uge coordination involves two distinct applications:
ety and source-side fuse, and relay and loac-side fuse.
reieyan cases the relay fo serving as a circuit breaker
Bire-and-trip contro, But the coordination objectives of
fotwo applications are entirely diferont.
'fne oblective of relay and source-side fuse coordina
tion & that the felaved breaker should go through its
‘nla operating sequence without causing fuse melting
‘Sedamage. s0 that the smallest segment ofthe circuit will
‘Se sectionalized. The objacive of relay and load-side fuse
‘eorcination, on the other hand, is generally accepted to
fearelay curve that slower than the fuse curve, s0 that
fusing operation and isolation ofthe fault take place before
hebroaker completes its sequence. In the attercase, the
Sidiion of instantaneous relay elements that function
{ister than the load-side fuse on the first broker opera-
tion provides a measure of transient fault protection.
“These two applications are discussed in detail below.
{ELAY AND SOURCE-SIDE FUSE
COORDINATION
‘Tho principal application would be a primary fuse protect-
inga substation transformer witha reiayed breaker serv
{ng 2s the socondary protection. Coordination can be
tndertakon by either of two methods: total accumulated
time or cooling factors. For comparison a lay and use
fime-current characteristics to be made, both curves must
‘be expressed on the same voltage base by sifting one of
the curves, as discussed In the preceding section on
tecloser and Tuse-link coordination, beginning with the
fourth paragraph ander “Coordination with Sourse-Side
Fuse Links
‘Total Accumulated Time Method
‘Tho simplest and most conservative method of achieving
coordination is to add up the relay fault timings that are
separated by less than ten seconds, the time typically
fequired for fuses to cool completely, and compare this,
foialto the fuse curve. A time margin of 80 percent ofthe
souroe-side fuse's minimum-mell curve is recommended.
'o allow for preloading, ambient, predamage, 2né non-
repeatability of relay characteristics. Some vtities Use
8 seconds asa margin rather than a percentage.
‘AS a basis for discussion, an installation involving a
relayed breaker and source-side fuse is diagrammed in
Figure 20A3 ‘The transformer and breakor ratings are
indicated. The fuse is a 125E power fuse. The overcurrent
relay isa type IACS3, with a CT rato of 10005. It can be.
al at tap 2 0° 4, and has an instantaneous tap setting of
10.Thereclosing relay has areciosing sequence of instan-
faneous, 15 seconss, and 45 seconds For more details
fogarding relay settings, roler to ‘Creuil Broakers and
Relays’ in Section A2
In Figure 213, the fuse and breaker relay curves are
‘compared. The fuse minimum-melt curve hes been re
ferred to the secondary by the vollage ratio 69/1247,
because the tanstormer connection is symmetrical.
\wye-grounded/ wye-arounded. For proper coordination
‘Up ta'S KA. itappears hat both relay time-lever settings
Relay-Fuse Coordination
on t240/72v04rs
3
gure 2082
Diagram of installation with relayed breaker and source
Sido fuse.
(2 and 4) will coordinate for only one fault timing. But
Since the reclosing relay has an insiantaneous (INST)
Setting, the frst two fault timings of the relay must be
added together and plotted for true comparison with the
fuse curve. With tha in mind, tis obvious lever 4 will not
‘coordinate, sino its curve crosses the fuse curve at the.
55000-ampere level. Although the fuse will not necessarily
{unction on the fist operation ofthe breaker iteould see
tenough eurrent for heat damage to oocur
Lotus take a closer look, then, a the total accumulatod
time for lever 2, with its instantaneous time as Indicated
(Figure 2282). (The total accumulated curve consists of
th fist two fault timings ofthe relay; the instananeous
element was operative on the lirst shot only) As can be
seen, comparing the adjusted lever 2relay curve withthe
fuse curve shows margin greater than 50 percent for any
tault evel upto 8c00.amps. Therefore, the coordination is
acceptable with lever 2 and the settings shown,
Cooling-Factor Method
When coordination requirements are tighter, there is
another method that will result in more precise coordina:
tion, Ths involves the use of cooling fators for the fuse
link (explained in Table 2943) and an evaluation of the
Actual reclosing intervals ofthe relay The formula used is
Tett= TRIN) + GN x TF(NGI) + CNet x CN x
TRIN-2) +
Where Telt= theettective fault timing ofthe relay in-
‘corporating succaseive reclosing heating
offecs.
CN= the cooling factor forthe fuse during the
tenth closing (open) interval. This varies
{rom 1.0 at very short reclosing times 10
(0 atlong reclosina times.
‘TF(N) = Nth ‘ult duration of the reclosing device
Use ofthe above formula also requires a knowledge of
the reset characterstics of the reset relay. The relay’s,
ragot time is 10 seconds (at0 percent remaining losd) for
timo-lover 2, and the fuse scooting factors are as shown in
‘Table 2343. (Note that fuse-ink cooling factors may not
be generally availabe from manufacturers )
117
Distribution Impact Study Robinsons Land Corporation 500 KW On-Grid Three Phase Photovoltaic Power Plant Located in Robinsons Cybergate Bacolod, Araneta St. Brgy. Singcang, Bacolod City