Académique Documents
Professionnel Documents
Culture Documents
Manual
User Manual
Contents
1 Introduction ............................................................................................................................................ 9
1.1 SYMAP-Compact General Outline ......................................................................................... 9
1.2 Human machine interface (HMI) ................................................................................................. 9
1.3 Extension Board System EBS .................................................................................................... 9
1.4 Functional scope ....................................................................................................................... 10
1.4.1 SYMAP-Compact: Hardware and Software standard equipment ............................ 10
1.4.2 Extension Board System EBS ................................................................................... 24
1.4.2.1 EB-PS Communication and Power supply ........................................... 25
1.4.2.2 EB-BI8-A 8 Binary inputs ...................................................................... 26
1.4.2.3 EB-BI10-OC 10 Binary inputs (opto-couplers) ..................................... 27
1.4.2.4 EB-BO4-R 4 Binary outputs (change-over contacts)............................ 28
1.4.2.5 EB-BO6-R 6 Binary outputs (normal open NO contacts) ..................... 29
1.5 Diagnostics and Monitoring ....................................................................................................... 30
1.6 SYMAP-Compact Terminal Connections ............................................................................. 32
1.6.1 Analog Inputs for Measurement ................................................................................ 32
1.6.2 Binary Inputs and Outputs ......................................................................................... 33
1.6.3 Service interface ........................................................................................................ 33
1.6.4 Grounding Instructions .............................................................................................. 34
1.6.5 SYMAP-Compact Connection Diagrams .............................................................. 37
1.6.5.1 Hardware version 1-1.1 ........................................................................... 37
1.6.5.2 Hardware version 1-2.2 (SYMAP-Compact+ only!) ............................... 50
1.6.6 Plug-In Connection for Auxiliary Supply .................................................................... 56
1.7 Extension Board System EBS Terminal connections ............................................................ 57
1.7.1 EBS connection diagrams ......................................................................................... 57
1.8 Mounting instruction .................................................................................................................. 60
1 Introduction
This manual describes the digital protection relays of the SYMAP-Compact product line. The
overview represents relay features, applications and functionalities.
CAUTION: SYMAP-Compact(+) devices are not applicable for 3-phase power systems
with anti-clockwise rotating field!
Please refer to Table 1-1 to Table 1-8 in section 1.4.1 for detailed information on software and
hardware capacities of SYMAP-Compact(+) device variants.
The SYMAP-Compact(+) is a numerical protection relay for use in low, medium and high-
voltage systems and, by its integrated protective functions and its HMI interface capacities, it
has proven to be an efficient and cost-effective solution for all types of switch panel. It is
equipped with three high-performance micro-processors and offers a comprehensive range of
protective functions for generators, motors (synchronous or asynchronous), transformers, power
lines, and substations. All protection functions can be activated and used at a time and without
restrictions. Both, digital and analog outputs can be connected to the controls of the main panel
via SYMAP-Compact(+) control unit. These features guarantee highest flexibility during
commissioning and subsequent use In addition, communication of the SYMAP-Compact(+)
and the SCADA system is possible via several serial ports and different data protocols.
The men is navigated using the touchscreen from the main menu, which provides access to
the submenus Operating, Alarms, Breaker, Parameters, Recorder, Settings and Info.
For many applications the number of binary inputs and binary output of SYMAP-Compact(+) is
not sufficient. To provide the possibility to process additional, peripheral signal via SYMAP-
Compact(+), special extension boards (Extension Board System EBS) for binary inputs and
outputs can be connected to the SYMAP-Compact(+). Parameter setting of the boards can be
conducted via application software SYMAP-Compact Parameter Toll (SCPT).
Hardwareversion v1-1.x
Table 1-1 Standard equipment of SYMAP-Compact(+)Fx device variants HW v1-1.x
PRODUCT LINE SYMAP-Compact
DEVICE TYPE Compact Compact+
DEVICE VARIANT F0 F1 F2 F3 F4 F1 F2 F3 F4
Application
Portection system - - - -
Protection and Control system - - - - -
Dimensions
Housing dimensions (WxHxD = (210x210x87)mm - - - -
Housing dimensions (WxHxD = (210x250x87)mm - - - - -
Front plate dimensions (WxHxD = (210x210x4)mm - - - -
Front plate dimensions (WxHxD = (210x250x4)mm - - - - -
Cutout (WxH = 192x192)mm - - - -
Cutout (WxH = 192x232)mm - - - - -
Front plate
Stucke Design
LED indications
3 Status LEDs (TRIP:red/ ALARM: yellow/ SYSTEM: red/ green)
8 Alarm LEDs (parameterizable; colour: red) - - - -
8 Alarm LEDs (parameterizable; colours: red/green/yellow) - - - - -
Membrane keyboard
4 membrane keys (navigation/ parameter setting/reset) - - - -
6 membrane keys (navigation/parameter setting/reset /ON/OFF) - - - - -
Display
Graphical LC-Display / Touchscreen (320x240 pixel)
Current measurement
1 x CT1 (3-phase; 020 x In; sec. nominal current: see order code) -
1 x CT-GND1 (1-phase; sec. nominal current: see order code) -
Voltage measurement
1 x PT1 (3-phase; meas. ranges**: 50 to 200V AC and 200 to 700 V AC) - - - -
1 x PT2 (3-phase: meas. ranges**: 50 to 200V AC and 200 to 700 V AC) - - - - - -
1 x PT3 (3-phase: meas. ranges**: 50 to 200V AC and 200 to 700 V AC) - - - - - - - -
1 x PT-GND1 (1-phase: meas. ranges**: 50 to 200V AC and 200 to 700 V
- -
AC)
Binary inputs
5 pcs (10220V DC/230V AC; rooted) - - - -
19 pcs. (10220V DC/230V AC; rooted) - - - - -
Binary outputs
5 pcs (potential-free contacts, NO) - - - -
12 pcs (potential-free contacts, NO) - - - - -
Communication interfaces
1 x Mini-USB (side of housing; for parameter setting)
1 x RS485/422* (Modbus RTU; half- and full duplex*)
1 x USB-A (at front plate; for parameter setting)
1 x RJ45 (side of housing; for EBS and for parameter setting*)
1 x CANBUS1 (external communication*)
1 x CANBUS2 (external communication*)
In compliance with the standards of the American National Standards Institute (ANSI), product
line SYMAP-Compact offers different protection functions according to the device variants.
Table 1-5 Standard equipment of SYMAP-Compact(+)Fx device variants Software functions
PRODUCT LINE SYMAP-Compact
DEVICE TYPE Compact Compact+
DEVICE VARIANT F0 F1 F2 F3 F4 F1 F2 F3 F4
Protection functions (ANSI Code)
21B Generator backup protection - - - - - - -
21FL Fault locator - - - - -
24 Overexcitation U/F* - - - - -
25 Synchrocheck - - - - - -
27 Under voltage - - - -
27Q Reactive power/Under Voltage (BDEW) - - - - -
27T Under Voltage, time-dependent (BDEW; Fault ride through) - - - -
32 Directional Power - - - - -
32N/G Zero Power - - -
37 Undercurrent -
40 Loss of Field* - - - - -
46 Negative phase sequence I2 -
46BC Negative phase sequence I2/I1 (broken conductor) -
47 Phase sequence / Phase balance - - - - -
48 Motor start up (incomplete sequence) -
49 Thermal Replica -
50BF Breaker failure -
50/51 Time Overcurrent -
51LR Locked Rotor* -
51MS Motor start* -
50/51G Time Ground Overcurrent -
51/46VR Overcurrent (voltage restrained) - - - - -
52 Pole discordance -
55 Power factor* - - - - -
59 Over voltage - - - -
59AV 10 min overvoltage RMS protection - - - -
59N/G Neutral Voltage Displacement (NVD) - -
64REF Restricted earth fault (REF) -
66 No. Of Starts (Motor)* -
67 Directional Time Overcurrent - - - - -
67G Directional Time Ground Overcurrent - - -
74TC Trip circuit supervision
78 Vector surge - - - -
78S Power Swing / Out-Of-Step* - - - - -
79 Automatic Reclose (AR) -
81 Under / Over Frequency - - - -
81R RoCoF (df/dt) - - - -
81RAV Frequency supervised average (DF/DT) - - - -
86 Lockout relay
87H High impedance phase current differential protection* -
87GH High impedance ground current differential protection* -
95i Harmonics stabilizer -
CLD Cold Load Detection -
CTS Current transformer supervision -
DCVM DC voltage monitoring - - - -
PTS Potential transformer supervision - - - -
SGF 100% stator ground fault protection* - - -
SOTF Switch-On-To-Fault -
Control and Interlocking
Indirect control: 1 switching element; Field interlocking: up to 3 sw. devices) - - - - - - - - -
Indirect control: 5 switching elements; Field interlocking: up to 8 sw. devices) - - - - -
Measurement (indication)
Current measurement values -
Voltage measurement values - - - -
Power measurement values - - - - -
MIN*-/MAX- and average* (AVG) measuring values (statistic)
Recording functions
Alarm control
Active Alarms/Events
Event recorder
Fault recorder
Disturbance recorder**
Counters
Operating hours
Energy counters - - - - -
Short circuit currents* -
Switching operations (breaker control) - - - - -
Monitoring functions
Wire fault supervision: Binary inputs*
Short circuit supervision: Binary inputs*
LVM Limit value monitoring
Logical functions
PLC (programmable logic control)
Graphical functions
Configurable menu pages
Trend representation of measuring values*
Vector representation of measuring values
Representation of harmonics
* not available yet
** not available for HW v1-1.0!
Counters
Operating hours
Energy counters - -
Short circuit currents* - - -
Switching operations (breaker control) - - -
Monitoring functions
Wire fault supervision: Binary inputs*
Short circuit supervision: Binary inputs*
Aux. power supervision: Binary outputs (Shunt 1 and 2 only)*
LVM Limit value monitoring -
Logical functions
PLC (programmable logic control)
Graphical functions
Configurable menu pages
Trend representation of measuring values* -
Vector representation of measuring values -
Representation of harmonics -
* not available yet
** not available for HW v1-1.0!
NOTE: Please note that the above mentioned table represents the availability of protection
functions at the final development state. At this time, only those protective functions
which are described in this manual are available!
According to different, available hardware versions the two following tables give conclusion
about all ordering options of all device variants.
The Extension Board System EBS consists of several board types for different functions. Each
board is designed for DIN rail mounting according to the standard DIN TS35. Communication
between the boards is established by internal CAN BUS connection (Inter.Link); communication
to the SYMAP-Compact(+) device is Ethernet.
Using extension boards for e.g. binary inputs requires the communication and power supply
board EB-PS. On the one hand this board establishes communication between the connected
boards to the SYMAP-Compact(+) device, on the other hand it provides the necessary power
supply to the other boards.
Communication of EB-PS to the SYMAP-Compact(+) device uses the Ethernet protocol with
the physical interface 2 x RJ45. The second RJ45 is the service interface for parameter setting
of the devices via application software SYMAP-Compact Parameter Tool (SCPT). The service
interface has to be activated via parameter EBS Ethernet switch enabled [P] in the menu:
I/O\General.
Besides main tasks such as communication and power supply board EB-PS provides three
binary inputs and one binary output which is designed as change-over contact.
Readiness of EB-PS is indicated by a System-LED at its front. Separate LEDs for the binary
inputs and the binary output give conclusion about their status.
Board EB-BI8-A provides 8 binary inputs which are devided into two groups with 4 Bis and two
common termials each. Each BI-group can be operated with different nominal voltages to
activate the binary inputs. The applied nominal voltages can be assigned via parameters EBx
Group 1 [P] und EBx Group 2 [P] in the menu: I/O\Binary inputs/EBS Groups.
Separate LEDs for the binary inputs give conclusion about their status.
Power index: 5
Board EB-BI8-A provides 10 binary inputs which are devided into two groups with 5 BIs and two
common termials each. Each BI-group can be operated with different nominal voltages to
activate the binary inputs.
NOTE: It is not possible to operate the binary inputs with different voltages. Different voltages
can only be processed by different variants of board EB-BI10-OC (see order code).
Separate LEDs for the binary inputs give conclusion about their status.
Power index: 5
Board EB-BO4-R provides 4 binary outputs which are designed for change-over contacts. Each
binary output can individually be adjusted via the parameters of menu I/O\Binary outputs\EBS
Function outputs.
Separate LEDs for the binary inputs give conclusion about their status.
Power index: 18
Board EB-BO6-R provides 6 binary outputs which are designed for normal open contacts (NO).
Each binary output can individually be adjusted via the parameters of menu I/O\Binary
outputs\EBS Function outputs.
Separate LEDs for the binary inputs give conclusion about their status.
Power index: 18
All of the three SYMAP-Compact(+) microprocessors have an integrated system for mutual
monitoring. Self-supervision comprises the internal hardware components of SYMAP-
Compact(+), and is done through cyclical requests and plausibility checks.
NOTE: All system supervision events can only be reset with ACK.
Following the detection of an internal error, the measures listed in Table 1-11 will be
performed. If these measures are not successful, event [E9000] will be activated, which can be
assigned to any binary output.
CAUTION: In case of a power supply failure, all binary outputs are being de-energized!
While booting mode the states of all binary outputs are maintained!
The SYMAP-Compact(+) field interface is via plug connectors at the back of the device. This
makes device replacement simple. The terminal blocks are divided into the following groups:
Analog inputs for measurement
Binary inputs and outputs
Communication interfaces
If current transformer plug is disconnected (SEOIL plugs only, see ordering option), circuits
close automatically to preclude interruption of CT circuits. All of the possible SYMAP-
Compact(+) connections for current and potential transformers are listed below:
Three phase current measurement inputs CT1-M/P*
Optionally**: additional three phase current measurement inputs CT2-M/P
(e.g. two-winding transformer differential protection)
Optionally**: additional three phase current measurement inputs CT3-M/P
(e.g. three-winding transformer differential protection, not available yet!)
Single phase current measurement input CT-GND1 (ground current)
Optionally***: additional single phase current measurement input CT-GND2
(e.g. applications with a second ground current measurement)
Three-phase voltage measurement inputs PT1 (e.g. voltage at incoming feeder)
Three-phase voltage measurement inputs PT2 (e.g. voltage at busbar 1)
Three-phase measurement inputs PT3 (e.g. voltage at busbar 2)**
Single-phase measurement input PT-GND1 (residual voltage)
* CT1: separate terminal connections: CT1-M for measuring winding and CT1-P for protection winding of current
transformers; SYMAP-Compact+ only
** SYMAP-Compact+ only!
*** SYMAP-Compact+: device variants without CT3 and CT1-M only! (not available yet!)
CAUTION: When using device variant equipped with CT1-M, e.g. for connecting separate
measuring core of an external CT to measure operating currents with a higher
accuracy, all terminals of CT1-M must be connected to the external CT!
The following values are measured via analog inputs and displayed:
Phase-to-Phase and Phase-to-Ground voltages of incoming feeder, busbar 1 and busbar 2
Three-phase feeding current (average/maximum)
Frequencies of all systems (minimum/maximum)
Ground current (maximum)
Residual voltage
Operating hours
NOTE: Hardware version v1-1.x provides up to 19 binary inputs with interconnected (rooted)
common terminals (Fct 10 to Fct 28: GND2).
Hardware version v1-2.x provides up to 18 binary inputs. Thus, Fct 28 is not
available!
The two binary inputs Fct. 26 and Fct. 27 are equipped with a seggregated common
terminal each (Fct. 26: GND 11 and Fct. 27: GND 10). Binary inputs Fct. 10 to Fct.
25 are provided with a rooted common terminal (GND2).
Ground straps of 250mm in length and above are to be used to connect the earthing connection
point of SYMAP-Compact(+) housing to the panel housing. The following table provides
information about standard cross sections and dimensions of ground straps to be applied
according to their lengths.
Table 1-12 Ground straps Standard cross sections and dimensions
Length (l) Cross section (A) Diameter of wire (d) Dimensions (width x thickness)
[mm] [mm2] [mm] [mm2]
250 500 6 2.75 9x1
500 750 10 3.55 14 x 1,5
750 1000 16 4.49 20 x 1,6
Figure 1-9 SYMAP-Compact F0; HW v1-1.1; as from order code version v1-6.x
Figure 1-10 SYMAP-Compact F1; HW v1-1.1; as from order code version v1-6.x
Figure 1-11 SYMAP-Compact F2; HW v1-1.1; as from order code version v1-6.x
Figure 1-12 SYMAP-Compact F3; HW v1-1.1; as from order code version v1-6.x
Figure 1-13 SYMAP-Compact F4; HW v1-1.1; as from order code version v1-6.x
Figure 1-14 SYMAP-Compact SYN; HW v1-1.1; as from order code version v1-6.x
Figure 1-15 SYMAP-Compact GC; HW v1-1.1; as from order code version v1-6.x
Press
here
NOTE: To release the plug-in connector, please press the lower area of the grooved side
where the lock catches.
Before connecting and start-up the SYMAP-Compact(+), it is necessary to install the device
into a housing or switchgear cabinet.
The following mounting instruction describes the installation of the SYMAP-Compact+ device
as an example!
First, it is necessary to prepare a cut-out in the door panel of the cubicle. The only restriction
regarding this is the size of the excisting installation surface. This may not fall below the overall
dimensions of the SYMAP-Compact+ device.
The next figure displays the dimensions of the device and the required cut-out:
1. After finishing the cut-out it shall look like the following example.
3. For keeping the device position in the cut-out, employ a slight counter-pressure to the
front plate of the device and look to the backside. Each side of the housing provides four
bolt heads for installation of the fixing clamps:
4. While holding the SYMAP-Compact+ device, click one fixing clamp to the that bolt head
which is next to the rear of the housing:
5. Insertation of the device into the panel cutout shall be conducted with a slight offset for
vertical and horizontal direction.To bring the head of the bolts into the cutout one after
the other please push the device alternateingly into the cutout in the following order:
right, top, left, and down until the seal is evenly seated on the installation surface (door
panel).
Figure 1-40 Device to be inserted with slight offset during installation into cutout
6. Now, turn the fixing clamp to the second bolt head with slight pressure. Hearing a click
indicates the correct installation.
7. Thereafter, install the remaining three fixing clamps on the other sides of the housing.
Now the four fastened fixing clamps can be tightened by using a screwdriver.
2 Operation of SYMAP-Compact(+)
This section describes the user interface (HMI) which comprises the display elements and the
keypads.
1
Compact
SYMAP- COMPACT
2 TRIP
7 ALARM 3
SYSTEM
20.06.2012 15:16:39
5 5
ALARM
Compact
SYMAP- COMPACT+
1
TRIP
7 3 ALARM
SYSTEM
2
20.06.2012 16:19:42
4
I
6
ALARM
0
The lable See documentation at the back panel of SYMAP-Compact(+) points to the location
of an exchangeable, rechargeable battery within the device.
On its LC-display, the SYMAP-Compact(+) offers several display options. Device settings and
controls are also shown. The user can navigate the menus using the resistive touchscreen. PC-
created graphics, alarms, events and measured values can be transferred to the SYMAP-
Compact(+). The large graphic display allows the user to view all important data at a glance.
G
CT2-M/P
CT1-M/P
PT1
30.08.2012 17:29:34
2072,56 A
20.00 kV
50,01 Hz
PT1 (Ph-Ph)
71,5 A
Frequency
CT2
CT1
start page
user page
assigned to
The Main Menu appears as a start page after switching on orresetting the SYMAP-
Compact(+).
The start page may be changed into a configured User Page, containing custom information
such as a bay single diagram or an alarm page.
NOTE: Up to four different user pages can be set up using SYMAP-Compact Parameter
Tool (SCPT) software.
To navigate from the User Page to the main menu, a hotkey may be set up on the User Page
which is assigned to the start page. For this, a pre-defined Main Menu hotkey is available via
the library in SCPT software (see Figure 2-8).
From the menu page Main Menu the following hotkeys are available in order to navigate back
through the menu:
Lower display status line: symbol for indicating the currently, active parameter set
Lower display status line: symbol for indicating effective Disturbance recorder
2.4.1 Operating
Menu Operating provides all of the relevant data generated while the SYMAP-Compact(+) is
in operating mode. The following operating data is available:
measuring values of current and voltage inputs,
measuring values during synchronizing process,
information about SD-card and Debug menu, and
measuring values of power management system PMS (availability depends on device
variant)
2.4.1.1 Meters
There are several measured value pages which can be used to view measured values in detail,
such as:
CAUTION: SYMAP-Compact(+) devices are not applicable for 3-phase power systems
with anti-clockwise rotating field!
Meters \ Voltage/Frequency
Depending on the SYMAP-Compact(+) device variant and according to the number of voltage
measuring inputs PT1, PT2 and PT3, phase-to-ground voltages and phase-to-phase voltages
will be displayed phase-selectively. Displayed frequency values refer to the voltage measuring
inputs.
Meters \ Current
This page displays information on current values. In addition to the currently measured values,
changes from previous measurements are calculated and the maximum value is saved.
Differential currents are displayed only for devices with differential current input.
The bargraphs indicate the current trends as a percentage of the nominal value. Depending on
the set values of the bargraphs colour thresholds (parameters), the bargraphs show the colours
green, orange or red.
Meters \ Power
Display of power values accords to the selected current measurement input by Ref hotkey.
This selection hotkey determines which current and voltage measurement input are used for
power value display.
The first row displays total power measurement values; it follows a phase-selective
representation according to phases L1, L2 and L3. Measured quantities are as follows:
Active Power P [kW]
Reactive Power Q [kvar]
Power Factor PF
Apparent Power S [kVA]
The real power factor PF does not carry any sign and is given in a range between 0 to 1.
Displayed power measurement values of the system (active power P, reactive power Q,
apparent power S and power factor PF) are deducted from measured phase currents and
voltages.
Depending on which measuring inputs are used to measure phase currents and voltages, there
are different selection options of touchscreen hotkey Ref for referencing the displayed power
values:
CT1: Displayed power measurement values, based on phase currents measured by
CT1 and measurement of the voltages by that measuring input which is assigned
to Parameter PT reference [P9410].
CT2: Displayed power measurement values, based on phase currents measured by
CT2 and measurement of the voltages by that measuring input which is assigned
to Parameter PT reference [P9413].
NOTE: The assignment of the voltage measurement input (PT1, PT2 or PT3) to the current
measurement input CT1 (or CT2) should be done using the following parameters, in
the submenu SYSTEM\Measuring\Power:
PT reference [P9410] for CT1 and
PT reference [P9413] for CT2.
2.Quadrant 1.Quadrant
3.Quadrant 4.Quadrant
-Q
Im
2.Quadrant 1.Quadrant
3.Quadrant 4.Quadrant
-Q
Device-depending sign definition of active power P, reactive power Q and power factor PF
To differentiate the different AC loads without any further indicator and to control the reactive
power by the power factor, in SYMAP-Compact(+) devices the power factor shows the sign of
the reactive power.
Device-dependent sign definition of power mesurement values
2.Quadrant 1.Quadrant
3.Quadrant 4.Quadrant
-Q
Im
2.Quadrant 1.Quadrant
3.Quadrant 4.Quadrant
-Q
NOTE: The above mentioned is only valid for a three-phase system whith clockwise field of
rotation!
When SYMAP-Compact(+) is connected and configured according to the LRAS, active power
P (ohmic load) and reactive power Q (inductive load) will be indicated with a positive sign. The
power factor is also indicated as positive. In case of a capacitive load the reactive power as well
as the power factor shows a negative sign.
According to the above mentioned, the following graphics show the sign definition of the
measuring values P, Q and PF as examples:
17
U'12 U'31 SYMAP-Compact F3
19
U'23
PT1
21
U'L1 U'L2 U'L3
26
15
U'GND PT-GND1
16
I1 I2 I3
P1 I'1
S1
1
I'1
2
P2 S2
P1 S1 I'2
3
I'2 CT1
4
P2 S2
P1 S1 I'3
5
I'3
6
S2
P2
I'GND
7
CT-GND1
8
Parameter settings:
SCPT SYSTEM\Measuring\Power:
POWER CT1:
PT reference [P9410] = PT1
Direction [P9411] = 0
CT1:
Direction L1 (Measuring) [P662] = 0
Direction L2 (Measuring) [P663] = 0
Direction L3 (Measuring) [P664] = 0
Direction L1 (Protection) [P665] = 0
Direction L2 (Protection) [P666] = 0
Direction L3 (Protection) [P667] = 0
Figure 2-17 Example: Power measurement of outgoing feeder (LRAS) connection diagram
and sign definition of measuring values P, Q and PF
CAUTION: Earthing of the secondary side of the phase current transformers must take place
at that side where the secondary side of the CTs are interconnected!
17
U'12 U'31 SYMAP-Compact F3
19
U'23
PT1
21
U'L1 U'L2 U'L3
26
15
U'GND PT-GND1
16
I1 I2 I3
P1 I'1
S1
1
I'1
2
P2 S2
P1 S1 I'2
3
I'2 CT1
4
P2 S2
P1 S1 I'3
5
I'3
6
S2
P2
I'GND
7
CT-GND1
8
Parameter settings:
SCPT SYSTEM\Measuring\Power:
POWER CT1:
PT reference [P9410] = PT1
Direction [P9411] = 0
CT1:
Direction L1 (Measuring) [P662] = 0
Direction L2 (Measuring) [P663] = 0
Direction L3 (Measuring) [P664] = 0
Direction L1 (Protection) [P665] = 0
Direction L2 (Protection) [P666] = 0
Direction L3 (Protection) [P667] = 0
Figure 2-18 Example: Power measurement of incoming feeder (LRAS) connection diagram
and sign definition of measuring values P, Q and PF
NOTE: Any change in one of the conditions for sign definition of the measured power values
will lead to a change in the sign for measured values of P and Q!
17
U'12 U'31 SYMAP-Compact F3
19
U'23
PT1
21
U'L1 U'L2 U'L3
26
15
U'GND PT-GND1
16
I1 I2 I3
P1 I'1
S1
1
I'1
2
P2 S2
P1 S1 I'2
3
I'2 CT1
4
P2 S2
P1 S1 I'3
5
I'3
6
S2
P2
I'GND
7
CT-GND1
8
Parameter settings:
SCPT SYSTEM\Measuring\Power:
POWER CT1:
PT reference [P9410] = PT1
Direction [P9411] = 180
CT1:
Direction L1 (Measuring) [P662] = 0
Direction L2 (Measuring) [P663] = 0
Direction L3 (Measuring) [P664] = 0
Direction L1 (Protection) [P665] = 0
Direction L2 (Protection) [P666] = 0
Direction L3 (Protection) [P667] = 0
Figure 2-19 Example: Power measurement of incoming feeder (GRAS) connection diagram
and sign definition of measuring values P, Q and PF
Meters \ Counter
The Counter page provides energy counting values and counting values of operating hours.
Energy counting
For each measuring sample, the values of different power quantities are calculated. At the end
of the nominal period each power value is multiplied by the duration of the nominal period which
provides the energy values for one nominal period. Displayed energy conuting values represent
summation of all the energy values of one nominal period individually for all the different energy
quantities.
Absolute/Temporary energy counting values of different power quantities:
o positive, active power Wp+
o negative, active power Wp-
o positive, reactive power Wq+
o negative, reactive power Wq-
Absolute/Temporary operating hours:
o h: hours
o m: minutes
o s: seconds
Reset
The Reset touch-screen button only refers to temporary counting values (energy values and
operating hours). After reset of temporary counting values counting starts from start value 0.
Using the reset function it is possible to have counting values for a certain time period without
deleting the counting values for the total operating time.
Meters \ Ground
The Ground page shows all measured or calculated residual voltage and ground current
values.
According to different manners of building the measurement quantities of the zero sequence
system, there are following variedly generated measuring values available:
UG,PT1: residual voltage calculated from the phase voltages of PT1
UG,PT2: residual voltage calculated from the phase voltages of PT2
UG,PT3: residual voltage calculated from the phase voltages of PT3
UG,PT-GND1: residual voltage directly measured via PT-GND1
IG,CT1: ground current calculated from phase currents of CT1 (3 x I0,CT1 = IG,CT1)
IG,CT2: ground current calculated from phase currents of CT2 (3 x I0,CT2 = IGND,CT2)
IG,CT-GND1: ground current directly measured via CT-GND1
Selection
Up to six selectable voltage and current measurement quantities can be displayed via vector
diagram. The measurement quantities (Signal button) have to be assigned to the vector
(Channel button) using the touchscreen. One additional reference channel (selection option
Ref. signal) is used to define the reference vector (0) for the alignment of all other vectors
within the diagram.
NOTE: That measurement quantity (signal) which is assigned to the Ref. signal channel is
not to be displayed in the vector diagram!
The magnitude of measuring quantities can be displayed using the Unit ref. button, either as
absolute value (units: [V], [A]), or as relative value ([%]).
Vector diagram
The colour serves as the corresponding factor between vector and measuring quantity (signal)
listed on the left side of the diagram.
Figure 2-24 Operating measurements selected U/I values via vector diagram
Tabulated form
Each available voltage and current measurement quantity (signal) is displayed according to its
magnitude and phase angle.
Meters \ DC Voltage
This submenu shows the actual measurement values of DC voltage measurement.
Meters \ Harmonics
This submenu shows the harmonic content (fundamental oscillation and harmonics) of a
selected measuring value which is represented in tabulated form and as bar chart.
Harmonics are additional, sinusoidal oscillations with frequencies fx which are multiple integers
of the measuring quantitys fundamental frequency f1 (= nominal frequency fn). The fundamental
oscillation and the harmonics are represented on the display according to their ordinal number n
(multiple integer of the fundamental frequency n = fx/f1) and the magnitude of the measuring
value:
Fundamental oscillation: ordinal number 1, and
Harmonics: ordinal number 2 to 17.
The magnitude of the fundamental oscillation is shown as an absolute value; the magnitude of
the harmonics as percentage referrring to the absolute value of the measuring signals
fundamental.
Graphical representation
Operating Diagram hotkey opens menu page Harmonics diagram which shows a bar chart
with the percentage distribution of the total of all different harmonics.
The amount of the fundamental oscillation A1 and the amount of the harmonics Ax are
represented as percentage according to their ordial number n = fx/f1 referring to the measuring
quantitys fundamental oscillation.
2.4.1.2 Synchronizer
While synchronizing process all relevant measurement values of each synchronizing unit
(Sync. unit 1, Sync. unit 2 or Sync. unit 3). are displayed via the Synchronizer menu page.
Depending on parameter setting of menu SETUP and the synchronizing units, it is possible to
perform a manual start of the synchronizing functions using the Manual Start hotkey.
NOTE: Hotkey Manual Start only appears at the synchronizing page if function Start
synchronizer manually is assigned to one of the four user levels and the assigned user
level is activated!
NOTE: When synchronisation is conducted between two voltage systems of different voltage
levels (e.g. high-voltage side and low-voltage side of a transformer), displayed
voltage values at the synchronisation page refer to that voltage reference system
which is assigned to parameter Voltage reference [P2307], [P2347] or [P2387].
As soon as a synchronizing unit is activated, hotkey Manual Stop is shown as well as status
information of the selected synchronizing unit. The current synchronization can be cancelled by
using Manual Stop hotkey.
SD-card
This menu page provides information about the type of SD-card which is used for data
recordings.
NOTE: The maximum size of the SD card is 2000MB!
Debug
This menu page only provides information about special data of communication standard IEC
61850.
While operating the PMS actual measurement values and status indications of the power
management functions are displayed in PMS menu.
PMS overview
PMS overview
No. LOAD 100% I% Net M STATUS APC FC
2 98 85 1 A CB ON SYM ON
3 95 86 1 A CB ON SYM ON
17 97 85 1 A CB ON SYM ON
5 96 80 1 A CB ON ON ON
6 63 57 1 M CB ON OFF OFF
11 0 0 17 A CB OFF OFF OFF
8 0 0 23 A CB OFF OFF OFF
32 0 0 9 A CB OFF OFF OFF
1 2 3 4 5 6 7 8
1: No.: this column shows the device numbers of those generators which are operating
for the power management. The device number of the local device is highlighted.
2: Load: this column shows the actual measuring value of the emitted/consumed active
power of each generator. The values are given as a percentage of the nominal power
value which is set by parameter Power [P6x5]. The power values are represented
digitally and graphically (via bar graph: top scale value = 0%, indicated graduation bar =
100%, full scale = 127%). Any occurring reverse power is indicated by a change of the
bar graph colour: blue turns to red (reverse power), and the digital value has a
negative sign.
3: I%: this column shows the actual current measuring value of each generator. The
values are given as a percentage of the nominal generator current value which is set by
parameter current [P6x4].
4: Net: this column shows the actual net number (busbar section) one or more
generators are operating at.
5: M: this column shows the actual operating mode of each generator (A: automatic
mode, M: manual mode).
6: STATUS: this column shows the actual status indications of the switching element
(CB) positions for those generators which are operating for the power management.
Status indications are as follows:
Table 2-3 Status indications of CB positions
Status Description
CB OFF Circuit breaker is open.
CB ON Circuit breaker is closed.
7: APC: this column shows the actual status indications of the active power controller
(APC) of the local device. Status indications are as follows:
Table 2-4 Status indications of active power controller
Status Description
OFF The controller is disabled/blocked.
ON The controller is active.
SYM The controller is in balanced mode.
8: FC: this column shows the actual status indications of the active frequency controller
(FC) of the local device. Status indications are as follows:
Table 2-5 Status indications of frequency controller
Status Description
OFF The controller is disabled/blocked.
ON The controller is active.
PMS controller 1
This menu page shows actual status indications and measuring values of the active power
controller and the frequency controller of the local device.
PMS controller 1
1 Net: 23 AUTO LOAD FREQUENCY
2 Status Balanced 4 ON
3 Setpoint 60.0 % 50.00 Hz
4 Actual 50.0 % 51.00 Hz
5 Difference 10.0 % 1.00 Hz
6 Interval 1.50 s 3.00 s
7 Pulse 0.37 s 0.87 s
1: Net: this cell shows the actual net number the local generator is operating at, and it
shows the actual status of the operating mode of all four controllers
2: Status: this cell shows the actual status of the active power controller and the
frequency controller of the local device. Status indications are as follows:
Table 2-6 Status indications of controller 1
Status Description
OFF Disabled
ON Active
BALANCED Balanced mode (the number of devices is shown also)
BLOCK NET All devices in the own net are blocked by own device
BLOCK OWN Blocked by own device
BLOCK CB OFF Blocked by CB OFF
BLOCK MANU Blocked by manual mode
All devices in the own net are blocked by other
BLOCK BY DEVICE
device(s)
BLOCK NO DEVICE No devices: balanced mode not possible
BLOCK FREQ Speedcontrol outside range (P7004, 7005)
DEADBAND Controller is idle
3: Setpoint: this line shows the actual setpoint of the active power controller and the
frequency controller.
4: Actual: this line shows the actual measurement value of the active power controller
and the frequency controller.
5: Difference: this line shows individually the actual control deviation (= setpoint actual
value) of the active power controller and the frequency controller.
6: Interval: this line shows individually the set interval time of the active power controller
and the frequency controller of the local device.
7: Pulse: this line shows individually the actual, calculated pulse time of the active power
controller and the frequency controller of the local device.
PMS controller 2
This menu page shows actual status indications and measuring values of the voltage controller
and the power factor controller of the local device.
PMS controller 2
1 Net: 23 AUTO VOLTAGE POWER FACTOR
2 Status ON Balanced 3
3 Setpoint 100.0 % 0.95
4 Actual 90.0 % -0.90
5 Difference 10.0 % 0.15
6 Interval 1.50 s 3.00 s
7 Pulse 0.37 s 0.83 s
1: Net: this cell shows the actual net number the local generator is operating at, and it
shows the actual status of the operating mode of all four controllers
2: Status: this cell shows the actual status of the active power controller and the
frequency controller of the local device. Status indications are as follows:
Table 2-7 Status indications of controller 1
Status Description
OFF Disabled
ON Active
BALANCED Balanced mode (the number of devices is shown also)
BLOCK NET All devices in the own net are blocked by own device
BLOCK OWN Blocked by own device
BLOCK CB OFF Blocked by CB OFF
BLOCK MANU Blocked by manual mode
BLOCK BY DEVICE All devices in the own net are blocked by other device(s)
BLOCK NO DEVICE No devices: balanced mode not possible
BLOCK RANGE Block by range
DEADBAND Controller is idle
3: Setpoint: this line shows the actual setpoint of the voltage controller and the power
factor controller.
4: Actual: this line shows the actual measurement value of the voltage controller and the
power factor controller.
5: Difference: this line shows individually the actual control deviation (= setpoint actual
value) of the voltage controller and the power factor controller.
6: Interval: this line shows individually the set interval time of the voltage controller and
the power factor controller of the local device.
7: Pulse: this line shows individually the actual, calculated pulse time of the voltage
controller and the power factor controller of the local device.
2.4.2 Alarms
The user can find information on the active alarm messages as well as all active events on the
front panel (HMI) display.
When an alarm occurs, this page will open automatically. Depending on the configuration of the
alarm channels, the alarm number (which also serves as event number), the active alarm colour
(OFF, red, green or yellow), and the alarm description (editable text; max. 40 characters) are
displayed. Up to 449 alarms can be managed.
Active alarms appear in order of occurrence. If the SYMAP-Compact(+) saves more than 11
alarm messages, the list can be scrolled up and down via:
touch-screen or
if configured assigned buttons on the front panel of the device (see menu: SYSTEM\
Graphic\Button Configuration.
NOTE: For configuration of the alarms please refer to chapter 3.5.2 Alarm channels
(configuration via software SYMAP-Compact Parameter Tool (SCPT) only!).
If an alarm occurs, the Alarm LED at the front plate and the active alarm colour in the Active
alarms menu page will blink fast until acknowledged or until the alarm is no longer active.
The Alarm LED and the active alarm colour in the Active alarms menu page will blink at a
slower interval if the alarm is no longer active but not yet acknowledged.
An audible signal may also be activated.
Table 2-8 describes LED and audible signal control (beeper) according to the alarm status.
If the audible signal is ON, an alarm has to be acknowledged twice: once to switch the beeper
OFF and a second time to register the alarm.
NOTE: If the alarm is still active after registering, the audible signal (beeper) will be activated
again!
This page represents all active events by their respective event numbers as well as the total
number of active events. Event registration occurs chronologically with the first column top
down.
2.4.3 Breaker
The Breaker selection page gives an overview of the current status of switching elements
(circuit breakers, disconnectors, grounding switches, etc.) used in the application.
2.4.4 Parameters
Among others the main menu also shows submenu Parameters. After clicking to this submenu
the following pop-up window gives opportunity to enter the parameter mode:
Here, the parameters of the different submenus can be set via touchscreen.
Example: Menu SYSTEM\Nominals\Voltage transformers; setting of parameter
Assignment [P642]
By clicking to the parameter the following window opens in which selection of the required
selection option can be done:
Discard changes will ignore any modification of parameter settings and shows the adjusted
Home page.
Apply changes will lead to system reboot of the device to save all the changes of parameter
settings:
NOTE: Device parameters cannot be set or modify from the HMI display, they can be set only
via configuration software SYMAP-Compact Parameter Tool (SCPT)!
2.4.4.1 SETUP
The SETUP menu shows how the SYMAP-Compact(+) variant has been adapted to the
application. For this, two sub-menus are provided:
User levels sub-menu (configuration of different user levels) and
Measuring inputs sub-menu (enable/disable the current measurement inputs: CT1, CT2
and CT-GND1, and voltage measurement inputs: PT1,
PT2, PT3, PT-GND1)
User levels
The User levels submenu provides parameters to individually configurate the different user
levels. Parameters refer to:
the activation of the different user access levels, and
the assignment of certain functions to the different user levels.
Measuring inputs
The Measuring inputs submenu provides parameters to enable/disable current and voltage
measurement inputs according to the application.
NOTE: Disabled measurement inputs will not provide any measurement quantities.
2.4.4.2 SYSTEM
2.4.4.3 RECORDER
The RECORDER submenu provides all of the parameters about configuration of recording
functions such as Fault recorder and Disturbance recorder. Further information on this can
be found in the Recorder (File information and Manual trigger) chapter.
2.4.4.4 PROTECTION
2.4.4.5 ALARMS
The ALARMS submenu provides all of the parameters relating to alarms and LED
configuration of SYMAP-Compact(+). Further information on this can be found in the System
settings chapter.
2.4.4.6 I/O
The I/O provides submenu all of the parameters about analog/binary inputs and outputs of the
SYMAP-Compact(+). Further information on this can be found in the System settings chapter.
2.4.4.7 LVM
The LVM submenu provides all of the parameters about configuration of LVM Limit Value
Monitoring function. Further information on this can be found in the LVM Limit Value
Monitoring chapter.
The SWITCHGEAR CONTROL submenu provides all of the parameters about configuration of
switching elements. Further information on this can be found in the System settings chapter.
2.4.4.9 PMS
The submenu PMS provides all functions of the power management system. At present only
function Generator control is available for device variants SYMAP-Compact GC, ECG, +GC
and +ECG.
For each recording function a recording file can be generated. The file endings of the recording
files are assigned as follows:
Event recorder: xxx.ser
Fault recorder: xxx.sfr
Disturbance recorder: xxx.sdr
NOTE: Saved recording file xxx.sdr cannot be read using the SYMAP-Parameter Tool
(SCPT) application software! However, the file can be converted to Comtrade
format. The Comtrade file can then be opened using appropriate software.
The event history saves up to 10000 events by using the first-in-first-out (FIFO) principle. Each
event provides information such as:
the consecutive number
the event number
the event text
date and time stamp
NOTE: In the displayed event list active events are are highlighted light green; and inactive
events are represented with white backgroung colour.
The latest event is always assigned to consecutive number 0.
Events are recorded with a temporal resolution of 1ms, and will be displayed in chronological
order. The latest event is on the top of the event list. To scroll the list either use button Up/Down
or the scroll bar on the left of the display.
To refresh the displayed event list automatically, an Auto Refresh button is available on the
screen, with the settings:
ON: will activate automatic refresh.
OFF: will deactivate automatic refresh of the displayed event list.
NOTE: When using the scroll buttons or the scroll bar, the automatic refresh of the event list
is stopped (Auto Refresh: OFF).
The fault recorder saves up to 1000 recordings by using the first-in-first-out (FIFO) principle.
When fault recording is started by the active trigger-event which is assigned to parameter
Trigger event [P8061] (see menu: RECORDING/Fault recorder), it takes a snapshot of the
measurement values.
In addition to any trigger-event (assigned event to parameter P[8061] or any trip-event), fault
recording can also be started manually via the Trigger hotkey. In this case, there is no
registered event-number in the fault recorder, but the Manual trigger event-text will be
indicated.
NOTE: The recorded data of each fault recording is saved as an individual fault recording file
(xxx.sfr) on the SD card. A read-out of the recording file data is only possible via
SYMAP-Compact Parameter Tool (SCPT)!
The recorded data of a fault recording can be shown on the device display via double-
clicking the selected file entry on the following menu page:
Main Menu\Recorder\Fault Recorder.
2.4.6 Settings
This page allows changes to device settings of colour and brightness of LC-display, menu
language and time, displayed single line diagram, entering different user levels. By the
submenu Resets all available counters and memories can be reset.
2.4.6.1 Display
Settings of colour layout and brightness for menu pages components can be changed for the
following ranges:
Background colour of menu pages (Page Background)
Background colour of hotkey lower half (Button Bottom)
Background colour of hotkey upper half (Button Top)
Text colour of Hotkeys (Button Text)
Settings of brightness only refer to the whole menu page. For changing brightness please use
the touch-screen slider control. Colours can be adapted separately by red, green and blue. The
array Preview shows the adjusted colour scheme. To save the settings, press button Apply.
For resetting the colour scheme to factory settings, press button Restore Defaults.
Menu language, date and time can be set under Change Language & Time.
Changing to different user levels via touchscreen is possible under Change User Level.
2.4.6.4 Reset
After pressing the EBS automatic configuration hotkey of Reset menu, a confirmation prompt
for starting the initialisation process will be displayed.
Pressing the OK button will release the initialisation process. The Cancel button returns the
user to the previous menu page.
2.4.7 Info
3 System settings
The event system of SYMAP-Compact(+) allows the user to implement individual applications,
as events are used to activate or deactivate device functions. An event is the internal logic
representation of the device process. The event system offers source and sink events.
The source events have unique and permanent event numbers. A source event will be activated
(positive logic: true) if the conditions of this event are met (e.g. threshold exceeded); otherwise
it is inactive (positive logic: false).
Sink events are linked to fixed processes or functions and are user-programmable. The user
may connect source and sink by assigning the source number to the sink. The sink (function)
will then be active as soon as the corresponding source gets active.
NOTE: Some modules are both, a source and a sink; for example all binary outputs are sinks
and activated by a source event. But each binary output, however, again generates
source events upon its activation. The same applies for alarm messages and all
elements of the programmable logic unit (PLC). Source events can be linked via logic
elements of the PLC and then generate new source events.
EXAMPLE: The overcurrent protection ANSI 50/51 is meant to open a breaker via binary
output (Shunt Trip 1). ANSI 50/51 is a source and the binary output a sink. For
instance, an event number referring to ANSI 50/51 is ANSI50/51-1 trip [E1425]
(1st limit attained and delay time run down).
This event number has to be assigned to one parameter (e.g. 01 = 1425) of
the binary output Shunt Trip 1 and, as a consequence, protection trip signal
opens the breaker.
The event list summarizes all software events that are available by the device.
NOTE: Event numbers (e.g. [E1234]) relating to parameter sets (SET1 SET4) exist only once
for all four parameter sets!
Event Event
Event No. Name Description
system recorder
E1091 ANSI27-5 trip
E1094 ANSI27-6 step active
E1095 ANSI27-6 blocked step
E1096 ANSI27-6 blocked step by min. start voltage
E1097 ANSI27-6 blocked step by min. start frequency
E1098 ANSI27-6 pickup
E1099 ANSI27-6 trip
E1102 ANSI27-7 step active
E1103 ANSI27-7 blocked step
E1104 ANSI27-7 blocked step by min. start voltage
E1105 ANSI27-7 blocked step by min. start frequency
E1106 ANSI27-7 pickup
E1107 ANSI27-7 trip
E1110 ANSI27-8 step active
E1111 ANSI27-8 blocked step
E1112 ANSI27-8 blocked step by min. start voltage
E1113 ANSI27-8 blocked step by min. start frequency
E1114 ANSI27-8 pickup
E1115 ANSI27-8 trip
E1118 ANSI27-9 step active
E1119 ANSI27-9 blocked step
E1120 ANSI27-9 blocked step by min. start voltage
E1121 ANSI27-9 blocked step by min. start frequency
E1122 ANSI27-9 pickup
E1123 ANSI27-9 trip
E1126 ANSI27-10 step active
E1127 ANSI27-10 blocked step
E1128 ANSI27-10 blocked step by min. start voltage
E1129 ANSI27-10 blocked step by min. start frequency
E1130 ANSI27-10 pickup
E1131 ANSI27-10 trip
E1134 ANSI27-11 step active
E1135 ANSI27-11 blocked step
E1136 ANSI27-11 blocked step by min. start voltage
E1137 ANSI27-11 blocked step by min. start frequency
E1138 ANSI27-11 pickup
E1139 ANSI27-11 trip
E1142 ANSI27-12 step active
E1143 ANSI27-12 blocked step
E1144 ANSI27-12 blocked step by min. start voltage
E1145 ANSI27-12 blocked step by min. start frequency
E1146 ANSI27-12 pickup
E1147 ANSI27-12 trip
E1150 ANSI59 module active
E1151 ANSI59 blocked module
E1154 ANSI59-1 step active
E1155 ANSI59-1 blocked step
E1156 ANSI59-1 pickup
E1157 ANSI59-1 trip
E1162 ANSI59-2 step active
E1163 ANSI59-2 blocked step
E1163 ANSI59-2 pickup
E1164 ANSI59-2 trip
E1170 ANSI59-3 step active
E1171 ANSI59-3 blocked step
E1172 ANSI59-3 pickup
E1173 ANSI59-3 trip
E1178 ANSI59-4 step active
E1179 ANSI59-4 blocked step
E1180 ANSI59-4 pickup
E1181 ANSI59-4 trip
E1186 ANSI59-5 step active
E1187 ANSI59-5 blocked step
E1188 ANSI59-5 pickup
E1189 ANSI59-5 trip
E1194 ANSI59-6 step active
E1195 ANSI59-6 blocked step
E1196 ANSI59-6 pickup
E1197 ANSI59-6 trip
E1202 ANSI59-7 step active
E1203 ANSI59-7 blocked step
E1204 ANSI59-7 pickup
Event Event
Event No. Name Description
system recorder
E1205 ANSI59-7 trip
E1210 ANSI59-8 step active
E1211 ANSI59-8 blocked step
E1212 ANSI59-8 pickup
E1213 ANSI59-8 trip
E1218 ANSI59-9 step active
E1219 ANSI59-9 blocked step
E1220 ANSI59-9 pickup
E1221 ANSI59-9 trip
E1226 ANSI59-10 step active
E1227 ANSI59-10 blocked step
E1228 ANSI59-10 pickup
E1229 ANSI59-10 trip
E1234 ANSI59-11 step active
E1235 ANSI59-11 blocked step
E1236 ANSI59-11 pickup
E1237 ANSI59-11 trip
E1242 ANSI59-12 step active
E1243 ANSI59-12 blocked step
E1244 ANSI59-12 pickup
E1245 ANSI59-12 trip
E1250 ANSI81 module active
E1251 ANSI81 blocked module
E1254 ANSI81-1 step active
E1255 ANSI81-1 blocked step
E1256 ANSI81-1 blocked step by min. start voltage
E1257 ANSI81-1 pickup
E1258 ANSI81-1 trip
E1262 ANSI81-2 step active
E1263 ANSI81-2 blocked step
E1264 ANSI81-2 blocked step by min. start voltage
E1265 ANSI81-2 pickup
E1266 ANSI81-2 trip
E1270 ANSI81-3 step active
E1271 ANSI81-3 blocked step
E1272 ANSI81-3 blocked step by min. start voltage
E1273 ANSI81-3 pickup
E1274 ANSI81-3 trip
E1278 ANSI81-4 step active
E1279 ANSI81-4 blocked step
E1280 ANSI81-4 blocked step by min. start voltage
E1281 ANSI81-4 pickup
E1282 ANSI81-4 trip
E1286 ANSI81-5 step active
E1287 ANSI81-5 blocked step
E1288 ANSI81-5 blocked step by min. start voltage
E1289 ANSI81-5 pickup
E1290 ANSI81-5 trip
E1294 ANSI81-6 step active
E1295 ANSI81-6 blocked step
E1296 ANSI81-6 blocked step by min. start voltage
E1297 ANSI81-6 pickup
E1298 ANSI81-6 trip
E1302 ANSI81-7 step active
E1303 ANSI81-7 blocked step
E1304 ANSI81-7 blocked step by min. start voltage
E1305 ANSI81-7 pickup
E1306 ANSI81-7 trip
E1310 ANSI81-8 step active
E1311 ANSI81-8 blocked step
E1312 ANSI81-8 blocked step by min. start voltage
E1313 ANSI81-8 pickup
E1314 ANSI81-8 trip
E1318 ANSI81-9 step active
E1319 ANSI81-9 blocked step
E1320 ANSI81-9 blocked step by min. start voltage
E1321 ANSI81-9 pickup
E1322 ANSI81-9 trip
E1326 ANSI81-10 step active
E1327 ANSI81-10 blocked step
E1328 ANSI81-10 blocked step by min. start voltage
E1329 ANSI81-10 pickup
Event Event
Event No. Name Description
system recorder
E1330 ANSI81-10 trip
E1334 ANSI81-11 step active
E1335 ANSI81-11 blocked step
E1336 ANSI81-11 blocked step by min. start voltage
E1337 ANSI81-11 pickup
E1338 ANSI81-11 trip
E1342 ANSI81-12 step active
E1343 ANSI81-12 blocked step
E1344 ANSI81-12 blocked step by min. start voltage
E1345 ANSI81-12 pickup
E1346 ANSI81-12 trip
E1350 ANSI27T module active
E1351 ANSI27T blocked module
E1352 ANSI27T reactivate limit reached
E1353 ANSI27T activate limit reached
E1354 ANSI27T pickup
E1355 ANSI27T trip
E1356 ANSI27T trip by voltage drops count
E1357 ANSI27T trip by curve underrun
E1370 ANSI59N/G module active
E1371 ANSI59N/G blocked module
E1373 ANSI59N/G-1 step active
E1374 ANSI59N/G-1 blocked step
E1375 ANSI59N/G-1 pickup
E1376 ANSI59N/G-1 trip
E1381 ANSI59N/G-2 step active
E1382 ANSI59N/G-2 blocked step
E1383 ANSI59N/G-2 pickup
E1384 ANSI59N/G-2 trip
E1389 ANSI59N/G-3 step active
E1390 ANSI59N/G-3 blocked step
E1391 ANSI59N/G-3 pickup
E1392 ANSI59N/G-3 trip
E1397 ANSI59N/G-4 step active
E1398 ANSI59N/G-4 blocked step
E1399 ANSI59N/G-4 pickup
E1400 ANSI59N/G-4 trip
E1405 ANSI27Q module active
E1406 ANSI27Q blocked module
E1408 ANSI27Q pickup
E1409 ANSI27Q 1st trip
E1410 ANSI27Q 2nd trip
E1412 ANSI27Q voltage reclosing limit reached
E1413 ANSI27Q reclosing release
E1415 ANSI50/51 module active
E1416 ANSI50/51 blocked module
E1422 ANSI50/51-1 step active
E1423 ANSI50/51-1 blocked step
E1424 ANSI50/51-1 pickup
E1425 ANSI50/51-1 trip
E1430 ANSI50/51-2 step active
E1431 ANSI50/51-2 blocked step
E1432 ANSI50/51-2 pickup
E1433 ANSI50/51-2 trip
E1438 ANSI50/51-3 step active
E1439 ANSI50/51-3 blocked step
E1440 ANSI50/51-3 pickup
E1441 ANSI50/51-3 trip
E1446 ANSI50/51-4 step active
E1447 ANSI50/51-4 blocked step
E1448 ANSI50/51-4 pickup
E1449 ANSI50/51-4 trip
E1454 ANSI50/51-5 step active
E1455 ANSI50/51-5 blocked step
E1456 ANSI50/51-5 pickup
E1457 ANSI50/51-5 trip
E1462 ANSI50/51-6 step active
E1463 ANSI50/51-6 blocked step
E1464 ANSI50/51-6 pickup
E1465 ANSI50/51-6 trip
E1470 ANSI95i-CT1 module active
E1471 ANSI95i-CT1 blocked module
Event Event
Event No. Name Description
system recorder
E1472 ANSI95i-CT1 blocked module by Imax
E1473 ANSI95i-CT1 L1 blocked by 2H
E1474 ANSI95i-CT1 L2 blocked by 2H
E1475 ANSI95i-CT1 L3 blocked by 2H
E1476 ANSI95i-CT1 L1 blocked by 5H
E1477 ANSI95i-CT1 L2 blocked by 5H
E1478 ANSI95i-CT1 L3 blocked by 5H
E1479 ANSI95i-CT1 2H supervision blocked
E1480 ANSI95i-CT1 5H supervision blocked
E1485 ANSI95i-CT2 module active
E1486 ANSI95i-CT2 blocked module
E1487 ANSI95i-CT2 blocked module by Imax
E1488 ANSI95i-CT2 L1 blocked by 2H
E1489 ANSI95i-CT2 L2 blocked by 2H
E1490 ANSI95i-CT2 L3 blocked by 2H
E1491 ANSI95i-CT2 L1 blocked by 5H
E1492 ANSI95i-CT2 L2 blocked by 5H
E1493 ANSI95i-CT2 L3 blocked by 5H
E1494 ANSI95i-CT2 2H supervision blocked
E1495 ANSI95i-CT2 5H supervision blocked
E1515 ANSI95i-GND1 module active
E1516 ANSI95i-GND1 blocked module
E1517 ANSI95i-GND1 blocked module by Imax
E1518 ANSI95i-GND1 blocked by 2H
E1519 ANSI95i-GND1 blocked by 5H
E1520 ANSI95i-GND1 2H supervision blocked
E1521 ANSI95i-GND1 5H supervision blocked
E1570 ANSI78 module active
E1571 ANSI78 blocked module
E1576 ANSI78-1 step active
E1577 ANSI78-1 blocked step
E1578 ANSI78-1 blocked by min. start voltage
E1579 ANSI78-1 pickup
E1580 ANSI78-1 trip
E1584 ANSI78-2 step active
E1585 ANSI78-2 blocked step
E1586 ANSI78-2 blocked by min. start voltage
E1587 ANSI78-2 pickup
E1588 ANSI78-2 trip
E1592 ANSI78-3 step active
E1593 ANSI78-3 blocked step
E1594 ANSI78-3 blocked by min. start voltage
E1595 ANSI78-3 pickup
E1596 ANSI78-3 trip
E1630 ANSI87 module active
E1631 ANSI87 blocked module
E1650 ANSI87-1 step active
E1651 ANSI87-1 blocked step
E1652 ANSI87-1 pickup
E1653 ANSI87-1 trip
E1654 ANSI87-1 L1 blocked by CTS
E1655 ANSI87-1 L2 blocked by CTS
E1656 ANSI87-1 L3 blocked by CTS
E1657 ANSI87-1 CTS supervision active
E1670 ANSI87-2 step active
E1671 ANSI87-2 blocked step
E1672 ANSI87-2 pickup
E1673 ANSI87-2 trip
E1680 ANSI50G/51G module active
E1681 ANSI50G/51G blocked module
E1687 ANSI50G/51G-1 step active
E1688 ANSI50G/51G-1 blocked step
E1689 ANSI50G/51G-1 pickup
E1690 ANSI50G/51G-1 trip
E1695 ANSI50G/51G-2 step active
E1696 ANSI50G/51G-2 blocked step
E1697 ANSI50G/51G-2 pickup
E1698 ANSI50G/51G-2 trip
E1703 ANSI50G/51G-3 step active
E1704 ANSI50G/51G-3 blocked step
E1705 ANSI50G/51G-3 pickup
E1706 ANSI50G/51G-3 trip
Event Event
Event No. Name Description
system recorder
E1711 ANSI50G/51G-4 step active
E1712 ANSI50G/51G-4 blocked step
E1713 ANSI50G/51G-4 pickup
E1714 ANSI50G/51G-4 trip
E1719 ANSI50G/51G-5 step active
E1720 ANSI50G/51G-5 blocked step
E1721 ANSI50G/51G-5 pickup
E1722 ANSI50G/51G-5 trip
E1727 ANSI50G/51G-6 step active
E1728 ANSI50G/51G-6 blocked step
E1729 ANSI50G/51G-6 pickup
E1730 ANSI50G/51G-6 trip
E1735 ANSI67 module active
E1736 ANSI67 blocked module
E1741 ANSI67-1 step active
E1742 ANSI67-1 blocked step
E1743 ANSI67-1 pickup L1
E1744 ANSI67-1 pickup L2
E1745 ANSI67-1 pickup L3
E1746 ANSI67-1 pickup
E1747 ANSI67-1 trip L1
E1748 ANSI67-1 trip L2
E1749 ANSI67-1 trip L3
E1750 ANSI67-1 trip
E1751 ANSI67-1 low voltage L1
E1752 ANSI67-1 low voltage L2
E1753 ANSI67-1 low voltage L3
E1757 ANSI67-2 step active
E1758 ANSI67-2 blocked step
E1759 ANSI67-2 pickup L1
E1760 ANSI67-2 pickup L2
E1761 ANSI67-2 pickup L3
E1762 ANSI67-2 pickup
E1763 ANSI67-2 trip L1
E1764 ANSI67-2 trip L2
E1765 ANSI67-2 trip L3
E1766 ANSI67-2 trip
E1767 ANSI67-2 low voltage L1
E1768 ANSI67-2 low voltage L2
E1769 ANSI67-2 low voltage L3
E1773 ANSI67-3 step active
E1774 ANSI67-3 blocked step
E1775 ANSI67-3 pickup L1
E1776 ANSI67-3 pickup L2
E1777 ANSI67-3 pickup L3
E1778 ANSI67-3 pickup
E1779 ANSI67-3 trip L1
E1780 ANSI67-3 trip L2
E1781 ANSI67-3 trip L3
E1782 ANSI67-3 trip
E1783 ANSI67-3 low voltage L1
E1784 ANSI67-3 low voltage L2
E1785 ANSI67-3 low voltage L3
E1789 ANSI67-4 step active
E1790 ANSI67-4 blocked step
E1791 ANSI67-4 pickup L1
E1792 ANSI67-4 pickup L2
E1793 ANSI67-4 pickup L3
E1794 ANSI67-4 pickup
E1795 ANSI67-4 trip L1
E1796 ANSI67-4 trip L2
E1797 ANSI67-4 trip L3
E1798 ANSI67-4 trip
E1799 ANSI67-4 low voltage L1
E1800 ANSI67-4 low voltage L2
E1801 ANSI67-4 low voltage L3
E1805 ANSI32 module active
E1806 ANSI32 blocked module
E1807 ANSI32-1 step active
E1808 ANSI32-1 blocked step
E1809 ANSI32-1 pickup
E1810 ANSI32-1 trip
Event Event
Event No. Name Description
system recorder
E1815 ANSI32-2 step active
E1816 ANSI32-2 blocked step
E1817 ANSI32-2 pickup
E1818 ANSI32-2 trip
E1823 ANSI32-3 step active
E1824 ANSI32-3 blocked step
E1825 ANSI32-3 pickup
E1826 ANSI32-3 trip
E1831 ANSI32-4 step active
E1832 ANSI32-4 blocked step
E1833 ANSI32-4 pickup
E1834 ANSI32-4 trip
E1839 ANSI32-5 step active
E1840 ANSI32-5 blocked step
E1841 ANSI32-5 pickup
E1842 ANSI32-5 trip
E1847 ANSI32-6 step active
E1848 ANSI32-6 blocked step
E1849 ANSI32-6 pickup
E1850 ANSI32-6 trip
E1855 ANSI25-1 Active
E1856 ANSI25-1 Blocked
E1857 ANSI25-1 Negative phase seq. PT1
E1858 ANSI25-1 Negative phase seq. PT2
E1865 ANSI25-1 SC: Blocked
E1866 ANSI25-1 SC: PT1 > Max. voltage
E1867 ANSI25-1 SC: PT1 < Min. voltage
E1868 ANSI25-1 SC: PT1 > Max. frequency
E1869 ANSI25-1 SC: PT1 < Min. frequency
E1870 ANSI25-1 SC: PT1 in range
E1871 ANSI25-1 SC: PT2 > Max. voltage
E1872 ANSI25-1 SC: PT2 < Min. voltage
E1873 ANSI25-1 SC: PT2 > Max. frequency
E1874 ANSI25-1 SC: PT2 < Min. frequency
E1875 ANSI25-1 SC: PT2 in range
E1876 ANSI25-1 SC: dU > Max. dU
E1877 ANSI25-1 SC: dU < Min. dU
E1878 ANSI25-1 SC: dU in range
E1879 ANSI25-1 SC: df < Min. df
E1880 ANSI25-1 SC: df > Max. df
E1881 ANSI25-1 SC: df in range
E1882 ANSI25-1 SC: dPHI < Min. dPHI
E1883 ANSI25-1 SC: dPHI > Max. dPHI
E1884 ANSI25-1 SC: dPHI in range
E1885 ANSI25-1 SC: Synchronous pre-event
E1886 ANSI25-1 SC: Synchronous
E1890 ANSI25-1 VC: Blocked
E1891 ANSI25-1 VC: PT1 > Max. voltage
E1892 ANSI25-1 VC: PT1 < Min. voltage
E1893 ANSI25-1 VC: PT1 > Max. frequency
E1894 ANSI25-1 VC: PT1 < Min. frequency
E1895 ANSI25-1 VC: PT1 in range
E1896 ANSI25-1 VC: PT1 > No voltage limit
E1897 ANSI25-1 VC: PT1 < No voltage limit
E1898 ANSI25-1 VC: PT2 > Max. voltage
E1899 ANSI25-1 VC: PT2 < Min. voltage
E1900 ANSI25-1 VC: PT2 > Max. fequency
E1901 ANSI25-1 VC: PT2 < Min. frequency
E1902 ANSI25-1 VC: PT2 in range
E1903 ANSI25-1 VC: PT2 > No voltage limit
E1904 ANSI25-1 VC: PT2 < No voltage limit
E1905 ANSI25-1 VC: Synchronous pre-event
E1906 ANSI25-1 VC: Synchronous
E1910 ANSI25-2 Active
E1911 ANSI25-2 Blocked
E1912 ANSI25-2 Negative phase seq. PT1
E1913 ANSI25-2 Negative phase seq. PT3
E1920 ANSI25-2 SC: Blocked
E1921 ANSI25-2 SC: PT1 > Max. voltage
E1922 ANSI25-2 SC: PT1 < Min. voltage
E1923 ANSI25-2 SC: PT1 > Max. frequency
E1924 ANSI25-2 SC: PT1 < Min. frequency
Event Event
Event No. Name Description
system recorder
E1925 ANSI25-2 SC: PT1 in range
E1926 ANSI25-2 SC: PT3 > Max. voltage
E1927 ANSI25-2 SC: PT3 < Min. voltage
E1928 ANSI25-2 SC: PT3 > Max. frequency
E1929 ANSI25-2 SC: PT3 < Min. frequency
E1930 ANSI25-2 SC: PT3 in range
E1931 ANSI25-2 SC: dU > Max. dU
E1932 ANSI25-2 SC: dU < Min. dU
E1933 ANSI25-2 SC: dU in range
E1934 ANSI25-2 SC: df > Max. df
E1935 ANSI25-2 SC: df < Min. df
E1936 ANSI25-2 SC: df in range
E1937 ANSI25-2 SC: dPHI > Max. dPHI
E1938 ANSI25-2 SC: dPHI < Min. dPHI
E1939 ANSI25-2 SC: dPHI in range
E1940 ANSI25-2 SC: Synchronous pre-event
E1941 ANSI25-2 SC: Synchronous
E1945 ANSI25-2 VC: Blocked
E1946 ANSI25-2 VC: PT1 > Max. voltage
E1947 ANSI25-2 VC: PT1 < Min. voltage
E1948 ANSI25-2 VC: PT1 > Max. frequency
E1949 ANSI25-2 VC: PT1 < Min. frequency
E1950 ANSI25-2 VC: PT1 in range
E1951 ANSI25-2 VC: PT1 > No voltage limit
E1952 ANSI25-2 VC: PT1 < No voltage limit
E1953 ANSI25-2 VC: PT3 > Max. voltage
E1954 ANSI25-2 VC: PT3 < Min. voltage
E1955 ANSI25-2 VC: PT3 > Max. frequency
E1956 ANSI25-2 VC: PT3 < Min. frequency
E1957 ANSI25-2 VC: PT3 in range
E1958 ANSI25-2 VC: PT3 > No voltage limit
E1959 ANSI25-2 VC: PT3 < No voltage limit
E1960 ANSI25-2 VC: Synchronous pre-event
E1961 ANSI25-2 VC: Synchronous
E1965 ANSI25-3 Active
E1966 ANSI25-3 Blocked
E1967 ANSI25-3 Negative phase seq. PT2
E1968 ANSI25-3 Negative phase seq. PT3
E1975 ANSI25-3 SC: Blocked
E1976 ANSI25-3 SC: PT2 > Max. voltage
E1977 ANSI25-3 SC: PT2 < Min. voltage
E1978 ANSI25-3 SC: PT2 > Max. frequency
E1979 ANSI25-3 SC: PT2 < Min. frequency
E1980 ANSI25-3 SC: PT2 in range
E1981 ANSI25-3 SC: PT3 > Max. voltage
E1982 ANSI25-3 SC: PT3 < Min. voltage
E1983 ANSI25-3 SC: PT3 > Max. frequency
E1984 ANSI25-3 SC: PT3 < Min. frequency
E1985 ANSI25-3 SC: PT3 in range
E1986 ANSI25-3 SC: dU > Max. dU
E1987 ANSI25-3 SC: dU < Min. dU
E1988 ANSI25-3 SC: dU in range
E1989 ANSI25-3 SC: df > Max. df
E1990 ANSI25-3 SC: df < Min. df
E1991 ANSI25-3 SC: df in range
E1992 ANSI25-3 SC: dPHI > Max. dPHI
E1993 ANSI25-3 SC: dPHI < Min. dPHI
E1994 ANSI25-3 SC: dPHI in range
E1995 ANSI25-3 SC: Synchronous pre-event
E1996 ANSI25-3 SC: Synchronous
E2000 ANSI25-3 VC: Blocked
E2001 ANSI25-3 VC: PT2 > Max. voltage
E2002 ANSI25-3 VC: PT2 < Min. voltage
E2003 ANSI25-3 VC: PT2 > Max. frequency
E2004 ANSI25-3 VC: PT2 < Min. frequency
E2005 ANSI25-3 VC: PT2 in range
