providing intelligent solutions


Why Aegis?

Cost effective
Safe
Maintenance free
Simple operation
Easy to install
Climate independent
Automation ready

To find out more about us, visit:


www.lucyswitchgear.com
Contents

Introduction to Lucy Switchgear 4

Product panorama: Lucy medium voltage and high voltage range 5

Introduction to Aegis 6

Installation and operating conditions 7

Safety features 8

Application examples 9

Aegis range presentation 10

Available configuration 12

Standards 12

Product characteristics 13

General 13

Product presentation
User interface and interlocking mechanism

L: LBS Load Break Switch 14

Standard features
Optional features, factory fitted
Optional features also available as retrofit

Circuit Breaker; T or V modules 15

Standard features
Optional features, factory fitted
Optional features also available as retrofit

Circuit breaker protection 16

TLF
Protection relays
Protection CT (Current transformers) for TLF and relays

Options and accessories 19

Secondary injection
Actuators (motorised)
Cable compartment
Shunt trip coils
Earth Fault Indicators (EFI)

Air metering unit 20

Switchgear automation 21

Cable bushings and cable terminations 22

Technical data sheet 23

Dimensions 24

Order form 26

Page 3
Introduction to Lucy Switchgear

Lucy Switchgear is a global leader in switching, and offers a complete product portfolio, with a wide scope of
protection and automation solutions for services and dedicated after sales support throughout the
electrical distribution systems, with over 100 productlifecycle.
years industry experience. Today the company is A specialist UK research and development facility, with a continuous
a specialist in secondary power distribution, programme of R&D, ensures that Lucy Switchgears products are
engineering high-performance medium voltage always at the cutting edge, designed to anticipate the evolving
technical and market demands of our customers. And our
switchgear for utility, industrial and commercial
multi-million pound, purpose built, state of the art UK
applications, overhead line equipment and
manufacturing facility provides complete control over production.
providing retrofit and automation solutions to
Lucy Switchgear is a truly international company with offices in
customers internationally.
China, Dubai, Malaysia and South Africa; manufacturing facilities in
Engineering excellence, based on a long tradition of expertise, the United Arab Emirates, Saudi Arabia and India; and an established
coupled with state of the art technology to meet customers global network of industrial partners and contractors operating in
stringent specifications, make Lucy Switchgear one of the few over 50 countries worldwide.
companies that can offer truly bespoke solutions. We have the
capability to manufacture units for any location, climate or situation

Ring main unit range evolution

Trident

Scimitar

Sabre

Aegis

1965 1970 1975 1980 1985 1990 1995 2000 2005 2010 2015

Page 4
Product panorama: Lucy medium
voltage and high voltage range
Rated Mode of Rated
Insulation Installation
Ring main units voltage fault current
medium
current Mounting
condition
Operation
(up to) interruption (up to)

Ground / Indoor / Local /


Aegis 24kV Vacuum SF6 630A
Transformer Outdoor Remote

Ground / Indoor / Local /


Sabre 24kV Vacuum SF6 630A
Transformer Outdoor Remote

Ground / Indoor / Local /


Scimitar 17.5kV Fuse SF6 630A
Transformer Outdoor Remote

Ground / Indoor / Local /


Trident 15.5kV Fuse Oil 630A
Transformer Outdoor Remote

Switch disconnectors

Local /
Rapier DSB 145kV - Air 2500A Structure Outdoor
Remote

Local /
Rapier GX 38V - SF6 630A Pole Outdoor
Remote

Local /
Rapier AX 36kV - Air 800A Pole Outdoor
Remote

Page 5
Introduction to Aegis

Aegis is a new generation of Ring Main Units Characteristics:


mainly designed for secondary distribution
12kV, 17.5kV and 24kV ratings
networks up to 24kV. This range is available
in indoor and outdoor formats to suit various Extensible and non extensible range with up to
4 switching functions in a single tank
application needs. All the live parts and switching
functions are insulated with SF6 gas and sealed Hermetically sealed stainless steel tank insensitive
to environment
in a stainless steel tank ensuring a high level
Intuitive single line mimic diagram for simple and
of reliability, personnel safety and virtually
safe operation
maintenance free operation.
Vacuum Circuit Breaker enclosed in an SF6 insulated tank
The structural tank welding is performed by a robotic welding for extra protection against corrosion and pollution
process ensuring high reliability with a product life expectancy of P rovision for motor actuators for remote operation
more than 30 years. The housing is fully treated using zinc coated and control
steel and electro statically applied, oven cured paint to resist
degradation from pollution and harsh climatic conditions. Integrated cable testing facility on front face
eliminating the need for cable disconnection
The transformer protection is by Vacuum Circuit Breaker. On Suitable for indoor and outdoor applications
request, the units can be supplied with integrated automation for
remote monitoring and control functions. V
 arious protection options (TLF, relays) to suit
customer needs
Low roof height designed for kiosks and
mini substations
E asy integration with SCADA network for remote
operation and control
S tandard RAL7032 paint finish with other colours
available on request

