Hydro UNI-NB/NK
Grundfos fire systems
Unit configuration
System diagram 8
Components and materials 8
Configuration drawing 9
Unit description
Operating pressure 10
Hydraulic components 10
Inspection and checks 10
Jockey pump options 10
Accessories 10
Versions on request 10
Duty pumps
General description of duty pumps 11
Operating conditions 11
Description of construction 11
Motor 12
Jockey pump
Product description 13
Operating conditions 13
Description of construction 14
Control panels
Control panels of duty and jockey pumps 15
Installation
Requirements to the room 16
Requirements to the pipework 16
Requirements to control panels 16
2
Applications Hydro UNI-NB/NK
Performance range
3
Product description Hydro UNI-NB/NK
Please note that in the following the term unit covers The pumps are prepared for the connection of a priming
the fire pump set described in this data booklet, circuit in the case of suction lift installation.
whereas the term system covers the fire hydrants or In order to prevent damage caused by overheating due
sprinkler systems of a building. to possible operation against closed isolating valve, the
In accordance with UNI 9490, Hydro UNI-NB/NK units pumps are equipped with connection for a bypass.
with one duty pump are designed for fire systems of the To ensure correct operation of the jockey pump, the
low hazard class type, units with two duty pumps are unit must be equipped with at least two 24-litre, PN-16
designed for fire systems of the ordinary hazard class diaphragm tanks. Additional tanks may be connected to
type. a port fitted for the purpose in the discharge manifold.
Hydro UNI-NB/NK are normally supplied as factory- A common suction manifold is available as an option. A
tested units equipped with unit with suction manifold is called complete (CPL) ver-
One or two Grundfos NB or NK single-stage, end- sion.
suction electrically powered duty pumps.
In two-pump units Other fire pump sets for fire fighting
- each of the two pumps must be capable of achiev-
Apart from the Hydro UNI-NB/NK, the Grundfos fire
ing the required performance (one pump is a
standby pump), system product range according to UNI standards
- the two pumps must be supplied from separate includes
power supplies to ensure continued operation in Hydro Syntex-NB/NK fire pump set with two hori-
case of power cut or failure to the first duty pump. zontal, single-stage, end-suction pumps (NB/NK) of
See Duty pumps on page 11. which one is electrically powered and one is diesel
One Grundfos CR multistage electrically powered powered
jockey pump. The jockey pump is also connected to Hydro Diesel-NB/NK fire pump set with one (or
the common discharge manifold. two) horizontal, single-stage, end-suction, diesel
The jockey pump automatically maintains pressure powered pumps (NB/NK)
in the system in case of leaks and prevents the duty
Hydro UNI-CR fire pump set with one or two verti-
pumps from starting up when not required.
cal, multistage, in-line, electrically powered pumps
See Jockey pump on page 13.
(CR).
One separate control panel for each pump.
See Control panels on page 15.
4
Identification Hydro UNI-NB/NK
Type key
Fixed number
Fire pump set
B HUNI NB/NK: One or two NB or NK pumps with one jockey pump
Hydraulic variants
A Standard version
B With suction manifold (CPL version)
C With discharge manifold dimensioned for two pumps operating simultaneously
D Variant B + variant C
E Without flowmeter and test circuit
F* Bronze impeller in duty pumps
G Stainless steel manifold
H CPL version with stainless steel manifolds
Duty pump variants
A Standard version
B Programmable and automatic test of duty pump(s)
E Timer on duty pump (according to UNI 10779)
H Timer and automatic test of duty pump (according to UNI 10779)
L Starting method differs from standard (DOL or SD)
Jockey pump variants
A CR 3 pump
2 CR 5 pump
5 CR 10 pump
6 CR 15 pump
Serial number (consecutive numbering)
* Optional except for NK 80/M, NK 80/P, NK 100/C and NK 100/E, see Material specification on page 11.
5
Unit functions Hydro UNI-NB/NK
6
Unit functions Hydro UNI-NB/NK
Operating conditions
Flow rate Up to 320 m3/h per pump.
7
Unit configuration Hydro UNI-NB/NK
System diagram
Configuration (example):
Two duty pumps + one jockey pump
Ref. Description
Aca Priming circuit connection *
Acr Bypass connection *
CA Suction manifold (optional)
CM Discharge manifold
M Pressure gauge
Mp Flowmeter
Mv Pressure and vacuum gauge
Pj Jockey pump
Pr1 Pressure switch (discharge pressure)
Pr2 Pressure switch (cut-in, cut-out of pump)
Ps Duty pump
Rm Multi-function valve for pressure gauge
Sm Diaphragm tanks, 24 litres, PN 16 (accessory) **
Vi(t) Isolating valve (ball valve)
Vid Isolating valve on discharge side (butterfly type)
Isolating valve on suction side (ball or butterfly
Vis
type)
Vr Spring-loaded non-return valve
Inspectable non-return valve on discharge side
Vrd
of duty pump
* Connections to be made during installation
** During installation, fit at least two 24-litre diaphragm tanks,
PN 16, see Accessories on page 10 and Installation on
page 16.
