A Practical Guide to Nonlinear Static Analysis

Preface
Reinforced concrete (RC) frames with unreinforced masonry (URM) infill walls are
commonly used as the structural system for buildings in many seismically active regions
around the world. Structural engineers recognize that many buildings of this type have
performed poorly during earthquakes. URM infill walls used in Pakistan and adjoining
regions comprise of either burnt clay bricks or cement concrete block masonry. These URM
infill walls are generally treated as non-structural elements, because they are used mainly for
architectural purposes, and structural engineers often ignore them during structural design.

During earthquakes, infill walls affect the response of the structure, and may either beneficial
or detrimental effects. Infill walls contribute to the lateral force resisting capacity and
damping of the structure up to a certain level of ground motion. Infill walls increase the
initial stiffness and decrease the fundamental period of the structure, which might be
beneficial or detrimental, depending on the frequency content of the ground motion.

URM infill walls are prone to early brittle failure, and infill wall failures may lead to the
formation of a weak story, which can cause the building to collapse. Infill walls interact with
the surrounding frame in such a way that column shear failure is made more likely. In
addition, an unequal spatial distribution of infill walls for functional reasons for example,
windows and open commercial spaces on the street frontage and full walls adjacent to
neighbouring buildings can create torsion that places additional demands on columns and
may cause them to fail.

Because of the potentially dire consequences of ignoring the structural role of URM infill
walls, proper consideration of infill walls is essential in any structural analysis of RC frame
buildings with infill walls. This document provides engineers with guidance on how to model
infill walls and include them in structural analyses. Because the consequences of ignoring
infill walls are not region related but exist throughout the world, the authors anticipate that
the guide will be useful for practicing engineers in Pakistan as well as in other countries with
many similar buildings.

This document discusses and illustrates how to analyze infill building with an example in
ETABS building analysis and design software by Computers and Structures, Inc. of a 2-D
nonlinear static pushover analysis of a six storey RC building with URM infill walls, based
on guidelines and modeling procedures given in the ATC-40 and FEMA-356 documents. The
procedures for defining the strength and stiffness of equivalent strut members used to model
infill walls are also applicable for linear analyses.

This manual was developed as part of a project that NED University of Engineering (NED)
and Technology and GeoHazards International (GHI), a California based non-profit
organization that improves global earthquake safety, conducted together to assess and design
seismic retrofits for existing buildings typical of the local building stock, such as the one
described in this report. The project was funded by the Pakistan Higher Education
Commission (HEC) and The National Academies through a grant from the United States
Agency for International Development (USAID).

3
A Practical Guide to Nonlinear Static Analysis of Reinforced Concrete Buildings with
Masonry Infill Walls

Copyright 2011 NED University of Engineering and Technology, and GeoHazards


International. All rights reserved, with the exception that Computers and Structures, Inc.
retains copyright to all material pertaining to their ETABS building analysis and design
software.

Developed by:
Sarosh H. Lodi, Professor and Dean, Faculty of Civil Engineering and Architecture, NED
University of Engineering and Technology, Karachi
Aslam F. Mohammed, Assistant Professor, NED University of Engineering and Technology,
Karachi
Rashid A. Khan, Professor, NED University of Engineering and Technology, Karachi
M. Selim Gunay, Post-doctoral Researcher, University of California, Berkeley

Technical reviewers:
Khalid M. Mosalam, Professor, University of California, Berkeley
Gregory G. Deierlein, Professor, Stanford University
David Mar, Principal, Tipping Mar, Berkeley California
Sahibzada F. A. Rafeeqi, Professor and Pro-Vice Chancellor, NED University of Engineering
and Technology, Karachi

Technical editing:
Janise Rodgers, GeoHazards International
Justin Moresco, GeoHazards International

Acknowledgments:
The project team wishes to thank Computers and Structures, Inc. of Berkeley, California for
their generous donation of ETABS building analysis and design software, which was used
to perform the analyses in this guide.

Disclaimer: All parties, including but not limited to NED University of Engineering and
Technology, GeoHazards International, Higher Education Commission, The National
Academies, the United States Agency for International Development, and Computers and
Structures, Inc., are not responsible for any damage or harm that may occur despite or
because of the application of measures and techniques described in this guide. In addition,
users of this guide are solely responsible for the accuracy of structural models, analyses, and
results and for their subsequent usage in any structural design or construction works.
A Practical Guide to Nonlinear Static Analysis

Contents

Chapter 1 Introduction..........................................................................................................7
Chapter 2  Masonry Infill Walls are Important .....................................................................8
An Example of the Effects of Unreinforced Masonry Infill ................................................10
Chapter 3 Performance Based Analysis .............................................................................12
3.1 Nonlinear Static Procedures in Current Standards.........................................................12
3.1.1 Displacement Coefficient Method from FEMA 356 / ASCE 41...........................13
3.1.2 Capacity Spectrum Method from ATC-40 ............................................................14
3.2 Modelling Infill Walls as Struts....................................................................................15
Chapter 4 Pushover Analysis Using ETABS .....................................................................18
4.1 Defining how nonlinearity is considered .....................................................................18
4.2 Determining Analysis Cases ........................................................................................19
4.3 Defining Loading .........................................................................................................19
4.4 Selecting the Type of Load Control.............................................................................20
4.5 Analysis Results...........................................................................................................20
4.6 Procedure .....................................................................................................................21
4.7 Important Considerations.............................................................................................21
Chapter 5 Example of Pushover Analysis Using ETABS .......................................................22
5.1 Modelling.....................................................................................................................22
5.2  Defining and Assigning Loads on Structure .............................................................30
5.3 Analysis.....................................................................................................................34
5.3.2 Non-Linear Static Analysis................................................................................36
5.4 Results .......................................................................................................................53
Sources of Additional Information ..........................................................................................58
References................................................................................................................................59

5
A Practical Guide to Nonlinear Static Analysis

Chapter1 Introduction
The 2005 Kashmir earthquake dramatically demonstrated the lethal combination of
vulnerable buildings and strong ground shaking. But the earthquake-affected areas arent the
only places at risk earthquake faults underlie many parts of Pakistan. The countrys cities,
including Karachi (see sidebar) have many reinforced concrete (RC) frame buildings with
masonry infill walls that are at risk of earthquake damage. There is a growing need for
engineers to evaluate these buildings to determine their potential performance in a major
earthquake. This guide will show you how to use a simple yet powerful analysis technique
called nonlinear static analysis, or pushover analysis, to determine what type and extent of
earthquake damage may occur in these buildings, and the effects of potential strengthening
measures that you can apply to reduce damage.

The recent advent of structural design for a particular


The city of Karachi, with more
level of earthquake performance, such as immediate
than 14 million inhabitants, sits
post-earthquake occupancy, (termed performance
close to a tectonic plate boundary
based earthquake engineering), has resulted in
and within reach of earthquakes
guidelines such as ATC-40 (1996), FEMA-273 (1996)
on numerous faults surrounding
and FEMA-356 (2000) and standards such as ASCE-
the city. Karachis buildings are
41 (2006), among others. New Zealands building
at risk due to the combination of
code is performance-based. Among the different types
seismic hazard and structural
of analyses described in these documents, pushover
vulnerability.
analysis comes forward because of its optimal
accuracy, efficiency and ease of use.

Pushover analysis gives necessary insight into


nonlinear behaviour without the additional
complexities of nonlinear dynamic analysis. Pushover
analysis is a static, nonlinear procedure in which the
magnitude of the structural loading is incrementally
increased in accordance with a certain predefined
pattern. As the load increases, the structure begins to
yield and become damaged, and the structural
deficiencies and failure modes of the building become
apparent. The loading is monotonic (i.e., in a single direction) with the effects of the load
reversals that occur during a real earthquake being estimated by using modified monotonic
force-deformation criteria and with damping approximations. The goal of static pushover
analysis is to evaluate the real strength of the existing structure, rather than to give the lower
bound strength for design.

