Académique Documents
Professionnel Documents
Culture Documents
1. Safety 4
1.1 For your safety 4
1.2 Skilled personnel 4
1.3 Crucial information 4
2. General description 5
2.1 Outer assembly 6
3. Transport and handling 7
3.1 By receiving inspection 7
3.2 Storage 7
4. Technical data 8
4.1 Electrical data SafeRing 8
4.2 Electrical data SafePlus 8
5. Installation 9
5.1 Standard 3-way switchgear 9
5.2 3-way switchgear with base frame (AFL) 10
5.3 3-way switchgear with base frame (AFLR) 11
6. Dimensions 13
7. Cable compartment 16
7.1 Standard cable compartment 16
7.2 Arc-proof cable compartment 16
7.3 Cable connection 17
8. Extension of switchgear 18
8.1 External busbar 18
8.2 Side connection 18
2
14 Operation 25
14.1 Operation of cable switch 25
14.2 Operation of vacuum circuit-breaker 26
14.3 Operation of vacuum circuit-breaker 12kV/25kA, 24kV/20kA 27
14.4 Operation of fuse-switch disconnector 28
14.5 Installation and replacement of fuses 28
14.6 Fuse selection tables 30
14.6.1 Fuse selection table - CEF 30
14.6.2 Fuse selection table - CEF-S 31
3
1. SAFETY WARNING
1.1 For your safety! Make sure that the specified electrical ratings are
Strictly follow these Installation and operating instructions. not exceeded under switchgear operating condi-
Only install switchgear in indoor conditions according to tions. Keep the manuals accessible to all personnel
IEC 62271-1 cl.2.1. involved in installation, operation and maintenance.
Ensure that installation, operation and maintenance is The users personnel are responsible for all matters
only carried out by professional p ersonnel. regarding safety in the workplace and correct use
Comply fully with the standards in force (IEC or local), the of the switchgear.
connection conditions of the local power utility and the
applicable safety at work regulations. WARNING
Observe the relevant information in the manual for all Always follow the instructions in the manual and
actions involving the switchgear. respect the rules of good engineering practice
Use gloves when installing or operating switchgear. (GEP)! Hazardous voltages can cause serious in-
jury or death! Disconnect the power and earth live
1.2 SKILLED PERSONNEL parts before proceeding with any work on the
All the installation, putting into service, running and main- switchgear. Follow the safety regulations in force in
tenance operations must be carried out by skilled personnel the place of installation.
with in-depth knowledge of the apparatus.
CONTACT US
When carrying out any maintenance work, the regulations in If you have any further questions about this manual, our field
the country of installation must be strictly complied with. service team will be pleased to help. See the backside of this
Maintenance work must only be performed in a professional manual for contact information.
way by trained personnel familiar with the characteristics of
the switchgear, in accordance with all the relevant IEC safety
regulations and those of other technical authorities, also re-
specting other overriding instructions. It is recommended that
ABB service personnel be called in to perform the servicing
and repair work.
4
2. GENERAL DESCRIPTION
SafeRing is a SF6-insulated ring main unit and SafePlus is a
SF6-insulated compact switchgear for applications in medium
voltage distribution networks. SafeRing and SafePlus offer a
sealed stainless steel tank which contains all the live compo-
nents and switching functions. The transformer is protected
either by a switch fuse combination or a vacuum circuit-
breaker.
The units are delivered from the factory ready for installation.
Available configurations:
DeF, CCF, CCC, CCCF, CCFF, DeV, CCV, CCCC, CCCV,
CCVV.
The units are delivered from the factory ready for installation.
5
2.1 OUTER ASSEMBLY
5 6 7 8
Upper front cover
17
9 1. Manometer
1 2. Nameplate of module
SafePlus
3. Short circuit indicator
2 4. Capacitive voltage indication
5. Load break / earthing switch position indicator
18
3 6. Push buttons close/open operation
4 7. Charged spring indicator
8. Self-powered protection relay
10
9. Vacuum circuit-breaker position
12
11
Lower front cover
10. Nameplate of switchgear
13
11. Fuse blown indicator
12. Disconnector / earthing switch position indicator
13. Capacitive voltage indication
16 Side cover
17. Lifting lug
18. Operating handle (suspended on the side wall, by
default on the right hand side wall)
6
3. TRANSPORT AND HANDLING
The units are delivered from the factory ready for installation.