Page 6
Installation and operating conditions

IP54 IP41
Outdoor metal clad non extensible units only Indoor extensible and non extensible

i. Indoor and outdoor type units Temperature De-rating Curves


ii. A
 mbient temperature for operation without derating:
40C (for higher temperature applications please refer to 630A at 40C
temperature derating curve below) 700
iii. Average value over 24 hours max: 40C 650
Rated Current (Amps)

iv. M
 aximum altitude for operation without derating: 600
1000m (above sea level)*
550
v. Insulation medium: SF6 Gas
500
vi. Rated pressure at +20C: 0.03 MPa
450
vii. Interruption medium: vacuum
400
* F or higher altitude applications please contact local
Lucy Switchgear sales office. 350

300
40 45 50 55 60 65
Ambient Temperature C

Page 7
Safety features

Operation mechanism Earth and test facility


T he mechanism consists of one operating shaft and one selector. The The cable earth and test facility is an optional feature on the Load
operating shaft is used for switching ON / OFF (Mains or Earth) and Break Switch and the Circuit Breaker. It is located at the front of
the selector is used for selection of the Mains or Earth positions. It is the unit for ease of access. It is used for testing cable insulation
impossible to simultaneously close the Load Break Switch or Circuit and to locate faults in the circuit without the need to remove the
Breaker and the Earth switch. main cables from the cable compartment, which improves the
The mechanism incorporates mechanical interlocks and padlocking operatorsafety.
facilities to improve operator safety. The cable test access cover is fully interlocked and cannot be opened
until the Load Break Switch or Circuit Breaker Switch is in Earth ON
position. The test bushings are earthed with a star bar which has to
be removed for cable tests.

Anti reflex mechanism:


Ensures a time delay between switching operations to allow
sufficient time for the main breaker to trip and clear a fault.
Cable compartment
The cable compartments are located at the front of the units with
Internal Arc withstand horizontal mounted DIN 400 type C bushings for ease of cable
Aegis SF6 Gas insulated stainless steel tanks are fully internal arc connection. Vacuum Circuit Breaker function has factory mounted
rated and this feature is also available on the cable compartment protection CT (current transformers) on the cable bushings for ease
(optional) to ensure maximum operator safety in the event of of installation and to avoid any potential damage to CTduring
internal faults. As standard, all the tanks are rated for AF (operator transit and connections.
safety from the front of the unit) and there is an option to request for F or enhanced operator safety, the cable compartments are earthed
AFL (front and side) and AFLR (front, side and back of the unit). and fully interlocked allowing access to the operator only if the
For more details on IAC ratings, please refer to the technical data function is in Earth ON position.
sheet on page 20. There is an option of supplying these cable compartments with
Internal Arc rating as per IEC standards.

Page 8
Earth bar in cable compartment VPIS
A fully rated copper earth bar is mounted inside the cable VPIS (Voltage Presence Indication System) is an optional feature in
compartment. This earth bar is used to connect the screened cable the Aegis range. It is used for checking the presence of voltages in
connectors through M12 size bolts. The bar runs through the the cables. The VPIS gets a voltage signal through the voltage divider
width of the unit and protrudes 125mm to the rear of the cable built into the cable bushings. They can also be fitted with neon lights
compartment or connection to the main earthing system. For and momentary latching push buttons to show voltage presence
additional safety it is not possible to remove it while unit is live. without needing external testing probes.
Two types of voltage presence indication device are offered:
Pfisterer sockets
N
 eon indicators with push-to-test buttons and phase
comparator sockets

Pfisterer sockets Neon indicator with


push-to-test buttons

Application examples
The key areas of application are:

Energy
i. Generation: wind power, solar power
ii. Distribution: compact substations

Infrastructure: tunnels, airports, ports,


underground railwaystations

Commercial buildings: hospitals,


shopping centres, hotels, office
buildings, data centres

Industries: water and waste water,


mining,minerals, automotive, iron
and steel,paper and pulp, cement
andpetroleum

Page 9
Aegis range presentation

The Aegis range is available in four configurations, ranging from 1function to 4 functions, as shown below.

