Vous êtes sur la page 1sur 34

CHAPTER 5

EXHAUST SYSTEMS
Note: Portions of this chapter have been reproduced in their entirety from NFPA 96-1999.

501.0 Scope. structural framing, roofs, roof ceilings, floors, and


This chapter includes requirements for environmental floor-ceiling assemblies continuously enclosing a
air ducts, product-conveying systems, and grease duct on four sides where one or more sides
commercial hoods and kitchen ventilation. require protection per Section 507.2.
COMBUSTIBLE MATERIAL. Material subject to an
increase in combustibility or flame-spread rating
Part I Environmental Air Ducts and Product-
beyond the limits established in the definition of
Conveying Systems
Limited-Combustible Material.
COMMERCIAL FOOD HEAT-PROCESSING
502.0 Definitions. EQUIPMENT. Equipment used in a food
For the purposes of this chapter, the following establishment for heat-processing food or utensils
definitions apply: and that produces grease vapors, steam, fumes,
ACCESS PANEL. A closure device used to cover an smoke, or odors that are required to be removed
opening into a duct, an enclosure, equipment, or an through a local exhaust ventilation system.
appurtenance. COMPENSATING HOOD. A hood that has an
AIR INTAKES. An opening in a building's envelope outside-air supply with air delivered below or
whose purpose is to allow outside air to be drawn within the hood. When makeup air is diffused
into the structure to replace inside air that is directly into the exhaust within the hood cavity, it
removed by exhaust systems or to improve the becomes a short-circuit hood.
quality of the inside air by providing a source of air CONCEALED SPACES. That portion(s) of a building
having a lower concentration of odors, suspended behind walls, over suspended ceilings, in pipe chases,
particles, or heating content. attics, and elsewhere whose size might normally
AIR POLLUTION CONTROL DEVICES. Equipment range from 1-3/4 inch (44.45 mm) stud spaces to
and devices used for the purpose of cleaning air eight (8) foot (2.44 m) interstitial truss spaces and that
passing through them or by them in such a manner as might contain combustible materials such as building
to reduce or remove the impurities contained therein. structural members, thermal and/or electrical
APPURTENANCE. An accessory or a subordinate insulation, and ducting. Such spaces have sometimes
part that enables the primary device to perform or been used as HVAC plenum chambers.
improve its intended function. CONTINUOUS ENCLOSURE. A recognized architec-
AUTOMATIC. That which provides a function tural or mechanical component of a building having a
without the necessity of human intervention. [NFPA fire resistance rating as required for the structure and
96: 3.3.6] whose purpose is to enclose the vapor removal duct
for its full length to its termination point outside the
BAFFLE PLATE. An object placed in or near an
structure without any portion of the enclosure having
appliance to change the direction or retard the flow
of air, air-fuel mixtures, or flue gases. a fire resistance rating less than the required value.
CERTIFIED. A formally stated recognition and CONTINUOUS WELD. A metal-joining method that
approval of an acceptable level of competency, produces a product without visible interruption or
acceptable to the Authority Having Jurisdiction. variation in quality. For the purpose of the definition,
[NFPA 96 3.3.9] it specifically includes the exhaust compartment of
hoods and welded joints of exhaust ducts, yet
CLASSIFIED. See Listed.
specifically does not include filter support frames or
CLEARLY IDENTIFIED. Capable of being appendages inside hoods.
recognized by a person of normal vision without
causing uncertainty and indecisiveness about the COOKING APPLIANCE FLUE OUTLET. The
location or operating process of the identified item. opening or openings in a cooking device where
vapors, combustion gases, or both leave the cooking
CLOSED COMBUSTIBLE CONSTRUCTION.
device. There might or might not be ductwork
Combustible building construction, including walls,
attached to this opening.

59
502.0 2007 CALIFORNIA MECHANICAL CODE

DAMPER. A valve or plate within a duct or its FUME INCINERATORS. Devices utilizing intense
terminal components for controlling draft or the flow heat or fire to break down and/or oxidize vapors
of gases, including air. and odors contained in gases or air being exhausted
DETECTION DEVICES. Electrical, pneumatic, into the atmosphere.
thermal, mechanical, or optical sensing instruments, FUSIBLE LINK. A form of fixed-temperature heat-
or subcomponents of such instruments, whose detecting device sometimes employed to restrain the
purpose is to cause an automatic action upon the operation of an electrical or mechanical control until
occurrence of some preselected event. In the context its designed temperature is reached. Such devices are
of this document, the event in question could be to be replaced following each operation.
excessive temperature or flame, and the action could GREASE. Rendered animal fat, vegetable shortening,
be the operation of a fire-extinguishing system. and other such oily matter used for the purposes of
DIPS. Depression or cuplike places in horizontal and resulting from cooking and/or preparing foods.
duct runs in which liquids could accumulate. Grease might be liberated and entrained with exhaust
DISCHARGE. The final portion of a duct or pipe air or might be visible as a liquid or solid.
where the product being conveyed is emptied or GREASE DUCTS. A containment system for the
released from confinement; the termination point of transportation of air and grease vapors that is designed
the pipe or duct. and installed to reduce the possibility of the
EASILY ACCESSIBLE. See Accessible, Readily in accumulation of combustible condensation and the
Section 203.0, Chapter 2. occurrence of damage if a fire occurs within the system.
ENVIRONMENTAL AIR DUCT. Ducting used for GREASE FILTER. A removable component of the
conveying air at temperatures not exceeding 250F grease removal system designed to capture grease
(121C) to or from occupied areas of any occupancy and direct it to a safe collection point before it enters
through other than heating or air-conditioning a duct system. Filters are expected to minimize the
projection of flames downstream when attacked by
systems, such as ventilation for human usage,
flame on the upstream side and are expected to
domestic kitchen range exhaust, bathroom exhaust
maintain their strength, shape, and integrity when
ducts, and domestic-type clothes dryer exhaust ducts.
exposed to the anticipated rough handling, cleaning,
FACTORY-BUILT GREASE ENCLOSURES. A listed and service found in the field.
factory-built grease duct enclosure system evaluated
GREASE FILTER, MESHTYPE. A general-purpose
for reduced clearances to combustibles, and as an
air filter designed to collect and retain lint and grease
alternative to a duct with its fire-rated enclosure.
from the air passing through it. This type of filter is
FIELD-APPLIED GREASE DUCT ENCLOSURES. not tested, listed, or acceptable for commercial
A listed system evaluated for reduced clearances to cooking operations due to the increased fire hazard.
combustibles, and as an alternative to a duct with its
GREASE REMOVAL DEVICES. A system of
fire-rated enclosure.
components designed for and intended to process
FLAMMABLE VAPOR OR FUMES. The concen- vapors, gases, and/or air as it is drawn through such
tration of flammable constituents in air that exceeds devices by collecting the airborne grease particles
twenty-five percent (25%) of its lower flammability and concentrating them for further action at some
limit (LFL). future time, leaving the exiting air with a lower
FIRE BARRIER WALL. A wall assembly complying amount of combustible matter.
with the requirements of NFPA 221, Standard for GREASETIGHT. Constructed and performing in
Fire Walls and Fire Barrier Walls, having a fire such a manner as not to permit the passage of any
resistance rating of four (4) hours. grease under normal cooking conditions.
FIRE PARTITION. An interior wall or partition of a HIGH BROILER. See Upright Broiler.
building that separates two areas and serves to restrict HIGH LIMIT CONTROL. An operating device
the spread of fire but does not qualify as a fire wall. installed in and serving as an integral component of
FIRE RESISTANCE RATING. A relative value in a deep-fat fryer. Its purpose is the secondary
minutes or hours assigned to materials or assemblies limitation of temperature allowed by the cooking
that have withstood a fire exposure as established in operation and, if that temperature is exceeded, the
accordance with NFPA 251, Standard Methods of automatic interruption of the thermal energy input.
Tests of Fire Endurance of Building Construction HOOD. An air-intake device connected to a mechanical
and Materials. exhaust system for collecting and removing grease,

