Vous êtes sur la page 1sur 32
ANSI/ASHRAE Standard 37-2009 (Supersedes ANSI/ASHRAE Standard 37-2005) ASHRAE STANDARD Methods of Testing for Rating Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment Approved by the ASHRAE Standards Committe on Juno 20, 2000; by he ASHAAE Board of Director on June 24, 2009; and by the American National Standards Insists on June 25,2008 ASHAAE Standards ae scheduled to be updated on a five-year cyclo; the date following the standard number 'sthe year of ASHRAE Board of Dtectos approval Th latatcosies may be purchasad from ASHFAE Cus tomer Service, 1791 Tulie Cire, NE, Alana, GA 20929-2205. E'mal: orders @ashrze.ong. Fax: 404-924 5478, Tdephone: 404-8%.8400 (wotdwide) otal ree 1-300-577-4723 (for orders in US end Canada) © Copyright 2000 American Sccity of Heating, Roigeraing and Ai-Cenditoning Enginoor, inc ISSN 1041-2506 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. 1791 Tullie Circle NE, Atlanta, GA 30329 wwwashrae.org ASHRAE Standard Project Committee 37 Cognizant TC: TC 8.11, Unitary and Room Air Conditioners and Heat Pumps PLS Liaison: Matt R. Hargan ‘Alberto A. da Rosa, Chair” Byron. Horak* Grea S. Bennett H. Michae! Hughes* Dany Denton ff Fiot’ A. Domanski BAEK Brian P Dougherty" ‘Arvo Lanaus “Denotes members cf voting siatus when the document was approved for publeation ‘ASHRAE STANDARDS COMMITTEE 2008-2000 Hugh F Crowther, Chair Jay A. Kohler Steven T. Bushby, Vice-Chair Carol E. Narrott Rebert G. Baker Nerle F McBride Michael F. Beda Frank Myers Donald L Brandt H. Michael Newman Paul W. Cabot Jarice C. Paterson Kenneth W. Cooper Douglas T. Reindl ‘Samuel D. Cummings, Jr. Lawrence J. Schoen K. Wiliam Dean Boggarm S. Setty Martin Dieryckx Boch R. Subherwal Rebert G. Doerr Willam F. Water Allan B. Fraser Michae! W. Woodford Nadar R. Jayaraman, David E. Knobel, BOD ExO Byron W. Jones ‘Andrew K. Bersiy, CO ‘Stephanie Reiniche, Manager of Standards ‘SPECIAL NOTE “This american Natonal Stancard (ANS) isa natonal voluntay consensus standard Gaveloped under ine auspes ofthe American. ‘Sosiay of Heating, Retigamting and Air-Coraitioning Enginaere (ASHRAE). Cangenous ie defined bythe Anencan National Standacla Insitute (ANS), of which ASHPAE is @ memter and whch has approved tis standard 2s an ANS, as “substantial agreement reacted by rect are mately affcte irtarest categores. This signifies the concurrence of mora tran a simple majory, but rot eacessary unanimity ‘Consensus requies that al views and objects be corsidered, and that an efor be made towaré their resoutin” Compliance with ris ‘Standards veluntary unt ard unless algal jarsdcton makes compliance mandatory trough legislation. "ASHEAE obiaine conaenove trough participation o tanatonal and tematondl mombore aesoctted saciotos, and public rvion. ‘ASHRAE Standards are psepared by a Project Commitee appointed specifically for the purpose of witing the Standard. The Projact ‘Commitee Chair and Vice-Char must be members ofASHRAE, whle cther commis members may ofa not bs ASHRAE memnbor, al ‘must be tachicaly quatfed in the subject ava of he Standard, Evaty effort is made to balance the conoemned inerests on all Project Committees. "Tho Assistant Droctor of Tochnolegy for Stardards and Special Proocts of ASHRAE should be contactodtor: ‘a. imarpretation ofthe contents ofthis Standard, anticipation in he next review ofthe Standard ©. aienng sonstuctve erucism tor mproving ie Stardara, cr permission to reprint portions ofthe Standard DISCLAIMER ASHAAE uses ts best forts to promulgate Standers and Guidelines forthe benefit of he puolicin ight of avalabl intormaton end ccepted dust practices. However, ASHRAE does not guarantee, erty, of assure the safety or performance of ary products, compenets, fr ystome testad installaa, or oparated in scocrance wih ASHRAE's Standatda or Guudalinas or that any tas condurtos unr fe ‘Standards or Guidelines willbe norhazarcous ora from rk. "ASHRRE INDUSTRIAL ADVERTISING POLICY ON STANDARDS |ASHRAE Standards and Guidlines are established to assst industry andthe public by offering a uniorm method of testing fr rating purposes by suggesting sa practic in designing and insaling equpment, by providing groper defintiors ofthis equipment ard by proving ‘thor informaton hatmay servo guid tho induct. The cretion of ASHE Standards and Gudoinosis determinedby the nocd for thom, ‘and contomancato then is conpltely volar. Inferring to this Standard or Guideline andin marking of equigment and in advetisng, no cam shall be made, einer staedor imple, ta te product has Deen approved By ASHAAE. © 2009, American Society of Heating, Reitigerating and Air-Conditioning Engineers, Inc. (wwwashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission. CONTENTS ANSI/ASHRAE Standard 37-2009 Methods of Testing for Rating Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment SECTION PAGE ee ne 3 DeHNHIONS enn enenennn eset seventeen 4 Classifications. 2 5 INSHUMENS nentnnetenianeniannstavinininantnininnannaneinnminanenan 8 6 Airfow and Air Diflerential Pressure Measurement AppArEtUS..novsnnen o eee 7 Methods of Testing and Calculation een ee severe 8 TeSt PrOCECUTES nnn sn a seosintnstnne 1B 9 Data to be Recorded 2 10 TeSt RESUS eonennereninntnntneniniinimininieniinntnniiininanennennnnces 11 Symbols used in Equations an. estan seventeen 12 Reference Properties and Data... tetris 18. REfSFENO2 eens nnnenaninnenennineninninttnntne seventeen BD Informative Appendix A:Classfications of Uritary Air Conditioners and Heat PumpS .a..venevewnseeneees 28 NOTE When addenda, interpretations, or errata to this standard have been approved, they can be downloaded free of charge from the ASHRAE Web site at http://www.ashrae.org. © Copyright 2009 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. 1791 Tulle Circle NE ‘Atanta, GA 30320 ‘www.ashrae.org All rights reserved. (This foreword is aot part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard, It has not been pro- ‘cessed according to the ANSI requirements for a stan ‘dard and may contain material that has not been subject ‘to public review or a consensus process. Unresolved ‘objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.) FOREWORD This isa revision of Standard 37-2005. This standard was ‘prepared under the auspices of the American Heating Refrig- ‘erating and Air-Conditioning Engineers (ASHIRAB). lt may be ‘used, in whole or in part, By an association or government ‘agency with due credit to ASHRAE, Adherence (s trcdly on a voluntary basis and merely in the interests of obiaining uni- form standards throughout the industry This version updates ‘the references section, superscripts references cited ia the text ‘and correc the erratum in section 7.7.2.1 1, PURPOSE 1.1 _The purpose ofthis standard isto provide test methods {or determining the conling capacity of unitary aircandition- ing equipment and the cooling or heating capacitis, a both, ‘of unitary hest pump equipment. 1.2 These test methods do not specify method of establish ing ratings that involve factors such as manufacturing tole ‘ances and quality contol procedures. 2. SCOPE 21. This standard applies to electrically driven mechani- ‘al-sompression tniary air condifoners nd heat pumps con ‘stig of one oF more assembles tha include an indoor ait coil(s), a compressor(s), and an outdoor coil(s). Where such ‘equipment is provided in more than onc assembly, he spa- rated assemblies ae designed to be used together. 22. This standard does not include methods of testing the fellowing (2) cooling cols or separate use () condensing units for separate use (©) room air conditioners (@) heat-operated unitary equipment (6) Viguid citing packages (8) rukiple indoor ar coils operating simultancously in heat- ‘ing and cooling modes 3. DEFINITIONS air, standard: dry ar having a mass density of 1.204 kgm? (QOTS Tye), ‘apparatus: 3s used in this standard, this term refers excl sively to test room facilities and instrumentation capacity, heating: the rate, expressed in watts (Btwn), ot ‘which the equipment adés heat to the air passing through it under specified conditions of operation. ‘capacity, latent cooling: the rte, expressed in watts (Btw), at which the equipment removes latent heat from the air pass ing through it under specified conditions of operation ‘capacity, sensible cooting:therate, expressed in warts(Btwh), at which the equipment removes sensible heat from the air ‘passing through it under specified conditions of operation. ‘capacity total cooling: the rate, expressed in wats (Btw), t ‘which the equipment removes heat from the air passing \yough it under specified conditions of operation, oil, indoor: the beat exchanger that removes heat from or adds heat to the concitioned space. «oil, outdoor: the heat exchanger that rejects heatto orabsorbs ‘heat from a source external tothe conditioned space. ‘equipment: as uscd in this standard, this term refers exclu sively to the unitary equipment to be tested ‘equipment, unitary: his term shall be defined as provided in Section 2 and Section 4 indoor side: that part ofthe system that removesheat from cr ‘adds heat to the indoor airstream, ‘outdoor side: that part of the system that rejects heat to or absorbs heat ftom a source extemal tothe indoor airstream, pressure, standard barometric: 01.325 kPa (14.696 psi). refrigerant, volatile: rerigerant that changes from the liquid tothe vapor state inthe process of absorbing heat. shall: where “shall” or “shall not” is used for provision, that provision is mandatory if compliance with the standard is, clsimed. should, recommended, or it 1s recommended: “should,” “recommended,” or “itis recommended!” are used to indicate provisions that are not mandatory but thet are desirable es a ‘good practice. 4. CLASSIFICATIONS Unitary equipment within the scope ofthis standard may be clasified as follows 4.1 Component Arrangement: (a) Units employing compressor(s), indoor air coils}, and ‘ouidoor coils) in a single package assembly. (b) Units employing compressor(s) and indoor coil(s) in one ‘or more assemble with romote outdoor eoil(s). {c) Units employing indoor coil assemblies, with outdoor oil) and compressor(s in one or more assemblies. 42. Method of Outdoor Coil Heat Exchange: (©) ax, (0) liquid ana (©) evaporative cooled condensing Note: Related Ai-Condltioning and Refrigeration Institute (ARI) classifications for unitary air conditioners and beat pumps are given in Tables A-I and A-2, respectively, in “Appendix A, and are illustrative bat not restrictive 5, INSTRUMENTS 5 Temperature Measuring Instruments, SL] All temperature measurements (with the exception ‘of dew point 2) shall be made in accordance with ANSUASHRAE Standard 41.1." S.L.2 Lused in determining the water vapor content ofthe air, dew point hygrometers shall be applied as specified in ANSV/ASHRAE Standard 41,6? and shall be accurate to ‘within 40.2°C (04°F). 