Académique Documents
Professionnel Documents
Culture Documents
Best practice for using surge protective devices (SPDs) and RCD together (photo
credit: CITELSurgeProtectors via Youtube)
IMPORTANT NOTES // S type RCDs satisfy this requirement. In the case of surge
currents higher than 3 kA 8/20, the RCD may trip causing interruption of the power
supply.
If the SPD is installed downstream of the RCD, the RCD should be of the time
delayed type with an immunity to surge currents of at least 3kA 8/20. Section
534.2.2 of BS 7671 details the minimum SPD connection requirements (based on
the SPD modes of protection) at the origin of the installation (typically a Type 1
SPD).
In case you are not familiar with surge protective devices operation and types, you
Therefore in order to meet the requirements for safe disconnection times, RCDs
Should the SPD become defective it would therefore create a short circuit
current rather than an earth fault current and as such would ensure that the
overcurrent protective devices (OCPDs) in-line with the SPD safely operates within
the required disconnection time.
A higher energy SPD is used between neutral and the protective conductor .
This higher energy SPD (typically a spark-gap for a Type 1 SPD) is required as
lightning currents arise towards the protective conductor and as such this higher
energy SPD sees up to 4 times the surge current of the SPDs connected between
the live conductors.
Clause 534.2.3.4.3 therefore advises that the SPD between neutral and the
protective conductor is rated at 4 times the magnitude of the SPD between the live
conductors.
If BS 7671 would allow the application of SPDs to the TN-C side (utility side) of the
TN-C-S system (observed in some parts of Europe), then it may be possible to
install SPDs within 0.5m of the PEN split to N and PE and omit the N to PE SPD
protection mode.
However as SPDs can only be applied the TN-S side (consumer side) of the TN-
C-S system, and given SPDs are typically installed at the main distribution board,
the distance between the SPD installation point and the PEN split will almost
always be greater than 0.5 m, so there is a need to have an SPD between N and
PE as required for a TN-S system.
As Type 1 SPDs are specifically installed to prevent the risk of loss of human life (to
BS EN62305) through dangerous sparking which could present a fire hazard for
example, in the interests of safety alone, the engineering judgement is that an SPD
should be fitted between N and PE for a TN-C-S system as it would in a TN-S
system.
In summary, as far as Section 534 is concerned, TN-C-S systems are treated the
This is the most commonly used and most practical type of overvoltage
protection.
Type 1 SPD
Protection against transient overvoltages due to direct lightning strokes . The
Type 1 SPD is recommended to protect electrical installations against partial
lightning currents caused by direct lightning strokes. It can discharge the voltage
from lightning spreading from the earth conductor to the network conductors.
Type 3 SPD
Type 3 SPD is used for local protection for sensitive loads . These SPDs have a
low discharge capacity. They must therefore only be installed as a supplement to
Type 2 SPD and in the vicinity of sensitive loads. They are widely available as hard
wired devices (frequently combined with Type 2 SPDs for use in fixed installations).