Functions available:
SW: Switching functions: L: LBS - 12kV/15.5kV : 630A
- 17.5kV: 400A
- 24kV: 400A
CB: Circuit breaker functions: V: VCB - 12kV/15.5kV: 630A
T: VCB - 12kV/15.5kV: 250A
- 17.5kV: 250A
- 24kV: 400A
Metering functions: M1: Busbar metering - 17.5kV: 630A

1-function 2-functions 3-functions

4-functions

Page 10
Non extensible: (12kV/15.5kV, 17.5kV and 24kV)
This range has 3 and 4 functions insulated by SF6 gas in a single
hermetically sealed stainless steel tank. This solution is available in
indoor (IP41) and outdoor (IP54) versions and is perfectly suitable
for integration into compact substations to form standard ring main
secondary networks with transformer protection.

Extensible: (12kV/15.5kV only)


The extensible range is used to add another function on the left,
right or both sides of switchgear installed in secondary networks.
This range has 1,2,3 and 4 functions insulated by SF6 gas in a single
hermetically sealed stainless steel tank. It is an ideal solution if
additional functions are needed in the present or foreseeable future.
Available in indoor (IP41), these units can be easily extended in any
combination on site without specific tooling or floor preparation,
and without the need to transfer SF6 gas.
Busbar extension system
The units are extended as shown in these diagrams:

Extension bushings

Page 11
Available configuration

Non extensible (compact range) Extensible range

Positions of the functions in the unit Positions of the functions in the unit

1st 2nd 3rd 4th 1st 2nd 3rd 4th


L L L L L L L L
Types of functions Types of functions
T T T T T T T T
V V V V V V V V
3 functions unit 1 function unit

4 functions unit 2 functions unit

3 functions unit

4 functions unit

All of the extensible units are available in the following


extensibility functions:
Left hand
Right hand
Both sides

Standards
International Standards
IEC 62271-1
IEC 62271-100
IEC 62271-102
IEC 62271-103
IEC 62271-200

Page 12
Product characteristics
General
Product presentation 1 2
3
4

1 EFI
2 Pressure indicator 5 6

3 Marshalling Box 10
7 11
4 Optional VPIS
5 Earth and Test Facility 8 14 12
13
6 Protection Relay
7 'Push To Trip' Button
8 Circuit Breaker Indication
9 Interlocked Cable Box Cover
10 Disconnector Indication
9 15
11 Cable Test and Cable Box Interlock
12 Disconnector Operation Collar
13 Operation Collar
14 Switch Indication
15 Operating Handle

User interface and interlocking mechanism


Safety interlocking
Each LBS and VCB module has safety interlocked access via a rotary knob on the fascia to enable access to the cable connection compartment and
also the cable test access panel (if specified as an option) located on the fascia.
Operating handle access shafts have the facility for individualpadlocks.

Load Break Switch Circuit Breaker

Position Interlock status Position Interlock status


Load Selector Cable Earth & Test Circuit Selector Cable Earth & Test
Break compartment interlock Breaker compartment interlock
Switch interlock (if fitted) interlock (if fitted)
ON Main Locked Locked ON Main Locked Locked
OFF Main Locked Locked OFF (Tripped) Main Locked Locked
OFF Earth Locked Locked OFF (Reset) Earth Locked Locked
Earth ON Earth Unlocked Unlocked Earth ON Earth Unlocked Unlocked
Earth ON Earth Locked Locked
OFF (Tripped) Earth Locked Locked

Page 13
Product characteristics
Switching functions L: LBS load break switch

Standard features Optional features, factory fitted


T hree positions (ON, OFF & Earth), spring loaded mechanism, Internal arc rating of cable compartment for
independent manualoperation additional safety
S ingle mechanism with two independent operating shafts, one Remote low gas pressure alarm,1N/O (only one per tank)
for switch ON / OFF position and another for selecting in Mains VPIS Voltage Presence Indication System
and Earth operation
Remote switch position indicator
Interlocked selector, locked from operation when
(1N/O,1N/C and 2N/O,2NC)
switch is in ON position
F ully interlocked cable earth and test (E&T) facility
S ingle line intuitive mimic diagram with clear indication to show
without removing main cable connections
the status of switch (ON, OFF or Earth positions)
Short circuit and Earth Fault Current Indicators (EFI)
G
 as pressure indicator with Red and Green sectors to indicate
minimum permissible pressure for safe operation (only one Wiring for motorisation
pertank)
H
 orizontal cable terminations in front with DIN400
type C bushings Optional features also available as retrofit
F ully interlocked cable compartment allowing entry M
 otor operation for Load Break Switch (only if unit is pre wired
only if function is in Earth ON position for motorisation)
P adlock facility (8.5mm diameter hole) for all the W
 ide range of cable clamps, and glands to accommodate 1 and
operating positions 3 core cables (refer to cable compartment section on page 17
for further information)

