CONTINUING EDUCATION

Presented by:

POST-FRAME CONSTRUCTION
IN LOW-RISE COMMERCIAL BUILDINGS
LEARNING OBJECTIVES
At the end of this program, participants will be able to:
1. Describe the methods of construction employed in
post-frame construction.
2. Review the importance of material and finish choice
for post-frame construction.
3. Discuss the attributes of post-frame construction in
terms of durability and energy efficiency and review
applications in low-rise commercial buildings.
4. Describe how post-frame construction is code-
accepted and code-compliant with applicable
building regulations.

CONTINUING EDUCATION
CREDIT: 1 LU
COURSE NUMBER: ARaug2015.1
Use the learning objectives to focus your
study as you read this article. To earn credit
and obtain a certificate of completion, visit
http://go.hw.net/AR815Course1 and complete
the quiz for free as you read this article. If you
are new to Hanley Wood University, create a free
learner account; returning users log in as usual.

By Paige Lozier, in collaboration with Marissa Hovraluck

INTRODUCTION attached to the primary framing members to


provide lateral support and to transfer sheathing
The term post-frame building system refers
loads, both in-plane and out-of-plane, to the
to a building characterized by primary structural
posts and roof framing.
frames of wood posts as columns and trusses or
rafters as roof framing. Roof framing is attached This type of framing system outperforms other
to the posts, either directly or indirectly through building types in any climate or soil condition.
girders. Posts are embedded in the soil and After hurricanes Katrina and Rita ravaged
supported on isolated footings, or are attached the southern U.S. coastal states, post-frame
to the top of piers, concrete or masonry walls, buildings stood tall amidst the rubble. The same
or slabs-on-grade. This type of framing system METHODS OF CONSTRUCTION is true of snowstorms in the North. Post-frame
outperforms other building types in any climate buildings are not only strong but they allow
The term post-frame building system refers
or soil condition and is an energy-efficient for flexibility in design and construction when
to a building characterized by primary structural
building method. compared to other building methods, as the
frames of wood posts as columns and trusses or
choices for size, roof style, materials, ceiling
This article will discuss construction methods rafters as roof framing. Roof framing is attached
systems, flooring, thermal insulation systems
and materials, as well as performance measures to the posts, either directly or indirectly through
and interior wall configurations are virtually
for post-frame buildings and their application in girders. Posts are embedded in the soil and
unlimited. Post-frame buildings feature wide
low-rise commercial buildings. It discusses how supported on isolated footings, or are attached
open interior spaces thanks to their truss system,
a combination of quality materials, expert work- to the top of piers, concrete or masonry walls,
which allows for a virtually unlimited selection of
manship, energy efficiency and low maintenance or slabs-on-grade. Secondary framing members,
interior layouts as well as exterior features.
in a post-frame building can optimize value. purlins in the roof and girts in the walls, are
CONTINUING EDUCATION