5.1.3 Inlet air temperature measurements are to be taken ‘upstream of static pressure taps onthe inlet duct (installed), ‘Outlet air temperature measuraments shall be taken down ‘stream of the static pressure taps en the outlet. 52_ Refrigerant, Liquid, and Barometric Pressure Mea ‘suring Instruments 5.2.1 Pressure measurements shall be male with ene or ‘more of the following instruments: (@) liquid column (@) Bourdon tube gauge (©) electronic pressure transducer ASHRAE Standard 41.3° should be referred to for infor sation on the above instruments 52.2 Theaccuracy of the pressure measuring instruments shall permit measarements to within 42.5% of the reading. $23. Calibration of the pressure measuring instrument ‘shall be with respect toa deadweight tester or by comparison “with aliquid column, 5.24 In ro case shall the smallest scale division of the _pressuremeasuring instrument exceed two timesthe specified ‘accuracy, 53. Nir Differential Pressureand Airflow Measurements 53.1 The static pressure difference across nozzles and ‘velocity pressures at nozzle throats shall be measured with ‘manometets or electoaic pressure transducers that have been calibrated against a pressure standard to within 1.0% ofthe reading. The resolution ofthe device shall be equal to or less than 2.0% of the reading. 53.2 Duct static pressure shall be measured with one or ‘more menometers or clestranie pressure transducers that sre ‘accurate to within 22.5 Pa (£0.01 in. 10). 53.3. Areas of nozzles shall be determined by measuring their dismoters to within 40.20% in four places spproxi- ‘mately equally spaced around the nozzle in each of wo planes ‘through the nozzle throat, one atthe outlet andthe other inthe straight section near the radius. ANSUASHRAE Standard 37-2009 54 Flectrical Instruments $44.1 Electrical measurements shall be made with indicat- ing or integrating instruments $4.2 Instruments used for measuring the electrical power input fo fan motors, compressor motors, or other equipment _acovssories shall be accurate 10 within #2.0% ofthe reading. ‘Note: For an efficiency rating purpose, a more accurate mes ‘surement of the electrical power input may be required. 5.4.3 Instruments used for measuring the clectrcsl power input to heaters or other apparatus furnishing heat loads (see 77.1.2 and Figure 10) shall beaccursteta within +1.0%of the ‘quantity measured 4.1 Voltages shall be measured atthe equipment termi- ‘nals, Instruments used for measuring voltage shall bo accurate to within #1.0% of the reacing. 55. Volatile Refrigerant Flow Measurement 5.5.1 Volatile veftigerant flow shall be measured with an integrating flow measuring system that is accurate to within $1.0% of the reading. 56 Liquid Flow Measurement 5.6.1 Water and brine flow rates shall be measured with a liquid flow meter or quantity mater that is sccurate to within 51.0% of the reading. 5.6.2 Condensate collection rates shall be determined using a liquid quantity meter that is accurate to within +1.0% ofthe reading. 57 Speed Measuring Instruments 5.7.1 Spood measurements shall be made with a revolu- tion counter, tachometer, stoboscope, or oscilloscope that is accurate to within +I.09% of the reading, 58 Time and Mass Measurements 58.1 Time interval measurements shall be made with an instrument that is accurate 1 within 40.2% ofthe reeding, 58.2_Mass measurements shall be made with an appara- ‘tus thet is accurate to within +1.0% of the reading. 59° Volatilerefrigeraat mass composition measurements for ‘zeotropic refrigerants shall be made using an instrument that isin accordance with ARI Standard 700-95. 6. AIRFLOW AND AIR DIFFERENTIAL PRESSURE MEASUREMENT APPARATUS 61. Enthalpy Apparatus. Recommended configurations forthe test apparatus are provided below. In all cases, suitable ‘means for determining the dry-bulb temperature and water ‘vapor content of the air entering and leaving the unit and for measuring the external resistance to airflow shall be provided. 6.1.1 ‘Thearrangement forthe tunnel ai-enthalpy method is shown schomatieally in Figure I. An airflow meacuring “device is attached to the equipment air discharge (indoor or ‘outdoor, or both, as applicable). This device discharzes directly into the test raom or space, which is provided with suitable moans for maintaining the air entering the unit at the desiced wer and dry-bulb temperatures. 6.1.2 An arrangement for a typical loop ar-cnthalpy ‘method is illustrated in Figure 2. The unit is installed as it ‘would be for the turmel srrangement. The airflow measuring. view dissharge is connected to suiteble reconditioning equipment that is, in wr, connected to the equipment inlet. The resulting closed test “loop” shall be sealed so that air leakage at places that would influence eapacity measurements docs not exceed 1.0% of the test aieflow rate. The dry-bulb and wet-bulb temperatures of the ar surrounding the ©quip- ‘ment shall be maintzined to within =3°C (5°F) of tho speci fied indoor and outdoor conditions. 6.1.3 The arrangement for the calorimeter air mthalpy method is pictured in Figare 3. In this arangement, an enclo- sure is placed over the equipment, or applicable part of the equipment, under test. This enclose may be constructed oF any suitable moterial but shall be norhygroscopis end should be airtight and insulatd, It shouldbe lage enough to permit inlet air to culate fedly between the equipment and the cnelosurs, and inno cae shal the enclossrebe closer than 1S 2 (6 in) to any part o the equipment. The int tothe enlo- sure shouldbe remotely located fom the equipment inlet so 45 to cause circulation throughout the entire enclosed space. ‘An airflow measuring device is connected tothe equipment discharge. Dry-bulb temperature and water vapor content of the air entering the equipment are 1o be determined at the enclosure inlet. 6.14 ‘The room air enthalpy method arrangement is shownin Figure 4. An airflow measuring device is sttached to the equipment air discharge (evaporstor or condenser, as applicable) and then, in tum, connected to suitable recondi- tioning equipment. The discharge from the reconditioning apparatus provides ai othe testroom at the desired éry-bulb temperature and water vapor content 6.1.8 Thearaangements shown in Figures 1,2, 3, andre intended to illustrate various possibilities available and should not be constmued as applying specifically or solely to the types of equipment with which they are chown, However, fan enclosure as shown in Figure 3 must be used when the compressor is inthe indoor section and separately ventilated 6.1.6 Other means of handling the air leaving the airflow measuring device and supplyingair atthe proper conditions to the equipment inlet may be employed provided that they do not interfere with the preseribed means of measuring airflow rate, emperature, and extemal resisance and provided that they do not create abnormal conditions surrounding the cuipment. ! | (WITLI 1BNDOOR SIDE / i ‘TESTROOM =] TU gon { ; i] = FE jefey~ Figure 1 Tunnet air enthalpy test method arrangement. ANSVASHRAE Stncare 37-2100 wn eRe za (Neto t SE ee ||| oo emai cere, wi Ti eR yiles = etiio+ igure? Leop al enthalpy test method arrangement { 1 pe mena SSIS, INDOOR SIDE st "TEST ROOM Figure 3 Calorimeter alr enthalpy (est method arrangement. "ANSUASHRAE Sundar 37-2009 \ 1 {HNL gon [INDOORSIDE } TEST ROOM S\, OUTDOOR SIDE ‘TEST ROOM. se |- glyse soos in LS Ss | as & TBettie- “aa Figure Room air enthalpy test method arrangement, 62. Nozale Airflow Measuring Apparatus 6.2.1 As shown in Figure 5, the nozzle sirflow measuring apparatus basically consists of reveiving chamber anda dis ‘charge chamber separated by a partition in which one or more ‘nozzles are located. Air fiom the equipment under testis con- veyed via duet to the receiving chamber, passes through the ‘nozzle or nozzles, and is then exhausted to the test room or ‘channeled to the reconditioning equipment. 6.2.2 Thenozzle airflow measuring apparatus and its con- nections to the equipment outlt shall be sealed so that air Teakage does not excoed 1.0% of the airflow rate being mea- sured. 6.2.3 Tho conterto-conter distance between nozzles in ‘uso shall be not lesthan throo times the threat diameter of the largest nozzle, andthe distance from the center of any nozzle ‘to the noarest discharge or receiving chamber side wall shall ‘be not loss than 15 times its throat diameter 6.2.4 Diffusers shall be installed inthe receiving chamber located at least |. times the largest nazzle throat diameter ‘upstream of the partition wall, Diffusers in the discharge ‘chamiber shall be located atleast 2.5 times the largest nozzle ‘throst diameter downstream of the exit plane of the largest nozzle. 6.25 An exhaust fan, capable of providing the desired Static pressure at the equipment outlet, shall be installed in ‘one wall ofthe discharge chamber, ard 2 means shall be pro- ‘vided to vary the capacity of this fan, 6.2.6 Thestatic pressure drop across the nozzle or nozzles shall bemeasired with a manometer or anclctenic presse transducer One side ofthe ressue measuring device shall be ccomeced to four maniflded pressre tans installed within the roccving chamber The other side ofthe prssare meas. jing device shall be connected to four manifolded pressure taps. insalled-withn the discharge chamber. Aleratvey, the ‘oloity head ofthe airstream leaving the norzle er moles may be measured by a pitot tube as shown in Figure 5, but ‘when more than one nozzle isn use, the pitt ube reading ‘hall be determined fer exch noe 62.7 Recommendstions onhow to fbricate ndmanifol, the atc pressure tps, iPused in measuring ar volume rte, ‘ave provided in 6.5. Gudance on the placement of the static Pressure tapsand the poston ofthe effusion tae relative to the receiving chamber ines provided in Figure 12 of ANSU ASHRAE Standard 51.5 6.2.8 Means shall be provided determine the air density atthe nozale throat 63. Noses 63.1 The throat air velocity of any nozzle in use shall be rot less than 1S m/s (3000 fpm) or more than 35 m/s (7000 fm. 6.3.2 When norzles are consracted in accordance with Figure 6 and installed in accordance with 6.2 and 6.3, they may he used without calibration Ifthe throat diamtr is 25 cm (10 in.) or larger, the coefficient of discharge (C) may ANSVASHRAE Standard 37-2008, DIFFERENTIAL NOTE: pIFFUSION parFLES PRESSURE [4 SHOULD HAVE UNIFORM. MEASUREMENT PESFORATIONS wth APPROX fore =REE AREA RECEIVING 1 een naS| DISCHARGE CHANBER J a L ai EXHAUST FAN an ——> now 8! a piror TuBe —] | etionay Foam Nerloainw memories peat veasumsdtabe 099, Formals smal tan 25cm (10) is dietr tov ucluod x pecid in 63.30) -— ted. Adon infrmaten and ulane on erating tbe ccticgfdichat rol n ANSIASHRAE Sur {= Axes OF dard SI.) (Appendix F of ANSUASHRAE Standard 51, for 2 crample, Shows the rave poset fr Stalag he me confet of dchage) Where a mor poise cosh desired, the nozale should be calibrated. 