Académique Documents
Professionnel Documents
Culture Documents
Index
1 Data
2 Tower height
4 Tower area
5 Compensation water
6 Operating diagram
8 Example 7.1
9 Comment
10 Trapezoidal rule
Ref. 1
Ref. 2
Ref
Collaborations
, according Treybal [1]
Index
Schema
This application will be realized with following numerical data (Note 1).
Notes
1.- This data has been taken from [1], example 7.1, pages 278-281.
2.- The data "Q" is not used, since it would be in contradiction with other input data (See sheet 9)
Q= 270 W
Help Variables
Cooling Tower Schema
State L1
Water leaving the tower
tL1 = twbG1 + t
tbhG1 24 L2 =
t = 5 K tL2 =
tL1 = 29 C
Product Ky*a
Ky*a = Ky*a
ky = 0.0018 kg / ( m2*s)
a= 500 m/m
Ky*a = 0.90 kg / ( m3*s)
Rev. cjc. 08.11.2014
15 kg / s
45 C Air
Water
2
L2 G2
Cooling
tower
G1
G1 tdbG1 = 30 C
1 L1
twbG1 24 C
Water
29 C Air
Blowdown water: B
2000 ppm
Cooling Tower height
kg
Gd
HTU s
M B ky a A kg kmol m 2
2
m
kmol m 2 s m 3
Gd
HTU m
M B ky a A
Introducin g the Air unit mass flow rate G'
Gd
kg
G' s m2
A
G'
HTU m
M B ky a
G'
HTU m
M B ky a
HTU = G' / ( MB * ky * a )
G' = 2 kg dry air /( s*m)
MB = 28.96 kg/kmol
ky = 6.2E-05 kmol/(m*s)
a= 500 m/m
HTU = 2.2 m
NTU and HTU calculations
Column 1 Column 2
Equilibrium curve for saturated air.
Water temperature at inlet of tower (top) The curve is drawn using the function
tL2 = 45 C hair,sat = Sicro_Enthalpy_tdb_f_H
Water temperature at tower outlet (bottom) using a relative humidity
tL1 = 29 C f= 100 %
Range: tL2 -> tL1 and the local heigt
H= 0 m.a.s.l.
Number of sections A temperature range is selected to
The range will be divided in a number "N" cover a range A-B, with
of sections tA = 25 C
N= 6 tB = 47 C
Column 3
Column 1 starts with temperature "tL2" Operation line for the minimum possible
and ends with temperature "tL1". air flow rate G's.min. (i.e., r = 1)
Between both temperatures, "N-1" For this type of operation, the operation
temperatures are inserted to define line will have the minimum slope that
the N sections. All section are defined would allow it to touch the equilibrium
with the same temperature differential. curve (will be tangent to this curve).
Air enters at the bottom of the tower at
Temperature differential contition G1:
tL = tL2 - tL1 C tbsG1 = 30 C
tL2 = 45 C tbhG1 24 C
tL1 = 29 C H= 0 m.a.s.l.
tL = 16 K hG1 #VALUE! kJ/kg
fG1 = #VALUE! %
Section temperature increment Air leaves at the top (case r = 1)
tL_Sect = tL / N Sheet 8, shows the calculation of the
tL = 16 K enthalpy obtained when accomplishing
N= 6 - with this condition.
tL_Sect = 2.67 K Th calculated value is
hGo' = #VALUE! kJ/kg
Temperature at point "i+1" at a temperature
ti+1 = ti + tL_sect tGo' = 45 C
Note1. 3
The equilibrium data used by Treybal is Enthalpy potential
taken from a graphic (Fig. 7.5a) Columns 3a and 5
The equilibrium data resulting from the Ref. 4 (28.4)
use of the functions, is similar to the
data from Ashrae Fundamentals
Example Ashrae Functions Treybal
t C ts kJ/kg ts kJ/kg ts kJ/kg
45 214.16 212.96 216
29 94.88 94.41 100
Note 2
Integration according the the trapezoidal rule
See sheet 10.
ky a H ' Hi H ' 1
NTU
dI y
1
I y ,i I y
I y ,b
H 2'
dH ' (7.51b)
NTU '
H'
Hi H ' The numerial integration of NTU is
1
performed by means of the trapezoidal
where H'2 and H'1 are the enthalpies of integration method.
the air-water mixture for the actual case, According this method, the integration
that is, in this case for r = 1.5. is realized as it is shown in the columns
6, 7 and 8.
hL _ a hL _ b
Z =HTUNTU [ m ] (7.51d)
NTU
2 N
f ( x)
NTU = (hL_a - hL_b) /(2* N) *
Also where
hL_in_r=1.5 = #VALUE!
