Vous êtes sur la page 1sur 6

Study of FACTS Device Applications

for the 500kV Vietnams Power System


Quyen LE-CAO, Tuan TRAN-QUOC, Senior Member, IEEE, Anh NGUYEN-HONG

Abstract This paper presents a study of FACTS devices The Vietnam power system is separated into three regions:
applications, in particularly choice of adequate shunt the Northern, the Southern and the Central regions. In 2015,
compensators (type of FACTS devices, location) in order to outside of existing lines, several new circuits of 500 kV
improve voltage and transient angle stability. The study is transmission lines will be constructed. In this period, the peak
carried out for the 500kV Southern Vietnam power system in load demands in Vietnam will be about 37500 MW. The risk
2015 with a high load scenario. The load flow calculation, P-V of voltage instability and transient angle stability is evident
curve analysis and transient stability study are examined by
due to the sizable length of the Southern-Northern
transmission lines (about 1500 km), the resulting considerable
using the PSS/E-30 software. The obtained results show that with
amount of power transmitted through these lines, the fast
the application of FACTS devices, voltage stability and transient
increase of load demands and the specific configuration of the
angle stability of this power system are considerably improved. Vietnam power system (500 kV system).
Keywords Voltage stability, Transient stability, reactive In order to improve voltage collapse on the Vietnam power
power allocation, FACTS, PSS/E system, FACTS device applications are studied by using
several indices for voltage collapse such as P-V curve analysis
I. INTRODUCTION and dynamic voltage stability analysis. In order to demonstrate

P ower system plays an important role as the major


infrastructure in any country. However, with the increases
in economic and environment pressure, the power system now
the advantages of FACTS applications to improve transient
angle stability in this power system, the time domain
simulation with the help of the PSS/E program is carried out.
become large-scales, more complex and operating closer to After the study, an adequate location and type of FACTS
their stability limit. Some power system blackouts that devices are determined.
occurred throughout the world in recent years are
consequence of that situation. Generally, network blackouts II. VOLTAGE STABILITY ANALYSIS
related to voltage collapse caused by lack of reactive power In [2], voltage instability is mainly associated with the lack
support in heavy conditions, or by faults. of reactive power. The loadability of a bus in the power
Flexible Alternative Current Transmission System system depends on the reactive power support that the bus can
(FACTS) controllers have been proposed to enhance the receive from the system. When the system approaches the
transient or dynamic stability of power systems. The recent
maximum loading point or voltage collapse point, both real
development and use of FACTS controllers in power
and reactive power losses increase rapidly. Therefore, the
transmission system have led to many applications not only to
improve the voltage and transient angle stability of the reactive power supports are necessary to avoid voltage
existing power networks but also to provide operation collapse.
flexibility of power systems as presented by J. Paserba in [12, There are two types of voltage stability studies: static and
13]. Especially, due to the fast response to provide reactive dynamic analysis. Static analysis involves only the solution of
powers, the shunt dynamic VAR compensators such as Static algebraic equations and therefore it is computationally less
VAR Compensators (SVC) and Static Synchronous extensive than dynamic analysis. Static voltage stability is
Compensators (STATCOM) have become feasible alternatives used to determine voltage stability limit for many
of reactive compensation, and therefore they have received contingencies.
intensive interests. Reactive power planning analysis or Var Voltage collapse makes the system voltage decay to a level
planning category is considered to find optimal allocation to from which they are unable to recover. This phenomenon can
cover normal as well as contingency conditions. It is be seen by the plot of the transferred power versus the voltage
necessary to use dynamic analysis in time domain simulations at receiving end. The plots are popularly referred to as P-V
to determine the type of Var source such as dynamic Var curve or Nose curve. In normal condition, when the power
source or static transfer increases, the voltage at the receiving end decreases.
Var source and the response of these devices in fault Eventually, for an operation state near to the critical (nose)
conditions [1]. point, the increase in active power transfer will lead to very
rapid decrease in voltage magnitude. Before reaching the
LE CAO Quyen is with the Power Engineering Consulting Company 4
critical point, the large voltage drop due to heavy reactive
(PECC4), Electricity of Vietnam (EVN), (email: lecaoquyen@gmail.com)
TRAN-QUOC Tuan is with IDEA, G2ELab, BP 46, 38402 Saint Martin power losses can be observed. One way to save the system
dHres, France (e-mail: Tuan.Tran-Quoc@g2elab.grenoble-inp.fr) from voltage collapse is to reduce the reactive power load or
NGUYEN HONG Anh is with Quinhon University, Vietnam add additional reactive power.