E2006 ANSI25-3 VC: PT2 > No voltage limit
E2007 ANSI25-3 VC: PT2 < No voltage limit
E2008 ANSI25-3 VC: PT3 > Max. voltage
E2009 ANSI25-3 VC: PT3 < Min. voltage
E2010 ANSI25-3 VC: PT3 > Max. frequency
E2011 ANSI25-3 VC: PT3 < Min. frequency
Event Event
Event No. Name Description
system recorder
E2012 ANSI25-3 VC: PT3 in range
E2013 ANSI25-3 VC: PT3 > No voltage limit
E2014 ANSI25-3 VC: PT3 < No voltage limit
E2015 ANSI25-3 VC: Synchronous pre-event
E2016 ANSI25-3 VC: Synchronous
E2020 ANSI25A-1 Frequency higher event
E2021 ANSI25A-1 Frequency lower event
E2022 ANSI25A-1 Voltage higher event
E2023 ANSI25A-1 Voltage lower event
E2025 ANSI25A-2 Frequency higher event
E2026 ANSI25A-2 Frequency lower event
E2027 ANSI25A-2 Voltage higher event
E2028 ANSI25A-2 Voltage lower event
E2030 ANSI25A-3 Frequency higher event
E2031 ANSI25A-3 Frequency lower event
E2032 ANSI25A-3 Voltage higher event
E2033 ANSI25A-3 Voltage lower event
E2035 ANSI67G module active
E2036 ANSI67G blocked module
E2038 ANSI67G-1 step active
E2039 ANSI67G-1 blocked step
E2040 ANSI67G-1 pickup
E2041 ANSI67G-1 trip
E2042 ANSI67G-1 low voltage
E2046 ANSI67G-2 step active
E2047 ANSI67G-2 blocked step
E2048 ANSI67G-2 pickup
E2049 ANSI67G-2 trip
E2050 ANSI67G-2 low voltage
E2054 ANSI67G-3 step active
E2055 ANSI67G-3 blocked step
E2056 ANSI67G-3 pickup
E2057 ANSI67G-3 trip
E2058 ANSI67G-3 low voltage
E2062 ANSI67G-4 step active
E2063 ANSI67G-4 blocked step
E2064 ANSI67G-4 pickup
E2065 ANSI67G-4 trip
E2066 ANSI67G-4 low voltage
E2070 PTS-1 symmetry check active
E2071 PTS-1 symmetry check blocked
E2072 PTS-1 symmetry failure
E2073 PTS-1 symmetry failure delayed
E2076 PTS-1 fuse failure check active
E2077 PTS-1 fuse failure check blocked
E2078 PTS-1 fuse failure 3 phase
E2079 PTS-1 fuse failure failure
E2080 PTS-1 fuse failure failure delayed
E2084 PTS-1 general check active
E2085 PTS-1 general check blocked
E2086 PTS-1 general failure
E2087 PTS-1 general failure delayed
E2090 PTS-2 symmetry check active
E2091 PTS-2 symmetry check blocked
E2092 PTS-2 symmetry failure
E2093 PTS-2 symmetry failure delayed
E2096 PTS-2 fuse failure check active
E2097 PTS-2 fuse failure check blocked
E2098 PTS-2 fuse failure 3 phase
E2099 PTS-2 fuse failure failure
E2100 PTS-2 fuse failure failure delayed
E2104 PTS-2 general check active
E2105 PTS-2 general check blocked
E2106 PTS-2 general failure
E2107 PTS-2 general failure delayed
E2110 PTS-3 symmetry check active
E2111 PTS-3 symmetry check blocked
E2112 PTS-3 symmetry failure
E2113 PTS-3 symmetry failure delayed
E2116 PTS-3 fuse failure check active
E2117 PTS-3 fuse failure check blocked
E2118 PTS-3 fuse failure 3 phase
Event Event
Event No. Name Description
system recorder
E2119 PTS-3 fuse failure failure
E2120 PTS-3 fuse failure failure delayed
E2124 PTS-3 general check active
E2125 PTS-3 general check blocked
E2126 PTS-3 general failure
E2127 PTS-3 general failure delayed
E2130 CTS-1 symmetry check active
E2131 CTS-1 symmetry check blocked
E2132 CTS-1 symmetry fault
E2133 CTS-1 symmetry fault delayed
E2135 CTS-1 diff check active
E2136 CTS-1 diff check blocked
E2137 CTS-1 diff fault
E2138 CTS-1 diff fault delayed
E2140 CTS-2 symmetry check active
E2141 CTS-2 symmetry check blocked
E2142 CTS-2 symmetry fault
E2143 CTS-2 symmetry fault delayed
E2145 CTS-2 diff check active
E2146 CTS-2 diff check blocked
E2147 CTS-2 diff fault
E2148 CTS-2 diff fault delayed
E2335 SOTF active
E2336 SOTF blocked
E2338 SOTF-1 active
E2339 SOTF-1 blocked
E2340 SOTF-1 trigger
E2341 SOTF-1 pickup
E2342 SOTF-1 trip
E2344 SOTF-2 active
E2345 SOTF-2 blocked
E2346 SOTF-2 trigger
E2347 SOTF.2 pickup
E2348 SOTF-2 trip
E2160 ANSI79 Ready
E2161 ANSI79 Blocked
E2162 ANSI79 Locked
E2163 ANSI79 Cycle
E2164 ANSI79 1. Pause time
E2165 ANSI79 2. Pause time
E2166 ANSI79 3. Pause time
E2167 ANSI79 4. Pause time
E2168 ANSI79 5. Pause time
E2169 ANSI79 6. Pause time
E2170 ANSI79 7. Pause time
E2171 ANSI79 8. Pause time
E2172 ANSI79 Breaker close command
E2173 ANSI79 Breaker close success time
E2174 ANSI79 Success
E2175 ANSI79 Fail
E2176 ANSI79 Off-time
E2180 YG active
E2181 YG blocked
E2185 YG-1 active
E2186 YG-1 blocked
E2187 YG-1 pickup
E2188 YG-1 trip
E2190 YG-2 active
E2191 YG-2 blocked
E2192 YG-2 pickup
E2193 YG-2 trip
E2195 YG-3 active
E2196 YG-3 blocked
E2197 YG-3 pickup
E2198 YG-3 trip
E2200 YG-4 active
E2201 YG-4 blocked
E2202 YG-4 pickup
E2203 YG-4 trip
E2205 YG-5 active
E2206 YG-5 blocked
E2207 YG-5 pickup
Event Event
Event No. Name Description
system recorder
E2208 YG-5 trip
E2210 YG-6 active
E2211 YG-6 blocked
E2212 YG-6 pickup
E2213 YG-6 trip
E2215 ANSI50BF module active
E2216 ANSI50BF blocked module
E2217 ANSI50BF-1 step active
E2218 ANSI50BF-1 blocked step
E2219 ANSI50BF-1 pickup
E2220 ANSI50BF-1 trip
E2223 ANSI50BF-2 step active
E2224 ANSI50BF-2 blocked step
E2225 ANSI50BF-2 pickup
E2226 ANSI50BF-2 trip
E2229 ANSI50BF-3 step active
E2230 ANSI50BF-3 blocked step
E2231 ANSI50BF-3 pickup
E2232 ANSI50BF-3 trip
E2235 ANSI74TC active
E2236 ANSI74TC blocked
E2237 ANSI74TC pickup
E2238 ANSI74TC trip
E2240 ANSI51/46VR module active
E2241 ANSI51/46VR blocked module
E2242 ANSI51/46VR prot.blocking
E2245 ANSI46 module active
E2246 ANSI46 blocked module
E2248 ANSI46-1 step active
E2249 ANSI46-1 blocked step
E2250 ANSI46-1 pickup
E2251 ANSI46-1 trip
E2256 ANSI46-2 step active
E2257 ANSI46-2 blocked step
E2258 ANSI46-2 pickup
E2259 ANSI46-2 trip
E2264 ANSI46-3 step active
E2265 ANSI46-3 blocked step
E2266 ANSI46-3 pickup
E2267 ANSI46-3 trip
E2272 ANSI46-4 step active
E2273 ANSI46-4 blocked step
E2274 ANSI46-4 pickup
E2275 ANSI46-4 trip
E2280 ANSI32N/G module active
E2281 ANSI32N/G blocked module
E2282 ANSI32N/G-1 step active
E2283 ANSI32N/G-1 blocked step
E2284 ANSI32N/G-1 pickup
E2285 ANSI32N/G-1 trip
E2290 ANSI32N/G-2 step active
E2291 ANSI32N/G-2 blocked step
E2292 ANSI32N/G-2 pickup
E2293 ANSI32N/G-2 trip
E2298 ANSI32N/G-3 step active
E2299 ANSI32N/G-3 blocked step
E2300 ANSI32N/G-3 pickup
E2301 ANSI32N/G-3 trip
E2306 ANSI32N/G-4 step active
E2307 ANSI32N/G-4 blocked step
E2308 ANSI32N/G-4 pickup
E2309 ANSI32N/G-4 trip
E2314 ANSI32N/G-5 step active
E2315 ANSI32N/G-5 blocked step
E2316 ANSI32N/G-5 pickup
E2317 ANSI32N/G-5 trip
E2322 ANSI32N/G-6 step active
E2323 ANSI32N/G-6 blocked step
E2324 ANSI32N/G-6 pickup
E2325 ANSI32N/G-6 trip
E2330 CLD active
E2331 CLD blocked
Event Event
Event No. Name Description
system recorder
E2332 CLD pickup
E2333 CLD cold load
E2350 ANSI49 module active
E2351 ANSI49 module blocked
E2352 ANSI49-1 step active
E2353 ANSI49-1 step blocked
E2354 ANSI49-1 warning
E2355 ANSI49-1 trip
E2356 ANSI49-2 step active
E2357 ANSI49-2 step blocked
E2358 ANSI49-2 warning
E2359 ANSI49-2 trip
E2360 ANSI49-3 step active
E2361 ANSI49-3 step blocked
E2362 ANSI49-3 warning
E2363 ANSI49-3 trip
E2364 ANSI49-4 step active
E2365 ANSI49-4 step blocked
E2366 ANSI49-4 warning
E2367 ANSI49-4 trip
E2368 ANSI86 module active
E2370 ANSI64REF active
E2371 ANSI64REF blocked
E2372 ANSI64REF-1 active
E2374 ANSI64REF-1 blocked
E2375 ANSI64REF-1 pickup
E2376 ANSI64REF-1 trip
E2379 ANSI64REF-2 active
E2380 ANSI64REF-2 blocked
E2381 ANSI64REF-2 pickup
E2382 ANSI64REF-2 trip
E2385 ANSI21FL active
E2386 ANSI21FL blocked
E2387 ANSI21FL busy
E2390 TIG active
E2391 TIG blocked
E2392 TIG pickup
E2393 TIG trip
E2395 DCVM module active
E2396 DCVM module blocked
E2397 DCVM-1 step active
E2398 DCVM-1 blocked step
E2399 DCVM-1 overvoltage pickup
E2400 DCVM-1 overvoltage trip
E2401 DCVM-1 undervoltage pickup
E2402 DCVM-1 undervoltage trip
E2403 DCVM-1 GF +pole pickup
E2404 DCVM-1 GF +pole trip
E2405 DCVM-1 GF -pole pickup
E2406 DCVM-1 GF -pole trip
E2407 DCVM-2 step active
E2408 DCVM-2 blocked step
E2409 DCVM-2 overvoltage pickup
E2410 DCVM-2 overvoltage trip
E2411 DCVM-2 undervoltage pickup
E2412 DCVM-2 undervoltage trip
E2413 DCVM-2 GF +pole pickup
E2414 DCVM-2 GF +pole trip
E2415 DCVM-2 GF -pole pickup
E2416 DCVM-2 GF -pole trip
E2417 DCVM-3 step active
E2418 DCVM-3 blocked step
E2419 DCVM-3 overvoltage pickup
E2420 DCVM-3 overvoltage trip
E2421 DCVM-3 undervoltage pickup
E2422 DCVM-3 undervoltage trip
E2423 DCVM-3 GF +pole pickup
E2424 DCVM-3 GF +pole trip
E2425 DCVM-3 GF -pole pickup
E2426 DCVM-3 GF -pole trip
E2427 DCVM-4 step active
E2428 DCVM-4 blocked step
Event Event
Event No. Name Description
system recorder
E2429 DCVM-4 overvoltage pickup
E2430 DCVM-4 overvoltage trip
E2431 DCVM-4 undervoltage pickup
E2432 DCVM-4 undervoltage trip
E2433 DCVM-4 GF +pole pickup
E2434 DCVM-4 GF +pole trip
E2435 DCVM-4 GF -pole pickup
E2436 DCVM-4 GF -pole trip
E2437 DCVM-5 step active
E2438 DCVM-5 blocked step
E2439 DCVM-5 overvoltage pickup
E2440 DCVM-5 overvoltage trip
E2441 DCVM-5 undervoltage pickup
E2442 DCVM-5 undervoltage trip
E2443 DCVM-5 GF +pole pickup
E2444 DCVM-5 GF +pole trip
E2445 DCVM-5 GF -pole pickup
E2446 DCVM-5 GF -pole trip
E2447 DCVM-6 step active
E2448 DCVM-6 blocked step
E2449 DCVM-6 overvoltage pickup
E2450 DCVM-6 overvoltage trip
E2451 DCVM-6 undervoltage pickup
E2452 DCVM-6 undervoltage trip
E2453 DCVM-6 GF +pole pickup
E2454 DCVM-6 GF +pole trip
E2455 DCVM-6 GF -pole pickup
E2456 DCVM-6 GF -pole trip
E2457 ANSI37 module active
E2458 ANSI37 module blocked
E2459 ANSI37-1 step active
E2460 ANSI37-1 blocked step
E2461 ANSI37-1 pickup
E2462 ANSI37-1 trip
E2463 ANSI37-2 step active
E2464 ANSI37-2 blocked step
E2465 ANSI37-2 pickup
E2466 ANSI37-2 trip
E2467 ANSI37-3 step active
E2468 ANSI37-3 blocked step
E2469 ANSI37-3 pickup
E2470 ANSI37-3 trip
E2471 ANSI81R module active
E2472 ANSI81R blocked module
E2473 ANSI81R-1 step active
E2474 ANSI81R-1 blocked step
E2475 ANSI81R-1 pickup
E2476 ANSI81R-1 trip
E2477 ANSI81R-2 step active
E2478 ANSI81R-2 blocked step
E2479 ANSI81R-2 pickup
E2480 ANSI81R-2 trip
E2481 ANSI81R-3 step active
E2482 ANSI81R-3 blocked step
E2483 ANSI81R-3 pickup
E2484 ANSI81R-3 trip
E2485 ANSI81R-4 step active
E2486 ANSI81R-4 blocked step
E2487 ANSI81R-4 pickup
E2488 ANSI81R-4 trip
E2489 ANSI81R-5 step active
E2490 ANSI81R-5 blocked step
E2491 ANSI81R-5 pickup
E2492 ANSI81R-5 trip
E2493 ANSI81R-6 step active
E2494 ANSI81R-6 blocked step
E2495 ANSI81R-6 pickup
E2496 ANSI81R-6 trip
E2497 ANSI47 module active
E2498 ANSI47 blocked module
E2499 ANSI47-1 step active
E2500 ANSI47-1 blocked step
Event Event
Event No. Name Description
system recorder
E2501 ANSI47-1 pickup
E2502 ANSI47-1 trip
E2503 ANSI47-2 step active
E2504 ANSI47-2 blocked step
E2505 ANSI47-2 pickup
E2506 ANSI47-2 trip
E2507 ANSI47-3 step active
E2508 ANSI47-3 blocked step
E2509 ANSI47-3 pickup
E2510 ANSI47-3 trip
E2511 ANSI47-4 step active
E2512 ANSI47-4 blocked step
E2513 ANSI47-4 pickup
E2514 ANSI47-4 trip
E2515 ANSI47-5 step active
E2516 ANSI47-5 blocked step
E2517 ANSI47-5 pickup
E2518 ANSI47-5 trip
E2519 ANSI47-6 step active
E2520 ANSI47-6 blocked step
E2521 ANSI47-6 pickup
E2522 ANSI47-6 trip
E2523 ANSI52 module active
E2524 ANSI52 blocked module
E2525 ANSI52-1 step active
E2526 ANSI52-1 blocked step
E2527 ANSI52-1 pickup
E2528 ANSI52-1 trip
E2529 ANSI52-2 step active
E2530 ANSI52-2 blocked step
E2531 ANSI52-2 pickup
E2532 ANSI52-2 trip
E2533 ANSI52-3 step active
E2534 ANSI52-3 blocked step
E2535 ANSI52-3 pickup
E2536 ANSI52-3 trip
E2537 ANSI21 module active
E2538 ANSI21 blocked module
E2539 ANSI21 group B active
E2540 ANSI21 low voltage
E2545 ANSI21 pickup
E2546 ANSI21 earth fault pickup
E2547 ANSI21 pickup loop L1-E
E2548 ANSI21 pickup loop L2-E
E2549 ANSI21 pickup loop L3-E
E2550 ANSI21 pickup loop L1-L2
E2551 ANSI21 pickup loop L2-L3
E2552 ANSI21 pickup loop L3-L1
E2553 ANSI21-1 zone active
E2554 ANSI21-1 blocked zone
E2561 ANSI21-1 pickup
E2562 ANSI21-1 pickup L1
E2563 ANSI21-1 pickup L2
E2564 ANSI21-1 pickup L3
E2565 ANSI21-1 trip
E2566 ANSI21-1 trip L1
E2567 ANSI21-1 trip L2
E2568 ANSI21-1 trip L3
E2569 ANSI21-2 zone active
E2570 ANSI21-2 blocked zone
E2577 ANSI21-2 pickup
E2578 ANSI21-2 pickup L1
E2579 ANSI21-2 pickup L2
E2580 ANSI21-2 pickup L3
E2581 ANSI21-2 trip
E2582 ANSI21-2 trip L1
E2583 ANSI21-2 trip L2
E2584 ANSI21-2 trip L3
E2585 ANSI21-3 zone active
E2586 ANSI21-3 blocked zone
E2593 ANSI21-3 pickup
E2594 ANSI21-3 pickup L1
Event Event
Event No. Name Description
system recorder
E2595 ANSI21-3 pickup L2
E2596 ANSI21-3 pickup L3
E2597 ANSI21-3 trip
E2598 ANSI21-3 trip L1
E2599 ANSI21-3 trip L2
E2600 ANSI21-3 trip L3
E2601 ANSI21-4 zone active
E2602 ANSI21-4 blocked zone
E2609 ANSI21-4 pickup
E2610 ANSI21-4 pickup L1
E2611 ANSI21-4 pickup L2
E2612 ANSI21-4 pickup L3
E2613 ANSI21-4 trip
E2614 ANSI21-4 trip L1
E2615 ANSI21-4 trip L2
E2616 ANSI21-4 trip L3
E2617 ANSI21-5 zone active
E2618 ANSI21-5 blocked zone
E2625 ANSI21-5 pickup
E2626 ANSI21-5 pickup L1
E2627 ANSI21-5 pickup L2
E2628 ANSI21-5 pickup L3
E2629 ANSI21-5 trip
E2630 ANSI21-5 trip L1
E2631 ANSI21-5 trip L2
E2632 ANSI21-5 trip L3
Event Event
Event No. Name Description
system recorder
E4740 E4779
E4210 Binary input Fct. 10 inverted event Binary input event inverted event
E4211 Binary input Fct. 11 inverted event Binary input event inverted event
E4212 Binary input Fct. 12 inverted event Binary input event inverted event
E4213 Binary input Fct. 13 inverted event Binary input event inverted event
E4214 Binary input Fct. 14 inverted event Binary input event inverted event
E4215 Binary input Fct. 15 inverted event Binary input event inverted event
E4216 Binary input Fct. 16 inverted event Binary input event inverted event
E4217 Binary input Fct. 17 inverted event Binary input event inverted event
E4218 Binary input Fct. 18 inverted event Binary input event inverted event
E4219 Binary input Fct. 19 inverted event Binary input event inverted event
E4220 Binary input Fct. 20 inverted event Binary input event inverted event
E4221 Binary input Fct. 21 inverted event Binary input event inverted event
E4222 Binary input Fct. 22 inverted event Binary input event inverted event
E4223 Binary input Fct. 23 inverted event Binary input event inverted event
E4224 Binary input Fct. 24 inverted event Binary input event inverted event
E4225 Binary input Fct. 25 inverted event Binary input event inverted event
E4226 Binary input Fct. 26 inverted event Binary input event inverted event
E4227 Binary input Fct. 27 inverted event Binary input event inverted event
E4228 Binary input Fct. 28 inverted event Binary input event inverted event
E4229 E4299
Extension Board System EBS:
and EBS: inverted event Fct. x
binary input Fct. x: inverted event
E4780 E4819
Active if any of the wirefault events is
4300 Binary input general wirefault event
active
E4310 Binary input Fct. 10 wirefault event Binary input event wirefault event
E4311 Binary input Fct. 11 wirefault event Binary input event wirefault event
E4312 Binary input Fct. 12 wirefault event Binary input event wirefault event
E4313 Binary input Fct. 13 wirefault event Binary input event wirefault event
E4314 Binary input Fct. 14 wirefault event Binary input event wirefault event
E4315 Binary input Fct. 15 wirefault event Binary input event wirefault event
E4316 Binary input Fct. 16 wirefault event Binary input event wirefault event
E4317 Binary input Fct. 17 wirefault event Binary input event wirefault event
E4318 Binary input Fct. 18 wirefault event Binary input event wirefault event
E4319 Binary input Fct. 19 wirefault event Binary input event wirefault event
E4320 Binary input Fct. 20 wirefault event Binary input event wirefault event
E4321 Binary input Fct. 21 wirefault event Binary input event wirefault event
E4322 Binary input Fct. 22 wirefault event Binary input event wirefault event
E4323 Binary input Fct. 23 wirefault event Binary input event wirefault event
E4324 Binary input Fct. 24 wirefault event Binary input event wirefault event
E4325 Binary input Fct. 25 wirefault event Binary input event wirefault event
E4326 Binary input Fct. 26 wirefault event Binary input event wirefault event
E4327 Binary input Fct. 27 wirefault event Binary input event wirefault event
E4328 Binary input Fct. 28 wirefault event Binary input event wirefault event
E4329 E4399
Extension Board System EBS:
and EBS: wirefault event Fct. x
Binary input Fct. x: wirefault
E4820 E4859
Active if one of the short circuit events
4400 Binary input general shortcircuit event
is active
E4410 Binary input Fct. 10 shortcircuit event Binary input event shortcircuit event
E4411 Binary input Fct. 11 shortcircuit event Binary input event shortcircuit event
E4412 Binary input Fct. 12 shortcircuit event Binary input event shortcircuit event
E4413 Binary input Fct. 13 shortcircuit event Binary input event shortcircuit event
E4414 Binary input Fct. 14 shortcircuit event Binary input event shortcircuit event
E4415 Binary input Fct. 15 shortcircuit event Binary input event shortcircuit event
E4416 Binary input Fct. 16 shortcircuit event Binary input event shortcircuit event
E4417 Binary input Fct. 17 shortcircuit event Binary input event shortcircuit event
E4418 Binary input Fct. 18 shortcircuit event Binary input event shortcircuit event
E4419 Binary input Fct. 19 shortcircuit event Binary input event shortcircuit event
E4420 Binary input Fct. 20 shortcircuit event Binary input event shortcircuit event
E4421 Binary input Fct. 21 shortcircuit event Binary input event shortcircuit event
E4422 Binary input Fct. 22 shortcircuit event Binary input event shortcircuit event
E4423 Binary input Fct. 23 shortcircuit event Binary input event shortcircuit event
E4424 Binary input Fct. 24 shortcircuit event Binary input event shortcircuit event
E4425 Binary input Fct. 25 shortcircuit event Binary input event shortcircuit event
E4426 Binary input Fct. 26 shortcircuit event Binary input event shortcircuit event
E4427 Binary input Fct. 27 shortcircuit event Binary input event shortcircuit event
E4428 Binary input Fct. 28 shortcircuit event Binary input event shortcircuit event
E4429 E4499
Extension Board System EBS:
and EBS: shortcircuit Fct. x
Binary input Fct. x:shortcircuit
E4860 E4899
Event Event
Event No. Name Description
system recorder
Binary output events E4500 E4599
E4500 Shunt Trip 1 output set Shunt Trip 1 output event
E4501 Shunt Trip 2 output set Shunt Trip 2 output event
E4502 Lockout relay set Lockout relay event
E4503 Lockout relay predelay Lockout relay predelay event
E4504 Synchron relay set Synchron relay event
E4505 Synchron relay predelay Synchron relay predelay event
E4506 Function output Fct. 1 set Function output 1event
E4507 Function output Fct. 1 predelay Function output 1 predelay event
E4508 Function output Fct. 2 set Function output 2 event
E4509 Function output Fct. 2 predelay Function output 2 predelay event
E4510 Function output Fct. 3 set Function output 3 event
E4511 Function output Fct. 3 predelay Function output 3 predelay event
E4512 Function output Fct. 4 set Function output 4 event
E4513 Function output Fct. 4 predelay Function output 4 predelay event
E4514 Function output Fct. 5 set Function output 5 event
E4515 Function output Fct. 5 predelay Function output 5 predelay event
E4516 Function output Fct. 6 set Function output 6 event
E4517 Function output Fct. 6 predelay Function output 6 predelay event
E4518 Function output Fct. 7 set Function output 7 event
E4519 Function output Fct. 7 predelay Function output 7 predelay event
E4520 Function output Fct. 8 set Function output 8 event
E4521 Function output Fct. 8 predelay Function output 8 predelay event
Extension Board System EBS:
E4522 EBS: Function output 1 activated
Function output 1: output event
Extension Board System EBS:
EBS: Function output 1 additional predelayed
E4523 Function output 1: delayed output
event activated
event
Extension Board System EBS:
E4680 EBS: Function output 80 activated
Function output 80: output event
Extension Board System EBS:
EBS: Function output 80 additional predelayed
E4681 Function output 80: delayed output
event activated
event
Analog input events E4900 E4902
E4900 Analog inputs: wirefault Analog inputs general event: wirefault
Analog inputs 3
E4901 Analog input 3: wirefault
(0 to 20mA): wirefault
Analog inputs 4
E4902 Analog input 4: wirefault
(0 to 20mA): wirefault
Event system
E5950 Event history stop Event recording stop is active
Breaker feedback events E6010 E6085
E6010 ON-Feedback 1 Breaker 1 (feedback)
E6011 OFF-Feedback 1 Breaker 1 (feedback)
E6012 OUT-Feedback 1 Breaker 1 (feedback)
E6013 IN-Feedback 1 Breaker 1 (feedback)
E6014 EARTH ON-Feedback 1 Breaker 1 (feedback)
E6015 EARTH OFF-Feedback 1 Breaker 1 (feedback)
E6020 ON-Feedback 2 Breaker 2 (feedback)
E6021 OFF-Feedback 2 Breaker 2 (feedback)
E6022 OUT-Feedback 2 Breaker 2 (feedback)
E6023 IN-Feedback 2 Breaker 2 (feedback)
E6024 EARTH ON-Feedback 2 Breaker 2 (feedback)
E6025 EARTH OFF-Feedback 2 Breaker 2 (feedback)
E6030 ON-Feedback 3 Breaker 3 (feedback)
E6031 OFF-Feedback 3 Breaker 3 (feedback)
E6032 OUT-Feedback 3 Breaker 3 (feedback)
E6033 IN-Feedback 3 Breaker 3 (feedback)
E6034 EARTH ON-Feedback 3 Breaker 3 (feedback)
E6035 EARTH OFF-Feedback 3 Breaker 3 (feedback)
E6040 ON-Feedback 4 Breaker 4 (feedback)
E6041 OFF-Feedback 4 Breaker 4 (feedback)
E6042 OUT-Feedback 4 Breaker 4 (feedback)
E6043 IN-Feedback 4 Breaker 4 (feedback)
E6044 EARTH ON-Feedback 4 Breaker 4 (feedback)
E6045 EARTH OFF-Feedback 4 Breaker 4 (feedback)
E6050 ON-Feedback 5 Breaker 5 (feedback)
E6051 OFF-Feedback 5 Breaker 5 (feedback)
E6052 OUT-Feedback 5 Breaker 5 (feedback)
Event Event
Event No. Name Description
system recorder
E6053 IN-Feedback 5 Breaker 5 (feedback)
E6054 EARTH ON-Feedback 5 Breaker 5 (feedback)
E6055 EARTH OFF-Feedback 5 Breaker 5 (feedback)
E6060 ON-Feedback 6 Breaker 6 (feedback)
E6061 OFF-Feedback 6 Breaker 6 (feedback)
E6062 OUT-Feedback 6 Breaker 6 (feedback)
E6063 IN-Feedback 6 Breaker 6 (feedback)
E6064 EARTH ON-Feedback 6 Breaker 6 (feedback)
E6065 EARTH OFF-Feedback 6 Breaker 6 (feedback)
E6070 ON-Feedback 7 Breaker 7 (feedback)
E6071 OFF-Feedback 7 Breaker 7 (feedback)
E6072 OUT-Feedback 7 Breaker 7 (feedback)
E6073 IN-Feedback 7 Breaker 7 (feedback)
E6074 EARTH ON-Feedback 7 Breaker 7 (feedback)
E6075 EARTH OFF-Feedback 7 Breaker 7 (feedback)
E6080 ON-Feedback 8 Breaker 8 (feedback)
E6081 OFF-Feedback 8 Breaker 8 (feedback)
E6082 OUT-Feedback 8 Breaker 8 (feedback)
E6083 IN-Feedback 8 Breaker 8 (feedback)
E6084 EARTH ON-Feedback 8 Breaker 8 (feedback)
E6085 EARTH OFF-Feedback 8 Breaker 8 (feedback)
Breaker position events E6110 E6187
E6110 OPEN 1 Breaker 1 (position)
E6111 CLOSED 1 Breaker 1 (position)
E6112 OUT OPEN 1 Breaker 1 (position)
E6113 OUT CLOSED 1 Breaker 1 (position)
E6114 EARTH 1 Breaker 1 (position)
E6115 DIFF (Moving) 1 Breaker 1 (position)
E6116 FAIL 1 Breaker 1 (position)
E6117 OPEN ERROR 1 Breaker 1 (position)
E6120 OPEN 2 Breaker 2 (position)
E6121 CLOSED 2 Breaker 2 (position)
E6122 OUT OPEN 2 Breaker 2 (position)
E6123 OUT CLOSED 2 Breaker 2 (position)
E6124 EARTH 2 Breaker 2 (position)
E6125 DIFF (Moving) 2 Breaker 2 (position)
E6126 FAIL 2 Breaker 2 (position)
E6127 OPEN ERROR 2 Breaker 2 (position)
E6130 OPEN 3 Breaker 3 (position)
E6131 CLOSED 3 Breaker 3 (position)
E6132 OUT OPEN 3 Breaker 3 (position)
E6133 OUT CLOSED 3 Breaker 3 (position)
E6134 EARTH 3 Breaker 3 (position)
E6135 DIFF (Moving) 3 Breaker 3 (position)
E6136 FAIL 3 Breaker 3 (position)
E6137 OPEN ERROR 3 Breaker 3 (position)
E6140 OPEN 4 Breaker 4 (position)
E6141 CLOSED 4 Breaker 4 (position)
E6142 OUT OPEN 4 Breaker 4 (position)
E6143 OUT CLOSED 4 Breaker 4 (position)
E6144 EARTH 4 Breaker 4 (position)
E6145 DIFF (Moving) 4 Breaker 4 (position)
E6146 FAIL 4 Breaker 4 (position)
E6147 OPEN ERROR 4 Breaker 4 (position)
E6150 OPEN 5 Breaker 5 (position)
E6151 CLOSED 5 Breaker 5 (position)
E6152 OUT OPEN 5 Breaker 5 (position)
E6153 OUT CLOSED 5 Breaker 5 (position)
E6154 EARTH 5 Breaker 5 (position)
E6155 DIFF (Moving) 5 Breaker 5 (position)
E6156 FAIL 5 Breaker 5 (position)
E6157 OPEN ERROR 5 Breaker 5 (position)
E6160 OPEN 6 Breaker 6 (position)
E6161 CLOSED 6 Breaker 6 (position)
E6162 OUT OPEN 6 Breaker 6 (position)
E6163 OUT CLOSED 6 Breaker 6 (position)
E6164 EARTH 6 Breaker 6 (position)
E6165 DIFF (Moving) 6 Breaker 6 (position)
E6166 FAIL 6 Breaker 6 (position)
E6167 OPEN ERROR 6 Breaker 6 (position)
E6170 OPEN 7 Breaker 7 (position)
E6171 CLOSED 7 Breaker 7 (position)
Event Event
Event No. Name Description
system recorder
E6172 OUT OPEN 7 Breaker 7 (position)
E6173 OUT CLOSED 7 Breaker 7 (position)
E6174 EARTH 7 Breaker 7 (position)
E6175 DIFF (Moving) 7 Breaker 7 (position)
E6176 FAIL 7 Breaker 7 (position)
E6177 OPEN ERROR 7 Breaker 7 (position)
E6180 OPEN 8 Breaker 8 (position)
E6181 CLOSED 8 Breaker 8 (position)
E6182 OUT OPEN 8 Breaker 8 (position)
E6183 OUT CLOSED 8 Breaker 8 (position)
E6184 EARTH 8 Breaker 8 (position)
E6185 DIFF (Moving) 8 Breaker 8 (position)
E6186 FAIL 8 Breaker 8 (position)
E6187 OPEN ERROR 8 Breaker 8 (position)
Breaker counter events E6311 E6383
E6311 CLOSED -> OPEN cycles max 1 Breaker 1 (counter)
E6313 OPEN -> EARTH cycles max 1 Breaker 1 (counter)
E6321 CLOSED -> OPEN cycles max 2 Breaker 2 (counter)
E6323 OPEN -> EARTH cycles max 2 Breaker 2 (counter)
E6331 CLOSED -> OPEN cycles max 3 Breaker 3 (counter)
E6333 OPEN -> EARTH cycles max 3 Breaker 3 (counter)
E6341 CLOSED -> OPEN cycles max 4 Breaker 4 (counter)
E6343 OPEN -> EARTH cycles max 4 Breaker 4 (counter)
E6351 CLOSED -> OPEN cycles max 5 Breaker 5 (counter)
E6353 OPEN -> EARTH cycles max 5 Breaker 5 (counter)
E6361 CLOSED -> OPEN cycles max 6 Breaker 6 (counter)
E6363 OPEN -> EARTH cycles max 6 Breaker 6 (counter)
E6371 CLOSED -> OPEN cycles max 7 Breaker 7 (counter)
E6373 OPEN -> EARTH cycles max 7 Breaker 7 (counter)
E6381 CLOSED -> OPEN cycles max 8 Breaker 8 (counter)
E6383 OPEN -> EARTH cycles max 8 Breaker 8 (counter)
Breaker select events E6391 E6398
E6391 Select Breaker 1 Breaker 1 selected via touchscreen
E6392 Select Breaker 2 Breaker 2 selected via touchscreen
E6393 Select Breaker 3 Breaker 3 selected via touchscreen
E6394 Select Breaker 4 Breaker 4 selected via touchscreen
E6395 Select Breaker 5 Breaker 5 selected via touchscreen
E6396 Select Breaker 6 Breaker 6 selected via touchscreen
E6397 Select Breaker 7 Breaker 7 selected via touchscreen
E6398 Select Breaker 8 Breaker 8 selected via touchscreen
Event of assigned function is active as
Function key (front plate) events E6400 E6414
long as button is pressed
E6400 0
E6401 1
E6402 Stop
E6403 Start
E6404 Page Up
E6405 Page Down"
E6406 Key Calls up menu page User levels
E6407 Alarm Ack Acknowledgement of alarms
E6408 Alarm page Calls up menu page Alarms
E6409 Auto/Manual
E6414 Emergency OFF 1 / Emergency OFF 2
8 additional function keys (optionally; front plate) Button event is active as long as
events E6415 E6422 button is pressed
E6415 (not parameterizable) Button 1
E6416 (not parameterizable) Button 2
E6417 (not parameterizable) Button 3
E6418 (not parameterizable) Button 4
E6419 (not parameterizable) Button 5
E6420 (not parameterizable) Button 6
E6421 (not parameterizable) Button 7
E6422 (not parameterizable) Button 8
ComU general events 6432 - 6497
E6432 - E6497 ComU general events ComU general purpose events
ComU GGIO4 events 6500 - 6515
E6500 - E6515 GGIO4 events Events for GGIO4
ComU general events 6516 - 6593
Event Event
Event No. Name Description
system recorder
E6516 - E6593 ComU general events ComU general purpose events
Modbus/Profibus in events 6600 - 6631
E6600 - E6631 Modbus/Profibus in events Could be set via Modbus or Profibus
Operation mode events 6810 - 6811
E6810 Local mode
E6811 Remote mode
User levels E6801 - E6804
E6801 - User level 1 activated
E6802 - User level 2 activated
E6803 - User level 3 activated
E6804 - User level 4 activated
GU user page events E6900 - E6963
Event activated by GU user page
E6900 E6963 GU user page button
button
System events
Event becomes active when system
starts (booting phase) and
E6970 System booting automatically becomes inactive when
system start has finished (booting has
finished).
E6971 WD reset CU Watchdog for reset of control unit (CU)
Watchdog for reset of measuring unit
E6972 WD reset MU
(MU)
Watchdog for reset of graphic unit
E6973 WD reset GU
(GU)
Watchdog for reset of communication
E6974 WD reset ComU
unit (ComU)
E6975 HMI OK Detached HMI operates without error
Device restart after loss of power
E6976 System reset: Power on
supply
Device restart after uploading
E6977 System reset: Parameter file
parameter file
PMS Generator control: E7000 E7274
E7000 Manual mode
E7001 Automatic mode
E7004 Collective event: speed increase
E7005 Collective event: speed decrease
E7006 Collective event: voltage increase
E7007 Collective event: voltage decrease
E7100 Active power controller active
E7101 Active power controller blocked
E7123 Active power increase
E7124 Active power decrease
E7140 Limit active
E7141 Limit reached
E7160 Frequency controller active
E7161 Frequency controller blocked
E7183 Frequency increase
E7184 Frequency decrease
E7200 Voltage controller active
E7201 Voltage controller blocked
E7223 Voltage increase
E7224 Voltage decrease
E7250 Power factor controller active
E7251 Power factor controller blocked
E7273 Excitation increase
E7274 Excitation decrease
E7290 Power factor curve active
Disturbance recorder E8000 - E8007
E8000 DiREC-Ready
E8001 DiREC-Recording
E8002 DiREC-Buffer overflow
E8003 DiREC-Backup
E8004 DiREC-Full memeory
E8005 DiREC-No memory card
E8006 DiREC-Memory error
E8007 DiREC-File error
Event Event
Event No. Name Description
system recorder
Main Menu\Parameters\SETUP
User levels
Event description:
E 6801
to
E 6804
Event of activated user level 1; as soon as one of the four user levels is efffective, then
event [E6801], [E6802], [E6803] or [E6804] is activated.
Parameter description:
Activation
P Priority
Priority setting of the user level against activation of other user levels; when two or more
user levels are activated simultaneously, then, the user level with the highest priority is
activated. According to the setting options of parameter Priority [P], order of priority is
as follows:
2: lowest priority
3: third highest priority
4: highest priority.
NOTE: User level 1 is only active, when none of the user levels 2, 3 and 4 are
activated!
P Password
Enter 4-digit password to activate the relevant user level
P Activation time
Duration for activated user level; as soon as user level 2, 3 or 4 is activated, activation
time set by parameter Activation time [P] starts. As soon as the timer has run down,
SYMAP-Compact(+) automatically activtes user level 1.
P Active by event
User level 2, 3 or 4 can be activated by any active event. For activation, the number
related to this activating event has to be assigned to parameter Active by event [P].
Activation is only effective, however, as long as the activating event is active. As soon as
the user level is active, corresponding event [E6802], [E6803] or [E6804] is activated.
If activation of user level 2, 3 or 4 by the activating event is not required, set this
parameter to 0.
P Block by event
User level 2, 3 or 4 can be blocked by any active event. For blocking, the number related
to this blocking event has to be assigned to parameter Block by event [P]. Blocking is
only effective, however, as long as the blocking event is active.
If blocking of user level 2, 3 or 4 by the blocking event is not required, set this parameter
to 0.
Funktionen (Functions)
P Change language/time
Authorisation for setting parameters of sub-menu Language & Time (Main
Menu/Settings/Language & Time); setting of these parameters is only permitted, if the
user level which is assigned to parameter Change language/time [P] is activated.
Authorisation for blocking of data recordeing and counting functions; blocking of data
recording of event recorder, fault recorder or counting is only permitted, if the user level
which is assigned to parameter Block all histories [P] is activated.
Main Menu\Parameters\SETUP
Measuring inputs
Parameter description:
P91500 PT1
This parameter enables/disables 3-phase voltage measurement input PT1 where:
Enabled: enables or
Disabled: disables the measurement input.
P91501 PT2
This parameter enables/disables 3-phase voltage measurement input PT2 where:
Enabled: enables or
Disabled: disables the measurement input.
P91502 PT3
This parameter enables/disables 3-phase voltage measurement input PT3 where:
Enabled: enables or
Disabled: disables the measurement input.
P91500 PT-GND1
This parameter enables/disables 1-phase voltage measurement input PT-GND1 where:
Enabled: enables or
Disabled: disables the measurement input.
P91510 CT1
This parameter enables/disables 3-phase current measurement input CT1 where:
Enabled: enables or
Disabled: disables the measurement input.
P91511 CT2
This parameter enables/disables 3-phase current measurement input CT2 where:
Enabled: enables or
Disabled: disables the measurement input.
P91510 CT-GND1
This parameter enables/disables 1-phase current measurement input CT-GND1 where:
Enabled: enables or
Disabled: disables the measurement input.
3.3.1 General
The parameters of General submenu refer to parameters settings for time zone and daylight
saving time.
Main Menu\ Parameters\SYSTEM\
General
Parameter description:
Parameters of Nominals menu are for setting rated values of the application. These include:
Rated data for protection functions and measurement values (Reference values),
PT ratios and PT assignment (Potential transformers) and adjustment of PT measuring
ranges,
CT ratios, CT assignment and measurement direction (Current transformers)
Main Menu\Parameters\SYSTEM\Nominals
Reference
Values
P/E No. System Description Value Unit (Setting range)
Primary W1
P600 Connection type Y - none/Y/D
P602 Star point grounding isolated - isolated/compensated/earthed
P603 Voltage (L-L) 20000 V 0 999999
P604 Current 100 A 0 999999,9
P605 Power 3464 kW 0 9999999
P606 Ground voltage 20000 V 0 999999
P607 Ground current 100 A 0 99999,999
Secondary W2
P610 Connection type y - none/y/d
P611 Phase shift 0 deg 1/2/3/4/5/6/7/879/10/11
P612 Star point grounding isolated - isolated/compensated/earthed
P613 Voltage (L-L) 20000 V 0 999999
P614 Current 100 A 0 999999,9
P615 Power 3464 kW 0 9999999
P616 Ground voltage 20000 V 0 999999
P617 Ground current 100 A 0 99999,999
Tertiary W3
P620 Connection type y - none/y/d
P621 Phase shift 0 deg 1/2/3/4/5/6/7/879/10/11
P622 Star point grounding isolated - isolated/compensated/earthed
P623 Voltage (L-L) 20000 V 0 999999
P624 Current 100 A 0 999999,9
P625 Power 3464 kW 0 9999999
P626 Ground voltage 20000 V 0 999999
P627 Ground current 100 A 0 99999,999
Frequency
P630 Nominal frequency 50 Hz 50/60
Figure 3-6 System parameters Reference Values
Parameter description:
P604 Current
Nominal phase current of the primary side W1 (or transformer primary side W1); the
absolute set point is taken as reference quantity (base quantity) for measurement and
percentage protection settings.
P605 Power
Nominal power of the primary side W1 (or transformer primary side W1); the absolute set
point is taken as reference quantity (base quantity) for measurement and percentage
protection settings. The absolute set point can refer to apparent power, active or reactive
power.
EXAMPLE: The setting Phase shift [P611] = 5 means a phase shift between the
primary and secondary voltage of the transformer by 5 x 30 = 150.
P614 Current
Nominal phase current of the secondary side W2 (or transformer secondary side W2);
the absolute set point is taken as reference quantity (base quantity) for measurement
and percentage protection settings.
P615 Power
Nominal power of the secondary side W2 (or transformer secondary side W2); the
absolute set point is taken as reference quantity (base quantity) for measurement and
percentage protection settings. The absolute set point can refer to apparent power,
active or reactive power.
EXAMPLE: The setting Phase shift [P621] = 5 means a phase shift between the
primary and secondary voltage of the transformer by 5 x 30 = 150.
P624 Current
Nominal phase current of the tertiary side W3 (or transformer tertiary side W3); the
absolute set point is taken as reference quantity (base quantity) for measurement and
percentage protection settings.
P625 Power
Nominal power of the tertiary side W3 (or transformer tertiary side W3); the absolute set
point is taken as reference quantity (base quantity) for measurement and percentage
protection settings. The absolute set point can refer to apparent power, active or reactive
power.
Frequency
P630 Frequency
Nominal frequency of the three-phase system; the absolute set point is taken as
reference quantity (base quantity) for measurement and percentage protection settings.
NOTE: For special applications (such as genset test beds or mobile, switchable rental
units) parameter setting of the nominal frequency of the three-phase system
can be changed by a command of the data protocol Profibus DP.
To change parameter settings the user must activate the parameter change
mode by sending once the instruction number 1000 (start of parameter change).
After that, one or more parameter settings can be changed by sending the
related instruction numbers 1002 to 1012 (see document SYMAP-
Compact_Appendix_Modbus-Profibus-IEC103) with appropriate data values.
To finish parameter setting process the user must send once the instruction
number 1001. Subsequently, the SYMAP-Compact(+) device will reboot.
Parameter description:
Potential transformer 1
Potential transformer 2
Potential transformer 3
Parameter description:
Current transformer CT1-P (connecting protection winding of the current transformer to CT1)
P660 Primary
Primary side nominal current of current transformer CT1-M/P
P661 Secondary
Secondary side nominal current of current transformer CT1-M/P
P668 Assignment
Assignment of the voltage level (transformer winding side: W1, W2 or W3) to CT1-M.
Beyond the protection winding, the measurement winding of the used current transformer can
be additionally connected to the SYMAP-Compact+ for measurement purposes.
The connecting terminals for the CT2 only receive the protection winding on the SYMAP-
Compact+.
Current transformer CT2-M/P (connecting protection winding of the current transformer to CT2)
P669 Primary
Primary side nominal current of current transformer CT2-M/P
P670 Secondary
Secondary side nominal current of current transformer CT2-M/P
P671 Direction L1
Setting the measuring direction for the phase current IL1 at the measurement inputs CT2-
M/P. With correct connection of the secondary side of the current transformer, setting
0 means for the SYMAP-Compact+ a reference angle of 0 for determination of
phase position of the current IL1. Setting 180 reverses the phase position of the current
by 180. In case of inversed secondary lines of the current transformer, this setting can
be used to correct measuring direction without need to modify wiring.
P672 Direction L2
Setting the measuring direction for the phase current IL2 at the measurement inputs CT2-
M/P. With correct connection of the secondary side of the current transformer, setting
0 means for the SYMAP-Compact+ a reference angle of 0 for determination of
phase position of the current IL2. Setting 180 reverses the phase position of the current
by 180. In case of inversed secondary lines of the current transformer, this setting can
be used to correct measuring direction without need to modify wiring.
P673 Direction L3
Setting the measuring direction for the phase current IL3 at the measurement inputs CT2-
M/P. With correct connection of the secondary side of the current transformer, setting
0 means for the SYMAP-Compact+ a reference angle of 0 for determination of
phase position of the current IL3. Setting 180 reverses the phase position of the current
by 180. In case of inversed secondary lines of the current transformer, this setting can
be used to correct measuring direction without need to modify wiring.
P674 Assignment
Assignment of the voltage level (transformer winding side: W1, W2 or W3) to CT1-M/P.
P681 Primary
Primary side nominal current of the ground current transformer CT-GND1
P682 Secondary
Secondary side nominal current of the ground current transformer CT-GND1
P682 Secondary
Setting the measuring direction for the ground current IG at the measurement input CT-
GND1. With correct connection of the secondary side of the current transformer, setting
0 means for the SYMAP-Compact(+) a reference angle of 0 for determination of
phase position of the current IE. Setting 180 reverses the phase position of the current
by 180. In case of inversed secondary lines of the current transformer, this setting can
be used to correct measuring direction without need to modify wiring.
P684 Assignment
Assignment of the voltage level (transformer winding side: W1, W2 or W3) to CT-GND1.
Parameters of menu Measuring are for coordinating the measuring channels to the
application; these include:
coordination of voltage and current measuring inputs for power measurement (Power),
assignment of power measuring for energy counters (Energy),
setting options for zero current compensation (star point grounding) and assignment of the
current measuring input for determination of the ground current for function ANSI 64REF-
Restricted ground fault protection (Differential),
setting options to adjust measuring ranges of voltage measurement inputs (PT inputs),
setting options to enable/disable DC voltage measurement via PT1, PT2 and/or PT3
(DC voltage),
coordination of sample function for frequency measurement (Sampler), and
setting of DC-filter for current measuring (Other).
CAUTION: SYMAP-Compact(+) devices are not applicable for 3-phase power systems
with anti-clockwise rotating field!
3.3.3.1 Power
Power
Parameter description:
Assignment of voltage and current values for combined U/I measuring values (Measuring)
POWER CT1
9410 PT reference
For power measurement, this parameter determines which of the potential transformers
(PT1, PT2 or PT3) cooperates with the current transformer CT1.
In dependence of the SYMAP-Compact(+) device variant, the following options are
available:
PT1: current measuring by CT1, voltage measuring by PT1
PT2: current measuring by CT1, voltage measuring by PT2
PT3: current measuring by CT1, voltage measuring by PT3
NOTE: All protective functions whose protective criteria depends on current and
voltage measurement values as well (e.g. ANSI 32, 67 etc.), could optionally
refer to the setting of parameter PT reference [P9410] or parameter
PT reference [P9413].
P9411 Direction
Internal adaption of metered energy flow; to define the signs of measurement values, the
following setting options are available:
0: When the 3-phase voltage measurement input (PT1, PT2 or PT3),
assigned by parameter PT reference [P9410], is connected equally to the
connection diagram of this manual and
The current measurement input CT1 is connected the way that measured
secondary current flow is from terminal X1.1:1 to terminal X1.1:2, from
POWER CT2
P9413 PT reference
For power measurement, this parameter determines which of the potential transformers
(PT1, PT2 or PT3) cooperates with the current transformer CT2.
In dependence of the SYMAP-Compact(+) device variant, the following options are
available:
PT1: current measuring by, voltage measuring by PT1
PT2: current measuring by, voltage measuring by PT2
PT3: current measuring by, voltage measuring by PT3
NOTE: All protective functions whose protective criteria depends on current and
voltage measurement values as well (e.g. ANSI 32, 67 etc.), could optionally
refer to the setting of parameter PT reference [P9410] or parameter
PT reference [P9413].
P9414 Direction
Internal adaption of metered energy flow; to define the signs of measurement values, the
following setting options are available:
0: When the 3-phase voltage measurement input (PT1, PT2 or PT3),
assigned, by parameter PT reference [P9413] is connected equally to the
connection diagram of this manual and
The current measurement input CT2 is connected the way that measured
secondary current flow is from terminal X1.1:7 to terminal X1.1:8, from
terminal X1.1:9 to terminal X1.1:10 and from terminal X1.1:11 to terminal
X1.1:12 and
parameters Direction [P677] to [P679] are set to 0,
then, active power P and reactive power Q will show positive signs (P > 0,
Q > 0) when current lags the voltage. In case of the same connection and
setting preconditions the current leads the voltage, active power P will show
positive sign (P > 0) and reactive power will show negative sign (Q < 0).
180: In case that the 3-phase voltage measurement input (PT1, PT2 or PT3),
assigned by parameter PT reference [P9413], is connected equally to the
connection diagram of this manual and
The current measurement input CT2 is connected the way that measured
secondary current flow is from terminal X1.1:7 to terminal X1.1:8, from
terminal X1.1:9 to terminal X1.1:10 and from terminal X1.1:11 to terminal
X1.1:12 and
parameters Direction [P677] to [P679] are set to 0,
then, active power P and reactive power Q will show negative signs (P < 0,
Q < 0) when current lags the voltage. In case of the same connection and
setting preconditions the current leads the voltage, active power P will show
negative sign (P < 0) and reactive power will show positive sign (Q > 0).
P9419 PT reference
For power measurement of the zero sequence system, this parameter determines which
of the potential transformers (PT1, PT2, PT3 or PT-GND1) cooperates with the current
transformer CT1.
In dependence of the SYMAP-Compact(+) device variant, the following options are
available:
PT-GND1: caculation of IG by CT1, measuring of UG by PT-GND1
PT1: caculation of IG by CT1, caculation of UG by PT1
PT2: caculation of IG by CT1, caculation of UG by PT2
PT3: caculation of IG by CT1, caculation of UG by PT3
NOTE: All protective functions whose protective criteria depends on current and
voltage measurement values of the zero sequence system as well (e.g. ANSI
67G etc.), could optionally refer to the setting of parameter
PT reference [P9419], PT reference [P9422] or parameter PT reference
[P9428].
P9420 Direction
Internal adaption of metered energy flow; to define the signs of measurement values of
the zero sequence system, the following setting options are available:
0: When the 1-phase or 3-phase voltage measurement input (PT-GND1,
PT1, PT2 or PT3), assigned by parameter PT reference [P9419], is
connected equally to the connection diagram of this manual and
the current measurement input CT1 is connected the way that measured
secondary current flow is from terminal X1.1:1 to terminal X1.1:2, from
terminal X1.1:3 to terminal X1.1:4 and from terminal X1.1:5 to terminal
X1.1:6 and
parameters Direction [P662] to [P667] are set to 0,
then, active ground power P0 and reactive ground power Q0 will show
positive signs (P0 > 0, Q0 > 0) when ground current IG lags the residual
voltage UG. In case of the same connection and setting preconditions the
ground current IG leads the residual voltage UG, active ground power P0 will
show positive sign (P0 > 0) and reactive ground power will show negative
sign (Q0 < 0).
180: In case that the 1-phase or 3-phase voltage measurement input (PT-GND1,
PT1, PT2 or PT3), assigned by parameter PT reference [P9419], is
connected equally to the connection diagram of this manual and
the current measurement input CT1 is connected the way that measured
secondary current flow is from terminal X1.1:1 to terminal X1.1:2, from
P9422 PT reference
For power measurement of the zero sequence system, this parameter determines which
of the potential transformers (PT1, PT2, PT3 or PT-GND1) cooperates with the current
transformer CT2.
In dependence of the SYMAP-Compact(+) device variant, the following options are
available:
PT-GND1: caculation of IG by CT2, measuring of UG by PT-GND1
PT1: caculation of IG by CT2, caculation of UG by PT1
PT2: caculation of IG by CT2, caculation of UG by PT2
PT3: caculation of IG by CT2, caculation of UG by PT3
NOTE: All protective functions whose protective criteria depends on current and
voltage measurement values of the zero sequence system as well (e.g. ANSI
67G etc.), could optionally refer to the setting of parameter
PT reference [P9419], PT reference [P9422] or parameter PT reference
[P9428].
P9423 Direction
Internal adaption of metered energy flow; to define the signs of measurement values of
the zero sequence system, the following setting options are available:
0: In case that the 1-phase or 3-phase voltage measurement input (PT-GND1,
PT1, PT2 or PT3), assigned by parameter PT reference [P9422], is
connected equally to the connection diagram of this manual and
the current measurement input CT2 is connected the way that measured
secondary current flow is from terminal X1.1:7 to terminal X1.1:8, from
terminal X1.1:9 to terminal X1.1:10 and from terminal X1.1:11 to terminal
X1.1:12 and
parameters Direction [P677] to [P679] are set to 0,
then, active ground power P0 and reactive ground power Q0 will show
positive signs (P0 > 0, Q0 > 0) when ground current IG lags the residual
voltage UG. In case of the same connection and setting preconditions the
ground current IG leads the residual voltage UG, active ground power P0 will
show positive sign (P0 > 0) and reactive ground power will show negative
sign (Q0 < 0).
180: In case that the 1-phase or 3-phase voltage measurement input (PT-GND1,
PT1, PT2 or PT3), assigned by parameter PT reference [P9422], is
connected equally to the connection diagram of this manual and
the current measurement input CT2 is connected the way that measured
secondary current flow is from terminal X1.1:7 to terminal X1.1:8, from
terminal X1.1:9 to terminal X1.1:10 and from terminal X1.1:11 to terminal
X1.1:12 and
9428 PT reference
For power measurement of the zero sequence system, this parameter determines which
of the potential transformers (PT1, PT2, PT3 or PT-GND1) cooperates with the ground
current transformer CT-GND1.
In dependence of the SYMAP-Compact(+) device variant, the following options are
available:
PT-GND1: measuring of IG by CT-GND1, measuring of UG by PT-GND1
PT1: measuring of IG by CT-GND1, caculation of UG by PT1
PT2: measuring of IG by CT-GND1, caculation of UG by PT2
PT3: measuring of IG by CT-GND1, caculation of UG by PT3
NOTE: All protective functions whose protective criteria depends oncurrent and
voltage measurement values of the zero sequence system as well (e.g. ANSI
67G etc.), could optionally refer to the setting of parameter
PT reference [P9419], PT reference [P9422] or parameter PT reference
[P9428].
P9429 Direction
Internal adaption of metered energy flow; to define the signs of measurement values of
the zero sequence system, the following setting options are available:
0: In case that the 1-phase or 3-phase voltage measurement input (PT-GND1,
PT1, PT2 or PT3), assigned by parameter PT reference [P9428], is
connected equally to the connection diagram of this manual and
the current measurement input CT-GND1 is connected the way that
measured secondary current flow is from terminal X1.1:7 to terminal X1.1:8,
(SYMAP-Compact) or from terminal X1.1:13 to terminal X1.1:14
(SYMAP-Compact+) and
parameter Direction [P683] is set to 0,
then, active ground power P0 and reactive ground power Q0 will show
positive signs (P0 > 0, Q0 > 0) when ground current IG lags the residual
voltage UG. In case of the same connection and setting preconditions the
ground current IG leads the residual voltage UG, active ground power P0 will
show positive sign (P0 > 0) and reactive ground power will show negative
sign (Q0 < 0).
180: In case that the 1-phase or 3-phase voltage measurement input (PT-GND1,
PT1, PT2 or PT3), assigned by parameter PT reference [P9428], is
connected equally to the connection diagram of this manual and
the current measurement input CT-GND1 is connected the way that
measured secondary current flow is from terminal X1.1:7 to terminal X1.1:8,
(SYMAP-Compact) or from terminal X1.1:13 to terminal X1.1:14
(SYMAP-Compact+) and
parameter Direction [P683] is set to 0,
then, active ground power P0 and reactive ground power Q0 will show
negative signs (P0 < 0, Q0 < 0) when ground current IG lags the residual
voltage UG. In case of the same connection and setting preconditions the
ground current leads the residual voltage UG, active ground power P0 will
show negative sign (P0 < 0) and reactive ground power Q0 will show
positive sign (Q0 > 0).
3.3.3.2 Energy
Energy
Parameter description:
The parameters Current [P604], Current [P614] and Current [P624] are located in
submenu: SYSTEM\Nominals\Reference values
P9451 Blocking
Energy counting function can be completely blocked by any active event. For blocking,
the number related to this blocking event has to be assigned to parameter [P9451].
Blocking is only effective as long as the blocking event is active. If the blocking event
becomes inactive, blocking is abandoned and energy counting is to be continued with
the counting value which was saved at the point of time of blocking.
If blocking of the energy counting function is not required, set this parameter to 0.
3.3.3.3 Differential
Differential
Parameter description:
Zero compensation
Ground differential
The following parameters refer to the protective function Restriced earth fault ANSI 64REF
P9439 CT-GNDxsource
Assignment of the current measurement input which measures the ground current
directly for protective function Restricted earth fault ANSI 63REF. At present, the
characteristic quantity (ground current) of restricted earth fault protection is to be
measured via ground current measurement input CT-GND1:
CT-GND1: measured ground current IG by CT-GND1
P9440 CTxsource
Assignment of the current measurement input which calculates the ground current for
protective function Restricted earth fault ANSI 63REF. Depending on the SYMAP-
Compact(+) device variant, that measurement input which calculates the ground current
from the 3-phase current measurement input of protective function Restricted earth fault
ANSI 64REF, can be assigned to a certain current measurement input (CT1 or CT2).
Parameter [P9440] determines the current measurement input which will provide
measurement values as characteristic quantity (ground current) to the restricted earth
fault protection:
of the transformer.
3.3.3.4 Impedance
Main Menu\Parameters\SYSTEM\Measuring
Impedance
Parameter description:
3.3.3.5 PT inputs
PT inputs
Parameter description:
PT input mode
Settings for measuring ranges of the potential transformers (Analog inputs)
Each of the voltage measurement inputs is equipped with two measuring ranges:
Lower range: 0 to 200V AC
Upper range: 0 to 1100V AC
Depending on the set values (parameters [P9400] to [P9402] of the voltage measuring inputs,
the different voltage measuring inputs of SYMAP-Compact(+) apply either the lower or the
upper measuring range.
3.3.3.6 DC voltage
DC voltage
Parameter description:
3.3.3.7 Sampler
Sampler
Parameter description:
Sampler
The Sampler sub-menu provides parameters of the module for sampling current and voltage
measurement values.
The sample rate for U/I measurement is 36 samples per cycle. In case that the frequency of the
measured voltage quantities will differ from the set value of parameter Nominal frequency
[P630], the time between two samples (sample time) has to be modified to the meet the rate of
36 samples per cycle.
Parameters [P9455] and [P9456] determine the range of the measured frequency which is valid
for effectiveness of sample time adaption.
Fn: calculation of the sample time reflects the set value of parameter
Nominal frequency [P630]
Auto: calculation of the sample time reflects the measured frequency value
of PT1. If there is no frequency measurement at PT1 (fPT1 = 0), then
calculation of the sample time reflects the measured frequency value
of PT2. If there is no frequency measurement at PT2 (fPT2 = 0), then
calculation of the sample time reflects the measured frequency value
of PT3. If there is no frequency measurement at PT3 (fPT3 = 0), then
calculation of the sample time reflects the set value of parameter
Nominal frequency [P630].
Floating average
Parameter description:
3.3.3.9 Other
Other
Parameter description:
P9435 DC regulator
Rapidity controller for DC elemination of analog current measurement values; generelly,
current measurement values are measured according to TRMS (true root means square)
principle. Such analog signals include harmonics as well as DC portion.
To eleminate the DC portion parameter DC regulator [P9435] can be used. The DC
regulator modifies the TRMS signal afflicted with DC portion, with an adjustable rapidity.
A low set value of parameter [P9435] means slow elemination; whereas a high set value
is for rapid elemination of DC portion:
For instance, a setting value of parameter DC regulator = 2048 LSB means an
elemination of the DC portion after one cycle of the measured current signal.
However, a setting value of parameter DC regulator = 1 LSB means an entire
elemination of the DC portion after 2048 cycles of the measured current signal.
Counter
Parameter description:
NOTE: When sending the parameter file to the device, the set values of parameters [P700]
and [P710] to [P713] will only be saved if you tick the box Overwrite counters of
configuration software SCPT!
P710 Wp+
Set value for the absolute counting values of the positive, active energy counter;
precisely at the time when the set value of parameter Wp+ [P710] is saved (download
of parameter file xxx.cpt; e.g. after exchange of the device), the positive, active energy
counter continues operating using the set counting value as new start value.
P711 Wp-
Set counting value for the negative, active energy counter; precisely at the time when
the set value of parameter Wp- [P711] is saved (download of parameter file xxx.cpt;
e.g. after exchange of the device), the negative, active energy counter continues
operating using the set counting value as new start value.
P712 Wq+
Set counting value for the positive, reactive energy counter; precisely at the time when
the set value of parameter Wq+ [P712] is saved (download of parameter file xxx.cpt;
e.g. after exchange of the device), the positive, reactive energy counter continues
operating using the set counting value as new start value.
P713 Wq-
Set counting value for the negative, reactive energy counter; precisely at the time when
the set value of parameter Wq- [P713] is saved (download of parameter file xxx.cpt;
e.g. after exchange of the device), the negative, reactive energy counter continues
operating using the set counting value as new start value.
Event description:
3.3.5 Filter (Filter functions for measurement, display and event recording)
Filter
Parameter description:
Dead Band
Dead band parameters [P800] to [P802] are applicable for device display and transmission via
communication protocols of measurement values only!
P800 Current
Minimum limit of current measurement display; as soon as a measured current value
falls below the set value of parameter Current [P800], the current value is displayed as
NULL.
NOTE: The minimum limit [P800] is to be set as a percentage of the nominal value of
the characteristic quantity (phase current). The nominal value of the
characteristic quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P624] are
located in submenu: SYSTEM\Nominals\Reference values.
P801 Voltage
Minimum limit of voltage measurement display; as soon as a measured voltage value
falls below the set value of parameter Voltage [P801], the voltage value is displayed as
NULL.
NOTE: The minimum limit [P801] is to be set as a percentage of the nominal value of
the characteristic quantity (phase-to-phase voltage). The nominal value of the
characteristic quantity is to be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2 or
Voltage (L-L) [P623], for tertiary side W3.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
P802 Power
Minimum limit of power measurement display; as soon as a measured power value falls
below the set value of parameter Power [P802], the power value is displayed as NULL.
NOTE: The minimum limit [P802] is to be set as a percentage of the nominal value of
the characteristic quantity (active power, reactive power or apparent power).
The nominal value of the characteristic quantity is to be set by parameter:
Power [P605], for primary side W1 or
Power [P615], for secondary side W2 or
Power [P625], for tertiary side W3.
The parameters Power [P605], Power [P615] and Power [P625] are
located in submenu: SYSTEM\Nominals\Reference values.
Frequency
If the frequency difference f is below the set value of parameter Max rate of
change [P806], the new measured frequency value is valid for the measuring unit of
SYMAP-Compact.
P881 - to
Blocking of event recording for selected events; together with parameter Filter event
recording from [P880] a range of consecutive events can be determined which are not
to be recordered by the event recorder. For blocking the event recording of a selectable
range of consecutive events, the number of the last selected event has to be assigned to
parameter [P881].
If blocking of event recording for a selected range of consecutive events is not required,
set this parameter to 0.
Each SYMAP-Compact(+) provides a standard interface RS422/485 using the Modbus RTU
data protocol. For additional communication options, please refer to the valid order code. As
well as the standard communication, the following parameter descriptions also take into account
all available communication options.
Port settings
Parameter description:
P900 Port
Standard interface of SYMAP-Compact(+); the physical interface provides following
setting options:
OFF: disabled,
RS485: enabled (working principle of physical interface is RS485) or
RS422: enabled (working principle of physical interface is RS422)
P901 Address
Slave address of standard interface; the setting range of slave addresses is between 0
and 255.
P902 Baudrate
Unit of the symbol rate for data transmission; the following setting options provide
different symbol rates (unit: [Bd]):
9600
19200
38400
57600
NOTE: Care should be taken that the symbol rate (Baud rate) is the same for both,
the sender and the receiver.
P903 Protocol
Options for data protocol of standard interface; the data protocol (Modbus RTU) of the
standard interface can be:
none: disabled, or
P904 Format
Format definition (byte frame) of date telegram for protocoll type MODBUS RTU; the
byte frame of the data telegram of SYMAP-Compact(+) can be adapted to the interface
configuration of the applied Modbus Master system. The byte frame is determined as
follows: Start bit = 1 (fix); No. of data bits, parity, No. of Stop bits.
8, None, 1: 1 start bit, 8 data bits, no parity, 1 stop bit
8, None, 2: 1 start bit, 8 data bits, no parity, 2 stop bits
8, Even, 1: 1 start bit, 8 data bits, even parity, 1 stop bit
8, Even, 2: 1 start bit, 8 data bits, even parity, 2 stop bits
8, Odd, 1: 1 start bit, 8 data bits, odd parity aritt, 1 stop bit
8, Odd, 2: 1 start bit, 8 data bits, odd parity, 2 stop bits
Serial port 2
Parameter description:
P905 Port
Standard interface of SYMAP-Compact(+); the physical IEC 60870-5-103 interface
provides following setting options:
OFF: disabled or
ON: enabled.
P906 Address
Slave address of standard interface; the setting range of slave addresses is between 0
and 255.
P907 Baudrate
Unit of the symbol rate for data transmission; the following setting options provide
different symbol rates (unit: [Bd]):
9600
19200
38400
57600
NOTE: Care should be taken that the symbol rate (Baud rate) is the same for both,
the sender and the receiver.
P908 Protocol
Options for data protocol of standard interface; the data protocol of interface serial port
2 is only:
IEC 870-5-103: data protocol IEC 60870-5-103 is enabled.
P915 Format
Format definition (byte frame) of date telegram for protocoll type IEC 60870-5-103; the
byte frame of the data telegram of SYMAP-Compact(+) can be adapted to the interface
configuration of the applied Modbus Master system. The byte frame is determined as
follows: Start bit = 1 (fix); No. of data bits, parity, No. of Stop bits.
8, None, 1: 1 start bit, 8 data bits, no parity, 1 stop bit
8, None, 2: 1 start bit, 8 data bits, no parity, 2 stop bits
8, Even, 1: 1 start bit, 8 data bits, even parity, 1 stop bit
8, Even, 2: 1 start bit, 8 data bits, even parity, 2 stop bits
8, Odd, 1: 1 start bit, 8 data bits, odd parity aritt, 1 stop bit
8, Odd, 2: 1 start bit, 8 data bits, odd parity, 2 stop bits
3.3.6.3 Profibus DP
Profibis
Parameter description:
P910 Port
Profibus interface of SYMAP-Compact(+); the physical Profibus interface provides
following setting options:
OFF: disabled or
ON: enabled
P911 Address
Slave address of Profibus interface; the setting range of slave addresses is between 1
and 123.
The Ethernet port (RJ45) at the housing side can simultaneously be used:
to connect the extension board system EBS, and/or
to connect a notebook/PC via LAN to configurate the SYMAP-Compact(+) device via
configuration software SCPT => service port.
For using the Ethernet port as service port there are the following parameters available to adjust
the IP address for the SYMAP-Compact(+) device:
Parameter description:
3.3.6.5 Ethernet
Ethernet
Parameter description:
Network Topology
Parameter description:
Double Star: Star topology with one additional (stand by) port. Ethernet
communication via port 1 and port 2 are active,
however, the device can receive and send Ethernet frames
via first connected port. If connection is broken down
(Link down), the device will try to establish connection via
the next connected port (Link up). It can be the same port
or the second port. If connection breaks down (Link down)
again, the device will try to establish connection via next
connected (Link up) port,
Ring with HSR: Ring topology - Ethernet communication port A and port B
are active; device can send and receive Ethernet frames
via both ports using protocol type IEC 62439-3 High-
availability Seamless Redundancy (HSR) protocol.