60
EXHAUST SYSTEMS 502.0

vapors, fumes, smoke, steam, heat, or odors from LIQUIDTIGHT. Constructed and performing in such a
commercial food heat-processing equipment. manner as not to permit the passage of any liquid at any
Fixed Baffle. A listed unitary exhaust hood temperature.
design where the grease removal device is a LISTED. Equipment, materials, or services included
nonremovable assembly that contains an in a list published by an organization that is
integral fire-activated water-wash fire- acceptable to the Authority Having Jurisdiction and
extinguishing system listed for this purpose. concerned with evaluation of products or services,
Type I is a kitchen hood for collecting and that maintains periodic inspection of production of
removing grease and smoke. listed equipment or materials or periodic evaluation
of services, and whose listing states that the
Type II is a general kitchen hood for collecting
equipment, material, or service meets identified
and removing steam, vapor, heat, or odors.
standards or has been tested and found suitable for a
INTERCONNECTED. Mutually assembled to specified purpose.
another component in such a manner that the
operation of one directly affects the other or that the NONCOMBUSTIBLE MATERIAL. A material that,
contents of one specific duct system are allowed to in the form in which it is used and under the
encounter or contact the products being moved by conditions anticipated, will not ignite, burn, support
another duct system. combustion, or release flammable vapors when
subjected to fire or heat. Materials that are reported
LABELED. Equipment or materials to which has
as passing ASTM E 136, Standard Test Method for
been attached a label, symbol, or other identifying
Behavior of Materials in a Vertical Tube Furnace at
mark of an organization that is acceptable to the
750C, shall be considered noncombustible materials.
Authority Having Jurisdiction and concerned with
product evaluation, that maintains periodic OPEN COMBUSTIBLE CONSTRUCTION. Combustible
inspection of production of labeled equipment or building constructions including wall, structural
materials, and by whose labeling the manufacturer framing, roof, roof ceiling, floor, and floor ceiling
indicates compliance with appropriate standards or assemblies adjacent to a grease duct on three or
performance in a specified manner. fewer sides where one or more sides require
protection per Section 507.2.
LIMITED-COMBUSTIBLE MATERIAL. A building
construction material that does not comply with the PITCHED. To be fixed or set at a desired angle or
definition of noncombustible material, that, in the inclination.
form in which it is used, has a potential heat value PRODUCT-CONVEYING DUCT. Ducting used for
not exceeding 3,500 Btu/lb. (8141 kJ/kg)(see NFPA conveying solid particulates, such as refuse, dust,
259, Standard Test Method for Potential Heat of fumes, and smoke; liquid particulate matter, such as
Building Materials), and that complies with either of spray residue, mists, and fogs; vapors, such as
the following (A) or (B). Materials subject to an vapors from flammable or corrosive liquids; noxious
increase in combustibility or flame-spread rating and toxic gases; and air at temperatures exceeding
beyond the limits herein established through the 250F (121C).
effects of age, moisture, or other atmospheric QUALIFIED. A competent and capable person or
conditions shall be considered combustible. company that has met the requirements and training
(A) Materials having a structural base of for a given field acceptable to the Authority Having
noncombustible material, with a surfacing Jurisdiction. [NFPA 96: 3.3.37]
not exceeding a thickness of 1/8 inch (3.2 RECIRCULATING SYSTEMS. Systems for control of
mm), and with a flame-spread rating not smoke or grease-laden vapors from commercial
greater than fifty (50). cooking equipment that do not exhaust to the outside.
(B) Materials in the form and thickness used, REMOVABLE. Capable of being transferred to
other than as described in (A), having neither another location with a limited application of effort
a flame-spread rating greater than twenty- and tools.
five (25) nor evidence of continued progressive REPLACEMENT AIR. See Air, Makeup in Section
combustion and of such composition that 203.0, Chapter 2.
surfaces that would be exposed by cutting
through the material on any plane would SALAMANDER BROILER. See Upright Broiler.
have neither a flame-spread rating greater SHALL. Indicates a mandatory requirement.
than twenty-five (25) nor evidence of SINGLE HAZARD AREA. As considered in the
continued progressive combustion. applicable extinguishing system standard (see

61
502.0 503.2 2007 CALIFORNIA MECHANICAL CODE

Section 513.2) or as determined by the Authority Class 1. Ducts conveying nonabrasives, such as
Having Jurisdiction. smoke, spray, mists, fogs, noncorrosive fumes
SOLID COOKING FUEL. Any solid, organic, and gases, light fine dusts, or powders.
consumable fuel such as briquettes, mesquite, Class 2. Ducts conveying moderately abrasive
hardwood, or charcoal. particulate in light concentrations, such as
SOLID-FUEL COOKING EQUIPMENT. Cooking sawdust and grain dust, and buffing and
equipment that is fired with solid cooking fuel. This polishing dust.
equipment includes ovens, tandoori charcoal pots, Class 3. Ducts conveying Class 2 materials in
grills, broilers, rotisseries, barbecue pits, or any other high concentrations and highly abrasive
type of cooking equipment that derives all or part of materials in low concentrations, such as
its heat source from the burning of solid cooking fuel. manganese, steel chips, and coke.
SOLVENT. A substance (usually liquid) capable of Class 4. Ducts conveying highly abrasive
dissolving or dispersing another substance; a material in high concentrations.
chemical compound designed and used to convert Class 5. Ducts conveying corrosives, such as
solidified grease into a liquid or semiliquid state in acid vapors.
order to facilitate a cleaning operation.
SPARK ARRESTER. A device or method that 503.0 Motors, Fans, and Filters.
minimizes the passage of airborne sparks and
embers into a plenum, duct, and flue. 503.1 General. Motors and fans shall be sized to
provide the required air movement. Motors in areas
STANDARD. A document, the main text of which that contain flammable vapors or dusts shall be of a
contains only mandatory provisions using the word type approved for such environments. A manually
shall to indicate requirements and that is in a form operated remote control installed at an approved
generally suitable for mandatory reference by another location shall be provided to shut off fans or blowers
standard or code or for adoption into law. in flammable vapor or dust systems. Electrical
Nonmandatory provisions shall be located in an equipment used in operations that generate explosive
appendix, footnote, or fine-print note and are not to be or flammable vapors, fumes, or dusts shall be
considered a part of the requirements of a standard. interlocked with the ventilation system so that the
TERMINATION. The final or intended end portion of equipment cannot be operated unless the ventilation
a duct system that is designed and functions to fulfill fans are in operation. Motors for fans used to convey
the obligations of the system in a satisfactory manner. flammable vapors or dusts shall be located outside
THERMAL RECOVERY UNIT. A device or series of the duct or shall be protected with approved shields
devices whose purpose is to reclaim only the heat and dustproofing. Motors and fans shall be accessible
content of air, vapors, gases, or fluids that are being for servicing and maintenance.
expelled through the exhaust system and to transfer 503.2 Fans. Parts of fans in contact with explosive or
the thermal energy so reclaimed to a location flammable vapors, fumes, or dusts shall be of
whereby a useful purpose can be served. nonferrous or nonsparking materials or their casing
TRAINED. A person who has become proficient in shall be lined or constructed of such material. When
performing a skill reliably and safely through the size and hardness of materials passing through a
instruction and practice/field experience acceptable fan could produce a spark, both the fan and the
to the Authority Having Jurisdiction. [NFPA 96 casing shall be of nonsparking materials. When fans
3.3.47] are required to be spark-resistant, their bearings
TRAP. A cuplike or U-shaped configuration located shall not be within the airstream, and all parts of the
on the inside of a duct system component where fan shall be grounded. Fans in systems handling
liquids can accumulate. materials that are likely to clog the blades, and fans
in buffing or woodworking exhaust systems, shall be
UPRIGHT BROILER. An appliance used in the of the radial-blade or tube-axial type.
preparation of food whereby foods are exposed to
intense radiant heat, and perhaps to convective heat, Equipment used to exhaust explosive or
with the food and the radiant source not limited to a flammable vapors, fumes, or dusts shall bear an
horizontal mode. identification plate stating the ventilation rate for
which the system was designed.
502.1 Product-Conveying Ducts Classification.
Fans located in systems conveying corrosives
Product-conveying ducts shall be classified shall be of materials that are resistant to the corrosive
according to their use, as follows: or shall be coated with corrosion-resistant materials.

62
EXHAUST SYSTEMS 503.3 504.5

503.3 Air filters shall be listed units. Liquid adhesive exhaust ducts shall not extend into or through
coatings used on filters shall have a flash point of ducts or plenums.
350F (177C) or higher, as determined by the Fire 504.3.2 Domestic Clothes Dryers. When a
Code standards. compartment or space for a domestic clothes
dryer is provided, a minimum four (4) inch
504.0 Environmental Air Ducts. diameter (102 mm) moisture exhaust duct of
504.1 Makeup and Exhaust-Air Ducts. Environ- approved material shall be installed in
mental air ducts not regulated by other provisions of accordance with this section and Section 504.0.
this code shall comply with this section. Ducts shall When a closet is designed for the installation
be substantially airtight and shall comply with the of a clothes dryer, a minimum opening of 100
provisions of Chapter 6. Exhaust ducts shall not square inches (64,516 mm2) for makeup air shall be
extend into or through ducts or plenums. Exhaust provided in the door or by other approved means.
ducts shall terminate outside the building and shall 504.3.2.1 Domestic Dryer Vents. Domestic
be equipped with back-draft dampers. [For OSHPD clothes dryer moisture exhaust ducts shall
1, 2 & 4] Exception: Back-draft dampers are not required be of metal and shall have smooth interior
when the exhaust fan must operate continuously. surfaces.
Environmental air ducts that have an alternate
Exception: Listed clothes dryer transition
function as a part of an approved smoke-control
system do not require design as Class 1 ducts not more than six (6) feet (1,829 mm)
product-conveying ducts. in length may be used in connection
with domestic dryer exhausts.
504.2 Domestic Range Vents. Ducts used for domestic
kitchen range ventilation shall be of metal and shall Flexible clothes dryer transition
have smooth interior surfaces. Ducts for domestic range ducts shall not be concealed within
hoods shall only serve cooking appliances. construction.
Exception: Ducts for domestic kitchen 504.3.2.2 Length Limitation. Unless
downdraft grill-range ventilation installed under otherwise permitted or required by the dryer
a concrete slab floor may be of approved manufacturers installation instructions and
Schedule 40 PVC provided: approved by the Authority Having
Jurisdiction, domestic dryer moisture
(1) The under-floor trench in which the duct is
exhaust ducts shall not exceed a total
installed shall be completely backfilled with
combined horizontal and vertical length of
sand or gravel.
fourteen (14) feet (4,263 mm), including two
(2) Not more than one (1) inch (25.4 mm) of six (2) 90 degree (1.57 rad) elbows. Two (2) feet
(6) inch diameter (152 mm) PVC coupling (610 mm) shall be deducted for each 90
may protrude above the concrete floor surface. degree (1.57 rad) elbow in excess of two.
(3) PVC pipe joints shall be solvent cemented to 504.3.3 Commercial Clothes Dryers. Commer-
provided an air and grease-tight duct. cial dryer exhaust ducts shall be installed in
(4) The duct shall terminate above grade accordance with their listings. The installation of
outside the building and shall be equipped commercial clothes dryer exhaust ducts shall
with a back-draft damper. comply with the appliance manufacturers
504.3 Clothes Dryers. installation instructions.
504.3.1 Moisture Exhaust Ducts. Moisture 504.4 Heat (Energy) Recovery Ventilators.
exhaust ducts shall terminate on the outside of 504.4.1 Heat (energy) recovery ventilators shall
the building and shall be equipped with a back- be installed in accordance with their listings and
draft damper. Screens shall not be installed at the comply with the appliance manufacturers
duct termination. Ducts for exhausting clothes installation instructions. Heat (energy) recovery
dryers shall not be connected or installed with ventilator ducts shall comply with the
sheet metal screws or other fasteners that will provisions of Chapter 6.
obstruct the flow. Clothes dryer moisture exhaust
504.5 Termination of Environmental Air Ducts.
ducts shall not be connected to a gas vent
Environmental air duct exhaust: three (3) feet (914
connector, gas vent, or chimney, and shall only
mm) from property line; three (3) feet (914 mm) from
serve clothes dryers. Clothes dryer moisture
openings into the building.