Weight table
Maximum weights for standard SafeRing
2-way DeV 300 kg 2-way DeF 300 kg
3-way CCV 450 kg 3-way CCF 450 kg
4-way CCCV 600 kg 4-way CCCF 600 kg
4-way CCVV 600 kg 4-way CCFF 600 kg
3-way CCC 450 kg
4-way CCCC 600 kg
SafePlus
Max angle 60o Standard 1-way 150 kg
2-, 3- and 4-way as for SafeRing
5-way 750 kg
M - metering module incl. trafo 250 kg
Mt - metering tariff module incl. trafo 350 kg
NOTE:
Use only approved slings when lifting.
Maximum angle on lifting lugs is set to 60o.
3.2 STORAGE
SafeRing / SafePlus must be stored under cover in a dry and
well ventilated area until it is installed and put into operation.
7
4. TECHNICAL DATA
4.1 ELECTRICAL DATA SAFERING
1)
Depending on the current rating of the fuse-link 2)
Limited by high voltage fuse-links 3) Maximum rating for bushings Interface A (200 series plug-in)
4)
Maximum rating for bushings Interface B (400 series plug-in) 5) Maximum rating for bushings Interface C (400 series bolted)
6)
GOST version is available with 42kV power frequency withstand voltage
Power frequency withstand voltage kV 281)/38/50 281)/38/50 281)/38/50 281)/38/50 281)/38/50 281)/38/50 281)/50 281)/50
Impulse withstand voltage kV 95/95/125 95/95/125 95/95/125 95/95/125 95/95/125 95/95/125 95/125 95/125
Breaking capacities:
1)
GOST version is available with 42kV power frequency withstand voltage 2) Depending on the current rating of the fuse-link 3) Limited by high voltage fuse-links
4)
Tested at 15,2 kV 5) Max. rating for bushings Interface A (200 series plug-in) 6) Max. rating for bushings Interface B (400 series plug-in
7)
Max. rating for bushings Interface C (400 series bolted)
8
5. INSTALLATION
Unit A B B with
sideplate
1-way 298 337 371
2-way 623 662 696
3-way 948 987 1021
4-way 1273 1312 1346
5-way 1598 1637 1671
9
5.2 3-WAY SWITCHGEAR WITH BASE FRAME (AFL)
Unit A B B with
sideplate
1-way NA NA NA
2-way 623 662 696
3-way 948 987 1021
4-way 1272 1312 1346
5-way 1597 1637 1671
10
5.3 3-WAY SWITCHGEAR WITH BASE FRAME (AFLR)
Unit A B With
sideplate indicates cable entry
1-way NA NA NA
2-way 623 662 696
3-way 948 987 1021
4-way 1273 1312 1346
5-way 1598 1637 1671
81/87*
*) Top extension: 8 mm / 81 mm
Side extension: 14 mm / 87 mm
8/14*
11
1786
1626
1045
885
Base frame, height 290 mm
AFLR baseframe Base frame, height 450 mm
* Dimensions for 290 mm baseframe
12
6. DIMENSIONS
13
When installing Ring Main Unit or Compact Switchgear
with Internal Arc Classification AFL with ventilation be-
hind the switchgear, the following must be considered:
Unit must be equipped with arc proof cable covers.
Distance from floor to roof must be minimum 2400 mm
Distance from back of unit to wall must be 100 mm
Arc deflection plate with height 650 mm must be mounted
If unit is freestanding (i.e. distance from back of unit to wall
exceeds 100 mm), the area behind the unit must be restric-
ted and not accessible.
*
WARNING
Switchgear can not be placed between
20 -300 mm from sidewall to maintain the
AFL-classification.
20 - 300 mm
14
For installation of switchgear with Internal Arc Classifi-
cation AFLR with ventilation upwards through exhaust
channel, the following must be considered:
Unit must be equipped with arc proof cable covers
Unit can be installed as free standing
Minimum height of ceiling: 2600 mm
Recommended distance from back wall is 100 mm
15
7. CABLE COMPARTMENT
CAUTION
In case of interlocked cable compartment, cover
can be opened / closed only when earthing switch
is in closed position.
1. Loosen the screws on the cable cover, pull out and lift 1. Lift handle to remove the cable cover, pull out and lift
cover off. cover up
B B
4. The mid-panel can be removed by unscrewing Ax2 and B. 4. The mid-panel can be removed by unscrewing Ax2 and B.
16
7.3 CABLE CONNECTION
SafeRing/SafePlus is equipped with external bushings which
comply with DIN47636T1 & T2/EDF HN 525-61 for termina-
tion of cables.