GS hL_out=r=1.5= #VALUE!
HTU = N= 6
M Bk yaA f(x) = #VALUE!
Comparison between the example calculation table and the table from Treibal
2
To be reviewed I y ,a
1
I
Explanation and
NTU dI y
Straight line, due Le = 1
I y ,b y,i I y
Ref. 4 (27.3.1)
sfer Units "NTU" Height of Transfer Unit "HTU" Height of Transfer Unit "HTU"
quation (7-51)
' GS
GS HTU =
HTU = M Bk yaA
1 k ya
I y ,i I y
dI y
HTU =
with
Gs =
tegration of NTU is MB =
eans of the trapezoidal HTU = G'S /( ky * a) ky_kmol =
G'S : 2.0 kg/(m*s) a=
method, the integration ky*a : 0.9 kg / ( m *s)
3
A=
is shown in the columns HTU = 2.2 m HTU =
Z= HTU * NTU
A:
L_a
- hL_b) /(2* N) * f(x) HTU = 2.2 m
NTU = #VALUE!
kJ/kg Z= #VALUE! m
kJ/kg
Treybal [2] result is
Z= 7.22 m
-
comes from the values of
properties.
ical integration method
nctions. b
ba N
7
Numerical
8
f ( x) dx gi f k
2 N k 1
a
integration
coefficient g i 1 para i 1 y N
Ci f(x) g i 2 para i 2 ... ( N 1)
NTU=(hL2 - hL1)/2*N* (f(x1) + 2*f(x2) + 2*f(x3) + .+ 2*f(xN-1) + f(xN) )
7 8
Numerical
integration
coefficient
Ci f(x) Treybal table differs from the calculation
table in the values of the psichrometric
properties.
Additionaly, Treibal uses a different
1 0.03575 numerical integration method, where
1 0.04545 the numerical integration coefficienst are
1 0.04292 not required (or Ci = 1)
1 0.03846 The numerical integration used is not
1 0.03195 indicated and Treybal gives as a
1 0.02410 final result a NTU value
1 0.01905
f(x) = 0.23767 NTU = 3.25 -
Rev. cjc. 08.11.2014
Page 1 of 4
GS L c pw
t L 2 t L1
hG 2 hG1
hG 2 hG1
m
t L 2 t L1
L c pw
GS
m
Page 2 of 4
(Column 1)
(Column 3)
wer (point 2' in diagram)
(Column 1)
(Column 3)
Page 3 of 4
eight of Transfer Unit "HTU"
GS
HTU =
M Bk yaA
GS / (MB * ky * a * A)
#VALUE! kg as/s
28.96 kg/kmol
6.2E-05 kmol / ( m2*s)
500 m/m
#VALUE! m
#VALUE! m
Page 4 of 4
Free-cross sectional surface of tower
kg / ( m3*s)
m
Compensation water
Entrainment water
W, daC
G2
Cooling
tower
L1 G1
Air
B, daC
Elimination water
kg/s
kg/s
kg/s
kg/s
Operation Diagram
1 2 3 3a 4 5 6
Curva de Lnea de Lnea de
equilibrio para operacin operacin
aire saturado para r = 1 h = para r = 1.5 h = 1/h
tL hair,sat hoper_r=1 hair,sat -hop_r=1 hoper_r=1.5 hair,sat -hop_r=1.5
kJ/kg kJ/kg kJ/kg kJ/kg kJ/kg 1/(kJ/kg)
25.0 #VALUE!
25.5 #VALUE!
29.0 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
31.7 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
34.3 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
37.0 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
39.7 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
42.3 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
45.0 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
47.0 #VALUE!
tL hT h tT From sheet 1
C kJ/kg kJ/kg C t N=
25.0 #VALUE! 0 #VALUE! h N=
25.5 #VALUE! 50 #VALUE! tO =
29.0 #VALUE! 100 #VALUE! tO' =
31.7 #VALUE! 150 #VALUE!