63
504.6 Table 5-1 2007 CALIFORNIA MECHANICAL CODE

504.6 Gypsum Wallboard Ducts. Bathroom and Standard on Explosion Prevention Systems
laundry room exhaust ducts may be of gypsum in Chapter 17, using one or more of the
wallboard subject to the limitations of Section 602.1. following techniques:
(a) Combustible concentration reduction
505.0 Design of Product-Conveying Ventilation (b) Oxidant concentration reduction
Systems. (c) Deflagration suppression
505.1 General. A mechanical ventilation or exhaust (d) Deflagration pressure containment
system shall be installed to control, capture, and Separate and distinct systems shall be provided for
remove emissions generated from product use or incompatible materials.
handling when required by the Building Code or Contaminated air shall not be recirculated to
Fire Code and when such emissions result in a occupied areas unless contaminants have been
hazard to life or property. The design of the system removed. Air contaminated with explosive or
shall be such that the emissions are confined to the flammable vapors, fumes, or dusts; flammable or toxic
area in which they are generated by air currents, gases; or radioactive material shall not be recirculated.
hoods, or enclosures and shall be exhausted by a 505.2 Minimum Velocities and Circulation. The
duct system to a safe location or treated by removing velocity and circulation of air in work areas shall be
contaminants. Ducts conveying explosives or such that contaminants are captured by an airstream
flammable vapors, fumes, or dusts shall extend at the area where the emissions are generated and
directly to the exterior of the building without conveyed into a product-conveying duct system.
entering other spaces and shall not extend into or Mixtures within work areas where contaminants are
through ducts and plenums. generated shall be diluted below 25 percent of their
lower explosive limit or lower flammability limit
Exception: Ducts conveying vapor or fumes with air that does not contain other contaminants.
having flammable constituents less than 25 The velocity of air within the duct shall be not less
percent of their lower flammability limit (LFL) than set forth in Table 5-1.
may pass through other spaces. Systems for removal of vapors, gases, and smoke
505.1.1 Incompatible materials shall not be shall be designed by the constant velocity or equal
conveyed in the same system. friction methods. Systems conveying particulate matter
shall be designed employing the constant velocity
505.1.2 In systems conveying flammable
method. Systems conveying explosive or radioactive
vapors, gases, or mists, the concentration shall
materials shall be prebalanced through duct sizing.
not exceed 25 percent of the lower flammability Other systems may be designed with balancing devices
limit (LFL). such as dampers. Dampers provided to balance airflow
Exception: Higher concentrations shall be shall be provided with securely fixed minimum-
permitted if the exhaust system is designed position blocking devices to prevent restricting flow
and protected in accordance with the below the required volume or velocity.

TABLE 5-1
Minimum Conveying Velocities

Feet per Minute (m/s)

Vapors, gases, smoke, fumes Any

Fine light dusts, such as cotton, lint, and wood flour (100 mesh and under) 2,000 (10.2)

Dry dusts; powders, such as fine rubber molding power, soap dust 2,5001 (12.7)1

Industrial dusts
Average dusts, such as sawdust, grinding dust, coal dust 3,500 (17.8)
Heavy dusts, such as metal turnings, lead dusts 4,000 (20.3)
Moist dusts and chips, such as lead dust with chips, sticky buffing lint,
quick-lime dust 4,500 (22.9)

Note:
1
The velocity for aluminum and magnesium powder shall be not less than 4,000 feet per minute (20.3 m/s).

64
EXHAUST SYSTEMS 505.3 506.2

505.3 Makeup Air. Makeup air shall be provided to materials may be used when it is shown that
replenish air exhausted by the ventilation system. these materials will be equivalent to metal
Makeup-air intakes shall be located so as to avoid ducts installed in accordance with this
recirculation of contaminated air within enclosures. chapter.
505.4 Hoods and Enclosures. Hoods and (2) Ducts serving a Class 5 system may be
enclosures shall be used when contaminants constructed of approved nonmetallic
originate in a concentrated area. The design of the material when the corrosive characteristics
hood or enclosure shall be such that air currents of the material being conveyed make a
created by the exhaust systems will capture the metal system unsuitable and when the
contaminants and transport them directly to the mixture being conveyed is nonflammable.
exhaust duct. The volume of air shall be sufficient to Approved nonmetallic material shall be
dilute explosive or flammable vapors, fumes, or either a listed product having a flame-spread
dusts as set forth in Section 505.2. Hoods of steel index of twenty-five (25) or less and a smoke-
shall have a base metal thickness not less than 0.027 developed rating of fifty (50) or less on both
inch (0.69 mm) (No. 22 gauge) for Class 1 and Class 5 inside and outside surfaces without evidence
metal duct systems; 0.033 inch (0.84 mm) (No. 20 of continued progressive combustion, or
gauge) for hoods serving a Class 2 duct system; 0.044 shall have a flame-spread index of twenty-
inch (1.12 mm) (No. 18 gauge) for hoods serving a five (25) or less and shall be installed with
Class 3 duct system; and 0.068 inch (1.73 mm) (No. an automatic fire-sprinkler protection system
14 gauge) for hoods serving a Class 4 duct system. inside the duct.
Approved nonmetallic hoods and duct systems
(3) Ducts used in central vacuum cleaning
may be used for Class 5 corrosive systems when the
systems within a dwelling unit shall be
corrosive mixture is nonflammable. Metal hoods
constructed of materials in compliance with
used with Class 5 duct systems shall be protected
with suitable corrosion-resistant material. Edges of the applicable standards referenced in
hoods shall be rounded. The minimum clearance Chapter 17. Penetrations of fire walls or
between hoods and combustible construction shall floor-ceiling or roof-ceiling assemblies shall
be the clearance required by the duct system. comply with the Building Code.
Copper or ferrous pipes or conduits
extending from within the separation
505.12 Pharmacies Compounding Area of

The pharmacy shall have a designated area for the between a garage and dwelling unit to the
Parenteral Solutions. [CA Board of Pharmacy]

preparation of sterile products for dispensing which shall: central vacuuming unit may be used.
1. Be ventilated in a manner not interfering with Aluminum ducts shall not be used in systems
laminar air flow. conveying flammable vapors, fumes, or explosive
Note: For additional pharmacy building standard dusts, nor in Class 2, 3, or 4 systems. Galvanized
requirements, see Chapter 12, California Building steel and aluminum ducts shall not be used when the
Code. temperature of the material being conveyed exceeds
400F (205C).
safety cabinet. [CA Board of Pharmacy] In
505.12.1 Pharmacies laminar flow biological
Metal ducts used in Class 5 systems that are
all pharmacies preparing parenteral cytotoxic agents, not resistant to the corrosiveness of the product shall
all compounding shall be conducted within a certified be protected with appropriate corrosion-resistant
Class II Type A or Class II Type B vertical laminar material.
airflow hood with bag in bag out design. The
506.2 Construction. Ducts used for conveying
pharmacy must ensure that contaminated air plenums
that are under positive air pressure are leak tight. products shall be of substantial airtight construction
and shall not have openings other than those
Note: For additional pharmacy building standard required for operation and maintenance of the
requirements, see Chapter 12, California Building Code.
system. Ducts constructed of steel shall comply with
Table 5-5 or 5-6.
506.0 Product-Conveying Ducts. Exceptions:
506.1 Materials. Materials used in product- (1) Class 1 product-conveying ducts that
conveying duct systems shall be suitable for the operate at less than four (4) inches water
intended use and shall be of metal. column (995.6 Pa) negative pressure and
Exceptions: convey noncorrosive, nonflammable, and
(1) Asbestos-cement, concrete, clay, or ceramic nonexplosive materials at temperatures not