978-1-4244-6547-7/10/$26.00 2010 IEEE 1


Usually, an effective solution to increase voltage stability specific parameters of the electrical power system (typically
margins is to place adequate reactive power support at the bus voltage).
weakest bus. The weakest bus is defined as the bus, which Figs. 2 and 3 show schematic diagram and V-I characteristic
is nearest to experiencing a voltage collapse. of a static var compensator. The compensator normally
The most effective way for utilities to improve voltage includes a thyristor controlled reactor (TR), thyristor-switched
stability of the system is to introduce the sources of reactive capacitors (TSCs) and harmonic filters. It might also include
power, such as shunt capacitors and/or FACTS controllers at mechanically switched shunt capacitors (MSCs), and then the
the appropriate location. term static var system is used. The harmonic filters (for the
Many analytical methodologies have been proposed for TCR-produced harmonics) are capacitive at fundamental
frequency. The TCR is typically larger than the TSC blocks so
studying this problem such as P-V and V-Q curve analysis,
that continuous control is realized. Other possibilities are
Continuation Power Flow (CPF), optimization methods
fixed capacitors (FCs), and thyristor switched reactors (TSRs).
(OPF), modal analysis, saddle node bifurcation analysis (for
Usually a dedicated transformer is used, with the compensator
static analysis) and Hopf bifurcation analysis, time-domain equipment at medium voltage. The transmission side voltage
simulation (for dynamic analysis) [4]-[8]. is controlled, and the Mvar ratings are referred to the
In this part of the paper, an algorithm for choosing transmission side.
adequate placement and the type of FACTS devices is
proposed. This approach is based on the Continuation Power
Flow (CPF). A dynamic simulation is carried out in order to
validate the choice of type of FACTS device. The algorithm is
described as below (Fig. 1):

STAR

Base case

Solve load flow Fig. 2. Schematic diagram of an SVC

Predictor step in CPF method UT

1.0
Corrector step in CPF method
0.9
0.8

NO 0.7
Complete PV
curve 0.6

YES 0.5
0.4
Optimal placement of FACTS device
0.3
0.2

Comparison between STATCOM and SVC by using


a time domain simulation program
IC I Cm ax I Lm ax IL
Capacity Inductive

Optimal type of Var source


Fig. 3. V-I characteristic of the SVC

EN STATCOM: A static synchronous generator operated as a


Fig. 1. Algorithm for choosing placement and type of FACTS devices shunt-connected static var compensator whose capacitive or
inductive output current can be controlled independently from
the AC system voltage. STATCOM is as if a controlled
III. FACTS DEVICE MODELLING reactive-power source. It provides voltage support by
generating or absorbing reactive power at the point of
This section explains briefly the modelling of SVC and common coupling without the need of large external reactors
STATCOM [10, 11]: or capacitor banks. The basic voltage-source converter scheme
Static Var Compensator (SVC): A shunt-connected static var and V-I characteristic of the STATCOM are shown in Figs. 4
generator or absorber whose output is adjusted to exchange and 5.
capacitive or inductive current so as to maintain or control

2
The ability of the STATCOM to maintain full capacitive
output current at low system voltage also makes it more
effective than the SVC in improving the transient stability.