Page 14
Product characteristics
Circuit breaker: T or V modules
T module 250A and 400A rated vacuum circuit Optional features, factory fitted
breakers for transformer protection. Internal arc rating of cable compartment for additional safety
V module: 630A rated vacuum circuit breaker for Remote low gas pressure alarm,1N/O (only one per tank)
transformer / downstream network protection. VPIS Voltage Presence Indication System
R
 emote circuit breaker position indicator
(1N/O,1N/C and2N/O,2NC)
Standard features
F ully interlocked cable test facility without the need to
T hree functions (ON, OFF & Earth), two position spring loaded remove main cable connections (refer to cable test facility
mechanism, independent manual operation forfurtherinformation)
S ingle mechanism with two independent operating shafts, one Self-powered relay for protection (customer specific)
for circuit breaker ON/OFF position and another for selecting
disconnector in Mains or Earth (isolation) TLF (Time Limit Fuses) for alternative protection

Interlocked disconnector selector, locked from Wide range of Current transformers for TLF and Relay protection
operation when circuit breaker is in ON position Shunt trip coils for external tripping
Mechanical push-to-trip button for local operation Wiring for motorisation
Trip coil for receiving tripping signal from relay or TLF devices
Protection function TLF or relay (customer specific) Optional features also available as retrofit
S ingle line intuitive mimic diagram with clear indication to show M
 otor operation for CB (only if unit is pre wired
the status of switch (ON, OFF or Earth positions) formotorisation)
G
 as pressure indicator with Red and Green sectors to indicate W
 ide range of cable clamps, and glands to accommodate 1 and
minimum permissible pressure for safe operation (only one 3 core cables (refer to cable compartment section on page 17
pertank) for further information)
H
 orizontal cable terminations at front of unit with DIN 400 C
type bushings
P rotection CT (current transformers) mounted on
cable bushings (customer specific)
F ully interlocked cable compartment allowing entry
only if function is in Earth ON position
P adlock facility (8.5mm diameter hole) for all the
operating positions

Page 15
Product characteristics
Circuit breaker protection
Two types of protection devices are offered to protect the circuit breaker;
TLF : Time limit fuses
Protection relays

TLF
When utilised in conjunction with circuit breaker type ring main
units, time limit fuses (TLF) are a cost effective method of providing
fault protection for overcurrent and earth faults (optional) to
a transformer of 2000kVA or less. It is a recognised method
of protection and was developed to comply with EA 41-26
(nowsuperseded by ENA TS 41-36) with fuse links in accordance
with ENATS 12-6.
It should be noted that the TLF protection system is not a device for
limiting overload levels of individual transformers. It should be used
for fault protectiononly.
T he TLF system provides protection for overcurrent and earth
faults between the MV circuit breaker and the LV protection
device. Theselected TLF rating should be such that it allows for
discrimination between the MV & LV devices. This will ensure
that the circuit breaker does not open for faults beyond the LV
distributorprotection device.
Fuse dimensions: Length 57mm x Diameter 13mm
 hen fitted with TLF, the ring main unit can also be configured
W
to enable tripping of the circuit breaker from remote devices
(Bukholtz,LV CB etc).
Lucy Switchgear customers in Europe, the Middle East, Africa
and Asia are currently using TLF protection system within their
distribution networks.

RMU

TLF

Transformer

LV distribution
Panel

Page 16
Recommended TLF settings

Transformer ratings (kVA)


200 315 500 800 1000 1250 1600 2000
Rated voltage (kV) TLF fuse rating (A)
3.3 10A
CT ratio
50/5 6.6 5A 10A 15A
11 3A 5A 10A 15A
Earth fault setting =
25A 13.8 3A 5A 10A 15A
(instantaneous trip)
24 3A 5A 7.5A
3.3 5A 10A 15A
CT ratio
100/5 6.6 5A 7.5A 12.5A 15A
11 5A 7.5A 10A 12.5A 15A
Earth fault setting =
30A 13.8 5A 7.5A 10A 12.5A 15A
(instantaneous trip)
24 5A 5A 7.5A