633. For airflow nozzles having a throat length to throat gp) diameter ratio of 0.6 (see Figure), the nozzle default cocthi- pny cient of discharge shall be calculated as follows! DB THROAT SECTION For Reynolds numbers (Re) of 12,000 and above, the Reynolds number is calculated as follows: ELLIPTICAL APPROACH igure 6 Construction of a nozzle ‘The dynamic viscosity (1) of gascous air behaving as an ideal gas at moderate pressures and temperatures is calculated using the following equation: w= (17234 00481,)* 10% "7 where jis expressed in kg/m and fy in °C. ~ (Sc FE} m0) wy [ b= (1190-+00181,)% 107 ] where Fis expressed in units of Rimi and D in unis of inches, here Lis expressed in Ibm -s and, in °. ANSUASHRAE Sunda 37-2008 6.4 External Static Pressure Measurements 641 General 641.1 External stic pressure shall be measured by @ ‘manometer oranelestronie pressure transducer 641.2 Static pressure taps, where used shouldbe fab- ricated and manifolded as described in 6.5 642. Units witha Fan and a Single Outlet 642.1 Whore an extemal stati pressure measurement i required a short plenum chamber shall bs atfachod tothe outlet ofthe discharge side of te equipment. This plenum shall have cross-sectional dimensions equal tothe dimensions Of the equipment outlet and shall dischage into an airflow roasting doves (or nto aatable camponing doves when a dre’ arfow measurement is not employed, se7-2.2).One side of the pressure measuring device shall be connected to oar maifded pressure tps inthe discharge plenum. Those tapsshll be positioned ditance af twice the mean goomet= rie cross-sectional dimension fom the equipment oie, a8 shown in Figure 7. 6422 I pace within te test room permits, an inet duct connection shoul be installed. If sed, the inlet dust shall have eros sectional dimensions equal vo those ofthe Cquipment and should otherwise be fareatd as shown by the setups ven in igures 7 en Te, One side ofthe pressure measuring device described in 6.4.2.1 shall be connected to far manifeldod pressure taps intlld within the inlet duct. fino ine duct eomecton is employed, however, one side of the pressure measuring device desorbed in 64.1 shall be open tothe surrounding atmosphere. 64.3. Units with Fans and Multiple Outlets and/or Mulivaporators 643. Units with muitiple discharge outlet duct con- nections or mali-evaporaor systems shall hae a shor ple- tnum conforming to Figue Ta atached fo each outlet. Each plenum shall discharge into a ingle common duct section. IF fir volume rate sto be measured cect then this duct seo- tion shall discharge into an sirflow measuring éevice. For the purpocs of oqualizing th stati pressure in eash plnam, an {djtalerestictr shall be located inthe pane where each plenum enters the common duct section, Exteral static pres sure in each plenum shall be measured as specified in 6.4.2. “Mulipe blower uit employinga single ciacharge dct con- nection fangs shall be tstee witn a single ttle dustin accordance with 642. Any other tes plenum arrangements shall not be used excop te smute duct designs spocifica’y fevommended by tie equipmeat manaictarer. 644 Units without a Fan 644.1 Forindoot col sections tat donot incorporate a fan, the inlet and outlet duct connections hall have cros-e=- tional dimensions aqual to the duct flange ofthe suppicd oF recommended coil enclosure 6442 Tho irstaticprossure drop skal be measared as shown in Figure8, One side ofthe presure measuring device Shall be cometed fo foar manfoided pressure tsps te out Jet dace wi the other side ofthe pressure measuring device bing connected to four manfeldod pressure taps inthe nt. | TO AK HOW MEASURING APPARATUS MANONETER PuNU Abe = oun BinleNSIONS ‘igure 7a External static pressure measurement. Note: Th following tatoments apply to Figures 7 and 8. For circular duets, substitute 07/4 for © x D and RD2/4 for Ax B. ‘The length of the inlet duct, 15 /E¥B. is a minimum Aimension. For more precise results, ase 4/C*D “The inlet and cult tps shall be installed relative othe col inlet and outlet, respectively, as shown i Figure 8 65 Recommended Practices for Static Pressure Measurements 651A tap shouldbe located at the conic of each face of «cach plenum rectangular, et four evenly eisbuted tcs- tions along the perimeter of an oval or round plenum. 632s recommended that the pressure taps consis of (6.25 mm (025m) diameter nipplessodere tothe oaterpl- sum surfaces and centered over mia (0.040 in) diameter Toles through the plonam. The edges o thor los shoulé Bo ffee of burs and other surtice ireglaries Static pressure aps should he manifold using one of the two recommended connection options shown in Figure 9 66 Duct Inulaton and Sealing Requirements 6.6.1 The plenum(s) and duct section(s) shall be sealed to prevent sir lakage, particularly atthe connestons to the ANSVASHRAE Star 37-2009 Nore: ror cincetan nucts supsrrure Bron (a x 9) 08 (6 x 0) Figure 7) External static pressure measurement. equipment and the airflow measuring device. The plenum(s) snd the duct section(s) shall be insulated to minimize heat leakage between the equipment inlet or outlet andthe temper- ‘ture measuring instruments. Duc losses may be caleulated using suitable conduction factors, inside air and outside ambi- ent temperature diffrence, and the total dict surface area ‘between the unit and the temperature measurement lovation. 7. METHODS OF TESTING AND CALCULATION Standard Test Methods. The following five test meth- ods for measuring space conditioning capacity are covered in this standard (2) Indoor air enthalpy method (see 73) (©) Outdoor air enthalpy method (see 73) (©) Compressor calibration method (see 74) (@) Reftigerant enthalpy method (see 75) (©), Ouidoor liquid coil method (sc° 7.6) Inadeition, an alternative tothe method described in 6.2 and 6 3 for messuring indoor airflow rate is described in 77. Section 7 describe: a method for measuring cooling condensate and determining latent cooling capacity. Use of | 7.7 and 7.8 is not required except when testing equipment having 2 rated cooling capacity of 40 KW (135,000 Buu/h) or {greater where the indoor air enthalpy method is not used. 2. Applicability of Test Methods 724 Simulianeous tts using the indoor sir enthalpy ‘method (Group A in Table |) and one other applicable method, from Group B in Table 1 shall be conducted when testing equipment rated as having a total cooling capacity thats less than 40 kW (135,000 Bru/h) 72.2. Whentesting equipment rated as having total cool- ing capecity of 40 kW (135,000 Bu/h) or greatr, at east one of theapplicable methods from Table 1, Group A or Group B, except the Outdoor Air Enthalpy Method, shall bo used. For cases where an air-source heat pump is to be tested and one or ‘more heating ecpacity tests in the defrost region are to be con- ducted (ee 88), the indoor air enthalpy method must be used. ‘When the indoor air enthalpy method is nat used, indoor air- flow rate shall be determined from the space conditioning capacity test using the indirect method described in 7.7.1.2 2 NOTE: FOR CIRCULAR DUCTS sunstirute EP ror (A x B) OR (C x D) Pigure7e External static pressure measurement. » ANSUASEIRAE Sader 37-2009 ‘TO AIR MEASURING APPARATUS t ‘ourter bucr. qd r os Gressune TAPS fressune raed | ‘A&B = OUTLET DIMENSIONS (AD=.NLET DIMENSIONS Figure Ar state pressure drop measurement for coil ‘onto fa) and 7.7.3 and, for cooling tess, latent cooling capacity shall be detemined by measuring condensate as deseribed in 78, 7.23. The methods describodin this standard may be wed to test unitary equipment not covered in Table 1. However, proper consideration must be given in the capacity caleula- tions to adhere to energy balance principles. 7.3. Indoor and Outdoor Air Enthalpy Methods 7.31 Space conditioning capacity is determined by mea- suring airflow rate and the dry-bulb temperature and water ‘vapor content of the air that enters and leaves the coil, Air enthalpies shall be determined in accordance with ANSI ASHRAE Standard 41 1.32 The outdoor air enthalpy method may be used when testing air cooled equipment that is rated as having a total cooling capacity less than 40 KWW (135,000 Buw/h) and that ‘doesnot use remote liquid chillers. Use ofthis method, how- ever, is subject to the additional requirements and apparatus arrangement limitations specified in 8.6 and, ifthe equipment uses a remote outdoor coils), 10 the line loss adjustments described in 7.33.4 and 7.34.4. 7.33 Cooling Calculations 1 1 Total, sensible, and latent indoor cooling capac- used on test data collacted sovonding to the indoor ait ANSUASHRAE Standard 37-2009 ‘Migure9 Recommended connection options for static pressure fps, enthalpy method, shall be calculated using the following ‘equations (see note below): yas) tos + 180s, 024+ 0440") pa = OOS + 180507, o2s+oaun, and Note: the latent indoor evoling capacity is a function ofthe latent beat of vaporization fig) of water in73.3.l equations for ‘isthe hg sorresponding 91°C STF) is sed: 2.47 10°) (1051 Buatbm). Also, theenergy associated withthe leaving condensate snot inchidad caus Ht impacto nat eapacty nagligble, TABLE 1 Applicable Test Methods |Greup 4% Group ne Secon Rene m= [afm] 7s | te | arate ipa conennt [Nori ae| ilo ir | Onto [Conmscr|Reien| Owe | — coe ‘Tomsmcns)" |"temaumecsin | mt’ | say” | cteses | ‘sms | cat | conn ant cycle ‘method | method! | mothed® | method‘! | mothod® | indirect airflow ‘Single package unit Aircooled x x xt x Fapatneyewtel | x x awroaes x fx ‘Remote outdoor heat Air cooled | x x xt x croup cnn: [Fama > cours Gagne |x x x Water cooled x xt x x Renacoaivorhat | arenes [| x |x |x| x x scares ome Frere | 8 xx x Wakraet [x x [ox x ‘Remote outdoor heat Aircooled x x xt xt x cscge ae = To Rpatheventsl| x a: x pressor within space |< a ‘Water cooled x xe xt x x 1 Farepipearring are cog cpaiy kt 1 (185500 Bel) apy hl demi ing ine a ey bala pani [tng an th opted fom Gm 1b Eeccqpencarings dency ca EW (1500 Bi ae reer ott one reentrant ofthe (Scriven iar 7 1 rou Fer cue whee hdr atiow cs mot Unc meson tno heer a ethyl tele ‘poten pechadis 72 halts moked ‘appiatleonyfeqtent ang aed slg capaci awh AOLW (35000 Ba) {hashes ob ES ot apie cnn ind Wine ny “ete 07 61.2 Metals fompmmr i weiter si Net ppc atannedcadborwner clo selina sno ri crpreurnunnelate ds eet by dor ari) 7, vas Fpalteaas) 600,65 (laa) a enna z 341g, = ete . YW) [ ceryiooy2mi2 Oni > ny ve Wy Spy = 1008+ 18057, 7.33.2. Total indoor cooling copocity based on test data [= o2s-osuw, collected acconding tothe outdoor air enthalpy method shall, bre calulated using. one ofthe fllowing equations: 7.33.3 When the indoor or outdoor air enthalpy method is used, the total and sensible cooling