Vous êtes sur la page 1sur 4

LOAD ESTIMATION

SQ. M LIGHTING LOAD ESTIMATE: 195824.16 VA


GROUND: 403.02
2ND FLOOR: 696.15
3RD-12TH: 6997.5
ROOFDECK: 62.67
TOTAL AREA: 8159.34
NOTE: TOTAL AREA x 16VA
FOR 3RD-12TH FLOOR TYPICAL UNITS: FOR GRD FLR. - 2ND FLR. COMMERCIAL UNITS:
FOR STUDIO UNITS W/ 19.91 SQ. M: FOR COMMERCIAL UNITS W/ 85.04 SQ. M:
VA D.F # of units VA VA D.F # of units VA
GEN. LIGHTING LOAD: 318.56 12 3822.72 GEN. LIGHTING LOAD: 2040.96 8 16327.68
SMALL APPL. LOAD: 1500 12 18000 SMALL APPL. LOAD: 935.44 8 7483.52
1 - Water Heater 3300 12 39600 EQUIPMENT
1 - 1HP ACU: 1840 12 22080 A. FRIDGE 2000 8 16000
TOTAL: 83502.72 B. CHILLER 2000 8 16000
FOR STUDIO UNITS W/ 22.13 SQ. M: C. VENDING MACHINE 500 8 4000
VA D.F # of units VA D.COFFEE MACHINE 400 8 3200
GEN. LIGHTING LOAD: 354.08 2 708.16 AIRCON
SMALL APPL. LOAD: 1500 2 3000 A.FAN COIL UNIT 2000 8 16000
1 - Water Heater 3300 2 6600 B. CONDENSING UNIT 4000 8 32000
1 - 1HP ACU: 1840 2 3680 SIGNAGE 1200 8 9600
TOTAL: 13988.16 TOTAL: 120611.2
FOR STUDIO UNITS W/ 24.94 SQ. M:
VA D.F # of units VA FOR COMMERCIAL UNITS W/ 97.8 SQ. M:
GEN. LIGHTING LOAD: 399.04 2 798.08 VA D.F # of units VA
SMALL APPL. LOAD: 1500 2 3000 GEN. LIGHTING LOAD: 2347.2 8 18777.6
1 - Water Heater 3300 2 6600 SMALL APPL. LOAD: 1175.8 8 9406.4
1 - 1HP ACU: 1840 2 3680 EQUIPMENT
TOTAL: 14078.08 A. FRIDGE 2000 8 16000
FOR TWO-BEDROOM UNITS W/ 42.23 SQ. M: B. CHILLER 2000 8 16000
VA D.F # of units VA C. VENDING MACHINE 500 8 4000
GEN. LIGHTING LOAD: 675.68 2 1351.36 D.COFFEE MACHINE 400 8 3200
SMALL APPL. LOAD: 1500 2 3000 AIRCON
1 - Water Heater 3300 2 6600 A.FAN COIL UNIT 2000 8 16000
1 - 1HP ACU: 1840 2 3680 B. CONDENSING UNIT 4000 8 32000
TOTAL: 14631.36 SIGNAGE 1200 8 9600
TOTAL: 124984
FOR 3RD-12TH FLOOR TYPICAL UNITS: OTHER LOAD REQUIREMENTS
CONNECTED LOAD MOTORS
TOTAL: 126200 VA per FLOOR VA D.F # of units VA
DEMAND LOAD 10 HP ELEVATOR MOTOR 7200 2 14400
TOTAL: 119214 VA per FLOOR 3 HP BOOSTER PUMP 2440 4 9760
DEMAND FACTOR: 94 PERCENT per FLOOR 7.5 HP TRANSFER PUMP 5600 2 11200
1.5 HP JOCKEY PUMP 1320 2 2640
FOR GRD FLR. - 2ND FLR. COMMERCIAL UNITS: 25 HP FIRE PUMP 17600 2 35200
CONNECTED LOAD TOTAL: 73200
TOTAL: 245595 VA
DEMAND LOAD
TOTAL: 245595 VA
DEMAND FACTOR: 100 PERCENT per FLOOR

TOTAL LOAD ESTIMATE OF THE BUILDING: 1853634.2 VA


GROUND FLOOR
LOBBY, STAIRS & ELEVATOR LOBBY W/ 101.62 SQ. M:
VA D.F VA
GEN. LIGHTING LOAD: 1016.2 1016.2
GEN. POWER. LOAD: 203.24 203.24
AIRCON
A. FANCOIL UNIT 2000 4000
B. CONDENSING UNIT 4000 16000
TOTAL: 21219.44
2ND FLOOR
LOBBY, STAIRS & ELEVATOR LOBBY W/ 116.28 SQ.M:
VA D.F VA
GEN. LIGHTING LOAD: 1162.8 1162.8
GEN. POWER. LOAD: 232.56 232.56
AIRCON
A. FANCOIL UNIT 2000 4000
B. CONDENSING UNIT 4000 16000
TOTAL: 21395.36
3RD FLOOR - 12TH FLOOR
LOBBY, STAIRS, HALLWAY & ELEVATOR LOBBY W/ 167.37 SQ.M:

VA D.F VA
GEN. LIGHTING LOAD: 1673.7 1673.7
GEN. POWER. LOAD: 334.74 334.74
AIRCON
A. FANCOIL UNIT 2000 8000
B. CONDENSING UNIT 4000 20000
TOTAL: 30008.44

CONNECTED LOAD
TOTAL: 342699.2 VA per FLOOR
DEMAND LOAD
TOTAL: 342699.2 VA per FLOOR
DEMAND FACTOR: 100 PERCENT per FLOOR

Vous aimerez peut-être aussi