Advantage of vacuum circuit breaker with TLF over HV fuses

Feature VCB with TLF Fuse switch


Overall cost of units Similar
Approximate fuse replacement cost $5 $50
Maximum rating of transformer, can be protected 2MVA* 1MVA
Maximum rated normal current 630A 200A
Physical size of fuses Small Large
Possibility of some pollution while changing fuses causing PD and flash over issues No Yes
Fuse location inside the unit LV side HV side
Range of fuses required for different rated transformers Very small with multi ratio CT Large

*No issues with transfer current switching to IEC 62271-105, which minimizes the MVA rating

Advantage of vacuum circuit breaker with TLF over protection relays

Feature VCB with TLF Protection relay


Installation cost of function Low High
Auxiliary power source for operation Not required As required
Delay in activation of trip function due to capacitor charging time lag Not delay Delay
Employee training on setting tripping curves Not required Required
Additional training on different manufacturer setting up procedure Not required Required
Maintenance and repair cost Low High
Operating temperature limitations None Up to 70 C
Range of fuses required for different rated transformers Yes Yes
Over current and earth fault protection Yes Yes

Page 17
Product characteristics
Circuit breaker protection

Protection relays Manufacturer Woodward


The Aegis range can be fitted with self-powered relays for protecting Range WIP1
the transformer or downstream network from fault currents by Functions
tripping the Circuit Breaker. These relays incorporate many advanced
Phase overcurrent
features and have a variety of settings to provide discrimination
protection in networks. The self-powered feature eliminates reliance Short circuit protection
on external power sources and increases the performance and Number of overcurrent elements 2
reliability of the protection function. Earth overcurrent
To the right are the technical characteristics of the Woodward WIP1 Number of earth overcurrent elements 2
relay, offered as a standard on the Aegis range (if ordered with relay
function). Other manufacturers relays can also be incorporated into
the units on request. Characteristics
Display (measuring values and parameters)
Setting via buttons
Standard CT 1A
LED pickup
LED trip indicator
Flag indication output
Fault memory
Clock
Password protection
Electro impulse and relay contact output
Number of output relays 3 C/O
Protection CT (current transformers) Input remote tripping
for TLF and relays Interface O
The protection CT are used in conjunction with Relays or RS 485 interface with pro open data protocol O
TLF protection to protect a wide (kVA) range of distribution RS-485 interface with Modbus protocol O
transformers. A comprehensive range of CT (current transformers) is
Additional power supply O
available to suit varied application requirements.
Dual Ratio CT 100/50/-
Dual Ratio CT 200:100/- Key Standard O Option

Triple Ratio CT 150:100:50/-


An extensive range of additional CTs are available on request, please Other manufacturers relays are also available on request,
contact our local sales office for more information. please contact our local sales office for more information.

Page 18
Product characteristics
Options and accessories

Secondary injection Shunt trip coils


S econdary injection is used to test the relays or TLF operation Shunt trips are magnetic coils
without switching on the high voltage supply to the unit. A low and are used to trip circuit
voltage is applied to the secondary side of the CT connection breakers through local push
(located in terminal box) to test the operation of the protection buttons, RTUs or additional
devices at the time of commissioning and routine tests. transformer protection devices.
Shunt trips are available in the
Actuators (motorised) following voltages;
Aegis units are fitted with 24V DC DC voltage: 12V, 24V, 48V and 110V
motors, which can be powered from
AC voltages: 110V, 240V
the Gemini remote terminal unit (RTU)
24V DC battery in the event of mains Multiple voltage range: 24VDC 240VAC
AC supply failure.
Earthfault indicators (EFI)
Cable compartment Earth fault indicators (EFI) are used for rapid location and isolation
 ll the cable clamps, glands and cable
A of faults on medium voltage networks in open loop ring main
compartment sealing devices are available as retrofit options. Below networks. When the unit detects asymmetrical currents greater than
is the list of clamps available in metal (steel) and plastics. 50A in the 3 phase cable an earth fault is indicated by means of a
Single 3 core cable flashing LED or mechanical flag.

3 single core cables Below is the list of EFIs available for the Aegis range.

An extensive range of additional


cable compartment clamps and
sealing devices are available on
request, please contact our local
sales office for more information.