espacitice shall be ‘adjusted for duct losses. The duct loss adjustment shall be ‘added to the total and sensible cooling capacities. The duct Toss adjustment shall be calculated 2s follows: [fusing the indoor air enthalpy testmethod and the quip- ] ‘ment indoor section is located in the indoor test room, then. sae, 0b vl) tee = WA daca a If using the outdoor air enthalpy method and the equip- ‘or forair-cooled equipment that does not re-evaporate drained Sener ree epee cae ae ‘condensate from the indoor coil, (Grosso = WAdect gl lot ~teo) ae Poke. tes 13) =e [fusing the indoor air enthalpy testmethod and the equip- vas) ‘ment indoor section is located in an outdoor test room, then Gowns + WA drollae 1.334. A tine loss capacity adjustment shall be applied if using the outdoor air enthalpy method as the secondary ‘method and if the adjusment is needed to obtain the enerey Inalance specified in 10.12 (For equipment having. a rated 1+ 0.005309", ‘atl + 79.80,AnL 063003044 LTD.A013 () For insulated lines, 4,= (092s osierny fale (oss +006crny nf a1*)0 ‘The temperature difference Atis defined asthe difference ‘between theaverage reftigerant temperature and the surround ing ambient temperature 74.4 Heating Calculations When Using the “S” Test Method of Sestion 8.8.2 7.34.1 The total heating capacity based test data col- lected according to the indoor air enthalpy method shall be ‘calculated using the following equation: 2) 0 nf pall ‘where c,, 8 calculated as specified in Section 7.33.1 and. mm 7.34.2 Thetotal heating capacity based on test data col- lected as described in the outdoor air enthalpy methed shall be caleulated using. Qatar hae). 0+) WW 4.34.3. Whenthe indoor or outdoor airerthalpy method is used, the total hesting capacity shall be adjusted forthe duct losses. The duct Joss adjusiment shall be calculated as spec- ified in 7.3.3.3 and then subiracted algebraically (Le, subiract toc if itis postive and add gia if it is negative) from the Iheating capacity determined using the indoor or outdoor air ‘enthalpy method. 7344 Aline loss capacity adjustment shall be applied if using the outdoor sir enthalpy method as the secondary ‘method and if the adjustment is needed to obtain the energy balance specified in 10.1.2 (For equipment having 2 rated ‘cooling capacity less than 40 kW [135,000 Btw). The line loss capacity adjustment specified in 7.3.34 shall be sub- ‘tracted algebraically (ic. subtract the 4,’ that are pasitive sand add the g's that sre negative) fiom the capacity deter ‘mined using the outdoor air enthalpy method, gi. 735 Heating Calculations When Using the “T” Test Method of Section 8.8.3, 734.1 For equipment in which defrosting occurs, an average heating capacity corresponding to thetotal number ‘of complete cycles shall be determined. If a defrost does not occur during the data collection interval, an average heating capacity shall be determined using data from the ‘entire interval. 73.82 Average space heating capacity shall be deter- ‘mined as follows: Lmioat tT), +H) anew ‘where ¢,_, is calculated as specified in Section 7.3.3.1, WW Way and T= [ugo-4 080 Forheat pumps that automatically cycle offthe indoor fan ‘during a deffost cycle, the quantity £,3(t) ~ f(t) shall be assigned as zero during the off interval. The elapsed time “while the indoor fans off shal be included as part of the total test time (Le, 12 ~ 7) that is used for evaluating average heat- ing capacity. 74 Compressor Calibration Method 74. General Description TAA For the compressor calibration method, total ‘cooling capacity or hesting capacity is determined. follows: (a) For cases where the superheat of the refrigerant leaving, the evaporator is 3°C (5°F) or higher, capacity shall be ‘evalusted by determining refiigerant flow rate and the ‘hangs in refrigerant enthalpy between the inlct and out let ofthe indoor section or indoor side of the equipment. Refrigerant flow rate shall be deduced based on prior ot ‘subsequent calibration of the compressor under identical ‘operating conditions: the same compresscr auction and. discharge pressures and the same suction temporiture. As described in Section 6 of ASHRAF Standard 23,7 compressor calibration may be achieved using ether ane ofthe calorimeter methods or one ofthe flow moter methods. (®) For cooling mode tests wre the superheat of the refiige rant leaving the evaporator is less than 3°C (S°F}, cool- ing capacity chal be dstomnined by eondustng o ssparsts vaporatorype calorimeter test where the compressor is ‘operated under the same test conditions as encountered {orth equipment test (©) For heating mode tess where the superheat of the refiige ‘rant leaving the evaporator is ess than 3°C (SY), heating capacity shall be dotermined as described above in (a) with the additional stipulation that rffigerant flow rate shall be deduced based on compressor celibrations con- ducted using a condonser-type calorimeter. 742 Refrigerant Properties Mensurement 7A.L1 With the equipment operating atthe desied tast conditions, the temperature and pressure of the reffigerant Teaving the indoor section or sid, entering the indoor section or side (heating mode), entering the expansion device (eool- ing mode), and entering and leaving the compressor shall be measured. For cases where the indoor air enthalpy method is also conducted, data used to calcalate capacity according to ‘the compressor calibration method anc the indoor sirenthalpy ‘method shall be collected over the same intervals 7422 On equipment not sensitive to reffigerant charge, pressure measuring insiruments may be tapped into the refrigerant lines provided that they do nat affect the total ‘charge by more than 0.5% 7A.23. On equipment sensitive to refrigerant charge, preliminary test is required prior to connecting any pressure _gatges or beginning the first oficial test. In preparation for this preliminary test, temperature sensors shall be attached to ‘the equipments indoor and outdoor coils. The scnors shall be located at points that ao not affected by vapor saperheat or liquid subcooling. Placementinear themidpoint ofthe ovil, at atetum bend, is recommended. The preliminary test shall be conducted us described in8.7 withthe additional requirement ‘that the temperatures of the on-coil sensors be included with ‘the ragularly recorded dats. After the preliminary testis com. pleted, the refrigerant shall be removed from the equipment, And the needed pressure gauges shall be installed. The equip ‘ment shall be evacuated and recharged with refrigerant. The ‘test shall then be ropested. Once steady-state operation is achieved, reffigerant shall be added orremoved until 3s eom- ‘pared to the average values from the preliminary tes, the fol- lowing conditions are achieved: 1) each on-col temperature sensor indieaies a reading that is within =0.3°C (05°F), (2) the temperatures ofthe refrigerant entcring and leeving the compressor are within 42°C (3°F), and (3) the refrigerant temperature entering the expansion dovice is within =0.5°C (10°F). Once these conditions have been achieved over an interval of at least ton minutos, refrigerant charging equip- ‘ment shall be removed and the firs! ofthe official tests shall be initiated. TAZA Reftigerant temperatures shall be measured by ‘means of thermocouples or equivalent devices that are prop erly attached to the lines at appropriate lecations. 7425. No instrumentation shall be removed, replaced, or otherwise disturbed during any portion of « complete capacity test 7A26 Temperatures and pressures of the refrigerant ‘vapor entering and leaving the compressor shall be measured st eppraximately 25 em (IU in.) from the compressor shal. If the reversing valve is included in the calibration, these mea suremgnts should be taken on the lines to the coils st approx imately 25 em (10 in.) fom the reversing valve 74.3. Compressor Flow Rate Calibration TASL. Refiigerant Mow rate shall be determined based on separate calibration tests condacted on the same compres sor as used by the equipment under test. For cases where the superheat of the refrigerant leaving the eveporator is 1°C (GF) orhighe, the calibration tests shall be conducted sing ‘one of the applicable methods specified in ASHRAE Stan dard 23.” For cases where the equipment is heating and the ‘refrigerant superheat leaving the evaporator is less than 3°C (6), however, the condenser calorimeter method described in ASHRAE Standard 23” and ANSUASHRAE Standard 41.9 shall be exclusively used to determine retigerant flow rate, Refrigerant flow rate calibration tests are no! applicable for cases where the equipment is cooling and the refrigerant supesheat leaving the evaporator is less than 3°C (S°F) (see 7.4. insted), 7432 Calibration tests shall be performed with the compressorandreversing valve (where used) atthe same smbient temperature and air pattern ax in the tested equipment 7.44 Cooling Capacity Secondary Test for Equipment, When Tesied, Having a Suction Superheat Less than 3°C °F) TAAL For cooling mode tess where the supetheat of ‘the refrigerant leaving any evaporatoris les than 3°C (S°F).a separate test using an eraperstor-ype calorimeter shall be conducted. ‘The three evaporator-ype calorimeters that may ‘bo used are |, Socondaryrefigerant calorimeter 2. Secondary Maid calorimeter 3. Primary reftigernt calorimeter ‘The separate calorimeter test shill be conducted as spee- iffedin ASHRAF Stancard 27” and ANSUASHRAF Standard 41.9% For these particular calorimeter tests, adherence to the requircments given in Sections 7.224, 7.225, 8224, 82.25, 92.23, and 9.2.2.5 of ANSUASHRAE Standard 41.9 shall be waived. 7442. In order to conduct the follow-up calorimeter test, knowledge ofthe following parameters ftom the original cquipmeattest are required: the evaporator saturation temper sture oF prossure and refrigerant tempersture leaving the evaporator. The condenser saturation temperature or pressure from the original equipment test should also be recorded. 