Post-frame buildings can be constructed any Laminated Columns and anchor bolts, using one of two techniques.
time of year, as weather-related construction A column on a formed wall with trenched
Nail laminated columns are the posts of choice.
delays are rare. Once the construction process footing below utilizes ready-mix concrete with
Typically 3-ply laminated lower columns that
begins the amount of time it takes to get under reinforcement. Column sockets are anchored
are hydraulically compressed during lamination
roof for a post-frame building is approximately with plated concrete anchor bolts and the
and provide a stronger column than solid posts
half of what is normally expected from other laminated column is bolted in the column
of the same dimension are chosen. Lower
construction techniques. This allows building socket. A column can also be mounted on a
columns should be pressure preservative treated
professionals to design buildings year-round monolithic slab, which is a good solution in
in accordance to AWPA treatment standards to
without feeling the pressure of a season change. rocky, difficult-to-dig soils and works well with
prevent fungal decay and insect infestation.
These attributes come as no surprise to those a poured concrete floor. As with the previous
who engineer and build post-frame structures Laminated columns provide superior treatment technique, column sockets are anchored to
because when built correctly, their unique design since this will allow 100% penetration of the plated concrete anchor bolts and the laminated
and construction performs exceptionally well sapwood, which cannot be obtained with column is bolted in the column socket. A
under tremendous weather extremes. square posts because they are treated with thickened edge meets heavy load requirements.
preservative on the outside edges only. It is
POST-FRAME FOUNDATION In-ground column foundations
preferred to treat only the lower portion of a
The structure of a post frame building is what column because a full length treated column Another economical foundation option that
sets it apart from others, so it is important to would make it harder to get a straight wall, can be utilized where conditions permit is a
explain how they are constructed from the as treated lumber has a tendency to warp and system with pre-cast concrete columns buried
ground up. twist as it dries out. Lamination also provides in the ground. Providing superior strength with
the ability to add column stiffeners and/or specially designed components and materials
Based on the specific climate, ground conditions increase the dimensional size of lumber for compared to laminated wood columns, the
and building use of a project, there are several high demand situations, like high wind areas, hybrid foundation can be used for a variety of
types of footings/foundations to choose from. earthquakes and buildings taller than 16 feet. building uses. The system consists of several
A manufacturers foundation and warranties components: a concrete column, an internal
must guarantee durability no matter what style is There are several foundation options and
threaded adjustment bracket, stainless splash-
chosen. The foundation system of a post-frame different ways to achieve a solid foundation in
board bracket, internal column connector and
building consists of columns that are buried in post-frame construction. All begin with these
a wood upper column. Because the foundation
the ground, embedded in concrete, or anchored three or four member laminated columns.
system utilizes concrete in the ground, there is
to a concrete foundation. Vertical loads from the no need for treatment, providing an eco-friendly
roof are transferred to the column, and from the foundation option for the building.
column to a concrete footing or foundation, and
then to the soil. Buried or embedded posts can
resist lateral loads.
Posts surface mounted on concrete foundations
need to be designed utilizing roof diaphragms
and shear resisting wall elements similar to
traditional wood construction. Most metal
roofing and siding manufacturers have design
values for their products that can be used. Column on Trenched Footing
Plywood and OSB substrates may also be used.
Concrete
Field placed concrete or ready mix provide the
best footings. This allows the concrete to con-
form to the column and fill the hole completely.
Utilizing specialized digging equipment provides
deeper holes for the footings and columns,
creating a uniform cylindrical shaft. Digging a
hole with shovels can result in shallower, funnel
shaped holes that will be uneven. Pre-formed
options, if used, shift and settle, creating an
uneven surface for the column even if the Column on Monolithic
hole was originally level. Industry standards
and design specifications typically require the Columns Mounted to Foundation
columns to be embedded in the ground a Columns can be mounted directly to the
minimum of 4 feet. concrete foundation with a steel column socket
CONTINUING EDUCATION