65
506.2 506.7 2007 CALIFORNIA MECHANICAL CODE

exceeding 250F (121C) may be constructed provided with deflagration venting to a safe outside
in accordance with Tables 6-1, 6-2, 6-3, 6-4, location.
6-5, 6-7, 6-8, or, with prior approval, UMC 506.5 Supports. Spacing of supports for ducts shall
Standard No. 6-2. not exceed twelve (12) feet (3,658 mm) for eight (8)
(2) Ducts used in central vacuuming systems inch (203 mm) ducts nor twenty (20) feet (6,096 mm)
within a dwelling unit shall be constructed for larger ducts, unless justified by the design.
of materials in compliance with the 506.5.1 Duct supports shall be designed to
applicable standards referenced in Chapter
carry the weight of the duct half filled with
17. Penetrations of fire-resistive walls, or
material. Where sprinkler protection is provided
floor-ceiling or roof-ceiling assemblies shall
in the duct, the hangers design shall include the
comply with the Building Code. Copper or
weight of the duct half filled with water or with
ferrous pipes or conduit extending from
the material being conveyed, whichever has the
within the separation between a garage and
higher density. Loads shall not be placed on
dwelling unit to the central vacuum unit
connecting equipment.
may be used.
The use of rectangular ducts conveying Exception: Where adequate drainage is
particulates shall be subject to approval of the provided, the weight of the water shall not
building official. The design of rectangular ducts require consideration.
shall consider the adhesiveness and buildup of 506.5.2 Hangers and supports exposed to
products being conveyed within the duct. corrosive atmospheres shall be Type 316 SS or
Aluminum construction may be used in Class 1 equivalent.
duct systems only. The thickness of aluminum ducts 506.5.3 To avoid vibration and stress on the
shall be at least two Brown and Sharpe gauges duct, hangers and supports shall be securely
thicker than the gauges required for steel ducts set fastened to the building or structure.
forth in Tables 5-5 and 5-6. 506.5.4 Hangers and supports shall be designed
506.3 Fittings. Fittings in Class 2, 3, and 4 systems to allow for expansion and contraction. [NFPA
shall be not less than two gauges thicker than the 91:2.5.1 through 2.5.4]
thickness required for straight runs. Flexible metallic
506.6 Fire Protection. Sprinklers or other
duct may be used for connecting ductwork to
fire-protection devices shall be installed within
vibrating equipment. Duct systems subject to wide
ducts having a cross-sectional dimension exceeding
temperature fluctuations shall be provided with
ten (10) inches (254 mm) when the duct conveys
expansion joints.
flammable vapors or fumes. Sprinklers shall be
Branches shall connect to main ducts at the large installed at twelve (12) foot (3,658 mm) intervals in
end of transitions at an angle not exceeding forty- horizontal ducts and at changes in direction. In
five (45) degrees (0.79 rad). vertical runs, sprinklers shall be installed at the top
Except for ducts used to convey noncorrosive and at alternate floor levels.
vapors with no particulate, accessible cleanouts shall
506.7 Duct Clearances.
be provided at ten (10) foot (3,048 mm) intervals and
at changes in direction. Access openings shall also be 506.7.1 All ductwork and system components
provided for access to sprinklers and other handling combustible material and operating at
equipment within the duct that require servicing. less than 140F (60C) shall have a clearance of
not less than 18 inches (46 cm) from combustible
506.4 Explosion Venting. Ducts conveying
construction or any combustible material.
explosive dusts shall have explosion vents, openings
protected by antiflashback swing valves, or rupture Exception No. 1: When the ductwork
diaphragms. Openings to relieve explosive forces system is equipped with an approved
shall be located outside the building. When relief automatic extinguishing system designed
devices cannot provide sufficient pressure relief, for the specific hazard, the clearance shall
ductwork shall be designed to withstand an internal be permitted to be reduced to six (6)
pressure of not less than 100 pounds per square inch inches (15 cm) from combustible materials
(689 kPa). and 1/2 inch (13 mm) from combustible
If a room or building contains a dust explosion construction.
hazard that is external to protected equipment, as Exception No. 2: When the combustible
defined in 2.2.3.1 of NFPA 654, such areas shall be material and construction is protected

66
EXHAUST SYSTEMS Table 5-2 506.7

TABLE 5-2
Reduction of Duct Clearance with Specified Forms of Protection

Clearance reduction applied to and covering all combustile surfaces Minimum Allowable Reduction in Clearance (%)
with the distance specified as required clearance with no protection
in 506.7.2

Form of Protection As Wall Protector As Ceiling Protector

(a) 3-1/2 in. (90 mm) thick masonry wall without ventilated airspace 33
(b) 1/2 in. (13 mm) thick noncombustile insulation board over 1 in. 50 33
(25.4 mm) glass fiber or mineral wool batts without ventilated airspace
(c) 0.024 in. (0.61 mm) (No. 24 gauge) sheet metal over 1 in. (25.4 mm) glass 66 66
fiber or mineral wool batts reinforced with wire, or equivalent, on rear face
with at least a 1 in. (25.4 mm) air gap
(d) 3-1/2 in (90 mm) thick masonry wall with at least a 1 in (25.4 mm) air gap 66
(e) 0.024 in. (0.61 mm) (No. 24 gauge) sheet metal with at least a 1 in. (25.4 mm) 66 50
air gap
(f) 1/2 in. (13 mm) thick noncombustible insulation board with at least a 1 in. 66 50
(25.4 mm) air gap
(g) 0.024 in. (0.61mm) (No. 24 gauge) sheet metal with ventilated airspace over 66 50
0.024 in. (0.61 mm) (No. 24 gauge) sheet metal with at least a 1 in. (25.4 mm)
air gap
(h) 1 in. (25.4 mm) glass fiber or mineral wool batts sandwiched between two 66 50
sheets 0.024 in. (0.61 mm) (No. 24 gauge) sheet metal with at least a 1 in.
(25.4 mm) air gap

Extent of protection required to reduce clearances from ducts.

by the use of materials or products board) shall have a minimum density of


listed for protection purposes or in eight (8) lb./ft. 3 (3.6 kq/m 3) and have a
accordance with Table 5-2. minimum melting point of 1,500F (816C).
506.7.1.1 Spacers and ties for protection 506.7.1.4 Insulation board used as a part of
materials shall be of noncombustible material a clearance-reduction system shall have a
and shall not be used directly behind the duct. thermal conductivity of 1 Btu in./ft.2 hrF
506.7.1.2 With all clearance reduction (0.14 W/m2 hrC) or less. Insulation board
systems using a ventilated airspace, air shall be formed of noncombustible material.
circulation shall be provided as described in 506.7.1.5 There shall be at least one (1) inch
Table 5-2. There shall be at least one (1) inch (2.5 cm) between the duct and the wall
(2.5 cm) between the wall protector and protector. In no case shall the clearance
combustible walls and ceilings for clearance, between the duct and the wall surface be
reduction systems using a ventilated space. reduced below that shown in Table 5-2.
506.7.1.3 Mineral wool batts (blanket or 506.7.2 Duct systems operating at elevated

67
Table 5-3 2007 CALIFORNIA MECHANICAL CODE

TABLE 5-3
Reduction of Clearances with Specified Forms of Protection

Where the required clearance with no protection from appliance, vent connector, or
single-wall metal pipe is:
36 in. 18 in. 12 in. 9 in. 6 in.
Allowable Clearances with Specified Protection (in.)
Type of protection applied
to and covering all surfaces Use Col. 1 for clearances above appliance or horizontal connector. Use Col. 2 for
of combustible material clearances from appliances, vertical connector, and single-wall metal pipe.
within the distance specified
as the required clearance Sides Sides Sides Sides Sides
with no protection and and and and and
[See Figures 9-1(a) Above Rear Above Rear Above Rear Above Rear Above Rear
through 9-1(c)] Col. 1 Col. 2 Col. 1 Col. 2 Col. 1 Col. 2 Col. 1 Col. 2 Col. 1 Col. 2

(1) 3-1/2 in. thick masonry -- 24 -- 12 -- 9 -- 6 -- 5


wall without ventilated air-
space
(2) 1/2 in. insulation board 24 18 12 9 9 6 6 5 4 3
over 1 in. glass fiber or
mineral wool batts
(3) 0.024 sheet metal over 18 12 9 6 6 4 5 3 3 3
1 in. glass fiber or mineral
wool batts reinforced with
wire on rear face with
ventilated airspace
(4) 3-1/2 in. thick masonry -- 12 -- 6 -- 6 -- 6 -- 6
wall with ventilated air
space
(5) 0.024 sheet metal with 18 12 9 6 6 4 5 3 3 2
ventilated airspace
(6) 1/2 in. thick insulation 18 12 9 6 6 4 5 3 3 3
board with ventilated air-
space
(7) 0.024 sheet metal with 18 12 9 6 6 4 5 3 3 3
ventilated airspace over
0.024 sheet metal with
ventilated airspace
(8) 1 in. glass fiber or 18 12 9 6 6 4 5 3 3 3
mineral wool batts
sandwiched between two
sheets 0.024 sheet metal
with ventilated airspace

For SI units, 1 in. = 25.4 mm.


Notes:
1 Reduction of clearances from combustible materials shall not interfere with combustion air, draft hood clearance and relief, and accessibility of
servicing.
2 All clearances shall be measured from the outer surface of the combustible material to the nearest point on the surface of the appliance, disregarding
any intervening protection applied to the combustible material.
3 Spacers and ties shall be of noncombustible material. No spacer or tie shall be used directly opposite the appliance or connector.
4 Where all clearance reduction systems use a ventilated air space, adequate provision for air circulation shall be provided as described.
[See Figures 9-1(a) through 9-1(c).]
5 There shall be at least 1 in. (25 mm) between clearance reduction systems and combustible walls and ceilings for reduction systems using a ventilated
airspace.
6 Where a wall protector is mounted on a single flat wall away from corners, it shall have a minimum 1 in. (25 mm) air gap. To provide adequate air
circulation, the bottom and top edges, or only the side and top edges, or all edges shall be left open.
7 Mineral wool batts (blanket or board) shall have a minimum density of 8 lb./ft.3 (128 kg/m3) and a minimum melting point of 1500F (816C).
8 Insulation material used as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu in./ft.2 /hr.-F (0.144 W/m-K) or less.
9 There shall be at least 1 in. (25 mm) between the appliance and the protector. In no case shall the clearance between the appliance and the combustible
surface be reduced below that allowed in Table 5-3.
10 All clearances and thicknesses are minimum; larger clearances and thicknesses are acceptable.
11 Listed single-wall connectors shall be installed in accordance with the terms of their listing and the manufacturer's instructions.