7A.4.3 Using the results from the evaporatortype calo- rimoter tes, total cooling capacity shall be calculated as spec- iffed in 7.4.5.2 Cooling Capacity When the Equipment Suction Superheat I 3°C (S°F) or Higher TA.S1 For tests in which the evaporator suparhoat is 3°C (5°F) orhigher, otal cooling capacity shall be calculated as follows tie = Ml Mpg ME, witty )-34 1d where fez, and Fare measured duringthe equipment tost, ‘and w, is determined based on prior or subsequent compressor calibration tests and refrigerant property measurements made during the equipment test 7AS2_ For tests in which the evaporator superheat is less than 3°C (SF), taal cooling capacity shall be calculated as follows: Ge = Me Ug) E; jt UA 341z ‘here Fis measured during the criginal equipment test while Go Ug ty, nd 4, are all measured daring the subsequent ‘evaporaior-type calorimeter test described in 7.44. ation Method Caleulations— 74.6 Compressor C: Heating Capaci 74.6.1 Total heating capacity shall be caleulated as fol- lows: Hg MM —Mad fly) hyp) + TAME where fi, /2,and &; are measured duringthe equipment test, and, is determined based on priororsubsequent compressor calibration tests and refrigerant property measurements made during the equipment test 7.5. Refrigerant Enthalpy Method TSA General Description TELL In this method, espacity is determined from the refiigerant enthalpy change and flow rate. Enthelpy changes are determined from measurements of entering and leaving pressures and temperatures of the refrigerant, and the flow rite is determined by a suitable flow meter inthe liquid Inc. ‘With the equipment operating at the desired test conditions, the temperature and pressure of the refrigerant leaving the indoor section or side and sther entoring the indoor section or side (eating mode) or entering the expansioa device (cooling mode) shall be measured. For cases where the indoor air cathalpy method is also conducted, dats used to caleulato capacity as described in the refrigerant enthalpy method and the indoor sir enthalpy method shall be collecied over the same interval, ANSUASHRAE Sirdar 17-2009 78.1.2 Thismethod may be used for tests of equipment in which the refrigerant charge isnot critical and where nor- ‘mal insiallation procedures invelye the ficld connection of refiigerant lines. 781.3 This method shall tbe used for tests ia which the refrigerant liquid leaving the low meter is subcooled less than 2°C (3°F) or for tests in which any instantancous mea- surement ofthe superheat ofthe vapor leaving the indoor sec- tion i less than 3°C (S°E). 782 Refrigerant Flow Measurement $2.1 Therefrigerant flow rate shall be measured with an integrating type flow meter connecied in the liquid line Uupsircam of the refrigerant control device. This meter shall be sized so tha its pressure drop does not exceod the vapor pres- sare change that a 2°C (°F) saturation temperature change ‘would produc 7.8.2.2 Temperature and pressure measuring instr ‘ments and a sight glass shall be iasalled immediately down- stream of the meter to determine if the rfiigerant liquid is adequately subcooled. Subcooling of 2°C (3°F) and the ansence of any vapor bubbles inthe liquid are considered ade- quate, tis recommended thatthe meter be installed at the bot tom of a vertical downward loop in the liquid line to take vantage of the static head of liquid thas provided. 78.23 Attheend ofthe tes, a sample ofthe circulating reffigerant and oil mixture should be taken from the equip- ment and the percentage of oil measured in accordance with ANSVASHRAE Standard 41.4. The total indicated flow rate should then be comrested for the emount of circulating oil, especially ifthe refrigerant enthalpy method is being used as the secondary method and the flow adjustment is needed to ‘comply with 19.1.2. 7814. For ystems using zsotropic refrigerants sam ple of the superbested vapor reftigerant should be removed while the unit is running in order io conduct a composition analysis, The refrigerant propertics should be adjusted based ‘on the measured composition using an established refrigerant property database. Such adjustments should be made espe cially ifthe reftigerant enthalpy method is being used as the secondary method and compliance with 10.1.2 is net other- wise achieved. 783. Refrigerant Temperature and Pressure Measurement 7.54.1 The temperature and pressure ofthe refigerant centering and leaving the indoor side oF the equipment shall be ‘measured with instruments in accordance with Section 5, TSA Refrigerant Enthalpy Method Calcutations— Cooling Capacity 754.1 Total cooling capacity shall be calculated as follows: 43 = EV lla) By = laa) F; [= 2PF (aA s)-341E, = 4m, (8,2) 341] TSS Refrigerant Enthalpy Method Caleulations— Heating Capaci 7581 follows: Total heating capacity shall be calculated as Bust — PF lla hg) +E, 2W lig bya) +E, FP, J BALE, = 20 (“Mg ) 2341] 7.6 Outdoor Liquid Coil Method 761 General Description 7.6.1.1 In this method, total cooling or beating capacity is datermined from measurements of the outdoor coil liquid ‘temperature change and flow rae 7.6.1.2 This method may be used for the test of equip ‘ment that uses.a liquid (e 2, water) as a heat sink or source. “The method may be used For factory-assembled packaged equipment, The method may also be used to test equipment with 2 remote outdoor col ifthe remote colli insulated or if the manufacturer recommends insulating the coil with the equivalent of not less than 25 mm (1.0 in.) of glass sibrous insulation. This methodmay only he wsed where the compres- sor is ventilated in the indoor airstream or is in an indoor closed compartment that isnot ventilated ors insulated in the same manner as described above forthe outdoor coil. 76.2 Liquid Flow Rate Measurement 7.6.2.1 The outdoor col liguid flow rate shall be mea sared witha liquid quantity or flow meter in accordance with 56. 7.63. Temperature Measurement 7.6.3.1 Entering and leaving liquid temperatures shall ‘be measured with insinaments in accordance with 51a the equipment connections. TSA Outdoor Liquid Coil Method Calculations — Capac 7.6.4.1 Total cooling capacity shall be calculated as follows: Gee = Mpls tn) Ey Emig {tefn) 341 765 Outdoor Liguid Coil Method Calealations— Heating Capacity 7.6.8.1 Total heating capacity shall be calculated as follows: Ihe = ep tes tad Fy Fw, (tn—ty)-SA1E,] 76.5 Pump Power Considerations 7.6.6.1 The total power input term, Ey inthe equations above (in Sections 7.6.4.1 and 7.6.5.1) shall include the mea- sured power input to the pump only if the pump is located ‘between the inlct and outlet water temperature sensors, ic, between fp and fs 7.6.7 Interconnecting Tubing Adjustment 7.671 For equipment with a remote outdoor coil, allowance shall be made inthe capacity calculations for heat gains or losses through the interconnecting tubing (see 7334). TL Aisflow Rate Mens TL Measurement Methods According to Rated Cooling Capacity TTL For equipment having a rated cooling capacity less than 40 KW (135,000 Btw/a), the indoor airflow rate shall be measured using the nozzle airflow measuring appa- satus described in 6.2 and pictured in Figure 5. The appara {us may also be used to measure the sirMlow race through the outdoor coil, which isneeded, for example, if using the out- door air enthalpy method to provide the secondary capacity ‘measurement. The airflow nozle(s) that is used shall be selected and applicd in accordance with 63 and Figure 6, The airflow rate shall be calculated as specifiog in 7.7.2. igure [2 of ANSI/ ASHRAE Standard 51° should he referred to for guidance on the placemen! ofthe static pressure taps and the postion ofthe diffusion baile (settling means) relative to the chamber inet Deviations fram the specified test setup shall be allowed nly ifsuch deviations are described in ANSVASHRAE Standard sus 7.7.2. For equipment having a rated capacity of 40 kW (135,000 Btwh) of higher, the indoor airflow rate may be ‘msasured as described in 7.7.11. For eases where a Section 6.2 nozzk aitflow messuringapparstus not used and eapac- ity is determined using one or more ofthe below listed test sthods, airflow rate shall be determined indirosty. Indirect ddecermination shall be achieved by using the calculated capacity or by measuring the dry-bulb temperature and water ‘vapor content of the ar that enters and leaves the indoor coil (see 7.73). (a), Compressor calibration method (b) Refligerantenthalpy method. (€}, Outdoor licuid coi! method [As a third option, airflow rate may be determined using the modified airflow measurement apparatus shown in Figure 10. For this thin option, the airstream is heated by a measur fable amount and the increase in ar dry-bull temperatare is ‘measured. The modified airflow measurement apparatus is located downstream of the static pressure taps, the dry-bull temperature sensors, and the insrumentation used ia deter= ‘mining the water vapor content of the outlet ait. Airflow rate shall be calculated as specified in 7.7.4 when the modified airflow measurement apparatus Is used. 1.7.2. Calulations Nozzle Airflow Measuring Apparates 5.72.1 The airflow ratethrough a single nozzle is caleu- lated by the following equations: Ons = Ay 2PM 097A, tr 7759¢4, 2 where Recewina |} HEAT SOURCE 3 | ascnanoe Bit Cease Bit ge fl ok min BEL min iam | osm wen | 1st | ts Figure 10 Modified airflow measurement apparatus. ‘CHAMBER ! i} we attr gi es ted SE oh a a Notes for Fgre 1 1. Airmixing and temperature measurcmeat shall be in accerdance with ANSUASHRAE Standard $11.) 2 Heat loss fra the enclostre sll be less than 1.0% ofthe heat input to he eat source. 5. Minimum temperature rise (fs ~ 2) 4105 te Rea source shall De 10°C (18°F). 101.3254 9 THEW, ~ PFW) be, 29.92% py ] Prin 7am) 7.7.22 Whenmore than one nozzle is used, the total air- fw rate isthe sam ofthe low rates ofthe individual nozzles calculated in accordance with 7.7.2.1. 7.1.2.3 Airflow rate, expressed in terms of standard air shall be calculated as follows: 2, Qui o,= St = On Tam, Tana, +H) 2, Qui DOTSY, oars + W. 77.3. Caleulations—tndirect Determination of i flow Rate 7.7.31 When altflow rate is determined indirectly in accordance with 7.7.1.2, then airflow rate shall be evaluated using the following equations: For Cooling: For Heating: ANSUVASHIRAE Standard 37-2009 Sin Fars) 4.732. Airflow rate, expressed in terms of standard air (Qj) shall be calculated as specified in 7.7.2.3, where vy and Hy shall be evaluated based on the indoor coil entering air Property measurements, i. assume vq =Yy and Wy= WW}. 7.74 Calculations Modified Airflow Measurement Apparatus 7.74. When the modified airflow measurement appa- satus described in 7.7.1. is used, airflow rate shall be caleu- lated as flows: @ ba] where 's\~ TOS FIRS NT, Ta) “all 4 [ warecaatina, The rate of energy added to the air, dyr shall be deter- ‘mined as follows (@) Ifelecricrohost is used: Ginn power input to hester(s) [= power input t9 heaters) x 3.41] () Iesteam coll rebeat is wsed: ri watt, hea) 7.742. Airflow rate, expressed in terms of standard ait, shall be calculated as follows To [mtn 4] 78 Cooling Condensate Measurement 7.8.1 For equipment whose indoor airflow rate is deter ‘mined indirectly in accordance with 7.7.1.2 and 7.73 during, ‘cooling mode tests, the Istent cooling capacity ofthe equip- ‘ment shall be determined from measurements of the conden- ‘sate flaw rate, The drain connection should be trapped to stabilize condensate flow. 782. Caleulations 7.8.2.1 Latent cooling capacity shall be calculated as follows: tng 247 108, [- 1061 wg) 182. a follows: ‘The semsible cooling capacity is then calculated sci ~ Gi Mes where dey OF gic may be substituted for gy (refrigerant ‘enthalpy method) if capacity is determined using sither the ‘outdoor Tiguid coll method or the compressor calibration ‘method, 8, TEST PROCEDURES 8.1 Test Room Requirements 8.1.1 Either one or two testrooms ae required. depending, ‘upon the type of equipment to be tested and the manufac ture’ installation instructions, 8.1.2. An indoor condition test room is always require. “This may be eny room or space in which the desired test con- ditions can be maintained within the prescribed tolerances. It is recommended that air velocities inthe vicinity ofthe equip- ‘ment under test do not exceed 2.5 rus (500 fp). 