Steel Bracket the affordability, design flexibility and energy leaks. A fully ventilated attic allows for air flow
efficiency of post-frame construction and is and adequate room for blown-in insulation.
Finally, pre-cast concrete foundation columns
a great option for a variety of building
are attached to the concrete columns with a Finally, as part of the insulation system a vapor
applications. These buildings feature pre-en-
steel bracket, which is welded to re-bars in retarder should be secured over the insulation
gineered steel trusses with an open-webbed
the concrete column that extend to the base to keep it dry and reduce infiltration and heat
design set on wood framing. The steel trusses
of the column. 10,000 PSI super high strength loss. This creates a seal between the elements
allow for a wider building, while wood framing
concrete is usually specified, as well as galva- and the inside of the building. Nailers are then
provides superior insulating properties and
nized steel uplift anchors. placed over the vapor barrier which allows
building strength. This hybrid technology also
interior walls to be attached. HVAC, electricity
makes buildings possible that have greater door
and plumbing can be run inside this barrier
clearance, giving the ability to use bigger doors
without compromising the seal.
with shorter walls, and allowing for a lower
profile building. Post-frame buildings feature an exceptionally
large built-in wall cavity that is nearly 9 inches
thick, six of which are insulation. Extra deep
truss heels also allow for extra insulation and
insulation descends below the top of the
concrete floor. All of these factors lower heating
and cooling costs throughout the year.
Its important to compare how insulating
methods differ for steel buildings as opposed
Trusses
to post-frame and why post-frame can obtain
Trusses are another structural member that a better R-value. Steel buildings offer several
provide post-frame buildings superior strength methods of installing insulation. In typical steel
and longevity. Specially engineered trusses are buildings, the insulation is draped over the roof
densely webbed and attached to the support ENERGY EFFICIENCY AND INSULATION purlins so that fiberglass blanket insulation is
columns; while the trusses can be mounted on rolled out over and perpendicular to the outside
While metal is a conductor of hot and cold,
the outside column member, to the side of the of the structural frame. Then the metal covering
wood is an insulator. At its very core, the wood
column or in a support header, the best method sheets are fastened to the frame, holding the
frame in post-frame construction creates a
is when they are centered in a column, positioned insulation in place, but this method compresses
controllable environment. The design of a
between column laminates. Extra deep truss the insulation when the roofing is applied. This
post-frame building should allow maximum
heels eliminate the need for knee braces, leaving compression can result in a loss of nearly half
insulation, air circulation and condensation
more usable space inside the building. Trusses of the thickness of the insulation, reducing
control. Be sure to specify insulation choices
should be made from premium-grade, such the insulations R-value, which is the standard
that save on heating and cooling costs for the
as MSR lumber which has been evaluated by measure of thermal resistance.
life of the building.
mechanical stress-rating equipment for stiffness,
Insulation can also be installed between purlins.
which then determines the lumbers strength. Where newer energy codes require higher
This allows for thicker insulation without com-
levels of insulation, post-frame is a particularly
Trusses which sit in a saddle and are bolted pression at the structural members by applying
good option because its walls and roof are
and nailed provide double strength against it between purlins rather than perpendicular
relatively easy to insulate and wide blankets of
wind shear. Finally, a predrilled, factory-cut to them, resulting in better thermal efficiency.
insulation can be used. Wide column spacing
continuous purlin system can add strength, However, the problem of thermal bridging
allows for continuous insulation between
rigidity and uniformity. There is the option of through the structural members in direct con-
structural elements, fewer interruptions in
straight- or raised-chord trussing, the latter of tact with the metal covering sheets still applies.
insulation material, and less chance of thermal
which provides greater interior clearance and While many steel-framed buildings feature 3
leakage. In fact, insulation breaks occur only
allows for the installation of taller end doors. inch fiberglass ceiling insulation, which provides
at the wood columns, which are spaced
Clear-span structures are available in a variety an R-9.5 rating, some post-frame insulation
further apart than other structures. Where the
of widths. Some manufacturers offer custom systems can obtain R-38 insulation on ceilings.
insulation is interrupted, wooden structural
clear-span widths up to 100 feet as well as
members have natural insulating properties MATERIAL AND FINISH CHOICES
double- and triple-wide trusses.
and conduct less heat than most structural
Steel Trusses steel or masonry components. Post-frame is an energy-efficient building
method and its primary material, wood, is a
Another option in post-frame construction is Air deflectors should be installed to move air renewable resource that is widely available and
a hybrid structure that allows for clear span up through the attic of the building and out sustainably harvested throughout North America.
buildings up to 150 feet when steel trusses are through the peak to promote good ventilation Wood is strong and innovations in engineered
used. Hybrid technology combines the strength throughout the building, protecting the insula- wood products allow it to be used for longer
and spanning capabilities of steel along with tion from condensation and the building from spans and taller structures than ever before.
CONTINUING EDUCATION

As discussed, wood is a good insulator, which QUIZ


reduces heat transfer. The widely spaced,
relatively thick wood side and end wall posts
1. True or False: In post-frame construction roof framing is attached to wood posts through girders.
minimize the number of thermal breaks and
minimize the thermal bridging effect in post- 2. Industry standards and design specifications typically require the columns to be embedded in the ground a
frame buildings. Condensation accumulation minimum of _____.
on the inside wall surfaces at thermal breaks is a. 5' b. 4'
practically eliminated in post-frame buildings. c. 6" d. 10'

EXTERIOR MATERIALS 3. True or False: 3-ply laminated lower columns that are hydraulically compressed during lamination provide a stronger
column than solid posts of the same dimension.
While the structural members of post-frame
buildings are made of wood, the roofing and 4. Which is the best foundation option to use in rocky, difficult-to-dig soils?
exterior siding can be clad in a variety of materi- a. True b. False
als from asphalt, cedar shake, slate or tile roofs
to stucco, brick, stone, fiber cement, wood or 5. True or False: 70% Fluoropolymer painted panels cannot chalk more than 5 Delta Es over a 10 year period.
vinyl siding. As in other building types, materials a. Column on trenched footing b. Column on monolithic slab

can be combined to create architectural details c. Column anchored to buried monolithic concrete