68
EXHAUST SYSTEMS 506.7 507.1

temperatures above 140F (60C) shall have Part II Commercial Hoods and Kitchen
clearances from combustible building construc- Ventilation
tion or any combustible material of not less than
eighteen (18) inch (46 cm).
507.0 General Requirements.
506.7.3 Where clearance is reduced by using an
507.1 Cooking equipment used in processes
airspace between the combustible wall and the
producing smoke or grease-laden vapors shall be
wall protector, air circulation shall be provided
equipped with an exhaust system that complies with
by one of the following methods.
all the equipment and performance requirements of
506.7.3.1 Air circulation shall be permitted this standard, and all such equipment and
to be provided by leaving all edges of the performance shall be maintained per this standard
wall protector open with at least a one (1) during all periods of operation of the cooking
inch (2.5 cm) air gap. equipment. Specifically, the following equipment
506.7.3.2 If the wall protector is mounted shall be kept in good working condition:
on a single flat wall away from corners, air (A) Cooking equipment
circulation shall be permitted to be provided
by one of the following: (B) Hoods
(A) Leaving top and bottom edges open (C) Ducts (if applicable)
to circulation by maintaining the one (1) (D) Fans
inch (2.5 cm) air gap. (E) Fire suppression systems
(B) Leaving top and both side edges (F) Special effluent or energy control equipment
open to circulation by maintaining the
All airflows shall be maintained. Maintenance
(1) inch (2.5 cm) air gap.
and repairs shall be performed on all
506.7.3.3 Wall protectors that cover two components at intervals necessary to maintain
walls in a corner shall be permitted to be these conditions.
open at the top and bottom edges with at 507.1.1 All solid-fuel cooking equipment shall
least a one (1) inch (2.5 cm) air gap. [NFPA comply with the requirements of Section 517.0.
91:2.6.1 through 2.6.3.8]
507.1.2 Multiple-tenancy applications shall
506.8 Protection from Physical Damage. Ducts require the concerted cooperation of design,
installed in locations where they are subject to physical installation, operation, and maintenance
damage shall be protected by suitable guards. responsibilities by tenants and by the building
506.9 Exhaust Outlets. Outlets for exhausts that owner.
exceed 600F (315C) shall be in accordance with 507.1.3 All interior surfaces of the exhaust
Table 5-7.
system shall be reasonably accessible for
The termination point for exhaust ducts cleaning and inspection purposes.
discharging to the atmosphere shall be not less than
507.1.4 Cooking equipment used in fixed,
the following:
mobile, or temporary concessions, such as
506.9.1 Ducts conveying explosive or trucks, buses, trailers, pavilions, tents, or any
flammable vapors, fumes, or dusts: thirty form of roofed enclosure, shall comply with this
(30) feet (9,144 mm) from property line; ten standard unless all or part of the installation is
(10) feet (3,048 mm) from openings into the exempted by the Authority Having Jurisdiction.
building, six (6) feet (1,829 mm) from
exterior walls or roofs; thirty (30) feet (9,144 507.1.5 Cooking equipment that has been listed
mm) from combustible walls or openings in accordance with UL 197 or an equivalent
into the building that are in the direction of standard for reduced emissions shall not be
the exhaust discharge; ten (10) feet (3,048 required to be provided with an exhaust system.
mm) above adjoining grade. [NFPA 96: 4.1.1.1]
506.9.2 Other product-conveying outlets: 507.1.6 The listing evaluation of cooking
ten (10) feet (3,048 mm) from property line; equipment covered by section 507.1.5 shall
three (3) feet (914 mm) from exterior wall or demonstrate that the grease discharge at the
roof; ten (10) feet (3,048 mm) from openings exhaust duct of a test hood placed over the
into the building; ten (10) feet (3,048 mm) appliance shall not exceed 5 mg/m3 when
above adjoining grade. operated with a total airflow of 0.236 cubic
meters per second (500 dm). [NFPA 96 4.1.1.2]

69
507.1 507.2 2007 CALIFORNIA MECHANICAL CODE

507.1.7 The responsibility for inspection, product shall be repaired and restored to
maintenance, and cleanliness of the ventilation meet its intended listing or clearance
control and fire protection of the commercial requirements and shall be acceptable to the
cooking operations shall be the ultimate Authority Having Jurisdiction. In the event
responsibility of the owner of the system of a fire within a kitchen exhaust system, the
provided that this responsibility has not been duct and its enclosure (rated shaft, factory-
transferred in written form to a management built grease duct enclosure, or field-applied
company or other party. [NFPA 96 4.1.5] grease duct enclosure) shall be inspected by
507.2 Clearance. qualified personnel to determine whether
the duct and protection method are
507.2.1 Except where enclosures are required,
structurally sound, capable of maintaining
hoods, grease removal devices, exhaust fans,
their fire-protection function, and suitable
and ducts shall have a clearance of at least
for continued operation.
eighteen (18) inches (457.2 mm) to combustible
material, three (3) inches (76.2 mm) to limited- 507.2.2 The protection methods for ducts to
combustible material, and 0 inches (0 mm) to reduce clearance shall be applied to the
noncombustible material. combustible or limited-combustible construction,
not to the duct itself.
Exception No. 1: Where the hood, duct, or
grease removal device is listed for lesser Exception: Field-applied grease duct
clearances. enclosures and factory-built grease duct
enclosures.
Exception No. 2: Reduced clearance to
combustible material if the combustible 507.2.3 Field-Applied and Factory Built
material is protected as follows: Grease Duct Enclosures. Field-applied grease
duct enclosures and factory-built grease duct
(a) 0.013 inch (0.33 mm) (no. 28 gauge) sheet
enclosures shall listed in accordance with UL
metal spaced out one (1) inch (25.4 mm) on
2221, Standard for Tests of Fire Resistive Grease
noncombustible spacers shall have nine
Duct Enclosure Assemblies, or equivalent
(9) inch (228.6 mm) clearance to com-
standard and installed in accordance with the
bustible material.
manufacturers instructions and the listing
(b) 0.027 inch (0.69 mm) (No. 22 gauge) sheet requirements. [NFPA 96: 4.3.1]
metal on one (1) inch (25.4 mm) mineral
507.2.4 Field-applied grease duct enclosures
wool batts or ceramic fiber blanket and factory-built grease duct enclosures shall
reinforced with wire mesh or equivalent demonstrate that they provide sufficient
spaced out one (1) inch (25.4 mm) on non- mechanical and structural integrity, resiliency,
combustible spacers shall have three (3) and stability when subjected to expected
inch (76.2 mm) clearance to combustible building environmental conditions, duct
material. movement under general operating conditions,
Exception No. 3: Reduced clearance to and duct movement due to fire conditions.
limited-combustible materials to zero clearance [NFPA 96: 4.3.2]
where protected by metal lath and plaster, 507.2.4.1 Measures shall be taken to prevent
ceramic tile, quarry tile, other noncombustible physical damage to any material or product
materials or assembly of noncombustible used for the purpose of reducing clearances.
materials, or materials and products that are
Exception: When the duct is protected with
listed for the purpose of reducing clearance
a field-applied grease duct enclosure or
and are acceptable to the Authority Having
factory-built grease duct enclosure.
Jurisdiction. The listed materials shall be
installed in accordance with the conditions of 507.2.4.2 The specifications of material,
the listing and the manufacturer's instructions gauge, and construction of the duct used in
and shall be acceptable to the Authority the testing and listing of field-applied grease
duct enclosures and factory-built grease duct
Having Jurisdiction.
enclosures shall be included as minimum
507.2.1.1 Measures shall be taken to prevent requirements in their listing and installation
physical damage to any material or product documentation. [NFPA 96: 4.3.3]
used for the purpose of reducing clearances.
507.2.4.3 The following clearance options
In the event of damage, the material or
for which field-applied grease duct

70
EXHAUST SYSTEMS 507.2 508.2

enclosures and factory-built grease duct system, including electrical schematics, shall be
enclosures have been successfully evaluated available on the premises.
shall be clearly identified in their listing and 507.4 If required by the Authority Having
installation documentation and on their Jurisdiction, notification in writing shall be given of
label [NFPA 96: 4.3.4]: any alteration, replacement, or relocation of any
(1) Open combustible clearance at manufac- exhaust or extinguishing system or part thereof or
turers requested dimensions. [NFPA cooking equipment. Satisfaction shall be provided to
96: 4.3.4(1)] the Authority Having Jurisdiction that the complete
(2) Closed combustible clearance at exhaust system as addressed in this standard is
manufacturers requested dimensions, installed and operable in accordance with the
with or without specified ventilation. approved design and the manufacturers instructions.
[NFPA 96: 4.3.4(2)]
(3) Rated shaft clearance at manufacturers 508.0 Hoods.
requested dimensions, with or without
508.1 Where Required. Hoods shall be installed at or
specified ventilation. [NFPA 96: 4.3.4(3)]
above all commercial-type deep fat fryers, broilers, fry
507.2.5 A duct shall be permitted to contact grills, steam-jacketed kettles, hot-top ranges, ovens,
noncombustible floors, interior walls, and other barbecues, rotisseries, dishwashing machines, and
noncombustible structures or supports, but it similar equipment that produces comparable amounts
shall not be in contact for more than 50 percent of steam, smoke, grease, or heat in a food-processing
of its surface area per each lineal foot of contact establishment. For the purpose of this section, a food-
length. Where such direct contact is made, the processing establishment shall include any building or
duct shall be protected from corrosion due to portion thereof used for the processing of food, but
this contact. shall not include a dwelling unit.
Exception: When the duct is protected with 508.1.1 Construction. The hood or that portion
a material or product listed for the purpose of a primary collection means designed for
of reducing clearance to zero. collecting cooking vapors and residues shall be
507.2.6 Clearances between the duct and constructed of and be supported by steel not less
interior surfaces of enclosures shall meet the than 0.043 inch (1.09 mm) (No. 18 MSG) in
requirements of Section 507.2. thickness, stainless steel not less than 0.037
507.3 A drawing(s) of the exhaust system installation inch(0.94 mm) (No. 20 MSG) in thickness, or
along with a copy of operating instructions for other approved material of equivalent strength
subassemblies and components used in the exhaust and fire and corrosion resistance.
Exceptions:
(1) Listed exhaust hoods with or without
exhaust dampers.
(2) Type II hoods shall be constructed of at least
0.024 inch (0.61 mm) (No. 24 gauge) steel.
Hoods constructed of copper shall be of
copper sheets weighing at least twenty-four
(24) ounces per square foot (7.32 kg/m 2).
Joints and seams shall be substantially tight.
Solder shall not be used except for sealing a
joint or seam.
All hoods shall be secured in place [For OSHPD
1, 2 & 4] to resist the lateral loads given in the
Califonria Building Code, Title 24, Part 2 b y
noncombustible supports.
508.2 All seams, joints, and penetrations of the hood
enclosure that direct and capture grease-laden
vapors and exhaust gases shall have a liquidtight
FIGURE 5-1 Typical Section of Eyebrow-Type continuous external weld to the hoods lower
Hood. outermost perimeter. Internal hood joints, seams,