Double Star with PRP: Star topology; the device receives and sends Ethernet
frames via both ports (port A and port B) at the same time.
This is redundancy using the double Star topology with
IEC 62439-3 Parallel Redundancy Protocol (PRP) protocol.
NOTE: The above selection options are not valid for SYMAP-Compact(+) device
variants equipped with IEC 61850 single communication port!
3.3.6.7 SNTP
SNTP
Parameter description:
IEC 61850
Parameter description:
As soon as a link with the IEC 61850 client has established, the event [E0328] is
activated.
NOTE: For more informationen about IEC61850 communication, please refer to the
SYMAP-Compact_Appendix_IEC61850 document.
NOTE: It is recommended to format the memory area for IEC 61850 communication
before uploading any new data model CID file (data model depends on
firmware version of IEC 61850 communication). Please use User level access
to avoid intentional or accidental deletion!
IEC 60870-5-103
Parameter description:
NOTE: For more informationen about IEC60870-5-103 communication, please refer to the
SYMAP-Compact_Appendix_Modbus-Profibus-IEC103 document.
NOTE: At present CAN Bus 1 can only be used for SYMAP-Compact GC and +GC devices
variants. Here, CAN Bus 1 supports function Generator control of Power
management system PMS.
CAN bus 1
Parameter description:
P920 Port
CAN Bus 1 interface of SYMAP-Compact(+); the physical interface provides following
setting options:
OFF: disabled or
ON: enabled.
When parameter setting Port [P920] = ON and data transfer is performed correctly,
then event CAN OK [E920] is activated.
In case that:
CAN Bus 1 communication wiring is disrupted or short-circuited, or
there is no further SYMAP-Compact(+) device conntected to CAN Bus 1, or
the set baud rates of the SYMAP-Compact(+) devices are different,
P921 Baudrate
Unit of the symbol rate for data transmission; the following setting options provide
different symbol rates (unit: [kBd]):
15,6
25
50
100
125
250
500
1000
NOTE: Care should be taken that the symbol rate (Baud rate) is the same for both,
the sender and the receiver.
P922 Address
Slave address of CAN Bus 1 interface; the setting range of slave addresses is between
1 and 127.
CAUTION: All SYMAP-Compact(+) devices connected to the CAN Bus 1 must show
different address numbers, set by parameter [P922]. If there are devices
set with the same address number, then event Address error [E922] is
activated.
3.3.6.11 FTP
FTP
Parameter description:
P980 FTP
This parameter activates/deactivates the TCP connection to the File transfer protocol
(FTP) server, where:
OFF: disables or
ON: enables the TCP connection.
P986 Password
This parameter is for setting the password which will be used for login in on the FTP
server.
P991 Port
Number of the TCP port which is used for FTP connection; standard port No. is 21!
3.3.6.12 RSTP
RSTP
Parameter description:
P980 Priority
This parameter is for setting the default value for Rapid Spanning Tree Protocol (RSTP)
bridge priority.
3.3.6.13 IRIG-B
IRIG-B
Parameter description:
Graphic
Figure 3-36 System parameters Referencing and selection of displayed measurement values
Parameter description:
Button Configuration
Function keys at the front plate are to be configurable individually by the following parameters.
Parameter description of parameter Button 1 functionality [P60010] is presented as an
example.
Menu Configuration
Depending on the application, all Meters pages accessed by the selection page Meters may
be hidden individually.
Display configuration
Figure 3-38 Meters Voltage Display of phase voltages UL1, UL2, UL3
Display of Meters page Voltage; to display or to hide phase measuring values of the
voltages, please choose among the following setting options:
OFF: display of phase voltage measuring values is disabled,
ON: display of phase voltage measuring values is ensabled.
Bargraph configuration
Besides percentage currents, the colours of the bargraphs displayed on the Meters page
Current represents the applications current load. Depending on the actual level of currents
and the set limits for colour changes (see parameters [P60057] and [P60058]), the bargraphs
show green, orange or red.
Different colours apply to defined scopes. The thresholds of the defined scopes are given as
percentages of the phase current and ground current, referring to the nominal values of the
application.
NOTE: The scopes of colours are to be set as a percentage of the nominal value of the
characteristic quantities (phase current and ground current). The nominal values of
the characteristic quantities are to be set by parameter:
The parameters Current [P604], Current [P614], Current [P614], Ground current
[P607], Ground current [P617] and Ground current [P627] are located in submenu:
SYSTEM\Nominals\Reference values.
NOTE: In case that set values are the same for both, parameter [P60057] and
[P60058], colour changes only between green and red.
3.4 PROTECTION
CAUTION: SYMAP-Compact(+) devices are not applicable for 3-phase power systems
with anti-clockwise rotating field!
Protective functions have been implemented in the SYMAP-Compact product line according to
the American National Standard Institute (ANSI) standard. Refer to the following figure for
allocation of process variables (measured values) and protection functions.
CT-GND1
PT-GND1
CT1-M/P
PT2
PT1
74TC 86
5*
12*
TIG
YG
21** (1)
21B
21FL
24
25
27
27T
27Q (1)
32 (1)
32N/G (1)
37
40 (1)
47 46
48
49
50BF
50/51
50/51G
51LR
51MS
51/46VR
55 (1)
59
59AV 52
(2) 59N/G CTS
PTS 64REF
DCVM 66
67 (1)
67G (2)
78
78S (1)
79
81
81R 87GH
81RAV 87**
95i
CLD
SOTF
SGF (2)
CT-GND1
PT-GND1
CT1-M/P
CT2-M/P
PT3
PT2
PT1
74TC 86
5*
12*
TIG
YG
21** (1)
21B
21FL
24
25
27
27T
27Q (1)
32 (1)
32N/G (1)
37
40 (1)
46
47 48
49
50BF
50/51
50/51G
51LR
51/46VR
55 (1)
59
59AV 52
(2) 59N/G CTS
PTS 64REF
DCVM 66
67 (1)
67G (2)
78
78S (1)
79
81
81R 87GH
81RAV 87**
95i
CLD
SOTF
SGF (2)
The SYMAP-Compact(+) offers four, identical protection parameter sets which each represent
the complete protective functionality with regards to setting options. Depending on the grid or
system situation, adaptation of the protection setting to current requirements may be necessary.
This demand can be met by pre-configuring up to four protection parameter sets and activating
them according to specific events occurring.
NOTE: Parameter numbers (e.g. [P2345]) relating to parameter sets (SET1 SET4) exist only
once for all four parameter sets!
Each protection parameter set is provided a general parameter to which a specific event
required for changeover is assigned.
CAUTION: The currently active parameter set is displayed at the lower status line of the
device display:
The following is determined on behalf of priority for the active protection parameter set in order
to guarantee that in case of simultaneously active events assigned to parameters [P1000] to
[P1002] only one protection parameter set is active.
General
Parameter description:
parameter set 3 is abandoned and parameter set 1 is effective again. Event [E1002] is
then deactivated automatically and event [E1000] becomes active again.
If changeover to parameter set 3 is not required, set parameter [P1001] to 0.
Protection parameter set 3 is given the third lowest priority!
Event description:
Figure 3-45 Example: Activation of prot. parameter set 2 via SCPT sending command
7. After sending the command, selected parameter set x (example: parameter set 2)
becomes active, which will be indicated by the following window:
Figure 3-46 Example: Activation of prot. parameter set 2 via SCPT actual status
As soon as the command Send is sent, the corresponding event Prot. param. set x
activated manually [E100x] is activated.
CAUTION: Once a parameter set is activated via SCPT, it is not possible to change the
active parameter set via any activation event assigned to parameters [P1000],
[P1001] or [P1002]!
In order to change the active parameter set via activation events again, first the
user has to go Change Parameter SET in the SYMAP-Compact Parameter
Tool (SCPT), select none and send it to the device.
Figure 3-47 Recovery of parameter switch possibility via activation events Send = None
Introduction
The distance protection function (impedance protection) is an impedance- and current
direction-dependent type of time grading protection and is based on the protection criterion
impedance Z as quotient of the voltage U and the current I variables as measured at the relay
location. Continuous comparison between the limit impedance value as set in the relay and the
lower value (loop impedance) occurring in case of fault causes the decision for: operating/fault
event.
Due to its operating principle, the distance protection, depending on the fault distance, is a
protection which allows locating the fault point (distance) measured from the protection device
location by determining the fault type as well as the direction. Its tripping times are graded and
rising with increasing fault distance (grading plan).
SC A SC B SC C
Grid
t
tA3
tA2
tA1
Z
ZA1
ZA2
ZA3
ZB1
ZB2
ZB3
ZC1
with:
SC: protection device (distance protection) ZC2
ZA1: first impedance zone of protection device A
ZA2: second impedance zone of protection device A ZC3
ZA3: third impedance zone of protection device A
tA: tripping times of impedance zone for protection device A
The distance or impedance protection serves as short-circuit protection (with and without earth
fault) for lines and cables of all network to which specific requirements apply according to
selectivity or short fault finding times and availability of the supply network regarding switching
off the faulty sections on the one hand or on the other hand for which selective fault detection
based on current alone is not possible due to changing or generally high source impedances.
The multi-stage, distance-dependent time grading protection is used as main protection (1st
stage or zone) in medium-voltage network as well as in high voltage and extra-high voltage
network for:
Current transmission:
o Overhead lines in transmission networks and
Current distribution:
o For cable and lines in particular in meshed networks, as well as
o Parallel lines (double lines)
Beyond that, distance protection takes on the function of back-up protection of second order
(the second and the then following protection stages or zones) for:
adjacent line sections which are up- or downstream the main protection zone,
transformers, and
generators.
Operating principle
In electrical transmission and distribution networks, overhead lines and earth cables are used
for power transmission. Depending on the conductor material, geometry, disposition and cross-
section, electrical parameters are defined which are constant in a homogeneous line and are
referred to as characteristic impedance. Find the specific longitudinal components which are
relevant for the impedance settings
characteristic resistance (RL: line resistance) and
characteristic inductivity (XL: line reactance),
indicated in the data sheets by the line and cable manufacturer in [/km]. The absolute
impedance of a line or a cable thus depends on the actual line length; i.e. the longer the line the
higher its impedance.
The specific line angle L is calculated from both above components as follows:
L = arctan(XL / RL)
and is used to determine the so-called line straight within the complex R-X level of
representing the locus for impedance measurement. The line straight again is used as
reference for adapting the distance protection characteristic of the protection unit (SYMAP-
Compact(+): polygonal surface as impedance locus) by means of the line impedance to the
possible load and short-circuit impedances in the available three-phase network.
The length of the line straight (absolute value of the impedance vector in the locus) then
corresponds to the maximum length of protected line run whose end represents the peak of the
impedance vector. The line starts in the zero point of the R-X level and represents the location
of the distance protection unit and thus the measurement point of currents and voltages used
for determining the impedance Z.
Depending on their distance to the line sending end, all network nodes which are located within
the line run, can be arranged on the impedance straight of the line.
During normal operation, the line impedance and the impedances of the subsequent load add
up to such that the total impedance which is measured at the installation point, is higher than
the line itself. In case of fault on the line, however, the measured impedance reduces and
generally attains values below the impedance of the total line length; the fault impedance then is
within the defined impedance zone (tripping range) and the distance protection will detect fault.
With the station points on the impedance straight line and according to the protection concept, it
is possible to determine the individual protection stages (impedance zones) to which the time
graduation for output of the tripping command is linked. Generally, time graduation is as follows:
Close-range fault: fast tripping (fault in the reach of the 1st protection zone Z1, up to
approx. 85% of line length)
Fault in the overreach range: fast tripping (fault out of reach of the 1st protection zone Z1;
approx. 120% of line length) in connection with automatic reclosing (AR) applications or
signal comparison protection processes
Distant-range fault: delayed tripping (back-up protection: fault in the reach of the
subsequent protection zones Z3 or Z4); the farther a protection zone reaches from the relay
installation point towards the line, the longer the selected tripping time of each stage
Line straight
X
Station D
Z4
Station C
Z3
Station B Z2
Z1
L L L L L
Station A R
with:
Z1: first impedance zone of protection device in station A
Z2: overreach impedance zone of protection device in station A
Z3: first impedance zone of protection device in station B
Z4: first impedance zone of protection device in station C
L: line angle
Fault Types
In three-phase networks, the distance protection function provides protection of the network
upon occurrence of transverse faults. These are single, double or three-phase faults, with or
without earth. Protection in case of longitudinal faults (e.g. conductor continuity faults) is
effected by other protection functions.
With regard to the distance the fault currents cover from relay to fault point and back,
combinatorial logic of external phases and earth lead to the following different six fault loops:
Phase-to-earth loops: L1 Earth; L2 Earth; L3 Earth, and
Phase-to-phase loops: L1 L2; L2 L3; L3 L1
Digital distance protection units make available a separate measuring system for each fault loop
so as to guarantee determination of fault type as well as phase-selective fault detection.
Direction decision
In order to locate the fault unambiguously, the protection device has to feature power flow
direction detection which defines decision for forward or backward direction in case of fault.
Generally, direction of the protection device operation can be determined by the following
definition:
NOTE: Forward direction: protection device measurement from network node towards the
line.
Backward direction: protection device measurement directed towards the line
behind the node.
Station D
F F
SC 7 SC 8
R R
R R R R R R
Grid
Fault
location
Station E
F
SC 9
with:
SC: protection device
F: forward direction
R: reverse direction
Figure 3-51 Definition of forward and backward direction
Example: Assuming that forestanding figure shows the fault location at 45% of the line section
AB and each of the SC protection devices activate two protection stages
(impedance stages) in forward direction (stage 1: setting to 85%; stage 2: setting to
120%) only and one stage in backward direction (setting to 85%), the distance
protection relays will pick-up the stations as follows:
Impedance calculation
Distance protection relay estimates line positive sequence impedance from the relay to the fault
in order to determinate whether the fault is within the protection zone or outside. The apparent
impedance calculation is based on dynamic phasor method. Dynamic phasor method assumes
that phasors are changeable over time. For an RL series circuit/loop equation is as follows:
X I
U RI
0 t
where :
U U (t ), I I (t ), 0 2 f 0
f 0 50 Hz / 60 Hz
X ReI
ReU R ReI
0 t
X ImI
ImU R ImI
0 t
Impedance calculation is based on the two equations above. Distance protection algorithm
processes current and voltage samples from the A/D converter. For each of the six supervised
fault loops, sampled values of voltage (u), current (i), and current differential (i) are fed to the
Fourier filter. The filter provides two orthogonal values for each input, real component and
imaginary component of complex phasor.
o U = Uxy
o I = ILx ILy
o I = ILx ILy
Fault resistance seen by the relay for single side fed phase-earth fault
L p L (1-p)
L3
L
L2
GRID
IL1
L1
z1 = r1 + j x1[/km] Rf
z0 = r0 + j x0[/km]
UL1
NOTE: Please note that relay sees fault resistant scaled by factor 1/(1 + RE/R1). This is
consequence of selected impedance calculation method method based on dynamic
phasors.
- 224/839 -
Figure 3-53
(Zone1 Pickup Ph-E) Internal signal
Internal signal T
1
(T-single phase (ph-e) delay") [E2565]
(ANSI21 Pickup loop L3-E) [E2549] ( Pickup L1-E) Internal signal T Internal signal
(ANSI21 Pickup loop L1-L2) [E2550] Internal signal 1
(ANSI21 Pickup loop L2-L3) [E2551]
(ANSI21 Pickup loop L3-L1) [E2552]
( Pickup L2-E) (T-multi phase delay")
Internal signal
[P3777]
( Pickup L3-E)
Z< D Internal signal
Loop selection
I> E
U/I
U/I/phi & M ( Pickup L1-L2)
U Internal signal
(Pickup program")
X
Zone definition & ( Pickup L2-L3)
directional element Internal signal
Measurement
(Pickup L3-L1)
Internal signal
Z
[E2566]
[E2562] & (ANSI21-1 Trip L1)
1 (ANSI21-1 Pickup L1)
(Zone1: Z L1-E<) Internal signal
(Zone1: Z L2-E<) Internal signal
(Zone1: Z L3-E<) Internal signal
(Zone1: Z L1-L2<) Internal signal
(Zone1: Z L2-L3<) Internal signal [E2567]
(Zone1: Z L3-L1<) Internal signal &
[E2563] (ANSI21-1 Trip L2)
SYMAP-Compact_Manual_v18.0_GB.docx
1 (ANSI21-1 Pickup L2)
[E2568]
[E2564] & (ANSI21-1 Trip L3)
1 (ANSI21-1 Pickup L3)
ANSI 21 Trip logic diagram: e.g. pickup and trip via impedance zone 1
[E2561]
1 (ANSI21-1 Pickup)
User Manual
SYMAP-Compact
User Manual
General
Figure 3-54 ANSI 21 Distance protection\General set parameters [P] and events [E]
Parameter description:
The following parameter descriptions refer to all general protection parameters of one
parameter set in General submenu of distance protection function ANSI 21.
NOTE: Each of the four parameter sets always provides the same group of general
protection parameters which apply for both, parameter group A and group B.
Hence, the parameter descriptions of the general protection parameters of SET 1
represented below are described in detail in the following examples.
Functional scope
is only effective, however, as long as the blocking event is active. As soon as blocking is
active, event ANSI21 blocked module [E2538] is activated. If the blocking event turns
inactive, blocking is abandoned and protective function is effective again. Then, event
[E2538] is deactivated automatically.
If blocking of the distance protection is not required, set this parameter to 0.
Miscellaneous parameters
NOTE: The total trip delay time (time between physical fault occurance and activation
of the trip command) takes into account:
the intrinsic delay time (app. 35ms),
the pickup delay time, and
the trip delay time according to the zone setting.
General parameters
Polarizing voltage
Positive sequence voltage U1 is used as polarizing voltage Upol. When positive sequence
voltage falls below its minimal operating value set by parameter Recorder start voltage
[P3758] memorized positive voltage U1_M from voltage recorder is used to ensure directional
sensitivity for close-in three phase faults. When both, measured positive sequence voltage U1
and memorized positive sequence voltage U1_M are available, polarization voltage is calculated
as follows:
NOTE: If either U1 or U1_M is unavailable, then the missing quantity is dismissed from equation
above to calculate polarization voltage Upol.
If both, U1 and U1_M are unavailable, then function ANSI 21 Distance protection is
blocked!
Direction determination
Direction determination is based on argument of apparent impedance calculated using
polarizing voltage and loop current. Polarizing quantities are shown in table below.
Forward characteristic is determined by:
U pol
Direction angle 1 < arg < Direction angle 2
I loop
U pol
Direction angle 1 180 < arg < Direction angle 2 180
I pol
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
General
General
Parameter description:
The following parameter descriptions refer to all general protection parameters of one
parameter set in General submenu of distance protection function ANSI 21.
NOTE: Each of the four parameter sets within parameter group A and B always provides the
same group of general protection parameters. Hence, the parameter descriptions of
the general protection parameters of Group A\SET 1\General represented below
are described in detail as examples.
Power system
Direction straight 2
Forward direction
Direction straight 1
Backward direction
NOTE: The ranges occurring between forward and backward direction are not defined as far
as fault detection is concerned and are not included.
Together with the related setting of the lower direction straight (parameter [P3775]) the
impedance zone range stretches (valid for all 5 zones).
Figure 3-58 ANSI 21 Distance protection\Group A\Pickup\ - parameters [P] and events [E]
Pickup
Parameter description:
The following parameter descriptions refer to all pickup protection parameters of one parameter
set in Pickup submenu of distance protection function ANSI 21.
NOTE: Each of the four parameter sets within parameter group A and B always provides the
same group of pickup protection parameters. Hence, the parameter descriptions of
the pickup protection parameters of Group A\SET 1\Pickup represented below are
described in detail as examples.
Pickup program
Different network conditions lead to different behaviour of process parameters such as current
and voltage and this requires adaptation of the pick-up processes to the fault detection. The
different pick-up modes generally include the following criteria:
current,
voltage,
phase angle between current and voltage and
impedance
Depending on the network situation, cases may occur in which the impedance behaviour
significantly distinguishes from that of the overcurrent criterion and the fault currents occurring
then do not attain the set short-circuit current values for overcurrent pick-up. This fact requires
alternative pick-up criteria which determine the fault situation unambiguously.
The SYMAP-Compact(+) provides the following four different pick-up modes:
overcurrent pick-up (I>pick-up),
angle-independent under-impedance pick-up (U/I pick-up),
angle-dependent under-impedance pick-up (U/I/phi pick-up) and
impedance pick-up Z<
For each of the above pick-up types, 5 impedance zones Z1, Z2, Z3, Z4 and Z5 are available
for each fault loop.
Generally, pick-up is effected only after all conditions for the selected pick-up mode have been
met; these are:
the pick-up value set for phase currents is exceeded in at least one phase (threshold I>)
and simultaneously, the pick-up value set for measurement voltages (phase-to-phase
voltages or phase-to-earth voltages) is fallen below in at least one phase or
pick-up value set for the phase currents is exceeded in at least one phase (threshold I>>) or
pick-up by the module for earth fault detection
In contrast to the impedance pick-up Z<, impedance calculation for the pick-up modes I>, U/I
and U/I/phi is effected after pick-up. It is only then that the related fault loop is selected and the
calculated impedance value is compared to the polygons of the impedance zones. Depending
on the polygon into which the impedance vector then falls, the timer for tripping delay will start.
The overcurrent pick-up monitors the phase currents for exceeding the set pick-up
value I>.
Condition for detecting earth faults: earth faults have to cause pick-up in the faulty
phase => the earth short-circuit currents have to be sufficiently high => this is possible
only in solidly earthed networks.
U
PICKUP
I
I>
PICKUP
Imin
5% Inom
PICKUP
5% Inom dI
For I> pickup, all measuring quantities (I, Imin, dI) must fall into corresponding pickup
regions presented in figure above. In addition, earth fault detection determinates
whether phase-to-earth or phase-to-phase loops will be released. Measuring quantities
are shown in table below.
Table 3-5 Measuring quantity for I> pickup
Measuring Loop
quantity L3-L1 L2-L3 L1-L2 L3-E L2-E L1-E
I IL1 IL3 IL2 IL3 IL2 IL1
Imin IL3 IL2 IL1 =1 =1 =1
dI IL3 IL1 IL2 IL3 IL1 IL2 =1 =1 =1
EF EF == 0 EF == 0 EF == 0 EF == 1 EF == 1 EF == 1
U< (I>>)
U< (I>)
PICKUP
I
I> I>>
PICKUP
Imin
I>
PICKUP
dI
I>
Measuring Loop
quantity L3-L1 L2-L3 L1-L2 L3-E L2-E L1-E
U U31 U23 U12 UL3 UL2 UL1
I IL1 IL3 IL2 IL3 IL2 IL1
Imin IL3 IL2 IL1 =1 =1 =1
dI IL3 IL1 IL2 IL3 IL1 IL2 =1 =1 =1
EF EF == 0 EF == 0 EF == 0 EF == 1 EF == 1 EF == 1
In order to differentiate in such cases the fault case from the load case and apart from
the current and voltage variables, the related phase angle is also measured.
To do so, the under-impedance pick-up is additionally equipped with an angle-
dependent region linked to the criterion of the phase angle between current and
voltage of the faulty phase (overcurrent pick-up depending on the undervoltage pick-up
and evaluation of the angle between current and voltage).
Angle-dependent underimpedance pickup U/I/phi basically consist of angle-
independent U/I characteristic and separate angle-dependent U/I characteristic,
working in parallel.
In case of fault the phase angle is significantly larger than in the load case such that by
adding the fault criterion phase angle the pick-up range can be made more sensitive
if compared to the angle-independent underimpedance pick-up. A minimum and a
maximum phase angle define the pick-up range.
If measurement proves angles which are smaller than the minimum phase angle
angle min, load range can be supposed, only angle independent UI pickup
characteristic, left side on figure below, is active. For angles in range between angle
min and angle max, angle dependent U/I pickup characteristic is active also.
Angles which are larger than the maximum set phase angle angle max may indicate
a fault in backward direction or equally a load range with a power flow in backward
direction; e.g. in case of a line with two-side supply, consequently only the angle
independent U/I pickup is possible.
The voltage- and angle-dependent under-impedance pick-up applies for the range in
which the current exceeds the current pick-up value I> to up to attaining the short-
circuit pick-up I>>. Should the current exceed I>>, the distance protection function
proceeds to pick-up disregarding the voltage level since it is a high-current fault
already.
U U
U< (Iphi>)
U< (I>>)
PICKUP PICKUP
I I
I> I>> I> Iphi>
OR
U U
PICKUP PICKUP
Imin Imin
I> I>
U U
PICKUP PICKUP
dI dI
I> I>
PICKUP
Angle max
Angle min
ref
PICKUP
quantities (U, I, Imin, dI, ) must fall into pickup region presented in figure above (right
side: angle dependent pickup).
In addition, earth fault detection determinates whether phase-to-earth or phase-to-
phase loops will be released. Measuring quantities are shown in table below.
Measuring Loop
quantity L3-L1 L2-L3 L1-L2 L3-E L2-E L1-E
U U31 U23 U12 UL3 UL2 UL1
I IL1 IL3 IL2 IL3 IL2 IL1
Imin IL3 IL2 IL1 =1 =1 =1
dI IL3 IL1 IL2 IL3 IL1 IL2 =1 =1 =1
EF EF == 0 EF == 0 EF == 0 EF == 1 EF == 1 EF == 1
OR
Measuring Loop
quantity L3-L1 L2-L3 L1-L2 L3-E L2-E L1-E
U U31 U23 U12 UL3 UL2 UL1
I IL1 IL3 IL2 IL3 IL2 IL1
Imin IL3 IL2 IL1 =1 =1 =1
dI IL3 IL1 IL2 IL3 IL1 IL2 =1 =1 =1
angle(UL3) angle(UL2) angle(UL1)
angle(U31) angle(U23) angle(U12)
angle(IL3 IL1) angle(IL2 IL3) angle(IL1 IL2)
angle(IL3) angle(IL2) angle(IL1)
EF EF == 0 EF == 0 EF == 0 EF == 1 EF == 1 EF == 1
X
Line straight
X[Z<]
Load max PP
Direction straight 2 R1 Load range PE
Load max PE
L L L
R2 R
R[Z<] PE
R[Z<] PP
Direction straight 1
RLoad min PP
RLoad min PE
PICKUP
I
I>
PICKUP
Imin
I>
PICKUP
I> dI
Z
PICKUP
Measuring Loop
quantity L3-L1 L2-L3 L1-L2 L3-E L2-E L1-E
I IL1 IL3 IL2 IL3 IL2 IL1
Imin IL3 IL2 IL1 =1 =1 =1
dI IL3 IL1 IL2 IL3 IL1 IL2 =1 =1 =1
Z Z31_2p Z23_2p Z12_2p Z3E_1p Z2E_1p Z1E_1p
EF EF == 0 EF == 0 EF == 0 EF == 1 EF == 1 EF == 1
Polarizing quantities for the R and X calculation according to measuring loops are:
Phase-to-earth loops: ZxE_1p; x = 1, 2 or 3
o U = ULx
o I = ILx (1 + RE/R1)
o I = ILx (1 + XE/X1)
Phase-to-phase loops: Zxy_2p; xy = 12, 23 or 31
o U = Uxy
o I = -2 ILy
o I = -2 ILy
[I>]
P3778 I>
Limit value of the overcurrent pick-up mode, this parameter is active only when the I>
mode setting has been selected via parameter Pickup program [P3777]
[U/I]
P3779 I>
First overcurrent pick-up value of under-impedance pick-up; this parameter is active only
when the U/I pickup mode setting has been selected for the parameter [P3777]
P3780 I>>
Second overcurrent pick-up value of under-impedance pick-up; this parameter is active
only when the U/Ipickup mode setting has been selected for the parameter [P3777]
[U/I/phi]
P3785 I>
First overcurrent pick-up value of under-impedance pick-up; this parameter is active only
when the U/I/phi pickup mode setting has been selected for the parameter [P3777]
P3786 I>>
Second overcurrent pick-up value of under-impedance pick-up; this parameter is active
only when the U/I/phi pickup mode setting has been selected for the parameter [P3777]
P3787 I_phi>
Second overcurrent pick-up value of under-impedance pick-up for angle dependent
region; this parameter is active only when the U/I/phi pickup mode setting has been
selected for the parameter [P3777]
[Z<]
P3796 I>
Minimum current for pickup-program Z<. This parameter is active only when the Z<
mode setting has been selected for the parameter [P3777]
(section on the R axis) for determination of the polygonal of the distance protection
impedance zone Z<. This parameter allows including fault resistance in addition to the
line resistance. This parameter is active only when Z< pickup mode setting has been
selected for the parameter [P3777]
None
I0
I0 AND U0
I0 OR U0
U0
(Earth fault recognition)
[P3802]
Ground current
3I0 3I0> [E2545]
stabilisation
& (ANSI21 earth fault pickup)
(3I0> Limit)
[P3806]
1
3U0 3U0>
(3U0> Limit)
In systems where the zero sequence current is measured as a sum of three phase currents, an
artificial ground current signal is measured when one or more of the phase current transformers
are driven into saturation. Saturation of a current transformer means that some part of the
primary current is lost in transmission and does not appear on the secondary side. So the
balance of currents is corrupted on the secondary side even if there is no zero sequence current
on the primary side.
Current transformer saturation is possible when short circuits take place in the main circuit. In
such cases, it is helpful to restrain ground current detection in order to maintain selectivity. The
ground current stabilization can be used for all ground current detecion that are based on the
three phase currents (either calculated inside SYMAP-Compact(+) or measured as the sum of
the current transformer secondarys in parallel connection).
Ground current stabilization is not recommended when a dedicated ground current transformer
is present that measures the zero sequence current with one magnetic core that embraces all
three phase conductors. In this case, the single phase current is of low effect for the
measurement.
NOTE: Some ground current transformers with very large core-windows and small iron cross-
section tend to a phase current depending error when the conductors are not placed in
the center of gravity. In such cases, a carefully adjusted ground current stabilization
might help too.
with:
I0 : measured zero sequence current.
I0,stab : stabilized (reduced) zero sequence current for further calculations.
IPHmax : highest RMS value of the three phase currents.
[P3804] = 0
[P3804] = 0.3
[P3804] = 0.5
[P3804] = 0.8
[P3804] = 1
Imax/In [%]
P3806 3U0>
3U0 limit for residual voltage pickup; the limit is set as percentage of the set value for the
nominal ground voltage of the referenced winding side W1, W2 or W3 (see parameter
Ground voltage [P606], [P616] or [P626]).
Zone definition
Figure 3-67 ANSI 21 Distance protection\Group A\ Zone definition\ - parameters [P] and events
[E]
Zone definition
Parameter description:
The following parameter descriptions refer to all zone definition parameters of one parameter
set in Zone definition submenu of distance protection function ANSI 21.
NOTE: Each of the four parameter sets within parameter group A and B always provides the
same group of zone definition parameters. Hence, the parameter descriptions of the
zone definition parameters of Group A\SET 1\Impedance zone Z1 represented
below are described in detail as examples.
Impedance zone Z1
P3812 Zone
This parameter enables/disables impedance zone Z1:
OFF: disables or
ON: enables the protective zone.
When impedance zone Z1 is enabled by parameter [P3810], then event ANSI21-1 zone
active [E2553] is activated.
Blocking of impedance zone Z1; it is possible to block the pick-up zone Z1 by any active
event after assigning the related event number to parameter [P3813]. Blocking is active
only for the time the blocking event is active. As soon as this event becomes inactive,
blocking is deactivated and pick-up zone Z1 is activated again.
If blocking of pick-up zone Z1 is not required, set the parameter to 0.
When impedance zone Z1 is blocked, then event ANSI21-1 blocked zone [E2554] is
activated.
Reduction angle for inclining the polygon in direction of the R axis for impedance zone
Z1; double-fed high resistive faults could cause overreaching of the distance protection.
Overreaching is not acceptable for distance protection zone Z1, which is generally
applied as underreaching zone and must not overreach in any possible cases. To
prevent zone Z1 to overreach, zone reduction defined by inclination angle can be used,
as shown in figure below.
a) Reduction angle = 0 b) Reduction angle = 15
L L
For group A and impedance zone Z1, symbols in figure above correspond to the
following parameters:
L: parameter Line angle [P3763]
: parameter Zone reduction angle [P3819]
In case of a protection trip function ANSI 21FL Fault locator is used for calculating the
distance between the fault location and the location of the corresponding protective device.
Calculation is automatically initiated for protective function:
ANSI 21.
Within the following protection functions:
ANSI 50/51,
ANSI 50G/51G,
ANSI 67 and
ANSI 67G
each protection step provides a separate paramater Start fault locator [Pxxxx] to start
calculation of fault distance.
Immediately prior to the protection trip all relevant current and voltage values are saved. At the
moment of protection trip, calculation of the fault location starts and event ANSI21FL busy
[E2387] is activated. When calculation is finished, event [E2387] is deactivated. The fault
location will be represented in the fault recorder subsequently to the evaluation of the
measuring values:
Fault loop: indication of the faulty phase-to phase or phase-to-earth loop
Fault type: indication of faulty phase
Resistance: calculated, absolute value of cable/line resistance referring to fault
distance
Reactance: calculated, absolute value of cable/line reactance referring to fault
distance
Distance: calculated, absolute value of fault distance
Distance [%]: calculated, relative value of fault distance referring to the total length of
the protectd cable/line
NOTE: Additionally to the tripping overcurrent protective function, function ANSI 21FL will
generate a fault recording which is accessable via SYMAP-Compact(+) display or
via SCPT application software. The xxx.sfr fault recording file can be read-out and
saved via SCPT.
ANSI 21FL
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides only one protection STEP and, as
consequence, only one group of parameters. SET PARAMETERS are therefore equal
to STEP parameters. The protection parameters of SET 1 represented below are
described in detail in the following examples.
P3465 Function
This parameter activates/deactivates the fault locator function where the setting:
OFF: deactivates the fault locator function or
ON: activates the fault locator function.
When fault locator function ANSI 21FL is enabled by parameter [P3465], then event
ANSI21FL active [E2385] is activated.
P3466 Blocking
Fault locator function can be completely blocked by any active event. For blocking, the
number related to this blocking event has to be assigned to parameter [P3466]. Blocking
is only effective as long as the blocking event is active. As soon as blocking is active,
event ANSI21FL blocked [E2386] is activated. If the blocking event becomes inactive,
blocking is abandoned and fault locator function is effective again. Event [E2386] is then
deactivated automatically.
If blocking of the fault locator function is not required, set this parameter to 0.
and:
L' = L/l
with: inductance L [H] and unit length l [km or miles]
=> characteristic quantity Reactance per km/miles: X' = X/l [ per km] or [ per miles]
for a defined conductor length of a single cable lead or line. The characteristic quantity is
indicated of e.g. 1 km/mile (see data sheet of the applied conductor).
jX
ZE
Zcable/line Zcable/line
ILx
ZF,meas.
RF = 0
ULx-E
ZE
R
Figure 3-72 ANSI 21FL Correction of earth fault impedance
It is: ZE = Zcable/line*kE
=> ZF,meas = Zcable/line + Zcable/line*kE
= Zcable/line * (1 + kE)
=> Zcable/line = ZF,meas / (1 + kE) = Rcable/line + jXcable/line
P3471 kE-amplitude
Amplitude correction factor for impedance of phase-to-ground loop; the setting of the
absolute value kE-amplitude [P3471] of the complex correction factor kE is as follows:
kE-amplitude [P3470] = |kE|
= [(X0,cable/line X1,cable/line)2 + (R0,cable/line R1,cable/line)2] / [3 * (R12,cable/line + X12,cable/line)]
with:
R0,cable/line: specific zero sequence resistance of the cable/line (see data sheet of cable/line)
R1,cable/line: specific positive sequence resistance of the cable/line (see data sheet of cable/line)
X0,cable/line: specific zero sequence resistance of the cable/line (see data sheet of cable/line)
X1,cable/line: specific positive sequence resistance of the cable/line (see data sheet of cable/line)
P3472 kE-angle
Angle correction factor for impedance of phase-to-ground loop; the setting of the angle
kE-angle [P3472] of the complex correction factor kE is as follows:
kE-angle [P3471] = kE
= arc tan [(X0,cable/line X1,cable/line)/(R0,cable/line R1,cable/line)] arc tan [X1,cable/line/ R1,cable/line]
NOTE: When using a 2-pole isolated voltage transformer for measuring phase-to-phase
voltage U12, the secondary side of the voltage transformer has to be connected to
terminals designated as UL1 and UL2 of the SYMAP-Compact(+) voltage
measurement inputs PT1, PT2 or PT3.
L1
L2
L3
-X1.3
SYMAP-Compact+
A N a n
17 UL1
U31 U12
W1 19 UL2
U23 PT1
21 UL3
GCB
-X1.3
A N a n
18 UL1
U31 U12
20 UL2 PT2
U23
22 UL3
W2
G
3~
Figure 3-74 ANSI 25 U12 voltage measurement via 1-pole isolated voltage transformers
L1
L2
L3
-X1.3
SYMAP-Compact+
A a
17 UL1
U12
W1 19 UL2
B b PT1
21 UL3
GCB
-X1.3
A a
18 UL1
U12
20 UL2 PT2
B b
22 UL3
W2
G
3~
Figure 3-75 ANSI 25 U12 measuremnt via 2-pole isolated voltage transformers
The parameters of the sub-functions relate to the following three submenus of one
synchronizing unit:
Submenu General: parameters, valid for all sub-functions, of one synchronizing
unit
Submenu Synchrocheck: parameters of synchronizing check and
Submenu Voltage check: parameters to determine the voltage and frequency operating
range
Figure 3-76 Synchronizing unit 1 [Synch. unit 1 (PT1-PT2)] Parameter menu of sub-functions.
General
Synchrocheck
Voltage check
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters for all three synchronizing units (Sync. unit 1 to Sync. unit 3).
Parameter descriptions of the SET PARAMETERS and the parameters of the first
synchronizing unit (Sync. unit 1) represented below, are described below in detail as
examples.
CAUTION: SYMAP-Compact(+) device variants which were built according to ordering option
G59:
do not provide frequency measurement via voltage measurement input PT3!
do provide phase-seggregated frequency measurement (zero crossings of
phase voltages) only at voltage measurement input PT2!
do provide frequency measurement at PT1 based on crossings of phase-to-
neutral voltages UL1 and UL2!
P2306 Blocking
Synchronizing unit 1 (Sync. unit 1) of function ANSI25 can be blocked by any active
event. For blocking, the number related to this blocking event has to be assigned to
parameter [P2306]. Blocking is only effective, however, as long as the blocking event is
active. As soon as blocking is active, event ANSI25-1 Blocked [E1856] is activated. If
the blocking event becomes inactive, blocking is abandoned and synchronizing unit 1 is
effective again. Then, event [E1856] is deactivated automatically.
If blocking of synchronizing unit 1 is not required, set this parameter to 0.
NOTE: When frequency of the three phase power system which is to be synchronized
is lower than frequency of the reference system, then angle indicator (red
triangle) in the graphical synchronizer page rotates anti-clockwise.
Subsequently, events for frequency decrease are activated.
When frequency of the three phase power system which is to be synchronized
is higher than frequency of the reference system, then angle indicator (red
triangle) in the graphical synchronizer page rotates clockwise. Subsequently,
events for frequency increase are activated.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
As soon as the rotating field supervision detects an incorrect phase sequence in either of
the two three phase power systems,
the event ANSI25-1 Negative phase seq. PT1 [E1857] and/or event ANSI25-1
Negative phase seq. PT2 [E1858] is activated and
functions Synchrocheck and Voltage check are automatically blocked!
CAUTION: Function Rotating field supervision is not applicable in case that phase-to-
phase voltage U12 is measured at PT1 and PT2 by a 2-pole isolated
voltage transformer each!
The symbol always shows the current state of the assigned switching element SE x.
Figure 3-87 Assignment of the switching element to the graphical synchronizer page
Figure 3-88 Synchronizer page: Sync. unit 1 lables of voltage and frequency
indicators
As reference system for synchronizing check (Synchrocheck), it is the three phase power
system, which is assigned to parameter Voltage reference [P2307].
CAUTION: SYMAP-Compact(+) device variants which were built according to ordering option
G59:
do not provide frequency measurement via voltage measurement input PT3!
do provide phase-seggregated frequency measurement (zero crossings of
phase voltages) only at voltage measurement input PT2!
do provide frequency measurement at PT1 based on crossings of phase-to-
neutral voltages UL1 and UL2!
P2315 Function
This parameter enables/disables the effectiveness of synchronizing unit 1 (Sync. unit 1)
for synchronizing check (Synchrocheck: U, f, U, f, ) where:
OFF: disables or
ON: enables the effectiveness of synchronizing unit 1.
P2316 Blocking
Function Synchrocheck (U, f, U, f, ) of synchronizing unit 1 (Sync. unit 1) can be
blocked by any active event. For blocking, the number related to this blocking event has
to be assigned to parameter [P2316]. Blocking is only effective, however, as long as the
blocking event is active. As soon as blocking is active, event ANSI25-1 SC: Blocked
[E1865] is activated. If the blocking event becomes inactive, blocking is abandoned and
synchronizing check is effective again. Then, event [E1865] is deactivated automatically.
If blocking of synchronizing check of synchronizing unit 1 is not required, set this
parameter to 0.
Im
Parameter: Max. voltage [P2317]
U12 PT1
U12 PT2
Re
Once all phase-to-phase voltages and frequencies of PT1 and/or PT2 are within the operating
range set by parameters:
Max. voltage [P2317] and Min. voltage [P2318], and
Max. frequency [P2319] and Min frequency [P2320],
the event:
ANSI25-1 SC: PT1 in range [E1870] and/or the event
ANSI25-1 SC: PT2 in range [E1875]
is activated, and the synchronizing check procedure (dU, df, dPHI) will be conducted.
Ueff
[P2317]
Max. voltage
Umax
U12 PT2
Un
U12 PT1
[P2318]
Min. voltage
Umin
t
f
[P2319]
Max. frequency
fmax
f12 PT2
fn
[P2320]
Min. frequency
fmin f12 PT1
t
[E1866]
ANSI25-1 SC: PT1 > Max. voltage
1
0
t
[E1867]
ANSI25-1 SC: PT1 < Min. voltage
1
0
t
[E1868]
ANSI25-1 SC: PT1 > Max. frequency
1
0
t
[E1869]
ANSI25-1 SC: PT1 < Min. frequency
1
0
t
[E1870]
ANSI25-1 SC: PT1 in range
0
t
Figure 3-90 Function Synchrocheck operating range PT1: parameters [P] and events [E]
NOTE: Verification of compliance with the set operating range for phase-to-phase voltages
and frequency of PT2 is conducted in a similar manner to PT1.
is activated.
is activated.
NOTE: For special applications (such as genset test beds or mobile, switchable rental
units) parameter setting of the maximum frequency limit of the operating range
of the phase-to-phase voltages U12PT1 and U12PT2 can be changed by a
command of the data protocol Profibus DP.
To change parameter settings the user must activate the parameter change
mode by sending once the instruction number 1000 (start of parameter change).
After that, one or more parameter settings can be changed by sending the
related instruction numbers 1002 to 1012 (see document SYMAP-
Compact_Appendix_Modbus-Profibus-IEC103) with appropriate data values.
To finish parameter setting process the user must send once the instruction
number 1001. Subsequently, the SYMAP-Compact(+) device will take ca 16s
for reboot.
NOTE: For special applications (such as genset test beds or mobile, switchable rental
units) parameter setting of the minimum frequency limit of the operating range
of the phase-to-phase voltages U12PT1 and U12PT2 can be changed by a
command of the data protocol Profibus DP.
To change parameter settings the user must activate the parameter change
mode by sending once the instruction number 1000 (start of parameter change).
After that, one or more parameter settings can be changed by sending the
related instruction numbers 1002 to 1012 (see document SYMAP-
Compact_Appendix_Modbus-Profibus-IEC103) with appropriate data values.
To finish parameter setting process the user must send once the instruction
number 1001. Subsequently, the SYMAP-Compact(+) device will take ca 16s
for reboot.
The following figure represents the verification of compliance with the set voltage difference U
Example: Voltage reference [P2307] = PT2
t
t0
Re
with:
dU: Voltage difference (amount) between phase-to-phase voltages U12PT1 and U12PT2
U: Phase-to-phase voltage of the three phase power system PT1 to be synchronized
Uref: Reference voltage of the three phase power system PT2, PT1 is to be synchronised to
NOTE: As soon as the voltage difference U lies within the tolerance range set by
parameters Max. dU [P2321] und Min dU [P2322], event ANSI25-1 SC: dU in
range [E1878] is activated.
P2321 Max. dU
Maximum limit of the voltage differenz U (difference between phase-to-phase voltages
U12PT1 and U12PT2) of a level in excess of the reference voltage Uref; for a successful
synchronizing check (Synchrocheck: U, f, U, f, ), voltages must not exceed the
maximum limit of the voltage differenz U.
In case that the measured voltage differenz U exceeds the maximum limit of the
voltage differenz U set by parameter Max.dU [P2321], the event ANSI25-1 SC: dU >
Max. dU [E1876] is activated.
P2322 Min. dU
Minimum limit of the voltage differenz U (difference between phase-to-phase voltages
U12PT1 and U12PT2) of a level below the reference voltage Uref; for a successful
synchronizing check (Synchrocheck: U, f, U, f, ), voltages must not fall below the
minimum limit of the voltage differenz U.
In case that the measured voltage differenz U falls below the minimum limit of the
voltage differenz U set by parameter Min.dU [P2322], the event ANSI25-1 SC: dU <
Min. dU [E1877] is activated.
The following figure represents the verification of compliance with the set voltage difference U
and the set frequency differencef.
Ueff
Max. dU [P2321] Min. dU [P2322]
[P2317]
Max. voltage
Umax
U12 PT2
Un
U12 PT1
[P2318]
Min. voltage
Umin
t
f
Max. df [P2323] Min. df [P2324]
[P2319]
Max. frequency
fmax
f12 PT2
fn
[P2320]
Min. frequency
fmin
f12 PT1
t
[E1866]
ANSI25-1 SC: PT1 > Max. dU
1
0
t
[E1867]
ANSI25-1 SC: PT1 < Min. dU
1
0
t
[E1870]
ANSI25-1 SC: dU in range
0
t
[E1868]
ANSI25-1 SC: PT1 > Max. df
1
0
t
[E1869]
ANSI25-1 SC: PT1 < Min. df
0
t
[E1870]
ANSI25-1 SC: df in range
0
t
NOTE: As soon as the frequency difference f lies within the tolerance range set by
parameters Max. df [P2323] und Min df [P2324], event ANSI25-1 SC: df in range
[E1881] is activated.
P2323 Max. df
Maximum limit of the frequency differenz f (difference between frequencies of phase-to-
phase voltages U12PT1 and U12PT2); for a successful synchronizing check
(Synchrocheck: U, f, U, f, ), the frequency difference must not exceed the
maximum limit of the frequency differenz f.
When the measured frequency differenz f exceeds the maximum limit of the frequency
differenz f set by parameter Max.df [P2323], the event ANSI25-1 SC: df > Max. df
[E1879] is activated.
P2324 Min. df
Minimum limit of the frequency differenz f (difference between frequencies of phase-to-
phase voltages U12PT1 and U12PT2); for a successful synchronizing check
(Synchrocheck: U, f, U, f, ), the frequency difference must not fall below the
minimum limit of the frequency differenz f.
When the measured frequency differenz f falls below the maximum limit of the
frequency differenz f set by parameter Min.df [P2324], the event ANSI25-1 SC: df <
Min. df [E1880] is activated.
The following figure represents the verification of compliance with the set phase angle
difference .
Example: Voltage reference [P2307] = PT2
PT1 < PT2
Im
Parameter: Min. dPHI [P2326]
U12, PT2
Ref
Re
with:
U12, PT1: Measured phase-to-phase voltage U12 of the three phase power system PT1 to be synchronized
U12, PT2: Measured phase-to-phase voltage U12 of the three phase power system PT2 (reference system), PT1 is to be synchronized to
d: Phase angle difference (dPHI) between the phase-to-phase voltages U12PT1 and U12PT2
: Phase angle of the phase-to-phase voltage U12PT1 of the three phase power system PT1 to be synchronized
Ref: Phase angle of the phase-to-phase voltage U12PT2 of the three phase power system PT2 (reference system), PT1 is to be
synchronized to
Figure 3-93 Function Synchrocheck Verification of compliance with phase angle difference
d
NOTE: As soon as the phase angle difference lies within the tolerance range set by
parameters Max. dPHI [P2325] und Min dPHI [P2326], event ANSI25-1 SC: dPHI
in range [E1884] is activated.
The following figure represents the correction of angular errors caused by connected potential
transformers (PT)
For the following example, assumptions are listed below:
the reference system is assigned to PT2 (parameter Voltage reference [P2307] = PT2)
the phase angle difference of the phase-to-phase voltages U12PT1 and U12PT2 is taken
to be zero
Example: Voltage reference [P2307] = PT2
t
t0
dF, PT = F, PT1 + F, PT2
U12, PT1, mess.
Im
U12, PT1
F, PT1 = +6 For the angular error correction it is:
= 14
Re
with:
U12, PT1: Actual phase-to-phase voltage U12 of the three phase power system PT1 to be synchronized
U12, PT2: Actual phase-to-phase voltage U12 of the three phase power system PT2, PT1 is to be synchronized to
U12, PT1, mess.: Measured phase-to-phase voltage U12 of the three phase power system PT1 to be synchronized
U12, PT2, mess.: Measured phase-to-phase voltage U12 of the three phase power system PT2, PT1 is to be synchronized to
F, PT1: Angular error of potential transformer (PT) connected to PT1
F, PT2: Angular error of potential transformer (PT) connected to PT2
dF, PT: Total angular error of potential transformers connected to PT1 and PT2
NOTE: Correction of angular errors does not depend on the current phase angles of the
phase-to-phase voltages U12PT1 und U12PT2.
NOTE: The correction angle is not for transformer vector group matching!
Vector group matching is to be set by appropriate parameter setting in
submenu SYSTEM\Nominals\Reference values.
NOTE: The set value of parameter CB closing delay [P2329] should be equal to the sum of
all operating times
Specific operating times of additionally applied, external components can be taken
from the data sheets of the maufacturer
xt
t0 1tn+1 tn+1 = tn + tCB closing time
U12, PT1
2tn+1
d
U12, PT2 d
2tn
U12, PT2
Re
with:
U12, PT1: Phase-to-phase voltage U12 of the three phase power system PT1 to be synchronized PT1, at the time tn
U12, PT1: Phase-to-phase voltage U12 of the three phase power system PT1 to be synchronized PT1, at the time tn+1
U12, PT2: Phase-to-phase voltage U12 of the three phase power system PT2, PT1 is to be synchronized to, at the time tn
U12, PT2: Phase-to-phase voltage U12 of the three phase power system PT2, PT1 is to be synchronized to, at the time tn+1
d: Phase angle difference, at the time tn
d: Phase angle difference, at the time tn+1
1: Angular frequency (1 = 2 fPT1) of phase-to-phase voltage U12 of the three phase power system PT1
2: Angular frequency (2 = 2 fPT2) of phase-to-phase voltage U12 of the three phase power system PT2, PT1 is to be
synchronized to
Figure 3-95 Function Synchrocheck Consideration of operating times: phasor
diagram
If at the time tn the calculated phase angle difference for the time tn+1 = tn + tCB closing time
is within the required tolerance range, then
synchronous-event ANSI25-1 SC: Synchronous pre-event [E1885] is activated and
if configured the Delay time [P2328] for on-delayed of the synchronous-event
ANSI 25-1 SC: Synchronous [E1886] is started.
Voltage.check (U, f)
Independent of function Synchrocheck (U, f, U, f, ) function Voltage check (U, f) checks
the voltage conditions of the two three phase power systems PT1 and PT2 to clearly
discriminate a live power system from a dead power system.
P2335 Function
This parameter defines the preconditions for the effectiveness of function Voltage
check (U, f) relating to the voltage conditions of the three phase power systems PT1
and PT2 and, subsequently, the activation of synchronous-events.
Function Voltage check (U, f) will only be initiated when
its effectiveness is activated (Function [P2335] OFF) and
synchronizing unit 1 (Sync. unit 1) is activated by the event which is assigned to
parameter Active by event [P2305].
P2336 Blocking
Function Voltage check (U, f) of synchronizing unit 1 (Sync. unit 1) can be blocked by
any active event. For blocking, the number related to this blocking event has to be
assigned to parameter [P2336]. Blocking is only effective, however, as long as the
blocking event is active. As soon as blocking is active, event ANSI25-1 VC: Blocked
[E1890] is activated. If the blocking event becomes inactive, blocking is abandoned and
synchronizing check is effective again. Then, event [E1890] is deactivated automatically.
If blocking of function Voltage check (U, f) of synchronizing unit 1 is not required, set
this parameter to 0.
Definition of tolerance ranges as precondition for determination of live and dead power
systems => Voltage check (U, f:
t
t0
Im
Parameter: Max. voltage [P2317]
U12 PT1
U12 PT2
Re
Figure 3-96 Voltage check operating ranges: phase-seggregated voltage check (amount)
As soon as the amount and the frequency of the phase-to-phase voltages U12 of PT1 and/or
PT2 are within the operating range set by parameters:
Max. voltage [P2337] and Min. voltage [P2338], and
Max. frequency [P2339] and Min frequency [P2340],
the event:
ANSI25-1 VC: PT1 in range [E1895] and/or the event
ANSI25-1 VC: PT2 in range [E1902]
is activated.
is activated.
is activated.
NOTE: For special applications (such as genset test beds or mobile, switchable rental
units) parameter setting of the maximum frequency limit of the operating range
of the phase-to-phase voltages U12PT1 and U12PT2 can be changed by a
command of the data protocol Profibus DP.
To change parameter settings the user must activate the parameter change
mode by sending once the instruction number 1000 (start of parameter change).
After that, one or more parameter settings can be changed by sending the
related instruction numbers 1002 to 1012 (see document SYMAP-
Compact_Appendix_Modbus-Profibus-IEC103) with appropriate data values.
To finish parameter setting process the user must send once the instruction
number 1001. Subsequently, the SYMAP-Compact(+) device will take ca 16s
for reboot.
NOTE: For special applications (such as genset test beds or mobile, switchable rental
units) parameter setting of the minimum frequency limit of the operating range
of the phase-to-phase voltages U12PT1 and U12PT2 can be changed by a
command of the data protocol Profibus DP.
To change parameter settings the user must activate the parameter change
mode by sending once the instruction number 1000 (start of parameter change).
After that, one or more parameter settings can be changed by sending the
related instruction numbers 1002 to 1012 (see document SYMAP-
Compact_Appendix_Modbus-Profibus-IEC103) with appropriate data values.
To finish parameter setting process the user must send once the instruction
number 1001. Subsequently, the SYMAP-Compact(+) device will take ca 16s
for reboot.
The minimum voltage limit is valid for both, three phase power system PT1 and PT2.
When the measured phase-to-phase voltage U12 of a power system (PT1 and/or PT2)
falls below the minimum voltage limit set by parameter No voltage limit [P2341], the
event:
ANSI25-1 VC: PT1 < Min. voltage [E1892] for PT1 and/or
ANSI25-1 VC: PT2 < Min. voltage [E1899] for PT2
is activated.
When the measured phase-to-phase voltage U12 of a power system (PT1 and/or PT2)
falls below the minimum voltage limit set by parameter No voltage limit [P2341], the
event:
ANSI25-1 VC: PT1 > No voltage limit [E1896] for PT1 and/or
ANSI25-1 VC: PT2 > No voltage limit [E1903] for PT2
is activated.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
NOTE: Control functions of ANSI 25A Automatic Synchronisation will not be executed until
the correspnoding synchronizing unit of function ANSI 25 Synchronization is
activated!
CAUTION: SYMAP-Compact(+) device variants which were built according to ordering option
G59:
do not provide frequency measurement via voltage measurement input PT3!
do provide phase-seggregated frequency measurement (zero crossings of
phase voltages) only at voltage measurement input PT2!
do provide frequency measurement at PT1 based on crossings of phase-to-
neutral voltages UL1 and UL2!
Controller
Controller
Parameter description:
The following parameter descriptions refer to all control parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters for all three synchronizing units (Sync. unit 1 to Sync. unit 3).
Parameter descriptions of the SET PARAMETERS and the parameters of the first
synchronizing unit (Sync. unit 1) represented below, are described below in detail as
examples.
CAUTION: SYMAP-Compact(+) device variants which were built according to ordering option
G59:
The following parameters Function [P2425] and Blocking [P2426] refer to all of the three
above mentioned control functions.
P2425 Function
This parameter enables/disables the effectiveness of synchronizing unit 1 (Sync. unit 1)
for automatic synchronization (Controller: frequency control, phase angle control and
voltage control) where:
OFF: disables or
ON: enables the effectiveness of synchronizing unit 1 for automatic
synchronization.
2.Fall: Generator (PT1) voltage and frequency is in or out of the defined Voltage check
operating range of function ANSI 25 Synchronizing;
Busbar (PT2) voltage and frequency is out of the defined Synchrocheck operating
range of function ANSI 25 Synchronizing, see parameters: Max. voltage [P2317],
Min. voltage [P2318], Max. frequency [P2319] and Min. frequency [P2320],
however, voltage level exceeds the set value of parameter No voltage limit [P2341].
ANSI25-1 SC: PT2 in range [E1875] = inactive and
ANSI25-1 VC: PT2 > No voltage limit [E1903] = active
Under these circumstances automatic blocking of the control functions avoids any
generator control actions to synchronize with the reference voltage system (busbar)
which is not dead but out of its defined Synchrocheck operating range.
P2426 Blocking
Automatic synchronization (Controller: frequency control, phase angle control and
voltage control) of synchronizing unit 1 (Sync. unit 1) can be blocked by any active
event. For blocking, the number related to this blocking event has to be assigned to
parameter [P2426]. Blocking is only effective, however, as long as the blocking event is
active. If the blocking event becomes inactive, blocking is abandoned and automatic
synchronization is effective again.
If blocking of automatic synchronization Controller of synchronizing unit 1 is not
required, set this parameter to 0.
Frequency control
As soon as synchronizing unit 1 is activated, frequency control is activated independently of
functions Voltage control and Phase angle control. Function frequency control affects that
three phase system, which is connected to PT1 (e.g. generator).
Due to the proportionality of motor revolutions RPM (e.g. Diesel motor drives generator) and
generator frequency, fast frequency control (frequency range: Hz) is to be done by the RPM
governer of the electric drive engine (motor) in a time range of milliseconds. Small and slow
frequency deviations (frequency range: millihertz; time range: seconds to minutes) are to be
equalized by function Frequeny control of SYMAP-Compact(+).
Function Frequency control of SYMAP-Compact(+) is designed as a three step control
including the output states: frequency increase and frequency decrease. For this, the following
two control-events are provided:
Frequency higher event [E2020]: signal to external speed governer to increase RPM
(=> Frequency increase), and
Frequency lower event [E2021]: signal to external speed governer to decrease RPM
(=> Frequency decrease)
Depending on the type of motor speed governer the control events have to be assigned to:
two different binary outputs of the SYMAP-Compact(+) (binary control, e.g. for naval
applications)
function Frequency control is only effective, if frequency fPT1 of Power system PT1 lies within
the tolerance range set by the set limits fmin and fmax.
REMARK: In view of the following statements the momentary control deviation (frequency
difference fU12 PT1; PT2) is given as a percentage f[%] of the nominal frequency fn
set by parameter Nominal Frequency [P603].
time [P2427].
[P2320]
Min. frequency
fmin
fU12, PT1
t
Counter pulse time
[P2428]
Frequency controller max pulse time
0
tFreq. contr. pulse 1
t
tFreq. contr. pulse 8 tFreq. contr. pulse 15
0
t
tFreq. contr. interval tFreq. contr. interval tFreq. contr. interval
[E2021]
Frequency lower event
1
0
t
[E2020]
Frequency higher event
1
0
t
Figure 3-100 Function Controller Frequency control
NOTE: When frequency of power system PT1 (generator) lies within the tolerance range set
by fmax and fmin (parameters Max. df [P2323] and Min df [P2324]), function
Frequency control is blocked.
Example: Parameter Frequency controller max puls time [P2428] = 100s (typical set
value)
As soon as Phase angle control ist activated, Frequency control is blocked. The regulation of
the phase angle is done by the control of the motor RPM governer which is used to change the
generator frequency. Thus, function Phase angle control also operates the control-events
Frequency higher event [E2020] and Frequency lower event [E2021].
The following figure shows as example the interactions between frequency control and phase
angle control with the implications for the control-events
fPhase contr.max
[P2429] fU12, PT2 fmax
Phase controller active at
fn
fmin
fPhase contr.max
fU12, PT1
t
5 7 12 14 16
4 6 8 13 15 17
180 U12, PT1
[P2325]
Max. dPHI max U12, PT2
[P2326]
Min. dPHI min t
-180
0
tFreq. contr. pulse 1 t
tPhase contr. pulse 4 tPhase contr. pulse 16
0
t
tFreq. contr. interval tFreq. contr. interval tFreq. contr. interval
0
t
Frequency higher event [E2020]
[E1885]
t
ANSI25-1 SC: Synchronous pre-event
0
t
Figure 3-101 Function Controller Phase angle control
NOTE: For most applications it is useful to choose the same settings of parameters
Phase controller active at [P2429] and Max. dPHI [P2325] or Min. dPHI
[P2326]. So, it is granted that phase angle control should begin, if
synchronizing criterion fU12, PT1; U12, PT2 < fmax respectively fU12, PT1; U12, PT2 <
fmin is fulfilled.
When the phase angle control is activated, the frequency control is deactivated.The
corresponding control-event:
Frequency higher event [E2020]: signal to external speed governer to increase
RPM (=> Frequency increase), or
Frequency lower event [E2021]: signal to external speed governer to decrease
RPM (=> Frequency decrease)
is activated due to the cyclically calculated pulse times tPhase contr. pulse x which depend on
the set value of parameter Phase controller max pulse time [P2430].
As soon as the measured phase angle difference lies within the tolerance range
(max; min) set by parameters Max. dPHI [P2325] and Min. dPHI [P2326],
synchronizing criterion min > U12 PT1; U12 PT2 < max is fulfilled.
Example: Parameter Phase controller max pulse time [P2430] = 0,5s (typical set value)
NOTE: An activated control event will only become inactive, if the subsequent,
calculated pulse time is below the set value of the set break time (parameter
Frequency controller intervall time [P2427]) or if the control direction changes
for the next calculated pulse time.
Voltage regulation
As soon as synchronizing unit 1 is activated, voltage control is activated independently of
functions Frequency control and Phase angle control. Function voltage control affects the
three phase system that is connected to PT1 (e.g. generator).
Function Voltage control of SYMAP-Compact(+) is designed as a three step control
including the output states: voltage increase and voltage decrease. For this, the following two
control-events are provided:
Voltage higher event [E2022]: signal to external voltage governer (=>Voltage increase),
and
Voltage lower event [E2023]: signal to external voltage governer (=>Voltage decrease)
Depending on the type of motor voltage governer the control events have to be assigned to:
two different binary outputs of the SYMAP-Compact(+) (binary control, e.g. for naval
applications)
Voltage control is only effective, if voltage UPT1 of Power system PT1 lies within the tolerance
range set by the set limits Umin and Umax.
REMARK: In view of the following statements the momentary control deviation (voltage
difference U12 PT1; PT2) is given as a percentage U[%] of the nominal voltage Un
set by parameter Voltage (L-L) [P603].
[P2338]
Min. voltage Umin
U12, PT1
t
Counter pulse time
[P2432]
Voltage controller max pulse time
0
tVolt. contr. pulse 1
t
tVolt. contr. pulse 8 tVolt. contr. pulse 15
0
t
tVolt. contr. interval tVolt. contr. interval tVolt. contr. interval
[E2023]
Voltage lower event
1
0
t
[E2022]
Voltage higher event
1
0
t
Figure 3-102 Function Controller Voltage control
Example: Parameter Voltage controller puls time [P2432] = 10s (typical set value)
Determination of the control direction:
U[V] > 0
If the voltage difference U is positive (UPT1 < UPT2), the voltage boost event
Voltage higher event [E2022] is activated for the duration of the calculated
pulse time.
U[V] < 0
If the voltage difference U is negative (UPT1 > UPT2), the voltage boost event
Voltage lower event [E2023] is activated for the duration of the calculated
pulse time.
ANSI 27 Undervoltage
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in detail in the following
examples.
SET PARAMETERS
The following SET PARAMETERS of the undervoltage protection exist only once in each of the
four parameter sets. Thus, the SET PARAMETERS apply to all of the 12 protection STEPS of
one parameter SET.
OFF: disables or
ON: enables the protective function.
NOTE: When no voltage measurement is possible, caused by locating the PTs below
the circuit breaker, and which is open, undervoltage protection must be
blocked by a suitable event. For this, the related number of such blocking
event has to be assigned to parameter [P1051].
For settings PT1, PT2 or PT3, event ANSI27-1 step acitve [E1054] is activated.
P1060 Limit
Pick-up value of the first undervoltage protection element. At the moment that the
characteristic quantity (voltage) falls below this limit, pick-up event ANSI27-1 pickup
[E1058] will become active, and the trip delay time (Delay time) of the first
undervoltage protection element will start.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
chosen characteristic quantity (phase-to-phase voltage or phase-to-neutral
voltage) by parameter Voltage reference [P1066]. However, the chosen
characteristic value refers to the nominal value of the phase-to-phase voltage
to be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2
Voltage (L-L) [P623], for tertiary side W3.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
NOTE: The reset limit should be set as a percentage of the nominal value of the
chosen characteristic quantity (phase-to-phase voltage or phase-to-neutral
voltage) by parameter Voltage reference [P1066]. However, the chosen
characteristic value refers to the nominal value of the phase-to-phase voltage
to be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2
Voltage (L-L) [P623], for tertiary side W3.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
If activation of the blocking criteria (see parameters [P1058] and/or [P1059]) during
generator start phase is not required, set parameter Activate start condition [P1065] to
0.
Ueff/Un
100%
[P1060] limit
t
[E1058]
ANSI27-1 pick-up
0
t
[P1061]
delay time
t
[P1064]
reset delay time
pick-up
t
[E1059]
ANSI 27-1 trip
0
t
[P1063]
reset delay time
trip
More and more distributed energy resources (DER) are fitted in the MV grid. The amount of
controllable power reserve (active and inductive reactive power) by means of large-scale
conventional plants is decreasing. Reactive power is used to maintain mains voltage stability.
Faults in the grid, increasing load with reactive power requirements and changes within the
network may lead to mains voltage drops.
In the event of serious voltage drops in several grid sections, such voltage instability may cause
a collapse of the mains voltage by means of cutting the power supply (blackout).
Protection equipment is of considerable importance for secure and reliable operation of
networks, connection facilities and generating plants. National grid codes and regulations
require that DER units feeding into MV grid have to support the mains voltage of a network
failure. Therefore, the purpose of voltage and frequency protection units at machine level is to
disconnect the generating units from the grid in case of faults. If a voltage drop and a inductive,
reactive power flow in the direction towards the generating unit are detected at the network
connection point simultanouslay, then first, the affected generating unit will be switched off
(disconnecting the generator circuit breaker). After an unsuccessfull attempt to disconnect the
generating unit, the whole DER plant will be switched of by the circuit breaker at the network
connection point.
As far as the disconnection of the affected generating unit (generator circuit breaker) from the
medium voltage network bases on one of the following protective functions:
Undervoltage protection (U<, U<<) or
Overvoltage protection (U>, U>>) or
Under frequency protection (f<, f<<) or
Overfrequency protection (f>, f>>)
The mains voltage may not necessarily measured at the network connection point. According to
the above mentioned protective functions, reclosing of the generator CB shall only take place
after a certain, given period of time (release signal for reclosing the generator CB).
In so far as the DER is disconnected from the grid at the network connection point, the
individual generating units are shut down, too. Consequently, reclosing of the CB at the network
connection point does not require any mains voltage measurement. Reclosing is done
manually.
Transmission Code 2007, Network and System Rules of the German Transmission System
Operators, Version 1.1, August 2007, from the German Electricity Association (VDEW) and
Association of network operator (VDN), see chapter 3.3.13.5 (6)
Technical guideline: Generating plants connected to the medium-voltage network
(Guideline for generating plants connection to and parallel operation with the medium-
voltage network), June 2008, Federal Association of the Energy and Water Industry -
BDEW, see chapter 3.2.3.2 Reactive power-Undervoltage protection Q&U<
Specification sheet Reactive power-Undervoltage protection, February 2010, Grid
technology/grid operation forum (FNN) of VDE
This U<& Q> protection is an upstream system protection. This U<& Q> protection function is
implemented in the SYMAP-Compact(+) devices as an autonomous protection element
according to the above mentioned BDEW (German) regulations.
Figure 3-105 ANSI 27Q Protection parameters [P] and events [E] of SET 1
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides only one protection STEP and, as
consequence, only one group of parameters. Thus, SET PARAMETERS are equal to
STEP parameters. The protection parameters of SET 1 represented below are
described in detail in the following examples.
NOTE: In case that no voltage measurement is possible, caused by locating the PTs
below the circuit breaker, and which is open, then undervoltage-/reactive
power protection must be blocked by a suitable event. For this, the related
number of such blocking event has to be assigned to parameter [P1581].