such as wainscoting, board-and-batten siding,


6. True or False: Wooden structural members have poor insulating properties and conduct more heat than most structural
cupolas, dormers and porches that enhance steel or masonry components.
the buildings architecture and aesthetics.
These exterior materials are easily adapted to 7. Which of the following can be used as exterior siding on a post-frame building?
post-frame construction and you will notice a. Brick b. Vinyl
examples of each throughout the course. c. Stucco d. Stone
That being said, the roof and siding of post- e. Fiber Cement f. All of the above
frame buildings are often made of ribbed steel
panels, which will be discussed in greater detail. 8. What is the ideal gauge of steel for ribbed steel panels used in post-frame construction?
a. 30 gauge b. 29 gauge
In order to get the strength needed to carry c. 15 gauge d. 26 gauge
roof loads, flat sheets of steel are run through a
roll-forming machine. Steel gauge is an important 9. True or False: Because diaphragms and shear walls are used in the lateral design of a post-frame building the structure acts
measurement and can vary depending on where as a box system and can outperform many steel structures.
the steel is purchased; typically big box retailers
sell 30 gauge steel, while many contractors offer 10. Post-frame buildings are wood structures and as such are classified as Type ______.

29 gauge. The thickness of steel can vary, even a. VC or VB b. AC or HV


c. VA or VB d. AV or BV
within the same gauge of the product; for post-
frame you should select a quality building that
11. The ASABE is a professional and technical organization comprised of members who are dedicated to advancement of
is constructed with a heavier (lower) gauge of engineering applicable to agricultural, food, and biological systems.
steel. 26 gauge (thickness range of .0179 inches a. NFPA b. ICC
to .019 inches) commercial steel is ideal because c. AWA d. ASABE
it is a thicker, superior steel product. 26 gauge
commercial steel is more flexible, minimizing
cracking during the roll-forming process, but it is
also heavier than 29 gauge steel (.0135 inches to SPONSOR INFORMATION
.0142 inches) or 30 gauge steel (.0157 inches to
.013 inches), making it better able to withstand
the elements.
An arch-shaped rib configuration varies by
manufacturer, offering a wide variety of profiles Morton Buildings is a construction-led designBUILD firm. Our in-house staff of project managers, construction
though-out the industry. Each panel type estimators, drafting technicians and construction coordinators provides a team with significant experience on
commercial projects that will work alongside qualified professionals. With more than a century of experience,
has its own structural and/or architectural
Morton is Americas leader in custom timber-frame construction.
design characteristics. Some manufacturers
recommend fastening into the intermediate
or flat ribs which allows water to run over
the fastener and rib. This is not best practice


and can be compared to putting holes in the This article continues on http://go.hw.net/AR815Course1. Go online to read the rest of the article
bottom of a gutter. The best practice is to and complete the corresponding quiz for credit.
fasten in the high rib to prevent leaking.
CONTINUING EDUCATION

