Alarm DDF
Designation Remarks Connection
No. SLOT
1 Door Cabinet Open(WHITE / 1 Connected directly to Sensor - DDF 1 - BBU SA
BLUE) BBU SA Card
2 High Temperature(WHITE / 2 Connected directly to Sensor - DDF 2 - BBU SA
ORANGE) BBU SA Card
3 Tower Light Failure 3 Connected directly to Sensor - DDF 3 - BBU SA
Alarm(WHITE / GREEN) BBU SA Card
4 Rectifier Alarm (WHITE / 4 From B201 SIB Board X15 - DDF 4 - BBU SA
BROWN) (Power Unit) - X15 port
5 AC Power Fail(WHITE / GRAY) 5 From B201 SIB Board X16 - DDF 5 - BBU SA
(Power Unit) - X16 port
6 Environmental Over 6 From B201 SIB Board X16 - DDF 6 - BBU SA
Humidity(RED / BLUE) (Power Unit) - X16 port
7 DC Low Voltage alarm(RED / 7 From B201 SIB Board X17 - DDF 7 - BBU SA
ORANGE) (Power Unit) - X17 port
8 SMOKE Alarm(RED / Green) 8 From B201 SIB Board X17 - DDF 8 - BBU SA
(Power Unit) - X17 port
<> 1
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
Door 1 sensor
ODU Cabinet Door open alarm
DDF Port 1 Door 2 sensor
Actual Tower
Medium light alarm cable
Tower Light Failre Alarm Control Junction
Low light alarm cable
DDF Port 3 box box
Low light alarm cable
NodeB(BS8800) part:
SA card D
(BS8800) D
F
For New site External alarm we through BS8800 SA card report to EMS/OMC.all external alarm sensor
should be connect to SA card through DDF terminal.before connect sensor,please make loop back test
from DDF to OMC,make sure 8channel no any cross.it very important for test external alarm.
External alarm connection :
SA card-------SA cable(B3 connector)---------SA E1 Cable----------DDF-------each sensor
1. SA cable :material code: 052740402435 DS-91228-001|Digital Signal Cable
<> 2
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
<> 3
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
3.connection picture:
<> 4
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
Door 1 sensor
ODU Cabinet Door open alarm
DDF Port 1 Door 2 sensor
SA card D
(BS8800) D
F
Door1 and Door2 Sensor cable need parallel connect to DDF port1
Door 1 Sensor :
Door2 Sensor
<> 5
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
ODU Cabinet
SA card D
(BS8800) D
F
<> 6
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
<> 7
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
SA card D
(BS8800) D
F
Tower
Medium light alarm cable
Tower Light Failre Alarm Control Junction
Low light alarm cable
DDF Port 3 box box
Low light alarm cable
Tower lignht Alarm cable(alarm output in control box) need connect to DDF port3
Medium light(1pcs) /low light(2pcs) cable (Brow/blue) connect to Junction box alarm input terminal,
From Junction box connect to Control box alarm input terminal, From Control box alarm output
connect to DDF port3 terminal. For detail connection please reference installation and operation
manual in the box.
<> 8
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
SA card D
Rectifier alarm
(BS8800) D B201 X15 Port(NC/COM)
DDF Port 4
F
Below description detail how to setting external alarm in ZXDU68 B201 system.
The boards of the zxdu68 B201system is integrated in the signal transfer box. Figure as below:
shown the board layout.
<> 9
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
The relays alarm function has two options on the signal board, one relay output-NO(normal open)
and one relay output-NC(normal close). So need to know the BTS interface alarm definition
which it is NO or NC.
If it is NO, and connect relay alarm cables step:
1 One group relay out need two signal cables , and one terminal connect with relay out ON and
relay output common end on the signal board interface, another terminal connect with the
BTS interface.
NO
COMMON
DDF
<> 11
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
2press the button ENTER of the monitor.
4 Enter the setup parameter system: 1. Setup Para, press the Enter button.
6 Enter the Alarm Para menu, find the 1.Set Relay to Enter
7 And find the relays alarm parameter. According to the relays alarm requirements, set the relay
<> 12
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
alarm.
Setup procedures
If the relay alarm connected the X15(1,2) of the signal board, it mean what it is SMR Alarm.
So the relay alarm parameter set A2.
Refer to above the Table-1.
ODU Cabinet
SA card D
(BS8800) D
F
Smoke alarm From Smoke sensor first connect to X24then X17 NC/COM connect to DDF port8
<> 13
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset)
Door 1 sensor
ODU Cabinet Door open alarm
DDF Port 1 Door 2 sensor
B201 Module
Rectifier alarm
B201 X15 Port(NC/COM)
DDF Port 3
SA card D
(BS8800) D
AC power fail alarm B201 X16 Port(NC/COM)
F
DDF Port 4
virtual
Generator
Generator Fault
Actual Generator
DDF Port 7
<> 14
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
For alarm No.1No.6,please refer ZTE ODU EXTERNAL ALARM CONFIGURATION TEST
(With Sceco) installation.
No7. Generator Fault(RED / ORANGE)
No8 Generator Low Fuel(RED / GREEN)
SA card D
(BS8800) D
F
Generator
Generator Fault
Generator
DDF Port 7
<> 15
All Rights reserved, No Spreading abroad without Permission of ZTE