NOTE: The assignment of the voltage measurement input (PT1, PT2 or PT3) to the
current measurement input CT1 or CT2 is to be done by the following
parameters (referring to the setting options of parameter [P1582]), in the
submenu SYSTEM\Measuring\Power:
PT reference [P9410], for Power_CT1 and
PT reference [P9413], for Power_CT2
L1
L2
L3
-X1.1
P1 1 SYMAP-Compact
S1 Parameter settings:
P2 S2
4 CT2-MP: Direction L1 [P671] = 0
P1 5 CT2-MP: Direction L2 [P672] = 0
LRAS
P2 S2
6
Normal operation: Example
P1 S1
8
9 ANSI 27Q: working principle by viewpoint of Utility (LRAS)
P2 S2 => protection trip: if U< and Q>0
CT2-M/P
P1 S1
10
P2 11
S2
P1 S1
12
Figure 3-106 ANSI 27Q Connection example and definition of load flow direction
[P1587]
[P1583] Q1 >
(Reference arrow system) UL1, UL2, UL3 (LARS)
U12 IL1, IL2, IL3 (Reactive power limit)
U23
1
[P1587]
U31
Q1 <
IL1 (GRAS)
IL2 S1 = P1 + jQ1
(Reactive power limit)
IL3
[P1589]
T 0 [E1409]
[P1586]
(ANSI27Q 1st trip)
I1>
(1. delay time")
[E1409]
(Current limit) & (ANSI27Q pickup)
[P1590]
[P1585]
T 0 [E1410]
U12< (ANSI27Q 2nd trip)
[P1585]
U23<
(Voltage limit)
[P1585]
U31<
(Voltage limit)
then the pick-up event ANSI27Q pickup [E1408] is activated, and the counters of 1st
delay time and 2nd delay time are started. As soon as one of the above mentioned
conditions becomes false, pick-up event ANSI27Q pickup [E1408] will be decativated.
NOTE: The voltage limit should be set as a percentage of the nominal value of the
characteristic quantity (phase-to-phase voltage). The nominal value of the
characteristic quantity should be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2 or
Voltage (L-L) [P623], for tertiary side W3.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
then the pick-up event ANSI27Q pickup [E1408] is activated, and the counters of 1st
delay time and 2nd delay time are started. As soon as one of the above mentioned
conditions becomes false, pick-up event ANSI27Q pickup [E1408] will be decativated.
NOTE: The current limit should be set as a percentage of the nominal value of the
characteristic quantity (phase current). The nominal value of the characteristic
quantity should be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P624] are
located in submenu: SYSTEM\Nominals\Reference values.
then, the pick-up event ANSI27Q pickup [E1408] is activated, and the counters of 1st
delay time and 2nd delay time are being started. As soon as one of the above
mentioned conditions becomes untrue, pick-up event ANSI27Q pickup [E1408] will be
decativated.
NOTE: The reactive power limit is to be set as a percentage of the nominal value of
the characteristic quantity (according to users input either as active power,
reactive power or apparent power). The nominal value of the characteristic
quantity is to be set by parameter:
Power [P605], for primary side W1 or
Power [P615], for secondary side W2.
The parameters Power [P605] and Power [P615] are located in submenu:
SYSTEM\Nominals\Reference values.
trip) will start. If the 1. reset delay time (1st trip) has run down, trip event ANSI27Q 1st
trip [E1409] is deactivated.
In case that the pick-up ANSI27Q pickup [E1408] becomes active before the first trip
reset delay time has run down, then counter 1. reset delay time (1st trip) will be reset
immediately.
Event [P1600]
(Reclosing trigger event 1")
Event [P1601]
[P1598]
(Reclosing trigger event 2")
A T 0 B
. 1
.
. (Delay time")
Event [P1615]
(Reclosing trigger event 16")
&
[P1596] [E1413]
(ANSI27Q reclosing release)
f f>
( Min. frequency, z.B. f > 47,5 Hz)
[P1597]
&
f<
[P1595]
U12 U12>
(Voltage limit)
[P1595]
[E1412]
U23 U23> & (ANSI27Q voltage reclosing limit reached)
(Voltage limit)
[P1599]
(External voltage release event)
Event [P1599]
Function [P1616] = ON
f
fn
t
URMS/Un
100%
t
[E1058]
ANSI27-1 trip
A t
(Input signal of counter
Delay time)
1
0
t
[P1598]
Delay time
B
(Output signal of counter t
Delay time)
1
0
t
[E1412]
ANSI27Q Voltage reclosing
limit reached 1
0
t
[E4010]
Binary input Fct.10
0
t
[E1413]
ANSI27Q reclosing release
0
t
P1616 Function
This parameter enables/disables reclosing function of ANSI 27Q Undervoltage-
/Reactive power protection where:
OFF: disables the reclosing function or
ON: enables the reclosing function.
NOTE: Disabling of reclosing function can be used for testing purposes of the
protection function.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
NOTE: As long as one of the trip events assigned to parameters [P1600] to [P1615] is
activated, reclosing release is blocked by means of deactivating event
ANSI27Q reclosing release [E1413].
According to the German Energy and Water Association (Bundesverband der Energie- und
Wasserwirtschaft e.V. BDEW) directive on connection and parallel operation of power plants in
medium-voltage grids (Erzeugungsanlagen am Mittelspanungsnetz (Richtlinie fr Anschluss
und Parallelbetrieb von Erzeugungsanlagen am Mittelspannungsnetz)), power plants being
operated in parallel to operators medium-voltage grids have to meet certain requirements of
grid support.
As far as their protection devices are concerned, such power plants shall, in case of voltage
drop, contribute to grid support and thus not be disconnected from the grid. Conventional under
voltage protection can thus not necessarily be used.
The time-dependent undervoltage relay ANSI 27T as used in the SYMAP-Compact(+) fully
meets the above mentioned requirement. The trigger characteristic can be freely defined by
parameterizing to up to 10 characteristic points. Due to this feature, the user may configure
several different time-dependent trigger areas. The number of tolerated brief voltage drops
(Number of blocked voltage drops) can be set by parameter and is acquired by a counter.
Maximum duration of counting (Time slot for voltage drops count) can be set.
Trigger characteristic is activated (Start of functional timer) as soon as the low limit pick-up
setting for under voltage (Activate Limit) is fallen below and will be reset (Stop of functional
timer) if grid voltage exceeds the reset value (Reactivate limit) for a settable duration
(Reactivate delay time).
Protection triggering depends on the situation in the grid. Generally, two situations can be
differentiated:
1st case: Grid voltage falls below the low trigger value set in the characteristic curve
and triggers a time-dependent protection
nd
2 case: The counted value is exceeded and triggers an immediate time-independent
protection
After the counter attains the set value, the characteristic curve will not be reset and the
subsequent voltage drop triggers a protection depending on the characteristic curve.
27t
150
100
%
50
0
-100 900 1900 2900 3900
ms
Setting limit
Figure 3-110 ANSI 27T Configurable trip curve
Main Menu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides only one protection STEP and, as
consequence, only one group of parameters. Thus, SET PARAMETERS are equal to
STEP parameters. The protection parameters of SET 1 represented below are
described in the following in detail as examples.
NOTE: In case that no voltage measurement is possible, caused by locating the PTs
below the circuit breaker, and which is open, then, time-dependent
undervoltage protection must be blocked by a suitable event. For this, the
related number of such blocking event has to be assigned to parameter
[P1476].
NOTE: The pick-up value for voltage drop is to be set as a percentage of the nominal
value of the characteristic quantity (phase-to-phase voltage). The nominal
value of the characteristic quantity is to be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2 or
Voltage (L-L) [P623], for tertiary side W3.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
then, the trip-event ANSI27T trip [E1355] is being acitvated, so too does either:
event ANSI27T trip by voltage drop count [E1356] or
event ANSI27T trip by voltage underrun [E1357].
Also the Time slot for voltage drops count is being reset. In case that there is no further
voltage drop, the attained value for counted voltage drops will be set to zero after the
expiry of the Time slot for voltage drops count.
NOTE: The reset limit for voltage drops is to be set as a percentage of the nominal
value of the characteristic quantity (phase-to-phase voltage). The nominal
value of the characteristic quantity is to be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2 or
Voltage (L-L) [P623], for tertiary side W3.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
Ueff/Un
Voltage drop Voltage curve
[P1497] 100%
[P1495]
Programmable
tripping curve
[P1491], [P1493]
[P1487], [P1489]
t
t1 = 0s t2, t3 t4 t5 t6
[P1490], [P1492]
Ueff/Un
Anrege-Event / Voltage drop
100%
[E1354] t
ANSI 27T pick-up
1
0
t
[E1352] t
ANSI 27T reactive limit reached
1
0
t
[P1485]
reactivate delay time
0
t
[P1478]
number of blocked 3
voltage drops = 2"
1
[P1479]
t
time slot for voltage drops
count
0
[E1355] t
ANSI 27T trip
1
0
[E1357] t
ANSI 27T trip by curve underrun
1
0
t
100%
t
[E1354]
ANSI 27T pick-up
1
0
t
(internal function timer)
t
[E1352]
ANSI 27T reactive limit reached
1
0
t
[P1485]
reactivate delay time
0
t
[P1478]
number of blocked 3
voltage drops = 2"
1
t
[P1479]
time slot for voltage drops
count
0
[E1355] t
ANSI27T trip
1
0
[E1356] t
ANSI 27T trip by voltage drops count
1
0
t
Figure 3-114 Time-independent protection trip
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
SET PARAMETERS
The following SET PARAMETERS of the directional power protection exist only once in each of
the four parameter sets. Thus, the SET PARAMETERS apply to all of the 6 protection STEPS of
one parameter SET.
NOTE: The assignment of the voltage measurement input (PT1, PT2 or PT3) to the
current measurement input CT1 or CT2 is to be done by the following
parameters (referring to the setting options of parameter [P1582]), in the
submenu SYSTEM\Measuring\Power:
PT reference [P9410], for Power_CT1 and
PT reference [P9413], for Power_CT2
To measure power direction correctly, the needed energy flow direction is to
be defined by following parameters:
Direction [P9411], for Power_CT1 and
Direction [P9414], for Power_CT2.
P2247 Mode
Selction of operating mode according to the protective criterion (characteristic quantity)
of the directional power protection; the first step of of directional power protection is
optionally adjustable. The set value of parameter Limit [P2248] refers to the
The following graphics represents all the different setting options for the applied
characteristic quantity as protective criterion.
Q Q
Trip zone
Trip zone
P P
[P2248] Limit
[P2248] Limit
Q Q
Trip zone Trip zone
P P
[P2248] Limit [P2248] Limit
P P
Trip zone
Trip zone
P P
[P2248] Limit
[P2248] Limit
Trip zone
P2248 Limit
Pick-up value of the first directional power protection element (STEP1); at the moment
that the characteristic quantity depending on the set value of parameter Mode
[P2247] exceeds (or falls below) this limit, ANSI32-1 pick-up [E1809] will become
active, and Delay time of the first directional power protection element will start.
In case that the characteristic quantity falls below (or exceeds) the Limit of the first
directional power protection element before Delay time has run down, the timer of
Delay time will be stopped and the attained time value is being safed.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
measurement quantity Power (according to users input either as active
power, reactive power or apparent power). The nominal value of this
measurement quantity is to be set by parameter:
Power [P605], for primary side W1 or
Power [P615], for secondary side W2 or
Power [P625], for tertiary side W3.
Here, it is that winding side relating to the directional power monitoring, which
is assigned to the applied current measurement input by parameter
Assignment [P668], for current measurement input CT1 or
Assignment [P674], for current measurement input CT2.
The parameters Power [P605], Power [P615] and Power [P625] are
located in submenu: SYSTEM\Nominals\Reference values.
NOTE: The reset limit is to be set as a percentage of the nominal value of the
measurement quantity Power (according to users input either as active
power, reactive power or apparent power). The nominal value of this
measurement quantity is to be set by parameter:
Power [P605], for primary side W1 or
Here, it is that winding side relating to the directional power monitoring, which
is assigned to the applied current measurement input by parameter
Assignment [P668], for current measurement input CT1 or
Assignment [P674], for current measurement input CT2.
The parameters Power [P605], Power [P615] and Power [P625] are
located in submenu: SYSTEM\Nominals\Reference values.
Peff/Pn
[P2247] Mode = P>
[P2248] Limit
100%
t
[E1809]
ANSI32-1 pick-up
1
0
t
[P2249]
Delay time
[P2252]
Reset delay time pick-up
t
[E1810]
ANSI32-1 trip
0
t
[P2251]
Reset delay time trip
Figure 3-117 Directional power protection Tripping and reset characteristic: over-run of P>
Peff/Pn
[P2247] Mode = P<
100%
[P2250] Limit
t
[E1809]
ANSI32-1 pick-up
0
t
[P2249]
Delay time
t
[P2252]
Reset delay time pick-up
t
[E1810]
ANSI32-1 trip
0
t
[P2251]
Reset delay time trip
Figure 3-118 Directional power protection Tripping and reset characteristic: under-run of P<
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
SET PARAMETERS
The following SET PARAMETERS of the zero power protection exist only once in each of the
four parameter sets. Thus, the SET PARAMETERS apply to all of the 6 protection STEPS of
one parameter SET.
NOTE: The assignment of the voltage measurement input (PT1, PT2, PT3 or PT-
GND1) to the zero current measurement input CT1, CT2 or CT-GND1 is to be
done by the following parameters (referring to the setting options of parameter
[P2460]), in the submenu SYSTEM\Measuring\Power:
PT reference [P9419], for GND Power_CT1
PT reference [P9422], for GND Power_CT2 and
PT reference [P9428], for GND Power_CT-GND1
To measure zero power direction correctly, the required energy flow direction
is to be defined by following parameters:
Direction [P9420], for GND Power_CT1 and
NOTE: In case that residual voltage is to be calculated by voltage measuring via PT1,
PT2 or PT3 it is required to connect terminal N of SYMAP-Compact(+)
device (SYMAP-Compact: -X1.2:18; SYMAP-Compact+: -X1.2:26) to ground
potential!
For test purposes via voltage generator test equipment it is required to
connect terminal N of SYMAP-Compact(+) device to the neutral potential
of the voltage test equipment!
P2977 Mode
Selection of operating mode according to the protective criterion (characteristic quantity)
of the zero power protection; the first step of zero power protection is optionally
adjustable. The set value of parameter Limit [P2978] refers to the characteristic
quantity of the set protective criterion of parameter Mode [P2977]. Following setting
options of the characteristic quantity are available:
P0<: protective function detects an alarm in case of zero active power limit
under-run
P0>: protective function detects an alarm in case of zero active power limit over-
run
Q0<: protective function detects an alarm in case of zero reactive power limit
under-run
Q0>: protective function detects an alarm in case of zero reactive power limit
over-run
S0<: protective function detects an alarm in case of zero apparent power limit
under-run
S0>: protective function detects an alarm in case of zero apparent power limit
over-run
P0r<: protective function detects an alarm in case of zero active power limit
under-run
P0r>: protective function detects an alarm in case of zero reverse active power
limit over-run
Q0r<: protective function detects an alarm in case of zero reactive power limit
under-run
Q0r>: protective function detects an alarm in case of zero reverse reactive power
limit over-run
The following graphics represents all the different setting options for the applied
characteristic quantity as protective criterion.
[P2977] Mode = P0> [P2977] Mode = P0<
Q0 Q0
Trip zone
Trip zone
P0 P0
[P2978] Limit
[P2978] Limit
Q0 Q0
Trip zone Trip zone
P0 P0
[P2978] Limit [P2978] Limit
P0 P0
Trip zone
Trip zone
P0 P0
[P2978] Limit
[P2978] Limit
Trip zone
P2978 Limit
Pick-up value of the first zero power protection element (STEP1); at the moment that the
characteristic quantity depending on the set value of parameter Mode [P2977]
exceeds (or falls below) this limit, ANSI32N/G-1 pick-up [E2284] will become active,
and Delay time of the first zero power protection element will start.
In case that the characteristic quantity falls below (or exceeds) the Limit of the first zero
power protection element before Delay time has run down, the timer of Delay time will
be stopped and the attained time value is being saved.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
measurement quantity Power (according to users input either as active
power, reactive power or apparent power). The nominal value of this
measurement quantity is to be set by parameter:
Power [P605], for primary side W1 or
Power [P615], for secondary side W2 or
Power [P625], for tertiary side W3.
Here, it is that winding side relating to the zero power monitoring, which is
assigned to the applied current measurement input by parameter
Assignment [P668], for current measurement input CT1 or
Assignment [P674], for current measurement input CT2 or
Assignment [P684], for current measurement input CT-GND1.
The parameters Power [P605], Power [P615] and Power [P625] are
located in submenu: SYSTEM\Nominals\Reference values.
NOTE: The reset limit is to be set as a percentage of the nominal value of the
measurement quantity Power (according to users input either as active
power, reactive power or apparent power). The nominal value of this
measurement quantity is to be set by parameter:
Power [P605], for primary side W1 or
Power [P615], for secondary side W2 or
Power [P625], for tertiary side W3.
Here, it is that winding side relating to the zero power monitoring, which is
assigned to the applied current measurement input by parameter
Assignment [P668], for current measurement input CT1 or
Assignment [P674], for current measurement input CT2 or
Assignment [P684], for current measurement input CT-GND1.
The parameters Power [P605], Power [P615] and Power [P625] are
located in submenu: SYSTEM\Nominals\Reference values.
P0 eff/Pn
[P2977] Mode = P0>
[P2978] Limit
10%
t
[E2284]
ANSI32N/G-1 pick-
up
1
0
t
[P2979]
Delay time
[P2982]
Reset delay time pick-up
t
[E2285]
ANSI32N/G-1
trip
1
0
t
[P2981]
Reset delay time trip
Figure 3-121 Zero power protection Tripping and reset characteristic: over-run of P0>
P0 eff/Pn
[P2977] Mode = P0<
30%
[P2978] Limit
t
[E2284]
ANSI32N/G-1 pick-
up
1
0
t
[P2979]
Delay time
t
[P2982]
Reset delay time pick-up
[E2285] t
ANSI32N/G-1
trip
1
0
t
[P2981]
Reset delay time trip
Figure 3-122 Zero power protection Tripping and reset characteristic: under-run of P0<
Main Menu\Parameters\PROTECTION\
ANSI 37 Undercurrent
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
SET PARAMETERS
The following SET PARAMETERS of the undercurrent protection exist only once in each of the
four parameter sets. Thus, the SET PARAMETERS apply to all of the 3 protection STEPS of
one parameter SET.
For settings CT1 or CT2, event ANSI37-1 step acitve [E2459] is activated.
P3563 Limit
Pick-up value of the first undercurrent protection element (STEP1); at the moment that
the characteristic quantity (phase current) falls below this limit in one of the three
phases, ANSI37-1 pick-up [E2461] will become active, and Delay time of the first
undercurrent protection element will start.
In case that the characteristic quantity (phase current) exceeds Limit of the first
undercurrent protection element in all three phases before Delay time has run down,
the timer of Delay time will be stopped and the attained time value is being safed.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
characteristic quantity (phase current). The nominal value of the characteristic
quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P614] are
located in submenu: SYSTEM\Nominals\Reference values.
NOTE: The Reset Limit is to be set as a percentage of the nominal value of the
characteristic quantity (phase current). The nominal value of the characteristic
quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P614] are
located in submenu: SYSTEM\Nominals\Reference values.
Ieff/In
100%
[P3563] Limit
t
[E2461]
ANSI37-1 pickup
0
t
[P3564]
Delay time
t
[P3567]
Reset delay time pickup
t
[E2462]
ANSI 37-1 trip
0
t
[P3566]
Reset delay time trip
Figure 3-124 Undercurrent protection Trip characteristic (DT) and Reset characteristic (DT)
STD
DP1
DP2
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
For settings CT1 or CT2, event ANSI46-1 step active [E2248] is activated.
P2892 Reference
The reference parameter sets the characteristic quantity for the NPS current protection
module; calculation the settings of parameters Limit and Reset limit of the NPS
current protection ANSI 46 can be assigned by the following setting options either:
I2/In: where I2 is negative phase sequence current component (NPS) of actual
measure current value and In is nominal current or
I2/I1: where I2 is negative phase sequence current component (NPS) of actual
measure current value and I1 is positive phase sequence current component
of actual measured current value
There are up to 7 different inverse time characteristics (IDMT) available, which accords
to the US standard of the American National Standard Institute ANSI or the
international standard of International Electrotechnical Commission IEC:
Definite: definite time (DT)
ANSI NINV: Normal Inverse (ANSI);
ANSI VINV: Very Inverse (ANSI);
ANSI EINV: Extremely Inverse (ANSI);
IEC NINV: Normal Inverse (IEC);
IEC VINV: Very Inverse (IEC);
IEC LINV: Long-term Inverse (IEC);
IEC EINV: Extremely Inverse (IEC)
tr
k t r (G ) TMS
t (G ) TMS c
Designating
1 G
G
1
G
S
S
G
k c tr
[s] [s] - [s] -
C 80 0 2 80 2 Extremely invers
whereby:
t(G): theoretical operate time with constant value of G (seconds)
tr(G): time setting (reset time for G=0 and TMS = 1)
k, c, : constant values which define the chosen curve shape
TMS: Time Multiplier Setting
G: measured value of the characteristic quantity
GS: setting value (start) of the characteristic quantity
For motor protection applications there are the following four thermal curves available
which represents different kinds of thermal characteritics:
Therm Flat
IT
I2T
I4T
5* k 5 * 3
t (G ) TMS t r (G ) TMS
Designating
G G
Gn Gn
1 2 0 2 0 Therm Flat
3 1 1 2 0 IT
3 2 2 2 0 I2 T
3 4 4 2 0 I4 T
whereby:
t(G): theoretical operate time with constant value of G (seconds)
tr(G): time setting (reset time for G=0 and TMS = 1)
k, , : constant values which define the chosen curve shape
TMS: Time Multiplier Setting
G: measured value of the characteristic quantity
Gn: nominal value (start) of the characteristic quantity
P2894 Limit
Pick-up value of the first NPS current protection element (STEP1); at the moment that
the characteristic quantity (inverse component of current) exceeds this limit the ANSI46-
1 pick-up [E2250] will become active, and Delay time/TMS of the first NPS current
protection element will start.
In case that the characteristic quantity (inverse component of current) falls below Limit
of the first NPS current protection element before Delay time/TMS has run down, the
timer of Delay time/TMS will be stopped and the attained time value is being saved.
The parameters Current [P604], Current [P614] and Current [P614] are
located in submenu: SYSTEM\Nominals\Reference values.
If pick-up event ANSI46-1 pick-up [E2250] is active and Delay Time/TMS run down,
trip event ANSI46-1 trip [E2251] will be activated. This event can be used for alarm or
output control purposes.
I/In
There are up to 7 different inverse time characteristics available, which accords to the
US standard of the American National Standard Institute ANSI or the international
standard of International Electrotechnical Commission IEC:
Definite: definite time (DT)
ANSI NINV: Normal Inverse (ANSI);
ANSI VINV: Very Inverse (ANSI);
ANSI EINV: Extremely Inverse (ANSI);
IEC NINV: Normal Inverse (IEC);
IEC VINV: Very Inverse (IEC);
IEC LINV: Long-term Inverse (IEC);
IEC EINV: Extremely Inverse (IEC)
NOTE: If the tripping characteristic of Delay time/TMS is set to Definite (DT), then
parameter Reset curve [P2897] only provides setting option Definite (DT).
If the tripping characteristic of Delay time/TMS is set to xxx INV (IDMT)or
themal curve, then parameter Reset curve [P2897] provides both, setting
option Definite (DT) or setting option xxx INV (IDMT) or themal curve.
For motor protection applications there are the following four thermal reset curves
available which represents different kinds of thermal characteritics:
Therm Flat
IT
I2T
I4T
As a result, processing of the stored counter value of the tripping delay time takes on a
different working principle, depending on the reset characteristic of Delay time/TMS
(DT or IDMT) to be set by parameter Reset curve [P2897]:
DT: the stored counter value is to be processed according to
the settings of Reset delay time pick-up
IDMT or thermal curves: the stored counter value is to be processed according to
the settings of Reset delay time trip/TMS
NOTE: If the reset curve of the first protection element (STEP1) is assigned a definite
time (DT) characteristic (parameter Reset curve [P2897] = Definite), and
the trip event ANSI46-1 trip [E2251] should immediately be reset, then set
parameter Reset Delay time trip/TMS [P2900] = 0.
The parameters Current [P604], Current [P614] and Current [P624] are
located in submenu: SYSTEM\Nominals\Reference values
If trip event ANSI46-1 trip [E2251] is activated and Reset delay time trip/TMS has run
down, the trip event ANSI46-1 trip [E2251] will be deactivated.
NOTE: In dependence of the set value of parameter Reset after TRIP immediately
[P2900], deactivating of trip event ANSI46-1 trip [E2251] takes on a different
working principle.
While the timer of the Reset delay time pick-up is running, the counter value of the
tripping delay time maintains at a constant level.
After the Reset delay time pick-up has run down, the counter value of the tripping delay
time (Delay time/TMS) will be reset.
NOTE: If the parameter Reference[P2892] is set to I2/In the min. start limit is set as
percentage of the nominal values of the characteristic quantity (phase current)
regarding with nominal current. The nominal value of the characteristic
quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P624] are located in
submenu: SYSTEM\Nominals\Reference values
The following dynamic STEP parameters of the negative phase sequence current protection
exist only once in each of the 4 independent protection STEPS. Thus, the dynamic STEP
parameters apply only to one of the 4 protection STEPS of one parameter SET
P3275 Limit
See description of parameter [P2894]
P3299 Limit
See description of parameter [P2894]
INPS/I
[P2894] Limit
10%
t
[E2250]
ANSI46-1 pick-up
1
0
t
[P2895]
Delay time/TMS
t
[P2901]
Reset delay time pick-up
t
[E2251]
ANSI 46-1 trip
0
t
[P2900]
Reset delay time trip/TMS
Figure 3-130 NPS current protection Trip characteristic (DT) and Reset characteristic (DT)
INPS/I
[P2894] Limit
10%
t
[E2250]
ANSI46-1 pick-up
1
0
t
(current dependent
delay time Ttrip)
t
[P2901]
Reset delay time pick-up
t
[E2251]
ANSI 46-1 trip
0
t
[P2900]
Reset delay time trip/TMS
Figure 3-131 NPS current protection Trip characteristic (IDMT) and Reset characteristic (DT)
INPS/I
[P2894] Limit
[P2899]Reset limit
10%
t
[E2250]
ANSI46-1 pick-up
0
t
(current dependent
delay time Ttrip)
t
[E2251]
ANSI 46-1 trip
1
0
t
(current dependent
delay time Ttrip)
t
[E2251]
ANSI 46-1 trip
1
0
t
Figure 3-132 NPS current protection Trip characteristic (IDMT) and Reset characteristic (IDMT)
Main Menu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
SET PARAMETERS
The following SET PARAMETERS of the negative phase sequence voltage protection exist only
once in each of the four parameter sets. Thus, the SET PARAMETERS apply to all of the 12
protection STEPS of one parameter SET.
For settings PT1, PT2 or PT3, event ANSI47-1 step acitve [E2499] is activated.
P3678 Limit
Pick-up value of the first negative phase sequence voltage protection element. At the
moment that the characteristic quantity (negative phase sequence voltage U2 of the 3-
phase voltage system) exceeds this limit, pick-up event ANSI47-1 pickup [E2501] will
become active, and the trip delay time (Delay time) of the first overvoltage protection
element will start.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
process quantity Phase-to-Ground voltage UL-E (UL-E = UL-L/3). The nominal
value of the phase-to-phase voltage UL-L is to be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2 or
Voltage (L-L) [P623], for tertiary side W3.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
NOTE: The reset limit is to be set as a percentage of the nominal value of the process
quantity Phase-to-Ground voltage UL-E (UL-E = UL-L/3). The nominal value of
the phase-to-phase voltage UL-L is to be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2 or
Voltage (L-L) [P623], for tertiary side W3.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
U2/Un
[P3678] Limit
15%
t
[E2501]
ANSI47-1 pick-up
1
0
t
[P3679]
Delay time
[P3682]
Reset delay time pick-up
t
[E2502]
ANSI 47-1 trip
0
t
[P3681]
Reset delay time trip
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
SET PARAMETERS
The following SET PARAMETERS of the Thermal replica exist only once in each of the four
parameter sets. Thus, the SET PARAMETERS apply to all of the 4 protection STEPS of one
parameter SET.
Ithermal,max. = IB x k
with:
IB: Basic current: percentage of nominal current In of the operating device to be protected
k: Basic current factor: overload factor as multiplier for basic current
NOTE: The basic current is to be set as a percentage of the nominal value of the
characteristic quantity (phase current). The nominal value of the characteristic
quantity is to be set by parameter:
Current [P604], for primary side W1 or
The parameters Current [P604], Current [P614] and Current [P614] are
located in submenu: SYSTEM\Nominals\Reference values.
The parameters Current [P604], Current [P614] and Current [P614] are
located in submenu: SYSTEM\Nominals\Reference values.
If there is no datasheet of the operating device available, the cooling time constant
usually should be twice or three times as much as the set value for the heating time
constant.
[P3403]
Current heating treshold
1,2
1,1
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
t
Normalised time (multiples of heating time constant)
t
Equipement switched on Equipement switched off
STD
DP1
DP2
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
For settings CT1 or CT2, event ANSI50/51-1 step acitve [E1422] is activated.
The first step of overcurrent protection can be blocked by any active event. For blocking,
the number related to this blocking event has to be assigned to parameter [P1626].
Blocking is only effective, however, as long as the blocking event is active. As soon as
blocking is active, event ANSI50/51-1 blocked step [E1423] is activated. If the blocking
event turns inactive, blocking is abandoned and protective function is effective again.
Then, event [E1423] is deactivated automatically.
If blocking of the first step of overcurrent protection is not required, set this parameter to
0.
There are up to 7 different inverse time characteristics (IDMT) available, which accords
to the US standard of the American National Standard Institute ANSI or the
international standard of International Electrotechnical Commission IEC:
tr
k t r (G ) TMS
t (G ) TMS c
Designating
1 G
G
1
G
S
GS
k c tr
[s] [s] - [s] -
C 80 0 2 80 2 Extremely invers
whereby:
t(G): theoretical operate timewith constant value of G (seconds)
tr(G): time setting (reset time for G=0 and TMS = 1)
k, c, : constant values which define the chosen curve shape
TMS: Time Multiplier Setting
G: measured value of the characteristic quantity
GS: setting value (start) of the characteristic quantity
P1628 Limit
Pick-up value of the first overcurrent protection element (STEP1); at the moment that the
characteristic quantity (phase current) exceeds this limit, ANSI50/51-1 pick-up [E1424]
will become active, and Delay time/TMS of the first overcurrent protection element will
start.
In case that the characteristic quantity (phase current) falls below Limit of the first
overcurrent protection element before Delay time/TMS has run down, the timer of
Delay time/TMS will be stopped and the attained time value is being safed.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
characteristic quantity (phase current). The nominal value of the characteristic
quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P614] are
located in submenu: SYSTEM\Nominals\Reference values.
If pick-up event ANSI50/51-1 pick-up [E1424] is active and Delay Time/TMS run
down, trip event ANSI50/51-1 trip [E1425] will be activated. This event can be used for
alarm or output control purposes.
NOTE: The Reset Limit is to be set as a percentage of the nominal value of the
characteristic quantity (phase current). The nominal value of the characteristic
quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2 or
The parameters Current [P604], Current [P614] and Current [P614] are
located in submenu: SYSTEM\Nominals\Reference values.
There are up to 7 different inverse time characteristics available, which accords to the
US standard of the American National Standard Institute ANSI or the international
standard of International Electrotechnical Commission IEC:
Definite: definite time (DT)
ANSI NINV: Normal Inverse (ANSI);
ANSI VINV: Very Inverse (ANSI);
ANSI EINV: Extremely Inverse (ANSI);
IEC NINV: Normal Inverse (IEC);
IEC VINV: Very Inverse (IEC);
IEC LINV: Long-term Inverse (IEC);
IEC EINV: Extremely Inverse (IEC)
NOTE: If the tripping characteristic of Delay time/TMS is set to Definite (DT), then
parameter Reset curve [P1630] only provides setting option Definite (DT).
If the tripping characteristic of Delay time/TMS is set to xxx INV (IDMT),
then parameter Reset curve [P1630] provides both, setting option Definite
(DT) or setting option xxx INV (IDMT).
As a result, processing of the stored counter value of the tripping delay time takes on a
different working principle, depending on the reset characteristic of Delay time/TMS
(DT or IDMT) to be set set by parameter Reset curve [P1630]:
DT: the stored counter value is to be processed according to the settings of
Reset delay time pick-up
IDMT: the stored counter value is to be processed according to the settings of
Reset delay time trip/TMS
While the timer of the Reset delay time pick-up is running, the counter value of the
tripping delay time maintains at a constant level.
After the Reset delay time pick-up has run down, the counter value of the tripping delay
time (Delay time/TMS) will be reset.
meaning, depending on the reset characteristic of Reset curve (DT or IDMT) set by
parameter Reset curve [P1630]:
DT reset characteristic: Reset curve [P1630] = Definite
The delay time to reset the trip event is equal to a constant time value, to be set by
parameter Reset delay time/TMS [P1633].
IDMT reset characteristic: e.g. Reset curve [P1630] = ANSI NINV
The delay time to reset the trip event is not a constant time value, but, depending on
the inverse curve shape and the measured value of the characteristic quantity
(phase current) it will be cyclically re-calculated. When applying any inverse curve
(IDMT) to the reset curve, this means the setting of parameter Reset delay time
trip/TMS [P1633] takes on a displacement of the inverse curve shape with regard to
the time axis (TMS: Time Multiplier Setting).
If trip event ANSI50/51-1 trip [E1425] is activated and Reset delay time trip/TMS has
run down, the trip event ANSI50/51-1 trip [E1425] will be deactivated.
NOTE: In dependence of the set value of parameter Reset after TRIP immediately
[P1631], deactivating of trip event ANSI50/51-1 trip [E1425] takes on a
different working principle.
NOTE: If the reset curve of the first protection element (STEP1) is assigned a definite
time (DT) characteristic (parameter Reset curve [P1630] = Definite), and
the trip event ANSI50/51-1 trip [E1425] should immediately be reset, then set
parameter Reset Delay time/TMS [P1633] = 0.
I/In
The following dynamic STEP parameters of the overcurrent protection exist only once in each of
the 6 independent protection STEPS. Thus, the dynamic STEP parameters apply only to one of
the 6 protection STEPS of one parameter SET
P3035 Limit
See description of parameter [P1628]
P3071 Limit
See description of parameter [P1628]
Ieff/In
[P1628] Limit
100%
t
[E1424]
ANSI50/51-1 pick-up
1
0
t
[P1629]
Delay time/TMS
t
[P1634]
Reset delay time pick-up
t
[E1425]
ANSI 50/51-1 trip
0
t
[P1633]
Reset delay time trip/TMS
Figure 3-142 Overcurrent protection Trip characteristic (DT) and Reset characteristic (DT)
Ieff/In
[P1628] Limit
100%
t
[E1424]
ANSI50/51-1 pick-up
1
0
t
(current dependent
delay time Ttrip)
t
[P1634]
Reset delay time pick-up
t
[E1425]
ANSI 50/51-1 trip
0
t
[P1633]
Reset delay time trip/TMS
Figure 3-143 Overcurrent protection Trip characteristic (IDMT) and Reset characteristic (DT)
Ieff/In
Limit: [P1628]
100%
t
[E14240]
ANSI50/51-1 pick-up
0
t
(current dependent
delay time Ttrip)
t
[E1425]
ANSI 50/51-1 trip
1
0
t
(current dependent
delay time Ttrip)
t
[E1425]
ANSI 50/51-1 trip
1
0
t
Figure 3-144 Overcurrent protection Trip characteristic (IDMT) and Reset characteristic (IDMT)
Main Menu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
SET PARAMETERS
The following SET PARAMETERS of the breaker failure protection exist only once in each of
the four parameter sets. Thus, the SET PARAMETERS apply to all of the 3 protection STEPS of
one parameter SET.
For settings CT1 or CT2, event ANSI50BF-1 step acitve [E2217] is activated.
P2840 Trigger
The first step of breaker failure protection can be activated (triggered) by any active
event. To activate, the number related to this trigger event has to be assigned to
parameter [P2840].
NOTE: Usually, those trIp-events of the current protection functions are used for the
trigger event. The trips events can be combined by a logical function of
function PLC. If so, output event of the logical function can be assigned to
parameter Trigger [P2840].
External tripping signals which are to be processed by binary inputs, for
instance, the events of the binary inputs are to be used as trigger-events.
If activating of the first step of breaker failure protection is not required, set this
parameter to 0.
P2841 Limit
Pick-up value of the first breaker failure protection element (STEP1); at the moment that
the characteristic quantity (phase current) exceeds this limit and the trigger-event
assigned to parameter Trigger [2840] is active, then ANSI50BF-1 pick-up [E2219] will
become active, and Delay time of the first breaker failure protection element will start.
In case that the characteristic quantity (phase current) falls below Limit of the first
overcurrent protection element before Delay time/TMS has run down, the timer of
Delay time/TMS will be stopped and the attained time value is being safed.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
characteristic quantity (phase current). The nominal value of the characteristic
quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P614] are
located in submenu: SYSTEM\Nominals\Reference values.
NOTE: The Reset Limit is to be set as a percentage of the nominal value of the
characteristic quantity (phase current). The nominal value of the characteristic
quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P614] are
located in submenu: SYSTEM\Nominals\Reference values.
While the timer of the Reset delay time pick-up is running, the counter value of the
tripping delay time maintains at a constant level.
After the Reset delay time pick-up has run down, the counter value of the tripping delay
time (Delay time/TMS) will be reset.
Ieff/In
100%
[P2841] Limit
t
[E1425] For instance:
ANSI 50/51-1 trip Protection trip by 1. step of
ANSI 50/51
1
0
t
[P2840] Trigger
0
t
[E2219]
ANSI50BF-1 pick-up
1
0
t
t
[P2845]
Reset delay time pick-up
t
[E2220]
ANSI 50BF-1 trip
0
t
[P2844]
Reset delay time trip
STD
DP1
DP2
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
For settings CT1 or CT2, event ANSI50G/51G-1 step acitve [E1687] is activated.
There are up to 7 different inverse time characteristics (IDMT) available, which accords
to the US standard of the American National Standard Institute ANSI or the
international standard of International Electrotechnical Commission IEC:
Definite: definite time (DT)
ANSI NINV: Normal Inverse, (ANSI)
ANSI VINV: Very Inverse (ANSI)
ANSI EINV: Extremely Inverse (ANSI)
IEC NINV: Normal Inverse, (IEC)
IEC VINV: Very Inverse (IEC)
IEC LINV: Long-term Inverse (IEC)
IEC EINV: Extremely Inverse (IEC)
tr
k t r (G ) TMS
t (G ) TMS c
Designating
1 G
G
1
G
S
GS
k c tr
[s] [s] - [s] -
C 80 0 2 80 2 Extremely invers
whereby:
t(G): theoretical operate timewith constant value of G (seconds)
tr(G): time setting (reset time for G=0 and TMS = 1)
k, c, : constant values which define the chosen curve shape
TMS: Time Multiplier Setting
G: measured value of the characteristic quantity
GS: setting value (start) of the characteristic quantity
P2038 Limit
Pick-up value of the first ground overcurrent protection element (STEP1); at the moment
that the characteristic quantity (ground current) exceeds this limit, ANSI50G/51G-1 pick-
up [E1689] will become active, and Delay time/TMS of the first ground overcurrent
protection element will start.
In case that the characteristic quantity (ground current) falls below Limit of the first
ground overcurrent protection element before Delay time/TMS has run down, the timer
of Delay time/TMS will be stopped and the attained time value is being safed.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
characteristic quantity (ground current IG). The nominal value of the
characteristic quantity is to be set by parameter:
Ground current [P607], for primary side W1 or
Ground current [P617], for secondary side W2 or
Ground current [P627], for tertiary side W3.
If pick-up event ANSI50G/51G-1 pick-up [E1689] is active and Delay Time/TMS run
down, trip event ANSI50G/51G-1 trip [E1690] will be activated. This event can be used
for alarm or output control purposes.
NOTE: The Reset limit is to be set as a percentage of the nominal value of the
characteristic quantity (ground current IG). The nominal value of the
characteristic quantity is to be set by parameter:
Ground current [P607], for primary side W1 or
Ground current [P617], for secondary side W2 or
Ground current [P627], for tertiary side W3.
The parameters Ground current [P607], Ground current [P617] and Ground
current [P627] are located in submenu: SYSTEM\Nominals\Reference
values.
There are up to 7 different inverse time characteristics available, which accords to the
US standard of the American National Standard Institute ANSI or the international
standard of International Electrotechnical Commission IEC:
Definite: definite time (DT)
ANSI NINV: Normal Inverse, (ANSI)
ANSI VINV: Very Inverse (ANSI)
ANSI EINV: Extremely Inverse (ANSI)
IEC NINV: Normal Inverse, (IEC)
IEC VINV: Very Inverse (IEC)
IEC LINV: Long-term Inverse (IEC)
IEC EINV: Extremely Inverse (IEC)
NOTE: If the tripping characteristic of Delay time/TMS is set to Definite (DT), then
parameter Reset curve [P2040] only provides setting option Definite (DT).
If the tripping characteristic of Delay time/TMS is set to xxx INV (IDMT),
then parameter Reset curve [P2040] provides both, setting option Definite
(DT) or setting option xxx INV (IDMT).
While the timer of the Reset delay time pick-up is running, the counter value of the
tripping delay time maintains at a constant level.
After the Reset delay time pick-up has run down, the counter value of the tripping delay
time (Delay time/TMS) will be reset.
(ground current) it will be cyclically re-calculated. When applying any inverse curve
(IDMT) to the reset curve, this means the setting of parameter Reset delay time
trip/TMS [P2043] takes on a displacement of the inverse curve shape with regard to
the time axis (TMS: Time Multiplier Setting).
If trip event ANSI50G/51G-1 trip [E1690] is activated and Reset delay time trip/TMS
has run down, the trip event ANSI50G/51G-1 trip [E1690] will be deactivated.
NOTE: In dependence of the set value of parameter Reset after TRIP immediately
[P2041], deactivating of trip event ANSI50G/51G-1 trip [E1690] takes on a
different working principle.
NOTE: If the reset curve of the first protection element (STEP1) is assigned a definite
time (DT) characteristic (parameter Reset curve [P2040] = Definite), and
the trip event ANSI50G/51G-1 trip [E1690] should immediately be reset, then
set parameter Reset Delay time/TMS [P2043] = 0.
I/In
The following dynamic STEP parameters of the ground overcurrent protection exist only once in
each of the 6 independent protection STEPS. Thus, the dynamic STEP parameters apply only
to one of the 6 protection STEPS of one parameter SET
P3107 Limit
See description of parameter [P2038]
P3143 Limit
See description of parameter [P2038]
IGND eff/In
[P2038] Limit
t
[E1689]
ANSI50G/51G-1 pick-up
1
0
t
[P2039]
Delay time/TMS
t
[P2044]
Reset delay time pick-up
t
[E1690]
ANSI 50G/51G-1 trip
0
t
[P2043]
Reset delay time trip/TMS
Figure 3-152 Ground overcurrent prot. Trip characteristic (DT) and Reset characteristic (DT)
IGND eff/In
[P2038] Limit
t
[E1690]
ANSI50G/51G-1 pick-up
1
0
t
(current dependent
delay time Ttrip)
t
[P2044]
Reset delay time pick-up
t
[E1690]
ANSI 50G/51G-1 trip
0
t
[P2043]
Reset delay time trip/TMS
Figure 3-153 Ground overcurrent prot. Trip characteristic (IDMT) and Reset characteristic (DT)
IGND eff/In
Limit: [P2038]
t
[E1689]
ANSI50G/51G-1 pick-up
0
t
(current dependent
delay time Ttrip)
t
[E1690]
ANSI 50G/51G-1 trip
1
0
t
(current dependent
delay time Ttrip)
t
[E1690]
ANSI 50G/51G-1 trip
1
0
t
Figure 3-154 Ground overcurrent prot. Trip characteristic (IDMT) and Reset characteristic (IDMT)
Main Menu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides only one protection STEP and, as
consequence, only one group of parameters. Thus, SET PARAMETERS of SET 1
represented below are described in the following in detail as examples.
P2875 Function
This parameter enables/disables voltage restraint overcurrent protection where:
OFF: disables or
ON: enables the protective function.
Setting the voltage restraint curve for calculating the multiplier for adaption of pick-up value
Limit and the Reset limit of activated protection steps of ANSI 50/51 and/or ANSI46
Each protective element of overcurrent protection ANSI 50/51 and negative phase sequence
current protection (NPS) ANSI46 provides an additional parameter Voltage restrained [Pxxxx]
for activating the voltage restrained adaption of the pick-up value Limit and the Reset limit.
These limits are to be multiplied by a calculated factor (Multiplier).
The multiplier is proportional to the voltage ratio U/Un. The curve for calculating the multiplier is
to be set by the following four parameters.
Multiplier
[P2881] Multiplier 2
[P2879] Multiplier 1
Figure 3-156 ANSI 51/46VR Voltage-dependent curve for calculation of the multiplier
P2878 Limit 1
Start value of the voltage ratio U/Un to define the voltage stabilising curve; together with
parameter Mulitplier 1 [P2879] the set value of parameter [P2878] determines the
beginning of the voltage-stabilized curve.
P2879 Multiplier 1
Start value of the multiplier to define the voltage stabilising curve; together with
parameter Limit 1 [P2878] the set value of parameter [P2879] determines the
beginning of the voltage-stabilized curve,
P2880 Limit 2
Maximum value of the voltage ratio U/Un to define the voltage stabilising curve; together
with parameter Mulitplier 2 [P2881] the set value of parameter [P2880] determines the
end of the voltage-stabilized curve, and as consequence, the maximum adaption of the
pick-up value Limit and the Reset limit.
P2881 Multiplier 2
Maximum value of the voltage ratio U/Un to define the voltage stabilising curve; together
with parameter Limit 2 [P2880] the set value of parameter [P2881] determines the end
of the voltage-stabilized curve, and as consequence, the maximum adaption of the pick-
up value Limit and the Reset limit.
If:
function Blocking protection is activated and
the voltage ratio U/Un exceeds the set value of parameter Limit 2 [P2880],
all the voltage restrained overcurrent protection steps (Voltage restrained [Pxxxx] =
ON) of function Overcurrent protection ANSI 50/51 automatically will be blocked.
Main Menu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
SET PARAMETERS
The following SET PARAMETERS of the pole discordance protection exist only once in each of
the four parameter sets. Thus, the SET PARAMETERS apply to all of the 3 protection STEPS of
one parameter SET.
When pole discordance protection ANSI 52 is enabled by parameter [P3718], then event
ANSI52 module active [E2523] is activated.
P3720 Function
This parameter enables/disables the first step of pole discordance protection, activation
of the protection step takes place by selecting the protection criterion (characteristic
quantity) for detection of the individual pole positions of the switching element primary
contacts) where selection option:
OFF: disables the protective function, or
Auxiliary contacts: enables the protective function => protective criterion:
detection of switching elements pole position via evaluation of
switching elements auxiliary contacts, or
CT1: enables the protective function => protective criterion:
detection of switching elements pole position via phase-
seggregated current check of phase currents measured by
CT1, or
CT2: enables the protective function => protective criterion:
detection of switching elements pole position via phase-
seggregated current check of phase currents measured by
CT2, or
When all three pole position feedbacks (phase L1, L2, and/or L3) indicate position Open
before the trip delay time (Delay time) has run down, the timer of Delay time will be stopped
and reset to zero, and the pick-up event [E2527] will be deactivated.
P3722 Open L1
Detection criterion for monitoring switching elements pole position Open of phase L1
P3723 Open L2
(analog to description of parameter [P3722], relating to phase L2)
P3724 Open L3
(analog to description of parameter [P3722], relating to phase L3)
P3725 Closed L1
Detection criterion for monitoring switching elements pole position Closed of phase L1
P3726 Closed L2
(analog to description of parameter [P3725], relating to phase L2)
P3727 Closed L3
(analog to description of parameter [P3725], relating to phase L3)
(Feedback: L1 Closed")
IL1
(Feedback: L2 Closed")
IL2 &
(Feedback: L3 Closed")
IL3
(Feedback: L1 Closed")
IL1
IL2 (Feedback: L2 Closed")
&
(Feedback: L3 Closed")
IL3
(Feedback: L1 Closed")
IL1
IL2 (Feedback: L2 Closed")
&
(Feedback: L3 Closed")
IL3
(Feedback: L1 Closed")
IL1
(Feedback: L2 Closed")
IL2 &
(Feedback: L3 Closed")
IL3
ANSI52-1 pickup [E3723]
1
(Feedback: L1 Open")
IL1
IL2 (Feedback: L2 Open")
&
(Feedback: L3 Open")
IL3
(Feedback: L1 Open")
IL1
(Feedback: L2 Open")
IL2 &
(Feedback: L3 Open")
IL3
Check Position Closed (I>)
(Feedback: L1 Open")
IL1
(Feedback: L2 Open")
IL2 &
(Feedback: L3 Open")
IL3
(Feedback: L1 Open")
IL1
IL2 (Feedback: L2 Open")
&
(Feedback: L3 Open")
IL3
(Feedback: L1 Open")
IL1
(Feedback: L2 Open")
IL2 &
(Feedback: L3 Open")
IL3
(Feedback: L1 Open")
IL1
(Feedback: L2 Open")
IL2 &
(Feedback: L3 Open")
IL3
event ANSI52-1 pickup [P2527] is activated and the trip delay time (Delay time) of the
first pole discordance protection element will start.
In case that the process quantity (phase current) falls below the Current limit in all
three phases before Delay time has run down, the timer of Delay time will be stopped
and reset to zero, and the pick-up event [E2527] will be deactivated.
Measuring and protection of AC voltage systems as floating 10min arithmetic mean protection
(ANSI 59AV)
When overvoltage protection is used for 10min arithmetic mean protection of decentralized
power generation systems in grid parallel operation, one of the SYMAP-Compact(+) voltage
measurement inputs PT1, PT2 or PT3 has to be configured accordingly via parameter Source
of Uavg 10min [P9463] of submenu: SYSTEM\Measuring\Floating voltage.
For those protection steps of overvoltage protection which shall operated as 10min arithmetic
mean protection the folowing parameter setting shall apply: Pickup source [12xx] = Uavg
10min.
Main Menu\Parameters\PROTECTION\
ANSI 59 Overvoltage
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
SET PARAMETERS
The following SET PARAMETERS of the overvoltage protection exist only once in each of the
four parameter sets. Thus, the SET PARAMETERS apply to all of the 12 protection STEPS of
one parameter SET.
Overvoltage protection can be completely blocked by any active event. For blocking, the
number related to this blocking event has to be assigned to parameter [P1201]. Blocking
is only effective, however, as long as the blocking event is active. As soon as blocking is
active, event ANSI59 blocked module [E1151] is activated. If the blocking event turns
inactive, blocking is abandoned and protective function is effective again. Then, event
[E1151] is deactivated automatically.
If blocking of the overvoltage protection is not required, set this parameter to 0.
For settings PT1, PT2, PT3 or Uavg 10min, event ANSI59-1 step acitve [E1154]
is activated.
P1207 Limit
Pick-up value of the first overvoltage protection element. At the moment that the
characteristic quantity (voltage) exceeds this limit, pick-up event ANSI59-1 pickup
[E1156] will become active, and the trip delay time (Delay time) of the first overvoltage
protection element will start.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
chosen characteristic quantity (phase-to-phase voltage or phase-to-neutral
voltage) by parameter Voltage reference [P1212]. However, the chosen
characteristic value refers to the nominal value of the phase-to-phase voltage
to be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2 or
Voltage (L-L) [P623], for tertiary side W3.
Hence, in case that the calculation of the pick-up value refers to the phase-to-
neutral voltage, parameter Voltage reference [P1212] is to be set to L-N, so
that factor 3 is not necessary to be considered for calculation.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
NOTE: The reset limit is to be set as a percentage of the nominal value of the chosen
characteristic quantity (phase-to-phase voltage or phase-to-neutral voltage) by
parameter Voltage reference [P1212]. However, the chosen characteristic
value refers to the nominal value of the phase-to-phase voltage to be set by
parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2 or
Voltage (L-L) [P623], for tertiary side W3.
Hence, in case that the calculation of the pick-up value refers to the phase-to-
neutral voltage, parameter Voltage reference [P1212] is to be set to L-N, so
that factor 3 is not necessary to be considered for calculation.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
If the trip reset delay time (Reset delay time trip) has run down, trip event ANSI59-1
trip [E1157] is deactivated. In case that the characteristic quantity (voltage) exceeds the
pick-up value (Limit) of the first overvoltage protection element before the timer of
Reset delay time trip has run down, the timer of Reset delay time trip will be reset.
Then trip event ANSI59-1 trip [E1157] remains active.
Ueff/Un
[P1207] limit
100%
t
[E1156]
ANSI59-1 pick-up
1
0
t
[P1208]
delay time
[P1211]
reset delay time
pick-up
t
[E1157]
ANSI 59-1 trip
0
t
[P1210]
reset delay time
trip
Main Menu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
SET PARAMETERS
The following SET PARAMETERS of the neutral voltage displacement protection exist only
once in each of the four parameter sets. Thus, the SET PARAMETERS apply to all of the 4
protection STEPS of one parameter SET.
For settings PT-GND1, PT1, PT2 or PT3, event ANSI59N/G-1 step acitve
[E1373] is activated.
NOTE: In case that residual voltage is to be calculated by voltage measuring via PT1,
PT2 or PT3 it is required to connect terminal N of SYMAP-Compact(+)
device (SYMAP-Compact: -X1.2:18; SYMAP-Compact+: -X1.2:26) to ground
potential!
For test purposes via voltage generator test equipment it is required to
connect terminal N of SYMAP-Compact(+) device to the neutral potential
of the voltage test equipment!
P1542 Limit
Pick-up value of the first neutral voltage displacement protection element; at the moment
that the characteristic quantity (neutral voltage) exceeds this limit, pick-up event
ANSI59N/G-1 pickup [E1375] will become active, and the trip delay time (Delay time)
of the first neutral voltage displacement protection step will start.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
characteristic quantity (residual voltage UG). The nominal value of the
characteristic quantity is to be set by parameter:
Ground voltage [P606], for primary side W1 or
Ground voltage [P616], for secondary side W2 or
Ground voltage [P626], for tertiary side W3
NOTE: The reset limit is to be set as a percentage of the nominal value of the
characteristic quantity (residual voltage UG). The nominal value of the
characteristic quantity is to be set by parameter:
Ground voltage [P606], for primary side W1 or
Ground voltage [P616], for secondary side W2 or
Ground voltage [P626], for tertiary side W3
element before the timer of Reset delay time trip has run down, the timer of Reset
delay time trip will be reset. Then trip event ANSI59N/G-1 trip [E1376] remains active.
[P1542] limit
t
[E1375]
ANSI59N/G-1 pick-up
0
t
[P1543]
delay time
[P1546]
reset delay time
pick-up
t
[E1376]
ANSI 59N/G-1 trip
0
t
[P1545]
reset delay time
trip
Figure 3-163 Neutral Voltage Displacement (NVD) Tripping and reset characteristic
This protection principle is advantageous because of the high degree of selectivity since the
CTs unambiguously define the protection range on both ends of the equipment to protect.
Consequently, fault finding can be effected in fast mode.
yn SYMAP-Compact(+)
IG
Protected CT-GNDx
zone
I = 3 x I0 = [I1 + I2 + I3 ]
CT1 or CT2
NOTE: For assigning the measuring input channels to measure IG and I see parameters:
CT-GNDx source [P9439] and
CTx source [P9440]
In the sub-menu: SYSTEM\Measuring\Differential
Main Menu\Parameters\PROTECTION\
Figure 3-165 ANSI 64REF Protection parameters [P] and events [E] of SET 1
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
SET PARAMETERS
The following SET PARAMETERS of the restricted earth fault protection (ground fault
differential protection) exist only once in each of the four parameter sets. Thus, the SET
PARAMETERS apply to protection STEP 1 and protection STEP 2 of one parameter SET.
When restricted earth fault protection ANSI 64REF is enabled by parameter [P3440],
then event ANSI64REF active [E2370] is activated.
P3441 Blocking :
Restricted earth fault differential protection can be completely blocked by any active
event. For blocking, the number related to this blocking event has to be assigned to
parameter [P3341]. Blocking is only effective, however, as long as the blocking event is
active. As soon as blocking is active, event ANSI64REF blocked [E2371] is activated. If
the blocking event turns inactive, blocking is abandoned and protective function is
effective again. Then, event [E2371] is deactivated automatically.
If blocking of the restricted earth fault protection is not required, set this parameter to 0.
P3442 Hystersis :
This parameter [P3442] determines the reset limit for the pick-up event ANSI64REF-1
pickup [E2375] of the stabilized restricted earth fault protection element (STEP1) or
ANSI64REF-2 pickup [E2381] for the unstabilized high-set restricted earth fault
protection element (STEP 2). At the moment the characteristic value (differential ground
current) falls below the reset limit, the activated pick-up event [E2375] or [E2381] will be
deactivated.
P3447 Function
This parameter activates/deactivates the stabilized restricted earth fault protection
element (STEP 1) whereby the setting:
OFF: deactivates the stabilized restricted earth fault protection element or
ON: activates the stabilized restricted earth fault protection element.
P3448 Blocking
Stabilized restricted earth fault protection element (STEP 1) can be completely blocked
by any active event. For blocking, the number related to this blocking event has to be
assigned to parameter [P3448]. Blocking is only effective, however, as long as the
blocking event is active. As soon as blocking is active, event ANSI64REF-1 blocked
[E2374] is activated. If the blocking event turns inactive, blocking is abandoned and
protective element is effective again. Then, event [E2374] is deactivated automatically.
If blocking of the stabilized restricted earth fault protection element (STEP 1) is not
required, set this parameter to 0.
Range 1: constant tripping value (gradient factor = 0) up to a settable value for the
stabilization current (see parameters Is0 [P3449]; Id0 [P3452])
Range 2: stabilized tripping characteristic with 1st gradient factor (see parameters Is1
[P3450]; Id1 [P3453])
Range 3: stabilized tripping characteristic with 2nd gradient factor (see parameters Is2
[P3451]; Id2 [P3454])
Id eff/In
Tripping range
Id>>
Id2"
Id1"
Blocking range
Id0"
(IS res")
NOTE: Parameters [P3449] to [P3454] are to be set as a percentage of the nominal value of
the characteristic quantity (ground current). The nominal value of the characteristic
quantity is to be set by parameter:
Ground Current [P607], for primary side W1 or
Ground Current [P617], for secondary side W2 or
Ground Current [P627], for tertiary side W3.
The parameters Ground Current [P607], Ground Current [P617] and Ground
Current [P627] are located in submenu: SYSTEM\Nominals\Reference values.
P3449 Is0
In combination with parameter Id0 [P3452] parameter [P3449] defines the first straight
line segment (as well as the starting point of the second straight line segement) of the
tripping curve of the stabilized restricted earth fault protection. The first straight line
segment is valid for a value range of the stabilisation current between Istab = 0 and Istab =
Is0, in which the tripping characteristic corresponds to the constant pick-up value of the
characteristic quantity (differential ground current Id) Id0.
P3450 Is1
In combination with parameter Id1 [P3453] parameter [P3450] defines the second
straight line segment (as well as the starting point of the third straight line segement) of
the tripping curve of the stabilized restricted earth fault. The second straight line
segment is valid for a value range of the stabilisation current between Istab = Is0 and
Istab = Is1.
P3451 Is2
In combination with parameter Id2 [P3454] parameter [P3451] defines the second point
to determine the slope of the third straight line segment of the tripping curve of the
stabilized restricted earth fault. An ending point of the third straight line segment can be
set by using parameter Id>> [P3462] which brings forth a corresponding stabilisation
current (IS res). Then, the third straight line segment is valid for a value range of the
stabilisation current between Istab = Is1 and Istab = IS res.
P3452 Id0
First, constant tripping value of the differential ground current Id for definition of the
tripping characteristic curve; exceeds the characteristic quantity (differential ground
current Id), the set value of parameter [P3452] for stabilization ground currents in the
range between Istab = 0 and Istab = Is0 the pick-up event ANSI64REF-1 pick-up
[E2375] will be activated.
If there is no active blocking of the Harmonics stabilizer ANI95i and Delay time
(Parameter Delay time [P3455]) run down, then, also trip event ANSI64REF-1 trip
[E2376] is activated. This event can be used for alarm or output control purposes.
P3453 Id1
In combination with parameter Is1 [P3450] parameter [P3453] defines the second
straight line segment (as well as the starting point of the third straight line segement) of
the tripping curve of the stabilized restricted earth fault. If the characteristic quantity
(differential ground current Id) exceeds the range of values set with the parameters
[P3450] and [P3453] for stabilization ground currents in the range between Istab = Is0
and Istab = Is1 the pick-up event ANSI64REF-1 pick-up [E2375] will be activated.
If there is no active blocking of the Harmonics stabilizer ANI95i and Delay time
(Parameter Delay time [P3455]) run down, then, also trip event ANSI64REF-1 trip
[E2376] is activated. This event can be used for alarm or output control purposes.
P3454 Id2
In combination with parameter Is2 [P3451] parameter [P3454] defines the second point
to determine the slope of the third straight line segment of the stabilized restricted earth
fault protection tripping curve. If the characteristic variable (differential ground current Id)
exceeds the range of values set with the parameters [P3451] and [P3454] for
stabilization ground currents in the range between Istab = Is1 and Istab = Is res the
pick-up event ANSI64REF-1 pick-up [E2375] will be activated.
If there is no active blocking of the Harmonics stabilizer ANI95i and Delay time
(Parameter Delay time [P3455]) run down, then, also trip event ANSI64REF-1 trip
[E2376] is activated. This event can be used for alarm or output control purposes.
P3460 Function
This parameter activates/deactivates the high-set restricted earth fault protection
element (STEP 2) whereby the setting:
OFF: deactivates the high-set restricted earth fault protection element or
ON: activates the high-set restricted earth fault protection element.
When high-set restricted earth fault protection element is enabled by parameter [P3460],
then event ANSI64REF-2 active [E2379] is activated.
P3461 Blocking
High-set restricted earth fault protection element (STEP 2) can be completely blocked by
any active event. For blocking, the number related to this blocking event has to be
assigned to parameter [P3461]. Blocking is only effective, however, as long as the
blocking event is active. As soon as blocking is active, event ANSI64REF-2 blocked
[E2371] is activated. If the blocking event turns inactive, blocking is abandoned and
protective element is effective again. Then, event [E2371] is deactivated automatically.
If blocking of the high-set restricted earth fault protection element (STEP 2) is not
required, set this parameter to 0.
P3462 Id>>
This parameter defines the pick-up value for the characteristic quantity (differential
ground current Id) of the high-set restricted earth fault protection element (STEP 2),
disregarding the height of the stabilization current Istab.
If the characteristic quantity exceeds the value set for parameter [P3462], the trip event
ANSI64REF-2 trip [E2382] will be activated disregarding the stabilized tripping
characteristic. This event can be used for alarm or output control purposes.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
characteristic quantity (ground current). The nominal value of the
characteristic quantity is to be set by parameter:
Ground Current [P607], for primary side W1 or
Ground Current [P617], for secondary side W2
Ground Current [P627], for tertiary side W3.
The parameters Ground Current [P607], Ground Current [P617] and
Ground Current [P627] are located in submenu:
SYSTEM\Nominals\Reference values.
STD
DP1
DP2
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
NOTE: The assignment of the voltage measurement input (PT1, PT2 or PT3) to the
current measurement input CT1 or CT2 is to be done by the following
parameters (referring to the setting options of parameter [P2160]), in the
submenu SYSTEM\Measuring\Power:
PT reference [P9410], for Power_CT1 and
PT reference [P9413], for Power_CT2
To measure current direction correctly, the needed energy flow direction is to
be defined by following parameters:
Direction [P9411], for Power_CT1 and
Direction [P9414], for Power_CT2.
There are up to 7 different inverse time characteristics (IDMT) available, which accords
to the US standard of the American National Standard Institute ANSI or the
international standard of International Electrotechnical Commission IEC:
Definite: definite time (DT)
ANSI NINV: Normal Inverse (ANSI);
ANSI VINV: Very Inverse (ANSI);
ANSI EINV: Extremely Inverse (ANSI);
IEC NINV: Normal Inverse (IEC);
IEC VINV: Very Inverse (IEC);
IEC LINV: Long-term Inverse (IEC);
IEC EINV: Extremely Inverse (IEC)
tr
k t r (G ) TMS
t (G ) TMS c
Designating
1 G
G
1
G
S
S
G
k c tr
[s] [s] - [s] -
C 80 0 2 80 2 Extremely invers
whereby:
t(G): theoretical operate timewith constant value of G (seconds)
tr(G): time setting (reset time for G = 0 and TMS = 1)
k, c, : constant values which define the chosen curve shape
TMS: Time Multiplier Setting
G: measured value of the characteristic quantity
GS: setting value (start) of the characteristic quantity
P2163 Limit
Pick-up value of the first directional overcurrent protection element (STEP1); at the
moment that the characteristic quantity (phase current) exceeds this limit and the
characteristic angle between phase current ILx and reference voltage UILx ref (with: x = 1,
2, 3) is located within the trip angle range, events ANSI67-1 pick-up [E1746] and phase
seggragated pickup event(s) depending on the fault loop ANSI67-1 pickup L1
[E1743] and/or ANSI67-1 pickup L2 [E1744] and/or ANSI67-1 pickup L3 [E1745] will
become active, and Delay time/TMS of the first directional overcurrent protection
element will start.
In case that the characteristic quantity (phase current) falls below Limit or the
characteristic angle is out the trip angle range of the first directional overcurrent
protection element before Delay time/TMS has run down, the timer of Delay time/TMS
will be stopped and the attained time value is being saved.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
characteristic quantity (phase current). The nominal value of the characteristic
quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P624] are
located in submenu: SYSTEM\Nominals\Reference values.
NOTE: Depending on the fault loop the phase-segregated pickup event(s) ANSI67-1
pickup L1 [E1743] and/or ANSI67-1 pickup L2 [E1744] and/or ANSI67-1
pickup L3 [E1745] and common pickup event ANSI67-1 pickup [E1746] will
be activated/deactivated simultaneously.
Table 3-14 ANSI 67 Fault loops and corresponding pickup events
Fault loop
Active pickup event
L1-E L2-E L3-E L1-L2 L1-L3 L2-L3 L1-L2-L3
ANSI67-1 pickup L1 [E1743] active inactive inactive active active inactive active
ANSI67-1 pickup L2 [E1744] inactive active inactive active inactive active active
ANSI67-1 pickup L3 [E1745] inactive inactive active inactive active active active
ANSI67-1 pickup [E1746] active active active active active active active
If pick-up event ANSI67-1 pick-up [E1746] and phase-seggregated pickup event(s) are
active, and Delay Time/TMS run down, trip event ANSI67-1 trip [E1750] and phase-
seggregated trip event(s) will be activated. These events can be used for alarm or
output control purposes.
NOTE: Depending on the fault loop the phase-segregated trip event(s) ANSI67-1 trip
L1 [E1747] and/or ANSI67-1 trip L2 [E1748] and/or ANSI67-1 trip L3
[E1749] and common trip event ANSI67-1 trip [E1750] will be
activated/deactivated simultaneously.
Fault loop
Active trip event
L1-E L2-E L3-E L1-L2 L1-L3 L2-L3 L1-L2-L3
ANSI67-1 trip L1 [E1747] active inactive inactive active active inactive active
ANSI67-1 trip L2 [E1748] inactive active inactive active inactive active active
ANSI67-1 trip L3 [E1749] inactive inactive active inactive active active active
ANSI67-1 trip [E1750] active active active active active active active
NOTE: The reset limit is to be set as a percentage of the nominal value of the
characteristic quantity (phase current). The nominal value of the characteristic
quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P624] are
located in submenu: SYSTEM\Nominals\Reference values.
There are up to 7 different inverse time characteristics available, which accords to the
US standard of the American National Standard Institute ANSI or the international
standard of International Electrotechnical Commission IEC:
Definite: definite time (DT);
ANSI NINV: Normal Inverse (ANSI);
ANSI VINV: Very Inverse (ANSI);
ANSI EINV: Extremely Inverse (ANSI);
IEC NINV: Normal Inverse (IEC);
IEC VINV: Very Inverse (IEC);
IEC LINV: Long-term Inverse (IEC) ;
IEC EINV: Extremely Inverse (IEC)
NOTE: If the tripping characteristic of Delay time/TMS is set to Definite (DT), then
parameter Reset curve [P2165] only provides setting option Definite (DT).
If the tripping characteristic of Delay time/TMS is set to xxx INV (IDMT),
then parameter Reset curve [P2165] provides both, setting option Definite
(DT) or setting option xxx INV (IDMT).
As a result, processing of the stored counter value of the tripping delay time takes on a
different working principle, depending on the reset characteristic of Delay time/TMS
(DT or IDMT) to be set set by parameter Reset curve [P2165]:
DT: The stored counter value is to be processed according to the settings of
Reset delay time pick-up
IDMT: The stored counter value is to be processed according to the settings of
Reset delay time trip/TMS
While the timer of the Reset delay time pick-up is running, the counter value of the
tripping delay time maintains at a constant level.
After the Reset delay time pick-up has run down, the counter value of the tripping delay
time (Delay time/TMS) will be reset.
If trip event ANSI67-1 trip [E1750] and phase-seggregated trip event(s) are activated
and Reset delay time trip/TMS has run down, the trip event ANSI67-1 trip [E1750]
and phase-seggregated trip event(s) will be deactivated.
NOTE: In dependence of the set value of parameter Reset after TRIP immediately
[P2168], deactivating of trip event ANSI67-1 trip [E1750] and phase-
seggregated trip event(s) take on a different working principle.
NOTE: If the reset curve of the first protection element (STEP1) is assigned a definite
time (DT) characteristic (parameter Reset curve [P2165] = Definite), and the
trip event ANSI67-1 trip [E1425] and phase-seggregated trip event(s) should
immediately be reset, then set parameter Reset Delay time/TMS [P2166] =
0.