UT

1.0
0.9
0.8
0.7
Fig. 4. Schematic diagram of a basic STATCOM
0.6

In the linear operating range the V-I characteristics (Figs. 3, 0.5

5) and functional compensation capability of the STATCOM 0.4

and the SVC are similar. Concerning the non-linear operating 0.3

range, the STATCOM is able to control its output current over 0.2

the rated maximum capacitive or inductive range 0.1


independently of AC system voltage, whereas the maximum IC I Cm ax I Lm ax IL
attainable compensating current of the SVC decreases linearly Capacity Inductive
with AC voltage. Theoretically, the STATCOM is more
Fig. 5. V-I characteristic of the STATCOM
effective than the SVC in providing voltage support under
large system disturbances during which the voltage excursions
would be well outside of the linear operating range of the
compensator.
To Da Nang 228.3kV Dai Ninh 2x(600+j98.5
PLeiku Bac Binh Vinh Tan
282+j113

364+j158 SeSan 3, 3A, 4


Doc Soi 880+j352

514.1kV 522.2kV
223.4kV 235.1kV
-171.6-j52.6
330+j99
225.3kV
114.9+j200.1 519.8kV
Di Linh
-458.5+j101.2

2079+j361
-886.5-j40 -473.5-j115.5 438.2+j305.1 511.0kV 747.6-j6.8
719+j171

516.0kV
Thanh My
416.8+j20.2 493.5kV 486.5kV
Son My
215.4kV 1245+j834.8 516.5kV
227.1kV 523.6kV 669.7+j241.2 2x(600+j149.1
1120+j375

Xekaman 3 Tan Dinh


64.6-j7.4

DakMi 1,4 4x(180+j64.0

163.6+j350.4
1241+j855 494.7kV

-31+j29.2
216.2kV
Song Buong 2,4
855+j592

Yaly Th.Duc Bac


Song May

498.9-j10
DakNong
509.3kV 27.3+j278.5 226.1kV
230.3kV 229.1kV
493.0kV
556.2+j232.4 Cau Bong 227.5kV
861+j730

1141+j520 3x(100+j100.0
641+j142.1
614.4+j32 Nha Be 6x(100+j153.8
212.7kV
Dong Nai 3,4,5 490.8kV
497.3kV 821.8+j839.8 508.7kV
Dak Tik 421.7+j86
1193+j793

384.1+j326.7
407.4+j44

My Phuoc
217.9kV Phu My
227.7kV
Duc Hoa 1213.1+j536.8
428.2+j117.8 Tra Vinh
124+j10.5
634.2+j274.6 1123.8+j171.4
992.4+j318
212.1kV 493.8kV
832.7+j440 502.5kV 516.8kV 230.8kV
1425+j1031

497.0kV Phu Lam My Tho 3x( 400+j412.3


1000+j244.8
651+j349
218.1kV
2424.8+j515.4

1476.6+j91.2 523.3kV 2x(600+j45.6


225.8kV
517.9kV
277+j116

Soc Trang
190+j36

Kien Luong 512.8kV 645.4+j209.4 O Mon


1252.8+j478.6 228.3kV
2x(600+j129.8 1199.8+j183.6 369+j602

229.9kV 234.0kV
523.9kV
Thot Not 1605.6+j746

Placement of SVC or STATCOM


Fig. 6. Load flow analysis for the 500 kV Southern Vietnam power system in 2015.