Due to the reasons mentioned above, this document focuses on nonlinear static analysis with
an emphasis on RC frame buildings with masonry infill walls. Pushover analysis is
demonstrated using the computer software ETABS, which was developed by Berkeley,
California-based Computers and Structures Inc. and is one of several available software
programs with the capability to conduct pushover analysis. ETABS is an integrated building

7
analysis and design software that incorporates linear, nonlinear, static and dynamic analysis
capabilities with the building design features.

Chapter2 MasonryInfillWallsareImportant
Reinforced concrete (RC) frame buildings with unreinforced masonry (URM) infill walls are
commonly built throughout the world, including in seismically active regions. URM infill
walls are widely used as partitions throughout Pakistan, and despite often being considered as
non-structural elements, they affect both the structural and non-structural performance of RC
buildings. Structural engineers recognize that many buildings of this type have performed
poorly and have even collapsed during recent earthquakes in Turkey, Taiwan, India, Algeria,
Pakistan, China, Italy and Haiti, as Figure 1shows.

a)
b)

d)
c)

f)
e)
A Practical Guide to Nonlinear Static Analysis

Figure 1. Masonry infill-related damage in recent


earthquakes
Most of the damage to reinforced
However, contrary to the experience gathered from concrete buildings observed after
these earthquakes, these buildings continue to be built the 2005 Kashmir earthquake was
in many seismic regions around the world. attributed to poor material
Particularly in countries with emerging economies, quality, inadequate reinforcement
vulnerable infilled frame buildings continue to be details and poor construction
built at a rapid rate in order to keep up with urban practices. Many URM infill walls
population growth and contribute greatly to increased were damaged themselves, and
global earthquake risk. When the seismic led to soft storey collapses in
vulnerabilities present in the RC system (such as lack medium to high rise buildings
of confinement at the beam and column ends and the with commercial space (shops) or
beam column joints, strong beam-weak column parking at the ground floor and a
proportions, and presence of shear-critical columns) large concentration of heavy, stiff
are combined with the complexity due to the infill walls in the stories above.
interaction of the infill walls and the surrounding These vulnerabilities in RC
frame and the brittleness of the URM materials, non- buildings exist throughout
ductile RC frames with URM infill walls may be Pakistan.
considered as one of the worlds most common types
of seismically vulnerable buildings. Therefore, it is
essential to apply existing knowledge on the
behaviour of this complex structural system to
develop proper modelling techniques and adequate
retrofit methods.

URM infill walls are generally treated as non-


structural elements which are used mainly for
architectural purposes. However, many researchers
(e.g., Humar et al., 2001; Saatcioglu et al., 2001;
Korkmaz et al., 2007; Mondal and Jain, 2008; Taher,
et al., 2008) and the experiences in past earthquakes
have shown that the presence of URM walls changes
the seismic response of framed building. The URM
walls function as structural elements, and they may
have beneficial or detrimental effects. Infill walls contribute to the lateral force resisting
capacity and damping of the structure up to a certain level of structural response. They
increase the initial stiffness and decrease the initial period of the structure, which might be
beneficial or detrimental depending on the frequency content of the experienced ground
motion. URM infill walls are prone to early brittle failure. Infill walls interacting with frames
tend to alter the buildings overall strength and stiffness distribution. This may be despite the
design intent of the engineer, because infill walls are typically considered as non-structural
and therefore neglected in the frame design. Many buildings have a soft storey created by
commercial space (shops) or parking at the ground floor (Figure 1a and b). Even in buildings
without open spaces at the ground floor, brittle infill wall failure may lead to the formation of
a weak and soft storey during ground shaking in buildings that would have otherwise not had
one (Figure 1c and d). In addition, infill walls interact with the surrounding frame in such a
way that column shear failure is made more likely (Figure 1e). Infill walls can also induce
torsion when some sides of the building have solid infill walls and the other sides have either
infill walls with openings or no infill walls for architectural or usage purposes (Figure 1f).
9
Considering the severity of the detrimental effects of infill they can cause collapse proper
modelling of URM infill walls within RC frames is essential for seismic evaluation and
consequently for the selection of adequate retrofit solutions to reduce damage and its
consequences.

AnExampleoftheEffectsofUnreinforcedMasonryInfill
Before moving ahead, it is instructive to see how infill alters the behaviour of a bare RC
frame. Using pushover analysis, we compare here the differences in behaviour between a
bare frame and the same frame with infill walls in all the stories except the first, shown in
Figure 2 below. The effect of the infill is emulated by a single diagonal compression strut in
each bay.

Figure 2. Bare frame (left) and the same frame with infill in all stories except ground (right)
The pushover curves are compared in Figure 3. The strength and stiffness of the infilled
frame is significantly increased due to the presence of infill, but the displacement capacity
decreases and a soft story develops, which is evident from the displacement profiles in Figure
4. The deformation accumulates in the bottom story the true behaviour during an
earthquake when infill is considered in the analysis, rather than being distributed evenly
over all stories when the designer ignores the infill and incorrectly models the building as a
bare frame.

So, based on these results, infill walls can be beneficial as long as they are properly taken into
consideration in the design process and the failure mechanism is controlled (i.e., no weak
story is allowed to occur). However, this example also shows that failing to consider infill
walls during structural design can lead to deadly weak-story collapses.
A Practical Guide to Nonlinear Static Analysis

Figure 3. Pushover curve comparison for the bare and infilled frames

Figure 4. Displacement profile comparison for the bare and infilled frames

11
Chapter3 PerformanceBasedAnalysis
The guidelines and standards mentioned in the introduction include modelling procedures,
acceptance criteria and analysis procedures for pushover analysis. These documents define
force-deformation criteria for potential locations of lumped inelastic behaviour, designated as
plastic hinges used in pushover analysis. As shown in Figure 5 below, five points labelled A,
B, C, D, and E are used to define the force deformation behaviour of the plastic hinge, and
three points labelled IO (Immediate Occupancy), LS (Life Safety) and CP (Collapse
Prevention) are used to define the acceptance criteria for the hinge. In these documents, if all
the members meet the acceptance criteria for a particular performance level, such as Life
Safety, then the entire structure is expected to achieve the Life Safety level of performance.
The values assigned to each of these points vary depending on the type of member as well as
many other parameters, such as the expected type of failure, the level of stresses with respect
to the strength, or code compliance.

Figure 5. Force-Deformation Relation for Plastic Hinge in Pushover Analysis

Both the ATC-40 and FEMA 356 documents present similar performance-based engineering
methods that rely on nonlinear static analysis procedures for prediction of structural demands.
While procedures in both documents involve generation of a pushover curve to predict the
inelastic force-deformation behaviour of the structure, they differ in the technique used to
calculate the global inelastic displacement demand for a given ground motion. The FEMA
356 document uses the Coefficient Method, whereby displacement demand is calculated by
modifying elastic predictions of displacement demand. The ATC-40 Report details the
Capacity-Spectrum Method, whereby modal displacement demand is determined from the
intersection of a capacity curve, derived from the pushover curve, with a demand curve that
consists of the smoothed response spectrum representing the design ground motion, modified
to account for hysteretic damping effects.

3.1NonlinearStaticProceduresinCurrentStandards
Current standards such as ASCE 41 provide two alternate methods of estimating the peak
displacement demand for use in nonlinear static procedures: the displacement coefficient
method and the capacity spectrum method. Both methods rely on an equivalent linearization
approach. The basic assumption in equivalent linearization techniques is that the maximum
inelastic deformation of a nonlinear single degree of freedom (SDOF) system is
approximately equal to the maximum deformation of a linear elastic SDOF system, provided
A Practical Guide to Nonlinear Static Analysis

that the linear elastic system has a period and a damping ratio that are larger than the initial
values of those for the nonlinear system.

The displacement coefficient method is conceptually simpler and easier to use, and is not
prone to the graphical misinterpretations that can occur with the capacity spectrum method.
The authors recommend using the displacement coefficient method, either alone or to check
results obtained by using the automated capacity spectrum method capabilities in ETABS.