The following graphics represents all the different setting options of parameter Direction
mode [P2170], each an example of phase L1 (phase current IL1 and its reference
voltage UIL1 ref):
NOTE: Parameter Angle absolute [P2171] is not valid for parameter setting option:
Direction mode [P2170] = Non-directional !
NOTE: The minimum limit of the measuring voltage is to be set as a percentage of the
nominal value of the characteristic quantity (phase-to-phase voltage). The
nominal value of the characteristic quantity is to be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2 or
Voltage (L-L) [P623], for tertiary side W3
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
I/In
While normal conditions the standard parameters STD are valid. When network conditions
change, dynamic parameters DP1 or DP2 can be activated by the event assigned to parameter
DP1 activation [P2157] or DP1 activation [P2158]. Hence, parameters [P3179] to [P3184] or
[P3203] to [P3208] becomes active and corresponding standard parameters becomes inactive.
As soon as the activating event becomes inactive, standard parameters are being activated and
dynamic parameters becomes inactive.
Change-over duration between standard parameters and dynamic parameters accords to the
protection cycle time (<2ms) of the protection device.
The following dynamic STEP parameters of the directional overcurrent protection exist only
once in each of the 4 independent protection STEPS. Thus, the dynamic STEP parameters
apply only to one of the 4 protection STEPS of one parameter SET
P3179 Limit
See description of parameter [P2163]
P3203 Limit
See description of parameter [P2163]
Ieff/In
[P2163] Limit
100%
0
t
[E1746]
ANSI67-1 pick-up
1
0
t
[P2164]
Delay time/TMS
t
[P2169]
Reset delay time pick-up
t
[E1750]
ANSI 67-1 trip
0
t
[P2168]
Reset delay time trip/TMS
Figure 3-176 Directional overcurrent protection Trip characteristic (DT) and Reset
characteristic (DT)
Ieff/In
[P2163] Limit
100%
0
t
[E1746]
ANSI67-1 pick-up
1
0
t
(current dependent
delay time ttrip)
t
[P2169]
Reset delay time pick-up
t
[E1750]
ANSI 67-1 trip
0
t
[P2168]
Reset delay time trip/TMS
Figure 3-177 Directional overcurrent protection Trip characteristic (IDMT) and Reset
characteristic (DT)
Ieff/In
Limit: [P2163]
100%
0
t
(current dependent
delay time Ttrip)
t
[E1750]
ANSI 67-1 trip
1
0
t
(current dependent
delay time Ttrip)
t
[E1750]
ANSI 67-1 trip
1
0
t
Figure 3-178 Directional overcurrent protection Trip characteristic (IDMT) and Reset
characteristic (IDMT)
STD
DP1
DP2
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
NOTE: The assignment of the voltage measurement input (PT1, PT2, PT3 or PT-
GND1) to the ground current measurement input CT1, CT2 or CT-GND1 is to
be done by the following parameters (referring to the setting options of
parameter [P2460]), in the submenu SYSTEM\Measuring\Power:
PT reference [P9419], for GND Power_CT1
PT reference [P9422], for GND Power_CT2 and
PT reference [P9428], for GND Power_CT-GND1
To measure ground current direction correctly, the required energy flow
direction is to be defined by following parameters:
Direction [P9411], for GND Power_CT1 and
Direction [P9414], for GND Power_CT2
Direction [P9429], for GND Power_CT-GND1.
NOTE: In case that residual voltage is to be calculated by voltage measuring via PT1,
PT2 or PT3 it is required to connect terminal N of SYMAP-Compact(+)
device (SYMAP-Compact: -X1.2:18; SYMAP-Compact+: -X1.2:26) to ground
potential!
For test purposes via voltage generator test equipment it is required to
connect terminal N of SYMAP-Compact(+) device to the neutral potential
of the voltage test equipment!
In case that residual voltage is to be calculated by voltage measuring via PT1,
PT2 or PT3 it is required to take into account 180 compared to directly
measured residual voltage via PT-GND1!
If blocking of the first step of directional ground overcurrent protection is not required, set
this parameter to 0.
There are up to 7 different inverse time characteristics (IDMT) available, which accords
to the US standard of the American National Standard Institute ANSI or the
international standard of International Electrotechnical Commission IEC:
Definite: definite time (DT)
ANSI NINV: Normal Inverse (ANSI);
ANSI VINV: Very Inverse (ANSI);
ANSI EINV: Extremely Inverse (ANSI);
IEC NINV: Normal Inverse (IEC);
IEC VINV: Very Inverse (IEC);
IEC LINV: Long-term Inverse (IEC);
IEC EINV: Extremely Inverse (IEC)
tr
k t r (G ) TMS
t (G ) TMS c
Designating
1 G
G
1
G
S
GS
k c tr
[s] [s] - [s] -
C 80 0 2 80 2 Extremely invers
whereby:
t(G): theoretical operate timewith constant value of G (seconds)
tr(G): time setting (reset time for G=0 and TMS = 1)
k, c, : constant values which define the chosen curve shape
TMS: Time Multiplier Setting
G: measured value of the characteristic quantity
GS: setting value (start) of the characteristic quantity
P2463 Limit
Pick-up value of the first directional ground overcurrent protection element (STEP1); at
the moment that the characteristic quantity (phase current) exceeds this limit and the
characteristic angle between ground current and residual voltage as reference voltage is
located within the trip angle range, ANSI67G-1 pick-up [E2040] will become active, and
Delay time/TMS of the first directional ground overcurrent protection element will start.
In case that the characteristic quantity (ground current) falls below Limit or the
characteristic angle is out the trip angle range of the first directional ground overcurrent
protection element before Delay time/TMS has run down, the timer of Delay time/TMS
will be stopped and the attained time value is being safed.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
characteristic quantity (ground current). The nominal value of the
characteristic quantity is to be set by parameter:
Ground current [P607], for primary side W1 or
Ground current [P617], for secondary side W2 or
Ground current [P627], for tertiary side W3.
If pick-up event ANSI67G-1 pickup [E2040] is active and Delay Time/TMS run down,
trip event ANSI67G-1 trip [E2041] will be activated. This event can be used for alarm
or output control purposes.
NOTE: The reset limit is to be set as a percentage of the nominal value of the
characteristic quantity (ground current). The nominal value of the
characteristic quantity is to be set by parameter:
Ground current [P607], for primary side W1 or
Ground current [P617], for secondary side W2 or
Ground current [P627], for tertiary side W3.
There are up to 7 different inverse time characteristics available, which accords to the
US standard of the American National Standard Institute ANSI or the international
standard of International Electrotechnical Commission IEC:
Definite: definite time (DT);
ANSI NINV: Normal Inverse (ANSI);
ANSI VINV: Very Inverse (ANSI);
ANSI EINV: Extremely Inverse (ANSI);
IEC NINV: Normal Inverse (IEC);
IEC VINV: Very Inverse (IEC);
IEC LINV: Long-term Inverse (IEC) ;
IEC EINV: Extremely Inverse (IEC)
NOTE: If the tripping characteristic of Delay time/TMS is set to Definite (DT), then
parameter Reset curve [P2465] only provides setting option Definite (DT).
If the tripping characteristic of Delay time/TMS is set to xxx INV (IDMT),
then parameter Reset curve [P2465] provides both, setting option Definite
(DT) or setting option xxx INV (IDMT).
As a result, processing of the stored counter value of the tripping delay time takes on a
different working principle, depending on the reset characteristic of Delay time/TMS
(DT or IDMT) to be set set by parameter Reset curve [P2465]:
DT: The stored counter value is to be processed according to the settings of
Reset delay time pick-up
IDMT: The stored counter value is to be processed according to the settings of
Reset delay time trip/TMS
While the timer of the Reset delay time pick-up is running, the counter value of the
tripping delay time maintains at a constant level.
After the Reset delay time pick-up has run down, the counter value of the tripping delay
time (Delay time/TMS) will be reset.
meaning, depending on the reset characteristic of Reset curve (DT or IDMT) set by
parameter Reset curve [P2465]:
DT reset characteristic: Reset curve [P2465] = Definite
The delay time to reset the trip event is equal to a constant time value, to be set by
parameter Reset delay time/TMS [P2468].
IDMT reset characteristic: e.g. Reset curve [P2465] = ANSI NINV
The delay time to reset the trip event is not a constant time value, but, depending on
the inverse curve shape and the measured value of the characteristic quantity
(ground current) it will be cyclically re-calculated. When applying any inverse curve
(IDMT) to the reset curve, this means the setting of parameter Reset delay time
trip/TMS [P2468] takes on a displacement of the inverse curve shape with regard to
the time axis (TMS: Time Multiplier Setting).
If trip event ANSI67G-1 trip [E2041] is activated and Reset delay time trip/TMS has
run down, the trip event ANSI67G-1 trip [E2041] will be deactivated.
NOTE: In dependence of the set value of parameter Reset after TRIP immediately
[P2468], deactivating of trip event ANSI67G-1 trip [E2041] takes on a
different working principle.
NOTE: If the reset curve of the first protection element (STEP1) is assigned a definite
time (DT) characteristic (parameter Reset curve [P2465] = Definite), and
the trip event ANSI67G-1 trip [E2041] should immediately be reset, then set
parameter Reset Delay time/TMS [P2466] = 0.
The following graphics represents all the different setting options of parameter Direction
mode [P2470], each an example of phase L1 (ground current IG and residual voltage UG
as its voltage reference):
NOTE: The minimum limit of the measuring voltage is to be set as a percentage of the
nominal value of the characteristic quantity (residual voltage). The nominal
value of the characteristic quantity is to be set by parameter:
Ground voltage [P606], for primary side W1 or
Ground voltage [P616], for secondary side W2 or
Ground voltage [P626], for tertiary side W3 .
Start of function Fault locator ANSI 21FL in case of a protection trip via the first step of
directional ground overcurrent protection; where:
OFF: does not start the fault locator function or
ON: starts the calculation of fault location by function Fault locator ANSI 21FL
in case that:
o function Fault locator ANSI 21FL is enabled (parameter Function
[P3465] = ON) and
o the trip event ANSI67G-1 trip [E2041] becomes active.
I/In
The duration of change-over between standard parameters and dynamic parameters accords to
the protection cycle time (<2ms) of the protection device.
The following dynamic STEP parameters of the directional overcurrent protection exist only
once in each of the 4 independent protection STEPS. Thus, the dynamic STEP parameters
apply only to one of the 4 protection STEPS of one parameter SET
P3227 Limit
See description of parameter [P2463]
P3251 Limit
See description of parameter [P2463]
IGND eff/In
[P2463] Limit
0%
0
t
[E2040]
ANSI 67G-1 pickup
1
0
t
[P2464]
Delay time/TMS
t
[P2469]
Reset delay time pickup
t
[E2041]
ANSI 67G-1 trip
0
t
[P2468]
Reset delay time trip/TMS
Figure 3-186 Directional ground overcurrent protection Trip characteristic (DT) and Reset
characteristic (DT)
IGND eff/In
[P2463] Limit
0%
t
0
t
[E2040]
ANSI 67G-1 pickup
1
0
t
(current dependent
delay time ttrip)
t
[P2469]
Reset delay time pickup
t
[E2041]
ANSI 67G-1 trip
0
t
[P2468]
Reset delay time trip/TMS
Figure 3-187 Directional ground overcurrent protection Trip characteristic (IDMT) and Reset
characteristic (DT)
IGND eff/In
Limit: [P2463]
0%
t
0
t
(current dependent
delay time Ttrip)
t
[E2041]
ANSI 67G-1 trip
1
0
t
(current dependent
delay time Ttrip)
t
[E2041]
ANSI 67G-1 trip
1
0
t
Figure 3-188 Directional ground overcurrent protection Trip characteristic (IDMT) and Reset
characteristic (IDMT)
Main Menu\Parameters\PROTECTION\
ANSI 74TC Trip circuit supervision
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides only one protection STEP and, as
consequence, only one group of parameters. Thus, SET PARAMETERS are equal to
STEP parameters. The protection parameters of SET 1 represented below are
described in the following in detail as examples.
SET PARAMETERS
P2865 Function
This parameter enables/disables trip circuit supervision function where:
OFF: disables or
ON: enables the protective function.
When trip circuit supervision ANSI74TC is enabled by parameter [P2865], then event
ANSI74TC active [E2235] is activated.
P2866 Blocking
Trip circuit supervision function can be completely blocked by any active event. For
blocking, the number related to this blocking event has to be assigned to parameter
[P2866]. Blocking is only effective, however, as long as the blocking event is active. As
soon as blocking is active, event ANSI74TC blocked [E2236] is activated. If the
blocking event turns inactive, blocking is abandoned and automatic reclosing (AR)
function is effective again. Then, event [E2236] is deactivated automatically.
If blocking of trip circuit supervision ANSI74TC function is not required, set this
parameter to 0.
For supervision of the CB trip circuit (circuit includes the binary output e.g. Shunt 1 of the
protective relais and the CB trip coil) two binary inputs are applied. Depending on the
connection with the auxiliary contacts of the CB (one normal open aux. contact: 52-a, and one
normal closed aux. contact: 52-b) the signal states of the binary inputs give conclusion about
an interrupted trip circuit.
NOTE: Function ANSI 74TC is only for trip circuit supervision of one breaker!
Table 3-17 Trip circuit supervision Signal states and supervision modes
CAUTION: Please ensure that the trip coil is included in the supervised circuit!
To protect the hardware of SYMAP-Compact(+) against any disturbances by
high cut-off voltage of inductive components (e.g. auxiliary relays, CB trip coil,
etc.) connected to the binary inputs and/or binary outputs of SYMAP-
Compact(+), the inductive components must be equipped with a flywheel diodes
(DC voltage) or varistors (AC voltage)!
Depending on the different hardware versions, see the following connection diagrams as
examples:
CAUTION: For correct operating of function ANSI74TC the polarity of the connected binary
inputs must accord to the following connection diagrams!
All of the binary inputs may be used for function ANSI 74TC.
CB position: OPEN
SYMPAP-Compact(+)
L
Binary output: (Shunt 1")
X2.3: 44 GND2
X2.5: 65 GND2
52-a 52-b
CB
CB aux.
contacts
52 trip coil
Figure 3-190 HW v1-1.x: Trip circuit supervision example of a connected trip circuit: CB open
When signal line A is broken while CB is open this will be indicated by function ANSI 74TC not
before the CB is switched on. Wire break of line B will be indicated when the CB is open.
CB position: CLOSED
SYMPAP -Compact(+)
L
Binary output: (Shunt 1")
X2.3: 44 GND2
X2.5: 65 GND2
52-a 52-b
CB
CB aux.
contacts
52 trip coil
Figure 3-191 HW v1-1.x: Trip circuit supervision example of a connected trip circuit: CB closed
When signal line A is broken while CB is closed this will be indicated immediately by function
ANSI 74TC. Wire break of line B will be indicated not before the CB is switched off.
CAUTION: For correct operating of function ANSI74TC the polarity of the connected binary
inputs must accord to the following connection diagrams!
For connection example below binary inputs Fct. 26 and Fct. 27 have to be
used for function ANSI 74TC!
CB position: OPEN
SYMPAP-Compact(+)
L+
Binary output: (Shunt 1")
X2.3: 30 GND 10
X2.3: 32 GND 11
52-a 52-b
CB
CB aux.
contacts
52 trip coil
Figure 3-192 HW v1-2.x: Trip circuit supervision example of a connected trip circuit: CB open
When signal line A is broken while CB is open this will be indicated by function ANSI 74TC not
before the CB is switched on. Wire break of line B will be indicated when the CB is open.
CB position: CLOSED
SYMPAP -Compact(+)
L+
Binary output: (Shunt 1")
X2.3: 30 GND 10
X2.3: 32 GND 11
52-a 52-b
CB
CB aux.
contacts
52 trip coil
Figure 3-193 HW v1-2.x: Trip circuit supervision example of a connected trip circuit: CB closed
When signal line A is broken while CB is closed this will be indicated immediately by function
ANSI 74TC. Wire break of line B will be indicated not before the CB is switched off.
P2867 Mode
Supervision mode of the evaluation logic referring to the binary inputs; whereby setting:
Both: checks the equality of signal states 0 / 0 and 1 / 1
Closed: checks only the equality of signal states 1 / 1
Open: checks only the equality of signal states 0 / 0
At the time the signal states 0 / 0 or 1 / 1 are detected, event ANSI 74TC pickup
[E2237] is activated, and the Delay time [P2870] is being started.
P2868 ON Feedback
Binary input to indicate the closed auxiliary contact of the CB; the event of the binary
input which indicates the closed auxiliary contact of the CB is to be assigned to this
parameter.
Trip delay time; it is the delay time of the trip event ANSI74TC trip [E2238].
As soon as:
function Trip circuit supervision is activated by parameter [P2865] and
signal states 0 / 0 or 1 / 1 are detected by the binary inputs and
blocking of function Trip circuit supervision is not activated by the blocking event
of parameter [P2562]
the pick-up event ANSI 74TC pickup [E2237] is activated and Delay time is being
started.
As soon as the pick-up event ANSI 74TC pickup [E2237] is active and Delay time run
down, trip event [E2238] will be activated. This event can be used for alarm or output
control purposes. Right after protection trip, and, as soon as faulty conditions will no
longer be existent, pick-up event [E2237] and trip event [E2238] are being deactivated
automatically.
Main Menu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
SET PARAMETERS
The following SET PARAMETERS of the vector surge protection exist only once in all four
parameter sets. Thus, the SET PARAMETERS apply to all of the 3 protection STEPS of one
parameter SET.
NOTE: In case that no voltage measurement is possible, caused by locating the PTs
below the circuit breaker, and which is open, then, vector surge protection
must be blocked by a suitable event. For this, the related number of such
blocking event has to be assigned to parameter [P1861].
When vector surge protection ANSI78 is enabled by parameter [P1860], then event
ANSI78 module active [E1570] is activated.
For settings PT1, PT2 or PT3, event ANSI78-1 step acitve [E1576] is activated.
remains below this minimum setting at least in one phase. For the duration of blocking
event ANSI78-1 blocked step by min. start voltage [E1578] is activated.
NOTE: The minimum limit of the measuring voltage is to be set as a percentage of the
nominal value of the characteristic quantity (phase-to-phase voltage). The
nominal value of the characteristic quantity is to be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2 or
Voltage (L-L) [P623], for tertiary side W3.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
Application: Min. start voltage delay time is used to detect a stable voltage
restoration.
P1871 K1
Correction factor to adjust the maximum permissible voltage angle difference (vector
surge) dependent of the grid impedance; multiplcation of the correction factor K1
[P1871] by the setting of parameter Limit [P1870] gives the maximum permissible
voltage angle difference max as the limit for vector surge protection.
Max. permissible voltage angle difference max = Limit [P1870] x K1 [P1871]
P1870 Limit
Pick-up value of vector surge protection; as soon as the characterisitc quantity (voltage
angle difference ):
exceeds the set value of the maximum permissible voltage angle difference max
(parameter Limit [P1864] and K1 [P1865]), and
no blocking event (parameter Blocking protection module [P1861]) is active, and
no blocking event (parameter Blocking protection step [P1866]) is active, and
no blocking by insufficient voltage (parameter Min. start voltage [P1867]) is active
P1872 Direction
Operating direction of vector surge protection protection; the working principle in view of
the vector surge direction ( > 0 => positive vector surge; < 0 => negative vector
surge) can be chosen by the following setting options of parameter Direction [P1872]:
none: supervision for the max. permissible voltage angle difference max
independent of a positive or negative vector surge
positive: supervision for a positive voltage angle difference
negative: supervision for a neagative voltage angle difference
The parameters Current [P604], Current [P614] and Current [P624] are
located in submenu: SYSTEM\Nominals\Reference values.
Main Menu\Parameters\PROTECTION\
ANSI 79 Automatic reclosing
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides only one protection STEP and, as
consequence, only one group of parameters. Thus, SET PARAMETERS are equal to
STEP parameters. The protection parameters of SET 1 represented below are
described in the following in detail as examples.
P2675 Enable
This parameter enables/disables Automatic Reclose (AR) where:
OFF: disables or
ON: enables the protective function.
When Automatic Reclose (AR) ANSI 79 is enabled by parameter [P2675], then event
ANSI79 Ready [E2160] is activated.
P2675 Block
Automatic Reclose (AR) function can be completely blocked by any active event. For
blocking, the number related to this blocking event has to be assigned to parameter
[P2675]. Blocking is only effective, however, as long as the blocking event is active. As
soon as blocking is active, event ANSI79 Blocked [E2161] is activated. If the blocking
event turns inactive, blocking is abandoned and protective function is effective again.
Then, event [E2161] is deactivated automatically.
If blocking of function Automatic Reclose (AR) is not required, set this parameter to 0.
P2676 Lock
An already running AR-cycle of Automatic Reclose (AR) function can be interrupted
(lcked) by any active event. For this, the number related to this locking event has to be
assigned to parameter [P2676]. As soon as locking is active, event ANSI79 Locked
[E2161] is activated. When the locking event becomes inactive, then the AR-cycle
remains interrupted.
If locking of an AR-cycle of function Automatic Reclose (AR) is not required, set this
parameter to 0.
P2677 Unlock
An already active but interrupted AR-cycle f Automatic Reclose (AR) function can be
released (unlocked) by any active event. For this, the number related to this unlocking
event has to be assigned to parameter [P2677]. As soon as the release event is active,
the locked AR-cycle is being continued, and event ANSI79 Locked [E2161] is
deactivated.
CAUTION: In the event that locking of an AR-Cycle is foreseen in the application,
please ensure that a corresponding unlocking event is being
assigned to parameter Unlock [P2677]!
P2679 Activate
The AR-cycle of Automatic Reclose (AR) function can be activated by any active event.
For activation, the number related to this event has to be assigned to parameter [P2679].
As soon as the assigned is active, the AR-cycle is started and event ANSI79 Cycle
[E2163] is activated.
If an event-activation of an AR-cycle of function Automatic Reclose (AR) is not required,
set this parameter to 0.
P2688 Activate
The AR-cycle of Automatic Reclose (AR) function can be activated by any active event.
For activation, the number related to this event has to be assigned to parameter [P2688].
As soon as the assigned is active, the AR-cycle is started and event ANSI79 Cycle
[E2163] is activated.
If an event-activation of an AR-cycle of function Automatic Reclose (AR) is not required,
set this parameter to 0.
Supervision time for a successful reclosing attempt; when the success time set by
parameter [P2698] run down, function Automatic reclosing (AR) checks wether the CB
is closed.
Hereby, the following cases have to be taken into account:
P2699 Off-time
Blocking time after the last AR-attempt; at the time the off-time run down, the events
ANSI79 Off-time [E2176] and ANSI79 Cycle [E2163] are deactivated and event
ANSI79 Ready [E2160] is activated.
Event ANSI79 Success [E2174] can be deactivated by command ACK (e.g. by
operating the function key at the front panel)
[E2160]
ANSI 79 ready
1
0
[P2679]
ANSI79 Activate Trigger-Event t
1
0
t
[E2163]
ANSI79 Cycle 1
0
t
[P2680]
1. Pause time
[E2164] t
ANSI79 1. Pause time
1
[P2697] t
Breaker close command
time
[E2172] t
ANSI 79 Breaker close
command 1
[P2698]
t
Breaker close success
time
[E2173] t
ANSI 79 Breaker close
success time 1
0
[P2700] t
Breaker closed Feedback event number: ON feedback [E6010]
1
0
t
[P2681]
2. Pause time
[E2165] t
ANSI79 2. Pause time
1
0
[E2174] t
ANSI 79 Success
1
0
[E2175] t
ANSI 79 Fail
1
0
t
[P2699] Off-time
[E2176] t
ANSI 79 Off-time
1
Function Ack
t
0
t
Main Menu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
SET PARAMETERS
The following SET PARAMETERS of the frequency protection exist only once in each of the
four parameter sets. Thus, the SET PARAMETERS apply to all of the 12 protection STEPS of
one parameter SET.
NOTE: In case that no voltage measurement is possible, caused by locating the PTs
below the circuit breaker, and which is open, then, undervoltage protection
must be blocked by a suitable event. For this, the related number of such
blocking event has to be assigned to parameter [P1326].
The following STEP parameters of the frequency protection exist only once in each of the 12
independent protection STEPS. Thus, the STEP PARAMETERS apply only to one of the 12
protection STEPS of one parameter SET.
NOTE: The operating mode of each protection STEPcan be adjusted seperately either as
*over frequency protection or as under frequency protection. Changing the option
can be done by parameter Limit [P1334].
For settings PT1, PT2 or PT3, event ANSI81-1 step acitve [E1254] is activated.
blocking is active, event ANSI81-1 blocked step [E1255] is activated. If the blocking
event turns inactive, blocking is abandoned and protective function is effective again.
Then, event [E1255] is deactivated automatically.
If blocking of the first step of over frequency protection is not required, set this parameter
to 0.
NOTE: The minimum limit of the measuring voltage to activate frequency protection is
to be set as a percentage of the nominalvalue of the characteristic quantity
(phase-to-phase voltage). The nominal value of the characteristic quantity is to
be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2 or
Voltage (L-L) [P623], for tertiary side W3.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
P1334 Limit
Pick-up value of the first frequency protection element. At the moment that the
characteristic quantity (frequency) exceeds this limit, pick-up event ANSI81-1 pickup
[E1257] will become active, and the trip delay time (Delay time) of the first frequency
protection element will start.
If the trip reset delay time (Reset delay time trip) has run down, trip event ANSI81-1
trip [E1258] is deactivated. In case that the characteristic quantity (frequency) exceeds
the pick-up value (Limit) of the first frequency protection element before the timer of
Reset delay time trip has run down, the timer of Reset delay time trip will be reset.
Then trip event ANSI81-1 trip [E1258] remains active.
[P1334] limit
fn
t
[E1257]
ANSI81-1 pick-up
1
0
t
[P1335]
delay time
[P1338]
reset delay time
pick-up
t
[E1258]
ANSI81-1 trip
1
0
t
[P1337]
reset delay time
trip
For settings PT1, PT2 or PT3, event ANSI81-1 step acitve [E1254] is activated.
CAUTION: SYMAP-Compact(+) device variants which were built according to ordering option
G59:
do not provide frequency measurement via voltage measurement input PT3!
do provide phase-seggregated frequency measurement (zero crossings of
phase voltages) only at voltage measurement input PT2!
do provide frequency measurement at PT1 based on crossings of phase-to-
neutral voltages UL1 and UL2!
NOTE: The minimum limit of the measuring voltage to activate frequency protection is
to be set as a percentage of the nominalvalue of the characteristic quantity
(phase-to-phase voltage). The nominal value of the characteristic quantity is to
be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2 or
Voltage (L-L) [P623], for tertiary side W3.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
P1334 Limit
Pick-up value of the first frequency protection element, at the moment that the
characteristic quantity (frequency) falls below this limit, pick-up event ANSI81-1 pickup
[E1257] will become active, and the trip delay time (Delay time) of the first frequency
protection element will start.
fn
[P1336] limit
t
[E1257]
ANSI81-1 pick-up
1
0
t
[P1335]
delay time
t
[P1338]
reset delay time
pick-up
t
[E1258]
ANSI81-1 trip
1
0
t
[P1337]
reset delay time
trip
Main Menu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
CAUTION: SYMAP-Compact(+) device variants which were built according to ordering option
G59:
do not provide frequency measurement via voltage measurement input PT3!
do provide phase-seggregated frequency measurement (zero crossings of
phase voltages) only at voltage measurement input PT2!
SET PARAMETERS
The following SET PARAMETERS of the rate of change of frequency (RoCoF) protection exist
only once in each of the four parameter sets. Thus, the SET PARAMETERS apply to all of the 6
protection STEPS of one parameter SET.
P3582 ROCOF
This parameter enables/disables rate of change of frequency (RoCoF) protection where:
OFF: disables or
ON: enables the protective function.
NOTE: In case that no voltage measurement is possible, caused by locating the PTs
below the circuit breaker, and which is open, then, rate of change of frequency
(RoCoF) protection must be blocked by a suitable event. For this, the related
number of such blocking event has to be assigned to parameter [P3583].
For settings PT1, PT2 or PT3, event ANSI81R-1 acitve [E2473] is activated.
CAUTION: SYMAP-Compact(+) device variants which were built according to ordering option
G59:
do not provide frequency measurement via voltage measurement input PT3!
do provide phase-seggregated frequency measurement (zero crossings of
phase voltages) only at voltage measurement input PT2!
do provide frequency measurement at PT1 based on crossings of phase-to-
neutral voltages UL1 and UL2!
NOTE: The minimum limit of the measuring voltage to activate rate of change of
frequency (RoCoF) protection is to be set as a percentage of the nominalvalue
of the characteristic quantity (phase-to-phase voltage). The nominal value of
the characteristic quantity is to be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2 or
Voltage (L-L) [P623], for tertiary side W3.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
Application: Min. start voltage delay time is used to detect a stable voltage
restoration.
P3588 Mode
Selction of operating mode according to the protective criterion (characteristic quantity)
of the rate of change of frequency (RoCoF) protection; the first step of the rate of change
of frequency (RoCoF) protection is optionally adjustable. Following setting options for the
characteristic quantity are available:
df/dt: Supervision of the frequency gradient df/dt depending on:
the set value of parameter df/dt limit [P3592], and
the supervision direction of the rate of change of frequency
(positive or negative sign of the frequency gradient slope) set by
parameter Direction [P3589].
If:
the measured frequency gradient exceeds the max. permissible
frequency gradient df/dtmax set by parameter df/dt limit [P3592],
and
the sign of the measured frequency gradient slope is equal to the
set value of parameter Direction [P3589], and
no blocking event (parameter Blocking protection module
[P3583]) is active, and
no blocking event (parameter Blocking protection step [P3585])
is active, and
no blocking by insufficient voltage (parameter Min. start voltage
[P3586]) is active,
then pick-up event ANSI81R-1 pick-up [E2475] is activated, and the
counter of the trip delay time (see parameter Delay time [P3595) is
started. As soon as trip delay time run down, trip event ANSI81R-1
trip [E2476] will be activated. This event can be used for alarm or
output control purposes.
In case that the characteristic quantity (df/dt) falls below the pick-up
value (df/dt limit Hysteresis), or the measured slope direction
differs from the set supervision direction before the trip delay time has
run down, the timer of trip delay time will be stopped and reset to
zero, and the pick-up event [E2475] will be deactivated.
f>&df/dt: Supervision of the frequency gradient df/dt depending on:
the set value of parameter df/dt limit [P3592], and
the supervision direction of the rate of change of frequency
(positive or negative sign of the frequency gradient slope) set by
parameter Direction [P3589], and
the max. permissible frequency limit set by parameter f> limit
[P3591].
If:
trip [E2476] will be activated. This event can be used for alarm or
output control purposes.
In case that the measured frequency gradient df/dt falls below the
pick-up value (df/dt limit), or the measured slope direction differs
from the set supervision direction, or the measured frequency
exceeds the min. permissible frequency limit before the trip delay time
has run down, the timer of trip delay time will be stopped and reset to
zero, and the pick-up event [E2475] will be deactivated.
f>&DF/DT: Supervision of frequency change (time-depending frequency change)
depending on:
the max. permissible frequency limit set by parameter f> limit
[P3591], and
the max. permissible frequency change set by parameter DF
[P3596], and
the supervision time set by parameter DT [P3597], and
If:
no blocking event (parameter Blocking protection module
[P3583]) is active, and
no blocking event (parameter Blocking protection step [P3585])
is active, and
no blocking by insufficient voltage (parameter Min. start voltage
[P3586]) is active, and
as soon as the measured frequency exceeds the max.
permissible frequency limit set by parameter f> limit [P3591],
then the pick-up event ANSI81R-1 pick-up [E2475] is activated, and
the counter of the supervision time DT is started.
While the supervision time DT is active, the frequency difference is
calculated form each actual measured frequency value and the
frequency value set by parameter f> limit [P3591]. When the amount
of the frequency difference |DF| exceeds the set value of parameter
DF [P3596], trip event ANSI81R-1 trip [E2476] will be activated.
This event can be used for alarm or output control purposes.
In case that the measured frequency falls below the max. permissible
frequency limit before the supervision time DT has run down, the
timer of trip delay time will be stopped and reset to zero, and the pick-
up event [E2475] will be deactivated.
f<&DF/DT: Supervision of frequency change (time-depending frequency change)
depending on:
the min. permissible frequency limit set by parameter f< limit
[P3590], and
the max. permissible frequency change set by parameter DF
[P3596], and
the supervision time set by parameter DT [P3597], and
If:
no blocking event (parameter Blocking protection module
[P3583]) is active, and
no blocking event (parameter Blocking protection step [P3585])
is active, and
P3589 Direction
Operating direction of rate of change of frequency (RoCoF) protection; the working
principle in view of the frequency slope direction (df/dt > 0 => positive slope; df/dt < 0 =>
negative slope) can be chosen by the following setting options of parameter Direction
[P3589]:
none: supervision of the change of frequency independent of a positive
or negative slope of df/dt
positive: supervision for a positive slope of the rate of change of frequency
negative: supervision for a neagative slope of the rate of change of frequency
P3593 Hysteresis
This parameter [P3593] determines the reset limit for the pick-up event ANSI81R-1
pickup [E2475] of the first protection element. At the moment the characteristic quantity
(rate of change of frequency df/dt) falls below the reset limit, the activated pick-up event
ANSI81R-1 pickup [E2475] will be deactivated:
P3594 K2
Correction factor to adjust the maximum permissible rate of change of frequency df/dtmax
dependent of the grid impedance; multiplcation of the correction factor K2 [P3594] by
the setting of parameter df/dt limit [P3592] gives the maximum permissible rate of
change of frequency df/dtmax as the limit for rate of change of frequency (RoCoF)
protection.
Max. permissible rate of change of frequency df/dtmax = df/dt limit [P3592] x K2
[P3594]
P3596 DF
This parameter defines the limit of the max. permissible frequency difference within the
supervision time set by parameter DT [3597] for the protection criterion DF/DT
P3597 DT
This parameter defines the duration of supervision time of the max. permissible
frequency difference set by parameter DF [3596] for the protection criterion DF/DT
Main Menu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS
represented below are described in the following in detail as examples.
P3435 Function
This parameter enables/disables function ANSI 86 Lockout relay where:
OFF: disables function ANSI 86 Lockout relay or
RS-FF volatile: enables function ANSI 86 Lockout relay, domination of
input element for resetting (R) accords to the RS-FlipFlop
logic scheme; current state of lockout relay output event
(editable) [E4502] is not being saved after system reboot;
or
RS-FF nonvolatile: enables function ANSI 86 Lockout relay, domination of
input element for resetting (R) accords to the RS-FlipFlop
logic scheme; current state of lockout relay output event
(editable) [E4502] is being saved after system reboot.
SR-FF volatile: enables function ANSI 86 Lockout relay, domination of
input element for setting (S) accords to the SR-FlipFlop
logic scheme; current state of lockout relay output event
(editable) [E4502] is not being saved after system reboot;
or
SR-FF nonvolatile: enables function ANSI 86 Lockout relay, domination of
input element for setting (S) accords to the SR-FlipFlop
logic scheme; current state of lockout relay output event
(editable) [E4502] is being saved after system reboot.
When Lockout relay ANSI 86 is enabled by parameter [P3435], then event ANSI86
module active [E2368] is activated.
NOTE: Function ANSI 86 only affects the reset behaviour of the active output event
(editable) [E4502] of the binary output Lockout relay!
When Lockout relay ANSI 86 is disabled by parameter [P3435], then reset of
the output event (editable) [E4502] only accords to the states of its assigned
logical input elements and the parameter settings of the binary output Lockout
relay!
P3436 Reset
Assignment of any available event to reset Lockout relay function; function can be reset
by any active event. For reset, the number related to this reset event has to be assigned
to parameter Reset [P3436].
If resetting of lockout relay is not required, set this parameter to 0.
Example 1: Function = RS-FF volatile; reset of lockout relay via binary input FCT. 17
(E4017])
[E6970]
System booting 1
0
t
[E2368]
ANSI86 module 1
active
0
t
e.g. [E1425]
ANSI 50/51-1 trip 1
0
t
[E4502]
Lockout relay
1
output
0
t
[Exxxx]
Name 1
0
t
Figure 3-204 ANSI 86 lockout and reset characteristic of lockout relay: RS-FF-volatile
Example 2: Function = RS-FF non-volatile; reset of lockout relay via binary input FCT. 17
(E4017])
[E6970]
System booting 1
0
t
[E2368]
ANSI86 module 1
active
0
t
e.g. [E1425]
ANSI 50/51-1 trip 1
0
t
[E4502]
Lockout relay
1
output
0
t
[Exxxx]
Name 1
0
t
Figure 3-207 ANSI 86 lockout and reset characteristic of lockout relay: RS-FF-nonvolatile
This protection principle is advantageous because of the high degree of selectivity since the
CTs unambiguously define the protection range on both ends of the equipment to protect.
Consequently, fault finding can be effected in fast mode.
The field of application of the current differential protection generally includes protection of
motors, generators and transformers as well as of overhead lines, cables and busbars.
Depending on the type and the operating behaviour of the equipment to protect, certain
particularities (measurement value adaptations as well as operation-relevant and transient error
currents) have to be included into the protective relaying.
Protection zone
I1 I2
Grid 2 PROTECTED OBJECT Grid 2
I1 I2
SYMAP
Compact+
The differential protection function of the SYMAP-Compact+ has been designed for protection
of motors, generators and two-winding transformers.
For motors and generators, the stator windings of the machine will be monitored. On the one
hand, the two current transformer sets are arranged between the leads of the stator windings on
the star point end of the generator and, on the other hand, at the power input end (motor) or the
power output end (generator). For the transformer differential protection, the transformer sets
will be connected each to the primary and secondary windings of the transformer.
In order to allow comparison of the phase currents on both ends of the equipment to protect
regarding their absolute values and the phasing, the current values need to be elevated to a
common reference plane. And the following is to include for this purpose:
Adaption of the current transformer ratios on both ends of the protection object (amplitude
adaptation):
To adapt the current values for comparison of the phase currents, the transformation ratios
(1, 2) of the current transformers are to be taken into account (see Figure 3-209):
Adaptation of possibly differing nominal currents of the current transformer sets to the
transformers transformation ratio (amplitude adaptation):
The primary nominal values of the current transformer sets on both ends of the protection
object (transformer) should be determined on the transformers nominal value. The primary
nominal transformer current I2n,CT,pri of the current transformer set on the secondary end W 2
should, under consideration of the transformer transformation ratio W 1/W 2, correspond to
the primary nominal transformer current I1n,transformer,pri of the current transformer sets on the
primary side W 1:
Should, due to incorrect transformer selection, the above condition no longer be given, the
factor by which the primary nominal transformer current of the transformer current be
included in the measurement value adaptation.
Example:
Transformer transformation ratio: W1/W2 = 40
CT data at the undervoltage end: 4000/1A
=> correct adaptation: transformer data at the overvoltage end: 100/1A
selected CT: transformer data at the overvoltage end: e.g.: 200/1A
The following table gives an overview about the different transformer vector groups:
Description Vector diagram Circuit Ratio
Secondary neutral
Application
point
Iden- Vector
tifier group
primary secondary primary secondary U1 : U2
W1
Dd0 Not available
W2
1U 1W 2U 2W
1U2 1V2 1W2 2U2 2V2 2W2
2 W1 Small distribution
Loadable up to rated
Dz0 transformer; for three
current
2N 3 W2 line connection
1U 1W 2U 2W
1U2 1V2 1W2 2U2 2V2 2W2
W1 Large distribution
Dy5 2V 2N transformer
Loadable up to rated
3 W2 current
1U 1W
2U 1U2 1V2 1W2 2U2 2V2 2W2 2N
W1
Dd6 Not available
W2
1U 1W 2V
1U2 1V2 1W2 2U2 2V2 2W2
W1 Loadable up to max.
6 Yy6 1N
2N
10% of rated current
W2
1U 1W 2V
1U2 1V2 1W2 2U2 2V2 2W2 2N
2N 2 W1 Loadable up to rated
Dz6
3 W2 current
1U 1W
2V 1U2 1V2 1W2 2U2 2V2 2W2 2N
W1 Loadable up to rated
Dy11 2N 2V
current
3 W2
1U 1W
2W 1U2 1V2 1W2 2U2 2V2 2W2
2 W1 Loadable up to rated
Yz11 1N 2N current
3 W2
1U 1W 2U 2W
1U2 1V2 1W2 2U2 2V2 2W2
0 0
ULx,HV, reference
ULx,LV, lagging
LV-HV = K x 30
= 5 x 30 LV-HV = K x 30
= 150 = 5 x 30
= 150
ULx,HV, reference
ULx,LV, lagging
180 180
measuring and/or to CT-GND1 for ground current measuring shall be according to the following
parameter settings:
CT1: Assignment [P668] = W1, and/or
CT2: Assignment [P674] = W1, and/or
CT-GND1: Assignment [P684] = W1.
The assignment of the measuring location to the voltage transformers which are installed at the
high voltage side and being connected to PT1, PT2 and/or PT3 for phase-to-neutral voltage
measuring and/or to PT-GND1 for residual voltage measuring shall be according to the
following parameter settings:
PT1: Assignment [P642] = W1 and/or
PT2: Assignment [P645] = W1 and/or
PT3: Assignment [P648] = W1 and/or
PT-GND1: Assignment [P651] = W1.
The assignment of the measuring location to the voltage transformers which are installed at the
low voltage side and being connected to PT1, PT2 and/or PT3 for phase-to-neutral voltage
measuring and/or to PT-GND1 for residual voltage measuring shall be according to the
following parameter settings:
PT1: Assignment [P642] = W2 and/or
PT2: Assignment [P645] = W2 and/or
PT3: Assignment [P648] = W2 and/or
PT-GND1: Assignment [P651] = W2.
The assignment of the measuring location to the voltage transformers which are installed at the
low voltage side and being connected to PT1, PT2 and/or PT3 for phase-to-neutral voltage
measuring and/or to PT-GND1 for residual voltage measuring shall be according to the
following parameter settings:
PT1: Assignment [P642] = W3 and/or
PT2: Assignment [P645] = W3 and/or
PT3: Assignment [P648] = W3 and/or
PT-GND1: Assignment [P651] = W3.
The following connection diagrams give examples of two different applications of transformer
differential protection:
YNd5 step-down transformer and
YNd5 step-up transformer (block protection).
In addition to the connection circuit required parameter settings and definition of winding sides
are given.
L1
L2
L3
Transformer-Differential protection ANSI 87
(step-down operation, CT1 = reference = high voltage side HV)
-X1.1
P1 1 SYMAP-Compact+
S1
P2 S2
2
P1 3
S1
CT1-M/P
! !
HV = W1 = Primary W1" S2
P2 4
P1 5
S1
P2 S2
6
Current transformer:
CT1
HV Primary [P660] = 200A
Secondary [P661] = 1A
YN CT1-M: Direction L1 (Measuring) [P662] = 0
CT1-M: Direction L2 (Measuring) [P663] = 0
YNd5 CT1-M: Direction L3 (Measuring) [P664] = 0
CT1-P: Direction L1 (Protection) [P665] = 0
CT1-P: Direction L2 (Protection) [P666] = 0
d5 CT1-P: Direction L3 (Protection) [P667] = 0
Assignment [P674] = W1
LV CT2
Primary [P660] = 1000A
Secondary [P661] = 1A
CT2-MP: Direction L1 [P671] = 0
CT2-MP: Direction L2 [P672] = 0
CT2-MP: Direction L3 [P673] = 0
-X1.2 Assignment [P674] = W2
P2 7
S2 Reference values:
Primary W1
Connection type [P600] = Y
P1 S1 Star point grounding [P601] = earthed
8 Voltage (L-L) [P602] = 10000V
P2 9
S2
! !
LV = W2 = Secondary W2" CT2-M/P Secondary W2
Connection type [P610] = d
P1 S1 Phase shift [P611] = 5
10 Star point grounding [P612] = isolated
P2 11 Voltage (L-L) [P613] = 400V
S2
P1 S1
12
L1
L2
L3
Differential protecion ANSI 87
Mains CB (step-up-operation; CT1 = reference = high voltage side HV)
-X1.1
P1 1 SYMAP-Compact+
S1
P2 S2
2
P1 3
S1
CT1-M/P
! !
HV = W1 = Primary W1" P2 S2
4
P1 5
S1
Parameter settings (example):
P2 S2 Current transformer:
6
CT1
Primary [P660] = 200A
Secondary [P661] = 1A
CT1-M: Direction L1 (Measuring) [P662] = 0
CT1-M: Direction L2 (Measuring) [P663] = 0
HV CT1-M: Direction L3 (Measuring) [P664] = 0
CT1-P: Direction L1 (Protection) [P665] = 0
YN CT1-P: Direction L2 (Protection) [P666] = 0
CT1-P: Direction L3 (Protection) [P667] = 0
Assignment [P674] = W1
YNd5
CT2
Primary [P660] = 1000A
d5 Secondary [P661] = 1A
CT2-MP: Direction L1 [P671] = 0
LV CT2-MP: Direction L2 [P672] = 0
CT2-MP: Direction L3 [P673] = 0
Assignment [P674] = W2
Gen. CB Reference values:
Primary W1
Connection type [P600] = Y
Star point grounding [P601] = earthed
Voltage (L-L) [P602] = 10000V
G Secondary W2
3~ Connection type [P610] = d
Phase shift [P611] = 5
Star point grounding [P612] = isolated
! ! Voltage (L-L) [P613] = 400V
LV = W2 = Secondary W2"
-X1.2
P2 7
S2
P1 S1
8
P2 9
S2
CT2-M/P
P1 S1
10
P2 11
S2
P1 S1
12
L1
L2
L3
Differential protecion ANSI 87
Mains CB (step-up-operation; CT1 = reference = low voltage side LV)
-X1.2
P1 7 SYMAP-Compact+
S1
P2 S2
8
P1 9
S1
CT2-M/P
! !
HV = W1 = Primary W1" P2 S2
10
P1 11
S1
Parameter settings (example):
P2 S2 Current transformer:
12
CT1
Primary [P660] = 1000A
Secondary [P661] = 1A
CT1-M: Direction L1 (Measuring) [P662] = 0
CT1-M: Direction L2 (Measuring) [P663] = 0
HV CT1-M: Direction L3 (Measuring) [P664] = 0
CT1-P: Direction L1 (Protection) [P665] = 0
YN CT1-P: Direction L2 (Protection) [P666] = 0
CT1-P: Direction L3 (Protection) [P667] = 0
Assignment [P674] = W2
YNd5
CT2
Primary [P660] = 200A
d5 Secondary [P661] = 1A
CT2-MP: Direction L1 [P671] = 0
LV CT2-MP: Direction L2 [P672] = 0
CT2-MP: Direction L3 [P673] = 0
Assignment [P674] = W1
Gen. CB Reference values:
Primary W1
Connection type [P600] = Y
Star point grounding [P601] = earthed
Voltage (L-L) [P602] = 10000V
G Secondary W2
3~ Connection type [P610] = d
Phase shift [P611] = 5
Star point grounding [P612] = isolated
! ! Voltage (L-L) [P613] = 400V
LV = W2 = Secondary W2"
-X1.1
P2 1
S2
P1 S1
2
P2 3
S2
CT1-M/P
P1 S1
4
P2 5
S2
P1 S1
6
L1
L2
L3
Transformer-Differential protection ANSI 87
(step-down operation; CT1 = reference = low voltage side LV)
-X1.2
P1 7 SYMAP-Compact+
S1
P2 S2
8
P1 9
S1
! ! CT2-M/P
HV = W1 = Primary W1"
P2 S2
10
P1 11
S1
P2 S2
12
Current transformer:
CT1
HV Primary [P660] = 1000A
Secondary [P661] = 1A
YN CT1-M: Direction L1 (Measuring) [P662] = 0
CT1-M: Direction L2 (Measuring) [P663] = 0
YNd5 CT1-M: Direction L3 (Measuring) [P664] = 0
CT1-P: Direction L1 (Protection) [P665] = 0
CT1-P: Direction L2 (Protection) [P666] = 0
d5 CT1-P: Direction L3 (Protection) [P667] = 0
Assignment [P674] = W2
LV CT2
Primary [P660] = 200A
Secondary [P661] = 1A
CT2-MP: Direction L1 [P671] = 0
CT2-MP: Direction L2 [P672] = 0
CT2-MP: Direction L3 [P673] = 0
-X1.1 Assignment [P674] = W1
P2 1
S2 Reference values:
Primary W1
Connection type [P600] = Y
P1 S1 Star point grounding [P601] = earthed
2 Voltage (L-L) [P602] = 10000V
P2 3
! ! S2
LV = W2 = Secondary W2" CT1-M/P Secondary W2
Connection type [P610] = d
P1 S1 Phase shift [P611] = 5
4 Star point grounding [P612] = isolated
P2 5 Voltage (L-L) [P613] = 400V
S2
P1 S1
6
-X1.1
P1 1 SYMAP-Compact+
S1
P2 S2
2
P1 3
S1
CT1-M/P
W1 = Primary W1"
P2 S2
4
P1 5
S1
P2 S2
6
Current transformer:
CT1
Primary [P660] = 200A
Secondary [P661] = 1A
CT1-M: Direction L1 (Measuring) [P662] = 0
CT1-M: Direction L2 (Measuring) [P663] = 0
G CT1-M: Direction L3 (Measuring) [P664] = 0
CT1-P: Direction L1 (Protection) [P665] = 0
3~ CT1-P: Direction L2 (Protection) [P666] = 0
CT1-P: Direction L3 (Protection) [P667] = 0
Assignment [P674] = W1
CT2
Primary [P660] = 200A
Secondary [P661] = 1A
CT2-MP: Direction L1 [P671] = 0
-X1.2
CT2-MP: Direction L2 [P672] = 0
P2 7 CT2-MP: Direction L3 [P673] = 0
S2
Assignment [P674] = W2
Reference values:
P1 S1 Primary W1
8
Connection type [P600] = none
P2 9
S2 Star point grounding [P601] = isolated
CT2-M/P Voltage (L-L) [P602] = 400V
W2 = Secondary W2" S1
P1 10 Secondary W2
11 Connection type [P610] = none
P2 S2 Phase shift [P611] = 0
Star point grounding [P612] = isolated
Voltage (L-L) [P613] = 400V
P1 S1
12
The single error currents IF1, IF2 and IF3 add up to a total error current IF, which can be shown
as differential current Id depending on the through-current ID as error current characteristic
curve. The through-current ID represents the power led though the object to protect i.e. in case
of increased load or a fault outside the protection range the operational differential current I d
raises as well.
The error current characteristic curve may be represented by the differential protection device
via tripping characteristic with double bend.
Id/In
ve
g cur
p pin IF3 : total fault current CTs
Tri stic
cteri
h ara
au lt c
al f IF2 : CT ratio, tap changer
Re (variable transformer)
ID/In
Since through-current ID cannot be directly measured, the so-called stabilization current Istab will
be introduced which is a calculated variable. Istab is calculated as follows:
I stab I 1 I 2
Id I1 I 2
NOTE: The reference directions of the currents I1 and I2 are defined acc. to Figure 3-208.
Range 1: constant tripping value (gradient factor = 0) up to a settable value for the
stabilization current (see parameters Is0 setting [P1992]; Id0 setting [P1995])
Range 2: stabilized tripping characteristic with 1st gradient factor (see parameters Is1
setting [P1993]; Id1 setting [P1996])
Range 3: stabilized tripping characteristic with 2nd gradient factor (see parameters Is2
setting [P1994]; Id2 setting [P1997])
Id eff/In
Tripping range
Id>>
Id2 setting"
Id1 setting"
Blocking range
Id0 setting"
(IS res")
100%
IK Ir ,
uK
with:
Ir: transformer rated current
uK: relative short-circuit voltage of the transformer
Consequently, in case of an external fault, the short-circuit current caused by the transformer is
never higher than the transformers short-circuit current and the differential current thus attains
a maximum value. In case of a fault outside the protection zone, the maximum differential
current occurs with a single-end, total transformer saturation since, in this case, the short-circuit
current caused by the transformer equals the differential current.
In case of a fault inside the protection zone (i.e. in the transformer) the short-circuit current and,
consequently, the differential current as well could attain higher values. In these cases, the
SYMAP-Compact+ activates instantaneous tripping without stabilization.
The setting value of parameter Id>> [P2022] of the high-current stage should be selected
according to the height of the transformers short-circuit range.
The inrush current, however, is not to be seen as a fault event which should lead to tripping on
faults but is a phenomenon against which the differential protection function should be stabilized
i.e. made more insensitive. A characteristic for the inrush current is the amount of 2nd harmonic
in the primary winding phase current. The highest contents for the inrush current are to be
observed for the 2nd harmonic.
Via Fourier analysis, the SYMAP-Compact+ evaluates the contents of the 2nd harmonic
(100Hz) and upon exceeding of a settable value for the ratio of the 2nd harmonic and the
fundamental of current I100Hz/I50Hz, temporary blocking of the pickup of the differential protection
function is activated according to the settings of the harmonic wave stabilization ANSI 95i
function. Blocking is maintained as long as the pick-up value for the 2nd harmonic is fallen below
or the maximum time slot for blocking has elapsed.
An important criterion for the overrexcited operation of the transformer is the 4th harmonic wave
(5th harmonic) in the phase current of the primary winding.
Via Fourier analysis, the SYMAP-Compact+ evaluates the contents of the 5th harmonic and
upon exceeding of a settable value for the ratio of the 5th harmonic in relation to the
fundamental of current I250Hz/I50Hz, temporary blocking of the pickup of the differential protection
function is activated according to the settings of the harmonic wave stabilization ANSI 95i
function. Blocking is maintained as long as the pick-up value for the 5th harmonic is fallen below
again or the maximum time slot for blocking has elapsed.
Depending on the cause of CT saturation and the fault location (inside or outside the protection
zone), the protection device has to trip or block.
In case a fault outside the protective zone forces CT saturation, the operating characteristic of
differential current/stabilizing current (Id/Istab) is fundamentally different from that behaviour of a
fault inside the protective zone with CT saturation. Such dynamic operating characteristic of
Id/Istab can be described by a locus curve.
To detect CT saturation SYMAP-Compact+ evaluates the locus curve of Id/Istab. The diagrams
discussed below represents different fault situations for an object tob e protected, and with one-
sided CT saturation.
Regarding faults inside the protective zone, differential current increase proportionally to the
stabilizing current (Id = Istab). Hence follows, that the operating point of the locus curve, e.g. (1) to
(6), proceeds along a straight line with a gradient of 100%.
Id eff/In
Tripping range 3
2
Blocking range
1
6
IStab/In
Figure 3-218 Locus diagram of fault within the protective zone, without CT saturation
Faults outside the protective zone which do not cause CT saturation yet, stabilisation current
increases rapidly, whereas differential current remains quite low. As consequence, the
operating point of the locus curve, e.g. (1) to (6), proceeds along a straight line with a slight
gradient (the following diagram shows an idealized locus with a gradient of 0%).
Id eff/In
Tripping range
Blocking range
5 4
6
3
1 2
IStab/In
Figure 3-219 Locus diagram of fault outside the protective zone, without CT saturation
For faults outside the protective zone which do cause CT saturation, here, stabilisation current
increase rapidly, too, and dfferential current remains at first at a low level. Hence, the operating
points proceed along the straight line towards such fault curve corresponding to faults outside
the protective object and without CT saturation: operating points (1) and (2). As soon as CT
saturation emerges: operating point (2), stabilisation current decreases combined with an
increase of differential: operating point (3). When exceeding the configured tripping curve: (4),
the differential protection function will trip.
To avoid unwanted tripping, SYMAP-Compact+ evaluates the locus curve with reference to the
operating characteristic of Id/Istab in case of a fault. The locus curve displayed above represents
the fundamental criterion to detect faults outside the protective zone and causing one-sided CT
saturation. The range CT saturation stabilisation is defined by parameters [P2005] to [P2008].
The locus curve has to enter the CT saturation stabilisation range definitely, before the
operating point will skip ahead to the tripping zone. If this is the case, differential protection trip
will be blocked.There is a maximum time window for blocking available, which is configurable by
parameter CT saturation blocking time [P2004].
Id eff/In
Tripping range
4 Blocking range
5
3
CT saturation stabilisation
[P2007] CT saturation Id0"
Begin of CT saturation
6 1 2
IStab/In
[P2005] CT saturation Is0" [P2006] CT saturation Is1"
Figure 3-220 Locus diagram of fault outside the protective zone, with CT saturation
NOTE: In dependence of the transformer vector shift group, zero compensation can be
activated/deactivated by the following parameters:
W1 zero compensation [P9436],
W2 zero compensation [P9437].
These parameters are located in the submenu: SYSTEM\Measuring\Differential.
Main Menu\Parameters\PROTECTION\
Figure 3-221 ANSI 87 Protection parameters [P] and events [E] of SET 1
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
SET PARAMETERS
The following SET PARAMETERS of the current differential protection exist only once in each
of the four parameter sets. Thus, the SET PARAMETERS apply to protection STEP 1 and
protection STEP 2 of one parameter SET.
P1977 Mode :
Application for current differential protection; in dependence of the kind of operating
device to be protected by current differential protection, one of the following applications
can be choosen:
Trafo: application: Transformer differential protection
Block prot.: application: Block protection (protective zone covers the generator
and the block transformer)
Mot/Gen: application: Motor/Generator differential protection
NOTE: For Transformer differential protection the vector shift group and possibly
also zero current compensation (parameter Star point grounding) has to be
considered. Corresponding parameters are to be found in the menu:
SYSTEM\Nominals\Reference values
P1978 Hystersis :
This parameter [P1978] determines the reset limit for the pick-up event ANSI87-1
pickup [E1652] of the stabilized current differential protection element (STEP1) or
ANSI87-2 pickup [E1672] for the unstabilized high-set current differential protection
element (STEP 2). At the moment the characteristic value (phase current) falls below the
reset limit, the activated pick-up event [E1652] or [E1672] will be deactivated.
NOTE: Parameters [P1992] to [P1997] are to be set as a percentage of the nominal value of
the characteristic quantity (phase current). The nominal value of the characteristic
quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P624] are located in
submenu: SYSTEM\Nominals\Reference values.
In combination with parameter Id2 setting [P1997] parameter [P1994] defines the
second point to determine the slope of the third straight line segment of the tripping
curve of the stabilized current differential protection element (STEP 1). An ending point
of the third straight line segment can be set by using parameter Id>> [P2022] which
brings forth a corresponding stabilisation current (IS res). Then, the third straight line
segment is valid for a value range of the stabilisation current between Istab = Is1 setting
and Istab = IS res.
The range for CT saturation stabilisation can be defined by four parameters: [P2005] to
[P2008].
NOTE: Parameters [P2005] to [P2008] are to be set as a percentage of the nominal value of
the characteristic quantity (phase current). The nominal value of the characteristic
quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P624] are located in
submenu: SYSTEM\Nominals\Reference values.
P2022 Id>>
This parameter defines the pick-up value for the characteristic variable (differential
current Id) of the high-set current differential protection element (STEP 2), disregarding
the height of the stabilization current Istab .
If the characteristic variable exceeds the value set for parameter [P2022], the trip event
ANSI87-2 trip [E1673] will be activated disregarding the stabilized tripping
characteristic. This event can be used for alarm or output control purposes.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
characteristic quantity (phase current). The nominal value of the characteristic
quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P624] are
located in submenu: SYSTEM\Nominals\Reference values.
Main Menu\Parameters\PROTECTION\
Figure 3-222 ANSI 95i Protection parameters [P] and events [E] of SET 1
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: The maximum phase current limit for harmonics stabilisation is to be set as a
percentage of the nominal value of the characteristic quantity (phase current).
The nominal value of the characteristic quantity is to be set by parameter:
Current [P604], for primary side W1 or
Current [P614], for secondary side W2
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P624] are
located in submenu: SYSTEM\Nominals\Reference values.
P1748 Mode
Parameterizable blocking mode:
1-phase: In case that only in one phase the limit of parameter(s) 2H Limit
[P1749] or/and 5H Limit [P1750] is(are) exceeded, then, protection
pickup of those protective functions with activated Harmonic stabilisation
is blocked only in the affected phase.
3-phase: In case that at least in one phase the limit of parameter(s) 2H Limit
[P1749] or/and 5H Limit [P1750] is(are) exceeded, then, protection
pickup of those protective functions with activated Harmonic stabilisation
is blocked in all three phases.
P1749 2H Limit
Pick-up value of 2nd Harmonic stabilisation; when the characteristic quantity (2. harmonic
portion in the phase currrents) exceeds the set value of parameter [P1749] in one ore
more phases, then according to the selected setting option of parameter Mode
[P1748] the following corresponding blocking event(s) is(are) activated:
ANSI95i-CT1 L1 blocked by 2H [E1473] and/or
ANSI95i-CT1 L2 blocked by 2H [E1474] and/or
ANSI95i-CT1 L3 blocked by 2H [E1475]
P1750 5H Limit
Pick-up value of 5th Harmonic stabilisation; when the characteristic quantity (5. harmonic
portion in the phase currrents) exceeds the set value of parameter [P1750] in one ore
more phases, then according to the selected setting option of parameter Mode
[P1748] the following corresponding blocking event(s) is(are) activated:
ANSI95i-CT1 L1 blocked by 5H [E1476] and/or
ANSI95i-CT1 L2 blocked by 5H [E1477] and/or
ANSI95i-CT1 L3 blocked by 5H [E1478]
Main Menu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS
represented below are described in the following in detail as examples.
SET PARAMETERS
The following SET PARAMETERS of the CLD function exist only once.
I< OR Event: enables CLD function using criterion I< OR Event for working
principle, at the moment that the characteristic quantity (phase
current) falls below the set value of parameter Trigger limit
[P3328] in all three phases or the trigger event which is assigned
to parameter Trigger event [P3331] is activated, event CLD
pickup [E2332] is activated, or
I< AND Event: enables CLD function using criterion I< AND Event for working
principle, at the moment thatthe characteristic quantity (phase
current) falls below the set value of parameter Trigger limit
[P3328] in all three phases and the trigger event which is assigned
to parameter Trigger event [P3331] is activated, event CLD
pickup [E2332] is activated.
P3326 Blocking
CLD function can be completely blocked by any active event. For blocking, the number
related to this blocking event has to be assigned to parameter [P3326]. Blocking is only
effective, however, as long as the blocking event is active. As soon as blocking is active,
event CLD blocked [E2331] is activated. If the blocking event turns inactive, blocking is
abandoned and protective function is effective again. Then, event [E2331] is deactivated
automatically.
If blocking of the CLD is not required, set this parameter to 0.
P3327 CT reference
Depending on the SYMAP-Compact(+) device variant CLD function can be assigned to
a certain current measurement input (CT1 or CT2). Parameter [P3327] determines the
current measurement input which will provide measurement values as characteristic
quantity (phase current) to CLD function:
CT1: current input CT1
CT2: current input CT2
NOTE: Parameter Trigger limit [P3328] is only valid for the following setting options:
I< and
I< OR Event and
I< AND Event
of parameter CLD function [P3325].
pickup event CLD pickup [E2332] is activated and the Delay time [P3329] for
activating event CLD cold load [E2333] starts.
Trigger event of criterion Event for detecting a cold load situation; criterion Event can
be fulfilled by any active event. For this, the number related to this trigger event has to
be assigned to parameter [P3331].
APPLICATION NOTE: It is recommended to assign the feedback event number of the
circuit breaker (e.g. OFF-feedback [E6011] of breaker no. 1)
to parameter Trigger event [P3331] to indicate cold load
situation while the circuit breaker is off.
NOTE: Parameter Trigger event [P3331] is only valid for setting options:
Event and
I< OR Event and
I< AND Event
of parameter CLD function [P3325].
pickup event CLD pickup [E2332] is activated and the Delay time [P3329] for
activating event CLD cold load [E2333] starts.
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group sub-functions such
as Symmetry check and Diff check. Hence, the parameter descriptions of
parameter SET 1 represented below are described in the following in detail as
examples.
CAUTION: When Holmgreen connection is used for current measurement and/or all three
CTs fail in a fully balanced 3-phase system, then function CTS Current
Transformer Supervision has to be deactivated!
IQ = IL,min/IL,max
In the event that quotient IQ falls below the set minimum permitted value IQ min.perm., it may be
concluded that there is a fault in one or more phase current paths of CT1.
P2630 Function
This parameter enables/disables sub-function Symmetry check of protective function
Current transformer supervision CTS where:
OFF: disables or
ON: enables the supervision function.
P2631 Blocking
Function Symmetry check of protective function Current transformer supervision CTS
can be completely blocked by any active event. For blocking, the number related to this
blocking event has to be assigned to parameter [P2631]. Blocking is only effective,
however, as long as the blocking event is active. As soon as blocking is active, event
CTS-1 symmetry check blocked [E2131] is activated. If the blocking event turns
inactive, blocking is abandoned and protective function is effective again. Then, event
[E2131] is deactivated automatically.
If blocking of function Symmetry check is not required, set this parameter to 0.
Current check for the presence of a minimum load as first criterion to detect a faulty current
transformer path of CT1
NOTE: The minimum limit of measured process quantity phase current is to be set
as a percentage of the nominal value of the process quantity. The nominal
value of the process quantity is to be set by parameter:
Current [P604], for primary side W1,
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P624] are
located in submenu: SYSTEM\Nominals\Reference values.
Check for current loss as second criterion to detect a faulty current transformer path of CT1
the pick-up event CTS-1 symmetry fault [E2132] is activated and Delay time is being
started.
As soon as the pick-up event CTS-1 symmetry fault [E2132] is active and Delay time
run down, trip event [E2133] will be activated. This event can be used for alarm or output
control purposes. Right after protection trip, and, as soon as faulty conditions will no
longer be existent, pick-up event [E2132] and trip event [E2133] are being deactivated
automatically.
In case that the characteristic quantity (quotient of the minimum and maximum phase
current IL,min/IL,max) exceeds the pick-up value (Symmetry quotient.) of the supervision
function Symmetry check before the trip delay time (Delay time) has run down, the
timer of Delay time will be stopped, the counter value is being reset to zero, and the
pick-up event [E2132] will be deactivated.
If the characteristic quantity subsequently exceeds the pick-up value (Symmetry
quotient.), then, the pick-up event CTS-1 symmetry fault [E2132] is activated and
Delay time is being started again.
I = IG1 3I0 = 0
In the event that quotient I falls below the set minimum permitted value I,max.perm.., it may be
concluded that there is a fault
in the ground current path CT-GND1 or
in one ore more of the phase current paths of CT1.
When supervision function Diff check is enabled by parameter [P2638], then event
CTS-1 diff check active [E2135] is activated.
P2639 Blocking
Function Diff check of protective function Current transformer supervision CTS can be
completely blocked by any active event. For blocking, the number related to this blocking
event has to be assigned to parameter [P2639]. Blocking is only effective, however, as
long as the blocking event is active. As soon as blocking is active, event CTS-1 diff
check blocked [E2136] is activated. If the blocking event turns inactive, blocking is
abandoned and protective function is effective again. Then, event [E2136] is deactivated
automatically.
If blocking of function Diff check is not required, set this parameter to 0.
the pick-up event CTS-1 diff fault [E2137] is activated and Delay time is being started.
As soon as the pick-up event CTS-1 diff fault [E2137] is active and Delay time run
down, trip event [E2138] will be activated. This event can be used for alarm or output
control purposes. Right after protection trip, and, as soon as faulty conditions will no
longer be existent, pick-up event [E2137] and trip event [E2138] are being deactivated
automatically.
In case that the characteristic quantity (total current difference I = IG1 3I0) exceeds
the pick-up value (Diff current limit.) of the supervision function Diff check before the
trip delay time (Delay time) has run down, the timer of Delay time will be stopped, the
counter value is being reset to zero, and the pick-up event [E2137] will be deactivated.
If the characteristic quantity subsequently exceeds the pick-up value (Diff current limit.),
then, the pick-up event CTS-1 diff fault [E2137] is activated and Delay time is being
started again.
IL max
(IL1; IL2; IL3)
Protective function DC voltage monitoring DCVM) is for monitoring the DC voltage for instance
of a batterie in view of undervoltage and overvoltage. Ground faults of the positive and negative
potential of the DC voltage can be monitored by subfunction Ground fault detection.
NOTE: When using subfunction Ground fault detection it is required to connect terminal N
of SYMAP-Compact(+) device (SYMAP-Compact: -X1.2:18; SYMAP-Compact+: -
X1.2:26) to ground potential!
Basically, each of the voltage measuring inputs PT1, PT2 or PT3 can be used for DC voltage
measurement. Connection diagram is as follows:
+ 17 UL1 PT1
- UDC SYMAP-Compact F3
19 UL2
21 UL3
UDC+ UDC-
26 N
15
PT-GND1
16
MainMenu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in detail in the following
examples.
SET PARAMETERS
The following SET PARAMETERS of the DCVM DC voltage monitoring function exist only
once in each of the four parameter sets. Thus, the SET PARAMETERS apply to all of the 6
protection STEPS of one parameter SET.
NOTE: Each protection step can be used individually as overvoltage and/or undervoltage
protection. Working principle should be set by parameters [P3490] to [P3493].
Subfunction Ground fault detection can be configured via parameters [P3494] to
[P3498]
For selection options PT1, PT2 or PT3 event DCVM-1 step active [E2397] is
activated.
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
characteristic quantity (DC voltage) set by parameter Nominal DC voltage
[P3489].
NOTE: The pick-up value is to be set as a percentage of the nominal value of the
characteristic quantity (DC voltage) set by parameter Nominal DC voltage
[P3489].
In case that the characteristic quantity (voltage) of the first DCVM DC voltage
monitoring step exceeds the reset limit (Hysteresis = 1% Un, not parameterizable!)
before the trip delay time (Delay time) has run down, the timer of Delay time will be
stopped and the counter value is set to zero.