All bushings are situated in the same height from the floor and
are protected by the cable cover.
Interface C with
M16 x 2 metric threads
400 series, In = 630A
Cable adapters
Adapters from following manufacturers are recommended:
ABB Kabeldon
Sdkabel
Tyco Electronics Raychem
Power Systems
3M
Euromold
NKT cables
DANGER
The manufacturers installation instructions must Earthing bar Cable clamp (additional equipment)
be followed. Be sure to lubricate the bushings
thoroughly with the silicone supplied.
Use only isolated cable connections.
17
8. EXTENSION OF SWITCHGEAR
1VDD006006 GB.
18
10. MOTOR OPERATION
Motor operation can be retrofitted. Use the manuals:
Switches, vacuum circuit-breakers and earthing switches are
operated by mechanisms located behind the front panel. The
All units are delivered with drawings showing the electrical
mechanisms for all the switches and breakers are operated
circuits.
manually with the operating lever (standard), or are fitted with
motor operation (additional equipment).
3PKE mechanism for load break switch (C-module) 3PKSE mechanism for load break switch (C-module)
1VDD200001 1VDD200002
We reserve all rights in this document and in the information contained therein: Reproduction, use or disclosure to third parties We reserve all rights in this document and in the information contained therein: Reproduction, use or disclosure to third parties
without express authority is strictly forbidden. ABB Technology Ltd. without express authority is strictly forbidden. ABB Technology Ltd.
www.abb.com www.abb.com
Edition Document status Responsible Title Language Edition Document status Responsible Title Language
1.0 RELEASED NODIS SafeRing/SafePlus 12/24 EN/NO 1.0 RELEASED NODIS SafeRing/SafePlus 12/24 EN/NO
Location Date Name Location Date Name
Prepared
PPMV 2015-06-23 Espen Motor operation Prepared
PPMV 2015-06-23 Espen Motor operation
Skien Fossen complete on 3PKE Skien Fossen complete on 3PKSE
Checked
PPMV 2015-08-10 Asgeir mechanism for C-, Sl- & Checked
PPMV 2015-08-10 Asgeir mechanism for C- & Sl-
Skien Elvestad F6-modules Skien Elvestad modules
Approved
PPMV 2015-08-13 Magne Approved
PPMV 2015-08-13 Magne
Skien Reinholdt Skien Reinholdt
Document No. Sheet No. Document No. Sheet No.
ABB Technology Ltd. 1VDD200001 1/34 ABB Technology Ltd. 1VDD200002 1/41
3PAE mechanism for fuse-switch (F-module) 1VDD200003 2PA mechanism for circuit-breaker (V-module) 1VDD200004
We reserve all rights in this document and in the information contained therein: Reproduction, use or disclosure to third parties We reserve all rights in this document and in the information contained therein: Reproduction, use or disclosure to third parties
without express authority is strictly forbidden. ABB Technology Ltd. without express authority is strictly forbidden. ABB Technology Ltd.
www.abb.com www.abb.com
Edition Document status Responsible Title Language Edition Document status Responsible Title Language
1.0 RELEASED NODIS SafeRing/SafePlus 12/24 EN/NO 1.0 RELEASED NODIS SafeRing/SafePlus 12/24 EN/NO
Location Date Name Location Date Name
Prepared
PPMV 2015-06-23 Espen Motor operation Prepared
PPMV 2015-06-23 Espen Motor operation
Skien Fossen complete on 3PAE Skien Fossen complete on 2PA
Checked
PPMV 2015-08-10 Asgeir mechanism for F- & Checked
PPMV 2015-08-10 Asgeir mechanism for V- & Sv-
Skien Elvestad SGT-modules Skien Elvestad modules
Approved
PPMV 2015-08-13 Magne Approved
PPMV 2015-08-13 Magne
Skien Reinholdt Skien Reinholdt
Document No. Sheet No. Document No. Sheet No.
ABB Technology Ltd. 1VDD200003 1/45 ABB Technology Ltd. 1VDD200004 1/45
19
11. RELAY AND CURRENT TRANSFORMERS
A protection relay is installed in each vacuum circuit-breaker
module. The cables from the protection relay to the current
transformers are installed from the factory, and end up in the
cable compartment, ready for connection to the three current
transformers supplied.
CAUTION
Before installation:
Check that the three current transformers have
been delivered and that they are all of the same
type.
75
107 107
Each current transformer must be mounted onto its high
voltage cable before the cable termination is fitted.