8
Unit configuration Hydro UNI-NB/NK
Configuration drawing
The following drawing shows the standard configuration of a Hydro UNI-NB/NK unit with two duty pumps. For any
changes or adaptations to specific requirements or additions of optional components and/or accessories not included
in our standard scope of supply, please consult Grundfos.
CM: Discharge manifold Ps: Direct coupled duty Pr2: Pressure switch (cut-in, cut- M: Pressure gauge with
pumps out of pump) Rm: multi-function valve on duty
pump discharge
Hydro UNI-NB units are normally supplied pre-assem- duty pump on its own base frame with pre-installed
bled on a common base frame. The pumps are fitted by hydraulic components
means of bolts and the control panels are fastened on discharge manifold with accessories fitted
stands. test circuit manifold with isolating valves and a flow-
Hydro UNI-NK units are normally supplied in separate meter
macro-components. This is due to the size and weight pump control panels on separate stands
of individual parts and to facilitate shipping, handling jockey pump fastened to the same base frame as
and positioning at the installation site. The separate the control panels.
components are normally
9
Unit description Hydro UNI-NB/NK
10
Duty pumps Hydro UNI-NB/NK
General description of duty pumps The BAQE seal is not suitable for liquids containing
abrasive particles. Modified versions are available as
The duty pumps (or supply pumps, as they are called in
options.
UNI 9490) are designed in accordance with UNI 9489
with specific reference to Bearing bracket (NK)
performance tolerance (according to ISO 9906 An- NK pumps include a bearing bracket with two sturdy
nex A) lubricated-for-life ball bearings.
value for NPSHR Material specification
maximum head.
NB, NBU pumps are of the close-coupled type. Pos. Component Material
1 Pump housing Cast iron 250 UNI - ISO 185
NK pumps are of the long-coupled type. 2 Pump head Cast iron 250 UNI - ISO 185
All pumps are end-suction, single-stage, centrifugal 3 Impeller Cast iron 250 UNI - ISO 185
3 Impeller * Bronze GCuSn5Zn5Pb5 - UNI 7013/8A-72
pumps with volute casing, axial suction port and radial
4 Pump shaft (NB) Stainless steel AISI 304 - UNI 6900/71
discharge port, with flanges complying with DIN 2533.
5 Pump shaft (NK) Stainless steel AISI 420 - UNI 6900/71
Rated performance and main dimensions comply with 6
Mechanical shaft
Carbon/Silicon carbide - EPDM
seal
DIN/EN 733 (formerly DIN 24255).
7 O-ring FPM
All pumps are dynamically balanced to guarantee relia- 8 Spacer Stainless steel AISI 304 - UNI 6900/71
bility and durability. 9 Cover Cast iron 250 UNI - ISO 185
10 Air vent screw Stainless steel AISI 304 - UNI 6900/71
Operating conditions * Optional except for NK 80/M, NK 80/P NK 100/C, NK 100/E, see Electri-
cal data and performance data of duty pumps on page 18.
Description of construction
8 9
Impeller
The impeller is of the double-curved, closed type with 3
smooth blades ensuring high efficiency.
All impellers are hydraulically balanced to compensate
for the axial thrust and to minimise the effect of load on 1
the shaft and seal.
TM03 3494 0406
11
Duty pumps Hydro UNI-NB/NK
12
Jockey pump Hydro UNI-NB/NK
tional reliability. Maximum inlet pres- Equal to the difference between 16 bar and the
sure maximum head of the specific pump model
The pump has a base and a pump head. The chamber Suction lift Influenced by NPSH value (max. 3 m), see also
Operating conditions on page 7
stack and outer sleeve are secured between the base
and pump head by means of staybolts. The base fea- Pumped liquid
tures in-line suction and discharge ports, with Grundfos Thin, clean, non-explosive liquids, not containing solids
oval and DIN flanges. or fibres and mechanically and chemically non-aggres-
sive to the pump materials.
The vital parts of the pump, such as shaft, outer sleeve,
chambers and impellers are made of stainless steel.
13
Jockey pump Hydro UNI-NB/NK
Material specification
Electric motor
Grundfos CR pumps are equipped with a Grundfos MG
three-phase, two-pole, squirrel cage, totally enclosed,
fan-cooled motor with dimensions complying with IEC
and DIN standards.
