Académique Documents
Professionnel Documents
Culture Documents
Application
Location Classes:
Temperature B
Humidity B
Vibration A
EMC A
Enclosure A
Notice: This Certificate is subject to terms and conditions overleaf. Any significant change in design or construction may render this Certificate invalid.
The validity date relates to the Type Approval Certificate and not to the approval of equipment/systems installed.
If any person suffers loss or damage which is proved to have been caused by any negligent act or omission of Det Norske Veritas, then Det Norske Veritas shall pay compensation to such person for his proved direct loss or damage.
However, the compensation shall not exceed an amount equal to ten times the fee charged for the service in question, provided that the maximum compensation shall never exceed USD 2 million.In this provision Det Norske Veritas shall
mean the Foundation Det Norske Veritas as well as all its subsidiaries, directors, officers, employees, agents and any other acting on behalf of Det Norske Veritas.
DET NORSKE VERITAS AS VERITASVEIEN 1, 1322 HVIK, NORWAY TEL: (+47) 67 57 99 00 FAX: (+47) 67 57 99 11
Form No.: 20.90a Issue: January 98 Page 1 of 9
Cert. No.: A-11462
File No.: 851.10
NPS Job No.: 262.1-001642-3
Product description
Generator / feeder protection and controlling units. There are three series of SYMAP
units as follows:
DET NORSKE VERITAS AS VERITASVEIEN 1, 1322 HVIK, NORWAY TEL: (+47) 67 57 99 00 FAX: (+47) 67 57 99 11
Form No.: 20.90a Issue: January 98 Page 2 of 9
Cert. No.: A-11462
File No.: 851.10
NPS Job No.: 262.1-001642-3
DET NORSKE VERITAS AS VERITASVEIEN 1, 1322 HVIK, NORWAY TEL: (+47) 67 57 99 00 FAX: (+47) 67 57 99 11
Form No.: 20.90a Issue: January 98 Page 3 of 9
Cert. No.: A-11462
File No.: 851.10
NPS Job No.: 262.1-001642-3
Depending on device type some or all of the following alarm and protection functions as
defined by ANSI are available:
ANSI no. Function / description
2 Time relay starting or closing
12 Overspeed device
14 Underspeed device
15 Matching device (motorpoti)
24 Overexcitation protection
25/A Automatic synchronizing
27 Undervoltage, instantaneous, definite time
27B Undervoltage, def. time (Bus 1 only)
32 Overload
37 Undercurrent
46 Reverse phase or phase balance current
47 Phase sequence voltage
49 Thermal overload protection
50 Overcurrent, instantaneous
50BF Circuit-breaker failure
50G/N Current earth fault, instantaneous
51 Overcurrent, def. time, iDMT (6 curves)
51G/N Current earth fault, def. time, IDMT (6 curves)
51LR Locked rotor
51VR Voltage restrained Overcurrent
59 Overvoltage, instantaneous, def. time, IDMT
64/59N Ground overvoltage / residual overvoltage
66 Number of starts
67 AC directional Overcurrent, def. time
67GS/GD AC directional earth fault, def. time
78 Vector surge upervision
78S Out of step tripping
DET NORSKE VERITAS AS VERITASVEIEN 1, 1322 HVIK, NORWAY TEL: (+47) 67 57 99 00 FAX: (+47) 67 57 99 11
Form No.: 20.90a Issue: January 98 Page 4 of 9
Cert. No.: A-11462
File No.: 851.10
NPS Job No.: 262.1-001642-3
The SYMAP system may include the following additional features depending on the
actual configuration of the assembled system:
StandardParameterSettingNo1.par
StandardParameterSettingNo2.par
StandardParameterSettingNo3.par
DET NORSKE VERITAS AS VERITASVEIEN 1, 1322 HVIK, NORWAY TEL: (+47) 67 57 99 00 FAX: (+47) 67 57 99 11
Form No.: 20.90a Issue: January 98 Page 5 of 9
Cert. No.: A-11462
File No.: 851.10
NPS Job No.: 262.1-001642-3
Electrical ratings:
Approval conditions
The Type Approval covers hardware, software and parameters listed under Product
description.
When the type approved software is revised (affecting all future deliveries) DNV is to be
informed by forwarding updated software version documentation. If the changes are judged
to affect functionality for which rule requirements apply a new functional type test may be
required and the certificate may have to be renewed to identify the new software version.