UDC/Un
Hysteresis = 1% Un
100%
t
[E2399]
DCVM-1 undervoltage pickup
0
t
t
[E2400]
DCVM-1 Overvoltage trip
0
t
Figure 3-229 DCVM: Overvoltage protection UDC tripping and reset characteristic
UDC/Un
100%
Hysteresis = 1% Un
t
[E2401]
DCVM-1 undervoltage pickup
0
t
[P3493]
Delay time
[E2402] t
DCVM-1 undervoltage trip
0
t
Figure 3-230 DCVM: Undervoltage protection UDC tripping and reset characteristic
NOTE: The pick-up value is to be set as a percentage of the half of the nominal value
of the characteristic quantity (DC voltage) set by parameter Nominal DC
voltage [P3489].
NOTE: The pick-up value is to be set as a percentage of the half of the nominal value
of the characteristic quantity (DC voltage) set by parameter Nominal DC
voltage [P3489].
UDC+/Un
100%
Hysteresis = 1% Un
t
[E2403]
DCVM-1 GF +pole pickup
0
t
[P3496]
Delay time
[E2404] t
DCVM-1GF +pole trip
0
t
Figure 3-231 DCVM: Ground Fault detection UDC+ tripping and reset characteristic
UDC-/Un
100%
Hysteresis = 1% Un
t
[E2405]
DCVM-1 GF -pole pickup
0
t
[P3498]
Delay time
[E2406] t
DCVM-1 GF -pole trip
1
0
t
Figure 3-232 DCVM: Ground Fault detection UDC tripping and reset characteristic
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group sub-functions such
as Symmetry check, Fuse failure check and General check. Hence, the
parameter descriptions of parameter SET 1 represented below are described in the
following in detail as examples.
UQ = UL-L,min/UL-L,max
In the event that quotient UQ falls below the set minimum permitted value UQ min.perm., it may be
concluded that there is a fault in one or more phase-to-phase voltage circuits of PT1.
P2540 Function
This parameter enables/disables sub-function Symmetry check of protective function
Potential transformer supervision PTS where:
OFF: disables or
ON: enables the supervision function.
NOTE: In case that no voltage measurement is possible, caused by locating the PTs
below the circuit breaker, and which is open, then, supervision of voltage
symmetry must be blocked by a suitable event. For this, the related number of
such blocking event has to be assigned to parameter [P2541].
P2541 Blocking
Function Symmetry check of protective function Potential transformer supervision
PTS can be completely blocked by any active event. For blocking, the number related to
this blocking event has to be assigned to parameter [P2531]. Blocking is only effective,
however, as long as the blocking event is active. As soon as blocking is active, event
PTS-1 symmetry check blocked [E2071] is activated. If the blocking event turns
inactive, blocking is abandoned and protective function is effective again. Then, event
[E2071] is deactivated automatically.
If blocking of function Symmetry check is not required, set this parameter to 0.
Voltage check for the presence of a minimum measuring voltage as first criterion to detect a
faulty voltage transformer circuit of PT1
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
Check for voltage unsymmetry as second criterion to detect a faulty potential transformer circuit
of PT1
the pick-up event PTS-1 symmetry fault [E2072] is activated and Delay time is being
started.
As soon as the pick-up event PTS-1 symmetry fault [E2072] is active and Delay time
run down, trip event [E2073] will be activated. This event can be used for alarm or output
control purposes. Right after protection trip, and, as soon as faulty conditions will no
longer be existent, pick-up event [E2072] and trip event [E2073] are being deactivated
automatically.
In case that the characteristic quantity (quotient of the minimum and maximum phase-to-
phase voltage UL-L,min/UL-L,max) exceeds the pick-up value (Symmetry quotient.) of the
supervision function Symmetry check before the trip delay time (Delay time) has run
down, the timer of Delay time will be stopped, the counter value is being reset to zero,
and the pick-up event [E2072] will be deactivated.
If the characteristic quantity subsequently falls below the pick-up value (Symmetry
quotient.), then, the pick-up event PTS-1 symmetry fault [E2072] is activated and
Delay time is being started again.
For supervision of a potential transformer fuse failure (tripping of miniature circuit breaker MCB),
function Fuse failure check provides the following sub-functions:
Sub-function Asymmetric fuse failure: for detection of 1-phase and 2-phase faults in the
secondary voltage measurement circuit of PT1
Sub-function 3 Phase fuse failure: for detection of a 3-phase fault in the secondary
voltage measurement circuit of PT1 (3-pole
PTfuse fail)
Sub-function Voltage difference: for detection of 1-phase and 2-phase faults in the
secondary voltage measurement circuit of PT1 or
in the secondary voltage measurement circuit of
PT-GND1
NOTE: Sub-functions Asymmetric fuse failure and 3 Phase fuse failure are only being
activated for the following parameter settings:
Function / Source [P2547] = CT1 or
Function / Source [P2547] = CT2!
Then, parameter [P2556] of function Fuse failure check will not apply!
A1-phase or 2-phase fault is being detected if there is a measured minimum load and an
impermissible voltage unsymmetry, but no impermissible current symmetry.
A 3-phase fault is being detected in case of an impermissibly high voltage drop at PT1 and if
there was no significant, impermissible current increase at current measuring input CT1 within
one measuring period.
When supervision function Fuse failure check is enabled by parameter [P2547], then
event PTS-1 fuse fail check active [E2076] is activated.
P2548 Blocking
Function Fuse failure check of protective function Potential transformer supervision
PTS can be completely blocked by any active event. For blocking, the number related to
this blocking event has to be assigned to parameter [P2548]. Blocking is only effective,
however, as long as the blocking event is active. As soon as blocking is active, event
PTS-1 fuse failure check blocked [E2077] is activated. If the blocking event turns
inactive, blocking is abandoned and protective function is effective again. Then, event
[E2077] is deactivated automatically.
If blocking of function Fuse failure check is not required, set this parameter to 0.
Check of phase current symmetry as first criterion to detect 1-phase and 2-phase tripping of
miniature circuit breakers (MCB) Asymmetric fuse failure
fall below the set value of parameter Symmetric current limit [P2549], the first criterion
for detecting 1-phase or 2-phase tripping of MCBs.
Current check for a minimum load as second criterion to detect 1-phase and 2-phase tripping of
miniature circuit breakers (MCB) Asymmetric fuse failure
Check of phase current symmetry as third criterion to detect 1-phase and 2-phase tripping of
miniature circuit breakers (MCB) Asymmetric fuse failure
exceed the set value of parameter Symmetric voltage limit [P2551], the third criterion
for detecting 1-phase or 2-phase tripping of MCBs is fulfilled.
Check of voltage loss as first criterion to detect a 3-phase tripping of miniature circuit breakers
(MCB) 3-Phase fuse failure
Current check for high-current faults as second criterion to detect a 3-phase tripping of
miniature circuit breakers (MCB) 3-Phase fuse failure
NOTE: The second criterion to detect a 3-phase tripping of miniature circuit breakers (MCB)
is fulfilled only if a minimum load is measured (exceeding of minimum limit set by
NOTE: Sub-function Voltage difference is only being activated for parameter setting:
Function / Source [P2547] = PT-GND1.
Then, parameters [P2549] to [P2555] of function Fuse failure check will not apply!
Function Voltage difference calcultes the residual voltage difference U between the
measured ground voltage (PT-GND1) and the residual current 3U0 calculated via the measured
phase currents of PT1 (3U0 = UL1-E + UL2-E + UL2-E). In case that all the voltage circuits of PT1
and PT-GND1 are in proper conditions and any PT tolerances are being neglected, it is:
U = UG 3U0 = 0
In the event that quotient U falls below the set minimum permitted value U,max.perm., it may be
concluded that there is a fault
in the ground voltage circuit of PT-GND1 or
in one or two of the phase voltage circuits of PT1 (1-pole or 2-pole fuse fail).
the pick-up event PTS-1 fuse failure [E2079] is activated and Delay time is being
started.
As soon as the pick-up event PTS-1 fuse failure [E2079] is active and Delay time run
down, trip event [E2080] will be activated. This event can be used for alarm or output
control purposes. Right after protection trip, and, as soon as faulty conditions will no
longer be existent, pick-up event [E2079] and trip event [E2080] are being deactivated
automatically.
In case the voltage and current conditions fail to apply with the foregoing failure
conditions before the trip delay time (Delay time) has run down, the timer of Delay
time will be stopped, the counter value is being reset to zero, and the pick-up event
[E2079] will be deactivated.
If the failure conditions subsequently are fulfilled again, then, the pick-up event [E2079]
is activated and Delay time is being started again.
When supervision function General check is enabled by parameter [P2561], then event
PTS-1 general check active [E2084] is activated.
P2562 Blocking
Function General check of protective function Potential transformer supervision PTS
can be completely blocked by any active event. For blocking, the number related to this
blocking event has to be assigned to parameter [P2562]. Blocking is only effective,
however, as long as the blocking event is active. As soon as blocking is active, event
PTS-1 general check blocked [E2085] is activated. If the blocking event turns inactive,
blocking is abandoned and protective function is effective again. Then, event [E2085] is
deactivated automatically.
If blocking of function General check is not required, set this parameter to 0.
Check of voltage condition as first criterion to detect a faulty voltage transformer circuit of PT1
Current check for the presence of a minimum load as second criterion to detect a faulty voltage
transformer circuit of PT1
Current check for short circuit as third criterion to detect a faulty voltage transformer circuit of
PT1
Circuit breaker (CB) position Closed as an alternative to current check for a minimum load
the pick-up event PTS-1 general failure [E2086] is activated and Delay time is being
started.
As soon as the pick-up event PTS-1 general failure [E2086] is active and Delay time
run down, trip event [E2087] will be activated. This event can be used for alarm or output
control purposes. Right after protection trip, and, as soon as faulty conditions will no
longer be existent, pick-up event [E2086] and trip event [E2087] are being deactivated
automatically.
In case the voltage and current conditions fail to apply with the foregoing failure
conditions before the trip delay time (Delay time) has run down, the timer of Delay
time will be stopped, the counter value is being reset to zero, and the pick-up event
[E2086] will be deactivated.
If the failure conditions subsequently are fulfilled again, then, the pick-up event [E2086]
is activated and Delay time is being started again.
Main Menu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
P3345 Function
This parameter enables/disables the first protection step of the SOTF function where:
OFF: disables the first protection step of SOTF function or
I<: enables the first protection step of SOTF function using criterion
I< for working principle, at the moment that the characteristic
quantity (phase current) falls below the set value of parameter
Trigger limit [P3348] in all three phases, event SOTF-1 trigger
[E2340] is activated or
Event: enables the first protection step of SOTF function using criterion
Event for working principle, at the moment that the trigger event
which is assigned to parameter Trigger event [P3353] is
activated, event SOTF-1 trigger [E2340] is activated or
I< OR Event: enables the first protection step of SOTF function using criterion
I< OR Event for working principle, at the moment the
characteristic quantity (phase current) falls below the set value of
parameter Trigger limit [P3348] in all three phases or the trigger
event which is assigned to parameter Trigger event [P3353] is
activated, event SOTF-1 trigger [E2340] is activated, or
I< AND Event: enables the first protection step of SOTF function using criterion
I< AND Event for working principle, at the moment the
characteristic quantity (phase current) falls below the set value of
parameter Trigger limit [P3348] in all three phases and the
trigger event which is assigned to parameter Trigger event
[P3353] is activated, event SOTF-1 trigger [E2340] is being
activated.
P3347 CT reference
Depending on the SYMAP-Compact(+) device variant the first protection step of the
SOTF function can be assigned to a certain current measurement input (CT1 or CT2).
Parameter [P3347] determines the current measurement input which will provide
measurement values as characteristic quantity (phase current) to the SOTF function:
CT1: current input CT1
CT2: current input CT2
NOTE: Parameter Trigger limit [P3348] is only valid for the following setting options:
I< and
I< OR Event and
I< AND Event
of parameter Function [P3345].
NOTE: Parameter Trigger event [P3353] is only valid for setting options:
Event and
I< OR Event and
I< AND Event
of parameter Function [P3345].
NOTE: Parameter Trigger pulse time [P3350] is only valid for setting option ON of
parameter Trigger pulse [P3349].
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides only one protection STEP and, as
consequence, only one group of parameters. Thus, SET PARAMETERS are equal to
STEP parameters. The protection parameters of SET 1 represented below are
described in the following in detail as examples.
P3475 Function
This parameter enables/disables TIG-Transient/Intermittent Ground Fault protection
function whereby the setting:
OFF: disables or
ON: enables the protective function.
P3476 Blocking
TIG-Transient/Intermittent Ground Fault protection can be completely blocked by any
active event. For blocking, the number related to this blocking event has to be assigned
to parameter [P3476]. Blocking is only effective, however, as long as the blocking event
is active. As soon as blocking is active, event TIG blocked [E2391] is activated. If the
blocking event turns inactive, blocking is abandoned and TIG function is effective again.
Then, event [E2391] is deactivated automatically.
NOTE: The assignment of the voltage measurement input (PT1, PT2, PT3 or PT-
GND1) to the ground current measurement input CT1, CT2 or CT-GND1 is to
be done by the following parameters (referring to the setting options of
parameter [P3477]), in the submenu SYSTEM\Measuring\Power:
PT reference [P9419], for GND Power_CT1
PT reference [P9422], for GND Power_CT2 and
PT reference [P9428], for GND Power_CT-GND1
To measure ground current direction correctly, the required zero energy flow
direction is to be defined by following parameters:
Direction [P9420], for GND Power_CT1 and
Direction [P9423], for GND Power_CT2
Direction [P9429], for GND Power_CT-GND1.
NOTE: In case that residual voltage is to be calculated by voltage measuring via PT1,
PT2 or PT3 it is required to connect terminal N of SYMAP-Compact(+)
device (SYMAP-Compact: -X1.2:18; SYMAP-Compact+: -X1.2:26) to ground
potential!
For test purposes via voltage generator test equipment it is required to
connect terminal N of SYMAP-Compact(+) device to the neutral potential
of the voltage test equipment!
P3478 Direction
Selction of operating mode according to the direction of the TIG-Transient/Intermittent
Ground Fault protection; the working principle for direction detection is as follows:
From the moment at which the maximum ground current sample IG,max causes the
exceeding of the set value of parameter Relative limit [P3481], the arithmetical mean
value UG,mean of 6 consecutive samples of the ground voltage UG will be calculated. Then
the signs of IG,max and UG,mean will be compared.
Function TIG-Transient/Intermittent Ground Fault is optionally adjustable as:
Non-directional: The protection function trips in forward and backward direction
Forward: The protection function trips only in forward direction; therefore,
IG,max and UG,mean must be of the same sign (+/+ or -/-).
Backward: The protection function trips only in forward direction; therefore,
IG,max and UG,mean must be of the different signs (+/- or -/+).
Absolute ground current value as first criterion to detect a transient/intermittent ground fault
Relative ground current value as second criterion to detect a transient/intermittent ground fault
Pickup logic
As soon as:
function TIG-Transient/Intermittent Ground Fault protection is activated via parameter
[P3475] and
the measured value of the ground current IG,TRMS exceeds the set value of parameter
Absolute limit [P3480] and
the calculated quotient of the quotient of the absolute value of the maximum IG sample per
cycle and the TRMS value of the ground current IG exceeds the set value of parameter
Relative limit [P3481] and
the measured ground voltage UG exceeds the set value of parameter Min. ground voltage
[P3479] and
optionally (only in case that parameter Direction [P3478] Non-directional): the
measured angle between ground current IG and reference ground voltage UG accords to the
selected direction mode via parameter Direction [P3478] and
blocking of function TIG-Transient/Intermittent Ground Fault is not activated by the
blocking event of parameter [P3476]
the pick-up event TIG pickup [E2392] is activated, Reset time is being started and the rising
edge of the pickup signal increases the counter for detection of an intermittent ground fault.
Main Menu\Parameters\PROTECTION\
Parameter description:
The following parameter descriptions refer to all protection parameters of one parameter set.
NOTE: Each of the four parameter sets always provides the same group of protection
parameters. Hence, the parameter descriptions of the SET PARAMETERS and the
parameters of STEP 1 represented below are described in the following in detail as
examples.
SET PARAMETERS
The following SET PARAMETERS of YG-Neutral Admittance Ground Fault Protection exist only
once in each of the four parameter sets. Thus, the SET PARAMETERS apply to all of the 6
protection STEPS of one parameter SET.
P2705 Function
This parameter enables/disables YG-Neutral Admittance Ground Fault protection where:
OFF: disables or
ON: enables the protective function.
P2706 Blocking
YG-Neutral Admittance Ground Fault protection can be completely blocked by any active
event. For blocking, the number related to this blocking event has to be assigned to
parameter [P2706]. Blocking is only effective, however, as long as the blocking event is
active. As soon as blocking is active, event YG blocked [E2181] is activated. If the
blocking event turns inactive, blocking is abandoned and protective function is effective
again. Then, event [E2181] is deactivated automatically.
If blocking of the YG-Neutral Admittance Ground Fault protection is not required, set this
parameter to 0.
P2707 CT source
Depending on the SYMAP-Compact(+) device variant the YG-Neutral Admittance
Ground Fault protection can be assigned to a certain current measurement input (CT1,
CT2 or CT-GND1).
Parameter [P2707] determines the current measurement input which will provide the
process quantity ground current IG needed for builing the protective criterion
(characteristic quantity such as: neutral admittance Y0, neutral conductance G0 or neutral
susceptance B0; see step parameters Function [P2715], [P2735], [P2755], [P2775],
[P2795] and [P2815]) to the YG-Neutral Admittance Ground Fault protection:
CT1: Calculation of residual voltage: IG = 3 x I0 = I1+I2+I3 by phase currents
measured via measurement input CT1,
CT2: Calculation of residual voltage: IG = 3 x I0 = I1+I2+I3 by phase currents
measured via measurement input CT2,
CT-GND1: Measurement input CT-GND1 (direct measurement of IG)
P2708 PT source
Depending on the SYMAP-Compact(+) device variant the YG-Neutral Admittance
Ground Fault protection can be assigned to a certain voltage measurement input (PT1,
PT2, PT3 or PT-GND1).
Parameter [P2708] determines the voltage measurement input which will provide the
process quantity residual voltage UG needed for builing the protective criterion
(characteristic quantity such as: neutral admittance Y0, neutral conductance G0 or neutral
susceptance B0; see step parameters Function [P2715], [P2735], [P2755], [P2775],
[P2795] and [P2815]) to the YG-Neutral Admittance Ground Fault protection:
PT1: Calculation of residual voltage: UG = 3 x U0 = UL1+UL2+UL3 by phase
voltages measured via measurement input PT1,
PT2: Calculation of residual voltage: UG = 3 x U0 = UL1+UL2+UL3 by phase
voltages measured via measurement input PT2,
NOTE: In case that residual voltage is to be calculated by voltage measuring via PT1,
PT2 or PT3 it is required to connect terminal N of SYMAP-Compact(+)
device (SYMAP-Compact: -X1.2:18; SYMAP-Compact+: -X1.2:26) to ground
potential!
For test purposes via voltage generator test equipment it is required to
connect terminal N of SYMAP-Compact(+) device to the neutral potential
of the voltage test equipment!
P2709 Direction
Internal adaption of measured Neutral-Admittance Y0 direction; to define the sign of the
complex phasor of Y0, the following setting options are available:
0: no change of sign, und
180: change of sign by 180
B0
Y0
Direction [P2709] = 0
Im
Re
G0
Y0'
Direction [P2709] = 180
'' = +15
' = -9
Y0''
B0
Y0
Y0'
Im
Re
G0
with:
Y0': Angle correction [P2710] = -9
Y0'': Angle correction [P2710] = +15
NOTE: The correction angle is not for transformer vector group matching!
Vector group matching is to be set by appropriate parameter setting in submenu
SYSTEM\Nominals\Reference values.
SET PARAMETERS
The following STEP parameters of the YG-Neutral Admittance Ground Fault protection exist
only once in each of the 6 independent protection STEPS. Thus, the SET PARAMETERS apply
only to one of the 6 protection STEPS of one parameter SET.
P2715 Function
This parameter disables/enables the first step of YG-Neutral Admittance Ground Fault
protection; enabling the first protection step is to be done by selecting the protective
criterion (characteristic quantity); whereas:
OFF: disables first protection step,
Yo: enables first protection step => protective criterion Neutral-Admittance,
Go: enables first protection step => protective criterion Neutral -Conductance,
Bo: enables first protection step => protective criterion Neutral -Susceptance.
P2716 Blocking
The first step of YG-Neutral Admittance Ground Fault protection can be blocked by any
active event. For blocking, the number related to this blocking event has to be assigned
to parameter [P2716]. Blocking is only effective, however, as long as the blocking event
is active. As soon as blocking is active, event YG-1 blocked [E2186]] is activated. If the
blocking event turns inactive, blocking is abandoned and protective function is effective
again. Then, event [E2186] is deactivated automatically.
If blocking of the first step of YG-Neutral Admittance Ground Fault protection is not
required, set this parameter to 0.
The following figure shows the interactions between different setting options of parameters
Function [P2715] and Direction mode [P2717] according to the tripping and operating ranges
of YG-Neutral Admittance Ground Fault protection:
Im
Re
Direction mode [P2717] = Non-directional Direction mode [P2717] = Forward Direction mode [P2717] = Backward
G0 G0 G0
Y0,operating Y0,operating Y0,operating
Trip zone Trip zone Trip zone
G0 G0 Trip G0
zone
Trip
Operating zone Operating zone Trip Operating zone
zone zone
Operating zone G0 G0 G0
Figure 3-241 Options of direction mode and protective criterion (characteristic quantity)
P2718 Admittance
Pick-up value of the first YG-Neutral Admittance Ground Fault protection element; at the
moment that the characteristic quantity Neutral-Admittance Y0[mS] exceeds this limit,
pick-up event YG-1 pickup [E2187] will become active, and the trip delay time, set by
parameter Delay time [P2727], of the first YG-Neutral Admittance Ground Fault
protection element will start.
the timer of Reset delay time has run down, the timer of Reset delay time will be
reset. Then trip event YG-1 trip [E2188] remains active.
NOTE: The minimum limit of measuring process quantity ground current is to be set
as a percentage of the nominal value of the process quantity. The nominal
value of the process quantity is to be set by parameter:
Ground current [P607], for primary side W1,
Ground current [P617], for primary side W2 or
Ground current [P627], for primary side W3
3.5.1 General
Main Menu\Parameters\ALARMS\
General
Parameter description:
Alarm message control is available by 449 different and programmable alarm channels with
output event numbers [E1] to [E449]
Table 3-18 Alarm channels
Main Menu\Parameters\ALARMS\
Alarm channels (No.1 to No.499)
Parameter description:
P Alarm text
As soon as the alarm is active, this editable alarm text appears on the alarm page.
An alarm text is restricted to 40 characters.
P Condition
At the moment that a trigger event is active the alarm event as well as the display of the
alarm text will become active.
Parameter Condition provides the following modes for variably dealing with the alarm
event and the display of the alarm text after clearance (trigger event = 0):
OFF: The alarm channel is disabled.
Latched: After clearance (trigger event = 0) the alarm event [E1] to [E449]
and the display of the alarm text remain active. Only after operating
the ALARM key or activation of remote acknowledgement via
activating event (see parameter Remote Ack [P5951]), the alarm
event as well as the display of the alarm text will be deactivated.
Unlatched: After clearance (trigger event = 0) the alarm event [E1] to [E449]
is immediately deactivated; however, the display of the alarm text
remains active. Only after operating the ALARM key or activation of
remote acknowledgement via activating event (see parameter
Remote Ack [P5951]), the display of the alarm text will be
deactivated.
No Ack: After clearance (trigger event = 0), both, the alarm event [E1] to
[E449] and the display of the alarm text are immediately deactivated.
Table 3-19 Parameter Condition settings and state changes
NOTE: In case of temporary loss of device power supply all active alarms are to be
saved failsafe (non-volatile)!
When several alarm events set with different selection options for parameter
Condition are assigned to the same alarm group, the alarm group event
behaves in the same manner as the actual, active events. For instance, one
active alarm event (Condition = No ACK) and another alarm event (Condition
= Latched) are assigned to the same alarm group. Here, the alarm group event
remains active until it is reset by the ALARM key or by assigned, active
activation event of parameter Remote ACK [P5951].
The ALARM key can be used either for:
acknowledgement of all active alarms simultaneously (call-up of Alarm
page and operate ALARM key), or for
individual acknowledgement of active alarms.
For individual acknowledgement the active alarm must be selected via touch
screen. Subsequently, the following window offers two operating options, OK
or Cancel:
P 1. Trigger
and
P 2. Trigger
Before alarm channels can be activated by so-called trigger events (OR logic), the
parameters 1. Trigger and 2. Trigger must be assigned the number of the events
intended to signal an alarm.
P Block
The alarm channel is blocked and the alarm causing event ([E1] to [E449]) will remain
inactive even if the trigger event is active.
P Delay
Activation of alarm channel can be delayed by the time set here.
P 1. Group
to
P 4. Group
Up to four alarm groups can be assigned to each alarm channel. Creation of up to 50
alarm groups (450 to 499) is available.Such alarm group event is activated as soon as
one alarm channel of this group is active.
P Option
none: no measure taken
Printer: alarm sent to printer (if available).
P Beeper
Select to activate the audible alarm signal (beeper).
P Trip LED
Select to activate LED TRIP at the device frontpage.
P LED Alarm
Select to activate LED ALARM at the device frontpage.
Select this parameter to activate the individual graphic array (located between alarm
number No. and Alarm Description) at menu page Active Alarms when alarm is
activated. The following setting options are available:
OFF: no colorization of graphic array when alarm is activated
Red: red colorized graphic array when alarm is activated
Yellow: yellow colorized graphic array when alarm is activated
Green: green colorized graphic array when alarm is activated
P Text colour
Available colours for static and flashing alarm text display:
Black: black colorized alarm text when alarm is activated
Red: red colorized alarm text when alarm is activated
Yellow: yellow colorized alarm text array when alarm is activated
Green: green colorized alarm text array when alarm is activated
Blink black: black-flashing alarm text when alarm is activated
Blink red: red-flashing alarm text when alarm is activated
Blink yellow: yellow-flashing alarm text when alarm is activated
Blink green: green-flashing alarm text array when alarm is activated
Main Menu\Parameters\ALARMS\
LEDs
Parameter description:
There are up to four activation events (see Fct.1 to Fct.4) which can be assigned to activate
each LED individually.
NOTE: Each of the eight LEDs always provides the same group of parameters. Hence, the
LED parameter descriptions of the LED 1 represented below are described in the
following in detail as examples.
Fct. 1 LED 1
P Colour
LED colour during activation; as soon as the event which is assigned to parameter
Event number is activated, the LED is illuminated either:
red or
green or
yellow .
P Event-No.
The LED indication can be activated by any active event. For activation, the number
related to this event has to be assigned to parameter Event-No.. Activation is only
effective, however, as long as the assigned event is active. If the event turns inactive,
the LED turns off.
If LED activation is not required, set this parameter to 0.
3.6.1 General
Parameters of this submenu refer to the voltage settings SYMAP-Compact(+) binary inputs,
and to activation and definition of the extension board system EBS.
The following board types are available:
EP-PS: board for communication to the SYMAP-Compact(+) and power supply
for connected extension boards, 1 binary output: changeo-over contact;
3 binary inputs: transistor technique
EB-BI8-A: 8 binary inputs devided into two groups around 4 binary inputs each:
transistor technique
EB-BI10-OC: 10 binary inputs devided into two groups around 5 binary inputs each:
opto-coupler technique
EB-BO4-R: 4 binary inputs: change-over contacts
EB-BO6-R: 6 binary inputs: normal open (NO) contacts
Main Menu\Parameters\I/O\
General
-
-
Board IDx
P4236 Board type None - None/EB-BI8-A/EB-BI10-OC/
EB-BO4-R/EB-BO6-R
P4237 Disable board Disabled - Ensabled/Disabled
Figure 3-246 General parameters of SYMAP-Compact and EBS
Parameter description
General
The following two parameters apply only for the binary inputs of the SYMAP-Compact(+)
device.
EBS General
The following two parameters apply for the extension board system EBS.
When EBS is enabled via parameter [P4100], event EBS OK [E4100] is activted.
Board ID 1 (EB-PS)
The following two parameters apply only for the communication and power supply unit EB-PS of
the extension board system EBS
Board ID 2
Each of the 63 available extension boards have the same parameters for its definition of board
type and activation/deactivation. Hence, the parameter descriptions of Board ID2 represented
below are described in the following in detail as examples.
Input Norm. Pre. Inv. Wire Short Filter ON delay OFF delay WF Lim. SC Lim.
No.
Event Clsd. Event Event fault circuit Ev. (0 6500 s) (0 6500 s) (0 255s) (0 255s)
10 4010 4110 4210 4310 4410 0,1 0,0 20 240
11 4011 4111 4211 4311 4411 0,1 0,0 20 240
12 4012 4112 4212 4312 4412 0,1 0,0 20 240
13 4013 4113 4213 4313 4413 0,1 0,0 20 240
14 4014 4114 4214 4314 4414 0,1 0,0 20 240
15 4015 4115 4215 4315 4415 0,1 0,0 20 240
16 4016 4116 4216 4316 4416 0,1 0,0 20 240
17 4017 4117 4217 4317 4417 0,1 0,0 20 240
18 4018 4118 4218 4318 4418 0,1 0,0 20 240
19 4019 4119 4219 4319 4419 0,1 0,0 20 240
20 4020 4120 4220 4320 4420 0,1 0,0 20 240
21 4021 4121 4221 4321 4421 0,1 0,0 20 240
22 4022 4122 4222 4322 4422 0,1 0,0 20 240
23 4023 4123 4223 4323 4423 0,1 0,0 20 240
24 4024 4124 4224 4324 4424 0,1 0,0 20 240
25 4025 4125 4225 4325 4425 0,1 0,0 20 240
26 4026 4126 4226 4326 4426 0,1 0,0 20 240
27 4027 4127 4227 4327 4427 0,1 0,0 20 240
28 4028 4128 4228 4328 4428 0,1 0,0 20 240
NOTE: Hardware version v1-1.x provides 19 binary inputs with interconnected (rooted)
common terminals.
Hardware version v1-2.x provides 18 binary inputs. Thus, Fct 28 is not available!
The two binary inputs Fct. 26 and Fct. 27 are equipped with a seggregated common
terminal each. Binary inputs Fct. 10 to Fct. 25 are provided with a rooted common
terminal!
No.
Function number of the binary Input
E Input Event
Input-Event of the binary input; the input event is immediately active/deactive after the
binary input has been activated/deactivated with regard to any delay time settings
(parameter ON delay and/or OFF delay).
NOTE: Hardware version v1-1.x:
Each input is assigned its own input event; see event numbers [E4010] to
[E4028].
Hardware version v1-2.x:
Each input is assigned its own input event; see event numbers [E4010] to
[E4027].
P Norm. Clsd.
Power to unlock principle (normally closed) of the binary input; this parameter
activates/deactivates the working principle power to unlock principle of the binary input:
: do not tick the box => working principle accords to power to lock principle
(normally open: the corresponding input-event [E40xx] will only be active if an
appropriate potential is present at the terminal of the binary input)
: do tick the box => working principle of the binary input accords to power to
unlock principle (normally closed: the corresponding input-event [E40xx] will
only be active if the appropriate potential is not present at the terminal of the
binary input)
P Pre. event
Additional pre-delay event of the binary input; if selected (parameter setting by tick box),
the binary input is attributed an additional pre-delay event [E41xx]. Independent of the
settings of parameters: ON delay or OFF delay, the additional pre-delay event is
immediately active/deactive after the binary input has been activated/deactivated at its
terminals.
To make the additional pre-delay event available, please tick the box in the array of the
inverted event Pre. Event [E41xx]:
41xx: do not tick the box => the additional pre-delay event of the binary input is
not available
41xx: do tick the box => the additional pre-delay event of the binary input is
available
NOTE: Hardware version v1-1.x:
Each input is assigned its own additional pre-delay event; see event numbers
[E4110] to [E4128].
Hardware version v1-2.x:
Each input is assigned its own additional pre-delay event; see event numbers
[E4110] to [E4127].
P Inv. event
Additional inverted event; if selected (parameter setting by tick box), the binary input is
attributed an additional inverted event [E42xx]. The state of the additional inverted event
is always equal to the inverted state of the input event [E41xx]. The additional inverted
event is immediately activated/deactivated after the input event has been
deactivated/activated.
To make the additional inverted event available, please tick the box in the array of the
inverted event Inv. Event [E42xx]:
42xx: do not tick the box => the additional inverted event of the binary input is
not available
42xx: do tick the box => the additional inverted event of the binary input is
available
NOTE: Hardware version v1-1.x:
Each input is assigned its own additional inverted event; see event numbers
[E4210] to [E4228].
Hardware version v1-2.x:
Each input is assigned its own additional inverted event; see event numbers
[E4210] to [E4227].
P Wirefault
Wirefault supervision of the binary input; if selected (parameter setting by tick box), the
external circuit of the binary input (connected pilot wire of the external switching contact)
can be monitored with regard to a broken wiring. For this, an ohmic restistance (R =
10k) must be connected in parallel to the external switching contact.
To activate/deactivate the wirefault supervision of a binary input, please use the tick box
in the array of the wirefault supervision events Wirefault [E43xx]:
43xx: do not tick the box => the wirefault supervision of the binary input is not
available
43xx: do tick the box => the wirefault supervision of the binary input is available
NOTE: The general wirefault monitoring event [E4300] is active if one of the individual
wirefault monitoring events is active. Such events may be used for triggering
the alarms.
P Short circuit
Short circuit supervision of the binary input; if selected (parameter setting by tick box),
the external circuit of the binary input (connected pilot wire of the external switching
contact) can be monitored with regard to a short-circuited wiring.
To activate/deactivate the short circuit supervision of a binary input, please use the tick
box in the array of the short circuit supervision events Short circuit [E44xx]:
44xx: do not tick the box => the short circuit supervision of the binary input is
not available
44xx: do tick the box => the short circuit supervision of the binary input is
available
NOTE: The general short circuit supervision event [E4400] is active if one of the
individual short circuit supervision events is active. Such events may be used
for triggering the alarms.
The filter function Filter event history can be activated/deactivated individually for all
binary inputs.
P ON delay
Switch-on delay time of the binary input; if the binary input is activated at its terminals
and the delay time, set by parameter On delay, run down, event [E40xx] is activated.
P OFF delay
Switch-off delay time of the binary input; if the binary input is dectivated at its terminals
and the delay time, set by parameter OFF delay, run down, event [E40xx] is
deactivated.
P WF Lim.
Minimum limit value for triggering the wirefault supervision event; if input signal of the
functional input falls below this value, the related wirefault event Wirefault [E43xx] is
activated.
Default setting: 20 LSB
P SC Lim.
Maximum limit value for triggering the short-circuit supervision event; if input signal of the
functional input exceeds this value, the related short-circuit event Short circuit [E44xx]
is activated.
Default setting: 240 LSB
EBS Groups
The following parameters are for setting the applied nominal voltage for the binary input groups
of the extension boards (EB-BI8-A and EB-BI10-OC)
Main menu\Parameters\I/O\Binary inputs
EBS Groups
Parameter description:
SC Lim. (0 127%)
WF Lim.(0 100%)
Input event-No.
Predelay event
Normal closed
Inverted event
Short circuit
Wire fault
Input-No.
Filter Ev.
EB-No.
EB-N0.
Function number of the extension board (board identification Board Idx)
Input-No.
Function number of the binary Input
E Input event
Input-Event of the binary input; the input event is immediately active/deactive after the
binary input has been activated/deactivated with regard to any delay time settings
(parameter ON delay and/or OFF delay).
P Normal closed
Power to unlock principle (normally closed) of the binary input; this parameter
activates/deactivates the working principle power to unlock principle of the binary input:
: do not tick the box => working principle accords to power to lock principle
(normally open: the corresponding input-event [E4xxx] will only be active if an
appropriate potential is present at the terminal of the binary input)
: do tick the box => working principle of the binary input accords to power to
unlock principle (normally closed: the corresponding input-event [E4xxx] will
only be active if the appropriate potential is not present at the terminal of the
binary input)
P Predelay event
Additional pre-delay event of the binary input; if selected (parameter setting by tick box),
the binary input is attributed an additional pre-delay event [E4xxx]. Independent of the
settings of parameters: ON delay or OFF delay, the additional pre-delay event is
immediately active/deactive after the binary input has been activated/deactivated at its
terminals.
To make the additional pre-delay event available, please tick the box in the array of the
inverted event Pre. Event [E4xxx]:
4xxx: do not tick the box => the additional pre-delay event of the binary input is
not available
4xxx: do tick the box => the additional pre-delay event of the binary input is
available
P Inverted event
Additional inverted event; if selected (parameter setting by tick box), the binary input is
attributed an additional inverted event [E4xxx]. The state of the additional inverted event
is always equal to the inverted state of the input event [E4xxx]. The additional inverted
event is immediately activated/deactivated after the input event has been
deactivated/activated.
To make the additional inverted event available, please tick the box in the array of the
inverted event Inv. Event [E4xxx]:
4xxx: do not tick the box => the additional inverted event of the binary input is
not available
4xxx: do tick the box => the additional inverted event of the binary input is
available
P Filter Ev.
Filter function for processing or not processing of all available input events of the binary
input in the event history; if selected (parameter setting by tick box), the input event
[E4xxx], the additional pre-delay event [E4xxx] and the additional inverted event [E4xxx]
are not being registered in the event history.
To activate/deactivate the filter function of a binary input, please use the tick box in the
array of Filter Ev.:
: do not tick the box => the filter function of the binary input is not available
: do tick the box => the filter function of the binary input is available
The filter function Filter event history can be activated/deactivated individually for all
binary inputs.
P ON delay
Switch-on delay time of the binary input; if the binary input is activated at its terminals
and the delay time, set by parameter On delay, run down, event [E4xxx] is activated.
P OFF delay
Switch-off delay time of the binary input; if the binary input is dectivated at its terminals
and the delay time, set by parameter OFF delay, run down, event [E4xxx] is
deactivated.
P Wire fault
Wirefault supervision of the binary input; if selected (parameter setting by tick box), the
external circuit of the binary input (connected pilot wire of the external switching contact)
can be monitored with regard to a broken wiring. For this, an ohmic restistance (R =
10k) must be connected in parallel to the external switching contact.
To activate/deactivate the wirefault supervision of a binary input, please use the tick box
in the array of the wirefault supervision events Wirefault [E4xxx]:
4xxx: do not tick the box => the wirefault supervision of the binary input is not
available
4xxx: do tick the box => the wirefault supervision of the binary input is available
NOTE: EB-BI8-A:
Each input is assigned its own wirefault supervision event.
EB-BI10-OC:
Function Wire fault supervision is not available!
NOTE: The general wirefault monitoring event [E4300] is active if one of the individual
wirefault monitoring events is active. Such events may be used for triggering
the alarms.
P WF Lim.
Minimum limit value for triggering the wirefault supervision event; if input signal of the
functional input falls below this value, the related wirefault event Wirefault [E4xxx] is
activated.
Default setting: 0%
NOTE: This parameter is not available for extension board type EB-BI10-OC !
P Short circuit
Short circuit supervision of the binary input; if selected (parameter setting by tick box),
the external circuit of the binary input (connected pilot wire of the external switching
contact) can be monitored with regard to a short-circuited wiring.
To activate/deactivate the short circuit supervision of a binary input, please use the tick
box in the array of the short circuit supervision events Short circuit [E4xxx]:
4xxx: do not tick the box => the short circuit supervision of the binary input is
not available
4xxx: do tick the box => the short circuit supervision of the binary input is
available
NOTE: EB-BI8-A:
Each input is assigned its own short circuit supervision event.
EB-BI10-OC:
Function Short circuit supervision is not available!
NOTE: The general short circuit supervision event [E4400] is active if one of the
individual short circuit supervision events is active. Such events may be used
for triggering the alarms.
P SC Lim.
Maximum limit value for triggering the short-circuit supervision event; if input signal of the
functional input exceeds this value, the related short-circuit event Short circuit [E4xxx]
is activated.
Default setting: 0%
NOTE: This parameter is not available for extension board type EB-BI10-OC !
P Activate level
Minimum voltage level to activate the binary input; the binaty input is activated when the
voltage at the binary input terminal exceeds the set value of parameter Activate level
[P].
NOTE: This parameter is not available for extension board type EB-BI10-OC !
P Drop-off level
Maximum voltage level to deactivate the binary input; the binaty input is activated when
the voltage at the binary input terminal falls below the set value of parameter Drop-off
level [P].
NOTE: This parameter is not available for extension board type EB-BI10-OC !
P Debouncing time
Minimum duration of the voltage signal which activates the binary input; to activate the
binary input the voltage of the signal wire which is connected to the binary input has to
exceed the set value of parameter Activate level [P] for a minimum of the set value of
parameter Debouncing time [P].
If the voltages falls below the set value of parameter Activate level [P] before the time
of debouncing time has run down, then the binary input remains inactive.
APPLICATION NOTE: Debouncing time can be used to avoid unwanted activation of
the binary inputs in case that the voltage exceeds the activation
level sporadically, e.g. casused by inductive or capacitive
influences on the signal wiring.
Depending on the device variant SYMAP-Compact(+) provides the following binary outputs:
Table 3-20 Binary outputs
additional SYMAP-Compact SYMAP-Compact +F1, +F2, +F3, +F4,
Binary Output Event-No.
pre-delay event F0, F1, F2, F3, F4 SYN, EC, GC, ECG, +GC, +ECG
Shunt Trip 1 4500 -
Shunt Trip 2 4501 -
Lockout relay 4502 4503
Synchron ON 4504 4505 ()
Function 1 4506 4507 ()
Function 2 4508 4509 ()
Function 3 4510 4511 ()
Function 4 4512 4513 ()
Function 5 4514 4515 ()
Function 6 4516 4517 ()
Function 7 4518 4519
Function 8 4520 4521
: Standard
(): Ordering option
CAUTION: When inductive loads are to be switched by the contacts of the binary outputs, the
contacts have to be protected against destruction by contact burning! For this, an
external protective circuit has to be connected to the contacts of the affected
binary output. The protective curcuitry shall be located close to the disturbing
source.
Using DC voltage as switching voltage: protective curcuitry with flywheel diode
Using AC voltage as switching voltage: protective curcuitry with varistor
The binary output Shunt Trip 1 provides a change-over contact. Its normally open (NO)
contact is designated for tripping the connected circuit breaker!
The first relay output Shunt trip 1 carries the event-number [E4500].
Parameter description:
01
to
22
Input elements of the logic scheme of the binary output; these parameters represent the
input elements for the (positive) logic control of output Shunt Trp 1. Each available
event can be used as an input element; therefore the event-number has to be registered
in the arrey besides the number of the input element.
Normally closed
Power to unlock principle (normally closed) of the binary output; this parameter
activates/deactivates the working principle power to unlock principle of the binary
output:
: do not tick the box => working principle of the binary output accords to
power to lock principle (normally open)
: do tick the box => working principle of the binary output accords to
power to unlock principle (normally closed)
NOTE: Power to unlock principle (normally closed) is only available when selection
button Output function = MONOSTABLE-I. The power to unlock principle
(normally closed) can be activated/deactivated individually for all binary
outputs.
CAUTION: Please note that the output event status of the binary outputs (BOs) do not
correspond to the set working principle (see tick box parameters Normally
closed) of the BOs! The output event status only depends on the
forestanding logic of the BOs!
The set working principle of the binary out only affects the position of the
BO contact!
The binary output Shunt Trip 2 provides a normally open (NO) contact which is designated for
tripping the connected circuit breaker!
The second relay output Shunt Trip 2 carries the event-number [E4501].
Parameter description:
Parameter description of binary output Shunt Trip 2 is equal to the binary output of the Shunt
Trip 1.
NOTE: In case that protective function ANSI 86 Lockout relay is not needed, please
disable the ANSI 86 module via parameter setting: Function [P3435] = OFF.
Parameter description:
Normally closed
Power to unlock principle (normally closed) of the binary output; this parameter
activates/deactivates the working principle power to unlock principle of the binary
output:
: do not tick the box => working principle of the binary output accords to
power to lock principle (normally open)
: do tick the box => working principle of the binary output accords to
power to unlock principle (normally closed)
NOTE: Power to unlock principle (normally closed) is only available when selection
button Output function = MONOSTABLE-I. The power to unlock principle
(normally closed) can be activated/deactivated individually for all binary
outputs.
CAUTION: Please note that the output event status of the binary outputs (BOs) do not
correspond to the set working principle (see tick box parameters Normally
closed) of the BOs! The output event status only depends on the
forestanding logic of the BOs!
The set working principle of the binary out only affects the position of the
BO contact!
Output function
Definition of switch behavior of the binary output; in view of the temporal scale the switch
behaviour of the relay contacts after or during activation of the binary output can be
defined by the following setting options of parameter Output function:
Monostable-I: This function generates pulses with monostable behaviour
(monostable interrupted); this means when output relay is
activated/deactivated its output contact closes/opens without any
time delay.
PULSER: This function generates pulses with the ON delay and the OFF
delay.
MONOFLOP-C: This function generates a constant pulse (permanent = ON
delay).
MONOFLOP-I: This function generates a pulse (permanent = ON delay). Pulse
is interrupted if logic turns false during ON delay.
Output ON delay
Switch-on delay time of the binary output; if the binary output is activated and the delay
time, set by parameter Output On delay, run down, event [E4502] is activated.
Setting range: 0 ... 6500 s.
01
to
22
Input elements of the logic scheme of the binary output; these parameters represent the
input elements for the (positive) logic control of output Lockout Relay. Each available
event can be used as an input element; therefore the event-number has to be registered
in the arrey besides the number of the input element.
3.6.3.4 Synchron ON
The relay of the binary output Synchron ON is equipped with two separate relay coils with
individually corresponding normal open contact which are connected in series. The sreies
connection is connected to the terminals of the binary output. The two internal relay coils of the
binary output relay Synchron ON are individually controlled by different CPUs. One is
controlled by the CPU ofr the control unit (CU), the other is controlled by the measuring unit
(MU).
The binary output Synchron ON shall preferably be used for switching on the connected circuit
breaker via synchronizing function ANSI 25 Synchro check.
Synchron ON relay exists only once, and carries event-number [E4504].
NOTE: Binary output Synchron ON is foreseen for function ANSI 25 Synchronising.
Alternatively, binary output Synchron ON can be used as a binary output such as
Function 1 or others.
Parameter description:
Parameter description of binary output Lockout Relay is equal to the binary output Synchron
ON.
Parameter description:
Parameter description of binary output Lockout Relay is equal to the binary outputs Function
1 to Function 8.
In dependence of the board types and the number of extension boards connected to the
SYMAP-Compact(+) Extension Board System EBS provides severel relay outputs (Function
output x). By using selection button Selection each relay output can be invoked individually.
Parameter description:
Parameter description of binary output Lockout Relay is equal to the binary outputs Function
x of the extension board system EBS.
NOTE: Input 01 of Function output 8 is assigned self-supervision event (watchdog)
Common alarm system total error [E9001] as default setting. This event can also be
assigned to another input of the same or another function output.
Analog inputs 1 and 2 designed for resistance Measurement are applicable for the following
applications:
Measuring temperature
Measuring pressure
NOTE: The analog inputs 1 and 2 for the resistance measurement are essentially for a
measuring range between 0 (range start) and 400 (end of range)!
Analog input 1
Analog input 2
Parameter description:
NOTE: Each of the two analog inputs (resistance measurement) provides the same
parameters. Hence, the parameter descriptions of analog input 1 represented below
are described in the following in detail as examples.
Input
P5788 Enable
This parameter enables/disables analog output 1, where:
OFF: disables or
PT100: enables the analogue input for temperature measurement
according to the PT100 temperature-resistance characteristic in the
range between 0 and 400 or
0 400: activates the analogue input for a direct, linear measurement of
resistance in the range between 0 and 400.
400
350
300
Resistance R []
250
200
150
100
50
0
-200 -100 0 100 200 300 400 500 600 700 800
Temperature T [C]
P94175 Name
Text editor for analog input 1; the name of analog input 1 can be changed by the user
according to the customerspecific designation (max. 24 characters).
Filter
P5794 Integrator
Attenuation of the measured signal for display of rapidly changing measured values; the
magnitude of digital, scaled value of the analogue input is calculated according to the
integrator defined by parameter [P5794].
In an instantaneous change in the magnitude of the measured signal between 0 (range
start) and 400 (end of range), the digital, scaled measuring value follows the measured
input signal within the time set with parameter [P5794].
P5795 Average
Representation of the analog measurement signal as a digitized, statistic value (eg for
measured value displays) of constantly fluctuating, analog measured signals; for the
displayed magnitude of the input signal, an average value is cyclically calculated,
according to the time period set by parameter [P5795].
Options
P5796 Freeze
Event-controlled saving of the actual value of the input signal; saving can be activated by
any active event. For activation, the number related to this event has to be assigned to
parameter [P5796]. Activation of saving function is only effective, however, as long as
the assigned event is active. As soon as the assigned event becomes inactive, the
saved value is erased and and the magnitude of the displayed value is equal to the
actual measuring value.
If event-controlled saving of the actual input value is not required, set this parameter to
0.
P5797 Substitute
Event-controlled provision of a pre-defined value for the actual input value; provision of a
pre-defined value can be activated by any active event. For activation, the number
related to this event has to be assigned to parameter [P5797]. Provision of a pre-defined
value is only effective, however, as long as the assigned event is active. As soon as the
assigned event becomes inactive, the pre-defined value is erased and and the
magnitude of the displayed value is equal to the actual measuring value.
If event-controlled saving of the actual input value is not required, set this parameter to
0.
Analog inputs 3 and 4 designed for mA current Measurement are applicable for the following
applications:
Measuring values from external process automation systems such as eg. current,
temperature, or pressure (eg. lub. oil pressure of an engine)
Measuring of setpoints for controlling of system-related process values such as active load
control bias signal and power factor control bias signal (NOTE: Measuring of setpoints is
not available yet!)
Analog input 3
Analog input 4
Parameter description:
NOTE: Each of the two analog inputs (resistance Measurement) provides the same
parameters. Hence, the parameter descriptions of analog input 1 represented below
are described in the following in detail as examples.
Input
P5756 Enable
This parameter enables/disables analog output 3, where:
OFF: disables or
0 20mA: enables the analogue input for mA measurement in the range
between 0 to 20mA or
4 20mA: enables the analogue input for mA measurement in the range
between. This setting should be selected when using the wirefault
monitoring.
NOTE: Depending on the measuring quantity (see parameter Select [P5757]), the set
values to define the value pairs for starting point and final point should be given as
absolute or percent values. Percent values always refer to the settings of the
reference values (e.g. generator rated power) via submenu
SYSTEM\Nominals\Reference values!
P94125 Name
Text editor for analog input 3; the name of analog input 3 can be changed by the user
according to the customerspecific designation (max. 24 characters).
Scale
P5757 Select
This parameter defines the measuring quantity of the analog input 3, where:
Percent [%]
Current [mA]
Current [A]
Voltage [mV]
Voltage [V]
Active power [kW]
Reactive power [kvar]
Apparent power [kVA]
Speed [RPM]
Pressure [bar]
Pressure [kPa]
Temperature [C]
Temperature [F]
Fuel [l]
Fuel [m3]
Fuel [gal]
HINWEIS: The displayed unit of the measured value is automatically adjusted to the
parameter "Select" [P5757]!
Filter
P5762 Integrator
Attenuation of the measured signal for display of rapidly changing measured values; the
magnitude of digital, scaled value of the analogue input is calculated according to the
stabilization defined by parameter [P5762].
In an instantaneous change in the magnitude of the measured signal between 0/4mA
(range start) and 20mA (end of range), the digital, scaled measuring value follows the
measured input signal within the time set with parameter [P5762].
P5763 Average
Representation of the analog measurement signal as a digitized, statistic value (eg for
measured value displays) of constantly fluctuating, analog measured signals; for the
displayed magnitude of the input signal, an average value is cyclically calculated,
according to the time period set by parameter [P5763].
Options
P5764 Freeze
Event-controlled saving of the actual value of the input signal; saving can be activated by
any active event. For activation, the number related to this event has to be assigned to
parameter [P5764]. Activation of saving function is only effective, however, as long as
the assigned event is active. As soon as the assigned event becomes inactive, the
saved value is erased and and the magnitude of the displayed value is equal to the
actual measuring value.
If event-controlled saving of the actual input value is not required, set this parameter to
0.
P5765 Substitute
Event-controlled provision of a pre-defined value for the actual input value; provision of a
pre-defined value can be activated by any active event. For activation, the number
related to this event has to be assigned to parameter [P5765]. Provision of a pre-defined
value is only effective, however, as long as the assigned event is active. As soon as the
assigned event becomes inactive, the pre-defined value is erased and and the
magnitude of the displayed value is equal to the actual measuring value.
If event-controlled saving of the actual input value is not required, set this parameter to
0.
Supervision
If no level-monitoring of the current input signal is required, the parameter must be set to
"0.0".
Analog outputs designed for a signal range of +/-10V are applicable for the following
applications:
Provision of measuring values for external process automation systems
Provision of setpoints for controlling of system-related process values such as speed and
voltage (NOTE: Provision of setpoints is not available yet!)
Analog output 1
Analog output 5
Parameter description:
NOTE: Each of the two analog outputs (+/-10V) provides the same parameters. Hence, the
parameter descriptions of analog out 1 represented below are described in the
following in detail as examples.
Output
P5878 Enable
This parameter enables/disables analog output 1, where:
OFF: disables or
ON: enables the analog output.
NOTE: Depending on the measuring quantity (see parameter Select [P5867]), the set
values to define the value pairs for starting point and final point should be given as
absolute or percent values. Percent values always refer to the settings of the
reference values via submenu SYSTEM\Nominals\Reference values!
P94275 Name
Text editor for analog output 1; the name of analog output 1 can be changed by the user
according to the customerspecific designation (max. 24 characters).
Select
P5867 Select
This parameter defines the measuring quantity which is to be provided by the analog
output 1, where:
none: does not provide any measuring value, or
the measuring quantity to be provided can be selected via selection button.
Depending on the SYMAP-Compact(+) device variant the following measuring
quantities are provided:
Table 3-21 Analog output 1 Measuring quantity selection
Name of meas. quantity Description Setting range Unit
none none 0-100.0 -
f,PT1 Frequency,PT1 0-99.99 Hz
f,PT2 Frequency,PT2 0-99.99 Hz
f,PT3 Frequency,PT3 0-99.99 Hz
U12,PT1 Phase-to-phase voltage U12,PT1 0-6000.0 %
U23 PT1 Phase-to-phase voltage U23 PT1 0-6000.0 %
U31,PT1 Phase-to-phase voltage U31,PT1 0-6000.0 %
UL1,PT1 Phase voltage UL1,PT1 0-6000.0 %
UL2,PT1 Phase voltage UL2,PT1 0-6000.0 %
UL3,PT1 Phase voltage UL3,PT1 0-6000.0 %
U12,PT2 Phase-to-phase voltage U12,PT2 0-6000.0 %
U23,PT2 Phase-to-phase voltage U23,PT2 0-6000.0 %
U31,PT2 Phase-to-phase voltage U31,PT2 0-6000.0 %
UL1,PT2 Phase voltage UL1,PT2 0-6000.0 %
UL2,PT2 Phase voltage UL2,PT2 0-6000.0 %
UL3,PT2 Phase voltage UL3,PT2 0-6000.0 %
U12,PT3 Phase-to-phase voltage U12,PT3 0-6000.0 %
U23,PT3 Phase-to-phase voltage U23,PT3 0-6000.0 %
U31,PT3 Phase-to-phase voltage U31,PT3 0-6000.0 %
UL1,PT3 Phase voltage UL1,PT3 0-6000.0 %
UL2,PT3 Phase voltage UL2,PT3 0-6000.0 %
UL3,PT3 Phase voltage UL3,PT3 0-6000.0 %
UG,PT-GND1 Residual voltage UG,PT-GND1 0-6000.0 %
UG,PT1 Residual voltage UG,PT1 0-6000.0 %
UG,PT2 Residual voltage UG,PT2 0-6000.0 %
UG,PT3 Residual voltage UG,PT3 0-6000.0 %
Udc,PT1 DC voltage, PT1 -3276.7-3276.7 %
Udc+,PT1 DC voltage (+pole),PT1 -3276.7-3276.7 %
Udc-,PT1 DC voltage (-pole),PT1 -3276.7-3276.7 %
Udc,PT2 DC voltage, PT2 -3276.7-3276.7 %
Udc+,PT2 DC voltage (+pole),PT2 -3276.7-3276.7 %
Udc-,PT2 DC voltage (-pole),PT2 -3276.7-3276.7 %
Udc,PT3 DC voltage, PT3 -3276.7-3276.7 %
Udc+,PT3 DC voltage (+pole),PT3 -3276.7-3276.7 %
Udc-,PT3 DC voltage (-pole),PT3 -3276.7-3276.7 %
IL1,CT1 Phase current IL1,CT1 0-6000.0 %
IL2,CT1 Phase current IL2,CT1 0-6000.0 %
IL3,CT1 Phase current IL3,CT1 0-6000.0 %
IL1,CT2 Phase current IL1,CT2 0-6000.0 %
IL2,CT2 Phase current IL2,CT2 0-6000.0 %
IL3,CT2 Phase current IL3,CT2 0-6000.0 %
IG,CT-GND1 Ground current IG,CT-GND1 0-6000.0 %
IG,CT1 Ground current IG,CT1 0-6000.0 %
IG,CT2 Ground current IG,CT2 0-6000.0 %
IG,CT3 Ground current IG,CT3 0-6000.0 %
Id1 Differential current Id1 0-6000.0 %
Id2 Differential current Id2 0-6000.0 %
Id3 Differential current Id3 0-6000.0 %
Is1 Stabilizing current Is1 0-6000.0 %
Is2 Stabilizing current Is2 0-6000.0 %
Is3 Stabilizing current Is3 0-6000.0 %
P,CT1 Active power,CT1 3000.0 %
Q,CT1 Reactive power,CT1 3000.0 %
S,CT1 Apparent power,CT1 0-6000.0 %
PF,CT1 Power factor, CT1 -0.99 ... +1.00 -
PL1,CT1 Active power, phase L1,CT1 3000.0 %
PL2,CT1 Active power, phase L2,CT1 3000.0 %
PL3,CT1 Active power, phase L3,CT1 3000.0 %
Filter
P5884 Integrator
Attenuation of the output signal for display of rapidly changing measurement values; the
magnitude of the output signal is calculated by the set value (time) of parameter [P5884].
If the magnitude of the measuring value jumps between the set values of parameters
Zero scale [P5882] und Full scale [P5883] without any delay, then duration for
changing the output signal from the set value of parameter Zero range [P5879] to the
set value of paramter Full range [P5880] is equal to the duration set by parameter
[P5884].
P5885 Average
Signal output as statistical value for display of continually changing measurement values
over an extended period of time (minutes to hours); for the displayed magnitude of the
output signal an average values is cyclically calculated according to the time period set
by parameter [P5885].
Options
P5886 Freeze
Event-controlled saving of the actual ouput signal; saving can be activated by any active
event. For activation, the number related to this event has to be assigned to parameter
[P5886]. Activation of saving function is only effective, however, as long as the assigned
event is active. As soon as the assigned event becomes inactive, the saved value is
erased and and the magnitude of the output signal is equal to the actual measuring
value.
If event-controlled saving of the actual ouput signal is not required, set this parameter to
0.
P5887 Substitute
Event-controlled provision of a pre-defined value for the actual ouput signal; provision of
a pre-defined value can be activated by any active event. For activation, the number
related to this event has to be assigned to parameter [P5887]. Provision of a pre-defined
value is only effective, however, as long as the assigned event is active. As soon as the
assigned event becomes inactive, the pre-defined value is erased and the magnitude of
the output signal is equal to the actual measuring value.
If event-controlled provision of a pre-defined value for the actual ouput signal is not
required, set this parameter to 0.
Analog outputs designed for a signal range of +/-20mA are applicable for the following
applications:
Provision of measuring values for external process automation systems
Provision of setpoints for controlling of system-related process values such as speed and
voltage (NOTE: Provision of setpoints is not available yet!)
Analog output 2
Parameter description:
Output
P5864 Enable
This parameter enables/disables analog output 2, where:
OFF: disables or
ON: enables the analog output.
Output signal
[mA]
NOTE: Depending on the measuring quantity (see parameter Select [P5867]), the set
values to define the value pairs for starting point and final point should be given as
absolute or percent values. Percent values always refer to the settings of the
reference values via submenu SYSTEM\Nominals\Reference values!
P94250 Name
Text editor for analog output 2; the name of analog output 2 can be changed by the user
according to the customerspecific designation (max. 24 characters).
adapted to the measuring range of the external signal receiver. For this, parameter
[5866] defines the end of the measuring range for the +/-20mA standard signal type.
Select
P5867 Select
This parameter defines the measuring quantity which is to be provided by the analog
output 2, where:
none: does not provide any measuring value, or
the measuring quantity to be provided can be selected via selection button.
Depending on the SYMAP-Compact(+) device variant the following measuring
quantities are provided:
Table 3-22 Analog output 2 Measuring quantity selection
Name of meas. quantity Description Setting range Unit
none none 0-100.0 -
f,PT1 Frequency,PT1 0-99.99 Hz
f,PT2 Frequency,PT2 0-99.99 Hz
f,PT3 Frequency,PT3 0-99.99 Hz
U12,PT1 Phase-to-phase voltage U12,PT1 0-6000.0 %
U23 PT1 Phase-to-phase voltage U23 PT1 0-6000.0 %
U31,PT1 Phase-to-phase voltage U31,PT1 0-6000.0 %
UL1,PT1 Phase voltage UL1,PT1 0-6000.0 %
UL2,PT1 Phase voltage UL2,PT1 0-6000.0 %
UL3,PT1 Phase voltage UL3,PT1 0-6000.0 %
U12,PT2 Phase-to-phase voltage U12,PT2 0-6000.0 %
U23,PT2 Phase-to-phase voltage U23,PT2 0-6000.0 %
U31,PT2 Phase-to-phase voltage U31,PT2 0-6000.0 %
UL1,PT2 Phase voltage UL1,PT2 0-6000.0 %
UL2,PT2 Phase voltage UL2,PT2 0-6000.0 %
UL3,PT2 Phase voltage UL3,PT2 0-6000.0 %
U12,PT3 Phase-to-phase voltage U12,PT3 0-6000.0 %
U23,PT3 Phase-to-phase voltage U23,PT3 0-6000.0 %
U31,PT3 Phase-to-phase voltage U31,PT3 0-6000.0 %
UL1,PT3 Phase voltage UL1,PT3 0-6000.0 %
UL2,PT3 Phase voltage UL2,PT3 0-6000.0 %
UL3,PT3 Phase voltage UL3,PT3 0-6000.0 %
UG,PT-GND1 Residual voltage UG,PT-GND1 0-6000.0 %
UG,PT1 Residual voltage UG,PT1 0-6000.0 %
UG,PT2 Residual voltage UG,PT2 0-6000.0 %
UG,PT3 Residual voltage UG,PT3 0-6000.0 %
Udc,PT1 DC voltage, PT1 0-6000.0 %
Udc+,PT1 DC voltage (+pole),PT1 -3276.7-3276.7 %
Udc-,PT1 DC voltage (-pole),PT1 -3276.7-3276.7 %
Udc,PT2 DC voltage, PT2 -3276.7-3276.7 %
Udc+,PT2 DC voltage (+pole),PT2 -3276.7-3276.7 %
Udc-,PT2 DC voltage (-pole),PT2 -3276.7-3276.7 %
Udc,PT3 DC voltage, PT3 -3276.7-3276.7 %
Udc+,PT3 DC voltage (+pole),PT3 -3276.7-3276.7 %
Udc-,PT3 DC voltage (-pole),PT3 -3276.7-3276.7 %
IL1,CT1 Phase current IL1,CT1 0-6000.0 %
IL2,CT1 Phase current IL2,CT1 0-6000.0 %
IL3,CT1 Phase current IL3,CT1 0-6000.0 %
IL1,CT2 Phase current IL1,CT2 0-6000.0 %
IL2,CT2 Phase current IL2,CT2 0-6000.0 %
IL3,CT2 Phase current IL3,CT2 0-6000.0 %
IG,CT-GND1 Ground current IG,CT-GND1 0-6000.0 %
IG,CT1 Ground current IG,CT1 0-6000.0 %
IG,CT2 Ground current IG,CT2 0-6000.0 %
IG,CT3 Ground current IG,CT3 0-6000.0 %
Id1 Differential current Id1 0-6000.0 %
Id2 Differential current Id2 0-6000.0 %
Id3 Differential current Id3 0-6000.0 %
Is1 Stabilizing current Is1 0-6000.0 %
Is2 Stabilizing current Is2 0-6000.0 %
Is3 Stabilizing current Is3 0-6000.0 %
P,CT1 Active power,CT1 3000.0 %
Q,CT1 Reactive power,CT1 3000.0 %
S,CT1 Apparent power,CT1 0-6000.0 %
PF,CT1 Power factor, CT1 -0.99 ... +1.00 -
PL1,CT1 Active power, phase L1,CT1 3000.0 %
PL2,CT1 Active power, phase L2,CT1 3000.0 %
PL3,CT1 Active power, phase L3,CT1 3000.0 %
Filter
P5870 Integrator
Attenuation of the output signal for display of rapidly changing measurement values; the
magnitude of the output signal is calculated by the set value (time) of parameter [P5870].
If the magnitude of the measuring value jumps between the set values of parameters
Zero scale [P5868] und Full scale [P5869] without any delay, then duration for
changing the output signal from the set value of parameter Zero range [P5865] to the
set value of paramter Full range [P5866] is equal to the duration set by parameter
[P5870].
P5871 Average
Signal output as statistical value for display of continually changing measurement values
over an extended period of time (minutes to hours); for the displayed magnitude of the
output signal an average values is cyclically calculated according to the time period set
by parameter [P5871].
Options
P5872 Freeze
Event-controlled saving of the actual ouput signal; saving can be activated by any active
event. For activation, the number related to this event has to be assigned to parameter
[P5872]. Activation of saving function is only effective, however, as long as the assigned
event is active. As soon as the assigned event becomes inactive, the saved value is
erased and and the magnitude of the output signal is equal to the actual measuring
value.
If event-controlled saving of the actual ouput signal is not required, set this parameter to
0.
P5873 Substitute
Event-controlled provision of a pre-defined value for the actual ouput signal; provision of
a pre-defined value can be activated by any active event. For activation, the number
related to this event has to be assigned to parameter [P5873]. Provision of a pre-defined
value is only effective, however, as long as the assigned event is active. As soon as the
assigned event becomes inactive, the pre-defined value is erased and the magnitude of
the output signal is equal to the actual measuring value.
If event-controlled provision of a pre-defined value for the actual ouput signal is not
required, set this parameter to 0.
Analog outputs designed for a signal range of 0 to 20mA are applicable for the following
applications:
Provision of measuring values for external analog measurement instruments
Provision of process values for externeal plant components such as building control
systems, ship automation systems, etc.
Analog output 3
Analog output 4
Parameter description:
NOTE: Each of the two analog outputs provides the same parameters. Hence, the parameter
descriptions of analog out 3 represented below are described in the following in detail
as examples.
Output
P5850 Enable
This parameter enables/disables analog output 2, where:
OFF: disables or
ON: enables the analog output.
Figure 3-270 Analog output 3 Example: Meas. value Active power and 10% reverse power
NOTE: Depending on the measuring quantity (see parameter Select [P5853]), the set
values to define the value pairs for starting point and final point should be given as
absolute or percent values. Percent values always refer to the settings of the
reference values (e.g. generator rated power) via submenu
SYSTEM\Nominals\Reference values!
On the assumption that power measurement is done via current measurement input
CT1 and voltage measurement input PT1, the following parameter setting should be
done in submenu SYSTEM\Measuring\Power:
PT reference [P9410] = PT1
On the assumption that current and voltage measurement is located at winding side
W1, the following parameter setting for voltage measurement should be done in
submenu SYSTEM\Nominals\Potential transformers:
Assignment [P642] = W1 , and
in submenu SYSTEM\Nominals\Current transformers the following parameter
setting should be done for current measurement:
Assignement [P668] = W1
P94225 Name
Text editor for analog output 3; the name of analog output 3 can be changed by the user
according to the customerspecific designation (max. 24 characters).
Select
P5853 Select
This parameter defines the measuring quantity which is to be provided by the analog
output 3, where:
none: does not provide any measuring quantity, or
the measuring quantity to be provided can be selected via selection button.