14
Control panels Hydro UNI-NB/NK
Ref. Component Duty pump Jockey pump Ref. Component Duty pump Jockey pump
Metal cabinet IP 54 z z Indicator lights
Mains voltage on z
A Mains switch, lockable z z
G Auxiliary circuit supply on z
Relay z H Pump ready for operation z
Fuse and contactor circuit z z I Pump operating z z
L Voltage to motor (two LEDs) z
Transformer with fuses for auxil-
z z M Voltage or phase failure (two
iary circuit z
LEDs) with relay and buffer battery
B Ammeter z
Relay operation z
C Voltmeter z
Voltmeter selector 0-L1/L2-L2/
D z Other outputs
L3-L1/L3-0
E MAN-0-AUT selector switch z z Potential-free NO/NC-contact for
Selector switch with key, only remote indication of power and/or z
z phase failure.
removable when in position AUT
Potential-free NC-contact for
F Start-stop buttons for test or man-
z remote indication that pump is z
ual operation
operating and pressure supplied.
V A
C A B
D E F G H I L M
0 0 0
START L1/L2 L2/L3 L1/L3
I
TM03 3499 0406
15
Installation Hydro UNI-NB/NK
Requirements to the room To facilitate installation, the pumps are fitted with com-
The UNI 9490 standard stipulates that a fire pump set ponents designed for the connection of a priming circuit
for fire fighting must be located in a room designed in the case of suction lift conditions.
exclusively for fire systems. To ensure the due precision of the flowmeter, follow the
The UNI 10779 standard on fire hose reel and hydrant instructions in the installation and operating instruc-
systems allows the installation of a fire pump set for fire tions when connecting the flowmeter downstream.
fighting in rooms shared with other engineering sys- If determined by specific system requirements, the test
tems provided the fire load in the room is low. manifold and flowmeter may be fitted reversely to the
The Hydro UNI-NB/NK units must be installed in a factory configuration during installation.
weatherproof, frost-free, well-ventilated room so as to To ensure correct operation of the jockey pump, the
ensure that the electric motors are satisfactorily cooled. unit must be equipped with at least two 24-litre, PN 16
According to UNI 9490 the ambient temperature must diaphragm tanks, see Product description on page 4,
be below +40C when the pumps are operating at max- System diagram on page 8 and Accessories on
imum load. page 10. If necessary, additional diaphragm tanks may
The unit must be placed with sufficient clearance in be connected to the discharge manifold.
front of it and at the sides for inspection, testing and
maintenance. The unit must be placed on a flat, even Requirements to control panels
surface, such as a concrete floor or foundation. If the To meet the requirements of UNI 9490, connect the
unit is not equipped with vibration dampers, it may be duty pump control panels with remote alarm equipment
bolted direct to the floor or foundation. to indicate power, phase failure and start-up of pumps.
The alarm equipment should
Requirements to the pipework give audible and visual signals
The pipes connected to the unit must be of appropriate
be equipped with a buffer battery
size. Provide expansion joints on the discharge mani-
fold - and the suction manifold, if fitted - to prevent res- be installed in a manned area, see Accessories on
page 10.
onance or mechanical stress due to incorrect
alignment.
Always install pipe hangers on both the discharge and
suction sides to ensure that the weight of the pipes
does not rest on the manifold (including the suction
manifold, if fitted) or on the pump.
16
Product selection Hydro UNI-NB/NK
Required head: 60 m.
From the 50 m3/h move down till you come to the part of the table with the heading Head. Move further down-
wards till you come to a figure equal to or slightly below/above the required head, in this case 62. The unit best
meeting this requirement is the 15 kW HUNI NBU 40/B which supplies a head of 62 m.
Jockey pump
The column on the far right of the duty pump performance tables states a reference letter for the jockey pump. If
you take this reference letter to the tables on page 19, you will find the jockey pump for your unit - in this case a
1.1 kW CR 3-15.