8.13 An outdoor condition test room or space is required for tests of ait and evaporatively cooled equipment and for ‘cats of remote water-cooled equipment. This test room shall be of sufficient volume and shal circulate arin manner such thatit does not change thenormal air circulating patter ofthe ‘equipment under test. It shall be of dimensions such that the ‘distance from ny room surface to any equipment surface from which ar is discharged is not less than 1.8 m (6 f) and the distance from any other room surface to any other eqpip- ‘mont surface isnot less than 0.9 m (3 f), except for floor oF ‘wall relationships required for normal equipment installation. ‘The room conditioning apparatus should handle air at arate ‘not loss than the outdoor airflow rate and preferably should ‘take this air from the direction ofthe equipment ar discharge ‘and retum it atthe desired conditions uniformly and at low ‘velocities. 82. Equipment Installation 82.1 The equipment to be tested shall be installed in the test reom(s) in accordance with the manufacturers intalla- tion instructions. Equipment that is intended to be installed. indoors shall be located entirely within the indoor test room: ‘equipment that is intended to be installed outdoors shall bo located entirely within the outdoor test room. Single-pack- ‘aged, ait-source equipment shall be located in or adjacent to ‘an opening inthe wal or partition separating the testroomsin ‘acoardance with the normal or primary recommendations of the manufacturer. In all eases, the manufacturer's recommen dations with respec to distances from adjacent walls, amount of extensions through walls, etc, shall be followed. 82.2 No akerations to the equipment shall be made ‘except for the attachment of required tes apparatus and instruments in the prescribed manner. 82.3 Where necessary, equipment shall be evacuated and ‘charged with the type and amount of refrigerant specified in ‘the manufacturer's published instructions. 824 Interconnesting tubing shall be as furnished or pre- ‘scribed by the manufacturer. In the absence of other instruc- tions, 7m Q5 ft) of tubing shoald be employed, atleast 3 m_ (10 A) oF which is located in the outdocr tot room, 82.5 If pressure measuring instruments are used, they ‘shall be connected to the equipment nly through short lengths of small diameter tubing and shall be located so that the readings are not influenced by Muid head in the tubing. 82.6 No change shall be made in fan speed or system resistance 1o comost for barometric variations, 82.7 _Forequipment in which the compressor is ventilated, independently of the outdoor airsiream, the calorimeter air ‘enthalpy arrangement (soe Figure 3) must be employed to ‘account for compressor shell heat losses. 83. Airflow Measursments 83.1 The airflow measuring device shall provide mea- surements in accordance with the provisions of 77. 84. External Resistance Measurement 4.1 External resistances shall be measured in accor dance with the provisions of Section 6.4. Connections to ‘equipment outlets skall comply with the provisions of 64. 85. Temperature Measurement 34.1 Temperature measurements shall be made in accor ‘dance with ANSUASHRAE Standard 41.1." 85.2 In-duct outlet tomperature and water vapor content| ‘measurements shall be taken at not les than trce locations at ‘the centers of equal segments of the crast-sectional area, oF suitable sampling or mixing devices giving equivalent results| ‘shall be provided. Typicsl mixing and sampling devises aro illustrated in ANSVASHRAE Standard 41.1.! Connections to ‘the equipment shall be insulated between the place of mea- ‘surement and the equipment so that heat leakage through the ‘connections dass not exceed 1.0% of the capacity. 85.3 Indoor inlet éry-bulb temperature and water vapor ‘content measurements shall he taken at not Tess than three positions equally spaced over the equipment inlet ares, oF ANSUASHRAE Standard 37-2009 equivalent sampling means provided. For units without an inlet duct connection or enclosure, the dry-bulb temperature snd water vapor content measuring instruments or sampling devices should be located approximately 15 cm (6 in.) froma the equipment inlet opening or openings. 854 Outdoor inlet air dry-bulb temperature and water vapor content shall be measured at locations such thatthe fol- lowing conditions are fulfilled: (2) ‘The measured dry-bulb temperature and water vapor eon- tent shall be representative ofthe conditions surrounding the outdoor section and simulate the conditions encour tered in an actual application. (©) At the point of measurement, the psychrometric proper ties ofthe air must not be affected by the air discharged from the outdoor section, This makes it mandatory that the air property measursments be made upsiram of any recirculation produced. It is intended that the ambient conditions sounding the outdoor section under test shall simulate as nearly at possible a normal inzallation ‘operating at ambient sir conditions identical with the specified test conditions. 855 _Wet-bulb measurements shall be corrected in accor dance with ANSVASHRAE Standard 41.1.! 8.6 Additional Requirements for the Outdoor Air Enthalpy Method 8.6.1 When the outdoor air enthalpy methed is employed, it is necessary to ascertain whether the attachment of the out door-side test apparatus (i2.. outlet duct, instrumentation, ‘mixing devices, and the nozzle airflow measuring apparatus [see 6.2}) changes the performance of the equiprent being tested and, i's, to corect for tis change. To accomplish this, ‘the equipment shall have temperature measuring devices attached to ret bends at approximately the midpoiats of cach indoor coil and outdoor coil circuit. Equipment not sen- sitive to rfiigerant charge may, as an altemative, be provided with pressure measuring devices connected to access valves or tapped into the suction and discharge lines. The equipment shall then be operated at the desired conditions, with the indoor-side test apparatus connected and the ouldoor side ‘pparatus disconnected. Data shall be sampled at qual inter- ‘val that span five minutes or less fors period of ene-halF hour softer equilibriam has boon attained. The outdoor side test ‘apparatus shall then be connected to the equipraent and the pressure oF temperatures indicated by the aforementioned instrumentation shall be noted. If, after equilibrium is again attained, the average of coll or pressure-equivaleat saturation temperatures does not agree within #0.3°C (£0.5°F) of the verage coil or saturation temperatures observed during the preliminary test, the outdoor airflow rate shall be adjusted ‘nil he specified agreement is attained. The test shall be cor- tinued fora period of at least one-half hour atthe proper com ditions with the outdoor test apparatus connected. During this petiod, the indoor side test results shall agree within +2.0% withthe results obtained during the preliminary test period. This check ofthe effect of the test apparatus en performance shall be conducted for one cooling test and one heating test snd may be conducted for any additional tests, ANSUASHIRAE Standard 37.2009 86.2 When the oudoer airflow rate is adjusted as described in 8.6.1, the adjusted airflow rte isemployed in the capacity caloulation. In such eases, however, the outdoor fan power iaput observed daring the applicable preliminary tet should be used for rating purposes. 87 Test Procedure for Cooling Capacity Tests 8.7L The tes room reconditioning apparatus and the equipment under tes shall be operated until steady-state per- formance that is consistont withthe tes tolerances specified in Table 2 is attained before cooling capacity test data are recorded. 8.72 Data used in evaluating cooling capacity shall then be recorded at equal intervals that span five minutes or less until roadings over period of enc-halfhour are within the tol- crances prescribed in 9.2. 8.7.8 When the outdoor ar enthalpy method is used, the soquirements in 8.7.1 and 8.7.2 apply to both the preliminary test specified in 8.6.1 and test itself. When the compressor calibration method is employed, the above requirements apply to both the equipment test and the compressor calibra- tion test. 88 Test Operating Procedure for Heating Capacity Tests 881 General 88.1.1 Heating capacity tests used to evaluate the heat- ing performance of. heat pump when operating st conditions that are conducive to frost accumulation on the outdoor coil should be conducted using the “I” test procedure described in 83. Othenwise, the manufacturer shall have the option of first tying 10 use the “S” test procedure of 88.2. If he requirements of the “S” test procedure cannot be achieved, ‘then thehesting capacity test shall be conducted using the “T” test provedure described in 8.83. 83.1.2 Except as noted, overriding of automatic defrost controls shall be prohibited. The controls may only be over= ridden when manually initiating a defrost cycle is permitted, 88.1.3 For heat pumps thal use a time-adaptive defrost control system, where deffost initiation depends on the length fof previous defrost eycles, the defrost controls of the heat pump shall be defeated during the offical dats collection interval ofall heating capacity tests. When the defrost con- ttols are defeated, defrost cycles (if any) shall he manually induced in accordance with the manufacturers instructions 88.14 Any defrost cycle, whether automatically or manually initiated, that occurs while conducting a heating capacity test shall always be terminated by the action of the ‘heat pump's defrost controls 88.15 Defrost termination shall be defined as occur- ring when the controls of the heat pump actuate the frst change in converting from defrost operation to normal heating operation. Whether automatically or manually initiated, defrost initition shall be defined as occuring when the con tuols ofthe hest pump firs alter its normal hesting operation in order to eliminate possible accumulations of frost on the ‘outdoor evil TABLE 2a Test Tolerances (S1Units) “ex Opening Tokrance “st Conn Terasawa ergs (iusloteen Range) Teom Speicd oe Cat) eae wine ‘teat wn | Jossierdy-bubienpestse(C> Eaemne wfefPe?