34.3 #VALUE! 200 #VALUE! From calculation, further down
37.0 #VALUE! tT =
39.7 #VALUE! hT =
42.3 #VALUE!
45.0 #VALUE! Point O' (hO', calculated further d
47.0 #VALUE! tO' =
Note hO'=
Column 3a shows that the resulting operation line is not exactly
tangent to the saturation curve. For tangency, the minimum Point O (hO, from sheet 3)
difference should be 0. tO =
A negative value indicates that the solution line is cutting the hO=
saturation curve.
8.0
6.0
Saturatio
12.0
10.0
tL hair,sat Polynom 8.0
C kJ/kg
25 #VALUE! 77.8 #VALUE! #VALUE! 6.0
26 #VALUE! 79.6 #VALUE! #VALUE!
29 #VALUE! 94.5 #VALUE! #VALUE! 4.0
32 #VALUE! 108.5 #VALUE! #VALUE!
2.0
34 #VALUE! 125.0 #VALUE! #VALUE!
37 #VALUE! 143.7 #VALUE! #VALUE! f(x) =
0.0
40 #VALUE! 164.9 #VALUE! #VALUE! 20 25 R = 0
42 #VALUE! 188.4 #VALUE! #VALUE!
45 #VALUE! 214.2 #VALUE! #VALUE!
47 #VALUE! 235.2 #VALUE! #VALUE!
Tangent point
Equation of the satutarion curve
h=0 .1659t 24 . 7921t +92 . 926
Value of the enthalpy in the saturation curve
at the point of tangency (t =tT )
2
h=0 .1659t T 4 .7921tT +92 . 926 (Eq . a)
H'*2 4
H'2 O
t L , H *
t ,H
i i
'
T
S
t L ,H'
R U
H'*1 3
H'1
N
Liquid temperature tL C
tL1 tL2
Figure 2
7 8
O
10.0 O'(tO' ,hO' )
1 #VALUE!
2 #VALUE!
2 #VALUE!
hT T
2 #VALUE! O
2 #VALUE! 8.0 O
2 #VALUE! O(to,ho)
1 #VALUE!
f(x) = #VALUE!
Equilibrium curve, Operating line with r=
6.0 for saturated air 1
rom sheet 1
29 C
Operating line with r = 1.5
#VALUE! kJ/kg
45 C 4.0O
A O
45 C
N (tN, hN)
8.0
6.0
Saturation curve for air at H = 0 m.a.s.l.
12.0
10.0 cc = 93.93
8.0
6.0
4.0
2.0
f(x) =
0.0
20 25 R = 0 30 35 40 45 50
a 0.3318
b - 4.7921 0.3318 t N Point N
c 4.7921 t N h N
Operation line for r = 1
where "r" is the ratio between the actual
a tT2 b tT c 0 mass flow rate and the minimum flow
rate.
a 0.1659 The line starts at a point defined by the
inlet air properties (point N in operating
b -0.3318 tn
diagram) also called state "G1"
c 4.7921 tn 92.93 hn
State G1 (Point N)
From sheet 3 tdbG1 = 30 C
tn = 29 twbG1 = 24 C
hn = #VALUE! H= 0 m
xG1 = Sicro_AbsoluteHumidity_tdb_twb_H
tT = ( -b + (b^2 - 4*a*c)^0.5 ) / ( 2*a ) xG1 = #VALUE! kg/kg
a= 0.1659 hG1 = hN = #VALUE! kJ/kg
b= -9.6222
c= #VALUE!
tT = #VALUE! C
Operating line for minimum air flow. Enthalpy hO'
h0' = hN + (hT - hN) / (t
Enthalpy h O' at temperature tO'
h N= #VALUE!
From Figure 1
h T= #VALUE!
h O' hN h hN t N=
T 29
t o' t N tT tN tT = #VALUE!
h T hN to'= 45
h O' hN t o' t N h0' = #VALUE!
tT tN
h T hN
h O' hN t o' t N
tT tN
Rev. cjc. 08.11.2014
O
O'(tO' ,hO' )
O
O(to,ho)
Equilibrium curve
th r= Polynomial (Equilibrium
curve)
Column E
Op. L. r = 1.5
1.5
h_tangent
t_tangent
tO = tO'
45.0 50.0
C]
Example 7.11. A plant requires that 15 kg / s (1984 lb / min) of cooling water will
flow through a condensation equipment for distillation; thus eliminating 270 W
(55270 Btu / min) from the condensers. The water leaves the condenser at 45 C.