17
Technical data Hydro UNI-NB/NK
Duty pump NK 80 3
Flow [m /h] with 1 duty pump in operation
Jockey
P2 I1/1 Starting 0 140 155 170 185 200 215 230 240 250 pump
Unit
[kW] [A] method Head [m]
HUNI NK 80/A 30 53 46 43 42 40 38 36 33 A
HUNI NK 80/B 37 64 51 50 49 47 45 43 41 38 A
HUNI NK 80/C 37 64 56 56 55 53 52 50 48 45 A
HUNI NK 80/D 45 78 63 63 62 61 59 57 55 A
HUNI NK 80/E 45 78 63 63 62 61 60 58 56 54 52 A
HUNI NK 80/F 55 96 SD 72 72 71 69 67 64 61 58 A
HUNI NK 80/H 55 96 75 75 74 72 70 67 64 61 58 A
HUNI NK 80/L 75 130 83 82 81 80 78 76 73 70 68 66 B
HUNI NK 80/M 75 130 90 90 89 87 85 83 80 77 74 B
HUNI NK 80/P 75 130 95 95 94 93 91 89 86 83 B
HUNI NK 80/R 75 130 98 97 96 95 93 91 89 86 84 82 B
18
Technical data Hydro UNI-NB/NK
The grey background indicates the performance in automatic operation according to the relevant pressure switch settings
The electrical data and performance data of optional jockey pump models can be obtained from the following tables.
These data also comply with ISO 9906 Annex A. For selection, look up the reference letter related to the various jockey
pumps in the above tables.
Jockey pump CR 15 3
Jockey pump flow [m /h]
Jockey
pump P2 I1/1 Starting 0 13 14.5 16 17.5 19 20.5 22
Pump
[kW] [A] method Jockey pump head [m]
C CR 15-6 5.5 11 85 75 73 70 66 62 57 52
DOL
D CR 15-8 7.5 15.2 113 97 93 88 83 77 70
The grey background indicates the performance in automatic operation according to the relevant pressure switch settings.
19
Dimensions and weights Hydro UNI-NB/NK
Hydro UNI-NB/NBU units with one duty pump and jockey pump
The drawings and dimensions shown above apply to the Hydro UNI-NB/NBU units described in this data booklet. For
any changes or adaptations to specific requirements or additions of optional components and/or accessories not
included in our standard scope of supply, please consult Grundfos.
20
Dimensions and weights Hydro UNI-NB/NK
Hydro UNI-NK units with one duty pump and jockey pump
1100
P L3
DN
D
M
1960
DN
HM
T
M2
DN
S
A
160
DN Dimensions [mm]
DN DN Weight
Unit S
D T A BP HM L L3 M M2 P V [kg]
z
HUNI NK 65/F 720
350 1435 1763 1161
HUNI NK 65/G 80 100 80 1345 558 492 381 244 720
HUNI NK 65/H 375 1475 1800 1186 793
HUNI NK 80/A 739
HUNI NK 80/B 350 1952 1281 744
1435 1360
HUNI NK 80/C 744
HUNI NK 80/E 375 1977 1306 811
HUNI NK 80/G 100 125 100 560 457 281 913
400 1725 2032 1385 1361
HUNI NK 80/H 913
HUNI NK 80/L 1028
HUNI NK 80/N 430 1800 2062 1665 546 1391 1028
HUNI NK 80/R 1028
HUNI NK 100/A 400 1825 2125 1385 1436 984
HUNI NK 100/B 1125
HUNI NK 100/D 1125
125 150 125 562 506 224
HUNI NK 100/F 430 1800 1665 1466 1125
HUNI NK 100/G 1125
HUNI NK 100/L 2155 1186
All flange connections to Hydro UNI-NK units are PN 16.
z Jockey pump suction port: Rp 1.
Other jockey pump models, such as CR 5, CR 10 and CR 15, are available as options, see Electrical data and performance data of jockey pumps on
page 19.
For the dimensions of units with alternative jockey pumps, please contact Grundfos.
As an option, units can be supplied with a suction manifold (CPL version); for dimensions, please contact Grundfos.
Note: The tolerance for the dimensions shown in the above table is 20 mm.
Dimensions may be changed without notice as a result of technological improvements to the components and/or materials used.
The drawings and dimensions shown above apply to the Hydro UNI-NK units described in this data booklet. For any
changes or adaptations to specific requirements or additions of optional components and/or accessories not included
in our standard scope of supply, please consult Grundfos.
21
Dimensions and weights Hydro UNI-NB/NK
Hydro UNI-NB/NBU units with two duty pumps and jockey pump
DN
D
DN
T
DN
S
DN
S
The drawings and dimensions shown above apply to the Hydro UNI-NB/NBU units described in this data booklet. For
any changes or adaptations to specific requirements or additions of optional components and/or accessories not
included in our standard scope of supply, please consult Grundfos.
22
Dimensions and weights Hydro UNI-NB/NK
Hydro UNI-NK units with two duty pumps and jockey pump
DN
D
DN
T
DN
DN S
S
The drawings and dimensions shown above apply to the Hydro UNI-NK units described in this data booklet. For any
changes or adaptations to specific requirements or additions of optional components and/or accessories not included
in our standard scope of supply, please consult Grundfos.