3
IV. IMPROVING VOLTAGE STABILITY In order to verify this choice, P-V curves are calculated with
Configurations of the 500 kV Vietnam power system in four shunt reactive power compensation devices placed at
2015 are used to analysis. This system consists of 114 buses 220kV buses of Cau Bong, Duc Hoa, Tan Dinh and Phu Lam.
(29 load busses and 85 generation buses), 82 500kV The SM for this application is increased to 1850MW (Fig. 8).
transmission lines and 71 500/220 kV transformers.
The purpose of this part is to find optimal placements of V. TRANSIENT STABILITY ASSESSMENT
shunt compensator for the 500kV Southern Vietnam power Transient stability assessment of the system with shunt
system with the high load scenario. compensation devices including SVC and STATCOM is
The result of load flow analysis of the 500kV Southern studied and compared in the Southern power system.
Vietnam power system is given in Fig. 6 with the peak load Program Power System Simulation Engineering (PSS/E) [9]
demands.
is employed for transient stability analysis with block diagram
The active and reactive load at all load buses in this power
of SVC (CSVGN1) and STATCOM (CSTCNT) in PSS/E
system is increased in step by step and the sources in this
library.
power system are mobilized to supply for these increase.
A three-phase fault is applied at near bus 500kV Tan Dinh
1.02
Bus Voltage (kV) and Di Linh-Tan Dinh line is tripped at 0.7sec after fault by
1.00 Stability area protection relays. Without FACTS installation, the power
0.98
SM=1550MW system is instable as shown as in Fig. 9.
0.96 All cases of simulation are carried out with the range for
0.94 the SVCs or STATCOMs from -300 MVAr to 300 MVAr.
0.92
These FACTS devices are placed at four indicated buses.
Instability area

CauBong
0.90 120
PhuLam
0.88
DucHoa
0.86 TanDinh SVC case
0.84

Relative Angle (Degree)


Incremental transfer (x103MW)
0.82
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7

Fig. 7. PV curves of 4 selected load buses where voltages are the lowest

The increasing of loads provides an incremental active


power transferred on 500kV Pleiku-Di Linh and Pleiku-Dak STATCOM case
Nong transmission lines (Fig. 5).
Fig. 7 shows that a voltage collapse occurs when the
transferred power reaches to 1550MW (SM=1550MW: Static Without FACTS
voltage stability Margin). The critical case corresponds to this
SM factor. -180

Based on the P-V curve analysis, the best location for shunt 0 3.0 6.0 9.0 12 15 18 21 24 27 30
TIME (SECONDS)
reactive power compensation in order to improve the voltage
Fig. 9. Rotor angle at Tra Vinh machine with three phases fault
stability margin is chosen at buses where voltages are the
lowest. These buses correspond to the weakest buses of the 120
system. By introducing shunt compensation devices at these
buses, this permits to improve the voltage stability (or to
increase SM). Relative Angle (Degree)

1.04
Bus Voltage (kV)
1.02 Stability area
1.00

0.98 SM=1850MW
0.96

0.94 CauBong
STATCOM case
0.92 PhuLam
Instability area

0.90 DucHoa

0.88 TanDinh SVC case

0.86
Incremental transfer (x103MW) -180
0.84
0 3.0 6.0 9.0 12 15 18 21 24 27 30
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2 TIME (SECONDS)

Fig. 8. PV curves of 4 selected load buses where voltages are the lowest Fig. 10. Rotor angle at O Mon machine with three phases fault

4
5
120
STATCOM at Tan Dinh

Rotor angle of Tra Vinh


machine
(STATCOM case)

Relative Angle (Degree)

VAR (pu)
STATCOM at Duc Hoa

Rotor angle of OMon machine


(STATCOM case)

Rotor angle of Tra Vinh and OMon machine


(SVC case)

-200 -5

0 3.0 6.0 9.0 12 15 18 21 24 27 30 0 2.0 4.0 6.0 8.0 10 12 14 16 18 20


TIME (SECONDS) TIME (SECONDS)

Fig. 11. Rotor angle at Tra Vinh and OMon machines with three phases fault Fig. 14. VAR output of STATCOM (Sbase =100MVA).
(SVC and STATCOM cases)
1.1 Fig. 9 and Fig. 10 show the angle variation of Tra Vinh and
O Mon machines with SVC or STACOM placed at 220kV
buses of Cau Bong, Duc Hoa, Tan Dinh and Phu Lam (the
same as the preceding part). It shows that the magnitude of
rotor angles variation of Tra Vinh machine (P=1000MW) and
STATCOM case O Mon machine (P=330MW) with SVC case is higher than in
Bus Voltage (pu)

comparison with STATCOM case.


