Vous êtes sur la page 1sur 3

PT UNILEVER OLEOCHEMICAL

CLIENT
INDONESIA TBK
PROJECT Project DOVE
Structural Design for DOC. NO. IES-PE-MU-UL-PDV- CS-DC-020-10
Dove Plant
REV. NO. 03
DATE 6-Apr-2015
PAGE NO.

3.5 Seismic Load Calculation R3

The dead load and Equipment Load has been assigned in seismic load case at both X & Z
directions. Seismic analysis has been carried out using Response spectrum Analysis. As per IBC 2009
section 1613, IBC recommends ASCE 7-05 for seismic effects on structures.

Occupancy Importance Factor = 1.0 (As per ASCE 7-05)


Site Class = D (As per Soil investigation report)
Response reduction factor = 8 (As per table 12.2-1 ASCE 7-05)
0.2 sec Spectral Response Acceleration, Ss = 0.63 (As per USGS data maps)
1 sec Spectral Response Acceleration, S1 = 0.26 (As per USGS data maps)
Long Term Period TL = 20 sec
Site Coefficient, Fa = 1.296 (As per table 11.4-1 ASCE 7-05)
Site Coefficient, Fv = 1.880 (As per table 11.4-2 ASCE 7-05)
Steel Moment resisting Frame, Ct = 0.072 (As per table 12.8-2 ASCE 7-05)
Coefficient for upper limit for time period, Cu = 1.4 (As per table 12.8-1 ASCE 7-05)
Height of the building = 31.00 m
Fundamental Period from ETABS, T along X dir = 3.25 sec
Fundamental Period from ETABS, T along Y dir = 3.25 sec
Approximate Fundamental Period, Ta = Cthnx = 1.13 (As per Cl.12.8.2.1 ASCE 7-05)
Upper limit of Time Period, Cu Ta = 1.58 sec (As per Cl.12.8.2 ASCE 7-05)
Time Period used for Analysis = 1.58 sec
Calculated Coefficients,

SDS = 2/3*Fa*Ss = 0.5443 (Eq.11.4.3 from ASCE 7-05)


SD1 = 2/3*Fv*S1 = 0.3259

Static Design Force Procedure : (Section 12.8 ASCE 7-05)

X- dir Y- dir
Seismic Response Coefficient, Cs = SDS / (R/I)
= 0.068 0.068
For T < TL, Cs should not exceed = SD1 / T (R/I)
= 0.0258 0.0258
For T > TL, Cs should not exceed = SD1 TL / T2 (R/I)
= 0.639 0.077

Seismic Response Coefficient, Cs = 0.0258 0.0258

Seismic Weight of the building (from ETABS) = 61862.00 kN


(1.0 DL + EQUIP)

Page 15 of 152
PT UNILEVER OLEOCHEMICAL
CLIENT
INDONESIA TBK
PROJECT Project DOVE
Structural Design for DOC. NO. IES-PE-MU-UL-PDV- CS-DC-020-10
Dove Plant
REV. NO. 03
DATE 6-Apr-2015
PAGE NO.

Response Spectrum Method Using ETABS

ETABS Input for Response Spectrum Analysis

Base shear is calculated as below,

Design Base Shear,V (along X dir) = Cs * W = 1596.04 kN (Cl.12.8-1 ASCE 7-05)

Design Base Shear,V (along Y dir) = Cs * W = 1596.04 kN (Cl.12.8-1 ASCE 7-05)

Base Shear along X dir from ETABS, Vbase,dynam = 501.00 kN

Base Shear along Y dir from ETABS, Vbase,dynam = 575.00 kN

Since the dynamic base shear is less than the static base shear, the factor f shall be
(Cl.12.9.4 ASCE 7-05)
fx = 0.85 (Vbase,static / Vbase,dynamic) fy = 0.85 (Vbase,static / Vbase,dynamic)
= 2.71 > 1 = 2.36 > 1

Page 16 of 152
PT UNILEVER OLEOCHEMICAL
CLIENT
INDONESIA TBK
PROJECT Project DOVE
Structural Design for DOC. NO. IES-PE-MU-UL-PDV- CS-DC-020-10
Dove Plant
REV. NO. 03
DATE 6-Apr-2015
PAGE NO.

Therefore, for re-analysis, the scale factors are assigned in the model in respective directions in ETABS
as shown above

After re-analysis, the base shears obtained as below,

Base Shear (from ETABS analysis), Vbase,dynamic = 1384.00 kN (X direction)

Vbase,dynamic = 1359.00 kN (Y direction)

The scale factors are recheck as below and the factors are considered in ASD combinations.

fx = Vbase,dynamic / Vbase, static fy = Vbase,dynamic / Vbase, static


= 0.87 1 = 0.85 0.85

The combined response of the modal base shear Vbase,dynamic is greater than 85 percent of the calculated
base shear (V) using the equivalent lateral force procedure.
(As per Cl. 12.9.4 of ASCE 7-05)