Some manufacturers produce ribs that have cool roof. The coating used on steel panels
a lower profile and sharper bends, but many must have certain qualities to remain virtually
believe a better quality steel panel features maintenance-free and easy to clean. First, it
high ribs with a rounded profile, which reflect should have superior protection against fading,
sunlight from various angles for better chalking, peeling and red rust. It should also have
aesthetics. Generous bend radii offer improved resistance to the effects of ultraviolet rays, rain
paint and metallic coating flexibility. and pollution. Finally, the coating should have
color and gloss retention that lasts far longer than
For buildings that will be used for living and
standard consumer or commercial paint coatings.
working areas, you may want to consider
specifying a high rib acoustical steelone of the There are a number of advantages to using
most efficient sound insulation systems in the powder coatings, as they cure to a durable
construction industry. Installed in a band around scratch resistant finish with improved corrosion
or in the ceiling, acoustical steel allows sound resistance. With powder coatings, particles of delivers and unloads the materials at the jobsite.
waves to pass through sound-absorbent materials the coating are made to float around and coat And finally, build using professional craftsman
in the wall and ceiling cavities, which significantly the surfaces of parts to which they are attracted trained extensively in post-frame construction.
improves the sound quality in a building. electrostatically. The part is moved to an oven The combination of quality materials, expert
where the particles rapidly melt, fuse to each workmanship, energy efficiency and low
other, and adhere to the part as a cured film. The maintenance will provide the most value for
powder epoxy is significantly easier to use than your project budget.
liquid epoxy paint, as the liquid counterparts Second and third generation owners of
become difficult to work with because of a post-frame buildings can attest to the fact that
tendency to gel in paint lines and guns. High they look like new after decades of use. From
performance liquids often present health foundations to fasteners, every detail should
hazards, whereas powders can be selected which be designed for minimal maintenance. Specify
do not pose additional health risks to operators. a building with the following details and it too
The powder coating process also improves the will last for generations. The paint used on the
protection of the sharp edges of a part, as liquid building should resist moisture and UV light.
paints tend to run away from sharp edges but Treated wood, true stainless steel screws and
powders cover the edges very well. rust-resistant ring shank fasteners all prevent
COATINGS
Powder coatings also have ecological benefits. corrosion and rot in the building. Eliminate
To form the ribs, the steel is stretched and bent. leaking and condensation build-up through
Liquid paints produce hazardous waste that
As a result, there is a strong likelihood that this appropriate roof pitches and ventilation
is costly to dispose of, while the overspray
stretching may result in hairline cracks in the paint systems. Controlling condensation also protects
of powders can be collected and used again
and zinc, which may result in future red rust. A insulation from moisture and sagging. Stand
and again. The small amount of remaining
roofing product that is more flexible, has a heavier strong against high wind and snow loads.
waste powder can be safely disposed of in
zinc coating and a durable paint system will resist Unlike concrete, post-frame construction has
approved landfills. Because they are greater
cracking during the roll-forming operation. some give, so when the ground shifts and
than 98 percent nonvolatile, they do not emit
Steel is commonly recognized as a strong any significant pollutants into the atmosphere. settles, the building remains structurally sound.
material but when unprotected and exposed Liquid paints on the other hand are typically Be sure to select a manufacturer with
to the weather, steel oxidizes rapidly and red made with greater than 50 percent solvents environmentally friendly construction practices
rust forms. If the steel is left unprotected, it which evaporate into the air during the such as manufacturing materials within 500
will likely rust through in a matter of years. To spraying and drying process. According to the miles of the building site to reduce transportation
protect the steel, a coating of zinc or a mixture EPA, paint solvents are among the chief causes pollutants. Open floor plans, like in many post-
of zinc and aluminum can be applied. The two of pollution. With liquid paints, the explosive frame buildings, maximize natural lighting which
coatings commonly used are galvanized and solvents must be exhausted from inside the reduces the need for electric lighting. In addition,
Galvalume. Galvanized is 100 percent zinc, oven in order to prevent their accumulation the structure allows plumbing, electrical and
while Galvalume is 30 percent zinc and 70 in the ovens air. A curing oven for powder HVAC to be placed between the insulation and
percent aluminum. coatings operates efficiently because there is no finished wall or ceiling, when using a suspended
need to exhaust the heated air, which aids in ceiling. This results in no penetration of the
A building is best accented with an outstanding the preservation of natural resources.
paint coating. A coating that consists of a 70 insulation and an increase in energy efficiency
percent polyvinylidene difluoride (PVDF) topcoat and overall insulation performance. ENERGY
POST-FRAME CONSTRUCTION
or color coat and polyurethane primer that STAR qualified components, such as windows
utilizes a Galvalume metallic coating is arguably The post-frame building you design should and doors, are available in a variety of styles to
superior. This type of coating in an appropriate be matched to site specific geography and maximize the energy performance of a building
color can be ENERGY STAR label qualified climate conditions. Choose a manufacturer that and cool roof paint colors are available that
for roofing applications and contribute to a produces products in the United States and are ENERGY STAR approved for reflectivity in
CONTINUING EDUCATION