3.1.1DisplacementCoefficientMethodfromFEMA356/ASCE41

The displacement coefficient method (simply called the coefficient method in FEMA 356) is
the primary method of estimating displacement for the nonlinear static procedure in ASCE
41, and its pre-standard FEMA 356. The displacement coefficient method generates an
estimate of the maximum global displacement, called the target displacement, by modifying
the linear elastic response of an equivalent SDOF system. This is accomplished by
multiplying the SDOF spectral displacement by a series of coefficients, C0 through C3. Figure
6 shows the process used to calculate the target displacement.

Figure 6. Schematic illustration of the process of estimating target displacement using the
displacement coefficient method, for a given response spectrum and effective period, Te
(reproduced from FEMA 440, Figure 2-12, a public domain document).
First an effective period, Te, is generated from the initial period, Ti, by a graphical procedure
using an idealized force-deformation curve (i.e., pushover curve) relating base shear to roof

13
displacement, which accounts for some stiffness loss as the system begins to behave
inelastically. The effective period represents the linear stiffness of the equivalent SDOF
system. The effective period is used to determine the equivalent SDOF systems spectral
acceleration, Sa, using an elastic response spectrum. The procedure assumes that the damping
(usually 5%) is appropriate for a structure in the elastic range.

Then, the peak elastic spectral displacement is determined from the spectral acceleration
using the following equation:

2
Teff
Sd Sa (1)
4S 2

The Displacement Coefficient Method then uses four coefficients to convert the peak elastic
spectral displacement first to elastic displacement at the roof and then to inelastic
displacement at the roof. FEMA 440, Improvement of Nonlinear Static Seismic Analysis
Procedures, explains each of the coefficients C0 through C3 as follows:

The coefficient C0 is a shape factor (often taken as the first mode participation factor) that
simply converts the spectral displacement to the displacement at the roof. The other
coefficients each account for a separate inelastic effect. The coefficient C1 is the ratio of
expected displacement for a bilinear inelastic oscillator to the displacement for a linear
oscillator. C1 depends on the ratio of elastic force, calculated as the spectral acceleration
multiplied by the mass, to the yield strength, the period of the SDOF system, Te and the
characteristic period of the spectrum. The coefficient C2 accounts for the effect of pinching in
load-deformation relationships due to degradation in stiffness and strength. Finally, the
coefficient C3 adjusts for second-order geometric nonlinearity (P-) effects. The coefficients
are empirical and derived primarily from statistical studies of the nonlinear response-history
analyses of SDOF oscillators and adjusted using engineering judgment.

3.1.2CapacitySpectrumMethodfromATC40

The initial step in the capacity spectrum method (as used in ATC-40) is the same as in the
displacement coefficient method: generate a pushover curve for the structure. However, in the
capacity spectrum method, the results are plotted in acceleration-displacement response
spectrum (ADRS) format, shown in Figure 7. To plot the pushover in ADRS format (called a
capacity curve), the base shear versus roof displacement relationship must be converted using
the dynamic properties of the system. The ground motion acceleration response spectrum,
representing the seismic demand, is also converted to ADRS format, so that the capacity
curve can be plotted on the same axes as the seismic demand. It is important to note that in
ADRS format, period is represented by radial lines emanating from the origin.
A Practical Guide to Nonlinear Static Analysis

Figure 7. Graphical representation of the Capacity Spectrum Method, as presented in ATC-


40 (reproduced from FEMA 440, a public-domain document).

Once the pushover curve and response spectrum are plotted together in ADRS format,
iteration is required to determine the maximum inelastic displacement, called the
performance point. FEMA 440 explains why:

The capacity spectrum method assumes that the equivalent damping of the system is
proportional to the area enclosed by the capacity curve. The equivalent period, Teq, is
assumed to be the secant period at which the seismic ground motion demand, reduced for the
equivalent damping, intersects the capacity curve. Since the equivalent period and damping
are both a function of the displacement, the solution to determine the maximum inelastic
displacement (i.e., performance point) is iterative. ATC-40 imposes limits on the equivalent
damping to account for strength and stiffness degradation.

3.2ModellingInfillWallsasStruts
The most common method of modelling infill walls is to use equivalent diagonal
compression struts (Figure 8).

15
Figure 8. Equivalent diagonal compression strut modelling of infill walls (reproduced from
FEMA 356, a public domain document)

The axial stiffness of an equivalent strut can be calculated with Equation 2 according to
Section 7.5.2 of FEMA-356.

0.25
E m t inf sin( 2)
O1 (2a)
4 E fe I col hinf

a 0.175 O1hcol 0.4 Ldiag (2b)

a E m t inf
k inf (2c)
Ldiag

In these equations, Em and Efe are the elastic moduli of the infill and the frame material,
respectively, tinf is the thickness of the infill wall, hcol and Icol are the height and moment of
inertia of the section of the column of the surrounding frame, hinf is the height of the infill
wall panel and Ldiag is the length of the diagonal strut. The strength of the compression strut is
calculated with Equation 3.
A Practical Guide to Nonlinear Static Analysis

Ainf fsinf
N comp (3)
cos

In Equation 3, Ainf is the cross sectional area of the infill wall, fsinf is the shear strength of
masonry and T is the angle of the diagonal strut with the horizontal.

As a special case, it is also possible to model an infill wall retrofitted with mesh
reinforcement and concrete by using two diagonal struts, one of which is a compression
member and the other is a tension member. In this case, stiffness is calculated with Equation
4 and distributed equally to the struts.

0.25
E m t inf  E c t c sin 2T
O1 (4a)
4 E fe I col hinf

a 0.175 O1 hcol 0.4 Ldiag (4b)

a E m t inf  Ec t c
k inf (4c)
Ldiag

In Equation 4, Em, Ec and Efe are the elasticity moduli of the infill, concrete used for retrofit
and the frame material, respectively. The other terms in the equation are defined as follows: tf
is the thickness of the infill wall, tc is the thickness of the concrete, T is the angle of the
diagonal strut with the horizontal, hcol and Icol are the height and moment of inertia of the
section of the column of the surrounding frame, hinf is the height of the infill wall panel and
Ldiag is the length of the diagonal strut. The strengths of compression and tension members
are calculated with Equations 5 and 6, respectively.

Ainf fsinf  Ac 3.3 fc


Ncomp (5)
cos T

As f ys Linf s
Ntens (6)
cos T

In Equations 5 and 6, Ainf and Ac (in2) are the cross sectional area of the infill wall and
concrete, respectively, fsinf is the shear strength of masonry, fc is concrete strength (psi), and T
is the angle of the diagonal strut with the horizontal. As is the total cross sectional area of
horizontal mesh reinforcement with spacing s, fys is the strength of steel, and Linf is the wall
length.
17
Chapter4 PushoverAnalysisUsingETABS
Pushover analysis is a very powerful feature offered only in the non-linear version of
ETABS. In addition to performing pushover analyses for performance-based seismic design,
this feature can be used to perform general static nonlinear analysis and the analysis of staged
(incremental) construction. ETABS menus and documentation refer to pushover analysis as
static nonlinear analysis.

Performing any nonlinear analysis takes time and requires patience. Please read the following
information carefully before performing pushover analysis. Make sure to pay special
attention to the Important Considerations section later in this guide. The key points for
conducting pushover analysis can be summarized as follows:

1. Defining how nonlinearity is considered


2. Determining analysis cases
3. Defining loading
4. Selecting the type of load control
5. Analysis Results
6. Procedure for conducting pushover analysis
7. Important Considerations

Information in the sections 4.1 through 4.7 has been adapted for Pakistan conditions from
user documentation for ETABS software, prepared by Computers and Structures, Inc.