=sfe>epe]o [osiorwschihimpeane OF ant os fag | oe w= poe po So w foe fw fo fw fw fo f= fndkerverbabiemeemr (Oe nein as | os @ [oer ing waren) es [os a po \seaelnfigerat pene oraningiemand | 171 @ po itor ste pee) int opera if ivi ei) | as a | oo [smalrseune tos (8) us | as esi woke 0 wan) 20 [20 [20 in ow a ed) 20 | 20) [omic rem depict) zo | 2 Tie Sete” lap we hai seth Rei ode a fr be rier ae i emai dra oe Theda pn ol ce Sat (Dikpis be fu snmnte Wie tereaing belo > Rpideewtensny Seca srerty me ‘Where avs eo tno Qe, sl te ced wen onping erage ee ee &_Aptemtcany entering gape unre natnes wb stroatwn eg Pag ene Rene oot ice be ah : Se FR ea pan tin ete ently mah tet tpi hc ll tne ed epee (Beco! hed ci nthe comesor frit cntos mae hee cr olan TABLE 2b Test Tolerances (LP Units) est Operating aera Tex Contes Ikan Veriton of erage (Gat Gerad Range ‘ie pete oe Coma) ot oh a et Fa cotng_| rowing | Porn| Ponion | Cooting | trong | rarton | Porton o. score ace wf ag | 2 f wo [oe fo | loaderwsrhubenpeatc()Eaeing we | 2 | oe fo | a ean ome |e aioe none. Ene se fo [oo fw [oo [ow foe [= startin CH Hang we | 03 [Gonna ane wie erp os [os oe | seinen repntecarmspaingttcmanees | 30 | 30 os | os gad ener ion ere ened os [os oa | [semalreirune toa nob fw) wos [ ows [sent ae a ating) ze [29 [se [ge tow i eg) xo [2 [None renin den cafe) xe | 2a) 2 TiS ri sl gp ne i ng ag i ia eg tg ThE’ lnc eat ‘Aptteely enemy ena aramapy oc Sealant orld vinnie ame Nipistiev ae nor insopret “ “Tomer pp oh forthe compencr atesce rena nly etd enue anor tie alba tel he em at (Gidea indore mutes er been gem os anger ane 20 ANSVASHRALStncar 37-2009 8.8.2 “S" Test Procedure 882.1 For heat pumps having arated cooling capacity that is less than 40 kW (135,000 Bta/h), a secondary measure- iment of heating capacity shall be made in accordance with 72.1 8.82.2 The ciy-bulb temperature ofthe sir entering the indoorside and the dry-bulb temperature and water vapor conten of thea entering the outdcor-sde shall be sampled at equal intervals that span one minate oF less throughout the preconditioning and data collection periods. Over these same periods. all otter applicable Table 2 non-fosting parameters used in evaluating equilibrium shall be surmple a! equal inter valsthat span five minutes or less. Al dat collected over the respective periods, except for parameters sampled between @ defrost initiation and ten minutes after the defrost termina- tion, shall be used to evahiate compliance with the test toler ances specified in Table 2 8.82.3 The tost oom rovonditioning apparatus and the equipment under test shall be operated until equilibrium con- ditions are attained, but for not less tan one hour, before tst data are recorded. At any time during the preconditioning period, tbe heat pump may undergo one or more defiost cycles if automatically initiated by its own controls. The precondi- tioning period may. in addition, end witha defrost cycle ané this period ending defrost cycle may bs cither automatically ormanually initiated. Ending ine preconditioning periog with a defrost cycle is especially recommenéed for heating cxpac- ity tests at low outdoor temperatures. Ifa defrost des occur, the beat pumpskall operate inthe heating mode for at least ten ‘minutes aftr defrost termination prior to resuming or begin- ning the dats collection described in 882.2 and 88.24, respectively 8824 Oncethe proconditioning describedin 88.2.3 is completed, the data required forthe specified or chosen tst ‘method(s) of 7.1 and 72 shall be eollected. These data shall bbe sampled at equal intervals that span five minutes or less. ‘The difference botwoon the dry-bull temperature ofthe ai leaving and entering the indoor ceil, Ajg(t), shall be eval- uated at equal intervals that span five minutes oF less. The temperature difference evaluated atthe start af the data collec- tion period, Afg(t ~0), shall be saved for purposes of evalu- ating 82.5.1 or 8826.1 compliance. 8825 Test Procedures If the Pre-Conditioning Period Ends with a Defrost Cyele 8825.1 Data collection skall be suspended immodi- ately if ay of the following conditions oecur prier to com- pleting a 30-minute interval where the Table 2 non-fresting test tolerances are satisfied: (@) if the hea parmp undergoes a defies; () ifthe indoor-side dy-bulb temperature difference dogrades such thatthe ratio [A%,4* =0)—AL, 0) At Oyexccods 0.025; or (6) if one or more ofthe applicable Table 2 non-fosting test tolerances ae excooded 88252 If the “S” test procedure is suspended because of condition “a” of 88.25 1, then the “T” test proce- dure described in 8.8.3 shal be used. ANSUASHRAE Standard 37-2009, $825.3 If the “S" test procedure is suspended because of condition “b” of 8.8.2.5, then the“ T” test proce- dure describod in 88.3 shal be used 3.8254 If the “S" test procedure is suspended because of condition “c” of 8.2.5.1, then another attempt at collecting data in accordance with 88.2 and the“S" test pro- cedure shall be made as scon as steady performance is attained. An automatic or manually mitiated detrost cycle ‘may occur prior to making this subsequent attempt. IF defrost does occur, the heat pump shall operate in the heating ‘mode for at leas ten minutes after defrost termination prior to beginning the data collection described in 8.82.4. The pre- conditioning requirements in 8.8.2.3 are not applicable when ‘making this subsequent attempt. $8255. [fthe“S" test procedure isnot suspended in accordance with 8.8.25.1, then the sampling specified ia 8.8.2.4 shall be terminated after 30 minates of data collection. ‘The test for which the Table 2 test tolerances fornon-frosting apply, shall be designated as a completed steady-stateeating capachy test. 88.26 Tet Procedure If the PreConditioning Period Does Not End with a Defrost Cycle $82.61 Data collection shall he suspended immedi ately i any of the following concitions occur prior to com pleting a 30-minute interval where the Table 2 non-frosting test tolerances are satisfied: (@) ifthe heat purnp undergocs a defrost; (©) if the indoor-side dry-bulb temperature difference degrades such thatthe ratio [Ait =O) ~ Aig) Ady Oj exceeds 0.025; or (©) iffone or more of the applicable Table 2 non-frostng tes toleraoes sre exceeded. 3.82.6.2 If the “S" test procedure is suspended because of condition “a” of 8.2.6.1, then another atempt at collecting data in eovordance with 88.2.4 and 8.8.2 shall be ‘made beginning ten minutes after the defrost cycle is termi= nated. The preconditioning requirements of 8.8.2.3 are act applicable when making ths subsequent attompt $82.63 If the “S” test procedure is suspended because of concition “b” of 8.2.6.1, then anotherattompt at collecting data in accordance with 88.2.4 and 8.8.25 shall be made. This subsequent attempt shall be delayed until en min- tutes after the hest pump completes 2 defrost cycle. This defrast cycle should be manually initiated, if possible, in ‘ider 10 avoid the delay of having to otherwise wait for the heat pump to automatically initiate a detfos. 8.82.64 If the “S" test procedure is suspended because of condition “e” of 88.2.6.1, then another atiemp at collecting data in accordance with 88.2 and the “S” test pro- cedure shall be made as soon a8 stoady performance is attained. An automatic or manually inidated defrost cycle may occur prior to making this subsequent attempt. If a defrost does occur, the heat pump shall oporate in the heating mode for al leas ten minutes after delrest termination prior to beginning the data collection described in 8.8.2.4. The pre- conditioning requirements in 8.8.2.3 are not applicable when ‘making this subsoquont attempt, 2 88.2.6.8 Ifthe “S" test procedure isnot susponded in ‘sccordance with §.8.206.1, then the sampling specified in 8.8.24 shallbe terminated after 30 minutes of data collection “The tes, for which the Table 2 text tolerances fornon frosting apply, shall be designated asa completed steady-state heating, capacity test. 883. “T” Test Procedure 88.3.1 Average becting capacity shall be determined using the indoor air enthalpy meted. The outdoor sir ‘enthalpy method shall rot be used and its associated outdoor Side measurement apparatus, if used in the previous test, shall be disconnected from the heat pump. In all eases, the normal ‘outdoor-sde airflow of the equipment shall not be disturbed. Use of a secondary test method is not required. ‘83.3.2 No changes in the airflow settings of the heat ‘pumps shall be made. [fthe heat pump tums the indoor fan of ‘during the deirest cycle, forced airflow through the indoor ‘oil shall cease nd the outlet duct shall be blocked while the fan is of. 88.3.3 The test tolerance given in Table 2, “heat with frost.” shall be satisfied when conducting. heating capacity ‘tests using tho“ T” test procedure, Asnoted in Table 2, tretost ‘tolerances are specified for two sub-intervals. “Heat portion” ‘consists of daia collected during each heating interval, with ‘the exception ofthe frst ten minttes after dofrost termination. “Deftost portion” consists of data collected during each frost cycle plus the first ten minutes ofthe subsoquent heat= ing interval. The tes tolerance parameters in Table 2 shall be ‘sampled throughout the preconditioning and data collection pretiods. For the purpose of evaluating compliance with the spovified test tolorinces, the dry-bulb temperature of the air ‘entering the indoor-sideand the cutdcor-side shall besampled. at least every minute during the heat portion andat least every 120 seconds during tho deffest portion. The water vapor con {ent ofthe air entering the outdocr-side shall be sampled at least every minute. All other Table 2 “beat with frost” param- ‘tors shall be sampled at equal intervalsthat span fiveminates ores. All data collected during each interval, heat portion and defrost portion, shall be used to evaluate compliance with the “Table 2 “heat with Fras” olerances. Data from two or more heat portion intervals or two or more defrost potion intervals shall not be combined and then used in evalusting Table 2 “heat with frost” compliance. Compliance is based en evalu- ‘ating data for each interval separately. ‘83.3.4 The test 1oom reconditioning apparatus and the ‘equipment under tes shall be operated until equilibrium con- ‘tions are attained, but for not less than one hour. Elapsed ‘ume associated witha failed atempt using the"S" test proce- ‘dure of 8.82 may be counted in meeting the minimum roquiroment for one hour of operation. Prior to obtaining, ‘equilibrium and completing one hour of operation, the heat ‘pump may undergo a deftostis) cycle if automatically init ‘ted by ite own controle 88.35 Oncetthe preconditioning described in 8.83.4 is ‘completed, a dafrart cycle shall occur before data are recorded. This deirost cycle should be manually initiated, if possible, in order to avoid the delay of having to otherwise “wait for the heat pump to automatically initiste @ defrost. ata collection shall bogin atthe termination of the defrost «ycle and skal continue until one ofthe following criteria is set. If, at an elapsed time of three hours, the heat pump has ‘completed at least one defrost cycle anda defiostcyele is not presently underway, then data collection shall be immeditely terminated. If, at an elapsed time of three hours, the heat ‘pump is conducting a defrost, the cycle shall be completed before terminating the collection of data. If three complete ‘eles are concluded prior to three hours, data collection shall be terminated atthe end ofthe third cycle. A complete cycle ‘consists of «heating period and a defrost period, from defrost ‘termination todefrost termination, For a heat purnp where the first defrost cycle is initiated afer throc hours but before sx ‘hours have elapsed, data collection shall cease when this fst deirost cycle terminates. Data collection shall cease at six hours ifthe heat pump docs not undergo adafrost cycle within six hours, 88.3.6 In order to constitute a valid tos, the tet toler- ‘ances in Table 2 “heat with frost” shall be satisfied during the applicable 8.8.3.5 test period. Because the test begins at defrost termination and may end at a defrost termination, the first defrest portion interval will only include data from the first ex-minute heating interval while the last defrost portion interval could potentially include data only from the last doirost cycle. 