Vous êtes sur la page 1sur 7

Proceedings of ICE

Civil Engineering 163 November 2010


Pages 3339 Paper 10-00017

doi: 10.1680/cien.2010.163.6.33
Keywords
composite structures;
dynamics; fatigue

The structural
design of Almas
Tower, Dubai, UAE
Ranjith Chandunni
MTech
The Almas Tower is a 360 m high office tower in Dubai, UAE.
is a senior structural engineer and
associate at WS Atkins in Dubai The design comprises two intersecting elliptical towers located
on a sculpted three-storey podium. The architectural form and
clients requirement for floor efficiencies of 80% resulted in
significant challenges for the structural design team. This paper
discusses the structural framing adopted, wind-tunnel studies
undertaken including building acceleration, lateral movements
and column-shortening effects and mitigation measures
introduced. It also describes the design of the towers spire, which
Farshad Berahman
PhD
features tuned mass dampers.
is a senior structural engineer at WS
Atkins in Dubai

The Dubai Multi Commodity Centres Structural system


Almas Tower is a 360 m high slender
office tower located in the Jumeirah Lake The following constraints had a sig-
Towers development in Dubai, United nificant impact on the structural design
Arab Emirates (UAE) (Figure 1). The of the tower and were considered at con-
building consists of five basements, two cept stage design
podium levels, 60 storeys of offices and
three mechanical floors. It has a total n the office floors to have an efficiency
floor area of approximately 85 000 m. of not less than 80%
A typical tower floor plan is in the n flexible column-free and wall-free
form of two diagonally offset ellipses, office space
with a floor plate approximately 64 m n final sellable area to be within 2.5%
long and 42 m wide (Figure 2). The floor of the area sold by the client to ulti-
plan from level 53 to level 64 consists mate office owners
of only one of the two ellipses. An 81 m n each office floor to be capable of sup-
slender spire peaks at 360 m, forming porting a 2.5 t safe placed anywhere
the highest point in the development. within an office space.
The building was completed in
September 2008 and according to the The principal structural framing con-
Council for Tall Buildings and Urban sists essentially of a tube-in-tube system.
Habitat (CTBUH), was the worlds sec- This is made up of a reinforced concrete
ond tallest building completed that year. peripheral frame and a central core wall,

Table 1. Parametric analysis to study the effectiveness of the structural system


Parameters Core wall Core wall + peripheral Core wall + peripheral frame
frame + belt walls + outriggers
Natural period: s 14.6 12.2 9.6
50 y wind sway: mm 1785 1258 771

Delivered by ICEVirtualLibrary.com to:


C I V I L ENG I NEER I NG
IP: 86.96.227.93 33
On: Mon, 22 Nov 2010 04:40:42
Chandunni and Berahman

0 m 20

Figure 2. Typical structural floor plan up to level +232 m showing hollow core slab supported on external
beams to core walls and internal beams

which are connected to each other by with the roof to the plant floors being
central spine beams on each floor and a 400 mm thick solid reinforced con-
outrigger walls at service floor levels. crete slab (except the top plant floor) to
A parametric study of the effective- provide an acoustic barrier to the floor
ness of different arrangements of the immediately above.
external frame, belt walls and outrigger The building was designed to British
walls was carried out and the findings standards, while UBC-97 (ICBO, 1997)
are shown in Table 1. was used for seismic load assessment in
The peripheral frame consists of accordance with local authority require-
1000mm deep, 500 mm wide beams ments. The concrete grades range from 45
supporting precast units which span onto to 70 MPa cube strength with a reinforce-
peripheral columns. The columns are ment grade 460 (fy = 460 MPa) and struc-
at a maximum spacing of 5 m and form tural steelwork S355 (fy = 355 MPa).
part of the lateral load resisting system.
The columns are designed compositely Finite-element modelling
in the lower half of the building to keep
the column sizes small compared to what A three-dimensional finite-element
Figure 1. The 360 m high Almas Tower in Dubai, would be needed for a reinforced con- model of the tower and podium was
UAE was completed in 2008 crete column alone (Figure 3). generated in Etabs (CSI, 2005), which
A typical floor slab consists of included the raft slab on spring supports
1100 320mm thick hollow-core precast pan- to simulate the piles although the raft
els with 80 mm thick structural topping. weight was not considered for the pur-
It ties the external frame to the central pose of assessing the seismic base shear.
reinforced concrete core walls or central An allowance was made in the section
spine beam. The floor is also designed properties for cracking under ultimate
to act as a diaphragm, transferring later- limit state according to UBC-97 and it
al wind and seismic forces to the central was assumed that all loads would be
core and external frame. The precast transferred to the ground through the
slab option was chosen because of pro- piles.
gramme benefits: they are comparatively The spring stiffness for the piles was
lightweight and provide uninterrupted based on the pile working load capacity
356 x 406 UC 634 space for services. and the theoretical settlement of the pile
Vertical Reinf: 24T32
The plant floors at levels 42, 121, 212 under that load, which was taken from
Figure 3. Cross section through a typical and 279 m above ground are 450 mm the geotechnical assessment. The effect
composite column (dimensions in mm) thick solid reinforced concrete slabs, of the podium on the lateral movement
Delivered by ICEVirtualLibrary.com to:
34 ProCeedings of the Institution of Civil Engineers CIVIL ENGINEERING, 2010, 163, No. CE6
IP: 86.96.227.93 issn 0965 089 X
On: Mon, 22 Nov 2010 04:40:42
The structural design of
Almas Tower, Dubai, UAE