4.1Defininghownonlinearityisconsidered
Properly modelling the nonlinear behaviour that the structure is expected to undergo is very
important for obtaining credible analysis results. However, more complicated models are not
necessarily more accurate. When developing a model, keep in mind that pushover analysis
contains inherent simplifications regarding the dynamic behaviour of the building, and select
the level of model complexity accordingly. Several types of nonlinear behaviour can be
considered in a pushover analysis:

1. Material nonlinearity at discrete, user-defined hinges in frame/line


elements. Plastic hinges can be assigned at any number of locations along the
length of any frame element (see Frame Nonlinear Hinge Assignments to Line
Objects in ETABS documentation for details), wherever yielding or other
inelastic behaviour is expected. Uncoupled moment, torsion, axial force and
shear hinges are available. There is also a coupled P-M2-M3 hinge that
considers the interaction of axial force and bending moments at the hinge
location. More than one type of hinge can exist at the same location. For
example, you might assign both an M3 (moment) and a V2 (shear) hinge to
the same end of a frame element. Default hinge properties are provided based
on ATC-40 and FEMA-356 criteria.

For reinforced concrete frame buildings, use coupled P-M hinges when
modelling columns and uncoupled moment hinges for beams. Separate shear
hinges are recommended. To reduce the size and complexity of the model, a
number of analysts check shear forces in each member against that members
shear capacity rather than using shear hinges.
A Practical Guide to Nonlinear Static Analysis

2. Material nonlinearity in the link elements. The available nonlinear


behaviour includes gap (compression only), hook (tension only), uniaxial
plasticity along any degree of freedom, and two types of base isolators (biaxial
plasticity and biaxial friction/pendulum). The link damper property has no
effect in a static nonlinear analysis.
3. Geometric nonlinearity in all elements. You can choose between
considering only P-delta effects or considering P-delta effects plus large
displacements. Large displacement effects consider equilibrium in the
deformed configuration and allow for large translations and rotations.
However, the strains within each element are assumed to remain small. The P-
Delta effects option (without large deformations) is recommended.

4. Adding or removing elements. Members can be added or removed in a


sequence of stages during each analysis case.

4.2DeterminingAnalysisCases
Static nonlinear analysis can consist of any number of cases. Each static nonlinear case can
have a different distribution of load on the structure. For example, a typical static nonlinear
analysis might consist of three cases. The first would apply gravity load to the structure, the
second would apply one distribution of lateral load over the height of the structure, and the
third would apply another distribution of lateral load over the height of the structure.

A static nonlinear case may start from zero initial conditions, or it may start from the results
at the end of a previous case. In the previous example, the gravity case would start from zero
initial conditions, and each of the two lateral cases could start from the end of the gravity
case.

Static nonlinear analysis cases are completely independent of all other analysis types in
ETABS. In particular, any initial P-delta analysis performed for linear and dynamic analysis
has no effect upon static nonlinear analysis cases. The only interaction is that linear mode
shapes can be used for loading in static nonlinear cases.

Static nonlinear analysis cases can be used for design. Generally it does not make sense to
combine linear and nonlinear results, so static nonlinear cases that are to be used for design
should include all loads, appropriately scaled, that are to be combined for the design check.

4.3DefiningLoading
The distribution of load applied on the structure for a given static nonlinear case is defined as
a scaled combination of one or more of the following:

x Any static load case.


x A uniform acceleration acting in any of the three global directions. The force at
each joint is proportional to the mass assigned to that joint (i.e., that calculated from
the tributary area) and acts in the specified direction.

19
x A modal load for any eigen or Ritz mode. The force at each joint is proportional to
the product of the modal displacement (eigenvector), and the mass tributary to that
joint, and it acts in the direction of the modal displacement.
The load combination for each static nonlinear case is incremental, meaning it acts in
addition to the load already on the structure if starting from a previous static nonlinear case.

Floor slabs in reinforced concrete frame buildings are generally modelled as rigid
diaphragms. The rigid diaphragm causes the joints connected to the same floor slab to
displace the same amount horizontally. You will need to consider diaphragm deformations,
and model the diaphragms as flexible, in the following cases:

x Concrete slab is thinner than 100 mm (4 inches);


x Diaphragm has span to depth ratio of 4:1 or greater, where span is defined as the span
between lines of lateral resistance; and
x Diaphragm has large opening (30% or more of floor area is a good rule of thumb).

4.4SelectingtheTypeofLoadControl
ETABS has two distinctly different types of control available for applying the load. Each
analysis case can use a different type of load control. The choice generally depends on the
physical nature of the load and the behaviour expected from the structure:

x Force control. The full load combination is applied as specified. Force control
should be used when the load is known (such as gravity load), and the
structure is expected to be able to support the load in the elastic range.
x Displacement control. A single Monitored Displacement component (or the
Conjugate Displacement) in the structure is controlled. The magnitude of the
load combination is increased or decreased as necessary until the control
displacement reaches a value that you specify. Displacement control should be
used when specified drifts are sought (such as in seismic loading), where the
magnitude of the applied load is not known in advance, or when the structure
can be expected to lose strength or become unstable.

4.5AnalysisResults
ETABS provides several types of output that can be obtained from the static nonlinear
analysis:

1. Base Reaction versus Monitored Displacement can be plotted.


2. Tabulated values of Base Reaction versus Monitored Displacement at each
point along the pushover curve, along with tabulations of the number of hinges
beyond certain control points on their hinge property force-displacement curve
can be viewed on the screen, printed, or saved to a file.
3. Base Reaction versus Monitored Displacement can be plotted in the ADRS
format where the vertical axis is spectral acceleration and the horizontal axis is
spectral displacement. The demand spectra can be superimposed on this plot.
4. Tabulated values of the capacity spectrum (ADRS capacity and demand
curves), the effective period and the effective damping can be viewed on the
screen, printed, or saved to a file.
A Practical Guide to Nonlinear Static Analysis

5. The sequence of hinge formation and the color-coded state of each hinge can
be viewed graphically, on a step-by-step basis, for each step of the static
nonlinear case.
6. The member forces and stresses can be viewed graphically, on a step-by-step
basis, for each step of the static nonlinear case.
7. Member forces and hinge results for selected members can be written to a file
in spreadsheet format for subsequent processing in a spreadsheet program.
8. Member forces and hinge results for selected members can be written to a file
in Access database format.

4.6Procedure
The following general sequence of steps is involved in performing a static nonlinear analysis:

1. Create a model just like you would for any other analysis. Note that material
nonlinearity is restricted to frame and link elements, although other element
types may be present in the model.
2. Define the static load cases, if any, that are needed for use in the static
nonlinear analysis (Define > Static Load Cases command). Define any other
static and dynamic analysis cases that may be needed for steel or concrete
design of frame elements.
3. Define hinge properties, if any (Define > Frame Nonlinear Hinge Properties
command).
4. Assign hinge properties, if any, to frame/line elements (Assign > Frame/Line
> Frame Nonlinear Hinges command).
5. Define nonlinear link properties, if any (Define > Link Properties command).
6. Assign link properties, if any, to frame/line elements (Assign > Frame/Line >
Link Properties command).
7. Run the basic linear and dynamic analyses (Analyze > Run command).
8. Define the static nonlinear load cases (Define > Static Nonlinear/Pushover
Cases command).
9. Run the static nonlinear analysis (Analyze > Run Static Nonlinear Analysis
command).
10. Review the static nonlinear results (Display > Show Static Pushover Curve
command), (Display > Show Deformed Shape command), (Display > Show
Member Forces/Stress Diagram command), and (File > Print Tables >
Analysis Output command).
11. Perform any design checks that utilize static nonlinear cases.
12. Revise the model as necessary and repeat.

4.7ImportantConsiderations
Nonlinear analysis takes time and patience. Each nonlinear problem is different. Expect to
spend a certain amount of time to learn the best way to approach each new problem. Start
21
simple and build up gradually. Make sure the model performs as expected under linear static
loads and modal analysis. Rather than starting with hinges everywhere, add them gradually
beginning with the areas where you expect the most nonlinearity. Start with hinge models
that do not lose strength for primary members; modify the hinge models later or redesign the
structure.

Perform your initial analyses without geometric nonlinearity. Add P-delta effects, and
possibly large deformations later. Start with modest target displacements and a limited
number of steps. In the beginning, the goal should be to perform the analyses quickly so that
you can gain experience with your model. As your confidence grows with a particular model,
you can push it further and consider more extreme nonlinear behaviour.

