TYPICAL WIRING DIAGRAM DEEP SEA ELECTRONICS 053-182

A larger diagram is available in the operators manual.


8610M KII INST ALL ATION INSTRUCTIONS ISSUE 1

ACCESSING THE FRONT PANEL CONFIGURATION EDITOR.


Ensure the engine is at rest and the module is in STOP mode by pressing the (Stop/Reset)
button.

Press the (Stop/Reset) and (Info) buttons simultaneously.


If a module security PIN has been set, the PIN number request is then
shown :
Press the (Tick) button the first digit will flash to enable the pin to be
entered.

Press (up) or (down) to adjust it to the correct value

Press (right) when the first digit is correctly entered. The digit you have just entered will now
show # for security.

Repeat this process for the other digits of the PIN number. You can press (left) if you need
to move back to adjust one of the previous digits.
When (Tick) is pressed after editing the final PIN digit, the PIN is checked for validity. If the
number is not correct, you must re-enter the PIN.

If the PIN has been successfully entered (or the module PIN has not been
enabled), the editor is displayed :

EDITING A PARAMETER

Enter the editor as described above.

Press the (Right) or (Left) to cycle to the section you wish to view/change. Then

press (Up) or (Down) to cycle to the parameter within the section you have chosen.

DIMENSIONS AND MOUNTING To edit the parameter, press (Tick) to enter edit mode. The parameter begins to flash to indicate
For flat surface mounting in a Type 1 enclosure to meet UL requirements that you are editing the value.
Press the up or down buttons to change the parameter to the required value.
DIMENSIONS PANEL CUTOUT:
240.0mm x 181.1mm x 41.7mm (9.4 x 7.1 x 1.6) 220mm x 160mm (8.7 x 6.3) Press (Tick) to save the value. The parameter ceases flashing to indicate that it has been saved.

To exit the editor at any time, press and hold the (Stop/ Reset) or (Tick) button.
Deep Sea Electronics Plc. Deep Sea Electronics inc.
Tel:+44 (0)1723 890099 Phone: +1 (815) 316-8706
Fax: +44 (0)1723 893303 Fax: +1 (815) 316- 8708 NOTE: When the editor is visible, it is exited after 5 minutes of inactivity to ensure security.
Email: support@deepseaplc.com TOLL FREE (USA only) : Tel: 1 866 636 9703
Web: www.deepseaplc.com Email: dsesales@deepseausa.com NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security.
Web: www.deepseausa.com
NOTE: Comprehensive module configuration is possible using the DSE Configuration Suite PC Software, refer to DSE publication
057-239 DSE8610 MKII & DSE8610 MKII Configuraiton Suite PC Software Manual.
ADJUSTABLE PARAMETERS Front Panel Configuration Editor (continued)