Single 3 core cable 3 single core cable

Manufacturer model: Suparule Sensorform BLZ-50 BFZ-50 MFZ-50 MLZ-50 CFZ-50 CLZ-50

Features
Power source 3.6V lithium AA 850mAH battery 110-240V a.c. CT on current carrying phase
Voltage range 1 38kV
Trip current 50A
Primary indication LED Mech-flag (RED) LED Mech-flag (RED) LED
Flashing duration >1000 hrs - - 10 hrs - 10 hrs
Minimum fault duration 2.5 cycles
Manual reset Push button
Automatic timer reset 4 or 8 hrs selectable 10 secs after mains restore
Manual trip test Push button
Operating temperature -40C to +80C
Operating humidity 0-100% RH
Ingress protection IP65
Current sensor diameter: CT100: 100mm
CT150: 150mm O O O O O O
CT300: 300mm O O O O O O
Remote flashing LED indicator O O O O O O
Auxiliary relay, 1N/O latching O O O O O O

Key Standard O Option Other manufacturers EFIs are also available on request, please contact our local sales office for more information.

Page 19
Air metering unit

AMU features
Busbar metering with extensibility on both sides
17.5kV and 630A rating
Rated lighting impulse voltage (BIL) 95kV
Power frequency voltage 38kV
IP41 for indoor installation
DIN 400 type C bushings for busbar connection
20kA 1-3 sec IAC rating
Ambient operation temperature -25 C to 40 C
HV fuse protection for VT
Anti-condensation space heater (option) Busbar metering
Wide range of CT and VT

AMU low voltage compartment


Facility to lock and seal the terminal (marshaling) box
Provision to disconnect and short circuit the CTs
DIN96 size KWH meter, ammeter and voltmeters
MCB/fuse protection for VT secondary side

Air metering unit

Page 20
Switchgear automation

The Gemini RTU is an advanced, highly flexible and ultra-efficient solution for remote
operation and control of electrical distribution networks. Enclosed in a stainless steel
casing for maximum protection, the Gemini RTU is designed to operate in the most
demanding environments.

The key features of the Gemini range are: In addition to the features
Embedded auto change over and auto sectionalising functions opposite, remotely monitored
C
 ontrol and monitoring of up to 4 motorised functions and controlled switchgear
(switches or circuit breakers) provides significant benefits
Inbuilt earth and fault passage indicators to customers such as:
A
 dvanced monitoring of current, voltage, battery condition, R
 educed time in diagnosing system anomalies as well
temperature compensation, switching status, automatic cooling as locating and isolating faulty sections of network
system, gas pressure etc Faster response time and quick network reconfiguration
F lexible communication through radio, RS232, RS485, packet O
 ptimisation of asset management through the implementation
data network, GSM, GPRS, PSTN, Bluetooth, ethernet TCP/IP, of customised automation schemes
optical fibre and SMS messaging
R
 educed operational cost associated with routine
Advanced battery back to operate under mains AC input failure networkswitching
F ully tested to ENATS (Energy Network Association Technical Increased operator safety
Standards), EMC and environmental standards

Gemini RTU specification


General Enclosure Stainless steel
Degree of protection IP54
Operating temperature -25 to 60C
Relative humidity Up to 95%
Method of mounting Floor, wall, pole or RMU switchgear
Dimensions H 600mm, W 400mm, D 210mm
RTU hardware Processor module ARM9 microprocessor
Power supply 110 / 230V AC supply over and under-voltage protection
Battery type 2 x 12V DC, sealed lead acid or high temperature NiMH
Battery charger Temperature compensated, fully protected
Control electronics PIC based processor with expandable I2C bus
Inner enclosure Stainless steel
Ventilation Microprocessor controlled, long life fan with baffle air intake filter
Inputs / outputs Digital inputs 14 isolated digital inputs expandable
Digital outputs 8 isolated digital outputs expandable
Analogue inputs 3 CT analogue inputs as standard (DIs reduced to 11)
Expansion I/O module 3 AIs / 4 DIs; 7 DIs / 2 DOs
Communications Communication interfaces 3 RS-232 for control (ethernet option), configuration and programming plus one expansion bus
Protocols DNP3, IEC 60870-5-101/104 and modbus (others on request)
RS-232 / 485, UHF / VHF radio, packet data, GSM / GPRS / EDGE, PTSN, leased or twisted pair lines,
Communication media
optical fibre, ethernet (TCP/IP) and Bluetooth
Membrane push-button for open / close operations in conjunction with activate push-button up to four
Switchgear interface Controls switching functions (standard 1, 2, 3 or 4 switch control formats)
Selector control for off, local or remote modes
RTU services such as DC / AC supplies, dummy control and debug LEDs
Switch status LEDs for open / closed positions
Indications
Control Output LEDs (illuminates when active)
Configurable LED indications
Software Cables Plug-in, multi-core umbilicals to switchgear
Configuration Windows-based software Protocol parameters including device and I/O addresses
for configuration of: Parameters for the communications device
Parameters for digital, analogue and counter points
Automation sequences
Power saving routines
Battery tests