Case-by-case:
For each design where the product is included (typically a switchboard) the following
information related to the SYMAP system is to be submitted for approval:
- Reference to this Type Approval Certificate
- System block diagram
- Power supply arrangement (may be part of the System block diagram)
- List of hardware modules as identified in this Type Approval Certificate
- Functional description, preferably covering all functions of the switchboard
- List of implemented alarm and protection functions (ref. the ANSI lists above) with
proposed limits and time delays
- Test program for test at the product manufacturer or the switchboard maker
- When the system is to be certified, ref. below, test program for test at the product
manufacturer or the switchboard maker
- When system certification is not anticipated, ref. below, information about which of the
three standard parameter sets provided by the maker (Stucke Elektronik GmbH) will be
installed and proposal for commissioning tests
Product certificate
For systems that are based on the ECG module and where the parameters installed at the
time of switchboard certification is one of the standard parameter sets listed above under
product description a product certificate according to Pt.4 Ch.9 Sec.1 A 202 will not be
required. Final test of correct configuration and set up for each delivery is then to be done
during commissioning after installation.
Verification of the installed set of parameters being identical with one of the standard sets
can be done by uploading the parameters to a maintenance PC and sending the parameter
file to the maker (Stucke Electronik GmBh) who in turn will inform possible differences.
Email address mail@stuckegmbh.de is to be used.
DET NORSKE VERITAS AS VERITASVEIEN 1, 1322 HVIK, NORWAY TEL: (+47) 67 57 99 00 FAX: (+47) 67 57 99 11
Form No.: 20.90a Issue: January 98 Page 6 of 9
Cert. No.: A-11462
File No.: 851.10
NPS Job No.: 262.1-001642-3
For all other systems, each delivery of the application system is to be certified according to
Pt.4 Ch.9 Sec.1. The certification test is to be performed before the system is shipped to the
yard, that is, at the manufacturer of the application system or at the switchboard
manufacturer if agreed and adequate system competence and test facilities are available
here. If certified together with the switchboard, a combined control system and switchboard
certificate may be issued. The certificate must identify this Type Approval Certificate plus
the firmware by versions and dates.
After the certification the following clause for application software control will be in force:
All changes in software and parameter settings are to be recorded as long as the system is in
use on board. The records of all changes are to be forwarded to DNV for evaluation and
approval. Major changes in the software are to be approved before being installed in the
computer.
Application/Limitation
Generator Intrumentation:
When SYMAP systems are used for generator protection/control, additional instruments
will be required to be fitted in the switchboard as required in DNV Rules, Pt.4 Ch.8
Electrical Installations.
Overspeed protection
Rule requirements for separate prime mover safety functions (e.g. diesel engine overspeed
protection) are to be observed.
For high speed vessels category B (ref. Pt.4 Ch.8 Sec.2F) the system must be configured so
as to ensure that the power management functions are active for each busbar section when
the bustie breaker is open. Also, the communication network between units for one busbar
section must not be affected by a defective communication network for the other busbar
section.
DET NORSKE VERITAS AS VERITASVEIEN 1, 1322 HVIK, NORWAY TEL: (+47) 67 57 99 00 FAX: (+47) 67 57 99 11
Form No.: 20.90a Issue: January 98 Page 7 of 9
Cert. No.: A-11462
File No.: 851.10
NPS Job No.: 262.1-001642-3
EMC tests according to GL Additional Rules and Guidelines part 7 chapter 3 edition 2001.
Vibration test according to IEC 60068-2-6 Test Fc
Cold test according to IEC 60068-2-1
Dry heat test according to IEC 60068-2-2
Damp heat test according to IEC 60068-2-30 Test Db
Insulation Resistance test
High Voltage Test
Flamability test according to IEC 60695-2-2
Software test (function test) according to IEC 60255
Marking of product
DET NORSKE VERITAS AS VERITASVEIEN 1, 1322 HVIK, NORWAY TEL: (+47) 67 57 99 00 FAX: (+47) 67 57 99 11
Form No.: 20.90a Issue: January 98 Page 8 of 9
Cert. No.: A-11462
File No.: 851.10
NPS Job No.: 262.1-001642-3
The scope of the retention/renewal survey is to verify that the conditions stipulated for the
type are complied with, and that no alterations are made to the product design or choice of
systems, software versions, components and/or materials.
The main elements of the survey are:
DET NORSKE VERITAS AS VERITASVEIEN 1, 1322 HVIK, NORWAY TEL: (+47) 67 57 99 00 FAX: (+47) 67 57 99 11
Form No.: 20.90a Issue: January 98 Page 9 of 9