SVC case
Fig. 11 shows the variation of angle at Tra Vinh and O
Mon when the fault is cleared about 0.8sec after fault (the
fault time is at t=1sec). With SVC case, the power system is
instable. Fig. 12 shows the variation of voltage at 500 kV Tan
Dinh.
With SVC case, the maximum transient capacitive current
is determined by the size of the capacitor and the magnitude
of the AC system voltage. The reactive power support
0 provided by the SVC is dependent on the AC system voltage
0 2.0 4.0 6.0 8.0 10 12 14 16 18 20 and hence its capability is de-rated at lower voltages (Fig.13).
5 120
TIME (SECONDS)
STATCOM: 300MVAr (a)
Fig. 12. Voltage at 500kV Tan Dinh with SVC and STATCOM cases. STATCOM: 200MVAr (b)

Relative Angle (Degree)


SVC at Duc Hoa VAR (pu)

Rotor angle of Tra Vinh machine


( case a)
VAR (pu)

Rotor angle of Tra Vinh machine


( case b)

SVC at Tan Dinh

-5 -200

0 3.0 6.0 9.0 12 15 18 21 24 27 30


TIME (SECONDS)

-4
Fig. 15. Rotor angle at Tra Vinh machines and VAR output of STATCOM at
0 2.0 4.0 6.0 8.0 10 12 14 16 18 20 Tan Dinh with two case: (a) STATCOM: 300MVAr ; (b) STATCOM:
TIME (SECONDS)
200MVAr.
Fig. 13. VAR output of SVC (Sbase =100MVA).

5
The obtained results show that STATCOM application is The transient angle stability simulations have shown that
better in order to improve the transient angle stability and STATCOM gives a better solution to improve the stability in
voltage stability in comparison with SVC application. comparison with SVC devices.
In contrast, STATCOMs compensating current is not
dependent on the voltage level at the connection point which
means that the compensating current is not lowered when the VII. BIOGRAPHIES
voltage drops.
With STATCOM case, when the reactive power of Quyen LE CAO was born in Vietnam. He received his engineer degree and
his MSc degree in Electrical Engineering from the Ho Chi Minh city
STATCOM is reduced from 300 to 200MVAr, the obtained University of Technology in 1999 and 2005, respectively. He is now working
result shows that the power system is also stable (Fig. 15). toward a PhD degree in the Danang University. Since 2005 he has been
Whereas with SVC case, the reactive power support provided working as Deputy-in-Chief of Substation Design Department in the Power
by the SVC is increased from 300 to 450MVAr to keep Engineering Consulting Company - PECC4.
transient angle stability (Fig.16). Tuan TRAN-QUOC (M' 93, SM' 99) received his Ph.D. degree in Electrical
120 1.1 5 Engineering and Habilitation Diriger des Recherches degree from the
Grenoble - Institut National Polytechnique (Grenoble-INP) in 1993 and 2000,
respectively. He works now with IDEA. His research interests are in the fields
of power system analysis, operations, electromagnetic transients and load
management.

Voltage at 500kV Tan Dinh Relative Angle (Degree)


Anh NGUYEN-HONG was born in Vietnam. He received his degree in
Bus Voltage (pu) Electrical Engineering from the Danang University of Technology (Vietnam)
in 1980. He received his Ph.D. degree in Electrical Engineering in 1990 in
Czech Republic. Since 1999 he has been professor at the Danang University
VAR (pu)

of Technology. He is presently President of Qui Nhon University.