88.3.7 Except for the deviations noted for the dry-buil ‘omporatures, the data required forthe indoor air enthalpy test ‘method shall be sampled at equal interval that span five min- utes or less. The dry-balb temperature of the air entering and leaving the indoor side or, if¢ thermopile is used, the difer- ‘ence between these two dty-bulb temperatures shall be sam- pled atleast every ten seconds during 1. defrost cycles and 2. the firstton minutos ater adsfros termination (includes the fist ten minutes ofthe data collection interval) 8823.8 Average heating capacity shall be calculated in ‘accordance with 7.3.5 using data fiom the total number of ‘complete cycles that are achieved before data collection iste ‘inated. In the ovent thatthe equipment docs not undergo a ‘defyost during the data collection interval, the entire six-hour data set shall be used forthe calculations in 735, ‘9. DATA TO BE RECORDED 9.1. Table 3 shows the data to be recorded during a test. Items indicated by an “x” under the test method columns, or their equivalents, are required when that test method is ‘employed, 9.2. Test Tolerances: 9.2.1 All test chsorvations shall be within the tolerances: specified in Table 2, 2s appropristeto the test methods, type of ‘equipment, and type of test (cooling, non-frosting, or heat ‘with frost). 9.2.2 The maximum permissible variation of any observa- tion during the capacity testis listed under “Test Opersting, “Tolerance” in Table 2. This represents the greatest permissible difference between maximum and mmimum instrument TABLE3 Data to be Recorded Indoor | Oatdvor irs | Ae enmatpy | exmapy Refrigerant Enmay forsee) arom pres KPa mH] supa nt ae [estima times wf fe fe wf fe fe [otal powereneay input to equipment, W/ Wh [W / WH] Power ipa indoor i, WWI [app vets ¥IVI rene, [Hz] Extemalresstaceo afew, Pan. HO) in ect, sine [Drybutb tempera fa enering equipment indor side, CTF] Wetbulb temperate ofa ents qupment dor sde,°CLF] x fn [oe [oe foe fe |e x fn [oe [oe foe fe |e Dry-bulb temperature fa leaving equipment indoor se, CF] Wet temperature ofa lewvine cauipment. indo sie °C" [Dry bulb tempera fa eneringequyment utdbor side “CF etal temperate far entrng equipment, cutdbo side °C [°F |x fos [oe fm oe foe [oe |e fe [Dry-bulb temperate ofa leaving equipment, onteor side. “CIF Wet ub tenperatire ofa levine equipment alder sde°C FT etsy pressure at nozze nate une pressure dfeece oss nor aco, Pie HO Temperaure at sozzie reat © PFL Pressure at woe trot, Pa Hl [contensing presi or tenner, KPa psig or-FI vaporsor prewar or lepertu, KPa ce Ips I Temp. of Fengerant vapor cnering camps, °C [F] [ramp oF retigeran vapor leaving compressor °C [remperatueofhich ie refrigerant wporlearing reversing vai. "CF x fn |e |e [xe Retest fom ate kg Retegennt volume in efgernt-il mixtre, in? PP] Joutioor ot water ow ae, ks [remperture of oto wae ntring equipment “CFF [rmpertus of outdoor wae aving saipment, CFI Rate ot condensate collection, eB) Refrgernt gud temperate, indoor side. °C [FL Not Refracrnt gud temperature outocr side. °C FFL Note Retegernt vapor temperate indoors °C Retrgennt vapor temperature, outoor ie, °C [FL Nate” Refegernt vapor esse, indoor side, Pa [sil 42 Required ely dung cocting capaci ests 1 Requied ely frline ls adjusmeat ANSUASHRAE Standard 37-2009 observations during the test. When expressed asa percentage, the maximum allowable variation isthe specified percentage of the arithmetic average of the observations. 9.2.3 The maximum permissible variations of the ayer age of the test observations from the standard or desired test conditions are shown in Table 2 under “Test Con: Tolerance.” 9.24 Variations greater than those prescribed shall inva idate the test. 40. TEST RESULTS 101 Capacity Test Requirements 10.4.1 The results ofa capacity test shal express quanti- tatvely the effects produced upon ai bythe equipment tested For given test conditions, the capacity test results shall. include each ofthe following quanities that are applisble to cooling or heating and tothe type of equipment tested (@) ‘ota cooting capacity, W (BW (b) sensible cooling capaciy. W [Btu] (6) ‘tent cooling xpssity, W [Btwh} (4) eating capacity, W [Buh] (e) indoor side airflow rate, m*/s standard air [cfm] (external resistance to incor airflow, Pa fin. HO} () ‘otal power input to equipment or power inputs to all equipment cemponents, W [W] Note: The capacities and power inputs may not include addi- tional fan power required to move the ar. 101.2 When two testmethods areroquired, the total oo! ing or heating (except frosting) capacity shall be the indoor side capacity ofthe two simultaneously conducted methods of test and these two capacities shall agree within 6.0%, Whea the compressor calibration method is employed, “simultanc- ously conducted” shall be construed to mean thatthe needed refrigerant property measurements are made during. the capacity test while either a prior or subsequent compressor calibration testis used in determining refrigerant flow rate oF, for cases described in 7.4.1.1(b), in determining cooling capacity 10.1.3 When two test methods for cooling are required, ‘the sensible and latent cooling eapacities shall be those deter- ‘mined using the indoor sir enthalpy methed. 10.1.4 Heating capacity under conditions of equipment cycling die to defrost cycles shall be determined using the indoor air enthalpy method. Heating capacity shall be ‘based on airflow and the indoor air temperature rise (or ‘drop when defrosting) averaged with respect to time for the centre test period. In the event the indoor air fan stops dur ing defrosting, the capacity during this interval is consid ‘ered to be zero; but this elapsed period of time must be included in the total test period for obtaining the average ‘temperature rise forthe indoor airstream, Thenst result for Units in which no defrost occurs isthe integrated capacity for the total test period. For units in which defrost occurs, ‘the not result is the integrated capacity for the total number ‘of complete cycles during the test period. A complete cycle ‘consists of a heating period and a defrest period from defrost termination to defrost termination 10.15 Test results shall be used to determine capacities “without adjustment for permissible variations in test con ditions. 10.1.5 Air enthalpies used in calculating space condition- ing capacities shall be evaluated for the measured ambient ‘conditions: dry-bulb temperature, water vapor content mes ‘surements, and barometric pressure ANSVASHRAE Stadird 372009 11. SYMBOLS USED IN EQUATIONS LLL. The significance of terms used in this standard is provided in Table 4 TABLE 4 Symbols ‘nozzle area, m?[#?] specific hes of sit entering the indoor side, They °C [Bawomg,*F} specific heat of ait leaving the indoor sie, Tay °C [Brom *F] specific heat of sr entering the ouldoor side, Tiy°C [Bawlomg,F] specific heat fait Having the cuter side, Ukgy"C [Brum F} specific heatoftheimuid (e.g, water) Ikg°C [Bette F] cate cocficint of diachaye, dimensionless nozale throat diameter, mm (m.] iameterofrefigerant tubing. mm fn. (OD)] power input, indoor sd, W wats] power input, total, W [vats} enthalpy. airenering indoor side, kaae [Revttma] ceualy,aieaving indoor ide, Thin [Butta enthalpy, air entering, outdoor side, Wk, Brutema cathalp,airleaving outdoor side, Vga, [Buttma cehalfy of retigorant ligula a saturation temperature coresponding tothe pressure of reffigerat vapor leaving the compressor, kg [Rete] ceubalyy of reffigeram liquid leaving. dhe condenser, Jkg [Bhulbm] cathalpy of refigernt vapor entering compresor under conitions specified. kg [Bete] ceubalpy of refligernt vapor entering conderser, Sky [BtuTom} cealpy, steam entering calorimeter evaporator, kg [Rb] crhalpy, ud leaving closer evaporator, ke [Blutomy ‘enthalpy refgarant entering indoor side, kg Brutem] cathalyy, rofhigorant leaving indoor side, Jeg [Beste] length of rfigeant ine, m [8] pressure, barometric, KPa fn. He] pressure t nozle throat, Pa fn. HO] velocty pressure at nozzle throat or static pressure diffrence across nozzle, Pain. HO] ANSUASHRAE Sundar 37-2009 a oo God osdos de ssi ei dee ui uo qe Gas ta tak) tas a6 TABLE 4 Symbols (continued) compressor capacity as determined in accordance with ASHRAE Standard 23-1993, ‘WI(Btwh] -ncatinpat to calorimeter evaporator, W [Btu] line loss, interconnecting tubing, W Btw] Tatent cooling capacity, indoor side data, W_ [Btwh] duct las corrction forthe indoce ir enthalpy amathod, W [Bw duct less comaction for the outdoor air enthalpy method, W [Btw/h] sensible cooling pacity, W [Btw] sensible cooling capacity, indoor side data, W {Bw} sensible reheat capacity, indoor side dats, W [Bewh] toial cooling capacity, compressor data, W [Bw] total cooling capacity, indoor side data, W [Btwh]) total cooling capacity, outdoor side dats, W [Buh] total heating capacity, compressor data, W [Btwh] total heating capacity, indoor side data, W [Bowh] ‘total heating capacity, outdoor side data, W_ [Bru] airflow, indoor, calsulated, m/s [fm] ‘airflow, indoor, measured, ms [fin] airflow, outdoor, measured [cf] ‘airflow, standard air, m?is [efi] Reynolds murbor temperature, ambient ait, ty bulb, °C [°F] ‘temperature, airentering indoor side, dry bulb,

Vous aimerez peut-être aussi