Mathematically, pushover analysis does not always guarantee a unique solution. Inertial
effects in dynamic analysis and in the real world limit the path a structure can follow. But this
is not true for static analysis, particularly in unstable cases where strength is lost due to
material or geometric nonlinearity.

Small changes in properties or loading can cause large changes in nonlinear response. For
this reason, it is extremely important that you consider different loading patterns, and that you
perform sensitivity studies on the effect of varying the properties of the structure. At
minimum, the recommended lateral load patterns include a uniform load distribution and a
triangular load distribution representing the fundamental vibration mode.

Chapter5ExampleofPushoverAnalysisUsingETABS
5.1Modelling

x Define the grid system according to your structure.

a. After opening ETABS, the first window to appear is shown here.


A Practical Guide to Nonlinear Static Analysis

b. Click on FILE followed by DEFAULT.EDB or NO, using the latter


option for a new model.

23
c. If your structure has one of the available structural systems, click the
desired one. Otherwise, click the GRID ONLY option. When you click the
GRID ONLY, the following grids appear.

In ETABS, the regular order of 1) defining materials, 2) defining sections and assigning the
defined materials to member sections and, 3) defining members and assigning the defined
sections to members is used similarly to most other structural analysis software. Nodes are
automatically created while defining members through the graphical user interface.
A Practical Guide to Nonlinear Static Analysis

x Define the materials (e.g., concrete, masonry, etc.) used in the model.

1. Click on DEFINE then MATERIAL PROPERTIES.

2. Define the necessary materials according to your model.

25
x Define the frame sections for beams, columns, struts, etc. For masonry struts, use
the actual masonry properties, if known, to calculate the equivalent strut capacity.
If the actual properties are not known, use the low values in ASCE-41. Parametric
studies, where the analyst conducts a series of analyses that vary one property of
interest, such as a material strength, while leaving the others fixed, are very useful
in bounding the potential response when the masonry properties are not known.
Using lower masonry strengths is not necessarily conservative, because stronger
infill panels can cause shear failures in the adjacent columns.

a. Click on DEFINE, then FRAME SECTIONS.


A Practical Guide to Nonlinear Static Analysis

b. The following window appears after clicking on FRAME SECTIONS.

27
c. In the previous window, click on the type of section that you want to use.
For example, the following window appears after selecting a rectangular
section. Section dimensions can be input in this window as well as the
reinforcement data in case of reinforced concrete. The material that will be
assigned to the section can also be selected from the list of previously
defined materials.

x Define the members of the structure such as beams, columns, walls, slabs, etc. The
graphical user interface is a powerful and efficient tool at this stage.

a. Members can be defined by using the highlighted tool bar shown in the
following image.
A Practical Guide to Nonlinear Static Analysis

b. For modelling of beams and columns, you can use line the element tool
bar. When you click on this, the following window appears, from which a
desired section can be selected.

c. For modelling an RCC wall, an area element tool bar can be used. When
you click on this, the following window appears.

29
5.2 DefiningandAssigningLoadsonStructure

x Apply gravity loads

Dead load and live load factors should be based on the expected gravity loads for the
building. For most pushover analyses, use the total dead load and 50% of the live load
(1.0 DL + 0.5 LL). You should also check the case of total dead load and zero live
load (1.0 DL + 0 LL).

All dead loads in the building (structural components, partitions, architectural finishes
and more) should be included in in defining the total dead load. The live load per unit
area is accepted as 40, 60 and 100 psf for office buildings, residential buildings and
mosques, respectively, per UBC-97, ASCE 7 and many other building design codes.

In this example, the partition load, live load and architectural finishes load are
assumed to be 50 psf, 40 psf and 24 psf, respectively. Masonry infill walls should be
considered as dead loads, because the infill walls are structural elements.

a. The next step is to apply the gravity loads on the structure. Use the
DEFINE option and click on STATIC LOAD CASES.

b. When you click on STATIC LOAD CASES, the following window


appears. In this window you can add the different types of load you want
to assign to your structure. Here is an example of a STATIC LOAD CASE
A Practical Guide to Nonlinear Static Analysis

DEFINITION window. Self Weight Multiplier is a scale factor which


multiplies the distributed gravity forces calculated by using the specific
weight of a material and the area of a section. It is typically 1 for dead
loads and 0 for other loads.

After defining the static load cases, the loads on the members
corresponding to each load case can be defined. For this purpose, select
any frame member, click on ASSIGN and then click on FRAME/LINE
LOADS. The following window appears.

If you want to apply a uniform load, click on the DISTRIBUTED option in


this window, which causes the following window to appear.

31
c. In this window, you can enter the magnitude of loading, its direction and
specify the load type.

x Define load combination as per design code.

a. The loads from individual static load cases can be combined using a load
combination. Click DEFINE and then LOAD COMBINATION.
A Practical Guide to Nonlinear Static Analysis

b. When you click on load combination, the following window appears. In


this window, click on ADD NEW COMBO

c. When you click on ADD NEW COMBO, the following window appears in
which you can define the load combination as per design code.

33
5.3 Analysis
Linear static analysis can be used as a way to validate the model since anything wrong in the
model will show itself in the response. These errors can be easily viewed through the user
interface. To conduct a linear static analysis, click on ANALYZE followed by RUN
ANALYSIS.

ETABS has tools that use the results of linear static analysis to size members and select
reinforcement for RCC members. While these tools can be used to estimate approximate
reinforcing if the reinforcement in an existing structure is not known, it is much more
reliable to conduct field investigations, especially in critical locations such as the ground
storey frame.

To design a structure:

a. Click on PREFERENCES < CONCRETE FRAME DESIGN.


A Practical Guide to Nonlinear Static Analysis

b. The desired design code can be assigned in the window that appears.

c. Click on ANALYZE in the main menu and then RUN ANALYSIS.

35
d. After the analysis, you should design the structure by selecting member
sizes and reinforcement. To do that, click on DESIGN < CONCRETE
FRAME DESIGN << START DESIGN/CHECK OF STRUCTURE.

e. After obtaining the reinforcement, the moment curvature response of the


sections can be determined for use in defining the behaviour of hinges for
nonlinear analysis. For an existing structure, this can be done using the
available reinforcement. One suitable software program for moment-
curvature analysis is RESPONSE 2000.

5.3.2 NonLinearStaticAnalysis

x Define the hinge definition in model.

In nonlinear analysis the condition of a structure can be determined on the basis of


the hinge status. In ETABS, there are several types of hinges, such as flexural,
shear, axial and axial plus flexural. These hinges can be defined and assigned as
required. For example, in the following case study, flexural hinges are used for
columns and beams and axial hinges are used for struts. Generally, columns
should be modelled with coupled axial-flexural (P-M) hinges. For simplicity,
shear hinges were not included beams and columns, and the shear failure potential
is controlled during post-processing by manually comparing the shear demand
from nonlinear static analysis with the shear capacity.
A Practical Guide to Nonlinear Static Analysis

a. To define a hinge, use DEFINE < FRAME NONLINEAR HINGE


PROPERTIES

b. When you click on FRAME NONLINEAR HINGE PROPERTIES, the


following window appears. In this window, click on ADD NEW
PROPERTY

c. After clicking on ADD NEW PROPERTY, the following window appears.


There are options available through which you can define any type of
hinge.

37
d. To define the flexural hinge for beam, click on MODIFY/SHOW FOR M3
in the preceding window. The following window appears.
A Practical Guide to Nonlinear Static Analysis

Define the hinges using the criteria in ASCE 41. The hinge properties
should properly consider the likely as-built conditions, rather that only the
design drawings or code provisions. Many buildings in Pakistan and the
region will have columns with poor confinement and inadequate ties.
Model the hinges conservatively, assuming that the strength and
deformation capacity are on the low end of the possible range.

x Assign the hinges in the columns, beams, struts and other structural members.

a. After defining the hinges, the next step is to assign the hinge in the frame
elements. Click on ASSIGN < FRAME/LINE < FRAME NONLINEAR
HINGES.