Rotor angle of Tra Vinh machine

VIII. REFERENCES
[1] H. G. Sarmiento, G. Pampin, J. D. de Leon, FACTS solutions for
voltage stability problems in a large metropolitan area, 2004 IEEE/PES
Power Systems Conference and Exposition, vol. 1, pp. 275 282, Oct.
SVC: +450MVAr 2004.
[2] A. Sode-Yome, N. Mithulananthan, K.Y. Lee, Static Voltage Stability
-200 0 -5 Margin Enhancement Using STATCOM, TCSC and SSSC,
0 3.0 6.0 9.0 12 15 18 21 24 27 30 Transmission and Distribution Conference and Exhibition: Asia and
TIME (SECONDS) Pacific, 2005 IEEE/PES, pp.1-6, 2005.
Fig. 16. Rotor angle at Tra Vinh machines, VAR output of SVC at Tan Dinh [3] B. Gao, G.K. Morison, P. Kundur, "Voltage Stability Evaluation Using
and Voltage at 500kV Tan Dinh with three phases fault. Modal Analysis," IEEE Trans. on Power Systems, vol. 7, no. 4, Nov.
. 1993.
[4] C. Caizares, F.L. Alvarado, "Point of Collapse and Continuation
The obtained results show that with the same reactive power Methods for Large AC/DC Systems," IEEE Trans. on Power Systems,
rating or lower, STATCOMs are more effective than SVCs for vol. 8, no. 1, pp. 1-8, Feb. 1993.
[5] V. Ajjarapu, C. Christy, "The Continuation Power Flow: A Tool for
a same situation.
Steady State Voltage Stability Analysis," IEEE PICA Conference
Procedings, pp. 304-311, May 1991.
VI. CONCLUSIONS [6] M. Noroozian, C.W. Taylor, Benefits of SVC and STATCOM for
electric utility application, Transmission and Distribution Conference
The P-V curve method for choosing optimal placement of and Exposition, IEEE PES, vol.3, pp.1192-1199, sept.2003
shunt compensation device have been used for this study. [7] T. Quoc Tuan, Ch. Praing, R. Feuillet, .C. Sabonnadire, U. La-Van, C.
One of the most important advantages of STATCOM in Nguyen-Duc, Improvement Of Voltage Stability On The Vietnam
Power System, Power Engineering Society Winter Meeting, vol.2,
comparison with SVC is that its compensating current is not pp.1513-1518, 2000
dependent on the voltage level at the connection point. This [8] T. Tran Quoc, J.C Sabonnadire, N. Hajdsaid, R. Feuillet, "Voltage/Var
means that the compensating current is not lower when the Control on the Vietnam Power System", 13th Power Systems
voltage drops. Computation Conference, Trondheim, NORWAY, June-July 1999
[9] PSS/ETM 30.2 online documentation, November 2005
The maximum compensating current of the SVC decreases [10] Narain G. Hingorani, Laszlo Gyugyi Understanding FACTS: Concepts
linearly with the AC system voltage and the maximum VAR and Technology of Flexible AC Transmission Systems, Wiley-IEEE
output decreases with the square of the voltage. This implies Press, December 1999
[11] SONG Yong Hua, JOHNS Allan T., Flexible AC transmission systems
that for obtaining the same dynamic performance, a higher
(FACTS), IEE power engineering series 30
rating SVC is required in comparison with a STATCOM. [12] John J. Paserba, Planning and implementing FACTS controllers for
An application of FACTS devices for the 500kV Vietnam Improving Power System Dynamic Performance HVDC and FACTS
power system in 2015 was studied to improve voltage stability Subcommittee Meeting IEEE PES General Meeting, July 23, 2008
[13] John J. Paserba, How FACTS Controllers Benefit AC Transmission
and transient angle stability of this power system. Systems, IEEE. Power Engineering Society General Meting, Denver,
The obtained results show that with the application of Colorado, 6-10 June 2004
FACTS devices, voltage stability and transient angle stability
of this power system are considerably improved.

Vous aimerez peut-être aussi