71
508.2 508.4 2007 CALIFORNIA MECHANICAL CODE

filter support frames, and appendages attached determined by application of the following
inside the hood need not be welded but shall be formulas:
sealed or otherwise made greasetight. WHERE:
Exception No. 1: Penetrations shall be permitted A = the horizontal surface area of the hood, in square
to be sealed by devices that are listed for such feet (m2).
use and whose presence does not detract from
P = that part of the perimeter of the hood that is open, in
the hood's or duct's structural integrity.
feet (mm).
Exception No. 2: Eyebrow-type hoods over gas
D = distance in feet (mm) between the lower lip of
or electric ovens shall be permitted to have a duct
the hood and the cooking surface.
constructed as in Section 510.0 from the oven
flue(s) connected to the hood canopy upstream of Q = quantity of air, in cubic feet per minute (L/s).
the exhaust plenum as shown in Figure 5-1. The
duct shall be connected to the hood with a When cooking equipment is installed back to back
continuous weld or have a duct-to-duct and is covered by a common island-type hood, the
connection as shown in Figure 5-6(b) through (d). airflow required may be calculated using the
Exception No. 3: Seams, joints, and penetrations formula for three sides exposed. Type II hood
of the hood shall be permitted to be internally airflow requirements shall be in accordance with the
welded, provided that the weld is formed requirements for low-temperature appliance hoods.
smooth or ground smooth, so as to not trap 508.4.1.2 The minimum airflow for solid-
grease, and is readily cleanable. fuel cooking equipment, grease-burning
Exception No. 4: Listed exhaust hoods with or charbroilers, and undefined equipment shall
without exhaust dampers. be:
508.3 Insulation materials other than electrical Number of Exposed Sides Formula
insulation shall have a flame-spread rating of 4 (island or central hood) Q = 300A
twenty-five (25) or less when tested in accordance 3 or less Q = 200A
with UL 723, Standard for Test for Surface Burning
Alternate formula Q = 100PD
Characteristics of Building Materials. Adhesives or
cements used in the installation of insulating 508.4.1.3 Type I hoods when the cooking
materials shall comply with the preceding equipment includes high-temperature
requirements when tested with the specific appliances such as deep-fat fryers:
insulating material. Number of Exposed Sides Formula
508.4 Hood Size. Hoods shall be sized according to 4 (island or central hood) Q = 150A
the following calculations and configured to provide 3 or less Q = 100A
for the capture and removal of grease-laden vapors. Alternate formula Q = 100PD
(See Section 511.2.2.)
508.4.1.4 Type I hoods where the cooking
508.4.1 Canopy Size and Location. For equipment includes medium-temperature
canopy-type commercial cooking hoods, the appliances such as rotisseries, grills, and
inside edge thereof shall overhang or extend a ranges:
horizontal distance of not less than six (6) inches
Number of Exposed Sides Formula
(152 mm) beyond the edge of the cooking
surface on all open sides, and the vertical 4 (island or central hood) Q = 100A
distance between the lip of the hood and the 3 or less Q = 75A
cooking surface shall not exceed four (4) feet Alternate formula Q = 50PD
(1,219 mm). 508.4.1.5 Type I hoods where the cooking
Exception: Listed exhaust hoods are to be equipment includes low-temperature
installed in accordance with the terms of appliances such as medium-to-low-
their listings and the manufacturers temperature ranges, roasters, roasting
installation instructions. ovens, pastry ovens, and equipment
508.4.1.1 Capacity of Hoods. Canopy-type approved for use under a Type II hood, such
commercial cooking hoods shall exhaust as pizza ovens:
through the hood a minimum quantity of air

72
EXHAUST SYSTEMS 508.4 509.2

Number of Exposed Sides Formula 508.7 Solid-Fuel Hood Assemblies. Where solid-
4 (island or central hood) Q = 75A fuel cooking equipment is to be used, the solid-fuel
hood assembly shall comply with Section 517.0.
3 or less Q = 50A
508.8 Exhaust Outlets. An exhaust outlet within an
Alternate formula Q = 50PD
unlisted hood shall be located so as to optimize the
capture of particulate matter. Each outlet shall serve
Exception: Listed exhaust hoods are to be not more than a twelve (12) foot (3658 mm) section of
installed in accordance with the terms of their an unlisted hood
listing and the manufacturers installation
instructions.
509.0 Grease Removal Devices in Hoods.
508.4.2 Capacity for Noncanopy Hoods.
509.1 Grease Removal Devices. Listed grease
In addition to all other requirements for
filters, baffles, or other approved grease removal
hoods specified in this section, the volume
devices for use with commercial cooking equipment
of air exhausting through a noncanopy-type
shall be provided. Listed grease filters shall be tested
hood to the duct system shall be not less
in accordance with UL 1046, Grease Filters for
than 300 cubic feet per minute per lineal foot
Exhaust Ducts. Mesh filters shall not be used.
(465 L/s per m) of cooking equipment.
Listed noncanopy exhaust hoods and filters 509.2 Installation.
shall be sized and installed in accordance 509.2.1 The distance between the grease
with the terms of their listing and the removal device and the cooking surface shall be
manufacturers installation instructions. as great as possible but not less than eighteen
Exception: Listed hood assemblies (18) inches (457.2 mm). [NFPA 96: 6.2.1.1]
designed and installed specifically for the 509.2.2 Where grease removal devices are used
intended use. in conjunction with charcoal or charcoal-type
508.5 Exhaust Hood Assemblies with Integrated broilers, including gas or electrically heated
Supply-Air Plenums. charbroilers, a minimum vertical distance of four
(4) feet (1.22 m) shall be maintained between the
The construction and size of these hoods shall
lower edge of the grease removal device and the
comply with the requirements of Sections 508.1 and
cooking surface. [NFPA 96: 6.2.1.2]
508.4.
Exception No. 1: Grease removal devices
508.5.1 The construction of the outer shell or the
supplied as part of listed hood assemblies
inner exhaust shell shall comply with Section
shall be installed in accordance with the
508.1. If the outer shell is welded, the inner shell
terms of the listing and the manufacturers
shall be of greasetight construction.
instructions. [NFPA 96: 6.2.1.5]
508.5.2 A fire-actuated damper shall be installed
Exception No. 2: For cooking equipment
in the supply air plenum at each point where a
without exposed flame and where flue
supply air duct inlet or a supply air outlet
gases bypass grease removal devices, the
penetrates the continuously welded shell of the
minimum vertical distance shall be
assembly. The damper shall be listed for such use
or be part of a listed exhaust hood with or permitted to be reduced to not less than six
without exhaust damper. The actuation device (6) inches (152.4 mm). [NFPA 96: 6.2.1.3]
shall have a maximum temperature rating of Exception No. 3: Where a grease removal
286F (141C). Supply-air plenums that discharge device is listed for separation distances less
air from the face rather than from the bottom or than those required in 6.2.1.1 and 6.2.1.2,
into the exhaust hood and that are isolated from the listing requirements shall be permitted.
the exhaust hood by the continuously welded [NFPA 96: 6.2.1.4]
shell extending to the lower outermost perimeter 509.2.3 Grease Removal Device Protection.
of the entire hood assembly shall not require a Grease removal devices shall be protected from
fire-actuated damper. combustion gas outlets and from direct flame
508.6 Listed Hood Assemblies. Listed hood impingement occurring during normal operation
assemblies shall be installed in accordance with the of cooking appliances producing high flue gas
terms of their listing and the manufacturers temperatures, such as deep-fat fryers or upright or
instructions. high broilers (salamander broilers), where the

73
509.2 Figure 5-2 2007 CALIFORNIA MECHANICAL CODE

distance between the grease removal device and shall be clearly so designated, or the hood shall
the appliance flue outlet (heat source) is less than be constructed so that filters cannot be installed
eighteen (18) inches (457.2 mm). [NFPA 96: 6.2.2.1] in the wrong orientation. [NFPA 96: 6.2.5]
509.2.3.1 This protection shall be permitted to 509.3 Solid-Fuel Grease Removal Devices.
be accomplished by the installation of a steel Where solid-fuel cooking equipment is provided
or stainless steel baffle plate between the heat with grease removal devices, these devices shall
source and the grease removal device. [NFPA comply with Section 517.0.
96: 6.2.2.2]
509.2.3.2 The baffle plate shall be sized and 510.0 Exhaust Duct Systems.
located so that flames or combustion gases
510.1 General.
shall travel a distance not less than (eighteen)
18 inches (457.2 mm) from the heat source to 510.1.1 Ducts shall not pass through fire walls
the grease removal device. [NFPA 96: 6.2.2.3] or fire partitions.
509.2.3.3 The baffle shall be located not less 510.1.2 All ducts shall lead as directly as is
than six (6) inches (152.4 mm) from the grease practicable to the exterior of the building, so as
removal devices. [NFPA 96: 6.2.2.4] not to unduly increase any fire hazard.
509.2.4 Grease Filters. Grease filters shall be 510.1.3 Duct systems shall not be interconnected
listed and constructed of steel or listed with any other building ventilation or exhaust
equivalent material and shall be of rigid system.
construction that will not distort or crush under 510.1.4 All ducts shall be installed without
normal operation, handling, and cleaning forming dips or traps that might collect residues.
conditions. [NFPA 96: 6.2.3.1 and 6.2.3.2] For In manifold (common duct) systems, the lowest
applications listed in Section 111 regulated by the end of the main duct shall be connected flush on
Office of State Fire Marshal, grease filters shall be the bottom with the branch duct. Duct systems
Class I when tested in accordance with the test serving a Type I hood shall be so constructed and
method in Part 12, Title 24, Chapter 12-71, SFM installed that grease cannot become pocketed in
Standard 12-71-1. any portion thereof, and the system shall slope
not less than 1/4 inch per lineal foot (21 mm/m)
509.2.4.1 Filters shall be tight fitting and
toward the hood or toward an approved grease
firmly held in place and grease filters shall
be arranged so that all exhaust air passes
through the grease filters. [NFPA 96: 6.2.3.3]
509.2.4.2 Filters shall be easily accessible
and removable for cleaning. [NFPA 96:
6.2.3.4]
509.2.4.3 Filters shall be installed at an
angle not less than 45 degrees from the
horizontal. [NFPA 96: 6.2.3.5]
509.2.4.4 [DHS] Grease filters shall be Class I
when tested in accordance with the test method
in SFM 12-71-1.
509.2.5 Grease Drip Trays. Filters shall be
equipped with a drip tray beneath their lower
edges. [NFPA 96: 6.2.4.1]
509.2.5.1 The tray shall be kept to the
minimum size needed to collect grease and
shall be pitched to drain into an enclosed
metal container having a capacity not
exceeding one (1) gallon (3.785 L) [NFPA 96:
6.2.4.2, and 6.2.4.3].
509.2.6 Grease Filter Orientation. Grease filters
that require a specific orientation to drain grease FIGURE 5-2 Permitted Duct-to-Hood Collar
Connection.