Front Panel Configuration Editor (Factory default settings are shown in bold italicised text) Section Parameter as shown on display Values
Timers LCD Page Timer 0h 0m 0s
Section Parameter as shown on display Values Scroll Delay 0h 0m 0s
Display Contrast 0% Engine Pre Heat Timer 0h 0m 0s
Language English, Other. Engine Crank Duration 0h 0m 0s
Current Date and Time hh:mm Engine Crank Rest Time 0h 0m 0s
Engine Oil Pressure Low Shutdown 0.00 bar Engine Safety On Delay 0h 0m 0s
Oil Pressure Low Pre Alarm 0.00 bar Engine Smoke Limiting 0h 0m 0s
Coolant Temp high Pre Alarm 0 C Engine Smoke Limiting Off 0h 0m 0s
Coolant Temp High Shutdown 0 C Engine Warm Up Time 0h 0m 0s
Start Delay Off Load 0h 0m 0s Engine Cool Down Time 0h 0m 0s
Start Delay Telemetry 0h 0m 0s Engine Speed Overshoot Delay 0h 0m 0s
Engine Pre Heat Timer 0h 0m 0s Engine Failed To Stop Delay 0h 0m 0s
Engine Crank Duration 0h 0m 0s Battery Under Voltage Warning Delay 0h 0m 0s
Engine Crank Rest Time 0h 0m 0s Battery Over Voltage Warning Delay 0h 0m 0s
Engine Safety On Delay 0h 0m 0s Return Delay 0h 0m 0s
Engine Smoke Limiting 0h 0m 0s Generator Transient Delay 0h 0m 0s
Engine Smoke Limiting Off 0h 0m 0s Scheduler Scheduler Active / Inactive
Engine Warm Up Time 0h 0m 0s Schedule On Load Active / Inactive
Engine Cool Down Time 0h 0m 0s Schedule Period Weekly, Monthly
Engine Speed Overshoot Delay 0h 0m 0s
Engine Speed Overshoot 0h 0m 0s Schedule Time & Date Selection (1-16) Press to begin editing then or when selecting the
Engine Failed To Stop Delay 0h 0m 0s different parameters in the scheduler.
Battery Under Voltage Warning Active / Inactive
Battery Under Voltage Warning Delay 0h 0m 0s
Battery Under Voltage Warning 0V ACCESSING THE RUNNING CONFIGURATION EDITOR
Battery Over Voltage Warning Active / Inactive
Battery Over Voltage Warning Delay 0h 0m 0s The running editor can be entered while the engine is running. All protections remain active if the
Battery Over Voltage Warning 0V engine is running while the running editor is entered.
Charge Alternator Failure Warning Active / Inactive
Charge Alternator Failure Warning 0V
Charge Alternator Warning Delay 0h 0m 0s
Press and hold the (Tick) button to enter the running editor.
Charge Alternator Failure Shutdown Active / Inactive
Generator Under Voltage Shutdown 0V ADJUSTABLE PARAMETERS (Running editor)
Under Voltage Pre-Alarm 0V
Loading Voltage 0V Enter the editor as described above.
Nominal Voltage 0V
Over Voltage Pre-Alarm 0V
Over Voltage Shutdown 0V
Under Frequency Shutdown 0 Hz
Under Frequency Pre-Alarm 0 Hz Press the (Up) or (Down) buttons to cycle to the section you wish to view/change.
Loading Frequency 0 Hz
Nominal frequency 0 Hz
Over Frequency Pre-Alarm 0 Hz
Over Frequency Shutdown 0 Hz To Edit the parameter press the (Tick) button to enter edit mode. The parameter begins to flash to
Full Load Rating 00 A indicate that you are editing the value.
kW Overload Trip 0%
Delayed Over current Active / Inactive
Gen Over Current Trip 0%
AC System 3 Phase 4 Wire
CT Primary 0A Power Cycle After Exit Press the (Up)or (Down) buttons to change the parameter to the required value.
CT Secondary 0A Power Cycle After Exit
Short Circuit Trip 0%
Earth CT Primary
Earth Fault Trip
0A
Active / Inactive
Press the (Tick) button to save the value. The parameter ceases flashing to indicate that it has
Earth Fault Trip 0% been saved.
Transient Delay 0h 0m 0s
Gen Reverse Power Delay 0h 0m 0s To exit the editor at any time , press and hold the (Tick) button.
Full kW Rating 0 kW
Full kVAr Rating 0 kvar
Load Ramp Rate 0%
Running Editor
Load Level For More Sets 0%
Load Level For Less Sets 0% Section Parameter as shown on display Values
Load Demand Priority 1 Display Contrast 0%
Gen Reverse Power 0 kW Language English, Other
Insufficient Capacity Delay 0h 0m 0s Load Demand Priority 1
Insufficient Capacity Action None / Indication / Warning / Shutdown / Electrical Trip Load Power Factor 0%
Reactive Load CTL Mode None / VAr Share Load Parallel Power 0%
Load Parallel Power 0 kW When In Mains Parallel Mode ) Commissioning Screens Active / Inactive
Load Power Factor 0% When In Mains Parallel Mode Override Starting Alarms Active / Inactive
Enable MSC Compatibility Active / Inactive Voltage Adjust (manual mode only engine running breaker open) 0%
Continued Overleaf Frequency Adjust (manual mode only engine running breaker open) 0%