39
b. After clicking on FRAME NONLINEAR HINGES, the desired type of
hinge can be assigned to the selected member from the list of defined
hinges.

x Define the non-linear static analysis.

a. After assigning hinges, click on STATIC NONLINEAR PUSHOVER


CASES.
A Practical Guide to Nonlinear Static Analysis

b. Click on ADD NEW CASE in the window that appears.

c. Two nonlinear cases are basically defined. One for gravity and one for
lateral forces. When ADD NEW CASE is clicked, the window that
appears is where the static nonlinear cases are defined.

41
A Practical Guide to Nonlinear Static Analysis

Before proceeding further, there are several terms that need to be defined in the nonlinear
static case definition window. The description of the options below is reprinted from the
ETABS software documentation.

A. Options

1. Force Control. Choose the type of analysis, force controlled or displacement


controlled, by checking the appropriate check box:

a. Load Level Defined By Pattern. Check the Load Level Defined By


Pattern check box to perform a force-controlled analysis. The analysis
applies the full load value defined by the sum of all loads specified in
the Load Pattern box (unless it fails to converge at a lower force
value). This option is useful for applying gravity load to the structure.

b. Push To Displ. Magnitude. Check the Push To Displ. Magnitude


check box to perform a displacement-controlled analysis. The load
combination specified in the Load Pattern area of the form is applied,
but its magnitude is increased or decreased as necessary to keep the
control displacement increasing in magnitude. This option is useful for
applying lateral load to the structure, or for any case where the
magnitude of the applied load is not known in advance, or when the
structure can be expected to lose strength or become unstable.

x Review the target Displacement Magnitude (i.e., the value in


the edit box opposite the Push to Disp. Magnitude check box)
and check the check box if you want to use the Conjugate
Displacement for control (recommended). If the box is not
checked, the Monitored Displacement is used for control.

x Use Conjugate Displ. for Control

The conjugate displacement is a generalized displacement


measure that is defined as the work conjugate of the applied
Load Pattern. It is a weighted sum of all displacement degrees
of freedom in the structure: each displacement component is
multiplied by the load applied at that degree of freedom, and
the results are summed.

The conjugate displacement is usually the most sensitive


measure of displacement in the structure under a given
specified load. It is usually recommended that you use the
conjugate displacement unless you can identify a displacement
in the structure that monotonically increases during the
analysis.

When you use the conjugate displacement to control the


analysis, the load increments are adjusted in an attempt to reach
the specified monitored displacement. However, the analysis
will usually only approximately satisfy the targeted
43
displacement, particularly if the monitored displacement is in a
different direction than the conjugate displacement.

x Monitor

Define the Monitored Displacement by selecting the


displacement degree of freedom, and by entering the label and
selecting the story level of the point to be monitored. The
Monitored Displacement is used to plot the pushover curve and
also for displacement control when the Push To Displ.
Magnitude option is used.

The Monitored Displacement is a single displacement


component at a single point that is monitored during a static
nonlinear analysis. When plotting the pushover curve, the
program always uses the monitored displacement for the
horizontal axis. The monitored displacement is also used to
determine when to terminate a displacement-controlled
analysis.

The monitored degree of freedom and the monitored point


location are all given default values by ETABS; you can easily
replace those default values. The default value for the
monitored point is a point located at the top of the structure; use
this point for infill frame buildings. The default monitored
degree of freedom is UX; other available directions are UY,
UZ, RX, RY, and RZ.

For the most meaningful pushover curve, it is important that


you choose a monitored displacement that is sensitive to the
applied load pattern. For example, you should not typically
monitor degree of freedom UX when the load is applied in
direction UY. Likewise you should not monitor joints that are
close to the restraints.

The same considerations apply when choosing a monitored


displacement for the purposes of displacement control. Choose
a displacement that is sensitive to the applied load and, if
possible, one that increases monotonically during the analysis.

You may use the monitored displacement or the conjugate


displacement for displacement control, but it is the magnitude
of the monitored displacement that is used to determine when
to terminate a displacement-controlled analysis.

When you use the conjugate displacement to control the


analysis, the load increments are adjusted in an attempt to reach
the specified monitored displacement. However, the analysis
will usually only approximately satisfy the targeted
displacement, particularly if the monitored displacement is in a
A Practical Guide to Nonlinear Static Analysis

different direction than the conjugate displacement. For the


typical first mode or triangular load pattern, it is suitable to use
the roof displacement in the lateral load direction as the
monitored displacement

The analysis is terminated when the Monitored Displacement


reaches the specified Displacement Magnitude (unless it fails to
converge at a lower displacement value).

The target Displacement Magnitude for the Monitored


Displacement is given a default value by ETABS of 0.04 times
the Z coordinate at the top of the structure. Note that if the base
of the structure has a Z coordinate greater than zero, the default
displacement may be quite large. You may change this value as
necessary. Only the absolute value of the Displacement
Magnitude is used: the direction of loading is determined by the
specified load pattern.

2. Start from Previous Case. To start the current case from the end condition of
a previously specified static nonlinear case, select the name of the previous
case from the Start From Previous Case drop down list. Typically this option
is used for a lateral static nonlinear case to specify that it should start from the
end of a gravity static nonlinear case.

3. Save Positive Increments Only. If you want only positive displacement


increments of the pushover curve to be saved, check the Save Positive
Increments Only check box. For the typical first mode or triangular load
pattern and roof displacement used as the monitored displacement, this option
is sufficient.

4. Review the following analysis control parameters, changing them if necessary.


In general, start with smaller limits on the maximums, increasing them as you
gain experience with your model.

x Minimum Saved Steps

The Minimum Saved Steps restricts the maximum step size used to
apply the load in a static nonlinear case. ETABS automatically creates
steps corresponding to events on the hinge stress-strain curves or to
significant nonlinear geometric effects. The results of these steps are
saved only if they correspond to a significant change in the slope of the
pushover curve.

You can use the Minimum Saved Steps to force the program to save
additional steps. A value between 5 and 20 is adequate for most cases,
although if you expect a lot of hinge events, a value of 1 is often the

45
best. If the Member Unloading Method is set to Restart Using Secant
Stiffness, a value of 1 is also recommended.

x Maximum Null Steps

The Maximum Null Steps is used, if necessary, to declare failure (i.e.,


non-convergence) in a run before it reaches the specified force or
displacement goal. The program may be unable to converge on a step
when catastrophic failure occurs in the structure, or when the load
cannot be increased in a load-controlled analysis. There may also be
instances where it is unable to converge in a step because of numerical
sensitivity in the solution.

There are four types of null steps.

1. When an event in one hinge changes the stiffness of the


structure such that another hinge has an immediate event. This
shows up as zero-length step.
2. When the Member Unloading Method is set to Unload Entire
Structure and the unloading of a hinge causes a reversal in the
direction of load applied to the structure. This shows up as
zero-length step.
3. When the Member Unloading Method is set to Apply Local
Redistribution and the unloading of a hinge causes the
application and removal of an internal local redistribution load.
This shows up as multiple zero-length steps.
4. When a step fails to converge within the Maximum
Iteration/Step and the step size is halved. This is not a zero-
length step.

Null steps are to be expected in any analysis; they are not necessarily
bad. However, an excessive number of them may indicate failure of the
analysis.

Typically the Maximum Null Steps should be set to about 25% of the
Maximum Total Steps (e.g., the default is 50 Maximum Null Steps for
200 Maximum Total Steps), but you may need at least twice as many
when the Member Unloading Method is set to Apply Local
Redistribution. Significant Large Displacement effects may also
require more null steps.

x Maximum Total Steps

The Maximum Total Steps limits the total time the analysis will be
allowed to run.
A Practical Guide to Nonlinear Static Analysis

ETABS attempts to apply as much of the specified load pattern as


possible but may be restricted by the occurrence of an event, failure to
converge within the Maximum Iterations/Step, or a limit on the
maximum step size from the Minimum Number of Saved Steps. As a
result, a typical static nonlinear analysis may consist of a large number
of steps. Additional steps may be required by some Member Unloading
Methods to redistribute load.