74
EXHAUST SYSTEMS 510.1 510.3

reservoir. Where horizontal ducts exceed 510.1.8 Ducts, Non-Grease. Ducts and
seventy-five (75) feet (22,860 mm) in length, the plenums serving Type II hoods shall be
slope shall be not less than one (1) inch per lineal constructed of rigid metallic materials as set
foot (83 mm/m). forth in Chapter 6. Duct bracing and supports
510.1.5 Openings required for accessibility shall shall comply with Chapter 6. Ducts subject to
comply with Section 510.3. positive pressure shall be adequately sealed.
510.1.6 A sign shall be placed on all access 510.2 Clearance.
panels stating the following: 510.2.1 Clearance between ducts and combustible
materials shall be provided in accordance with the
ACCESS PANELDO NOT OBSTRUCT
requirements of Section 507.2.
510.1.7 Duct bracing and supports shall be of
510.2.2 Listed grease ducts shall be installed in
noncombustible material, securely attached to the
accordance with the terms of their listings and
structure and designed to carry gravity and lateral
manufacturers instructions.
loads within the stress limitations of the Building
Code. Bolts, screws, rivets, and other mechanical 510.3 Openings.
fasteners shall not penetrate duct walls. 510.3.1 Openings shall be provided at the sides
or at the top of the duct, whichever is more
accessible, and at changes of direction. Openings
shall be protected by approved access panels
that comply with Section 510.3.4.5.
Exception: Openings shall not be required
in portions of the duct that are accessible
from the duct entry or discharge.
510.3.2 For hoods with dampers in the exhaust
or supply collar, an access panel for cleaning and
inspection shall be provided in the duct or the
hood collar. This access panel shall be as close to
the hood as possible but shall not exceed
eighteen (18) inches (457.2 mm).
Exception: Dampers that are accessible
from under the hood.
510.3.3 Exhaust fans with ductwork connected to
both sides shall have access for cleaning and
inspection within three (3) feet (0.92 m) of each side
of the fan. [NFPA 96: 7.3.7]
510.3.4 Openings in Ducts. Openings shall
conform with Sections 510.3.4.1 through
510.3.4.5. [NFPA 96: 7.4]
510.3.4.1 Horizontal Ducts. On horizontal
ducts, at least one 20 inch by 20 inch (508
mm by 508 mm) opening shall be provided
for personnel entry. [NFPA 96: 7.4.1.1]
510.3.4.1.1 Horizontal ducting shall be
secured sufficiently to allow for the weight
of personnel entry into the duct. Where an
opening of this size is not possible, openings
large enough to permit thorough cleaning
shall be provided at twelve (12) foot (3.7 m)
intervals. [NFPA 96: 7.4.1.3]
510.3.4.1.2 Support systems for horizontal
grease duct systems 609 mm (24 in.) and
larger in any cross-sectional dimension shall
FIGURE 5-3 Telescoping and Bell-Type Duct be designed for the weight of the ductwork
Connections.

75
510.3 510.7 2007 CALIFORNIA MECHANICAL CODE

plus 363 kg (800 lb) at any point in the duct Exception No. 1: Duct-to-hood collar
systems. [NFPA 96: 7.4.1.3] connections as shown in Figure 5-2 shall
510.3.4.2 On nonlisted ductwork, the edge be permitted.
of the opening shall be not less than 1-1/2 Exception No. 2: Penetrations shall be
inch (38.1 mm) from all outside edges of the permitted to be sealed by other listed
duct or welded seams. [NFPA 96: 7.4.1.4] devices that are tested to be greasetight
510.3.4.3 Vertical Ducts. On vertical and are evaluated under the same
ductwork where personnel entry is conditions of fire severity as the hood or
possible, access shall be provided at the top enclosure of listed grease extractors and
of the vertical riser to accommodate whose presence does not detract from
descent. [NFPA 96: 7.4.2.1] the hood's or duct's structural integrity.
510.3.4.3.1 Where personnel entry is Exception No. 3: Internal welding shall
not possible, adequate access for be permitted, provided the joint is
cleaning shall be provided on each formed or ground smooth and is readily
floor. [NFPA 96: 7.4.2.2] accessible for inspection.
510.3.4.4 Access Panels. Access panels 510.5.2.2 Overlapping duct connections of
shall be of the same material and thickness either the telescoping or the bell type shall
as the duct (Section 510.5.1). Access panels be used for welded field joints, not butt-
shall have a gasket or sealant that is rated for weld connections. The inside duct section
1,500F (815.6C) and shall be greasetight. shall always be uphill of the outside duct
Fasteners, such as bolts, weld studs, latches, section. The difference between inside
or wing nuts, used to secure the access dimensions of overlapping sections shall not
panels shall be carbon steel or stainless steel exceed 1/4 inch (6.4 mm). The overlap shall
and shall not penetrate duct walls. not exceed two (2) inches (50.8 mm). (See
Figure 5-3.)
Exception: Listed grease duct access
door assemblies (access panels) shall be 510.6 Exterior Installations.
installed in accordance with their terms 510.6.1 The exterior portion of the
of the listings and the manufacturer's ductwork shall be vertical wherever possible
instructions. and shall be installed and adequately
510.3.4.5 Openings for installation, servicing, supported on the exterior of a building.
and inspection of listed fire protection system Bolts, screws, rivets, and other mechanical
devices and for duct cleaning shall be fasteners shall not penetrate duct walls.
provided in ducts and enclosures and shall Clearance of any ducts shall comply with
conform to the requirements of 510.3. Section 507.2.
Enclosure openings required to reach access 510.6.2 All ducts shall be protected on the
panels in the ductwork shall be large enough exterior by paint or other suitable weather-
for the removal of the access panel. protective coating or shall be constructed of
510.4 Listed Grease Ducts. Listed grease ducts noncorrosive stainless steel. Ductwork
shall be installed in accordance with the terms of the subject to corrosion shall have minimal
listing and the manufacturers instructions. contact with the building surface.
510.5 Other Grease Ducts. Other grease ducts 510.7 Interior Installations.
shall comply with the requirements of this section. 510.7.1 In all buildings more than one story in
510.5.1 Materials. Ducts shall be constructed of height, and in one-story buildings where the roof-
and supported by carbon steel not less than ceiling assembly is required to have a fire
0.054 inch (1.37 mm) (No. 16 MSG) in thickness resistance rating, the ducts shall be enclosed in a
or stainless steel not less than 0.043 inch (1.09 continuous enclosure extending from the lowest
mm) (No. 18 MSG) in thickness. fire-rated ceiling or floor above the hood, through
any concealed spaces, to or through the roof so as
510.5.2 Installation.
to maintain the integrity of the fire separations
510.5.2.1 All seams, joints, penetrations, required by the applicable Building Code
and duct-to-hood collar connections shall provisions. The enclosure shall be sealed around
have a liquidtight continuous external weld. the duct at the point of penetration of the lowest

76
EXHAUST SYSTEMS 510.7 Figure 5-4

fire-rated ceiling or floor above the hood in order described in Section 507.2 are not applicable to
to maintain the fire resistance rating of the enclosures.
enclosure and shall be vented to the exterior of the Exception: Clearance from the outer surfaces
building through weather-protected openings. of field-applied grease duct enclosures and
Exception: The continuous enclosure factory-built grease duct enclosures to the
provisions shall not be required where a field- interior surfaces of construction installed
applied grease duct enclosure or a factory- around them shall be permitted to be
built grease duct enclosure (see Section reduced where the field-applied grease duct
507.2.3) is protected with a listed duct- enclosure materials and the factory-built
through-penetration protection system grease duct enclosures are installed in
equivalent to the fire resistance rating of the accordance with the conditions of their
assembly being penetrated, and the materials listings and the manufacturers instructions
are installed in accordance with the conditions and are acceptable to the Authority Having
of their listings and the manufacturers Jurisdiction.
instructions and are acceptable to the
510.7.3 For field-applied grease duct enclosures
Authority Having Jurisdiction.
and factory-built grease duct enclosures, the
For applications listed in Section 111 regulated by the materials and products shall conform to Sections
Office of the State Fire Marshal, see Section 510.7.1.1. 510.7.3.1 through 510.7.3.3.
510.7.1.1 [For SFM] A grease duct serving a 510.7.3.1 Field-applied grease duct
Type I hood which penetrates a ceiling, wall or floor enclosures and factory-built grease duct
shall be enclosed in a duct enclosure from the point enclosures shall demonstrate that they
of penetration. A duct may only penetrate exterior provide sufficient mechanical and structural
walls at locations where unprotected openings are
permitted by the building code. Duct enclosures
shall be constructed in accordance with the
California Building Code. Duct enclosures shall be
of a least one-hour fire resistive construction in all
buildings and shall be of two-hour fire-resistive
construction in Types I and II fire-resistive
buildings. The duct enclosure shall be sealed
around the duct at the point of penetration and
vented to the exterior through weather protected
openings. The enclosure shall be separated from the
duct by at least three (3) inches (76mm) and not
more than twelve (12) inches (305mm) and shall
serve as single grease exhaust duct system.
510.7.2 The enclosure required in Section 510.7.1
shall conform to Sections 510.7.2.1 through 510.7.2.3.
510.7.2.1 If the building is less than four stories
in height, the enclosure wall shall have a fire
resistance rating of not less than one (1) hour.
510.7.2.2 If the building is four stories or more
in height, the enclosure wall shall have a fire
resistance rating of not less than two (2) hours.
510.7.2.3 Clearance from the duct or the exhaust
fan to the interior surface of enclosures of
combustible construction shall be not less than
eighteen (18) inches (457.2 mm), and clearance
from the duct to the interior surface of enclosures
of noncombustible or limited-combustible
construction shall be not less than six (6) inches FIGURE 5-4 Exhaust Termination Distance from
Fresh Air Intake (FAI) or Operable Door or
(152.4 mm). Provisions for reducing clearances as
Window.