Gap during construction


Outrigger wall
(with large openings)

1000
Core wall

1400
2700

First service floor


1500

7850
Belt wall Core
wall
2500

2350
Belt wall Service
floor

Opening for air


intake and discharge
Figure 5. Elevation of a typical outrigger wall with service openings gaps in the
Figure 4. Extract of three-dimensional finite-element model of a plant floor wall adjacent to slab and belt wall were provided to disengage outrigger during
showing core walls, outriggers with openings and external belt walls construction to minimise differential shortening effects (dimensions in mm)

was considered by modelling lateral model was based on a 575 m radius.


springs at various levels based on the The model was placed on a turn-
stiffness of the podium structure. table and was rotated at 15 intervals
The belt walls and outrigger walls to determine wind loads for 24 direc-
include large service openings to allow tions. Structural properties such as
for air intake and discharge as well as to mass, mass distribution, mode shapes
allow for ductwork and piping routing and frequencies were obtained from the
(Figure 4). structural analysis model and input to
The outrigger walls, if constructed assess overall structural loads, building
along with the floors, would have trans- acceleration and cladding pressures.
ferred significant dead loads from the A damping value of 2% was assumed
peripheral columns onto the core, in for the calculations. The tests provided Figure 6. Scaled model of Almas Tower used in
addition to which the outriggers would overall structural loads using 24 load wind tunnel studies
have attracted forces due to differential combinations taking into account direc-
axial shortening between the core and tional effects for each sector. Table 2. Predicted building acceleration
the peripheral frame. To overcome this, The expected deflections under 50 y Return period: Peak total ISO criteria:
y acceleration: milli-g
the outrigger walls were disconnected winds were greater than H/500. As a milli-g
from the floor slab above and on one ver- result, soft joints are provided between 1 12.1 14.0
tical side until all of the floor slabs were the blockwork walls and the structure 5 16.7 19.5
cast, which significantly reduced the load in accordance with BS 8110-2 (BSI, 10 18.7 23.4*
transfer due to dead load and minimised 1985) to allow for racking movement * The criteria for a 10 year return period is not
differential shortening between the core between adjacent storeys under wind provided in ISO and has been extrapolated

and the frame (Figure 5). loads.


The expected building accelerations Seismic design
Wind engineering at the top floor for a 10 y return period
were 18.7 mg, which is within the com- Seismic loads used were based on
Wind tunnel testing was carried out monly accepted threshold of 23.4 mg UBC-97 zone 2A in accordance with
by Rowan Williams Davies & Irwin Inc. (Table 2) as per ISO criteria. A sensitiv- local authority requirements. A response
(RWDI, 2005) using a high-frequency ity check for a 1.5% damping resulted spectrum analysis based on UBC-97 was
force-balance model (Figure 6) with in an acceleration of 21.6 mg or an carried out with appropriate scale factors
wind loads based on a 3 s gust wind increase by a factor of (2/1.5) which used to obtain member forces and associ-
speed of 37.7 m/s for open terrain at was still within acceptable limits. ated drifts.
10m height, in accordance with meas- The overall cladding pressure results Section modifiers as per UBC-97
urements at Dubai International airport gave a maximum value of 4.5 MPa in were applied to the design, that is, 0.7
between 1983 and 1997. The proximity certain local areas. for uncracked walls and columns, 0.35
Delivered by ICEVirtualLibrary.com to:
issn 0965 089 X of the Institution of Civil Engineers CIVIL ENGINEERING, 2010, 163, No. CE6
IP: 86.96.227.93
ProCeedings 35
On: Mon, 22 Nov 2010 04:40:42
Chandunni and Berahman