Depending on the SYMAP-Compact(+) device variant the following measuring
quantities are provided:
Table 3-23 Analog output 3 Measuring quantity selection
Name of meas. quantity Description Setting range Unit
none none 0-100.0 -
f,PT1 Frequency,PT1 0-99.99 Hz
f,PT2 Frequency,PT2 0-99.99 Hz
f,PT3 Frequency,PT3 0-99.99 Hz
U12,PT1 Phase-to-phase voltage U12,PT1 0-6000.0 %
U23 PT1 Phase-to-phase voltage U23 PT1 0-6000.0 %
U31,PT1 Phase-to-phase voltage U31,PT1 0-6000.0 %
UL1,PT1 Phase voltage UL1,PT1 0-6000.0 %
UL2,PT1 Phase voltage UL2,PT1 0-6000.0 %
UL3,PT1 Phase voltage UL3,PT1 0-6000.0 %
U12,PT2 Phase-to-phase voltage U12,PT2 0-6000.0 %
U23,PT2 Phase-to-phase voltage U23,PT2 0-6000.0 %
U31,PT2 Phase-to-phase voltage U31,PT2 0-6000.0 %
UL1,PT2 Phase voltage UL1,PT2 0-6000.0 %
UL2,PT2 Phase voltage UL2,PT2 0-6000.0 %
UL3,PT2 Phase voltage UL3,PT2 0-6000.0 %
U12,PT3 Phase-to-phase voltage U12,PT3 0-6000.0 %
U23,PT3 Phase-to-phase voltage U23,PT3 0-6000.0 %
U31,PT3 Phase-to-phase voltage U31,PT3 0-6000.0 %
UL1,PT3 Phase voltage UL1,PT3 0-6000.0 %
UL2,PT3 Phase voltage UL2,PT3 0-6000.0 %
UL3,PT3 Phase voltage UL3,PT3 0-6000.0 %
UG,PT-GND1 Residual voltage UG,PT-GND1 0-6000.0 %
UG,PT1 Residual voltage UG,PT1 0-6000.0 %
UG,PT2 Residual voltage UG,PT2 0-6000.0 %
UG,PT3 Residual voltage UG,PT3 0-6000.0 %
Udc+,PT1 DC voltage (+pole),PT1 -3276.7-3276.7 %
Udc-,PT1 DC voltage (-pole),PT1 -3276.7-3276.7 %
Udc,PT2 DC voltage, PT2 -3276.7-3276.7 %
Udc+,PT2 DC voltage (+pole),PT2 -3276.7-3276.7 %
Udc-,PT2 DC voltage (-pole),PT2 -3276.7-3276.7 %
Udc,PT3 DC voltage, PT3 -3276.7-3276.7 %
Udc+,PT3 DC voltage (+pole),PT3 -3276.7-3276.7 %
Udc-,PT3 DC voltage (-pole),PT3 -3276.7-3276.7 %
IL1,CT1 Phase current IL1,CT1 0-6000.0 %
IL2,CT1 Phase current IL2,CT1 0-6000.0 %
IL3,CT1 Phase current IL3,CT1 0-6000.0 %
IL1,CT2 Phase current IL1,CT2 0-6000.0 %
IL2,CT2 Phase current IL2,CT2 0-6000.0 %
IL3,CT2 Phase current IL3,CT2 0-6000.0 %
IG,CT-GND1 Ground current IG,CT-GND1 0-6000.0 %
IG,CT1 Ground current IG,CT1 0-6000.0 %
IG,CT2 Ground current IG,CT2 0-6000.0 %
IG,CT3 Ground current IG,CT3 0-6000.0 %
Id1 Differential current Id1 0-6000.0 %
Id2 Differential current Id2 0-6000.0 %
Id3 Differential current Id3 0-6000.0 %
Is1 Stabilizing current Is1 0-6000.0 %
Is2 Stabilizing current Is2 0-6000.0 %
Is3 Stabilizing current Is3 0-6000.0 %
P,CT1 Active power,CT1 3000.0 %
Q,CT1 Reactive power,CT1 3000.0 %
S,CT1 Apparent power,CT1 0-6000.0 %
PF,CT1 Power factor, CT1 -0.99 ... +1.00 -
PL1,CT1 Active power, phase L1,CT1 3000.0 %
PL2,CT1 Active power, phase L2,CT1 3000.0 %
PL3,CT1 Active power, phase L3,CT1 3000.0 %
QL1,CT1 Reactive power, phase L1,CT1 3000.0 %
Filter
P5856 Integrator
Attenuation of the output signal for display of rapidly changing measurement values; the
magnitude of the output signal is calculated by the set value (time) of parameter [P5856].
If the magnitude of the measuring value jumps between the set values of parameters
Zero scale [P5854] und Full scale [P5855] without any delay, then duration for
changing the output signal from the set value of parameter Zero range [P5851] to the
set value of paramter Full range [P5852] is equal to the duration set by parameter
[P5856].
P5857 Average
Signal output as statistical value for display of continually changing measurement values
over an extended period of time (minutes to hours); for the displayed magnitude of the
output signal an average values is cyclically calculated according to the time period set
by parameter [P5857].
Options
P5858 Freeze
Event-controlled saving of the actual ouput signal; saving can be activated by any active
event. For activation, the number related to this event has to be assigned to parameter
[P5858]. Activation of saving function is only effective, however, as long as the assigned
event is active. As soon as the assigned event becomes inactive, the saved value is
erased and and the magnitude of the output signal is equal to the actual measuring
value.
If event-controlled saving of the actual ouput signal is not required, set this parameter to
0.
P5859 Substitute
Event-controlled provision of a pre-defined value for the actual ouput signal; provision of
a pre-defined value can be activated by any active event. For activation, the number
related to this event has to be assigned to parameter [P5859]. Provision of a pre-defined
value is only effective, however, as long as the assigned event is active. As soon as the
assigned event becomes inactive, the pre-defined value is erased and the magnitude of
the output signal is equal to the actual measuring value.
If event-controlled provision of a pre-defined value for the actual ouput signal is not
required, set this parameter to 0.
Main Menu\Parameters\
GW-Grenzwertberwachung
Parameter description:
NOTE: Each of the 100 steps of limit value monitoring function provides the same parameters.
Hence, the parameter descriptions of LVM step 1 represented below are described in
the following in detail as examples.
P74500 Function
This parameter disables/enables the first step of the LVM-Limit Value Monitoring
element; enabling the first step is to be done by selecting its working principle; whereas:
"OFF: disables first monitoring step, or
High limit: ensables first monitoring step => monitoring according to
threshold exceedance,
Low limit: ensables first monitoring step => monitoring according to
threshold undercut,
P74501 Type
This parameter defines the physical type of the measuring quantity for the first step of
the LVM-Limit Value Monitoring element; The measuring range of the physical quantity
accords to its type which can be selected as follows:
Voltage
Current
Power
Power factor
Frequency
Analog inputs
P74502 Select
This parameter defines the measuring quantity of the first setp of the LVM-Limit Value
Monitoring function, whereby the measuring quantity to be provided can be selected via
selection button. Depending on the SYMAP-Compact(+) device variant the following
measuring quantities are provided:
Table 3-24 LVM step 1 Selection of measuring quantity
Name of meas.
Description Setting range Unit
quantity
TYPE: VOLTAGE
U12,PT1 Phase-to-phase voltage U12,PT1 0-3000.0 %
U23 PT1 Phase-to-phase voltage U23 PT1 0-3000.0 %
U31,PT1 Phase-to-phase voltage U31,PT1 0-3000.0 %
MIN,PT1 Minimum phase-to-phase average voltage, PT1 0-3000.0 %
Max,PT1 Maximum phase-to-phase average voltage, PT1 0-3000.0 %
UL1,PT1 Phase voltage UL1,PT1 0-3000.0 %
UL2,PT1 Phase voltage UL2,PT1 0-3000.0 %
UL3,PT1 Phase voltage UL3,PT1 0-3000.0 %
ULxMIN,PT1 Minimum average phase voltage, PT1 0-3000.0 %
ULxMAX,PT1 Maximum average phase voltage, PT1 0-3000.0 %
Uo, PT1 Zero sequence voltage Uo, PT1 0-3000.0 %
U1,PT1 Positive sequence voltage U1 , PT1 0-3000.0 %
U2,PT1 Negative sequence voltage U2, PT1 0-3000.0 %
U12,PT2 Phase-to-phase voltage U12,PT2 0-3000.0 %
U23 PT2 Phase-to-phase voltage U23 PT2 0-3000.0 %
U31,PT2 Phase-to-phase voltage U31,PT2 0-3000.0 %
MIN,PT2 Minimum phase-to-phase average voltage, PT2 0-3000.0 %
Max,PT2 Maximum phase-to-phase average voltage, PT2 0-3000.0 %
UL1,PT2 Phase voltage UL1,PT2 0-3000.0 %
UL2,PT2 Phase voltage UL2,PT2 0-3000.0 %
UL3,PT2 Phase voltage UL3,PT2 0-3000.0 %
ULxMIN,PT2 Minimum average phase voltage, PT2 0-3000.0 %
ULxMAX,PT2 Maximum average phase voltage , PT2 0-3000.0 %
Uo, PT2 Zero sequence voltage Uo , PT2 0-3000.0 %
U1,PT2 Positive sequence voltage U1, PT2 0-3000.0 %
U2,PT2 Negative sequence voltage U2, PT2 0-3000.0 %
U12,PT3 Phase-to-phase voltage U12,PT3 0-3000.0 %
U23 PT3 Phase-to-phase voltage U23 PT3 0-3000.0 %
U31,PT3 Phase-to-phase voltage U31,PT3 0-3000.0 %
MIN,PT3 Minimum phase-to-phase average voltage, PT3 0-3000.0 %
Max,PT3 Maximum phase-to-phase average voltage, PT3 0-3000.0 %
UL1,PT3 Phase voltage UL1,PT3 0-3000.0 %
UL2,PT3 Phase voltage UL2,PT3 0-3000.0 %
UL3,PT3 Phase voltage UL3,PT3 0-3000.0 %
ULxMIN,PT3 Minimum average phase voltage, PT3 0-3000.0 %
ULxMAX,PT3 Maximum average phase voltage, PT3 0-3000.0 %
Uo, PT3 Zero sequence voltage Uo , PT3 0-3000.0 %
U1,PT3 Positive sequence voltage U1, PT3 0-3000.0 %
U2,PT3 Negative sequence voltage U2, PT3 0-3000.0 %
UG,PT-GND1 Residual voltage UG,PT-GND1 0-3000.0 %
TYPE: CURRENT
IL1,CT1 Phase current IL1,CT1 0-6000.0 %
IL2,CT1 Phase current IL2,CT1 0-6000.0 %
IL3,CT1 Phase current IL3,CT1 0-6000.0 %
MIN,PT1 Minimum average phase current, CT1 0-6000.0 %
Max,PT1 Maximum average phase current, CT1 0-6000.0 %
Io, PT1 Zero sequence current Io, CT1 0-6000.0 %
I1,PT1 Positive sequence current I1, CT1 0-6000.0 %
I2,PT1 Negative sequence current I2, CT1 0-6000.0 %
IL1,CT2 Phase current IL1,CT2 0-6000.0 %
IL2,CT2 Phase current IL2,CT2 0-6000.0 %
IL3,CT2 Phase current IL3,CT2 0-6000.0 %
MIN,CT2 Minimum average phase current, CT2 0-6000.0 %
Max,CT2 Maximum average phase current, CT2 0-6000.0 %
Io, CT2 Zero sequence current Io, CT2 0-6000.0 %
I1,CT2 Positive sequence current I1, CT2 0-6000.0 %
I2,CT2 Negative sequence current I2, CT2 0-6000.0 %
TYPE: POWER
P,Power,CT1 Active power,CT1 3000.0 %
Q,Power,CT1 Reactive power,CT1 3000.0 %
S,Power,CT1 Apparent power,CT1 0-3000.0 %
Name of meas.
Description Setting range Unit
quantity
P,Power,CT2 Active power,CT2 3000.0 %
Q,Power,CT2 Reactive power,CT2 3000.0 %
S,Power,CT2 Apparent power,CT2 0-3000.0 %
TYPE: POWER FACTOR
PF,Power,CT1 Power factor, CT1 -0.99 ... +1.00 -
PF,Power,CT2 Power factor,CT2 -0.99 ... +1.00 -
TYPE: FREQUENCY
f,PT1 Frequency,PT1 0-80.00 Hz
f,PT2 Frequency,PT2 0-80.00 Hz
f,PT3 Frequency,PT3 0-80.00 Hz
TYPE: ANALOG INPUTS
Analog input 1 Resistance measurement: see parameter Enable [P5788] 10000000.00 -
Analog input 2 Resistance measurement : see parameter Enable [P5772] 10000000.00 -
Analog input 3 Measurement value selection: see parameter Type [P5757] 10000000.00 -
Analog input 4 Measurement value selection: see parameter Type [P5741] 10000000.00 -
P74503 Limit
Pick-up value of the first LVM-Limit Value Monitoring element. At the moment that the
value of the monitored measuring quantity (see parameter Select [P74500]),
exceeds/falls below this limit, pick-up event LVM-1 pickup [E8100] will become active,
and the trip delay time (Delay time) of the first LVM-Limit Value Monitoring element will
start.
3.8 Virtual IO
Parameter description:
Subscribers
Source subscribe ID n
There are 128 Subscribers available. Each Subscriber is to defined individually by one
group named Source subscriber ID n, whereby n is some number from1 to128.
Source subscribe ID 1
NOTE: Each Source subscribe ID always provides the same group of parameters. Hence,
the parameter descriptions of Source subscribe ID 1 represented below are described
in the following in detail as examples.
P92551 Application ID
This parameter defines the Application ID of the subscribers. The setting range is from
0 65535
NOTE: The combination of Multicast MAC address and Application ID must be
unique in the Source subscriber ID table. This combination defines the
Publisher/address of the device which is sending the GOOSE message.
Example: As Source subscriber 1 you must set parameter Multicast MAC address 01-0C-CD-
01- P[92550] = 00-01 to get the elements of device B. In device B and the
parameter Application IDP[92551] = ID1 in Device B from the same Publisher 1.
whereby:
Device A: Receiving GOOSE messages
Device B: Sending GOOSE messages
Device C: Sending GOOSE messages
Parameter description:
GOOSE inputs represents the node GGIO7 of IEC61850 data model in SYMAP-Compact(+).
GGIO7$ST$Ind1- trigger setting to GGIO7$ST$Ind128- trigger setting defines the Ind1 to
Ind128 in logical node GGIO7 in SYMAP-Compact(+) icd file/Compact IEC61850 data model.
Each trigger setting provides the following parameters and events:
Example:
IED Device C
Publisher 2
Some dataset Y
Ind1StVal
Ind1q
Ind3StVal
Ind3q
Ind99StVal
...
MAC address 2
Application ID 2
Figure 3-275 Example: Inputs mapping
Event description:
Example:
IED Device B
Publisher 1
MAC address 1
Some dataset X
Application ID 1
Ind5StVal
Ind5q
Ind9StVal
Ind9q
Ind10StVal
...
The name GGIO6$ST$Ind n( whereby n is the number between 1 and 128) correspondents
to the element in logical device System/GGIO6/ST /Indn StVal (whereby n is the number
between 1 and 128 ) in SYMAP-Compact(+) ICD file /Compact IEC61850 Data model.
It is possible to define 128 virtual free programmable outputs.
GGIO6$ST$Indnumber between 1 and 128- trigger setting
GOOSE output is the logical node GGIO6
GGIO6$ST$Ind1- trigger setting to GGIO6$ST$Ind128- trigger setting defines the Ind1 to Ind
128 in logical node GGIO6 in SYMAP-Compact(+) IEC61850 Datamodel.
Parameter description:
Event description:
Parameter description:
Parameter description:
Switching operations can be launched either locally (directly in font of the cubicle), or remotely
(by SCADA or any other automation system). For reasons of personal and system protection
the possibility of local and remote operation in parallel is not permitted. This requires an
adjustment capability of the protection and control system SYMAP-Compact(+) to differentiate
cearly the local operation mode from the remote operation mode referring to switching
operations.
Moreover, switching operations in electrical power sytems underly certain authorisation, which
are being defined and given by the system operator.
Hence, switching operations triggered via the protection and control system SYMAP-
Compact(+) require several, different user levels. Entering a certain user level can be done
either by:
hardware-coded password (such as key switches or different USB sticks) or by
software-coded password via touchscreen (see chapter User levels)
of SYMAP-Compact (+).
In order to meet the requirements mentioned above, SYMAP-Compact (+) provides different
functions ensuring the unambiguous allocation of password-protected user level and local or
remote operation for function Breaker control.
Function Emergency-OFF
This function is required to switch off the circuit breaker locally as quick as possible, in case of a
hazardous situation. The local switch-off of the circuit breaker must occur independent of the set
mode for local or remote control, and independent of any active interlockingcondition for the
breaker.
For this, two of the function keys of SYMAP-Compact (+) can be configured in a manner, that
the circuit breaker will open when function keys are beioing operated simultaneously. There are
two setting options for the function keys available: Emergency 1 and Emergency 2(see
menu: Parameter/SYSTEM/Graphic/Button configuration: Parameter [P60010] to [P60015]).
3.9.1 General
General
Parameter description:
General
The following parameters apply for all of the 8 switching elements in common.
3.9.2 Feedback
The graphic display of the SYMAP-Compact(+) shows the individual single line diagram of
switch panel configuration. The actual displayed symbols of the switching elements correspond
to the current position.
For instance, the position of a circuit breaker (CB) is acquired via two separate signal lines
captured by the auxiliary contacts of the CB. They are connected each to a binary input of the
SYMAP-Compact(+). An auxiliary contact (normally open) signals ON position of the CB while
the second (normally closed) signals OFF position.
Circuit breaker
SYMAP - -X 2.3
Compact+
30
31
32
.
Binary inputs . +
24V/48/60/110/220/230V AC/DC
. -
43
44
GND2
Apart from the ON/OFF position, the breaker positions DIFF and FAIL may also be
acquired and signaled with these two signals.
Return signal 1 (NO) Return signal 2 (NC) Position indication of switching element
0 1 OFF
1 0 ON
"0 0 DIFF (Moving)
1 1 FAIL
The device type of switching elements (SE) is assigned via parameter Type [P] in submenu:
Parameters\SWITCHGEAR CONTROL\Feedbacks. The following selection options are
available:
Disconnector
Circuit breaker (CB)
Load break switch (LBS)
Circuit breaker truck (CB Truck)
3-position diconnector (3 Position Disconnector)
3-position circuit breaker (3 Position CB)
3-position load break switch (3 Porition LBS)
3-position circuit breaker truck (3 Porition CB Truck)
Moreover, the displayed SE- symbol can be configured via parameter Breaker style [P]
according to different standards in User page menu. The following setting options are
available:
IEC
IEEE
Neutral
Figure 3-285 Selection of switching element symbol according to different standards or neutral
symbol
Plain Disconnector
Plain CB
Disconnector
CB
3 Position Plain CB
3 Position Disconnector
3 Position CB
3 Porition LBS
Disconnector Round
CB Square
Feedbacks
Parameter description:
Feedbacks
Feedback/General parameter
The following parameters are individually available for all 8 switching elements.
P ON Feedback
Parameter for feedback signal for ON position; to determine the feedback signal for ON
position of a switching element the event number of the applied signal is to be set to
parameter ON-Feedback [P]. Usually, an auxiliary contact (NO) of the switching
elelement is to be connected to a binary input of the SYMAP-Compact(+). In that case
the event number of the binary input is to be used for parameter setting.
P OFF Feedback
Parameter for feedback signal for OFF position; to determine the feedback signal for
OFF position of a switching element the event number of the applied signal is to be set
to parameter OFF-Feedback [P]. Usually, an auxiliary contact (NC) of the switching
elelement is to be connected to a binary input of the SYMAP-Compact(+). In that case
the event number of the binary input is to be used for parameter setting.
P OUT Feedback
Parameter for feedback signal for extended position of a truck; to determine the
feedback signal for extended position of a 3-position-switch the event number of the
applied signal is to be set to parameter OUT-Feedback [P]. Usually, an auxiliary
contact (NC) of the truck is to be connected to a binary input of the SYMAP-
Compact(+). In that case the event number of the binary input is to be used for
parameter setting.
P IN Feedback
Parameter for feedback signal for retracted position of a truck; to determine the feedback
signal for retracted position of a 3-position-switch the event number of the applied signal
is to be set to parameter IN-Feedback [P]. Usually, an auxiliary contact (NO) of the
truck is to be connected to a binary input of the SYMAP-Compact(+). In that case the
event number of the binary input is to be used for parameter setting.
P EARTH ON Feedback
Parameter for feedback signal for earthing position of an earthing switch or 3-position-
switch; to determine the feedback signal for earthing position of an earthing switch or 3-
position-switch the event number of the applied signal is to be set to parameter EARTH
ON-Feedback [P]. Usually, an auxiliary contact (NO) of the earthing switch or 3-position-
switch is to be connected to a binary input of the SYMAP-Compact(+). In that case the
event number of the binary input is to be used for parameter setting.
P Blink by event
Flashing mode for breaker symbol on the device display; flashing mode can be activated
by any active event. To activate, the number related to this event has to be assigned to
parameter Blink by event [P]. Activation is only effective, however, as long as the
assigend event is active. If the event turns inactive, activation of the flashing mode is
abandoned.
If activating of the flashing mode is not required, set this parameter to 0.
P Invisible by event
Mode for hiding the breaker symbol on the device display; hiding mode can be activated
by any active event. To activate, the number related to this event has to be assigned to
parameter Invisible by event [P]. Activation is only effective, however, as long as the
assigend event is active. If the event turns inactive, activation of the hiding mode is
abandoned.
If activating of the hiding mode is not required, set this parameter to 0.
: do not tick the box => the supervision mode is not activated
: do tick the box => the supervision mode is activated
Event description:
E60x0 ON Feedback
Feedback event for ON position; as soon as the feedback signal of ON position set by
parameter ON Feedback [P] is active, the referring feedback event ON
Feedback [E60x0] is being activated.
E60x3 IN Feedback
Feedback event for retracted position of a truck; as soon as the feedback signal of
retracted position set by parameter IN-Feedback [P] is active, the referring
feedback event IN-Feedback [E60x3] is being activated.
E61x0 OPEN
Position event for OFF position; the position event OPEN [E61x0] is only being
activated in case that a switching element has taken a definite position. A definite
position is determined by evaluating both, feedback event ON-Feedback [E60x0] and
feedback event OFF-Feedback [E60x1]. To activate position event OPEN [E61x0],
feedback event OFF-Feedback [E60x1] has to be activated, and
feedback event ON-Feedback [E60x0] has to be deactivated.
E61x1 CLOSED
Position event for ON position; the position event CLOSED [E61x1] is only being
activated in case that a switching element has taken a definite position. A definite
position is determined by evaluating both, feedback event ON-Feedback [E60x0] and
feedback event OFF-Feedback [E60x1]. To activate position event CLOSED [E61x1],
feedback event OFF-Feedback [E60x1] has to be deactivated, and
feedback event ON-Feedback [E60x0] has to be activated.
E61x4 EARTH
Position event for earthing position of a 3-position switch; the position event EARTH
[E61x4] is only being activated in case that 3-position switch has taken a definite
position. A definite position is determined by evaluating its feedback events EARTH ON-
Feedback [E60x4] and EARTH OFF-Feedback [E60x5] as well as ON-Feedback
[E60x0] and OFF-Feedback [E60x1]. To activate position event EARTH [E61x4],
feedback event EARTH OFF-Feedback [E60x5] has to be deactivated, and
feedback event EARTH ON-Feedback [E60x4] has to be activated and
feedback event OFF-Feedback [E60x1] has to be activated, and
feedback event ON-Feedback [E60x0] has to be deactivated.
[E60x0] and feedback event OFF-Feedback [E60x1]. To activate position event DIFF
(Moving) [E61x5],
feedback event OFF-Feedback [E60x1] has to be deactivated, and
feedback event ON-Feedback [E60x0] has to be deactivated as well.
E61x6 FAIL
Position event for failure position; the position event FAIL [E61x6] is only being
activated in case that a switching elelement has taken an undefinite position. An
undefinite position is determined by evaluating both, feedback event ON-Feedback
[E60x0] and feedback event OFF-Feedback [E60x1]. To activate position event FAIL
[E61x6],
feedback event OFF-Feedback [E60x1] has to be activated, and
feedback event ON-Feedback [E60x0] has to be activated as well.
Each of the switching elements (SE) can be configured individually according to its control
timing as well as to its switching direction:
Timing: Settings for activation duration, activation-delay and postactivation of
corresponding binary output (BO)
Closing: Switching direction: OFF to ON
Opening: Switching direction: ON to OFF
Extending: Draw-out of the truck while CB is open
Retracting: Insertation of the truck while CB is open
Earthing: Switching direction of 3-postion switch: OFF to EARTHED
Unearthing: Switching direction of 3-postion switch: EARTHED to OFF
Timing
Parameter description:
Closing direction
Opening direction
Extending direction
Retracting direction
Earthing direction
Unearthing direction
Closing
Parameter description:
Control logic
P 01
to
P 08
Input elements (events) of the Control logic to activate the switching operation for the
switching direction of the selected switching element (SE x); to this parameter events are
to be assigned to set preconditions for triggering the switching operation for individual
switching direction.
Interlocking logic
P Enable
This parameter activates/deactivates interlocking logic by following setting options:
OFF: interlocking logic is deactivated,
ON: interlocking logic is activated.
P Logic
Activation of the configurated logic for switching conditions of the switching element to
be set by programmable logic control (PLC); the output event of the logical function,
which determines the switching conditions of the selected switching direction of the
selected switching element, can be activated for module Interlocking by any active
event. For activation, the number related to this event has to be assigned to parameter
Logic [P]. Activation of the logical function for switching conditions is only effective,
however, as long as the assigned event is active. If the event turns inactive, the output
event of the logical function is blocked.
If switching conditions for the selected switching direction of the selected switching
element are not required, set this parameter to 0.
NOTE: Switching conditions of a switching element is equal to the negated form (acc.
to Boolean algebra) of its Interlocking conditions!
Interlocking condition:
Defined conditions which have to be fulfilled to prohibit closing or opening of a
switching element, e.g. the CB.
Switching conditions:
Defined conditions which have to be fulfilled to allow closing or opening of a
switching element, e.g. the CB.
One can use a logical equation (Boolean algebra) to express defined
interlocking conditions. Moreover, negating a logical equation for interlocking
conditions will result in switching conditions.
P Bypass
Blocking of the configurated logic for switching conditions of the switching element to
be set by programmable logic control (PLC); the output event of the logical function,
which determines the switching conditions of the selected switching direction of the
selected switching element, can be blocked for module Interlocking by any active
event. For blocking, the number related to this blocking event has to be assigned to
parameter Bypass [P]. Blocking is only effective, however, as long as the assigned
event is active. If the event turns inactive, the output event of the logical function for
switching conditions is effective again.
If blocking of the configurated logic for switching conditions of the selected switching
direction of the selected switching element not required, set this parameter to 0.
Counter
Parameters SE 1 SE 2 SE 3 SE 4 SE 5 SE 6 SE 7 SE 8
Closed->OPEN cycles 065000 065000 065000 065000 065000 065000 065000 065000
Closed->OPEN cycles max 065000 065000 065000 065000 065000 065000 065000 065000
OPEN->EARTH cycles 065000 065000 065000 065000 065000 065000 065000 065000
OPEN->EARTH cycles max 065000 065000 065000 065000 065000 065000 065000 065000
Breaker Counter Events
Closed->OPEN cycles max 6311 6321 6331 6341 6351 6361 6371 6381
OPEN->EARTH cycles max 6313 6323 6333 6343 6353 6363 6373 7383
Parameter description:
P Closed->OPEN cycles
Set counting start value for all the switching operations of a switching element with
switching direction CLOSED to OPEN; this counter is being incremented, if switching
operation was conducted for the switching direction CLOSED to OPEN.
P OPEN->EARTH cycles
Set counting start value for all the switching operations of a 3-position switch with
switching direction OPEN to EARTH; this counter is being incremented, if switching
operation was conducted for the switching direction OPEN to EARTH.
Event description:
As soon as the set counting limit for all the switching operation with switching direction
OPEN to EARTH set by parameter OPEN->EARTH cycles max [P] has been
reached, event OPEN->EARTH cycles max [E63x3] is activated.
NOTE: Event [E63x3] can be used for indicating the need for revising the primary
contacts of the switching element.
3.10 RECORDER
Fault recorder
Parameter description:
P8061 Function
Fault recording can be activated by any active event (activation-event) assigned to
parameter P[8061] or by any active trip-event. For activation via activation-event the
number related to this event has to be assigned to parameter Function. At the time the
trigger-event is being activated, the rising signal edge of the trigger-event starts the
recording (snapshot of the measuring values).
If fault recording is not required, set this parameter to 0.
NOTE: Function Disturbance Recorder is not available for hardware version HW v1-1.x!
For function Disturbance recorder the device is equipped with a volatile 20 MB RAM-memory
for buffering the measuring data. That RAM-memory can be devided in up to 10 idividual
memory sections (buffers for recorded data) by parameter Number of internal buffers [P8002].
Each buffer provides the following states:
ready
recording
data
backup
inactive
When there are two buffers adjusted: Number of internal buffers [8002] = 2, buffer 1 assumes
state ready; whereas buffer 2 assumes state inactive.
NOTE: At the time, one of the buffers claims state ready, event DiREC Ready [E8000] is
being activated.
Then, the disturbance recorder first saves the recorded data of each sample in buffer 1. When
memory capacity limit of buffer 1 is reached, the oldest recorded sample of buffer 1 will be
overwritten according to the FIFO-principle.
As soon as:
one of the assigned trigger-events (see parameters Trigger [P8018] to [P8027]) is
activated or
a manual trigger of the disturbance recorder takes place by operating hotkey Trigger
Snapshot via touchscreenm (menu: Main Menu/Recorder/Disturbance recorder),
the state of buffer 1 changes over from ready to recording (recording mode), and event
DiREC Recording [E8001] is being activated.
In case a pre-trigger-time was taken into account by the set value of parameter Pre-trigger
time [P8007], the point of time of trigger does not represent the point of time of recording.
According to the set pre-trigger-time the recording duration is calculated which is for recording
data before the point of time of activating the trigger-event. Thus, the date of recording start is
befor the date of triggering the recorder.
The maximum recording time results from the size of the buffer memeory, the sample rate, and
the data volume of each sample.
As long as the trigger-event is activated, recording is for the set recording time. In case that
this time has not run down and the trigger-event becomes inactive, recording duration is
according to the recording time-after-trigger set by parameter Follow-up time [P8008] or the
recording time-after-manual trigger set by parameter Follow-up time (manual) [P8009].
When recording has finished the state of buffer 1 changes from recording to data (waiting
mode), and event DiREC Recording [E8001] is being deactivated. Hence follows, that buffer 1
contains recorded data which are prepared to be stored in a non-volatile manner on the memory
of SD-card.
Subsequently, function disturbance recorder tries buffer 1 to assume state ready. Hereby,
the following cases have to be taken into account:
Table 3-27 Disturbance recorder changes of states
Only if buffer 1 gains state ready, the disturbance recorder is able to processanother active
trigger-event; otherwise the new active trigger-event is being ignored.
As promptly as practicable, copying of data from buffer 1 to the memory of SD card will start.
Depending on the recording time and processor workload, transmitting data could last up to
several minutes. At the time the copy process is started buffer 1 assumes state backup, and
event DiREC Backup [E8003] is being activated.
After copy process has finished buffer 1 assumes state inactive, and event [E8003] is being
deactivated.
NOTE: At the time, the memory of the SD-Card is fully occupied, event DiREC Full memory
[E8004] is being activated.
In case that there is no SD-card available, the Event DiREC No memory card
[E8005] is being activated.
At the time, writing/reading the memory of the SD-card fails for any reason, event
DiREC Memory error [E8006] is being activated.
At the time, a CRC error of a recorded file is indicated, event DiREC File error
[E8007] is being activated.
Disturbance recorder
E8000 Di-REC-Ready - - -
E8001 Di-REC-Recording - - -
E8002 Di-REC-Buffer overflow - - -
E8003 Di-REC-Backup - - -
E8004 Di-REC-Full memory - - -
E8006 Di-REC-No memory card - - -
E8007 Di-REC-Memory error - - -
E8000 Di-REC-File error - - -
Figure 3-302 Fault recorder Parameter [P] and Events [E]
Parameter description:
General parameters
P8000 Function
This parameter enables/disables disturbance recording function where:
OFF: disables or
ON: enables the disturbance recording function.
P8004 Overwrite
Release for overwriting the next buffer; in case that all buffers provide recorded data for
saving at the SD-card and another trigger-event becomes active, then overwriting the
memory section of the next buffer can be released, however, the next buffer has to
provide status data. Setting option:
OFF: deactivates the release for overwriting,
ON: activates the release for overwriting.
At the time, overwriting of the next buffer starts, event DiREC Buffer overflow [E8002]
is being activated.
Trigger events
P8018 Trigger #1
to
P8027 Trigger #10
Data recording via disturbance recorder can be triggered by any active event. For
triggering, the number related to this blocking event has to be assigned to parameter
[P2876]. There are up to 10 individual trigger-events, see parameters [P8018] to
[P8027].
If triggering the disturbance recording by any trigger-event is not required, set this
parameter to 0.
Recording events
P8028 Event #1
to
P8059 Event #32
Freely-parameterizable events as measuring data for the disturbance file; for additional
recording of binary channels there are up to 32 parameters available which can be used
to assign any of the available events.
If none of the binary channels as measuring data required for recording, set this
parameter to 0.
3.11.1.1 AND/OR
By using selection button Selection the first of 500 available logic elements AND/OR can be
invoked. It carries the event-number [E5000].
Parameter description:
NOTE: Each one of the 500 logic elements AND/OR always provides equal parameters.
Hence, the parameter descriptions of the first logic element AND/OR represented
below are described in the following in detail as examples.
P Enable
This Parameter activates/deactivates the logic element AND/OR invoked by selection
button Selection.
: do not tick the box => logic element is deactivated
: do tick the box => logic element is activated
P Type
Assignment of the logic scheme to the selected logic element AND/OR via the
following setting options:
AND: logic scheme accords to an AND gate
OR: logic scheme accords to an OR gate
P Number of inputs
Definition of the number of applied input elements of the selected logical element
AND/OR via the following setting options:
2: logic element provides two input elements,
3: logic element provides three input elements,
4: logic element provides four input elements,
5: logic element provides five input elements.
P 01
to
P 05
Assignment of any available event to an input element of the selected logic element
AND/OR; the number of available input elements of the logic element is being
determined by parameter Number of inputs.
Each available event can be used as an input element; therefore the event-number has
to be registered in the arrey besides the number of the input element.
By using selection button Selection the first of 30 available logic elements NOT(Inverter) can
be invoked. It carries the event-number [E5500].
Parameter description:
NOTE: Each one of the 30 logic elements NOT(Inverter) always provides equal parameters.
Hence, the parameter descriptions of the first logic element NOT(Inverter)
represented below are described in the following in detail as examples.
P Enable
This Parameter activates/deactivates the logic element NOT(Inverter) invoked by
selection button Selection.
: do not tick the box => logic element is deactivated
: do tick the box => logic element is activated
P 01
Assignment of any available event to the input element of the selected logic element
NOT(Inverter)
Each available event can be used as an input element; therefore the event-number has
to be registered in the arrey besides the number of the input element.
By using selection button Selection the first of 20 available logic elements XOR (Exclusive
OR) can be invoked. It carries the event-number [E5530].
Parameter description:
NOTE: Each one of the 20 logic elements XOR (Exclusive OR) always provides equal
parameters. Hence, the parameter descriptions of the first logic element XOR
(Exclusive OR) represented below are described in the following in detail as
examples.
P Enable
This Parameter activates/deactivates the logic element XOR (Exclusive OR) invoked
by selection button Selection.
: do not tick the box => logic element is deactivated
: do tick the box => logic element is activated
P 01
and
P 02
Assignment of any available event to an input element of the selected logic element
XOR (Exclusive OR)
Each available event can be used as an input element; therefore the event-number has
to be registered in the arrey besides the number of the input element.
Figure 3-307 PLC XOR(Eclusive OR): inversion of input elements and output-event
3.11.1.4 FlipFlops
By using selection button Selection the first of 20 available logic elements FlipFlop can be
invoked. It carries the event-number [E5550].
Parameter description:
NOTE: Each one of the 20 logic elements FlipFlop always provides equal parameters.
Hence, the parameter descriptions of the first logic element FlipFlop represented
below are described in the following in detail as examples.
P Enable
This Parameter activates/deactivates the logic element FlipFlop invoked by selection
button Selection.
: do not tick the box => logic element is deactivated
: do tick the box => logic element is activated
P Store non-volatile
Definition of storing behaviour for the current state of the output event [E5550] of
selected logic element FlipFlop after system reboot:
: do not tick the box => current state of output event [E5550] of selected logic
element is not being saved after system reboot
: do tick the box => current state of output event [E5550] of selected logic
element is being saved after system reboot
P Type
Assignment of the logic scheme to the selected logic element FlipFlop via the following
setting options:
RS: logic scheme accords to RS-FlipFlop; domination of input element
for resetting (R) the flipflop or
RS-EDGE: logic scheme accords to RS-FlipFlop; setting of the flipflop only in
by rising edge signal of the event assigned to the input element S or
SR: logic scheme accords to SR-FlipFlop; domination of input element
for setting (S) the flipflop or
T: logic scheme accords to Toggle-FlipFlop;setting of the flipflop
by rising or a falling edge signal of the event assigned to the input
element S
P 01
and
P 02
Assignment of any available event to an input element of the selected logic element
FlipFlop
Each available event can be used as an input element; therefore the event-number has
to be registered in the arrey besides the number of the input element.
3.11.1.5 Counter
By using selection button Selection the first of 20 available logic elements Counter can be
invoked. It carries the event-number [E5570].
Parameter description:
NOTE: Each one of the 20 logic elements Counter always provides equal parameters.
Hence, the parameter descriptions of the first logic element Counter represented
below are described in the following in detail as examples.
P Enable
This Parameter activates/deactivates the logic element Counter invoked by selection
button Selection.
: do not tick the box => logic element is deactivated
: do tick the box => logic element is activated
P Store non-volatile
Definition of storing behaviour for the current counter value of selected logic element
Counter after system reboot:
: do not tick the box => current counter value of selected logic element is being
reset to the value given by parameter Start value
: do tick the box => current counter value of selected logic element is being
saved after system reboot
P Count edge
Definition of counting behaviour to increment/decrement the counting value of the
selected logic element Counter; depending on the following setting options the counter
value is being incremented/decremented:
RISING: only in case of a rising edge signal of the event assigned to the input
element Count or
FALLING: only in case of a falling edge signal of the event assigned to the input
element Count or
ANY: only in case of a rising or falling edge signal of the event assigned to
the input element Count.
P Start value
Start value of the selected logic element Counter; after system reoboot
incrementing/decrementing of the counting value starts at the set value of parameter
Start value [P] (setting range: 0 to 65000).
P Count limit
End value of the selected logic element Counter; as soon as the counter has reached
the set value of parameter Count limit [P] (setting range: 0 to 65000), counting is being
stopped and the output event [E5570] is activated.
P Count
Assignment of any available event to the input element Count of the selected logic
element Counter to increment/decrement the counting value; as soon as the assigned
event is active, the counting value is being incremented/decremented.
NOTE: The counting behaviour of the logic element Counter is set by parameter
Direction.
The counting behaviour for incrementing/decrementing depends on the signal
edge of the counting-event which is being set by parameter Count edge
P Block
Assignment of any available event to block counting procedure of selected logic element
Counter; counting procedure can be completely blocked by any active event. For
blocking, the number related to this blocking event has to be assigned to parameter
Block. Blocking is only effective, however, as long as the blocking event is active. As
soon as blocking is active, counting is stopped and the current counter value is saved. If
the blocking event turns inactive, blocking is abandoned and counting is effective again
continuing with the saved value.
If blocking of counting is not required, set this parameter to 0.
P Reset
Assignment of any available event to block counting procedure and reset of counitng
value to the start value of selected logic element Counter; counting procedure can be
completely blocked by any active event. For blocking, the number related to this blocking
event has to be assigned to parameter Block. Blocking is only effective, however, as
long as the blocking event is active. As soon as blocking is active, counting is stopped
and the current counter value is saved. If the blocking event turns inactive, blocking is
abandoned and counting is effective again continuing with the saved value.
If blocking of counting and resetting of counting value is not required, set this parameter
to 0.
P Direction
Definition of the counting behaviour according to incrementing/decrementing the
counting value of the logic element Counter; depending on the setting option:
0: the counter is being incremented or
1: the counter is being decremented.
3.11.1.6 Timer
By using selection button Selection the first of 80 available logic elements Timer can be
invoked. It carries the event-number [E5600].
Parameter description:
NOTE: Each one of the 80 logic elements Timer always provides equal parameters. Hence,
the parameter descriptions of the first logic element Timer represented below are
described in the following in detail as examples.
P Enable
This Parameter activates/deactivates the logic element Timer invoked by selection
button Selection.
: do not tick the box => logic element is deactivated
: do tick the box => logic element is activated
P Function
Definition of working priciple of the logic element Timer according to the following
setting options:
Delay: on-delayed/off-delayed activation of output event [E5600]; in case that
the event which is assigned to the input element 01 is activated and
delay time set by parameter ON time has run down, the output event
[E5600] is being activated. As soon as the event of the input element
has become deactivated and the delay time set by parameter OFF
time has run down, the output event is being deactivated.
Pulse-C: constant pulse duration (C); in case that the event which is assigned
to the input element 01 is activated, output event [E5600] is being
activated for the duration of time set by parameter ON time.
Pulse-CR: constant pulse duration (C) and possibility of restart (R); in case that
the event which is assigned to the input element 01 is activated,
output event [E5600] is being activated for the duration of time set by
parameter ON time. In case that during on-time the event of the input
element is activated once again (rising edge of event signal), the
output event [E5600] remains active for the duration of set on-time.
Pulse-I: pulse duration and possibility of interrupt (I);in case that the event
which is assigned to the input element 01 is activated, output
event [E5600] is being activated for the duration of time set by
parameter ON time. In case that during on-time the event of the input
element is deactivated (falling edge of event signal), the on-time is
stopped and output event [E5600] is being deactivated.
Pulses: pulses of defined duty cycle; in case that the event which is assigned
to the input element 01 is activated, output event [E5600] is being
activated for the duration of time set by parameter ON time. As soon
as the on-time has run down, the output event is being activated for the
duration of time set by parameter OFF time.
P ON time
Settable time delay (setting range: 0 to 65000ms/s/min/h) of an on-delayed activation of
the output event [E5600] of the logic element Timer
P OFF time
Settable time delay (setting range: 0 to 65000ms/s/min/h) of an off-delayed deactivation
of the output event [E5600] of the logic element Timer
P Unit
Unit of time for setting options of parameters ON time and OFF time;
ms: millisecond
sec: second
min: minute
h: hour
NOTE: The tolerance specification is valid for the following setting options of the
logical element Timer:
ms and sec: +/- 10 ms
min and h: +/- 1 s
P 01
Assignment of any available event to the input element of the selected logic element
Timer
Each available event can be used as an input element; therefore the event-number has
to be registered in the arrey besides the number of the input element.
By using selection button Selection the first of 20 available logic elements Timer switch can
be invoked. It carries the event-number [E5680].
Parameter description:
NOTE: Each one of the 20 logic elements Timer switch always provides equal parameters.
Hence, the parameter descriptions of the first logic element Timer switch
represented below are described in the following in detail as examples.
P Enable
This Parameter activates/deactivates the logic element Timer switch invoked by
selection button Selection.
: do not tick the box => logic element is deactivated
: do tick the box => logic element is activated
P Mode
Operating mode for termination of activating the output event [E5680] for a duration set
by parameter Pulse according to following setting options:
Day in month: output event [E5680] is being activated on a certain day of
each calendar month, at a specific time set by parameter
Time and for a specific duration of time set by parameter
Pulse.
Day of week: output event [E5680] is being activated on a certain day of
each week, at a specific time set by parameter Time and
for a specific duration of time set by parameter Pulse.
Weekday in month: output event [E5680] is being activated on a certain weekday
of each month, at a specific time set by parameter Time
and for a specific duration of time set by parameter Pulse.
P Day
Termination of the day of activating the output event [E5680] in dependence of the
setting options of parameter Modus and for a duration time set by parameter Pulse;
According to the selected mode for the logic element Timer switch, there are different
setting options of the parameter Day:
Modus = Day in month:
1: activation of output event [E5680] occurs on the 1rst calendar day of each
calendar month
:
31: activation of output event [E5680] occurs on the 31rst calendar day of each
calendar month
CAUTION: Choice of calendar day depends on the maximum number of days of the
different months!
P Time
Specific time at which the output event [E5680] is being activated in dependence of the
selected mode and of the specific duration set by parameter Pulse; the set time is to be
registered as hours:minutes:seconds = 00:00:00
P Pulse
Specific duration of time delay (setting range: 0 to 65000ms) of the output event [E5680]
is being activated for, in dependence of the selected mode, selected setting option of
parameter Day and specific time set by parameter Time.
The "Power Management System (PMS)" controls and ensures the provision of electrical
energy in a consumer system.
SYMAP-Compact(+) is an independent PMS with many features for managing and monitoring
of energy generation and distribution systems in low and medium voltage range. The functions
of the PMS are included in each SYMAP-Compact(+) device of a system and are not part of an
external controller. If one of the SYMAP-Compact(+) fails, the PMS function is maintained by
the remaining devices. Thus, the control of energy supply is independent of all other automation
systems and redundant in itself.
SYMAP-Compact(+) is suitable for the control of various equipment, such as:
Emergency power systems
Naval equipment (auxiliary diesel, emergency generator, shaft generators) and turbines
Because of its extensive features, it is the ideal solution for many applications:
Power Plant systems / Emergency power systems:
Monitoring of one or more utility grids by one device
Automatic start of the genset in case of mains failure (AMF)
Monitored control of engine start and stop phase
Group start of multiple gensets and synchronization during starting (dead-field paralleling )
Energizing of transformers or electric motors by generator during starting phase
Control of one or more mains breaker
Automatic synchronization and control of the generator breaker
Generator protection
Protection of the prime mover
Control of generator voltage and frequency
Balancing of active and reactive power in multi-generator operation
Separate load balancing on each bus section
Load shedding on overload
Automatic load transfer from generator to mains with synchronization
Test run parallel to the mains
Functions for mains decoupling according to VDE-AR-4105 / BDEW
Active and reactive power control in accordance with VDE-AR-4105 / BDEW
G G
Bus tie
Consumer Consumer
Figure 3-315 Example: Emergency power system
Emergency-
generator
G
Shaft- 1st Aux.- 2nd Aux.-
generator generator generator
G G G
Bus tie
Consumer
essential unessential Shore- Consumer
connection
Figure 3-316 Example: Naval power system
General
Parameter description:
NOTE: The assignment of the voltage measurement input (PT1, PT2 or PT3) to the
current measurement input CT1 or CT2 is to be done by the following
parameters (referring to the setting options of parameter [P1582]), in the
submenu SYSTEM\Measuring\Power:
PT reference [P9410], for Power_CT1 and
PT reference [P9413], for Power_CT2
To measure power direction correctly, the needed energy flow direction is to
be defined by following parameters:
Direction [P9411], for Power_CT1 and
Direction [P9414], for Power_CT2.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
NOTE: The maximum limit Pmax of the operating range of the active power controller is
to be set as a percentage of the nominal value of the chosen characteristic
quantity generator power (nominal value of the motor drive [kW]). This
nominal value is to be set by parameter:
Here, it is that winding side relating to the active power measurement, which is
assigned to the applied current measurement input by parameter
The parameters Power [P605], Power [P615] and Power [P625] are
located in submenu: SYSTEM\Nominals\Reference values.
NOTE: The minimum limit Pmin of the operating range of the active power controller is
to be set as a percentage of the nominal value of the chosen characteristic
quantity generator power (nominal value of the motor drive [kW]). This
nominal value is to be set by parameter:
Power [P605], for primary side W1 or
Power [P615], for secondary side W2 or
Power [P625], for tertiary side W3.
Here, it is that winding side relating to the active power measurement, which is
assigned to the applied current measurement input by parameter
The parameters Power [P605], Power [P615] and Power [P625] are
located in submenu: SYSTEM\Nominals\Reference values.
If a busbar of a power system (network) is powered by several generators and divided into
several busbar sections (subnetwork) by sectionalizers (switching elements), then it is
necessary to adapt the energy of the generator(s) feeding to one busbar section to the
remaining load connected to that subnetwork.
When several generators are connected to one busbar section, these generators have to
contribute proportionally to provide the required feed-in power. The shared provision of power is
called load sharing, whereby power control of each generator is to be done by its individual
SYMAP-Compact generator control unit.
Establishing of the busbar sections is a dynamic process and depends on the positions of the
sectionalizers (see various operating modes of the power system).
For a load sharing process within one busbar section the following requirements should be met:
It has to be assigned an individual net number to each busbar section
The net number of a busbar section has to be set in all those SYMAP-Compact generator
control units which conrtibutes to provide feed-in power to the same busbar section
Recognition of the switch positions of all sectionalizers which contributes to built a busbar
section
Establishment of device-device-communication between all SYMAP-Compact generator
control units of the power system
Possibility to adapt the set net number of each SYMAP-Compact generator control unit
depending on the actual operating mode (net selection procedure)
Net configuration
Parameter description:
Net selector:
NOTE: When all digits are of binary state 0, the generator control unit
operates with net number 1!
If several energy recources contribute to provide electrical energy in a power system (mains
parallel operation or parallel operation in isolated operation), the control of active power (feed-in
power) provided by generators always becomes necessary.
As opposed to that, for isolated operation of a single genset (motor drive + generator) no load
sharing is possible, and as a result, control of active power is not necessary.
Parallel operation differentiates between the following, different applications:
Parallel operation of several gensets (isolated operation of more than two gensets)
Parallel operation: genset / grid
Parallel operation: genset / genset (isolated operation of two gensets)
Different kinds of parallel operation require different ways to distribute the load
(symmetrical/asymmetrical) to the applied energy recources. Hence, different methods for
controlling the active power of the generator(s) are required.
To avoid any speed changes the motor drive of the gensets are always equipped with a speed
controller. Parallel operation of such gensets would only be possible:
if a load balancing signal is available (symmetrical load sharing), or
if the genset(s) are equipped with an additional droop control (asymmetrical load sharing).
For parallel operation of gensets without load balancing signal the motor drives must be
equipped with additional droop controllers.
If the motor drive does neither provide a load balancing signal nor a droop controller, then droop
functionality can be established by the setpoint parameters of the SYMAP-Compact(+)
frequency controller (see chapter 3.12.1.4 Frequency Controller):
1. Droop [P7166],
2. Droop [P7169], or
3. Droop [P7172]
CAUTION: The parameters for droop control are not available yet!
By using a droop controller the genset is able to operate according to a static characteristic
curve which defines the linear dependence between machine rotation speed n and generator
output active power Pout.
Idling speed
Full load speed
Pn Pout
Parameter description:
P7100 Function
This parameter activates/deactivates the active power controller, whereby setting:
OFF: deactivates the active power controller, or
AUTO: activates the active power controller automatically as soon as events
assigned to parameters Automatic mode [P7001] and Busbar
connected [P7002] becomes active, or
ON: activates the active power controller automatically as soon as event
assigned to parameter Busbar connected [P7002] becomes active.
When active power controller is activated by parameter [P7100] event Active power
controller active [E7100] becomes active.
NOTE: The maximum limit Pmax of the operating range of the active power controller is
to be set as a percentage of the nominal value of the chosen characteristic
quantity generator power (nominal value of the motor drive [kW]). This
nominal value is to be set by parameter:
Power [P605], for primary side W1 or
Power [P615], for secondary side W2 or
Power [P625], for tertiary side W3.
Here, it is that winding side relating to the active power measurement, which is
assigned to the applied current measurement input by parameter
The parameters Power [P605], Power [P615] and Power [P625] are
located in submenu: SYSTEM\Nominals\Reference values.
CAUTION: When setting the setpoint for active power control of the local generator the
following should be taken into account:
Mains parallel operation: here, the setpoint for the feed-in power of the local
generator must not exceed rated power at the network connection point!
Parallel operation in isolated operation (asymmetrical load sharing): the feed-
in power of the local generator must not exceed the consumed load; otherwise
busbar frequency would increase!
When several events for activating the different setpoints are simultaneously activated, the
following table gives conclusion about the priority of the setpoint supplied to the active power
controller:
Table 3-33 Priorities of setpoint supply to the active power controller
Status of activation-events
Active setpoint
2.Setpoint enable 3. Setpoint enable 4. Setpoint enable (Communication)
[P7106] [P7108] [P7110]
inactive inactive inactive 1. Setpoint (default) [P7205]
inactive inactive active 4. Setpoint (Communication) [P7110]
inactive active inactive 3. Setpoint [P7109]
inactive active active 3. Setpoint [P7109]
active inactive inactive 2. Setpoint [P7107]
active inactive active 2. Setpoint [P7107]
active active inactive 2. Setpoint [P7107]
active active active 2. Setpoint [P7107]
NOTE: The setpoint settings are to be set as a percentage of the nominal value of the
chosen characteristic quantity generator power (nominal value of the motor
drive [kW]). This nominal value is to be set by parameter:
Power [P605], for primary side W1 or
Power [P615], for secondary side W2 or
Power [P625], for tertiary side W3.
Here, it is that winding side relating to the active power measurement, which is
assigned to the applied current measurement input by parameter
The parameters Power [P605], Power [P615] and Power [P625] are
located in submenu: SYSTEM\Nominals\Reference values.
P7107 2. Setpoint
Second setpoint for the event-controlled changeover of the active power controller; when
event-controlled function asymmetrical load sharing (see Parameter Balanced mode
[P7103] is deactivated and event-controlled changeover of the active power controller to
the second setpoint (see parameter 2.Setpoint enable [P7106]) is active, the active
power controller operates according to the setpoint set by parameter [P7107]
P7109 3. Setpoint
See description of parameter [P7107]
3-point controller
The Active power controller of SYMAP-Compact(+) is designed as a three step control
including the output states: active power increase and active power decrease. For this, the
following two control-events are provided:
Active power increase [E7123]: signal to external speed governer to increase machine
rotation speed (motor drive) => increase of output
active power of a single generator in mains parallel
operation, or several, parallel operating gensets in
isolated operation, and
Active power decrease [E7124]: signal to external speed governer to decrease machine
rotation speed (motor drive) => decrease of output
active power of a single generator in mains parallel
operation, or several, parallel operating gensets in
isolated operation.
Additionally, two further collective events are provided:
Collective event: speed increase [E7004]: this event becomes active when event(s)
[E7183] or/and event [E7123] is/are active,
and
Collective event: speed decrease [E7005]: this event becomes active when event(s)
[E7184] or/and event [E7124] is/are active,
which are individually OR-connected with both, the events of the frequency controller:
Frequency increase [E7183]: signal to external speed governer to increase machine
rotation speed (motor drive) => increase of generator
frequency for islolated operation (single genset or
several gensets in parallel operation), and
Frequency decrease [E7184]: signal to external speed governer to decrease machine
rotation speed (motor drive) => decrease of generator
frequency for islolated operation (single genset or
several gensets in parallel operation),
Depending on the type of motor speed governer the control events have to be assigned to:two
different binary outputs of the SYMAP-Compact(+) (binary control, e.g. for naval applications)
REMARK: In view of the following statements the momentary control deviation (active power
difference Pset, act.) is given as a percentage P[%] of the nominal power Pn set
by parameter Power [P605].
Depending on the activation of function Symmetrical load sharing (see parameter Balanced
mode [P7103], active power control is according to either a dynamic setpoint (symmetrical load
sharing) or a static setpoint (asymmetrical setpoint).
1.Deadband [P7124]
pset 1.Deadband [P7124]
pact(t)
t
Counter Pulse time
[P7123]
1. Pulse duration at 100% deviation
0
tP-contr., pulse time 1
t
tP-contr., pulse time 8 tP-contr., pulse time 15
0
t
tP-contr., Interval time tP-contr., Interval time tP-contr., Interval time
0
t
Active power increase [E7123]
0
t
Figure 3-321 Active power control dynamic setpoint supply (symmetrical load sharing)
Deadband [P7124]
pset
Deadband [P7124]
pact(t)
t
Counter Pulse time
[P7123]
1. Pulse duration at 100% deviation
0
tP-contr., pulse time 1
t
tP-contr., pulse time 8 tP-contr., pulse time 15
0
t
tP-contr., interval time tP-contr., interval time tP-contr., interval time
0
t
[E7123] Active power increase
0
t
Figure 3-322 Active power control static setpoint supply (asymmetrical load sharing)
P7124 1. Deadband
Deadband of the 3-point controller; when control deviation is below the set value of
parameter 1. Deadband [P7124], then events Active power increase [P7123] and
Active power decrease [P7124] are deactivated (blocked).
P7128 2. Deadband
Second deadband which is used by the 3-point controller when the event assigned to
parameter 2 Settings enable [P7125] is active.
See description of parameter [P7124]
NOTE: When several switch-over signals for limit activation are activated simultaneously by
the grid operator, the active power output is controlled according to the lowest active,
required limit!
Table 3-34 Prioritization of active power limits
Activation-events of parameters:
active limit
1. Limit enable [P7140] 2. Limit enable [P7142] 3. Limit enable [7144]
inactive inactive inactive no limit active
active inactive inactive 1. limit active
inactive active inactive 2. limit active
inactive inactive active 3. limit active
active active inactive 1. limit active
active inactive active 1. limit active
inactive active active 2. limit active
active active active 1. limit active
Controllable, connected power generation systems have to launch active power output
reduction immediately, and finish within one minute. When required limit value is less than 10%
of rated power, the operator of the connected power generation system is entitled to disconnect
the power system from the grid.
Event-controlled changeover of the active power controller to the first active power limit
set by parameter 1. Limit [P7141] to meet the required maximum active power output;
changeover can be activated by any active event. For activation of the first active power
limit, the number related to this activation event has to be assigned to parameter
[P7140]. Activation is only effective, however, as long as the assigned event is active. As
soon as the first active power limit is active, the active power output of the connected
power generating system is limited to the set value of parameter [P7141] and event
Limit active [E7140] is activated. If the assigned event becomes inactive, event [E7140]
is deactivated unless the 2. limit or 3. limit is activated.
If activation of the first, parameterizable active power limit for the active power controller
is not required, set this parameter to 0.
P7141 1. Limit
Set value for the first limit for the required maximum active power output; as soon as the
event which is assigned to parameter 1. Limit enable [P7140] turns to active, the active
power output is limited to the set value of parameter [P7141].
P7143 2. Limit
Set value for the second limit for the required maximum active power output; as soon as
the event which is assigned to parameter 2. Limit enable [P7142] turns to active, the
active power output is limited to the set value of parameter [P7143].
P7145 3. Limit
Set value for the third limit for the required maximum active power output; as soon as the
event which is assigned to parameter 3. Limit enable [P7144] turns to active, the active
power output is limited to the set value of parameter [P7145].
fGrid P
p
P = 40%PM/Hz
50,2Hz fGrid
p = 20 PM
50Hz
50,2Hz < fGrid <51,5Hz
NOTE: When grid frequency exceeds 51,5Hz the connected power generating system has to
be immediately disconnected from the grid!
When grid frequency falls below the set value of parameter Activation limit [P7147]
according to BDEW directive: 50,2Hz, increase of the active power output is performed
according to the set values of the active power controller (see BDEW directive: 10%
rated power of the connected power generating system per minute).
If several energy recources contribute to provide electrical energy in an isolated operated power
system, frequency control of the generator(s) individually equipped with a droop controller
(static characteristic curve of machine rotation speed/output power) always becomes
necessary.
As opposed to that, for isolated operation of a single genset (motor drive + generator) the droop
controller can be neglected or switched off.It is the speed of the motor drive which obtains a
constant frequency along the whole range of consumed load. Hence, it is not necessary to
provide frequency control via SYMAP-Compact(+) .
Parallel operation differentiates between the following, different applications:
Parallel operation: genset / grid
Parallel operation of several gensets with (e.g. shaft generator)
Synchronisation process of local genset to another network
To avoid any speed changes the motor drive of the gensets are always equipped with a speed
controller. Parallel operation of such gensets would only be possible:
if a load balancing signal is available (symmetrical load sharing), or
if the genset(s) are equipped with an additional droop control (asymmetrical load sharing).
For parallel operation of gensets without load balancing signal the motor drives must be
equipped with additional droop controllers (static characteristic speed curve with proportionality
factor or droop).
If the motor drive does neither provide a load balancing signal nor a droop controller, then droop
functionality can be established by the setpoint parameters of the SYMAP-Compact(+)
frequency controller:
1. Droop [P7166],
2. Droop [P7169], or
3. Droop [P7172]
CAUTION: The parameters for droop control are not available yet!
By using a droop controller the genset is able to operate according to a static characteristic
curve which defines the linear dependence between machine rotation speed n and generator
output active power Pout.
Idling speed
Full load speed
Pn Pout
Frequency controller
Parameter description:
P7160 Function
This parameter activates/deactivates the active frequency controller, whereby setting:
OFF: deactivates the active frequency controller, or
AUTO: activates the active frequency controller automatically as soon as events
assigned to parameters Automatic mode [P7001] and Busbar
connected [P7002] becomes active, or
ON: activates the active frequency controller automatically as soon as event
assigned to parameter Busbar connected [P7002] becomes active.
When active frequency controller is activated by parameter [P7160] event Frequency
controller active [E7160] becomes active.
CAUTION: When setting the setpoint for frequency control of the local generator the following
should be taken into account:
Isolated operation of the local genset: here, the frequency setpoint of the local
generator must not exceed rated frequency of the genset (rated speed of
motor drive)!
Parallel operation in isolated operation: all generator controls of the gensets
have to be supplied with the same setpoint for their frequency controllers.
When several events for activating the different setpoints are simultaneously activated, the
following table gives conclusion about the priority of the setpoint supplied to the frequency
controller:
Table 3-35 Priorities of setpoint supply to the frequency controller
Status of activation-events
Active setpoint
2.Setpoint enable 3. Setpoint enable 4. Setpoint enable (Communication)
[P7167] [P7170] [P7173]
inactive inactive inactive 1. Setpoint (default) [P7165]
inactive inactive active 4. Setpoint (Communication) [P7173]
inactive active inactive 3. Setpoint [P7171]
inactive active active 3. Setpoint [P7171]
active inactive inactive 2. Setpoint [P7168]
active inactive active 2. Setpoint [P7168]
active active inactive 2. Setpoint [P7168]
active active active 2. Setpoint [P7168]
(P7166 1. Droop)
CAUTION: The parameters for droop control are not available yet!
Proportionality factor for speed decrease in dependence of generator output active
power; when the local genset is in parallel operation with several gensets or with the
grid, the motor drive of the local genset needs to be provided with a load balancing
signal or a droop controller (static characteristic frequency curve). If the local genset is
only equipped with speed controller, then the required static control function can be
established by the following frequency controller parameters of SYMAP-Compact(+):
1. Droop [P7166],
2. Droop [P7169], or.
3. Droop [P7172]
characteristic quantity power (nominal value of the motor drive in [kW]). This
nominal value is to be set by parameter:
Power [P605], for primary side W1 or
Power [P615], for secondary side W2 or
Power [P625], for tertiary side W3.
Here, it is that winding side relating to the active power measurement, which is
assigned to the applied current measurement input by parameter
The parameters Power [P605], Power [P615] and Power [P625] are
located in submenu: SYSTEM\Nominals\Reference values.
Function of droop parameters could only be applied when the speed setpoint
is supplied as an analog signal or via CAN 1 communication, and the supplied
setpoint is transmitted to the speed controller of the genset motor drive!
P7168 2. Setpoint
See description of parameter [P7165]
(P7169 2. Droop)
CAUTION: The parameters for droop control are not available yet!
See description of parameter [P7166]
P7171 3. Setpoint
See description of parameter [P7168]
(P7172 3. Droop)
CAUTION: The parameters for droop control are not available yet!
See description of parameter [P7169]
3-point controller
The Frequency controller of SYMAP-Compact(+) is designed as a three step control
including the output states: frequency increase and frequency decrease. For this, the following
two control-events are provided:
Frequency increase [E7183]: signal to external speed governer to increase machine
rotation speed (motor drive) => increase of generator
frequency for islolated operation (single genset or
several gensets in parallel operation), and
Frequency decrease [E7184]: signal to external speed governer to decrease machine
rotation speed (motor drive) => decrease of generator
frequency for islolated operation (single genset or
several gensets in parallel operation).
Additionally, two further collective events are provided:
Collective event: speed increase [E7004]: this event becomes active when event(s)
[E7183] or/and event [E7123] is/are active,
and
Collective event: speed decrease [E7005]: this event becomes active when event(s)
[E7184] or/and event [E7124] is/are active,
which are individually OR-connected with both, the events of the active power controller:
Active power increase [E7123]: signal to external speed governer to increase machine
rotation speed (motor drive) => increase of output
active power of a single generator in mains parallel
operation, or several, parallel operating gensets in
isolated operation, and
Active power decrease [E7124]: signal to external speed governer to decrease machine
rotation speed (motor drive) => decrease of output
active power of a single generator in mains parallel
operation, or several, parallel operating gensets in
isolated operation,
REMARK: In view of the following statements the momentary control deviation (frequency
difference fset, act.) is given as a percentage f[%] of the nominal frequency fn set
by parameter Frequency [P603].
1.Deadband [P7184]
fset
1.Deadband [P7184]
fact(t)
t
Counter Pulse time
[P7183]
1. Pulse duration at 100% deviation
0
tf-contr., pulse time 1
t
tf-contr., pulse time 8 tf-contr., pulse time 15
0
t
tf-contr., interval time tf-contr., interval time tf-contr., interval time
0
t
Frequency increase [E7183]
0
t
Example: Parameter 1. Pulse duration at 100% deviation [P7183] = 100s (typical set
value)
P7184 1. Deadband
Deadband of the 3-point controller; when control deviation is less than the set value of
parameter 1. Deadband [P7184], then events Frequency increase [P7183] and
Frequency decrease [P7184] are deactivated (blocked).
P7188 2. Deadband
Second deadband which is used by the 3-point controller when the event assigned to
parameter 2 Settings enable [P7185] is active.
See description of parameter [P7184]
If several energy recources contribute to provide electrical energy in an isolated operated power
system, voltage control of the generator(s) individually equipped with a droop controller (static
characteristic voltage curve of generator voltage/generator reactive power) always becomes
necessary.
As opposed to parallel operation, for isolated operation of a single genset (motor drive +
generator) the droop controller can be neglected or switched off.It is the generator voltage
control which obtains a constant voltage along the whole range of consumed load. Hence, it is
not necessary to provide voltage control via SYMAP-Compact(+) .
Parallel operation differentiates between the following, different applications:
Parallel operation: genset / grid
Parallel operation of several gensets operating with droop control
Synchronisation process of local genset to another network
To avoid any voltage changes the generators of the gensets are always equipped with a speed
controller. Parallel operation of such gensets would only be possible:
if a load balancing signal is available (symmetrical reactive load sharing), or
if the genset(s) are equipped with an additional droop control (asymmetrical reactive load
sharing).
For parallel operation of gensets without load balancing signal the motor drives must be
equipped with additional droop controllers (static characteristic voltage curve with proportionality
factor or droop).
If the motor drive does neither provide a load balancing signal nor a droop controller, then droop
functionality can be established by the setpoint parameters of the SYMAP-Compact(+)
frequency controller:
1. Droop [Pxxxx],
2. Droop [Pxxxx], or
3. Droop [Pxxxx]
CAUTION: The parameters for droop control are not available yet!
By using a droop controller the genset is able to operate according to a static characteristic
voltage curve which defines the linear dependence between generator voltage UGen and output
generator reactive power Qout.
UGen
Idling voltage
Full load voltage
Qn Qout
Voltage controller
Parameter description:
P7200 Function
This parameter activates/deactivates the active frequency controller, whereby setting:
OFF: deactivates the active frequency controller, or
AUTO: activates the active frequency controller automatically as soon as events
assigned to parameters Automatic mode [P7001] and Busbar
connected [P7002] becomes active, or
ON: activates the active frequency controller automatically as soon as event
assigned to parameter Busbar connected [P7002] becomes active.
When active frequency controller is activated by parameter [P7160] event Frequency
controller active [E7160] becomes active.
Blocking of all the frequency controllers in the local net (busbar section); all frequency
controller operating with the local net can be blocked by any active event. For blocking,
the number related to this blocking event has to be assigned to parameter [P7162].
Blocking is only effective, however, as long as the blocking event is active. As soon as
blocking is active, all frequency controller operating with the same net are blocked (a
blocking command of the local generator control unit is transmitted to all the other,
relevant generator control units via CAN 1 communication), and event Frequency
controller blocked [E761] becomes active in all the generator control units. If the
blocking event becomes inactive, blocking is abandoned and all frequency controllers
are effective again. Then, event [E7161] is deactivated automatically.
If blocking of all the frequency controllers in the local net is not required, set this
parameter to 0.
CAUTION: When setting the setpoint for voltage control of the local generator the following
should be taken into account:
Isolated operation of the local genset: here, the voltage setpoint of the local
generator must not exceed rated generator voltage of the genset!
Parallel operation in isolated operation: all generator controls of the gensets
have to be supplied with the same setpoint for their voltage controllers.
When several events for activating the different setpoints are simultaneously activated, the
following table gives conclusion about the priority of the setpoint supplied to the voltage
controller:
Table 3-36 Priorities of setpoint supply to the voltage controller
Status of activation-events
Active setpoint
2.Setpoint enable 3. Setpoint enable 4. Setpoint enable (Communication)
[P7206] [P7208] [P7210]
inactive inactive inactive 1. Setpoint (default) [P7205]
inactive inactive active 4. Setpoint (Communication) [P7210]
inactive active inactive 3. Setpoint [P7209]
inactive active active 3. Setpoint [P7209]
active inactive inactive 2. Setpoint [P7207]
active inactive active 2. Setpoint [P7207]
active active inactive 2. Setpoint [P7207]
active active active 2. Setpoint [P7207]
NOTE: The setpoint for voltage controller of the local generator is to be set as a
percentage of the nominal value of the chosen characteristic quantity (phase-
to-phase voltage or phase-to-neutral voltage). However, the chosen
characteristic value refers to the nominal value of the phase-to-phase voltage
to be set by parameter:
Voltage (L-L) [P603], for primary side W1 or
Voltage (L-L) [P613], for secondary side W2
Voltage (L-L) [P623], for tertiary side W3.
The parameters Voltage (L-L) [P603], Voltage (L-L) [P613] and Voltage (L-
L) [P623] are located in submenu: SYSTEM\Nominals\Reference values.
(Pxxxx 1. Droop)
CAUTION: The parameters for droop control are not available yet!
Proportionality factor for voltage decrease in dependence of generator output reactive
power; when the local genset is in parallel operation with several gensets or with the
grid, the motor drive of the local genset needs to be provided with a load balancing
signal or a droop controller (static characteristic voltage curve). If the local genset is only
equipped with voltage controller, then the required static control function can be
established by the following voltage controller parameters of SYMAP-Compact(+):
1. Droop [Pxxxx],
2. Droop [Pxxxx], or.
3. Droop [Pxxxx]
Here, it is that winding side relating to the reactive power measurement, which
is assigned to the applied current measurement input by parameter
The parameters Power [P605], Power [P615] and Power [P625] are
located in submenu: SYSTEM\Nominals\Reference values.