roofing applications. These approved colors help metal content are common in the construction that best fit a business needs. Consider a
to reflect sunlight and keep heat away from industry. Prime, pre-engineered commercial post-frame building for any low-rise commercial
the building, which helps to keep the building quality steel is preferable, as is more substrate that setting such as retail, office warehouse, office
cooler and reduce cooling loads. Finally, timber provides additional corrosion protection. Also, building, mini-storage buildings, commercial
frames should be manufactured from renewable high arch-shaped ribs with minor ribs between storage, veterinary clinic, kennel, bank,
resources and siding and roof steel are typically each provide the strongest architectural shape restaurant, child care facilities, car wash, vehicle
recycled and recyclable. These are just some of for withstanding water and weight. Steel panels dealership and repair, and aircraft hangar.
the options available that can add efficiency and should not be welded but rather fastened with
functionality to a post-frame building. screws and nails that add durability.
Post frame buildings are engineered for site and The buildings have many similarities regarding
building requirements; through quality design size, openings, and type of air furnace used.
and materials, they can be constructed to be as The differences lie in the roof pitch and interior
strong as a steel-frame building. The strength insulation used. In the post frame building there
lies in the framing system, from treated columns is a 4 in 12 roof pitch with an attic. 6 inch wall
that add stability, wind resistance and longevity insulation with R-19 and blown attic insulation
to a thin membrane diaphragm that creates an with R-38 is used. In the steel building there is
effective bracing system to resist lateral forces. a 1 in 12 roof pitch with no attic. 3 inch wall
insulation with R-9.5 and 3 inch roof insulation APPLICATIONS
The diaphragm is a flat structural unit
with R-9.5 is used. The table on this slide lists
acting like a deep, narrow beam. The term Whether planning a retail outlet, strip mall, or
actual annual natural gas usage for these
diaphragm is usually applied to roofs and any other commercial building it is important
buildings as predicted by the DOE 2.1E computer
floors. A shear wall, however, is just a vertical for business owners and designers to develop
simulation program, which was developed by
diaphragm. Shear walls provide support for the an inviting, energy-efficient space where they
Lawrence Berkley Laboratories in conjunction
roof and floor diaphragms transmitting forces can conduct their business. Its also vital to
with the Department of Energy. You can see
into the foundation. A diaphragm structure continue drawing in new customers while
that in every location, the therms used were
results when a series of diaphragms are properly maintaining the loyalty of regulars in order
considerably less in the post-frame building.
tied together to form a unit. When diaphragms for the business to succeed. A post-frame
and shear walls are used in the lateral design of Many manufacturers of post-frame buildings building can be customized with features and a
a building the structure acts as a box system. provide written warranties such as a 50 year layout that best suits the business needs.
snow load and a 5 year wind load warranty on
Because of this tremendously wind-resistant Offices and Warehouses
the building structuremuch longer than
box a post-frame structure can outperform
those provided by most steel frame building Business owners who need an office building
many steel structures, even before the siding
manufactures. Be sure to research the actual with the convenience of having a warehouse
is attached. Conversely, steel buildings derive
written warranty on any structure that you attached or an office and storage building for
their strength from a combination of the frame
are using to determine if it is a pro-rated type personal use, will get a building that is durable,
and panels. If either is compromised, the entire
warranty or a non-pro-rated, and whether or efficient and easy to maintain.
building is compromised.
not it includes the labor to make the necessary
repairs or not. Business owners are looking for a space thats
STEEL SIDING AND ROOF PANELS
welcoming to customers while being safe
All steel siding and roof panels are not created Custom building layouts with varying styles, and efficient for employees. Regardless of the
equal. Inferior, imported products with untraceable siding types and floor plans can be chosen industry, a post-frame building will provide a
dependable, professional office building that
Therms saved annually meets the needs of the company. From exterior
Location Therms used steel frame Energy performer ($ savings at $1 per therm)
siding options to interior features and floor
Grafton, ND 6080 9177 3097 plans, post-frame buildings offer the capabilities
Bismarck, ND 5025 7703 2678 of a truly customized office building.
Monticello, MN 4671 7088 2417 Storage Units
Norfolk, NE 3970 6058 2088 When designing a mini-storage building it is
Morton, IL 3690 5621 1931 imperative that it be a long-lasting, low-
Holton, KS 2987 4607 1620 maintenance building that will give customers
a safe and convenient place to store their
Monett, MO 2770 4228 1458 valuables. Whether theyre looking for a space
Conway, AR 1871 2902 1031 to house their collectibles, recreational vehicles
Waco, TX 1217 1926 709 or simply items that dont fit in their home,
post-frame facilities can be constructed where
Gainesville, FL 851 1373 522
customers will be confident renting space.
This chart shows a post frame vs. steel frame insulation comparison.
CONTINUING EDUCATION