To reuse water it is planned to cool it by contact with air in a cooling tower of
induced draft.
The design conditions are 30 C inlet air dry bulb temperature and 24C wet bulb
temperature. The water is to be cooled to 5 C below the wet bulb temperature of
the air (thus, to 29 C) ; a ratio of air/steam of 1.5 times the minimum value will
be used.
Water compensation will come from a dam at 10 C, with a hardness of 500 ppm
(parts / million) dissolved solids.
The circulating water cannot have a hardness greater than 2000 ppm. Regarding
the package that is to be used, it is expected that the value (Ky * a) will be
0.90 kg / (m * s) for a speed of the liquid of at least 2.7 kg / (m * s) and for a gas
speed of 2.0 kg / (m * s) (1991 and 1474 lbm / (hr * ft) respectively.
Calculate the dimensions of the packed section and water compensation required.
where Gs'min = 7.31 kg dry air / s. For gas flow of 1.5 times the minimum,
Gs = 1.5 * 7.31 = 10.97 kg dry air / s . Therefore,
and H2 '= 163000 J / kg dry air, plotted at point O. Therefore, the operating line
is ON. For a liquid flow of at least 2.7 (kg / m * s), the cross section
should be 15 / 2.7 = 5.56 m. For a gas flow of at least 2.0 kg / (m * s), the
cross section is 10.97 / 2.0 = 5.5 m. Therefore, the last value (5.5) is used, then
in this case the minimum flow of liquid will exceed the minimum an so ensuring
that kv*a = 0.90 .
Data from the last two columns are plotted with H as abscissa.
The area below the curve is 3.25. From equation (7.54)
If this data
Q= 270 W
is a requirement, then, the temperature
of the leving water is a calculated value
and cannot be an input data.
pecific volume
1.013 bar
#VALUE! kJ/kg
#VALUE! m/kg
Rev. cjc. 08.11.2014
Numerical integration with the trapezoidal rule
Numerical implementation
Illustration of trapezoidal rule used on a sequence of samples (in this case, a non-uniform grid).
Uniform grid
For a domain discretized into N equally spaced panels, or N+1 grid points a = x1 < x2 < ... < xN+1 =
Non-uniform grid
When the grid spacing is non-uniform, one can use the formula
Rev. cjc. 08.11.2014
< ... < xN+1 = b, where the grid spacing is h=(b-a)/N, the approximation to the integral becomes
Rev. cjc. 08.11.2014
[1] Operaciones de transferencia de masa 2/e
Robert E. Treybal
McGraw Hill,2003
1
NTU
I y ,i I y
dI y
Subscripts
I y ,b
B: dry air
the packing height becomes y: air phase = humid air
a: top of the tower
b: bottom of the tower
Z = HTUNTU i: corresponds to the boundary (i.e.
ower packing height [m]
ow rate of dry air (is a constat) [kg/s]
olar mass of air [kg/kmol]
ass transfer coefficient in the air [kmol/(ms)]
fective heat or mass transfer surface [m/m]
ee cross-sectional surface of the tower [m]
nthalpy in the air phase = enthalpy of humid air [J/kg]
n the bulk phase)
nthalpy in the air phase (i: at ther boundary,
at is, in saturated condition)
http://nptel.ac.in/courses/Webcourse-contents/IIT%20Kharagpur/Ref%20and%20Air%20Cond/New
[2]
[3]
http://library.kfupm.edu.sa/ISI/2006/5-2006.pdf
[4]
http://nptel.ac.in/courses/Webcourse-contents/IIT%20Kharagpur/Ref%20and%20Air%20Cond/New
http://nptel.ac.in/courses/112105129/pdf/R&AC%20Lecture%2027.pdf
http://nptel.ac.in/courses/Webcourse-contents/IIT%20Kharagpur/Ref%20and%20Air%20Cond/pdf
%20and%20Air%20Cond/New_index1.html
%20and%20Air%20Cond/pdf/R&AC%20Lecture%2028.pdf
India
China
Chile
Per