch o the capacitors when there is not enough load. This is a MUST. If the capacitors are kept ON when there is
no load or less load then Power factor goes to leading side and system voltage increases which may cause damage
to the capacitors as well as other electrical equipments and severe disturbance can be caused.)

If the line voltages are more than the capacitor rated voltage, then do not switch on the capacitors. As the load
builds up, the line voltage will fall. Switch on the capacitors then only.

Top

Operation of capacitor bank and co relatation with harmonics in the system

Harmonics can be reduced by limiting the non-linear load to 30% of the maximum transformers capacity. By doing
this we ensure that power system does not exceeds the 5% voltage distortion level of IEEE Standard 519. However,
with power factor correction capacitors installed, resonating conditions can occur that could potentially limit the
percentage of non-linear loads to 15% of the transformers capacity.

Use the following equation to determine if a resonant condition on the distribution could occur:

F R = kVASC / kVA RC

Where,

F R = resonant frequency as a multiple of the fundamental frequency


kVASC= short circuit current at the point of study
kVARC = capacitor rating at the system voltage

If F R equals or is closed to a characteristic harmonic, such as the 5th or 7th, there is a possibility that a resonant
condition could occur. Almost all harmonic distortion problems occur when the parallel resonance frequency is close
to the fth or seventh harmonic, since these are the most powerful harmonic current components. The eleventh and
thirteenth harmonics may also be worth evaluating.

Top

True and displacement power factor specially with regards to variable speed drives?

Power factor of variable speed drives With the six-step and current source inverters, the power factor will be
4/5
determined by the type of front end used. When SCRs are used, the power factor will be relatively poor at reduced
speeds. When diodes with a dc chopper are used, the power factor will be the same as a PWM inverter, which is
relatively high (near to unity) at all, speeds.

True power factor is the ratio of real power used in kilo watts (kW) divided by the total kilo volt-amperes.
Displacement power factor is a measure of the phase displacement between the voltage and current at the
fundamental frequency. True power factor includes the eects of harmonics in the voltage and current. Displacement
power factor can be corrected with capacitor banks. Variable speed drives have dierent displacement power factor
characteristics, depending on the type of rectier.

PWM type variable speed drives use a diode bridge rectier and, have displacement power factors very close to
unity. However, the input current harmonic distortion can be very high for these variable speed drives, resulting in a
low true power factor. True power factor is approximately 60% despite the fact that the displacement power factor is
very close to unity. The true power factor can be improved substantially in this case through the application of input
chokes or transformers which reduce current distortion.

Capacitor banks provide no power factor improvement for this type of variable speed drives and can make the
power factor worse by magnifying the harmonic levels.

5/5

Vous aimerez peut-être aussi