An event occurs whenever a hinge reaches a new point on its stress-


strain curve or elastically unloads. Thus the number of steps required
to reach a specified target load or displacement will increase with the
number of hinges in the model.

Each step takes about the same amount of computer time. As you gain
experience with a particular model, you will be able to set the
Maximum Total Steps to limit the time the static nonlinear analysis is
allowed to run. You should start small and gradually build up to larger
numbers of steps.

If your analysis does not reach its target within the Maximum Total
Steps, you can run it again with a larger number of steps, but first
examine the results to see whether the structure is still stable enough to
be worth pushing it any farther.

Only steps resulting in significant changes in the shape of the pushover


curve are saved for output.

5. Review the following analysis control parameters, changing them if necessary.


In most cases, the default values are adequate.

x Maximum Iterations/Step and Iteration Tolerance

Static equilibrium is checked at the end of each step in a static


nonlinear analysis. The unbalanced load is calculated as the difference
between the externally applied loads and the internal forces in the
elements. If the ratio of the unbalanced-load magnitude to the applied-
load magnitude exceeds the Iteration Tolerance, the unbalanced load is
applied to the structure in a second iteration for that step. These
iterations continue until the unbalanced load satisfies the Iteration
Tolerance or the Maximum Iterations/Step is reached. In the latter
case, the step size is halved and the load is applied again from the
beginning of the step.

If necessary, the step size is continuously halved until equilibrium is


finally achieved. Each halving of the step size counts as a null step. For
the next step after convergence, the program repeatedly doubles the
step size until it finds the largest size that will converge or until an
event occurs.

47
Iteration is primarily activated by nonlinear link properties and by
geometric nonlinearity, especially for large-displacement analysis.
Iteration is not usually required for material nonlinearity in the frame
hinges because of the event-to-event strategy used.

x Event Tolerance

The Event Tolerance is a ratio used to determine the lumping together


of events. When ETABS determines that one hinge has experienced an
event, it checks for other hinges that are close (within the Event
Tolerance) to experiencing an event. For all hinges within the Event
Tolerance, the program will modify their states to cause these nearby
events to occur.

Larger event tolerances can shorten analysis time by reducing the


number of steps caused by events, but can increase equilibrium errors
within the elements due to the modification of the hinge states. Smaller
event tolerances give more accurate results at the expense of more
computational time. The default value of 0.01 works well for most
cases.

Consider the figure, which shows the location of two hinges on their
force-displacement plots. Hinge 1 has reached an event location. For
hinge 2, if the Event Tolerance is met it too will be treated as part of
the event. In the figure, if the Force Tolerance divided by the Yield
Force is less than the Event Tolerance, and the Displacement
Tolerance divided by the horizontal distance from B to C is less than
the Event Tolerance, then hinge 2 will be treated as part of the event.
When determining the Force Tolerance Ratio, the denominator is
always the yield force. When determining the Displacement Tolerance
Ratio, the denominator is the horizontal length of the portion of the
force-displacement curve that the hinge is currently on. In the figure,
hinge 2 is on the B-C portion of the curve, thus we used the B-C
horizontal length in the denominator of the Displacement Tolerance
Ratio.

B. Member Unloading Method

1. Select the method to be used to handle hinges that drop load. This may affect
the number of steps you allow for the analysis.

When a hinge unloads, the program must find a way to remove the load that
the hinge was carrying and possibly redistribute it to the rest of the structure.
Hinge unloading occurs whenever the stress-strain (force-deformation or
moment-rotation) curve shows a drop in capacity, such as is often assumed
from point C to point D, or from point E to point F (complete rupture).

Such unloading along a negative slope is unstable in a static analysis, and a


unique solution is not always mathematically guaranteed. In dynamic analysis
(and the real world) inertia provides stability and a unique solution.
A Practical Guide to Nonlinear Static Analysis

Because ETABS is performing a static analysis, special methods are needed to


solve this unstable problem. Some methods may work better with some
problems. Different methods may produce different results for the same
problem.

ETABS provides three different methods to solve this problem of hinge


unloading, which are described next.

If all stress-strain slopes are positive or zero, these methods are not used
unless the hinge passes point E and ruptures. Instability caused by geometric
effects is not handled by these methods.

x Unload Entire Structure

When a hinge reaches a negative-sloped portion of the stress-strain


curve, the program continues to try to increase the applied load. If this
results in increased strain (decreased stress) the analysis proceeds. If
the strain tries to reverse, the program instead reverses the load on the
whole structure until the hinge is fully unloaded to the next segment on
the stress-strain curve. At this point the program reverts to increasing
the load on the structure. Other parts of the structure may now pick up
the load that was removed from the unloading hinge.

Whether the load must be reversed or not to unload the hinge depends
on the relative flexibility of the unloading hinge compared with other
parts of the structure that act in series with the hinge. This is very
problem-dependent, but it is automatically detected by the program.

This method is the most efficient of the three methods available, and is
usually the first method you should try. It generally works well if hinge
unloading does not require large reductions in the load applied to the
structure. It will fail if two hinges compete to unload, such as where
one hinge requires the applied load to increase while the other requires
the load to decrease. In this case, the analysis will stop with the
message UNABLE TO FIND A SOLUTION, in which case you
should try one of the other two methods.

This method uses a moderate number of null steps.

x Apply Local Redistribution

This method is similar to the Unload Entire Section method, except


that instead of unloading the entire structure, only the element
containing the hinge is unloaded. When a hinge is on a negative-sloped
portion of the stress-strain curve and the applied load causes the strain
to reverse, the program applies a temporary, localized, self-
equilibrating, internal load that unloads the element. This causes the
hinge to unload. After the hinge has unloaded, the temporary load is
reversed, transferring the removed load to neighbouring elements. This

49
process is intended to imitate how local inertia forces might stabilize a
rapidly unloading element.

This method is often the most effective of the three methods available,
but usually requires more steps than the first method, including a lot of
very small steps and a lot of null steps. The limit on null steps should
usually be set between 40% and 70% of the total steps allowed.

This method will fail if two hinges in the same element compete to
unload, such as where one hinge requires the temporary load to
increase while the other requires the load to decrease. In this case, the
analysis will stop with the message UNABLE TO FIND A
SOLUTION, after which you should divide the element so the hinges
are separated and try again. Check the .LOG file to see which elements
are having problems. Caution: the element length may affect default
hinge properties that are automatically calculated by the program, so
fixed hinge properties should be assigned to any elements that are to be
divided.

x Restart Using Secant Stiffness

This method is quite different from the other two. Whenever any hinge
reaches a negative-sloped portion of the stress-strain curve, all hinges
that have become nonlinear are reformed using secant stiffness
properties, and the analysis is restarted.

The secant stiffness for each hinge is determined as the secant from
point O to point X on the stress strain curve, where: Point O is the
stress-stain point at the beginning of the static nonlinear case (which
usually includes the stress due to gravity load); and Point X is the
current point on the stress-strain curve if the slope is zero or positive,
or else it is the point at the bottom end of a negatively-sloping segment
of the stress-strain curve.

When the load is re-applied from the beginning of the analysis, each
hinge moves along the secant until it reaches point X, after which the
hinge resumes using the given stress-strain curve.

This method is similar to the approach suggested by the FEMA 273


guidelines, and makes sense when performing pushover analysis where
the static nonlinear analysis represents cyclic loading of increasing
amplitude rather than a monotonic static push.

This method is the least efficient of the three, with the number of steps
required increasing as the square of the target displacement. It is also
the most robust (least likely to fail) provided that the gravity load is not
too large. This method may fail when the stress in a hinge under
gravity load is large enough that the secant from O to X is negative. On
the other hand, this method may also give solutions where the other
two fail due to hinges with small (nearly horizontal) negative slopes.
A Practical Guide to Nonlinear Static Analysis

C. Geometric Nonlinearity Effects

1. Select the Geometric Nonlinearity Effects to be included. Geometric


nonlinearity effects are considered on all elements in the structure. The
following options are available:

The large displacement option should be used for cable structures undergoing
significant deformation; and for buckling analysis, particularly for snap-
through buckling and post-buckling behaviour. Cables (modelled by frame
elements) and other elements that undergo significant relative rotations within
the element should be divided into smaller elements to satisfy the requirement
that the strains and rotations within an element are small.