for cracked walls and 0.35 for beams. realistic and required further investigation. 35% higher than the codified values and
Ductile detailing for the coupling beams Furthermore, the analysis model does not the compressive strength of concrete was
using diagonal reinforcement was speci- take into account the fact that about 10% higher than design strength.
fied according to UBC-97, although this Considering these factors, the long-term
is not required for zone 2A. n all floors are cast horizontally at the deflection at completion of the last floor
level shown on the design drawings, was estimated as 189 mm (H/1470) at
Foundation system thereby reducing the differential short- level +279 m and 126 mm (H/1900) at
ening calculated in the analysis model level +236 m. These values are well with-
The foundation for the tower is a 3m n vertical elements are built plumb in the acceptable range of H/1000.
thick piled raft supported on 1200 mm with reference to a fixed benchmark Although the analysis indicated that in
diameter friction piles, which are approxi- at ground level, thereby reducing the theory the sway would be within accept-
mately 40 m long. To mitigate the effect sway calculated in the analysis model able limits, the contractor monitored the
of the heat of hydration, 50% of the raft n effects of time-dependent factors such verticality of the building during construc-
cement was replaced with ground granu- as creep, shrinkage and age of concrete tion and made adjustments to account
lated blastfurnace slag (ggbs). Appropriate n modulus of elasticity achieved for for this sway by casting floors level to the
concrete cover was provided for the foun- concrete is usually 30% higher than ground benchmark. Adjustments were
dation and perimeter retaining walls to codified values relatively small for the lower symmetrical
achieve the intended building design life. n compressive strength of concrete part and relatively large for the upper
The columns and walls in the podium achieved is normally 10% higher asymmetrical part of the building.
area are supported by slabs spanning than specified values. Lateral sway recorded on site imme-
between pile caps and, to reduce the diately upon completion of the last floor
slab thickness, tension piles are designed Long-term dead load sway was 55 mm (H/5070) at level +279 m
to resist uplift in the podium basement Whereas a long-term dead load sway and 53 mm (H/4450) at level +236 m.
caused by the high water table. of H/1000 would be deemed acceptable, The procedure demonstrated that with
further assessments were carried out to simple compensation techniques on site,
Vertical asymmetry get a better estimate of the anticipated lateral dead load sway can be controlled
gravity load sway. to a large extent. Other factors such as
The tower has an inbuilt vertical The following procedure was under- stiffening effects of internal block wall
asymmetry due to one part of the tower taken to estimate dead load sway of the partitions and faade elements might have
extending 12 floors above the other building. also contributed to the reduction in sway.
while connected to one core throughout Sway analysis was carried out using a
the height of the building. It was realised full model of the building, with construc- Long term axial deformation and
early on in the design that there could tion sequence analysis performed from differential shortening
be lateral movement in the building that levels +236 m to +279 m. The instanta- As with all tall buildings, it was nec-
would be in excess of sways in a conven- neous dead load sway was 150 mm at essary to estimate the long-term axial
tional, symmetrically loaded building. +236m and 225 mm at the uppermost deformation (see Figure 7) and the dif-
Building movement monitoring was floor (+279 m). ferential shortening between the core
included in the specification to allow the The effect of time-dependent creep and the columns (see Figure 8). This
structural designers to compare actual was allowed for by a reduction in the deformation has an impact on the design
movements with those estimated. This effective elastic modulus. Calculations of connecting elements and also requires
required survey points at each floor, were carried out based on the principle adjustments while casting the floors to
which were monitored by laser surveying of area moment to work out a multiplier ensure that the floors are horizontal.
instruments (Leica TPS700) for lateral on lateral movement. This resulted in a Two approaches were considered one
drift against a fixed benchmark located net increase of 110% on the calculated using the Eurocode 2 (BSI, 2004) and
at ground level outside the building. value of lateral movement due to load another using the American Concrete
Further points were located at the core from level +236 m and above. Institute 209 (ACI Committee 209,
and periphery of each floor to monitor In applying a creep coefficient of 1.1, 1997) model.
movement due to axial shortening. long-term deflections were found to be The Eurocode method does not take
The results from the three-dimensional 472 mm (H/590) at level +279 m and into account the relaxation of creep
analysis model indicated that the horizon- 315 mm (H/750) at level +236 m. due to the presence of reinforcement,
tal gravity load sway would be of the order As a result of the calculated long-term whereas the ACI model does. This was a
of 225 mm (short term) at the uppermost sway values based on codified material significant factor in this building consid-
floor level. This value is an overestimate properties, the core walls in the taller ering that the columns were composite
as the model assumes the structure is portion of the building were thickened. and contained significant amounts of
built and then all loads are applied instan- The actual material test results from reinforcement and that the walls were
taneously a phenomenon known as site demonstrated that the values of heavily reinforced at lower levels.
switch-on gravity which is obviously not modulus of elasticity used were about It was therefore decided to use the ACI
Delivered by ICEVirtualLibrary.com to:
36 ProCeedings of the Institution of Civil Engineers CIVIL ENGINEERING, 2010, 163, No. CE6
IP: 86.96.227.93 issn 0965 089 X
On: Mon, 22 Nov 2010 04:40:42
The structural design of
Almas Tower, Dubai, UAE