WARNING
The earth shield on the cable must be led back
through the center hole in the current transformer
(see figure on left) and earthed on the earthing bar
in the cable compartment. A mounting plate for the
current transformers is fitted in the cable compart-
ment.
Installation of current transformers
The cable shielding is led back through the center hole
After the current transformers have been installed in the unit,
and earthed, as shown in figure.
the cables from the protection relay are connected. Consult
the manual supplied with the protection relay for a description
of the connections.
20
12. PRESSURE INDICATOR 5. Remove the filling hose and connect the pressure device to
SafeRing / SafePlus is usually supplied with a pressure indi- check the pressure inside the RMU/switchgear.
cator in the form of a manometer. Additionally it is possible 6. When the correct pressure of 0,4 bar (1,4 bar absolute)
to fit device for an electric signal if the pressure is low. This is obtained, remove the adapter, check that the sealing
requires auxiliary voltage supply. between the pressure indicator and the valve is smooth
and clean, and screw the pressure indicator to the RMU/
12.1 GAS PRESSURE switchgear with tightening torque max 45 Nm as shown
SafeRing / SafePlus contain SF6-gas with a nominal pressure above.
of 1,4 bar at 20o C.
WARNING
Operation when pressure is too low (pointer in
red area):
If pointer is in red area, the operation of the switch-
gear can not be done under love conditions (volta-
ge on). SF6-gas needs to be topped up according
to instruction and filling table below before operati-
on can be done under live conditions.
For more detailed description, see instruction ma-
nual 1VDD201603
WARNING
Replenishment of SF6-gas in SafeRing/SafePlus
Potential risk!
Operators must be trained and qualified for
SF6-gas handling
21
1,45
1,4
1,3 5 1328
10 1352
15 1376
1,25 20 1400
25 1424
30 1448
1,2 35 1472
40 1496
1,15
1,1
1,05
1
2000
1000
1500
500
0
Altitude
12.2 ALTITUDE
Max height above sea level for installation without reducing Top screw for adjusting
gas pressure is 1500 meters. In the interval from 1500 to pressure in higher altitudes
2500 meters, gas pressure has to be reduced according to
figure on previous page. For installation above 2500 meters,
please contact ABB for instructions.
22
13. OPERATION OF THE SWITCHGEAR Application of the X-ray regulations
13.1 OPERATING CONDITIONS One of the physical properties of vacuum insulation is the
Normal ambient conditions possibility of X-ray emissions when the contact gap is open.
SafeRing / SafePlus is generally equipped for operation/ The specified test performed by the Physikalisch-Technische
service in normal indoor conditions in accordance with Bundesanstalt (PTB) in Braunschweig demonstrates that the
IEC 62271-1. local dosage output of 1 ?Sv/h at a distance of 10 cm from
the touchable surface is not exceeded when the rated voltage
The following limitations apply: is applied.
23
13.2 GENERAL WARNINGS AND PRECAUTIONS 13.4 START-UP
Instructions
DANGER Comply with all relevant safety regulations.
Do not walk on the top of switchgear units! Ensure that the switch-disconnectors, circuit-breakers or
fuse-switches in the configuration are in the OPEN position.
Energize the power supply feeders.
DANGER Connect the switchgear step by step, observing the signals
Switchgear operations must be carried out with the and indicators.
doors closed. Where necessary, check that the conductors are in phase
when there are several incoming feeder cables and switch-
WARNING gear sections.
Operations and any type of work must be carried Carry out all measurements and check that all functions
out by trained and specialized personnel who are that depend on the medium voltage power supply are
familiar with SafeRing/SafePlus and follow all the connected.
safety regulations in accordance with the IEC Stan- Check there are no irregularities of any kind.
dards and other regulations in force, as well as any
local work regulations and instructions.
Other checkpoints
Depending on the allocation of responsibilities, it may also be
necessary to check the following equipment in the vicinity of
the switchgear:
Power cables
Auxiliary cables
Auxiliary power source
Remote control system
Complete earthing system
Switchgear installation room equipment
Switchgear installation room characteristics:
Pressure resistance in the case of an arc fault
Ventilation
Temperature
Humidity
24
14. OPERATION 14.1 OPERATION OF CABLE SWITCH
All switches can be operated with the included operating
handle.
Internal mechanical interlocking between the switch discon-
nector/isolator and the associated earthing switches pre-
vents incorrect operation. For detailed interlocking descrip-
tion, see dedicated overview for each module in catalogue
1VDD006104 GB.