For most other structures, the P-delta option is adequate, particularly when
material nonlinearity dominates. If reasonable, it is recommended that the
analysis be performed first without P-delta (i.e., use None), adding geometric
nonlinearity effects later.

x None
All equilibrium equations are considered in the undeformed
configuration of the structure.
x P-Delta
The equilibrium equations take into partial account the deformed
configuration of the structure. Tensile forces tend to resist the rotation
of elements and stiffen the structure, and compressive forces tend to
enhance the rotation of elements and destabilize the structure. This
may require a moderate amount of iteration.
x P-Delta and Large Displacements
All equilibrium equations are written in the deformed configuration of
the structure. This may require a large amount of iteration.
D. Load Pattern

One of the most difficult issues for pushover analysis is choosing the pushover load
distribution. During an actual earthquake, the effective loads on a structure change
continuously in magnitude, distribution and direction. The distribution of story shears
over the height of a building can thus change substantially with time, especially for
taller buildings where higher modes of vibration can have significant effects. In a
static pushover analysis, the distribution and direction of the loads are fixed, and only
the magnitude varies. Hence, the distribution of story shears stays constant. To
account for different story shear distributions, it is necessary to consider a number of
different pushover load distributions.

One option in FEMA 356 is to use uniform and triangular distributions over the
building height. Note that a uniform distribution usually corresponds to a uniform
acceleration over the building height, so that the load at any floor level is proportional
to the mass at the floor. Similarly, a triangular distribution usually corresponds to a
linearly increasing acceleration over the building height.
51
In ETABS the distribution of load applied on the structure for a given static nonlinear
case is defined as a scaled combination of one or more of the following:

x Any static load case.


x A uniform acceleration acting in any of the three global directions. The force
at each joint is proportional to the mass tributary to that joint and acts in the
specified direction.
x A modal load for any eigen or Ritz mode. The force at each joint is
proportional to the product of the modal displacement, the modal circular
frequency squared ( 2), and the mass tributary to that joint, and it acts in the
direction of the modal displacement.
The load combination for each static nonlinear case is incremental, meaning it acts in
addition to the load already on the structure if starting from a previous static nonlinear
case.

Add, modify or delete a Load Pattern for the static nonlinear case using the following
buttons.

x Add button. To add a Load to the Load Pattern definition, select the load
from the Load drop down box, type in the appropriate scale factor in Scale
Factor edit box, and click the Add button. If the selected load is a mode (only
available if mode shapes have been requested for the analysis), input the mode
shape in the resulting form and click the OK button.
x Modify button. To modify the scale factor for a load specified as part of the
load pattern, highlight the load in the Load/Scale Factor list box, edit the scale
factor in the Scale Factor edit box, and click the Modify button.Delete button.
To delete a load specified as part of the load pattern, highlight the load in the
Load/Scale Factor list box and click the Delete button.

Click the OK button to accept all of the changes made in the Static Nonlinear Case
Data form. Clicking the Cancel button means that none of the changes will be
accepted. Note that you must also click the OK button in the Define Static Nonlinear
Cases form to accept the changes.

Run the non-linear static analysis. Click the ANALYZE option, RUN STATIC
NONLINEAR ANALYSIS. During the analysis, sometimes there is a warning in
nonlinear analysis. You should stop the analysis and increase the number of null steps
and total steps in nonlinear static data form and again run the analysis.
A Practical Guide to Nonlinear Static Analysis

5.4 Results

x Check the pushover curve and capacity curve.

a. After the analysis, check the results by clicking on DISPLAY < SHOW
STATIC PUSHOVER CURVE.

53
b. When we click on SHOW STATIC PUSHOVER CURVE, the following
window appears.
A Practical Guide to Nonlinear Static Analysis

x Check the deformed shape of the structure at the performance point.

The performance point is the point at which the demand spectra and capacity
spectra intersect each other. At that point, we have to check if the structure can
meet the demand or not.

a. Next step is to check the number of steps at which the demand and
capacity curves intersect. At that step display, the deformed shape by
clicking on DISPLAY < SHOW DEFORMED SHAPE.

55
b. When we click on SHOW DEFORMED SHAPE, the following window
appears.
A Practical Guide to Nonlinear Static Analysis

c. In the previous window, set the case and step number and the following
window appears.

x Check the status of the internal hinges

Check the status of hinges to see if the structure can meet the demand or not.
Based on the hinge states and the failure mechanisms, the need for retrofit and the
type of retrofit can be determined.

The colour of hinges defines the status of hinges.

This building needs a retrofit to prevent the soft story from forming. Once
you have created a model, it is straightforward to modify it by adding new
elements in different places to test out potential retrofit solutions.

57
Sources of Additional Information
As the example in the previous chapter shows, nonlinear analysis is a powerful tool to
examine the expected behaviour of a building during a strong earthquake. The building
shown in the example needed a seismic retrofit, and a retrofit solution was selected by testing
a number of different retrofit options in ETABS. FEMA 547, Techniques for the Seismic
Rehabilitation of Buildings, which is available free of charge from www.fema.gov, provides
detailed information on potential retrofit solutions and how to select them. Also, the reports
on buildings analyzed as case studies during the Pakistan-US cooperative project provide
detailed examples of retrofit solutions for typical Pakistani buildings. These reports can be
downloaded from the GeoHazards International website at www.geohaz.org. Additional
detailed information about nonlinear analysis can be found in the NEHRP Seismic Design
Technical Brief No. 4, Nonlinear Structural Analysis for Seismic Design: A Guide for
Practicing Engineers, available free of charge from www.nehrp.gov.
A Practical Guide to Nonlinear Static Analysis

References

1. ETABS, User Interface Reference Manual. 2002, Computers & Structures (CSi):
California.

2. Federal Emergency Management Agency, FEMA-356: Prestandard and Commentary


for the Seismic Rehabilitation of Buildings. 2000: Washington DC.

3. American Society of Civil Engineers, ASCE-41: Seismic Rehabilitation of Existing


Buildings. 2006: Virginia.

4. Applied Technology Council, ATC-40: Seismic Evaluation and Retrofit of Concrete


Buildings. 1996: California.

5. Humar, J.M., D. Lau, and J.-R. Pierre, Performance of buildings during the 2001 Bhuj
earthquake. Canadian Journal of Civil Engineering, 2001. 28(6): p. 979-991.

6. Korkmaz, K.A., F. Demir, and M. Sivri, Earthquake Assessment of R / C Structures


with Masonry Infill Walls. International Journal of Science and Technology, 2007. 2:
p. 155-164.

7. Mondal, G. and S.K. Jain, Lateral Stiffness of Masonry Infilled Reinforced Concrete
(RC) Frames with Central Opening. Earthquake Spectra, 2008. 24(3): p. 701.

8. Saatcioglu, M., et al., The August 17, 1999, Kocaeli (Turkey) earthquake damage
to structures. Canadian Journal of Civil Engineering, 2001. 28(4): p. 715-737.

9. Taher, S.E.-D.F. and H.M.E.-D. Afefy, ROLE OF MASONRY INFILL IN SEISMIC


RESISTANCE OF RC STRUCTURES. The Arabian Journal for Science and
Engineering, 2008. 33: p. 291-306.

12. Murty, C.V.R., et al., AT RISK : The Seismic Performance of Reinforced Concrete
Frame Buildings with Masonry Infill Walls. 2006, Earthquake Engineering Research
Institute and the International Association for Earthquake Engineering: Oakland. p.
83.

13. Kodur, V.K.R., M.A. Erki, and J.H.P. Quenneville, Seismic design and analysis of
masonry-infilled frames. Canadian Journal of Civil Engineering, 1995. 22(3): p. 576-
587.