60 60

Elastic Creep and Total Differential Core 2 TC3-3


shrinkage shortening
50 50

40 40
Stories

Storey
30 30

20 20

10 10

0 0
0 20 40 60 80 100 120 140 0 20 40 60 80 100 120 140 160 180
Shortening: mm Settlement: mm

Figure 7. Long-term settlement curve for elastic shortening, creep and Figure 8. Settlement of a typical tower column (TC-3) and the core wall as well
shrinkage as well as the total shortening of a typical column as the differential settlement between the two typical column and core

method for the assessment. A computer 25mm either way in the 200 mm struc- diamond. The podium comprises an array
program was developed based on the tural depth allowance for cladding fixing. of eight triangular glass petals that radiate
procedure outlined in the ACI as well as from the central core (Figure 9). The dia-
that presented by the Portland Cement Podium mond exchange is accommodated within
Association (Fintel et al., 1987). the north-eastern petal that juts out over a
The program assessed the long-term The design of the podium was inspired terraced water feature stepping down to a
axial shortening of columns and walls by the inherent angular geometry of a lake. The three-storey podium accommo-
by considering elastic shortening, creep,
shrinkage and by allowing for the fact that 0 m 40
floors would be cast levelled to the position
indicated on the drawings. The calculation
was carried out for the core walls and col-
umns and the difference was allowed for in
the construction of the floors between the
cores and the columns. A typical difference
between the core walls and one column is
shown in Figure 8.

Cladding
The building faade consists of a
unitised cladding and curtain walling
system, which is manufactured incorpo-
rating aluminium, glass and insulation as
a complete module.
The vertical spacing was based on a
floor-to-floor height of 4 m while the
horizontal spacing was based on a com-
bination of the structural grid and the
widths of offices to achieve a maximum
number of vision bays.
A 10 mm gap was provided between
each panel for thermal and seismic move-
ment as well as the long-term movement
of the concrete frame due to creep and
shrinkage. The full depth of the mul-
lions, including the glazing or cladding Figure 9. Plan view of podium the largest of eight triangular-shaped petals radiating from the central core
is 150 mm, which left a tolerance of accommodates a diamond exchange centre

Delivered by ICEVirtualLibrary.com to:


issn 0965 089 X of the Institution of Civil Engineers CIVIL ENGINEERING, 2010, 163, No. CE6
IP: 86.96.227.93
ProCeedings 37
On: Mon, 22 Nov 2010 04:40:42
Chandunni and Berahman