Page 21
Cable bushings and cable terminations

The bushings for each ring switch and circuit


breakers are located at the front of the unit. All
sets of bushings are type C with in-line bolted
connections M16 threaded in accordance with
EN50181.
The bushings are accessible by removing the interlocked cable
compartment covers at the front of the unit.
The maximum cable size that can be used is:
300mm 3 - core
500mm single - core.
The following types of terminations can be used with the Aegis:

Insulating bushing boot Heat shrink insulating bushing boot

Profile 'C' bolted separable

Page 22
Technical data sheet

General Circuit breaker V and T function


Rated voltage kV 12/15.5 17.5 24 Rated normal current

Rated frequency Hz 50 60 50 V function A 630 - -

Rated lightning impulse withstand voltage T function A 250 250 400

Directly earthed kV 95 95 125 Rated active load breaking current A 630 250 400

Across disconnector kV 110 110 145 Rated short circuit breaking current kA 20 21 20

Rated power frequency withstand voltage Rated short circuit making current kA 50 54.6 50

Directly earthed kV 38 38 50 Rated cable charging breaking current A 25 31.5 31.5

Across disconnector kV 45 45 60 Rated short time withstand current

Protection Main electrical circuit

Tank with HV parts IP IP67 1 sec kA - 21 -

LV control box IP IP41 3 sec kA 20 - 20

Front face + mechanism IP IP41 Earthing circuit

Cable box IP IP41 1 sec kA - 21 -

Mechanical impact protection IK IK07 3 sec kA 20 - 20

Internal arc rating Mechanical endurance class

Freestanding kA 1 sec 21kA 1 Sec Circuit breaker M1/2000

Optional cable box kA 1 sec 21kA 1 Sec Earth switch M0/1000

AF (gas chamber) Standard Electrical endurance class

AFL (gas chamber) Optional Circuit breaker E2/2000

AFLR (gas chamber) Optional Earth switch E1

SF6 gas Operating mechanism

Filled pressure Bar (G) 0.4 0.4 0.5 Tripping time ms <80 <80 <80

Across disconnector Bar (G) 0 0 0.3 Operating sequence for mechanism 0-3min-CO-3min-CO

Annual leakage rate 0.1% per annum Local: close / open Hand lever / pushbutton

Installation conditions Remote: close / open Motor / coil

Ambient air temperature (without derating) C 40 55 55

Maximum altitude (without derating)* M 1000 Load break switch: L function


Relative humidity (max) - over period of 24hrs Rated normal current A 630 400 400
95%
(IEC 62271-1, sub-clause 2.1) Rated active load breaking current A 630 400 400

Rated short circuit making current kA 50 54.6 50


* For higher altitude applications please contact local Lucy Switchgear sales office.
Rated cable charging breaking current A 10 10 16

Rated short time withstand current

Main electrical circuit


BusBars
Rated normal current A 630 400 400 1 sec kA - 21 -

Rated short time withstand current 3 sec kA 20 - 20

1 sec kA - 21 - Earthing circuit

3 sec kA 20 - 20 1 sec kA - 21 -

Rated peak withstand current kA 50 54.6 50 3 sec kA 20 - 20

Mechanical endurance class

Load break switch M2/5000 M2/5000 M2/5000

Earth switch M0/1000 M0/1000 M0/1000

Electrical endurance class short circuit making

E3-5 E1-2 E1-2


Load break switch
(times) (times) (times)

E3-5 E1-2 E1-2


Earth switch
(times) (times) (times)

Operating mechanism

Local: close / open Hand Lever

Remote: close / open Motor

Page 23
Dimensions
Aegis ring main unit

500mm 840mm 1235mm

1-function 2-functions 3-functions

1650mm 886mm
A

50mm
4-functions

Cable Termination Height Dim Dim


(Distance between cable clamp and bushings) A B
450 1095 575
600 1245 727
800 1455 940

1: L function height is not affected with addition of E&T facility


2: For V & T functions with E&T facility add 150mm to overall height Aof the unit

Page 24
Dimensions
Air metering unit

617mm 967mm
1244mm

Page 25
Aegis order form
To use this form, please photocopy and return the completed form to your nearest Lucy Switchgear office (addresses can be found on the back cover)

Name: Company:
Address: Tel no:
Fax no:
Email:
Order number:

Order quantity / number of units (please fill separate form for each type)

