EMBEDMENT DESIGN

SINGLE BOLT COMBINED TENSION AND SHEAR- ACI 349-2R-8

Pu 40 kip
Vu 20 kip
phi for Pu 0.9
phi for Vu 0.85
shear friction coeff 0.7
phi for pull out 0.65
fc 4000 psi
fy 81000 psi
fut 105000 psi
assumed/provided dia of anchor/rebar 1.25 inch
threaded allowance 0.125
assumed/provided dia of anchor head or width across flats 2 inch
assumed/provided thickness of anchor head 0.78 inch
assumed/provided thickness of plate 0.5 inch

CALCULATIONS
area of anchor/rebars 1.23 sq inch
tensile stress area 0.99 sq inch
dia of anchor head govern 2.24 inch
use Pu=phi x Pn=phi x Ast x fy
required area of steel for pull force 0.55
required area of steel for shear force 0.41
required area of steel for shear force and pull 0.96
required dia of steel for shear force and pull 1.11 inch
whether provided Ast is greater than the required yes
area of anchor head 3.14
ratio anchor head area to tensile area of bolt 3.16
whether provided anchor head dia is greater than the required yes
required thickness of anchor head 0.53 inch
whether provided anchor head thickness is greater than the required yes
DETRMINE EMBED LENGTH
minimum specified tensile strength 104 kip
parameter =phi x 4 * sqrt(fc) 164 psi
pull out strength of concrete Pd 104 kip
quadratic eqn parameter b 2.24
quadratic eqn parameter c -202.04
development length 13.14 inch
pojected area of cone - Acp 635.13 sq inch
whether Pd is greater than minimum specified strength yes
parameter for plate thickness to be greater than 0.45
whether plate thickness is OK yes