Function of droop parameters could only be applied when the voltage setpoint
is supplied as an analog signal or via CAN 1 communication, and the supplied
setpoint is transmitted to the voltage controller of the generator!
P7207 2. Setpoint
See description of parameter [P7205]
(Pxxxx 2. Droop)
CAUTION: The parameters for droop control are not available yet!
See description of parameter [Pxxxx]
P7209 3. Setpoint
See description of parameter [P7208]
(Pxxxx 3. Droop)
CAUTION: The parameters for droop control are not available yet!
See description of parameter [Pxxxx]
3-point controller
The Voltage controller of SYMAP-Compact(+) is designed as a three step control including
the output states: voltage increase and voltage decrease. For this, the following two control-
events are provided:
Voltage increase [E7223]: signal to external voltage controller to increase
generator excitation current => increase of generator
voltage in isolated operation (single genset or several
gensets in parallel operation), and
Voltage decrease [E7224]: signal to external voltage controller to decrease
generator excitation current => decrease of generator
voltage in isolated operation (single genset or several
gensets in parallel operation).
Additionally, two further collective events are provided:
Collective event: voltage increase [E7006]: this event becomes active when event(s)
[E7183] or/and event [E7123] is/are active,
and
Collective event: voltage decrease [E7007]: this event becomes active when event(s)
[E7184] or/and event [E7124] is/are active,
which are individually OR-connected with both, the events of the power factor controller:
Excitation increase [E7273]: signal to external voltage controller to increase
generator excitation current => increase of output
reactive power of a single generator in mains parallel
operation, or several, parallel operating gensets in
isolated operation, and
Excitation decrease [E7274]: signal to external voltage controller to decrease
generator excitation current => decrease of output
reactive power of a single generator in mains parallel
operation, or several, parallel operating gensets in
isolated operation
REMARK: In view of the following statements the momentary control deviation (voltage
difference Uset, act.) is given as a percentage U[%] of the nominal voltage Un set
by parameter Voltage [P603], Voltage [P613], or Voltage [P623].
1.Deadband [P7224]
uset
1.Deadband [P7224]
uact(t)
t
Counter Pulse time
[P7223]
1. Pulse duration at 100% deviation
0
tU-contr., pulse time 1
t
tU-contr., pulse time 8 tU-contr., pulse time 15
0
t
tU-contr., interval time tU-contr., interval time tU-contr., interval time
0
t
Voltage increase [E7223]
0
t
Example: Parameter 1. Pulse duration at 100% deviation [P7223] = 10s (typical set
value)
P7224 1. Deadband
Deadband of the 3-point controller; when control deviation is less than the set value of
parameter 1. Deadband [P7224], then events Voltage increase [P7223] and Voltage
decrease [P7224] are deactivated (blocked).
P7228 2. Deadband
Second deadband which is used by the 3-point controller when the event assigned to
parameter 2 Settings enable [P7225] is active.
See description of parameter [P7224]
If several energy recources contribute to provide electrical energy in a power system (mains
parallel operation or parallel operation in isolated operation), the control of reactive power by
power factor control (reactive load sharing) provided by generators always becomes necessary.
As opposed to that, for isolated operation of a single genset (motor drive + generator) no
reactive load sharing is possible, and as a result, power factor control for reactive load sharing
is not necessary.
Parallel operation differentiates between the following, different applications:
Parallel operation of several gensets (isolated operation)
Parallel operation: genset / grid
Different kinds of parallel operation require different ways for reactive load sharing
(symmetrical/asymmetrical) to the applied energy recources. Hence, different methods for
power factor control of the generator(s) are required.
Parallel operation of several gensets in isolated operation (symmetrical reactive load sharing)
For an uncontrolled genset, the load variation within an isolated operated network leads to the
following:
In case that inductive, reactive power increases, the generator output reactive power
increases and generator voltage decreases, or
in case that inductive, reactive power decreases, the generator output reactive power
decreases and generator voltage increases.
To avoid any voltage changes the generators of the gensets are always equipped with a voltage
controller. Parallel operation of such gensets would only be possible:
if a load balancing signal between the voltage controllers is available (symmetrical reactive
load sharing), or
if the genset(s) are equipped with an additional voltage droop control (asymmetrical
reactive load sharing).
For parallel operation of gensets without load balancing signal the generators must be equipped
with additional droop controllers.
If the generator does neither provide a load balancing signal nor a droop controller, then droop
functionality can be established by the setpoint parameters of the SYMAP-Compact(+) voltage
controller (see chapter 3.12.1.5 Voltage Controller):
1. Droop [Pxxxx],
2. Droop [Pxxxx], or
3. Droop [Pxxxx]
CAUTION: The parameters for droop control are not available yet!
By using a droop controller the genset is able to operate according to a static characteristic
voltage curve which defines the linear dependence between generator voltage UGen and
generator output reactive power Qout.
UGen
Idling voltage
Full load voltage
Qn Qout
Parameter description:
P7250 Function
This parameter activates/deactivates the power factor controller, whereby setting:
OFF: deactivates the power factor controller, or
AUTO: activates the power factor controller automatically as soon as events
assigned to parameters Automatic mode [P7001] and Busbar
connected [P7002] becomes active, or
ON: activates the power factor controller automatically as soon as event
assigned to parameter Busbar connected [P7002] becomes active.
When power factor controller is activated by parameter [P7250] event Power factor
controller active [E7250] becomes active.
NOTE: The minimum limit of measured process quantity phase current to release
activation of the local power factor controller is to be set as a percentage of
the nominal value of the process quantity. The nominal value of the process
quantity is to be set by parameter:
Current [P604], for primary side W1,
Current [P614], for secondary side W2 or
Current [P624], for tertiary side W3.
The parameters Current [P604], Current [P614] and Current [P624] are
located in submenu: SYSTEM\Nominals\Reference values.
CAUTION: When setting the setpoint for power factor control of the local generator the
following should be taken into account:
Mains parallel operation: here, the setpoint for the feed-in reactive power of
the local generator must not exceed rated power at the network connection
point!
Parallel operation in isolated operation (asymmetrical load sharing): the feed-
in reactive power of the local generator must not exceed the consumed
reactive load; otherwise busbar voltage would increase!
When several events for activating the different setpoints are simultaneously activated, the
following table gives conclusion about the priority of the setpoint supplied to the power factor
controller:
Table 3-37 Priorities of setpoint supply to the power factor controller
Status of activation-events
Active setpoint
2.Setpoint enable 3. Setpoint enable 4. Setpoint enable (Communication)
[P7256] [P7258] [P7260]
inactive inactive inactive 1. Setpoint (default) [P7255]
inactive inactive active 4. Setpoint (Communication) [P7260]
inactive active inactive 3. Setpoint [P7259]
inactive active active 3. Setpoint [P7259]
active inactive inactive 2. Setpoint [P7257]
active inactive active 2. Setpoint [P7257]
active active inactive 2. Setpoint [P7257]
active active active 2. Setpoint [P7257]
-0.98 P 0.98
0.98 100% 0.98 Representation of
-0.9 0.9 power factor in
0.9 0.9 SYMAP-Compact(+)
-0.8 0.8
0.8 0.8
real power factor
50%
Operating range
Generator Generator
lagging leading
0% Q
-100% Generator -50% 0% 50% Generator 100%
consumes output
reactive power reactive power
Figure 3-332 Power diagram: Esample for permissable operating range of a generator
NOTE: The setpoint settings are to be set as a percentage of the nominal value of the
chosen characteristic quantity generator power (rated value of the generator
[kW]). This nominal value is to be set by parameter:
Power [P605], for primary side W1 or
Power [P615], for secondary side W2 or
Power [P625], for tertiary side W3.
Here, it is that winding side relating to the active power measurement, which is
assigned to the applied current measurement input by parameter
The parameters Power [P605], Power [P615] and Power [P625] are
located in submenu: SYSTEM\Nominals\Reference values.
P7257 2. Setpoint
Second setpoint for the event-controlled changeover of the power factor controller; when
event-controlled function asymmetrical reactive load sharing (see Parameter Balanced
mode [P7253] is deactivated and event-controlled changeover of the power factor
controller to the second setpoint (see parameter 2.Setpoint enable [P7256]) is active,
the power factor controller operates according to the setpoint set by parameter [P7257]
P7259 3. Setpoint
See description of parameter [P7257]
3-point controller
The Power factor controller of SYMAP-Compact(+) is designed as a three step control
including the output states: excitation increase and excitation decrease. For this, the following
two control-events are provided:
Excitation increase [E7273]: signal to external voltage controller to increase
generator excitation current => increase of output
reactive power of a single generator in mains parallel
operation, or several, parallel operating gensets in
isolated operation, and
Excitation decrease [E7274]: signal to external voltage controller to decrease
generator excitation current => decrease of output
reactive power of a single generator in mains parallel
operation, or several, parallel operating gensets in
isolated operation
Additionally, two further collective events are provided:
Collective event: voltage increase [E7006]: this event becomes active when event(s)
[E7183] or/and event [E7123] is/are active,
and
Collective event: voltage decrease [E7007]: this event becomes active when event(s)
[E7184] or/and event [E7124] is/are active,
which are individually OR-connected with both, the events of the voltage controller:
Voltage increase [E7223]: signal to external voltage controller to increase
generator excitation current => increase of generator
voltage in isolated operation (single genset or several
gensets in parallel operation), and
Voltage decrease [E7224]: signal to external voltage controller to decrease
generator excitation current => decrease of generator
voltage in isolated operation (single genset or several
gensets in parallel operation).
Depending on the type of motor speed governer the control events have to be assigned to:two
different binary outputs of the SYMAP-Compact(+) (binary control, e.g. for naval applications)
REMARK: In view of the following statements the momentary control deviation is given as
power factor difference PFset, act..
Depending on the activation of function Symmetrical reactive load sharing (see parameter
Balanced mode [P7253], power factor control is according to either a dynamic setpoint
(symmetrical reactive load sharing) or a static setpoint (asymmetrical reactive load sharing).
l2 l4 l7 l9 l11 l13 l14 l16 l18 l20 l23
l1 l3 l5 l6 l8 l10 l12 l13 l15 l17 l19 l22
l PF
0 1
1.Deadband [P7274]
lset 1.Deadband [P7274]
1 0
t
lact(t)
0 -1
0
tPF-contr., pulse time 1
t
tPF-contr., pulse time 8 tPF-contr., pulse time 15
Counter Interval
time
[P7272] 1. Interval time
0
t
tPF-contr, interval time tPF-contr, interval time tPF-contr, interval time
0
t
Excitation increase [E7273]
0
t
Figure 3-333 Power factor control dynamic setpoint supply (symmetrical reactive load sharing)
1.Deadband [P7274]
lset
1.Deadband [P7274]
1 0
t
lact(t)
0 -1
0
tPF-contr., pulse time 1
t
tPF-contr., pulse time 8 tPF-contr., pulse time 15
0
t
tPF-contr., interval time tPF-contr., interval time tPF-contr., interval time
0
t
Excitation increase [E7273]
0
t
Figure 3-334 Power factor control static setpoint supply (asymmetrical reactive load sharing)
Example: Parameter 1. Pulse duration at 100% deviation [P7273] = 10s (typical set
value)
P7274 1. Deadband
Deadband of the 3-point controller; when control deviation is less than the set value of
parameter 1. Deadband [P7274], then events Excitation increase [P7273] and
Excitation decrease [P7274] are deactivated (blocked).
P7276 2. Intervallzeit
Second interval time which is used by the 3-point controller when the event assigned to
parameter 2 Settings enable [P7275] is active.
See description of parameter [P7272]
P7278 2. Totzone
Second deadband which is used by the 3-point controller when the event assigned to
parameter 2 Settings enable [P7275] is active.
See description of parameter [P7274]
0,9
lagging
1
P/PE,max
leading
0,9
0,2 0,5 1
Figure 3-335 Power factor curve PF(P) for power generation systems in parallel operation with the low-
voltage power system acc. to VDE-AR-N-4105
PF
0,95
lagging
-1
1 P/PE,max
leading
0,95
Figure 3-336 Power factor curve PF(P) for power generation systems in parallel operation with the
medium-voltage power system acc. to BDEW
Activation is only effective, however, as long as the assigned event is active. As soon as
power factor curve is active, event Power factor curve active [E7290] becomes active.
If the assigned event becomes inactive, activation of power factor curve is abandoned.
Then, event [E7290] is deactivated automatically.
If Event-controlled activation of power factor curve (dynamic PF setpoint setting) for
power factor control is not required, set this parameter to 0.
which is set via parameter 4.Active power point [P7297], parameter [P7298] defines the
final point of the third straight of power factor curve.
The devices of SYMAP-Compact product line were designed numerically. All functions base on
tested hardware and software.
Maintenance
All devices of SYMAP-Compact product line are maintenance-free. However, there are some
certain, life-limited components, which cause replacement according to the given replacement
cycles listed in the table below. Following components are to be considered:
Hardware version v1-1.x:
1 x rechargeable battery, Type ML2430; for storage of data in the RAM memory and for
maintenance of counting date and time. The buffering time of a fully charged battery (stand-
by operation) is about 50 days. Manufacturers warranted life time of the accumulator type
is about 10 years.
Hardware version v1-2.x:
2 x rechargeable battery, Type ML2430; for storage of data in the RAM memory and for
maintenance of counting date and time. The buffering time of a fully charged battery (stand-
by operation) is about 100 days. Manufacturers warranted life time of the accumulator type
is about 10 years.
NOTE: To avoid any loss of data, batteries shall be replaced one after another!
In addition to the first cyclic voltage monitoring, another cyclic monitoring of the battery voltage
starts right after 40 hours of device operation. Here, cycle time is 1s and monitored voltage level
is 2.9V. When voltage drops below 2.9V, then event MU Battery low alarm [E9046] is
activated.
CAUTION: In such a case batteries are faulty and have to be replaced. If event [E9046] is still
activated after battery replacement, then SYMAP-Compact(+) device has to be
replaced by another one!
Servicing
All devices of the product line SYMAP-Compact provide extensive self supervision functions
for signalling different internal faults. Replacement of the life-limited components (see table
above) may be undertaken only under ESD-conform conditions at the device manufacturers
facility.
Retesting
A repeating secondary test is mainly to check the function of the hardware including the wiring
on a regular basis. Moreover, any non-documented changes of parameter settings can be
detected.
Retesting intervalls are to be allocated by the user. All repeated tests for functionality checks as
simplified functionality tests and secondary protection tests as complete check of the protection
system fall in the scope of the regulation, which apply to valid standards for the plant area
requiring the use of SYMAP-Compact(+) devices.
5 Safety guidelines
CAUTION: Please take note of the following safety guidelines for the procedures listed
below!
Table 5-1 SYMAP-Compact(+) Safety guidelines
Procedure Safety guidelines Link
CAUTION:
If a parameter file is directly loaded in the SYMAP-
Compact(+), the device proceeds to new start of the system See document
Load parameter file
(system reboot). Booting time takes ca 4 s. During the booting SCPT manual vx.x.docx
time SYMAP-Compact(+) does not provide any protective
function!
CAUTION:
While being in booting mode SYMAP-Compact(+) does not See document
Firmware-Update
provide any device functionality in particular no protective SCPT manual vx.x.docx
function!
6 Trouble-shooting
Find some of the devices error messages or messages occurring during application of the
configuration software SYMAP-Compact Parameter Tool (SCPT) listed in the following.
Beyond that, details on the messages are given and measures for clearance suggested.
SYMAP-Compact(+):
7 Technical Data
Table 7-1 HW v1-1.x: General Technical data of the SYMAP-Compact(+) device variants
Description Specification
Table 7-2 HW v1-2.x: General Technical data of the SYMAP-Compact(+) device variants
Description Specification
Description Specification
Description Specification
Description Specification
Description Specification
Description Specification
7.2.1 Environment
Temperature/Humidity
Earthquake test
Shock test
Cold test-operational
Acceleration: 50m/s2
Duration of the pulse: 11ms
18: 3 shocks in two directions
Number of shocks:
of the three axis: x,y,z
Seismic test (seismic parameters: class 2)
Orientation: x-, y-, z-axis DIN EN 60255-21-3: 1993
Frequency range: 5 35Hz
5 9Hz:Amplitude = 3,5mm
Z-axis frequency:
(7mm, peak-to-peak)
9 35Hz: Acceleration
Z-axis frequency:
amplitude = 10m/s2
5 9Hz:Amplitude = 7,5mm
x- and y-axis frequency:
(15mm, peak-to-peak)
9 35Hz: Acceleration
x- and y-axis frequency:
amplitude = 20m/s2
Sweep rate: 1 oct/min
Duration of the test: 1 cycle per axis
Insulation
Auxiliary
Dielectric test voltage power
NOTE: Test was conducted without supply, BIs, 2.8kV DC
installed overvoltage protection BOs, CTs,
Safety related (MOVs) for power supply input VTs
ELV circuits 700V DC EN 60255-27
Auxiliary
Impulse test voltage power
NOTE: Test was conducted without supply, BIs, 5kV; 1.2/50s
installed overvoltage protection BOs, CTs,
(MOVs) for power supply input VTs
ELV circuits 1kV; 1.2/50s
Conducted emission
Limit CLASS A
Frequency (dBuV)
(MHz) Quasi- Average EN 60255-25:2000
peak
Auxiliary power supply port EN 55022: 2010
0.15 0.5 79 66 EN 61000-6-4: 2007
0.5 5.0 73 60
5.0 30.0 73 60
Radiated emission
80 2700MHz
Frequency sweep
80 1000MHz (keying test)
10 / 20V/m
Field strength
20V/m (keying test)
1kHz sine wave, 80%, AM
Modulation
modulation
Frequency step 1% of fundamental
Dwell time / 2s
ON / OFF period 2s / 2s
Polarity of antenna Horizontal and vertical
3m for the test level 10V/m EN 60255-22-3: 2008
Test distance
1.8m for the test level 20V/m IEEE C37.90.2-2004
80, 160, 450, 900, 1850, 1890, EN 61000-4-3: 2006 + A1:
Tested spot frequencies (MHz)
2150 2008
5kHz and
Repetition
100kHz
frequency
Auxiliary power supply 2.5kHz
functional earth 15ms at 2.5kHz
and 5kHz, EN 60255-22-4: 2008
binary inputs Burst duration
0,75ms at EN 60255-4-4: 2004
binary outputs
100kHz IEEE C37.90.1-2002
CTs
VTs 60s at each
Test duration
polarity
Common mode 4kV
Differential
150Vrms EN 60255-22-7: 2003
Binary inputs mode
EN 61000-4-16: 1998
Common mode 300Vrms
Performance
Specification
level
Voltage dips (110V DC power
0% (50ms) A
supply) EN 60255-11: 2010
40% (200ms) C
EN 61000-4-11: 2004
70% (500ms) C
EN 61000-4-17: 1997
0% (25 cycles) A EN 61000-4-29: 2000
Voltage dips (230V AC power 40% (10/12
supply) cycles at C
50/60Hz)
50G
up to 3In +/-0.5 %
Instantaneous 0.1 % 0 s to 999999.999 s
up to 20In +/-1.0 %
groundovercurrent
up to 3In 0 s to 999999.999 s
51 +/-0.5 %
up to 30In 0.1 % (DEFT) or
Time overcurrent +/-1.0 %
see IDMT curve
0 s to 999999.999 s
51G up to 3In +/-0.5 %
0.1 % (DEFT) or
Time groundovercurrent up to 20In +/-1.0 %
see IDMT curve
ANSI 21FL
PT1,PT2,PT3: 100V*
*: fn = 50Hz
ANSI 27
Magnitude (minimum start voltage Umin; => UL-L) see test ANSI 59 and ANSI27 see test ANSI 59 and ANSI27
Magnitude (minimum start frequency fmin) See test ANSI 81O and ANSI 81U See test ANSI 81O and ANSI 81U
*: fn = 50Hz
**: Un = 100V, 400V
ANSI 27Q
Magnitude (frequency) see test ANSI 81 O/U see test ANSI 81 O/U
Magnitude (positive sequence reactive power Q1) at Q1set: 1% 75% Qn* 1% Qn*
for 1 (sin ) 0.766 at Q1set: 75% 100% Qn* 1.5% Qn*
at Q1set: 1% 40% Qn* 1% Qn*
Magnitude (positive sequence reactive power Q1)
at Q1set: 40% 50% Qn* 1.5% Qn*
for 0.766 (sin ) 0.5
at Q1set: 50% 100% Qn* 5% Qn*
Trip time: Definite time (DT) at tset: 0s 10s 35ms or 5% of tset
Reset time: Definite time (DT) at tset: 0s 10s 20ms or 5% of tset
CT1: 5A***, PT1: 100V***/400V***
Operate quantity Set range Deviation
Magnitude (frequency) see test ANSI 81 O/U see test ANSI 81 O/U
Magnitude (positive sequence reactive power Q1) at Q1set: 1% 50% Qn** 1% Qn**
for 1 (sin ) 0.766 at Q1set: 50% 100% Qn** 1.5% Qn**
Magnitude (positive sequence reactive power Q1) at Q1set: 1% 50% Qn** 1% Qn**
for 0.766 (sin ) 0.5 at Q1set: 50% 100% Qn** 5% Qn**
Trip time: Definite time (DT) See test CT1: 1A See test CT1: 1A
Reset time: Definite time (DT) See test CT1: 1A See test CT1: 1A
Functional test Activation criterion Test result
Reclosing Frequency and voltage recovering passed
Deactivation of Reclosing Parameter [P1616] passed
*: Qn = 173 [var] at 100V and Sn, Pn, Qn = 693 [var] at 400V
**: Qn = 866 [var] at 100V and Sn, Pn, Qn = 3464 [var] at 400V
*: In = 1A; **: In = 5A; ***: fn = 50Hz
ANSI 27T
ANSI 32
ANSI 32N/G
CT1,CT2: 1A
Magnitude (phase currents: IL1, IL2, IL3) at Iset: 1% 100% In* 1%In*
Magnitude (phase currents: IL1, IL2, IL3) at Iset: 1% 100% In** 1%In**
Trip time: Definite time (DT) See test CT1,CT2: 1A See test CT1,CT2: 1A
Reset time: Definite time (DT) See test CT1,CT2: 1A See test CT1,CT2: 1A
*: In = 1A
**: In = 5A
ANSI 46
Reset time: IDMT curve (Thermal) IDMT curve (Thermal) 45ms or 5% of tcalc
Functional test Activation criterion Test result
I2/In; passed
Supervision mode
I2/I1 passed
Voltage restrained Voltage dependend current limit passed
Dynamic parameters Activation-event passed
CT1: 5A
Operate quantity Set range Deviation
at Iset: 1% 100% In** 0.5% In**
Magnitude (negative phase sequence current: I2/In; I2/I1)
at Iset: 200% 600% In** 1% Iset
Trip time: IDMT IDMT curve (IEC, ANSI) 45ms or 5% of tcalc
Reset time: IDMT IDMT curve (IEC, ANSI) 45ms or 5% of tcalc
Trip time: IDMT curve (Thermal) IDMT curve (Thermal) 55ms or 5% of tcalc
Reset time: IDMT curve (Thermal) IDMT curve (Thermal) 45ms or 5% of tcalc
Functional test Activation criterion Test result
I2/In; passed
Supervision mode
I2/I1 passed
*: In = 1A
**: In = 5A
***: fn = 50Hz
PT1,PT2,PT3: 100V*
Magnitude (negative phase sequence voltage U2) at Uset: 2% 200% Un** 1,2% Un**
Magnitude (negative phase sequence voltage U2) at Uset: 2% 100% Un*** 1% Un***
*: fn = 50Hz
**: Un = 100V
***: Un = 400V
ANSI 49
CT1: 1A
Operate quantity Set range Deviation
Trip time calculation accuracy t(Ieq) *** (Ieq: 120% IB 500% IB) at IB: 10%In* 100% In*; t: 10s 3000s 5% Icalc or 1s
Trip time delay: Warning limit at tset: 0s 60s 10ms
Trip time delay: Trip limit at tset: 0s 60s 10ms
Functional test Activation criterion Test result
Warning limit at (t): 50% 100% passed
Trip limit at (t): 50% 100% passed
ANSI 50BF
CT1: 1A
Operate quantity Set range Deviation
Magnitude (phase currents: IL1, IL2, IL3) see test ANSI 67* see test ANSI 67*
Instantaneous operation 25ms
Trip time: Definite time (DT)
at tset: 0.1s 60s 25ms or 5% of tset
Instantaneous operation 35ms
Reset time: Definite time (DT)
at tset: 0.3s 30s 35ms or 5% of tset
*: In = 1A
NOTE: CT1 = 5A: see test ANSI 67!
ANSI 51/46VR
ANSI 50/51
ANSI 50/51G
CT-GND1: 1A
Operate quantity Set range Deviation
Magnitude (ground current IG) see test ANSI 67G* see test ANSI 67G*
Instantaneous operation 35ms
Trip time: Definite time (DT)
at tset: 0.1s 60s 35ms or 5% of tset
Instantaneous operation 35ms
Reset time: Definite time (DT)
at tset: 0.3s 30s 35ms or 5% of tset
Trip time: IDMT IDMT curve (IEC, ANSI) see test ANSI 67G
Reset time: IDMT IDMT curve (IEC, ANSI) see test ANSI 67G
Functional test Activation criterion Test result
Voltage restrained Voltage dependend current limit passed
Dynamic parameters Activation-event passed
*: In = 1A
NOTE: CT-GND1 = 5A and CT-GND1 = 2 3000mA: see test ANSI 67G!
CT1: 1A
Magnitude (phase currents: IL1, IL2, IL3) see test ANSI 37 see test ANSI 37
CT1: 5A
Magnitude (phase currents: IL1, IL2, IL3) see test ANSI 37 see test ANSI 37
ANSI 59N/G
PT-GND1: 100V*
Operate quantity Set range Deviation
Magnitude (residiual voltage UG) at Uset: 1% 100% Un** 0.5% Uset
Trip time: Definite time (DT) at tset: 0s 60s 35ms or 5% of tset
Reset time: Definite time (DT) at tset: 0s 60s 35ms or 5% of tset
PT1, PT2, PT3: 100V*
Operate quantity Set range Deviation
at Uset: 1% 70% Un** 0.5% Uset
Magnitude (voltages UL-N => calculated residiual voltage UG)
at Uset: 70% 100% Un** 1% Uset
PT1, PT2, PT3: 400V*
Operate quantity Set range Deviation
at Uset: 1% 70% Un*** 0.5% Uset
Magnitude (voltages UL-N => calculated residiual voltage UG)
at Uset: 70% 100% Un*** 1% Uset
*: fn = 50Hz
**: Un = 100V
***: Un = 400V
ANSI 64REF
Trip time: Step 1 see test: CT1: 1A; CT-GND1: 1A see test: CT1: 1A; CT-GND1: 1A
Trip time: Step 2 see test: CT1: 1A; CT-GND1: 1A see test: CT1: 1A; CT-GND1: 1A
CT1: 1A; CT-GND1: 2mA-3000mA
Trip time: Step 1 see test: CT1: 1A; CT-GND1: 1A see test: CT1: 1A; CT-GND1: 1A
Trip time: Step 2 see test: CT1: 1A; CT-GND1: 1A see test: CT1: 1A; CT-GND1: 1A
Functional test Activation criterion Test result
ID>> / Passed
Hysteresis / Passed
*: In = 1A
**: In = 5A
ANSI 67
Protection core:
at Iset: 12% 100% In*** 0.5% In***
Magnitude (phase currents: IL1, IL2, IL3) at Iset: 100% 600% In*** 1% Iset
Measuring core:
at Iset: 1% 200% In*** 0,5% In***
Protection core:
at Iset: 12% 16% In*** 6
at Iset: 16% 22% In*** 2.5
at Iset: 22% 30% In*** 2
at Iset: 30% 75% In*** 1.5
Angle (between phase current and reference voltage Uref) at Iset: 75% 400% In*** 1
Measuring core:
at Iset: 2% 4% In*** 7
at Iset: 4% 6% In*** 3
at Iset: 6% 16% In*** 2.5
at Iset: 16% 200% In*** 1
Trip time (non-directional): IDMT IDMT curve (IEC, ANSI) 35ms or 5% of tset
Reset time (non-directional): IDMT IDMT curve (IEC, ANSI) 35ms or 5% of tset
Trip time (directional): IDMT IDMT curve (IEC, ANSI) 65ms or 5% of tset
Reset time (directional): IDMT IDMT curve (IEC, ANSI) 70ms or 5% of tset
*: fn = 50Hz; **: In = 1A; ***: In = 5A
ANSI 67G
ANSI 74TC
Binary inputs: Fct. 26, Fct. 27; Binary output: Shunt trip 1
ANSI 78
Reset delay time trip (test only for PT1: 100V) at tset: 0.25s 60s 5ms or 5% of tset
Minimum start voltage delay time (test only for PT1: 100V) at tset: 0.5s 60s 20ms or 5% of tset
Current increase time (test only for PT1: 100V) at tset: 0.05s 60s 5ms or 5% of tset
PT2: 100V/400V (tested at nominal voltage and nominal frequency)
Operate quantity Set range Deviation
at set: 1 20 0.5
Magnitude (voltage angle difference )
at set: 20 25 1
PT3: 100V/400V (tested at nominal voltage and nominal frequency)
Operate quantity Set range Deviation
at set: 1 6 0.5
Magnitude (voltage angle difference ) at set: 6 15 1
at set: 15 25 2
Functional test Activation criterion Test result
Magnitude (minimum start voltage voltages UL-L) see test ANSI 27 and ANSI 59 see test ANSI 27 and ANSI 59
OR passed
Pickup mode
AND passed
*: fn = 50Hz
ANSI 79
Table 7-38 ANSI 81R Rate of change of frequency (ROCOF) protection (standard device)
ANSI 81R
Min. start voltage( UL-L) see test ANSI 27 and ANSI 59 see test ANSI 27 and ANSI 59
df/dt passed
f> & df/dt passed
Mode f< & df/dt passed
f> & DF/DT passed
f< & DF/DT passed
none passed
Direction positive passed
negative passed
f> & f< limits see test ANSI 81O and ANSI 81U see test ANSI 81O and ANSI 81U
DF DF Limit passed
DT DT Limit passed
Table 7-39 ANSI 81R Rate of change of frequency (ROCOF) protection (G59)
ANSI 81R
Min. start voltage( UL-L) see test ANSI 27 and ANSI 59 see test ANSI 27 and ANSI 59
df/dt passed
f> & df/dt passed
Mode f< & df/dt passed
f> & DF/DT passed
f< & DF/DT passed
none passed
Direction positive passed
negative passed
f> & f< limits see test ANSI 81O and ANSI 81U see test ANSI 81O and ANSI 81U
DF DF Limit passed
DT DT Limit passed
ANSI 86
ANSI 95i
CT1: 1A
Operate quantity Test range (phase current) Set range (IH/IFH) Deviation
at I2H,set: 1% 15% IFH* 0.5% IFH*
2nd (2H) harmonic (phase currents: IL1, IL2, IL3) at IFH,test: 300% 1000% In** at I2H,set: 15% 50% IFH* 1% IFH*
at I5H,set: 1% 15% IFH* 0.5% IFH*
5th (5H) harmonic (phase currents: IL1, IL2, IL3) at IFH,test: 300% 1000% In** at I5H,set: 15% 50% IFH* 1% IFH*
CT-GND1: 1A
Operate quantity Test range (ground current) Set range (IH/IFH) Deviation
nd
2 (2H) harmonic (ground current IG) at IFH,test: 300% 1000% In** at I2H,set: 1% 50% IFH* 0.5% IFH*
th
5 (5H) harmonic (ground current IG) at IFH,test: 300% 1000% In** at I5H,set: 1% 50% IFH* 1% IFH*
CT1: 5A
Operate quantity Test range (phase current) Set range (IH/IFH) Deviation
at I2H,set: 1% 15% IFH* 0.5% IFH*
2nd (2H) harmonic (phase currents: IL1, IL2, IL3) at IFH,test: 100% 260% In*** at I5H,set: 15% 50% IFH* 1% IFH*
at I2H,set: 1% 15% IFH* 1% IFH*
5th (5H) harmonic (phase currents: IL1, IL2, IL3) at IFH,test: 100% 260% In*** at I5H,set: 15% 50% IFH* 1% IFH*
CT-GND1: 5A
Operate quantity Test range (ground current) Set range (IH/IFH) Deviation
at I2H,set: 1% 15% IFH* 0.5% IFH*
2nd (2H) harmonic (ground current IG) at IFH,test: 100% 260% In*** at I5H,set: 15% 50% IFH* 1% IFH*
at I2H,set: 1% 15% IFH* 1% IFH*
5th (5H) harmonic (ground current IG) at IFH,test: 100% 260% In*** at I5H,set: 15% 50% IFH* 1% IFH*
CT-GND1: 2 3000mA (sensitive input)
Operate quantity Test range (ground current) Set range (IH/IFH) Deviation
at I2H,set: 1% 3% IFH* 3.5% IFH*
2nd (2H) harmonic (ground current IG) at IFH,test: 50% 200% In** at I2H,set: 3% 15% IFH* 2% IFH*
at I2H,set: 15% 50% IFH* 1% IFH*
at I5H,set: 1% 3% IFH* 7% IFH*
at IFH,test: 50% 100% In** at I5H,set: 3% 15% IFH* 6% IFH*
5th (5H) harmonic (ground current IG) at I5H,set: 15% 50% IFH* 1% IFH*
at IFH,test: 100% 200% In** at I5H,set: 1% 50% IFH* 1% IFH*
*: portion of current at Fundamental Harmonic (50Hz)
**: In = 1A;
***: In = 5A;
CT1: 1A
Operate quantity Set range Deviation
Magnitude (phase currents: IL1, IL2, IL3) see test ANSI 67 see test ANSI 67
Trip time: Definite time (DT) at tset: 0s 10s 35ms or 5% of tset
Reset time: Definite time (DT) at tset: 0s 10s 25ms or 5% of tset
Functional test Activation criterion Test result
I< passed
Event passed
Supervision modes
I< OR Event passed
CTS
Magnitude (phase currents: IL1, IL2, IL3) see test ANSI 67 see test ANSI 67
Magnitude (ground current IG) see test ANSI 67G see test ANSI 67G
Symmetry check:
at tset: 0s 60s 35ms or 5% of tset
Delay time: Definite time (DT)
Diff check:
at tset: 0s 60s 30ms or 5% of tset
Functional test Activation criterion Test result
Symmetry check passed
Min. start current passed
Supervision mode Diff check passed
Diff. current limit passed
Correction factor passed
*: fn = 50Hz
**: Un = 110VDC
***: Un = 440VDC
PTS
Magnitude (voltages UL-L, UL-N) see test ANSI 27, ANSI 59 see test ANSI 27, ANSI 59
Magnitude (ground voltage UG) see test ANSI 59N/G see test ANSI 59N/G
Magnitude (phase currents: IL1, IL2, IL3) see test ANSI 67 see test ANSI 67
Symmetry check:
at tset: 0s 60s 20ms or 5% of tset
Fuse Fail check:
Delay time: Definite time (DT)
at tset: 0s 60s 20ms or 5% of tset
General check:
at tset: 0s 60s 35ms or 5% of tset
Functional test Activation criterion Test result
Symmetry check passed
Min. start voltage passed
Symmetry quotient passed
Fuse failure check passed
Asymmetric fuse failure passed
Supervision mode 3-Phase fuse failure passed
Voltage difference passed
General check passed
CB closed Feedback passed
Voltage limit passed
Min/Max current limit passed
*: fn = 50Hz
SOTF
CT1: 1A
Operate quantity Set range Deviation
Magnitude (phase currents: IL1, IL2, IL3) see test ANSI 67 see ANSI 67
Instantaneous operation 35ms
Trip time: Definite time (DT)
at tset: 0.1s 60s 35ms or 5% of tset
Instantaneous operation 75ms
Reset time: Definite time (DT)
at tset: 0.3s 30s 60ms or 5% of tset
Functional test Activation criterion Test result
Trigger pulse Set trigger pulse duration passed
NOTE: For CT1 = 5A: see test ANSI 67!
TIG
YG
Magnitude (minimum start voltage UG) see test ANSI 59N/G see test ANSI 27 and ANSI 59
Magnitude (minimum start current IG) see test ANSI 50/51G see test ANSI 50/51G
*: fn = 50Hz
**: Yn; Gn; Bn: nominal values accord to primary set values of CT-GND1 and PT-GND1
*: fn = 50Hz
NOTE: Other protection and monitoring functions have not been type-tested yet!
Description Specification
1
Short circuit and wire break only for DC!
Table 7-51 HW v1-2.x: Specifications of binary inputs (BI) of the SYMAP-Compact(+) device
variants
Description Specification
Description Specification
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 45 V
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 12 ms
Max. turn-on delay
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 50 ms
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 12 ms
Max. turn-off delay
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 25 ms
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 695 mW
Power consumption
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 352 mW
220V DC
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 3,16 mA
Current
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 1,6 mA
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 157 V
HIGH level
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 183 V
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 76 V
LOW level
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 90 V
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 120 ms
Max. turn-on delay
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 40 ms
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 100 ms
Max. turn-off delay
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 20 ms
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 95,7 mW
Power consumption
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 49,5 mW
110V AC
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 0,87 mA
Current
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 0,45 mA
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 60 V
HIGH level
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 77 V
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 53 V
LOW level
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 55 V
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 200 ms
Max. turn-on delay
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 30 ms
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 60 ms
Max. turn-off delay
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 30 ms
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 420 mW
Power consumption
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 215 mW
230V AC
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 1,83 mA
Current
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 0,93 mA
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 180 V
HIGH level
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 170 V
BIs Fct.10 to Fct 25: X2.3:34 to 45 and X2.5:66 to 70 90 V
LOW level
BIs Fct.26 and Fct 27: X2.3:30 to X2.3:33 115 V
Description Specification
Number 3 ninary inputs (BIs); rooted COM
General 24/48/60/220V DC, 110V AC/DC, 230V AC (parameterizable)
Voltages
NOTE: max. permissible voltage for all BIs = 270V AC/DC
Max. turn-on delay 10ms
Max. turn-off delay 10ms
Power consumption 1,2mW
24V DC BIs Fct.1 to Fct 3: X2:1 to 4
Current 50A
HIGH level parameterizable
HIGH level parameterizable
Max. Einschaltverzgerung 10ms
Max. Ausschaltverzgerung 10ms
Leistungsaufnahme 4,8mW
48V DC BIs Fct.1 to Fct 3: X2:1 to 4
Strom 100A
HIGH-Pegel parameterizable
LOW-Pegel parameterizable
Max. Einschaltverzgerung 10ms
Max. Ausschaltverzgerung 11ms
Leistungsaufnahme 7,5mW
60V DC BIs Fct.1 to Fct 3: X2:1 to 4
Strom 125A
HIGH-Pegel parameterizable
LOW-Pegel parameterizable
Max. turn-on delay 11ms
Max. turn-off delay 11ms
Power consumption 25,3mW
110V DC BIs Fct.1 to Fct 3: X2:1 to 4
Current 230A
HIGH level parameterizable
HIGH level parameterizable
Max. turn-on delay 10ms
Max. turn-off delay 10ms
Power consumption 101,2mW
220V DC BIs Fct.1 to Fct 3: X2:1 to 4
Current 460A
HIGH level parameterizable
HIGH level parameterizable
Max. turn-on delay 25ms
Max. turn-off delay 29ms
Power consumption 27,94mW
110V AC BIs Fct.1 to Fct 3: X2:1 to 4
Current 254A
HIGH level parameterizable
HIGH level parameterizable
Max. turn-on delay 24ms
Max. turn-off delay 28ms
Power consumption 122,13mW
230V AC BIs Fct.1 to Fct 3: X2:1 to 4
Current 531A
HIGH level parameterizable
HIGH level parameterizable
Description Specification
Number 8 binary inputs (BIs); 2 groups by 4 BIs each, rooted COM
General 24/48/60/220V DC, 110V AC/DC, 230V AC (parameterizable)
Voltages
NOTE: max. permissible voltage for all BIs = 270V AC/DC
Max. turn-on delay 10ms
Max. turn-off delay 10ms
Power consumption BIs Fct.1 to Fct 4: X1:1 to 6 and 1,2mW
24V DC
Current BIs Fct.5 to Fct 8: X1:7 to 12 50A
HIGH level parameterizable
HIGH level parameterizable
Max. turn-on delay 10ms
Max. turn-off delay 10ms
Power consumption BIs Fct.1 to Fct 4: X1:1 to 6 and 4,8mW
48V DC
Current BIs Fct.5 to Fct 8: X1:7 to 12 100A
HIGH level parameterizable
HIGH level parameterizable
Max. turn-on delay 10ms
Max. turn-off delay 11ms
Power consumption BIs Fct.1 to Fct 4: X1:1 to 6 and 7,5mW
60V DC
Current BIs Fct.5 to Fct 8: X1:7 to 12 125A
HIGH level parameterizable
HIGH level parameterizable
Max. turn-on delay 11ms
Max. turn-off delay 11ms
Power consumption BIs Fct.1 to Fct 4: X1:1 to 6 and 25,3mW
110V DC
Current BIs Fct.5 to Fct 8: X1:7 to 12 230A
HIGH level parameterizable
HIGH level parameterizable
Max. turn-on delay 10ms
Max. turn-off delay 10ms
Power consumption BIs Fct.1 to Fct 4: X1:1 to 6 and 101,2mW
220V DC
Current BIs Fct.5 to Fct 8: X1:7 to 12 460A
HIGH level parameterizable
HIGH level parameterizable
Max. turn-on delay 25ms
Max. turn-off delay 29ms
Power consumption BIs Fct.1 to Fct 4: X1:1 to 6 and 27,94mW
110V AC
Current BIs Fct.5 to Fct 8: X1:7 to 12 254A
HIGH level parameterizable
HIGH level parameterizable
Max. turn-on delay 24ms
Max. turn-off delay 28ms
Power consumption BIs Fct.1 to Fct 4: X1:1 to 6 and 122,13mW
230V AC
Current BIs Fct.5 to Fct 8: X1:7 to 12 531A
HIGH level parameterizable
HIGH level parameterizable
Description Specification
Number 10 binary inputs (BIs); 2 groups by 5 BIs each, rooted COM
General 24/48/60/220V DC, 110V AC/DC, 230V AC (not parameterizable => see
Voltages ordering information!)
NOTE: max. permissible voltage for all BIs = 270V AC/DC
Max. turn-on delay In process (type test)
Max. turn-off delay In process (type test)
Power consumption BIs Fct.1 to Fct 5: X1:1 to 6 and In process (type test)
24V DC
Current BIs Fct.6 to Fct 10: X1:7 to 12 In process (type test)
HIGH level In process (type test)
HIGH level In process (type test)
Max. turn-on delay In process (type test)
Max. turn-off delay In process (type test)
Power consumption BIs Fct.1 to Fct 5: X1:1 to 6 and In process (type test)
48V DC
Current BIs Fct.6 to Fct 10: X1:7 to 12 In process (type test)
HIGH level In process (type test)
HIGH level In process (type test)
Max. turn-on delay In process (type test)
Max. turn-off delay In process (type test)
Power consumption BIs Fct.1 to Fct 5: X1:1 to 6 and In process (type test)
60V DC
Current BIs Fct.6 to Fct 10: X1:7 to 12 In process (type test)
HIGH level In process (type test)
HIGH level In process (type test)
Max. turn-on delay In process (type test)
Max. turn-off delay In process (type test)
Power consumption BIs Fct.1 to Fct 5: X1:1 to 6 and In process (type test)
110V DC
Current BIs Fct.6 to Fct 10: X1:7 to 12 In process (type test)
HIGH level In process (type test)
HIGH level In process (type test)
Max. turn-on delay In process (type test)
Max. turn-off delay In process (type test)
Power consumption BIs Fct.1 to Fct 5: X1:1 to 6 and In process (type test)
220V DC
Current BIs Fct.6 to Fct 10: X1:7 to 12 In process (type test)
HIGH level In process (type test)
HIGH level In process (type test)
General
Number 5 pcs or 12 pcs (depending on device variant)
NOTE For switching of inductive loads by DC voltage: Protective circuit
with flywheel diode for output contacts is required!
For switching of inductive loads by AC voltage: Protective circuit
with varistor for output contacts is required!
Contact load
Rated voltage (AC) 250V (AC*)
Max. Switching voltage 300V DC; 400V AC
Continuous current 8A (AC/DC)
Max. making current 15A (AC/DC) for 4s
Max. breaking capacity (AC) 2000VA
Sync. 1 ON Max. breaking capacity (DC)
(2 normally open 24V 192W
contacts in series) 48V 384W
60V 300W
110V 88W
220V 66W
Contact switching times
Max. turn-on delay 10ms
Max. turn-off delay 5ms
Mechanical contact life-cycle > 2 x 106 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
Contact load
Rated voltage (AC) 250V (AC*)
Shunt 1 (Trip),
Max. Switching voltage 300V DC; 400V AC
Shunt 2
Continuous current 8A (AC/DC)
(normally open
Max. making current 15A (AC/DC) for 4s
contacts)
Max. breaking capacity (AC) 2000VA
Max. breaking capacity (DC)
NOTE:
24V 192W
The normally
48V 96W
open (NO)
60V 60W
contact is
110V 66W
designated for
220V 88W
tripping the
Contact switching times
connected circuit
Max. turn-on delay 10ms
breaker!
Max. turn-off delay 5ms
Mechanical contact life-cycle > 2 x 106 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
Contact load
Rated voltage (AC) 250V (AC*)
Max. Switching voltage 300V DC; 400V AC
Continuous current 8A (AC/DC)
Max. making current 15A (AC/DC) for 4s
Max. breaking capacity (AC) 2000VA
LOCKOUT Max. breaking capacity (DC)
(normally open 24V 192W
contact) 48V 100W
60V 60W
110V 33W
220V 55W
Contact switching times
Max. turn-on delay 10ms
Max. turn-off delay 5ms
Mechanical contact life-cycle > 2 x 106 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
Contact load
Rated voltage (AC) 250V (AC*)
Max. Switching voltage 300V DC; 400V AC
Continuous current 6A (AC/DC)
Function 1 Max. making current 10A (AC/DC) for 4s
Function 2 Max. breaking capacity (AC) 1500A
Function 3 Max. breaking capacity (DC)
Function 4 24V 144W
Function 5 48V 19,2W
(normally open 60V 18W
contacts) 110V 22W
220V 33W
Contact switching times
Max. turn-on delay 12ms
Max. turn-off delay 5ms
Mechanical contact life-cycle 10 x 106 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
Contact load
Rated voltage (AC) 250V (AC*)
Max. Switching voltage 300V DC; 400V AC
Continuous current 8A (AC/DC)
Max. making current 10A (AC/DC) for 4s
Function 6 Max. breaking capacity (AC) 2000VA
Function 7 Max. breaking capacity (DC)
Function 8 24V 192W
(normally open 48V 96W
contacts) 60V 60W
110V 55W
220V 66W
Contact switching times
Max. turn-on delay 7ms
Max. turn-off delay 3ms
Mechanical contact life-cycle 30 x 106 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
*: U = URMS
General
Number: 5 pcs or 12 pcs (depending on device variant)
NOTE For switching of inductive loads by DC voltage: Protective circuit
with flywheel diode for output contacts is required!
For switching of inductive loads by AC voltage: Protective circuit
with varistor for output contacts is required!
Contact load
Rated voltage (AC) 250V (AC)
Max. Switching voltage 300V DC; 400V AC
Continuous current 6A (AC/DC)
Max. making current 10A (AC/DC) for 4s
Max. breaking capacity (AC) 1500VA
Sync. 1 ON Max. breaking capacity (DC)
(2 normally open 24V 144W
contacts in series) 48V 19,2W
60V 18W
110V 22W
220V 33W
Contact switching times
Max. turn-on delay 12ms
Max. turn-off delay 5ms
Mechanical contact life-cycle > 10 x 106 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
Contact load
Rated voltage (AC) 250V (AC*)
Max. Switching voltage 300V DC; 400V AC
Continuous current 16A (AC/DC)
Shunt Trip 1 Max. making current 30A (AC/DC) for 4s
(change-over contact) Max. breaking capacity (AC) 4000VA
Max. breaking capacity (DC)
NOTE: 24V 288W
The normally open (NO) 48V 63W
contact is designated for 60V 48W
tripping the connected 110V 44W
circuit breaker! 220V 66W
Contact switching times
Max. turn-on delay 8ms
Max. turn-off delay 6ms
Mechanical contact life-cycle > 30 x 106 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
Contact load
Rated voltage (AC) 250V (AC)
Max. Switching voltage 300V DC; 400V AC
Continuous current 16A (AC/DC)
Shunt Trip 2 Max. making current 30A (AC/DC) for 4s
(normally open contact) Max. breaking capacity (AC) 4000VA
Max. breaking capacity (DC)
NOTE: 24V 288W
The normally open (NO) 48V 53W
contact is designated for 60V 48W
tripping the connected 110V 44W
circuit breaker! 220V 66W
Contact switching times
Max. turn-on delay 8ms
Max. turn-off delay 6ms
Mechanical contact life-cycle > 30 x 106 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
Contact load
Rated voltage (AC) 250V (AC)
Max. Switching voltage 300V DC; 400 VAC
Continuous current 8A (AC/DC)
LOCKOUT Max. making current 15A (AC/DC) for 4s
(normally open contact) Max. breaking capacity (AC) 2000VA
Max. breaking capacity (DC)
24V 192W
48V 100W
60V 60W
110V 33W
220V 55W
Contact switching times
Max. turn-on delay 10ms
Max. turn-off delay 5ms
Mechanical contact life-cycle > 2 x 106 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
Contact load
Rated voltage (AC) 250V (AC)
Max. Switching voltage 300V DC; 400V AC
Continuous current 6A (AC/DC)
Max. making current 10A (AC/DC) for 4s
Max. breaking capacity (AC) 1500VA
Max. breaking capacity (DC)
24V 144W
Function 1 48V 19,2W
Function 2 60V 18W
Function 3 110V 22W
Function 4 220V 33W
Function 5 Contact switching times
Function 6 Max. turn-on delay 12ms
(normally open Max. turn-off delay 5ms
contacts) Mechanical contact life-cycle 10 x 106 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
NOTE: Function 1 and Function 2 relay contacts are connected
to the same common (rooted contact)! Thus, total
continuous current for the rooted contact of Function 1
and Function 2 contacts must not exceed 6A!
Function 3 to Function 6 relay contacts are connected to
the same common (rooted contact)! Thus, total continuous
current for the rooted contact of Function 3 to Function
6 contacts must not exceed 6A!
Contact load
Rated voltage (AC) 240V (AC)
Max. Switching voltage 300V DC; 400V AC
Continuous current 8A (AC/DC)
Max. making current 10A (AC/DC) for 4s
Max. breaking capacity (AC) 2000VA
Function 7
Max. breaking capacity (DC)
Function 8 (Watchdog)
24V 192W
(normally open
48V 96W
contacts)
60V 60W
110V 55W
220V 66W
Contact switching times
Max. turn-on delay 7ms
Max. turn-off delay 3ms
Mechanical contact life-cycle 30 x 106 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
*: U = URMS
General
Number 1 BO (change-over contact)
NOTE For switching of inductive loads by DC voltage: Protective circuit
with flywheel diode for output contacts is required!
For switching of inductive loads by AC voltage: Protective circuit
with varistor for output contacts is required!
Contact load
Rated voltage (AC) 250V (AC*)
Max. Switching voltage 300V DC; 400 V AC
Continuous current 10A (AC/DC)
Max. making current 25A (AC/DC) or 4s
Max. breaking capacity (AC) 3000VA
Max. breaking capacity (DC)
Fct 1 24V 288W
(change-over 48V 63W
contact) 60V 48W
110V 44W
220V 66W
Contact switching times
Max. turn-on delay
Max. turn-off delay 8ms
Mechanical contact life-cycle 6ms
> 30 x 103 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
*: U = URMS
General
Number 4 BOs (change-over contact)
NOTE For switching of inductive loads by DC voltage: Protective circuit
with flywheel diode for output contacts is required!
For switching of inductive loads by AC voltage: Protective circuit
with varistor for output contacts is required!
Contact load
Rated voltage (AC) 250V (AC*)
Max. Switching voltage 300V DC; 400 V AC
Continuous current 10A (AC/DC)
Max. making current 25A (AC/DC) or 4s
Fct 1 Max. breaking capacity (AC) 3000VA
Fct 2 Max. breaking capacity (DC)
Fct 3 24V 288W
Fct 4 48V 63W
(change-over 60V 48W
contacts) 110V 44W
220V 66W
Contact switching times
Max. turn-on delay 8ms
Max. turn-off delay 6ms
Mechanical contact life-cycle > 30 x 103 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
*: U = URMS
General
Number 6 BOs (normal open contact)
NOTE For switching of inductive loads by DC voltage: Protective circuit
with flywheel diode for output contacts is required!
For switching of inductive loads by AC voltage: Protective circuit
with varistor for output contacts is required!
Contact load
Rated voltage (AC) 250V (AC*)
Max. Switching voltage 300V DC; 400 VAC
Continuous current 8A (AC/DC)
Fct 1 Max. making current 15A (AC/DC) or 4s
Fct 2 Max. breaking capacity (AC) 2000VA
Fct 3 Max. breaking capacity (DC)
Fct 4 24V 192W
Fct 5 48V 96W
Fct 6 60V 60W
(normal open 110V 55W
contacts) 220V 66W
Contact switching times
Max. turn-on delay 9ms
Max. turn-off delay 5ms
Mechanical contact life-cycle > 100 x 103 Operating cycles (ON->OFF->ON, or OFF->ON->OFF)
*: U = URMS
Description Specification
The following specifications of measuring accuracy are only valid for the set nominal frequeny:
50Hz/60Hz
DEVIATION (MAGNITUDE)
Secondary nominal current In: 1A
Measuring ranges*: 0,02 ...1 x In, deviation: 0,5% In
1 ... 10 x In, deviation: 0,5% of meas. value
10 ... 20 x In, deviation: 1% of meas. value
20 ... 32 x In deviation: 3% of meas. value
Temperature influence: 0 ... 60C: deviation: 1% In
Frequency influence
- with adaption of sample time: fn +/-5Hz deviation: x%/Hz
- constant sample time: fn +/-5Hz deviation: x%/Hz
CT1**, CT-GND1 Harmonics influence: 20% of 3rd or 5th harmonic deviation: 1% In
Secondary nominal current In: 5A
Measuring ranges*: 0,02 ...1 x In, deviation: 0,5% In
1 ... 2 x In, deviation: 0,5% of meas. value
2 ... 20 x In, deviation: 1% of meas. value
20 ... 32 x In, deviation: 3% of meas. value
Temperature influence: 0 ... 60C: deviation: 1% In
Frequency influence
- with adaption of sample time: fn +/-5Hz deviation: x%/Hz
- constant sample time: fn +/-5Hz deviation: x%/Hz
Harmonics influence: 20% of 3rd or 5th harmonic deviation: 1% In
DEVIATION (MAGNITUDE)
Total measuring range: 2 ... 3000mA
Measuring ranges*: 2 ... 100mA, deviation: 1mA
100 ... 2500mA, deviation: 1% of meas. value
2500 ... 2800mA, deviation: 3% of meas. value
CT-GND1(sensitive input)
Temperature influence: 0 ... 60C: deviation: 1% In
Frequency influence
- with adaption of sample time : fn +/-5Hz deviation: x%/Hz
- constant sample time: fn +/-5Hz deviation: x%/Hz
Harmonics influence: 20% of 3rd or 5th harmonic deviation: 1% In
POWER CONSUMPTION
1A inputs*: at 1 x In: approx. 0,007VA
at 20 x In: approx. 2,8VA
at 100 x In: approx. 1,5kVA
CT1, CT-GND1 5A inputs*: at 1 x In: approx. 0,13VA
at 20 x In: approx. 45VA
at 100 x In: approx. 15kVA
NOTE: With a connecting cable (4mm; length:2,5m) and a 5A current transformer, the total load
at 20 x In (5A) amounts to 227VA
POWER CONSUMPTION
CT-GND1 (sensitive input) 2 ... 3000mA*: at 100mA: approx. 0,007VA
at 3000mA: approx. 2,8VA
AC OVERCURRENT PROOF
1A inputs*: at 250 x In: for 10ms (half- oscillation)
at 100 x In: up to 1s
at 45 x In: up to 10s
at 32 x In: up to 30s
at 5 x In: continuous
CT1, CT-GND1
5A inputs*: at 50 x In: for 10ms (half- oscillation)
at 32 x In: for 0,5s
at 20 x In: up to 1s
at 10 x In: up to 10s
at 7 x In: up to 30s
at 5 x In: continuous
Description Specification
AC OVERCURRENT PROOF
2 ... 3000mA*: at 50A: for 10ms (half- oscillation)
CT-GND1(sensitive input) at 30A: up to 1s
at 15A: up to 10s
at 3A: continuous
For current measurement, a distortion factor k < 5% is assumed.
* Environmental temperature: 20C; humidity: non-condensing; protection relay at steady operation at nominal values
** Information about deviation refers to both, CT1-M/P and CT1-M
Description Specification
Table 7-63 Specification of analog outputs (AO) of the SYMAP-Compact(+) device variants
Description Designation Specification
The number and type of available analog outputs (AO) depends on
Number:
selection option of the order code
between potential group and device
720V DC, for 1s
housing
Table 7-64 Specification of analog outputs (AO) of the SYMAP-Compact(+) device variants
Description Designation Specification
The number and type of available analog outputs (AO) depends on
Number:
selection option of the order code
between potential group and device
720V DC, for 1s
housing
Isolation to between two analog potential groups (ELV
other circuits 1,4kV DC, for 1s
circuits) and communication interfaces
Table 7-65 Specification of analog inputs (AI) of the SYMAP-Compact(+) device variants
Description Designation Specification
- Number: 4 analog inputs
between potential group and device housing 720V DC, for 1s
Designation
Data protocol Specification
phys. interface
Diameter core: 50m or 62,5m
Connection type: ST
Wavelength: 820 nm (Multimode)
Transmission distance: max. 2km
Network topology: star
Selectable ID addresses: 0 123 (parameterizable)
Laser class: 1
Interface: fibre optics (FO) (ordering option); multimode
Location: back panel
Terminals: star: TxD 1, RxD 1
star redundancy: TxD 1, RxD 1; TxD 2, RxD 2
double star: TxD 1, RxD 1; TxD 2, RxD 2
ring: TxD 1, RxD 1; TxD 2, RxD 2
X4.3 (star) /
ring redundancy: TxD 1, RxD 1; TxD 2, RxD 2
X4.4 (double
star, star Fibre type: glass fibre
redundancy, ring Diameter sleeve: 125m
or ring
Diameter core: 50m or 62,5m
redundancy)
Connection type: ST
Wavelength: 1300 nm
IEC 61850
Transmission distance: max. 2km
Selectable source subscriber IDs: 0 128 (parameterizable)
Laser class: 1
Interface: RJ45 (ordering option), electrical, galv. isolated
Location: back panel
X4.3 (star) /
X4.4 (double Terminals: star: Port 1
star, star star redundancy: Port 1; Port 2
redundancy, ring double star: Port 1; Port 2
or ring ring: Port 1; Port 2
redundancy) ring redundancy: Port 1; Port 2
Transmission distance: max.100m
Selectable source subscriber IDs: 0 128 (parameterizable)
Interface: fibre optics (FO) (ordering option); multimode
Location: back panel
Terminals: TxD, RxD
Fibre type: glass fibre
Diameter sleeve: 125m
Diameter core: 50m or 62,5m
X4.5
Connection type: ST
Wavelength: 820 nm (Multimode)
Transmission distance: max. 2km
Network topology: star
Selectable ID addresses: 0 255 (parameterizable)
Laser class: 1
Interface: RS485; serial port 2 (ordering option); electrical;
IEC 60870-5-103 galv. isolated
Connection type: 2-pole connector
Location: back panel
Signal transmission type: differential / half duplex
Terminals, half duplex: A1(+), B1(-)
Selectable symbol rates (Baud rate): 9600Bd, 19200Bd, 38400Bd and 57600Bd
X4.6 Transmission distance: max.1 km
Network topology: bus system
Bus load: 1/4 UL (unit load)
=> max. number of users depends on bus load of
the master connected to the bus system;e.g.
Master: 1/4 UL => max. 128 SYMAP-Compact(+)
Selectable ID addresses: 0 255 (parameterizable)
Signal wiring: shielded, twisted-pair
NOTE: Termination of 120 on both ends of the bus system is required!
8 Order Information
8.1 SYMAP-Compact Hardware versions v1-1.x and v1-2.x
(HW v1-2.x only available for SYMAP-Compact+!)
Order code: v1-6.0; Order information: v1.14.0 Ordering identifier 1 2 3
1. Device variant
Protection system: voltage relay (6 x U; 1 x UG1)
F0 ANSI: 25, 27, 27T, 47, 59, 59AV; 59N/G, 74TC, 78, 81, 81R, 81RAV, 86, DCVM, PTS
Protection system: current relay (3 x I, 1 x I1)
F1 ANSI: 37, 46, 46BC, 48, 49, 50BF, 50/51, 50/51G, 51LR, 51MS, 52, 64REF, 66, 74TC, 79, 86, 87GH,
87H, 95i, CLD, CTS, SOTF
Protection and control system: current relay (3 x I, 1 x IG1)
+F1 ANSI: 37, 46, 46BC, 48, 49, 50BF, 50/51, 50/51G, 51LR, 51MS, 52, 64REF, 66, 74TC, 79, 86, 87GH,
87H, 95i, CLD, CTS, SOTF
Protection system: current relay (3 x I, 1 x IG1, 1 x UG1)
F2 ANSI: 32N/G; 37, 46, 46BC, 48, 49, 50BF, 50/51, 50/51G, 51LR, 51MS, 52, 59N/G, 64REF, 66, 67G,
74TC, 79, 86, 87GH, 87H, 95i, CLD, CTS, SGF, SOTF
Protection and control system: current relay (3 x I, 1 x IG1, 1 x UG1)
+F2 ANSI: 32N/G; 37, 46, 46BC, 48, 49, 50BF, 50/51, 50/51G, 51LR, 51MS, 52, 59N/G, 64REF, 66, 67G,
74TC, 79, 86, 87GH, 87H, 95i, CLD, CTS, SGF, SOTF
Protection system: current and voltage relay (3 x I, 3 x U, 1 x IG1, 1 x UG1)
ANSI: 21FL, 24, 27, 27Q, 27T, 32, 32N/G; 37, 40, 46, 46BC, 47, 48, 49, 50BF, 50/51, 50/51G, 51LR,
F3 51MS, 51/46VR, 52, 55, 59, 59AV, 59N/G, 64REF, 66, 67, 67G, 74TC, 78, 78S, 79, 81, 81R, 81RAV,
86, 87GH, 87H, 95i, CLD, CTS, DCVM, PTS, SGF, SOTF
Protection and control system: current and voltage relay (3 x I, 3 x U, 1 x IG1, 1 x UG1)
ANSI: 21FL, 24, 27, 27Q, 27T, 32, 32N/G; 37, 40, 46, 46BC, 47, 48, 49, 50BF, 50/51, 50/51G, 51LR,
+F3 51MS, 51/46VR, 52, 55, 59, 59AV, 59N/G, 64REF, 66, 67, 67G, 74TC, 78, 78S, 79, 81, 81R, 81RAV,
86, 87GH, 87H, 95i, CLD, CTS, DCVM, PTS, SGF, SOTF
Protection system: current and voltage relay (3 x I, 6 x U, 1 x IG1, 1 x UG1)
ANSI: 21FL, 21B, 24, 25, 27, 27Q, 27T, 32, 32N/G; 37, 40, 46, 46BC, 47, 48, 49, 50BF, 50/51, 50/51G,
F4 51LR, 51MS, 51/46VR, 52, 55, 59, 59AV, 59N/G, 64REF, 66, 67, 67G, 74TC, 78, 78S, 79, 81, 81R,
81RAV, 86, 87GH, 87H, 95i, CLD, CTS, DCVM, PTS, SGF, SOTF
Protection and control system: current and voltage relay (3 x I, 9 x U, 1 x IG1, 1 x UG1)
ANSI: 21FL, 21B, 24, 25, 27, 27Q, 27T, 32, 32N/G; 37, 40, 46, 46BC, 47, 48, 49, 50BF, 50/51, 50/51G,
+F4 51LR, 51MS, 51/46VR, 52, 55, 59, 59AV, 59N/G, 64REF, 66, 67, 67G, 74TC, 78, 78S, 79, 81, 81R,
81RAV, 86, 87GH, 87H, 95i, CLD, CTS, DCVM, PTS, SGF, SOTF
Protection system: synchronizing relay (9 x U)
SYN ANSI: 25, 25A, 74TC, 86, DCVM,
Engine control (without U/I measuring)
EC ANSI: 5, 12, 14, 15
Generator control incl. protective functions (3 x I, 9 x U)
ANSI:15, 24, 25, 25A, 27, 27Q, 27T, 32, 32N/G; 40, 46, 46BC, 47, 49, 50BF, 50/51, 50/51G, 51/46VR,
GC 52, 55, 59, 59AV, 59N/G, 67, 67G, 74TC, 78, 78S, 81, 81R, 81RAV, 86, 95i, SGF, SOTF, CLD, CTS,
DCVM, PTS
Engine control and Generator protection (3 x I, 9 x U)
ANSI: 5, 12, 14, 15, 24, 25, 25A, 27, 27Q, 27T, 32, 32N/G; 40, 46, 46BC, 47, 49, 50BF, 50/51, 50/51G,
ECG 51/46VR, 52, 55, 59, 59AV, 59N/G, 67, 67G, 74TC, 78, 78S, 81, 81R, 81RAV, 86, 95i, SGF, SOTF,
CLD, CTS, DCVM, PTS
Generator control incl. protective functions (3 x I, 9 x U, 1 x IG1, 1 x UG1)
ANSI:15, 21B, 21FL, 24, 25, 25A, 27, 27Q, 27T, 32, 32N/G; 40, 46, 46BC, 47, 49, 50BF, 50/51,
+GC 50/51G, 51/46VR, 52, 55, 59, 59AV, 59N/G, 64REF, 67, 67G, 74TC, 78, 78S, 81, 81R, 81RAV, 86,
87GH, 87H, 95i, SGF, SOTF, CLD, CTS, DCVM, PTS
Engine control and Generator protection (3 x I, 9 x U, 1 x IG1, 1 x UG1)
ANSI: 5, 12, 14, 15, 21B, 21FL, 24, 25, 25A, 27, 27Q, 27T, 32, 32N/G; 40, 46, 46BC, 47, 49, 50BF,
+ECG 50/51, 50/51G, 51/46VR, 52, 55, 59, 59AV, 59N/G, 64REF, 67, 67G, 74TC, 78, 78S, 81, 81R, 81RAV,
86, 87GH, 87H, 95i, SGF, SOTF, CLD, CTS, DCVM, PTS
2. Phase current transformer CT1
A without (device variants: SYMAP-Compact F0, EC0, EC1 only)
B CT1: 1A secondary, rated current (HW v1-1.x: 0,02-20 x In; HW v1-2.x: 0,02-32In)
C CT1: 5A secondary, rated current (HW v1-1.x: 0,02-20 x In; HW v1-2.x: 0,02-32In)
CT1: 1A and 5A secondary, rated current (1A: HW v1-1.x: 0,02-20 x In; HW v1-2.x: 0,02-32In or
D 5A: 0,02-5xIn), Gen-Set controls only
CT1-MP: 1A secondary, rated current (M: 0,02-2In, P: HW v1-1.x: 0,02-20 x In; HW v1-2.x:
E 0,02-32In), SYMAP-Compact+ only, and only device variants without CT-GND2 and without CT3 !
CT1-MP: 5A secondary, rated current (M: 0,02-2In, P: HW v1-1.x: 0,02-20 x In; HW v1-2.x:
F 0,02-32In), SYMAP-Compact+ only, and only device variants without CT-GND2 and without CT3 !
3. Phase current transformer CT2
0 without (Standard)
CT2: 1A secondary, rated current (HW v1-1.x: 0,02-20 x In; HW v1-2.x: 0,02-32In),
1 SYMAP-Compact+ only !
CT2: 5A secondary, rated current (HW v1-1.x: 0,02-20 x In; HW v1-2.x: 0,02-32In),
2 SYMAP-Compact+ only !
Ordering identifier 4 5 6 7 8 9 10 11
Ordering option
Ordering identifier 12 13 14 15 16 17
Ordering option
Ordering identifier 18 19 20 21 22 23 24 25
Ordering option
Ordering Ordering
option identifier
SYMAP-Compact 1. Device variant
2. Phase current transformer CT1
3. Phase current transformer CT2
4. Phase current transformer CT3
5. Ground current transformer CT-GND1
6. Ground current transformer CT-GND2
7. Power supply device
8. Binary Inputs
9. Binary Outputs
10. Analog Inputs and Outputs
11. Communication SCADA Port-1
12. Communication SCADA Port-2
13. Communication SCADA Port-3
14. Communication Interfaces
15. Frequency measurement
16. Additional protective function
17. User levels
18. Control and interlocking
19. Safety Device
20. Front plate (design)
21. Detached HMI
22. Voltage measurement inputs
23. LED indications front plate
24. Firmware version (FW)
25. Hardware version (HW)
Device variant
Application: "Binary inputs (opto-couplers)"
Dimensions:
Housing dimensions: (BxHxT): (91,5x30,5x76,2)mm
Mounting:
DIN rail TS35
Device front:
"Stucke"-Design
LED indication:
1 status LED (Power: green)
BI10- 10 status LEDs (binary inputs: green)
Binary inputs:
10 BIs (Un: see ordering option 1. "Nominal voltage - Binary inputs")
Grouping of Binary inputs:
2 groups of 5 BIs each
Technical design:
Opto couplers (OC)
Communication interfaces:
2 x RJ45, Inter-Link (in/out)
Power index: 5
1. Nominal voltage - Binary inputs
0 12V DC
1 24V DC
2 48V DC
3 60V DC
4 110V DC
5 220V DC