Switch disconnector:
Close: Turn the operating handle clockwise.
Open: Turn the operating handle anti-clockwise.
Earthing switch:
Close: Turn the operating handle clockwise.
Open: Turn the operating handle anti-clockwise.
25
14.2 OPERATION OF VACUUM CIRCUIT-BREAKER
26
14.3 OPERATION OF VACUUM CIRCUIT-BREAKER - 12kV/25kA, 24kV/20kA
Indication -
spring charged / discharged
CAUTION
If the vacuum circuit-breaker is equipped with motor
operation (optional) it is not necessary to charge
the spring by hand. The motor starts charging the
spring automatically as soon as the auxiliary volta-
ge is switched on.
27
14.4 OPERATION OF FUSE-SWITCH DISCONNECTOR 14.5 INSTALLATION AND REPLACEMENT OF FUSE-LINKS
A red indicator below the fuse symbol on the lower front panel
WARNING indicates that at least one fuse-link has blown. Fuse links are
For correct function of F-module, it is required to replaced as shown in the sequence of illustrations. Switch-
use fuses suitable for rating of protected distri- fuse configurations are supplied without fuse-links installed.
bution transformer, see fuse selection table on
following pages. Use of improper fuse can cause When installing fuse-links for the first time, follow the
void of warranty. sequence of illustrations 1-9.
B A
Switch-fuse disconnector:
Charging springs: Turn the operating handle clockwise to
charge the closing and the opening spring.
Close: Push the green button (A)
Open: Push the red button.(B)
28
3. Unscrew fuse cover. 7. Fix the fuses to the fuse cover using the contact screw
4. Tilt out the fuse panel to gain access to fuse canisters.
- The striker must point out from the fuse canister for the
fuse to function properly.
5. Applying the operating handle and turning anti-clockwise 8.Turn the handle on the fuse cover clockwise to close and
opens the fuse canisters. seal the fuse canister.
Use the operating handle.
6. Pull out the fuse handle. The fuses are firmly fixed in the
fuse cover.
29
14.6 FUSE SELECTION TABLE
Fuse-link
100% Transformer rating (kVA) rated
voltage
Un (kV) 25 50 75 100 125 160 200 250 315 400 500 630 800 1000 1250 1600
3 16 25 25 40 40 50 50 80 100 125 160 160
3,3 16 25 25 40 40 50 50 63 80 100 125 160
4,15 10 16 25 25 40 40 50 50 63 80 100 125 160
7,2 kV
5 10 16 25 25 25 40 40 50 50 63 80 100 160 160
5,5 6 16 16 25 25 25 40 50 50 63 80 100 125 160
6 6 16 16 25 25 25 40 40 50 50 80 100 125 160 160
6,6 6 16 16 25 25 25 40 40 50 50 63 80 100 125 160
10 6 10 10 16 16 25 25 25 40 40 50 50 80 80 125 125
11 6 6 10 16 16 25 25 25 25 40 50 50 63 80 100 125 12 kV
12 6 6 10 16 16 16 25 25 25 40 40 50 63 80 100 125
13,8 6 6 10 10 16 16 25 25 25 25 40 50 50 63 80 100
15 6 6 10 10 16 16 16 25 25 25 40 40 50 63 80 100 17,5 kV
17,5 6 6 6 10 10 16 16 16 25 25 25 40 50 50 63 80
20 6 6 6 10 10 16 16 16 25 25 25 40 40 50 63 63
22 6 6 6 6 10 10 16 16 16 25 25 25 40 50 50 63 24 kV
24 6 6 6 6 10 10 16 16 16 25 25 25 40 40 50 63
Fuse-link
120% Transformer rating (kVA) rated
voltage
Un (kV) 25 50 75 100 125 160 200 250 315 400 500 630 800 1000 1250 1600
3 16 25 25 40 40 50 63 80 100 125 160
3,3 16 25 25 40 40 50 63 80 80 100 125
4,15 10 16 25 25 40 40 50 63 80 80 100 125
7,2 kV
5 10 16 25 25 25 40 40 50 63 80 80 125 160
5,5 6 16 16 25 25 25 40 50 50 80 80 100 125 160
6 6 16 16 25 25 25 40 40 50 63 80 100 125 160
6,6 6 16 16 25 25 25 40 40 50 63 80 80 100 125
10 6 10 10 16 16 25 25 25 40 40 50 63 80 80 125
11 6 6 10 16 16 25 25 25 25 40 50 50 80 80 100 125 12 kV
12 6 6 10 16 16 16 25 25 25 40 40 50 63 80 100 125
13,8 6 6 10 10 16 16 25 25 25 25 40 50 50 80 80 100
15 6 6 10 10 16 16 16 25 25 25 40 40 50 63 80 100 17,5 kV
17,5 6 6 6 10 10 16 16 16 25 25 25 40 50 50 63 80
20 6 6 6 10 10 16 16 16 25 25 25 40 40 50 63 80
22 6 6 6 6 10 10 16 16 16 25 25 25 40 50 50 63 24 kV
24 6 6 6 6 10 10 16 16 16 25 25 25 40 40 50 63
30
14.6.2 FUSE SELECTION TABLE - CEF-S
Fuse-link length
Fuse-link rated
Catalogue No.