Because a variety of people utilize storage units, facility can become a reality. Winery, Brewery, Distillery
from students to renters and homeowners to
A post-frame building can be customized to When a space is needed to house equipment to
business owners, the number of units and size
meet a child care owners needs while providing produce the best wine and spirits, a post-frame
of those units can be customized to best fit the
a comfortable environment for staff and building can offer design flexibility in high,
needs of a community. Mini-storage units can
children to work and play whether in a small open spaces and wide, clear spans. Design and
also be customized both inside and out with
daycare or large community center. construct a small brew or distilling operation or
features including steel, brick and stone siding,
a larger brewery with a restaurant or a winery
wainscot, overhead doors and a variety of
with a tasting room.
insulation options.
Veterinary Clinic/Kennel
A veterinary clinic or kennel owner will want
a long-lasting facility that provides exceptional
service for the animals left in its care. Post-
frame veterinary clinics not only provide a safe,
dependable place for owners to bring their pets,
theyre also a sound investment for the business.
From small, private practices to large clinics
Car Wash
and university learning complexes, space and
budget can be maximized. The facility can be Whether designing a simple building with a CODE-COMPLIANCE
customized to the clinics operation with layouts few stalls or a more elaborate building with an Post-frame construction is code-accepted and
that include a reception room, exam room, office for the business, post-frame buildings code-compliant with all applicable building
surgery room, break room, pharmaceutical offer many choices that can help add visual regulations. Several organizations have developed
storage and boarding facility. interest to a car wash. Best of all, the buildings industry standards for post-frame buildings
are virtually maintenance-free. that are then accredited by other standards
Kennels have become an increasingly popular
form of animal care for owners who are on Vehicle Dealership organizations such as the American National
vacation or out of town for extended periods. Standards Institute (ANSI), the American Society
At a vehicle dealership, potential customers for Testing and Materials (ASTM), and the National
To complement their veterinarian services, many
should find the space visually inviting, and the Fire Protection Association (NFPA). They coordinate
vet clinics now offer kennel services to their
building should be one that beckons them to standards with international standards so that
clients. Since a trust relationship has already
enter. Once theyre in, the atmosphere should American products can be used worldwide and
been established, this can be an ideal situation.
welcome them to stay and talk. The open floor can be adopted into the International Building
Bank plan of a post-frame building allows dealership Code (IBC), a model building code developed by
owners to utilize the interior space of their the International Code Council (ICC).
Trust is the foundation for every successful
building in the best way for the business, while
business relationship and when customers place IBC
clear span trusses provide greater overhead
their funds into the care of a bank, theyre
clearance. These features allow the design The International Building Code is a performance
affirming their trust in the security of that
team to start with a blank canvas and then based code which requires a design to meet cer-
financial institution. Banks, savings and loans,
customize the layout to fit their needs. Virtually tain performance criteria and when the design
credit unions, and other financial institutions can
maintenance-free and energy efficient post-frame does, the design is acceptable. For a structure
be constructed with post-frame construction.
buildings are an ideal structure for a dealership, this performance criteria is meeting wind loads,
Restaurants and with a variety of options available so owners live loads, snow loads, earthquake loads, etc.
can choose the style they want, inside and out. In a few instances, the IBC does address design
Restaurant owners want a space that is
welcoming to patrons while being safe and Aircraft hangars of elements specific to post-frame construction.
efficient for those working inside. Design a An example would be guidance in post depth
Traditional aircraft hangars are steel-framed design, which is found in the code at Section
post-frame building to create a place that is
buildings that can be difficult to insulate and 1807.3 Embedded Posts and Poles.
aesthetically pleasing and functional both inside
even worse to heat and cool. Plus, condensa-
and out. Post-frame buildings are wood structures and
tion can form in steel-framed buildings leaving
Child-Care Facility the aircraft, engine and instruments vulner- as such are classified as Type VA or VB. There
able to rust or deterioration due to build-up. is no minimum required fire resistance rating
When caring for children in an educational or of the elements of Type VB construction. With
Whether an aircraft is used for business, strictly
social setting, its important to provide them some exceptions, the minimum required fire
for hobby, or a combination of both, it is an
with a safe atmosphere and plenty of space. resistance rating of the elements of Type VA
important asset. To protect this investment,
Whether expanding a childcare operation, construction is one hour.
post-frame buildings provide hangars that are
remodeling an existing building or starting a
attractive, functional, strong, and efficient. Certain other standard writing organizations
new center, the vision of a quality, dependable
like ASABE provide standards for specific
CONTINUING EDUCATION