Extensibility (choose any one) Non extensible


Extensible left hand right hand both sides
IP rating: Installation conditions (choose any one)
IP54 Metal clad outdoor (available for non extensible range only)
IP41 Indoor (available for extensible and non extensible range)
Colour RA L7032 as standard (other colours are only available on request)

Features common to all functions

Voltage rating (choose any one) 12kV


15.5kV

17.5kV

24kV

Low gas pressure alarm 1N/O (tick if needed, only one per tank)
Number of ways and functions needed at each position:
Starting from the left, write any one of L, V or T in each box depending upon the
First Second Third Fourth
number of ways needed. (e.g. 1 function) (e.g. 2 function) (e.g. 3 function) (e.g. 4 function)
Voltage range
Functions current ratings 12kV/15.5kV 17.5kV 24kV
L 630A 400A 400A
T 250A 250A 400A
V 630A - -

For example: L V T L
Motor wiring (tick for each selected function, if needed)
Motor for remote operation (tick for each selected function, if needed)
Cable Earth & Test facility (E&T) (tick for each selected function, if needed)
Cable bushings termination height (choose any one) 450
600
810
Cable box: Internal arc proof
VPIS (choose any one) Neon indicator with push to test button
Pfisterer socket
Auxiliary switches (choose any one) 1N/O, 1N/C
2N/O, 2N/C
Cable compartment
Cable clamp material (choose any one) Metal
Plastic
Cable entry type (choose any one) 3 single core cable
Single 3 core cable

Page 26
Optional features applicable to L (Load Break Switch) function only

Rated current (choose any one) 400 Amps

630 Amps

EFI (choose any one) BFZ-50

MFZ-50

MLZ-50

CFZ-50

CLZ-50

BLZ-50

Any other*

Optional features applicable to V or T (Vacuum Circuit Breaker) function only

Secondary injection (tick for each selected function, if needed)

Protection device (choose any one) TLF (Time Limit Fuses)

WIP1

Other*

Protection (CT) current transformer for TLF or Relay (choose any one)

Dual (Primary) Ratio CT 100:50/-

Dual (Primary) Ratio CT 200:100/-

Triple (Primary) Ratio CT 150:100:50/-

Manual Push To Trip button (tick for each selected function, if needed)

Shunt Trips (choose any one) 12V DC

24V DC

48V DC

110V DC

110V AC

240V AC

Multiple voltage (24V DC - 240VDC)

Note: The ring main units gas chamber are supplied with AFL (Front and sideways) rating.
If you require units with AFLR (Front, side and rear) ratings please contact our local sales office.

*Please fill the details in comment section below.

Comments

Page 27
Disclaimer
Lucy Switchgear has a policy of continuous research and
development and accordingly reserves the right to change the
design and specification of its products without prior notice.

Lucy Switchgear worldwide offices

Lucy Middle East FZE Lucy Switchgear Arabia Co. Ltd. Lucy Asia Pacific Sdn Bhd
PO Box 17335, Jebel Ali, Dubai, Novotel Business Centre, L13A-03-03A, PJX-HM Shah Tower,
United Arab Emirates P.O. Box 35340, Dammam 31488, No16A Jalan Persiaran Barat,
Tel: +97 148 129 999 Saudi Arabia 46050 Petaling Jaya, Selangor, Malaysia
Fax: +97 148 129 900 Tel: +966 3 8147 910 Tel: +603 74910700
Email: salesme@lucyswitchgear.com Fax: +966 3 8147 914 Fax: +603 79316923
Email: salessa@lucyswitchgear.com Email: salesmy@lucyswitchgear.com
Lucy Switchgear Ltd.
Howland Road, Thame, Oxfordshire, Lucy Switchgear (South Africa) Lucy Electric (Beijing) Co. Ltd.
OX9 3UJ, United Kingdom Unit 2, Cranberry Industrial Park, Cranberry Street
Tel: +44 1844 267 267 General Laser Park, Honeydew, 2170, South Africa
Tel: +44 1844 267 222 Sales Tel: +27 11 025 7490 18A1122
Fax: +44 1844 267 223 Fax: +27 11 794 3277 : 100027
Email: salesuk@lucyswitchgear.com Email: salesza@lucyswitchgear.com : +86 1059 231 176
: +86 1059 231 177
Postal Address:
: salescn@lucyswitchgear.com
P.O. Box 1078, Honeydew, 2040

To find out more about us, visit:


www.lucyswitchgear.com

LSAEG0314

Vous aimerez peut-être aussi