voltage (kV)
voltage (kV)
25 50 75 100 125 160 200 250 315 400 500 630 Catalogue No. CEF-S
e (mm)
CEF-S-TCU
3 16 25 40 50
3.3 16 25 40 50 50
4.15 16 20 40 40 50 10A:1YMB531011M0001 10A:1YMB531861M0001
5 10 20 25 40 40 50 16A:1YMB531011M0002 16A:1YMB531861M0002
5.5 10 20 20 40 40 40 50 20A:1YMB531011M0003 20A:1YMB531861M0003
6/12 292
6 10 16 20 25 40 40 50 25A:1YMB531011M0004 25A:1YMB531861M0004
6.6 10* 16 20 25 40 40 50 50 40A:1YMB531011M0005 40A:1YMB531861M0005
10 10* 10 16 20 20 25 40 40 50 50A:1YMB531011M0006 50A:1YMB531861M0006
11 10* 10 16 20 20 25 40 40 40 50
12 10* 10 16 16 20 20 25 40 40 50
13.8 10* 10* 16 16 16 20 20 40 40 40
15 10* 10* 10 16 16 20 20 25 40 40 10A:1YMB531012M0001 10A:1YMB531862M0001
17.5 10* 10* 10 16 16 20 20 20 40 40 40 16A:1YMB531012M0002 16A:1YMB531862M0002
10/24 442
20 10* 10* 10* 10 16 16 20 20 25 40 40 20A:1YMB531012M0003 20A:1YMB531862M0003
22 10* 10* 10* 10 16 16 20 20 20 40 40 40 25A:1YMB531012M0004 25A:1YMB531862M0004
24 10* 10* 10* 10 16 16 16 20 20 25 40 40 40A:1YMB531012M0005 40A:1YMB531862M0005
Max.gG fuse-link
at LV side (A)
40 80 125 160 160 200 250 250 300 400 400 800
The table was calculated according to standards IEC 60787 For ratings marked with * transformer maximum short-circuit
and IEC 62271-105. The following transformer and switch- current at LV side, transferred to HV side, is below fuse-link
gear work conditions were assumed: minimum breaking current I3.
Maximum long-lasting transformer overload - 120%, The table above details the rated current of a particular fuse-
Magnetizing inrush current for transformers up and including link for a given line voltage and transformer rating. For differ-
630kVA - 12 x In during 100ms, ent criteria, the fuse selection must be recalculated.
Magnetizing inrush current for transformers above 630kVA -
10 x In during 100ms,
Standard ambient working conditions for SafeRing/SafePlus
switchgear (most important: ambient temperature -25 C to
+40 C),
31
15. METERING MODULE
DANGER!
Make sure there is no voltage in the busbars and
cable terminals and that the risk of reconnection
is eliminated in all units. Any remote control must
also be prevented.
2. Use handles to lift door first up (vertical), then pull the door
out (horizontal).
1.2 With key lock: Unlock door by using the key for the panel
door.
32
16. CAPACITIVE VOLTAGE INDICATORS
Each module of switchgears is equipped with a capacitive
voltage indicator in accordance with either IEC 61958 (VPIS)
or IEC 61243-5 (VDS).
WARNING
The indication of VPIS alone is not sufficient to pro-
ve that the system is dead: if operating procedures
make it mandatory, relevant voltage detectors
according to IEC 61243-1, IEC 61243-2 and IEC
61243-5 shall be used.
NOTE
Under very bright lighting it may be necessary to
improve visibility by additional means.
OPERATING TEMPERATURE
The VPIS will operate reliably over a temperature range of
25 to +50C.
33
16.2 VOLTAGE INDICATORS VDS
VDS is used to detect the presence or absence of medium
voltage according to IEC 61243-5.