Top of roof feature fatigue stresses were estimated for the


+18.60 m
+20.85 m first two modes in each direction (major
4th floor and minor) based on the codified intrin-
sic level of damping of 0.5%.
The calculations were re-run with
increasing levels of damping to establish
the minimum damping values required
in each mode and direction to produce
0 m 20 -8.30 m an acceptable fatigue life.
Car parking
The properties of tuned mass dampers
2nd basement
necessary to provide the required level of
Figure 10. Elevation of diamond exchange centre overhanging cascading podium landscape damping were then determined. Four 2t
dampers located close to the top of the
spire were installed. Table 3 shows the
dates a variety of retail spaces and food Spire structure mode shape, frequency and required and
courts, a business centre, a health club achieved damping values. The measured
and the diamond exchange centre. The top of the Almas Tower features frequencies showed good agreement
Each triangular retail petal consists of an 81 m tall spire, which forms the tip with the predicted frequencies. The
a steel framed structure with composite- of the building reaching to a height of provided damping of approximately 4%
metal deck floor slabs. The diamond 360m. The base of the spire is con- in the first mode and more than 5% in
exchange centre comprises profiled met- nected to the tower through a reinforced the second mode was confirmed by site
al-deck slabs supported on a grid of steel concrete upstand wall over a length of measurements when the dampers were
beams. These are in turn supported by 21 m, such that the free-standing length fine tuned.
an exposed steel truss and steel columns, of the spire in one direction is approxi- The design was then verified upon
which are straight or raking (Figure 10). mately 60 m. completion of the dynamic study with
The steel frames are stabilised by portal The spire has two distinct sections dynamic wind forces corresponding to
action and by the central core of the with a step transition approximately two- proposed damping. The Robot software
building to which they are connected. thirds of the way up. The lower portion was used to perform the static finite-
The ground floor slab is formed by a is roughly elliptical in shape and is con- element analysis and for member design
140 m diameter stepped floor, which radi- structed from a triangulated steel frame of the structure and an Etabs model was
ates from the central tower to the perim- with aluminium cladding. The major and run in parallel to verify the modal prop-
eter. Close to the tower, the podium is at minor axis of the ellipse is 7.4 and 3.4 m erties of the spire.
ground level, gradually stepping to base- at the base respectively. The 23 m high The top part of the spire needed to be
ment 1 level towards tower entrance and upper portion of the spire is of sheet installed in stages because of its weight.
basement 2 towards the rear side. steel construction. The major and minor The dampers were locked, that is inac-
The ground floor slab is a single unit axis of the upper portion is 4.3 and 1.5 tive, until the damper supplier was
of 750 mm thick folded concrete plate. m at its base respectively. allowed access to unlock and tune them.
All the basement columns outside the The spire structure was initially ana- Unpredictable winds during the installa-
tower terminate at ground floor slab lysed and designed for code-calculated tion could have led to an extended instal-
level. These columns form a regular static wind forces. However, due to the lation period until the dampers could
grid of 17.5 m x 8 m to incorporate the slender nature of the spire, it was real- be activated, which meant that exces-
clients requirement of a large column- ised early on in the design that without sive vibration could occur in that time.
free basement parking area. The folded additional damping, the spire would Therefore a vortex shedding suppres-
slab supports the landscape loading and vibrate excessively causing unacceptable sion device (see Figure 11) was attached
planted columns from the retail units fatigue stresses that could lead to struc- around the spire until the dampers were
and diamond exchange centre. tural failure. activated. This device caused wind tur-
A three-dimensional finite-element A dynamic analysis was carried out to bulence in this area rather than alternate
model generated using the Robot pack- assess the susceptibility of the spire to vortex shedding and hence prevented
age (Robobat, 2005) was used for analy- a number of wind-induced excitations, excessive movement of the spire.
sis and design of the slab. No expansion such as galloping, flutter, wind turbu-
joints were provided the slab is exposed lence and vortex shedding in accordance Conclusion
externally and therefore designed for with provisions in Eurocode 1 (BSI,
stresses due to seasonal temperature var- 2005). It was found that the critical wind The design of Almas Tower evolved
iations of 20 oC. All podium columns speed for vortex shedding was below from meeting the clients high expecta-
as well as perimeter retaining walls were those expected on site and hence did tions and stringent requirements. The
designed for additional lateral loads due have the potential to excite the spire. solution adopted by the design team
to thermal movements. Significant deflection amplitudes and proved to be most effective in producing
Delivered by ICEVirtualLibrary.com to:
38 ProCeedings of the Institution of Civil Engineers CIVIL ENGINEERING, 2010, 163, No. CE6
IP: 86.96.227.93 issn 0965 089 X
On: Mon, 22 Nov 2010 04:40:42
The structural design of
Almas Tower, Dubai, UAE