design elements like the ANSI/ASABE EP486.1 (and ceiling) diaphragms, endwalls, intermediate and various other lumber products installed at
that specifically applies to Post Foundation shearwalls, and building frames are the main or below grade for buildings in the use category
Design as does most of the ASABE Standards structural elements of a structural system used system: User Specification for Treated Wood
referenced. These are considered the method of to efficiently resist the design lateral (wind) Products." AWPA specifies UC4A for above-
construction standards. The IBC recognizes and loads. This engineering practice gives acceptable ground uses such as post-frame skirtboards and
approves post-frame construction in accordance methods for analyzing and designing the UC4B for building poles and permanent wood
with the referenced standards. elements of the diaphragm system. foundations embedded within the ground.
ASABE ASABE EP558, Load Tests for Metal-Clad ASTM International
Week-Frame Diaphragms
The ASABE is a professional and technical ASTM F1667Post-Frame Nails sets production
organization comprised of members who are This engineering practice establishes the test standards for threaded hardened nails, and is
dedicated to advancement of engineering procedures and the data analysis procedures referenced in the National Design Specification
applicable to agricultural, food, and biological for determining the in-plane shear strength and (NDS), published by the AWC. NDS establishes
systems. ASABE Standards are consensus in-plane shear stiffness of metal-clad, wood- the technical specifications for the dimensions,
documents developed and adopted by the framed structural diaphragms typically used tolerances and materials for the manufacture
organization to meet standardization needs in post-frame buildings and other sheathing of fasteners. Post-Frame Nails has exceptional
within the scope of the Society; principally in accordance with their performance withdrawal resistance characteristics. This
agricultural field equipment, farmstead characteristics. The in-plane shear strength and unique fastener has been thoroughly tested
equipment, structures, soil and water stiffness are required inputs for the engineering and is recognized by these construction
resource management, turf and landscape practices presented in ASABE EP484.2. industry standards.
equipment, forest engineering, food
This method shall be used for diaphragm This specification covers nails, spikes, staples,
and process engineering, electric power
assemblies constructed with roll-formed and other fasteners driven by hand tool, power
applications, plant and animal environment,
metal sheeting (for example, steel, aluminum) tool, or mechanical device in single or multiple
and waste management. Post-frame structures
attached to any type of wood framing system. strikes and are positioned by hand, tool, or
fall into this category, as they are often used for
If rigid or blanket insulation is to be installed machine. The driven fasteners are classified
agricultural buildings, but the standards apply
between the metal sheeting and wood framing as type one: nails (NL); type two: cut nails
to all post-frame buildings.
in the building being designed, identical (CN); type three: spikes (SP); and type four:
ANSI/ASABE insulation shall be installed in a similar fashion staples (ST). Materials shall be tested and the
in the test assembly. individual types shall conform to the material
In ANSI/ASABE EP486.1, Shallow Post Foundation
requirements and physical properties, such as
Design, the ASABE presents the engineering ASABE EP559, Mechanically
ductility, tensile strength. Protective coating and
basis for determining the depth of embedment Laminated Columns
finishes are also detailed.
for sidewall posts in post-frame buildings. It
This engineering practice presents the rational
presents a rational basis and design procedures NFBA
basis for determining the structural strength
for the required lateral and uplift capacity for the
and stiffness of mechanically laminated columns Finally, the National Frame Building Association
embedded post and for designing the foundation
used in many modern post-frame buildings. The (NFBA) has assembled all pertinent engineering
for a post-frame building. The design procedure
scope of this engineering practice is limited to information from codes and standards into the
provides necessary definitions, material
mechanically laminated columns with three or Post-Frame Building Design Manual, the only
requirements and design equations.
four laminations. current and complete published reference of its
The standard is currently being updated to kind on how to properly design and engineer
AWC
better address numerous considerations post-frame buildings.
including in-situ determination of soil properties; The American Wood Council (AWC) has
prescriptive soil bearing capacity values, which published the Design for Code Acceptance CONCLUSION
are considered too conservative for certain post document "DCA5Post-Frame Buildings" This article looked at the different methods
foundations; minimum footing sizes for plain which provides guidance to post-frame building and materials, as well as performance
and reinforced footings (both cast-in-place and designers for meeting the requirements of measures for post-frame buildings and their
precast; tests for modulus of horizontal sub the 2000 International Building Code and to application in low-rise commercial buildings.
grade reaction; adequacy of the uplift equation; confirm that a properly designed post-frame Post-frame buildings outperform all other
effects of backfill material on lateral strength and building is in fact code compliant. building types in any climate or soil condition,
stiffness; and use of dry concrete mixes. and can be designed to meet the highest
AWPA
ASABE EP484.2, Diaphragm Design standards for quality. Through a combination of
The American Wood Protection Association quality materials, expert workmanship, energy
This engineering practice presents the rational (AWPA) is another industry organization whose efficiency and low maintenance in a post-frame
engineering basis for diaphragm design of standards and EPA documents confirm the building, post-frame buildings are an efficient
post-frame buildings in a format suitable suitability of using properly treated building and economical option and are the construction
for acceptance by architects and engineers, posts in ground contact for permanent edifices. method of choice for low-rise applications.
referenced from IBC section 2306.1. The roof AWPA documents specify treatment of posts