The VDS are based on the HR system, the system consists
of a fixed device, installed in the switchgear, coupled with a
mobile device to visually detect the presence or absence of
service voltage and phase balance and on which the indicator
lights are installed.
The state of voltage present is visually indicated with at least
1Hz repetition frequency. Flashing light indication whose
Capacitive voltage impulse frequency must be between 1 Hz and 3 Hz with an
indicator type HR impulse / pause ratio of 4 to 1.
The voltage indicators which are recommended are the
VIM1 type used as a mobile device and VIM3 type, used as a
fixed and mobile device, made by Maxeta.
The voltage indicators have a maximum operating voltage
threshold of 90 V and a maximum current threshold of 2.5 uA
at 50Hz.
OPERATING TEMPERATURE
The VDS works reliably with a temperature range from 25C
to +50C.
PHASE COMPARATOR
The phase comparator detects the balance or unbalance of
the phases between the interface and/or the test points. De-
tection is by means of a luminous indicator.
The recommended phase comparator of the VDS is the PCM-
HR type, made by Maxeta. It consists of a 1.4 m long test
Phase sequence test
cable.
34
17. ADDITIONAL EQUIPMENT
17.1 LOW-VOLTAGE CONNECTIONS
Auxiliary contacts (2NO+2NC) can be supplied to indicate
switch positions on all switches/breakers. Access to the
low-voltage connections is obtained by removing the top
front panel. A shunt trip coil (AC or DC) can be fitted on the
transformer switch/breaker.
35
18. CABLE TESTING 18.1 PROCEDURE FOR SWITCHGEAR WITH TEST
Cable testing and locating cable faults is preformed in POINTS
three ways: 1. Open switch disconnector
1. Directly on the testing points if they are fitted on the unit. 2. Check voltage status
2.1 Directly on the cable connectors with the cable connected 3. If voltage is not present, close earthing switch.
to the switchgear. 4.Connect the testing equipment on top of the testing points
2.2 Cable connector dismounted from the switchgear. which hold the earth bar (B).
5. Remove the earth triangle and perform the test. Respect
CAUTION maximum test voltage
Cable testing must be carried out in accordance levels as detailed in table below.
with the cable manufacturers recommended 6. Refit the earth triangle. Tightening torque: 25 Nm
practice. 7. Disconnect test equipment
DANGER
Remember that the cable has two ends. Both ends
of the cable needs to be isolated. This is typically
done by opening the disconnectors of SafeRing
SafePlus switchgears connected to the cable.
Free end of the tested cable needs to be secured
against accidental access.
CAUTION
Sometimes cable testing through the busbar of the
switchgear is preferred. This way several sections
of cable can be tested at the same time. This is
feasable, but remember following limitations:
DC and VLF voltages must not be applied to
voltage transformers and surge arresters.
Maximum cable test voltages when testing cables using the cable test points of the switchgear
Rated voltage of the switchgear Ur (kV rms) 12kV 17,5kV 24kV Time
Power frequency cable test voltage Uct(ac) (kV rms) 12kV 17,5kV 24kV 15 min.
DC cable test voltage Uct(dc) (kV peak) 24kV 34,8kV 40kV 15 min.
VLF cable test voltage (Sine-wave, 0,1Hz) Uct(VLF) (kV rms) 18kV 26,1kV 28kV 15 min.
VLF cable test voltage (Cosine-rectangular, 0,1Hz Uct(VLF) (kV peak) 25,5kV 36,9kV 40kV 15 min.
36
18.2 PROCEDURE FOR TESTING DIRECTLY ON THE 18.3 PROCEDURE FOR TESTING DIRECTLY ON THE
CABLE CONNECTOR WITH THE CABLE CONNECTED TO CABLE CONNECTOR WITH THE CABLE DISCONNECTED
THE SWITCHGEAR FROM THE SWITCHGEAR
1. Open switch disconnector 1. Open switch disconnector
2. Check voltage status 2. Check voltage status
3. If voltage is not present, close earthing switch. 3. If voltage is not present, close earthing switch.
4. Open cable compartment cover 4. Open cable compartment cover
5. Connect test rod or test lead to cable connector, keeping 5. Remove cable connector from the switchgear.
the cable connected to the switchgear. 6. Connect test rod or test lead to cable connector.
6. Open earthing switch and perform the test. 7. Perform the test respecting maximum test voltage levels as
Respect maximum test voltage levels as detailed in table detailed in instructions from cable supplier and cable con-
below. nector supplier.