Table 3. Dynamic performance of spire


Parameters Mode 1 Mode 1 Mode 2 Mode 2
(minor axis) (major axis) (minor axis) (major axis)
Frequency predicted: Hz 0.64 0.70 2.47 2.87
Frequency measured: Hz 0.51 0.70 2.20 2.70

Mode shape

Figure 11. Temporary device to suppress vortex


shedding on the spire during construction of the Required damping 3% 3% 2% 2%
spire and installation of its tuned mass dampers Achieved damping 4% 4% >5% >5%

The top of the Almas Tower References


ACI Committee 209 (1997) Prediction of Creep,

features an 81 m tall spire, which Shrinkage and Temperature Effects in Concrete


Structures. American Concrete Institute,
Farmington Hills, MI.
forms the tip of the building BSI (British Standards Institution) (1985) BS 8110
Part 2 Structural Use of Concrete. Code of

reaching to a height of 360m


practice for special circumstances. BSI, Milton
Keynes.
BSI (2004) BS EN 1992-1-1 Design of Concrete
Structures General Rules for Buildings. BSI,
Milton Keynes.
BSI (2005) BS EN 1991-1-4 Action on Structures
General Actions Wind Actions. BSI, Milton
Keynes.
a floor usage of the highest efficiency. ture WS Atkins Dubai, dynamic analysis CSI (Computers and Structures Inc) (2005) ETABS
Detailed studies were carried out to of spire WS Atkins Epsom, wind tunnel nonlinear version 8.5, extended 3D analysis of building
address issues arising from the sway due specialist RWDI, third party structural systems. CSI, CA, USA.
Fintel M, Ghosh SK and Lyengar H (1987) Column
to vertical asymmetry of mass. This was reviewer Halcrow Yolles, project man- Shortening In Tall Structures Predictions and
overcome by using simple compensation agement Faithful & Gould, contractor Compensation. Portland Cement Association,
techniques during construction, thereby joint venture Taisei Corporation and Stokie IL, USA.
ICBO (International Conference of Building
demonstrating that a practical approach Arabian Contracting Company, tuned Officials) (1997) Uniform Building Code, UBC-97.
can be successful in addressing such mass damper supplier Gerb. Whittier, CA.
Robobat (2005) Robot Millenium Software Package.
issues. The authors would also like to thank Robobat, USA.
Vortex shedding suppression devices Chander Shahdadpuri, lead structural RWDI (Rowan Williams Davies & Irwin Inc.) (2005)
based on simple principles were used as engineer of the project and Shapour Wind-induced structural responses, DMCC Almas
Tower, Dubai, UAE. RWDI, Ontario, Canada.
temporary measures during the construc- Mehrkar-Asl, former head of structural
tion stage to prevent excessive wind- engineering at WS Atkins in Dubai,
induced movement of the spire. who were the main contributors of the What do you think?
paper presented at the conference of If you would like to comment on this paper,
Acknowledgements International Federation for Highrise please email up to 200 words to the editor at
journals@ice.org.uk.
Structures in 2007. They would also
The key members of the project team like to acknowledge that the computer If you would like to write a paper of 2000 to 3500
words about your own experience in this or any
were: client Dubai Multi Commodity program to estimate long-term axial related area of civil engineering, the editor will be
Centre, architect, building services engi- deformation was developed by Dr. happy to provide any help or advice you need.
neer, fire, life and safety, acoustics, struc- Mehrkar-Asl.
Delivered by ICEVirtualLibrary.com to:
issn 0965 089 X of the Institution of Civil Engineers CIVIL ENGINEERING, 2010, 163, No. CE6
IP: 86.96.227.93
ProCeedings 39
On: Mon, 22 Nov 2010 04:40:42

Vous aimerez peut-être aussi