Vous êtes sur la page 1sur 1

DESCRIPTION

F G H I
(E)TRANSFER 200 CFM
600 CFM (E)24x24 RAG
AIR BOOT (E) CD
(E) CD (TYPICAL)
(TYP-2) (TYP-4)

BY
OFFICE OFFICE OFFICE
801 802 804

DATE
8" 10" 10" 8" 10"
12"
OFFICE
(E)
(E)
8" (E) 808
VAV 8" VAV
VAV
1 OFFICE OFFICE 3 420 CFM
2
805 806 (E) CD
8" 8" 8"
12" (E)12" BOD=10'-7" 8"

(E)14" 10"

AIR CONDITIONING
CONTRACTORS

CARSON, CALIFORNIA 90745-2598

CLAY DUNN ENTERPRISES INC.


BOD=10'-8"
12"

TELEPHONE {310} 549-1698

1606 E. CARSON STREET


FAX {310} 549-8329

A DIVISION OF
LIC. #420650
(E)20" (E)18" (E)16"
(E)
UP
S 3
(E)
S (E)
(E) TRANSFER 1 S (E)14"
BOOT 12" 2
BOD=9'-4" 250 CFM
DN
(E) CD

3 (E)
190 CFM
(E)10"
BOD=9'-8"
VAV
8 (E) CD
8"
300 CFM OPEN AREA
10"
(E) CD 807

10"

AIR-TEC
360 CFM
BREAK / (E) CD
OFFICE
RECEPTION COPY ROOM
809
8" 803
800
(E)14" BOD=9'-4"
(E)
S 8
10"

(E)CSFD

240 CFM
(E)CD 8"
W/ CSFD (N)24x24 RAG

OFFICE
12" 810

(E)
S 4 (N)

(E)10" BOD=10'-8"
(E) 100 CFM 200 CFM
VAV (E) CD 10" (E) CD
7 (TYP-2)

201 SOUTH LAKE AVENUE


(E)

PASADENA, CALIFORNIA
VAV
4
6"

(E)
SERVER OFFICE
8"

2
8" S
7 813
(R)
811
AIR TERMINAL UNIT SCHEDULE

FARIENT
SUITE 804
S MANUFACTURER AND INLET SIZE CFM
5
MARK REMARKS
UP MODEL NO. COLD HOT MAX MIN
10"
(E)12x24 RAG
VAV-1 TITUS / DEDV 12" 8" 600 180 EXISTING / REBALANCE
10"
180 CFM VAV-2 TITUS / DEDV 12" 8" 800 240 EXISTING / REBALANCE
8"
(E) CD
(N)MANUAL VAV-3 TITUS / DEDV 8" 8" 420 125 EXISTING / REBALANCE
(E) S S (E) DN VOLUME
(E)20" (E)18" VAV-4 TITUS / DEDV 10" 8" 650 195 EXISTING / REBALANCE
DAMPER
(TYPICAL) VAV-5 TITUS / DEDV 10" 8" 720 215 EXISTING / REBALANCE
(E)16" VAV-6 TITUS / DEDV 10" 8" 670 200 EXISTING / REBALANCE
10" VAV-7 TITUS / DEDV 8" -- 280 -- EXISTING / REBALANCE
(E)14"
VAV-8 TITUS / DEDV 12" -- 850 -- EXISTING / REBALANCE
(R)
10"
S
6
8" 8"
(N)
360 CFM
(N)10" CD KEY PLAN N.T.S.
BUILDING'S EXISTING (E) (E) 10" (TYP-2)
MAIN SUPPLY TRUNKLINES VAV VAV
6 5

10" (R)24x24 RAG


(N) (TYP-2)
10" 12" 10"
OPEN AREA A B C D E F G H I

812 4

1 3
PROJECT CHIEF
RM
DRAWN BY
RM
(E) RA 335 CFM BOTTOM OF ROUND DUCTWORK SHALL BE CHECKED BY
OPENING (E) CD 9'-6" TYPICAL UNLESS OTHERWISE NOTED RM
(TYP-2) (TYP-2) OR WHERE CROSSOVERS MAY OCCUR 2
DATE
01-18-17
SCALE
1 1/4"=1'-0"

PARTIAL AIR CONDITIONING 8TH FLOOR PLAN JOB NO.


7020
SHEET

SCOPE OF WORK
M-3
OF -3- SHEETS

Vous aimerez peut-être aussi