7. Close the earthing switch. When the cables are disconnected at both ends the cable
8. Disconnect the test equipment. testing is independent from the switchgear. Procedures and
9. Complete the cable connector with insulating plugs. test values are determined by the cable, cable terminations
10. Refit cable compartment cover. and test equipment. Test procedure and methods must
follow recommendations and limitations related to the
cable, cable terminations and test equipment.
8. Disconnect test equipment
9. Refit cable connector to switchgear.
10. Refit cable compartment cover.
Maximum cable test voltages when testing directly on the cable connector with the cable connected to the switchgear
Rated voltage of the switchgear Ur (kV rms) 12kV 17,5kV 24kV Time
Power frequency cable test voltage Uct(ac) (kV rms) 12kV 17,5kV 24kV 15 min.
DC cable test voltage Uct(dc) (kV peak) 24kV 34,8kV 48kV 15 min.
VLF cable test voltage (Sine-wave, 0,1Hz) Uct(VLF) (kV rms) 18kV 26,1kV 36kV 15 min.
VLF cable test voltage (Cosine-rectangular, 0,1Hz Uct(VLF) (kV peak) 25,5kV 36,9kV 51kV 15 min.
37
19 SERVICE AND MAINTENANCE 19.2 MAINTENANCE INTERVALS
19.1 GENERAL WARNINGS AND CAUTIONS We recommend carrying out the maintenance work at the
following intervals:
WARNING
Pay attention to the following safety warnings: Activity performed According to section Time interval in years
Preparing the switchgear for safe assembly Inspection 19.3 5 2)
1. For each case, set safe working conditions with Service 19.4 As required 3)
38
No discharge should occur on the surfaces of equipment at
the operating voltage. This can, for example, be detected by
characteristic noises, a clearly perceptible smell of ozone, or
visible glowing in the dark.
NOTE
Should partial discharges occur as a result of
condensation, application of a thin silicone film
over the surface concerned is often effective as a
temporary remedy. It is advisable to ask the ABB
after-sales service department for advice regarding
permanent solutions to this uncommon type of
problem.
REPAIR MEASURES
If any irregular conditions are detected, appropriate servicing
or repair measures must be taken.
19.4 SERVICING
INSTRUCTIONS
If the need for servicing measures is established during the
course of an inspection, proceed as follows:
1. Clean all parts (e.g motors and mechanisms) with a
vacuum cleaner and visually inspect them. Clean the
surfaces in general:
Lightly settled dry dust deposits: clean with a soft dry
cloth.
2. Perform a closing/opening operation on all disconnectors
and circuit-breakers, fuse switches, and the earthing swit-
ches.
3. Connect the auxiliary control voltage, but ensure that no
remote signals can activate the components. Perform one
electrical operation sequence on all motor-operated de-
vices and tripping mechanisms.
4. For maintenance of gas-pressure, follow gas-chapter for
further instructions.
5. Completely remove all rust from damaged paint work areas
on steel sheet and other steel parts by mechanical means,
e.g. with a wire brush, and apply appropriate anti-corrosion
treatment.
19.5 REPAIRS
NOTE
If switchgear is damaged, contact ABB to evaluate
necessary repairs. Some advanced reparations/
operations should be carried out only by ABB
service personnel.
CAUTION
Follow the maintenance instructions in the manuals
for the relative components.
39
20. ENVIRONMENTAL CERTIFICATION
20.1 LIFE EXPECTANCY OF PRODUCT
less than 0.1 % per annum. Referring to the reference-pressu-
The product is developed in compliance with the requirements
re of 1.4 bar, the switchgear will maintain gas-tightness and a
denoted by IEC 62271-200. The design incorporates a life
gas-pressure better than 1.3 bar* throughout its designed life
span under indoor service conditions exceeding 30 years (IEC
span.
62271-200 annex GG).
*) at 20oC.
The switchgear is gas-tight with an expected diffusion rate of
**) All figures are collected from CCF 3-way unit with fuse canisters
20.3 END-OF-LIFE
ABB AS, Power Products Division, is committed to the pro- We also recommend ABBs website : http://www.abb.com/sf6
tection of the environment and adhere to ISO 14001 stan-
dards. It is our obligation to facilitate end-of-life recycling for ABB AS, Electrification Products division in Skien is equipped
our products. to reclaim SF6 gas from discarded switchgears.
40
Contact us
For more information please contact: Text and illustrations are not