77
510.7 Figure 5-6(b) 2007 CALIFORNIA MECHANICAL CODE

integrity, resiliency, and stability when


subjected to expected building environmental
conditions, duct movement under general
operating conditions, and duct movement
due to interior and exterior fire conditions.
510.7.3.2 Measures shall be taken to prevent
physical damage to any covering or
enclosure material. Any damage to the
covering or enclosure shall be repaired and
the covering or enclosure restored to meet its
intended listing and fire-resistive rating and
to be acceptable to the Authority Having
Jurisdiction.
510.7.3.3 In the event of a fire within a kitchen
exhaust system, the duct, the enclosure, or the
covering directly applied to the duct shall be
inspected by qualified personnel to determine FIGURE 5-5 Upblast Fan Clearances.
whether the duct, the enclosure, and the
covering directly applied to the duct are
structurally sound, capable of maintaining
their fire protection functions, suitable for
continued operation, and acceptable to the
Authority Having Jurisdiction.
510.7.4 For listed grease ducts, see Section 510.4.
510.7.5 If openings in the enclosure walls are
provided, they shall be protected by approved
self-closing fire doors of proper rating. Fire
doors shall be installed in accordance with
NFPA 80, Standard for Fire Doors and Fire
Windows. Openings on other listed materials or
products shall be clearly identified and labeled
according to the terms of the listing and the
manufacturer's instructions and shall be FIGURE 5-6(a) Typical Section of Duct-to-Fan
acceptable to the Authority Having Jurisdiction. ConnectionButt Joint Method.
The panels shall be readily accessible.
510.7.6 Each duct system shall constitute an
individual system serving only exhaust hoods in
one fire zone on one floor. Multiple ducts shall
not be permitted in a single enclosure unless
acceptable to the Authority Having Jurisdiction.
510.8 Termination of Exhaust System.
510.8.1 The exhaust system shall terminate as
follows:
(A) Outside the building with a fan or duct.
(B) Through the roof, or to the roof from
outside, as in Section 510.8.2, or through a
wall, as in Section 510.8.3.
510.8.2 Rooftop Terminations.
510.8.2.1 Rooftop terminations shall be
arranged with or provided with the
following: FIGURE 5-6(b) Typical Section of Duct-to-Fan
ConnectionOverlapping Method.

78
EXHAUST SYSTEMS Figure 5-6(c) 510.8

device that is applied to exhaust systems


shall not inhibit the performance of any fan.
Exception: Grease containers that are
evaluated for equivalency with the
preceding requirements and listed as
such.
(D) A listed grease duct complying with Section
510.4, or with ductwork complying with
Section 510.5.
(E) A hinged upblast fan supplied with flexible
weatherproof electrical cable and service
hold-open retainer to permit proper
inspection and cleaning that is listed for
commercial cooking equipment, provided
FIGURE 5-6(c) Typical Section of Duct-to-Fan the ductwork extends a minimum of
ConnectionSealant Method. eighteen (18) inches (457.2 mm) above the
roof surface and the fan discharges a
minimum of forty (40) inches (1.02m)
above the roof surface. (See Section 511.1.1.)
(F) Other approved fan, provided (1) it meets
the requirements of Sections 510.8.2(C) and
511.1.3, and (2) its discharge or its extended
duct discharge meets the requirements of
Section 510.8.2(B).
510.8.2.2 Listed flexible connectors may be
used on exterior roof locations when
required for proper equipment vibration
isolation.
510.8.2.3 Fans shall be provided with safe
FIGURE 5-6(d) Typical Section of Duct-to-Fan access and a work surface for inspection and
ConnectionDirect to Fan Inlet Cone Method. cleaning.
510.8.3 Wall Terminations.
(A) A minimum of ten (10) feet (3.05 m) of clearance 510.8.3.1 Wall terminations shall be
from the outlet to adjacent buildings, arranged with or provided with the
property lines, and air intakes. Where space following properties:
limitations absolutely prevent a ten (10) foot (A) Through a noncombustible wall with a
(3.05m) horizontal separation from an air minimum of ten (10) feet (3.05 m) of
intake, a vertical separation shall be permitted, clearance from the outlet to adjacent
with the exhaust outlet being a minimum of buildings, property lines, grade level,
three (3) feet (0.92 m) above any air intake combustible construction, or electrical
located within ten (10) feet (3.05 m) equipment or lines, and the closest
horizontally. point of any air intake or operable door
(B) The exhaust flow directed up and away or window at or below the plane of the
from the surface of the roof and a minimum exhaust termination. The closest point
of any air intake or operable door or
of forty (40) inches (1.02 m) above the roof
window above the plane of the exhaust
surface.
termination shall be a minimum of ten
(C) The ability to drain grease out of any traps (10) feet (3.05 m) distant, plus 0.25 feet
or low points formed in the fan or duct near (0.076m) for each 1 degree from horizontal,
the termination of the system into a the angle of degree being measured
collection container that is noncombustible, from the center of the exhaust termination
closed, rainproof, structurally sound for the to the center of the air intake or operable
service to which it is applied, and will not door or window. (See Figure 5-4.)
sustain combustion. A grease collection Exception: A wall termination in a

79
510.8 511.2 2007 CALIFORNIA MECHANICAL CODE

secured area can be at a lower located shall have the same fire resistance
height above grade if acceptable to rating as the enclosure.
the Authority Having Jurisdiction. 511.1.3 Utility set exhaust fans, if installed at the
(B) The exhaust flow directed perpendicularly rooftop termination point, shall meet the
outward from the wall face or upward. requirements of Section 510.8.2.1(A) through
(C) All the ductwork pitched to drain the Section 510.8.2.2. If the fan is installed within the
grease back into the hood(s), or with a building, it shall be located in an easily accessible
drain provided to bring the grease back area of adequate size to allow for service or
into a container within the building or removal. If the duct system connected to the fan is
into a remote grease trap. in an enclosure, the space or room in which the
(D) A listed grease duct complying with exhaust fan is located shall have the same fire
Section 510.4, or other ducts complying resistance rating as the enclosure. The fan shall be
with Section 510.5. connected to the exhaust duct by flanges securely
bolted as shown in Figures 5-6(a) through 5-6(d)
(E) An approved fan, provided it meets the
or by a system specifically listed for such use.
requirements of Sections 510.8.3.1(C)
Flexible connectors shall not be used. Exhaust
and 511.1.1 or 511.1.3.
fans shall have a drain directed to a readily
510.9 Solid-Fuel Duct Systems. Where solid-fuel accessible and visible grease receptacle not to
cooking equipment is to be vented, the duct system exceed one (1) gallon (3.8 L).
shall comply with Section 517.0.
511.1.4 Exhaust fan housings shall be
constructed of carbon steel not less than 0.054
511.0 Air Movement. inch (1.37 mm) (No. 16 MSG) in thickness or
511.1 Exhaust Fans for Commercial Cooking stainless steel not less than 0.043 inch (1.09 mm)
(No. 18 MSG) in thickness or, if listed,
Equipment.
constructed in accordance with the terms of the
Where solid-fuel cooking equipment is to be vented, listing.
the duct system shall comply with Section 517.0.
511.1.5 Openings for cleaning, servicing, and
511.1.1 Approved upblast fans with motors inspection shall conform to the requirements of
surrounded by the airstream shall be hinged, Section 510.3.3 Clearances shall conform to the
supplied with flexible weatherproof electrical requirements of Sections 507.2, or 510.7.2.3 if
cable and service hold-open retainers, and listed installed within an enclosure.
for this use. (See Figure 5-5.) Installation shall
511.1.6 All wiring and electrical equipment shall
conform to the requirements of Section 510.8.
comply with the California Electrical Code.
511.1.2 In-Line Exhaust Fans.
511.2 Airflow.
511.1.2.1 In-line fans shall be of the type
511.2.1 The air velocity through any duct shall
with the motor located outside the airstream
be not more than 2,500 feet (457.2 m) per minute.
and with belts and pulleys protected from
the airstream by a greasetight housing. Exception: Transition duct sections shall be
They shall be connected to the exhaust duct permitted to be connected to hoods and exhaust
by flanges securely bolted as shown in fans that do not meet this velocity, provided that
Figure 5-6(a), or by a system specifically they do not exceed three (3) feet (0.92 m) in
listed for such use. Flexible connectors shall length and do not contain traps for grease.
not be used. 511.2.2 Exhaust-air volumes for hoods shall be
511.1.2.2 If the design or positioning of the of sufficient level to provide for capture and
fan allows grease to be trapped, a drain removal of grease-laden cooking vapors. Test
directed to a readily accessible and visible data, performance acceptable to the Authority
grease receptacle, not exceeding one (1) Having Jurisdiction, or both, shall be provided,
gallon (3.8 L), shall be provided. In-line displayed, or both, upon request.
exhaust fans shall be located in an easily Exception: Lower exhaust-air volumes shall
accessible area of adequate size to allow for be permitted during no-load cooking
service or removal. If the duct system conditions, provided they are sufficient to
connected to the fan is in an enclosure, the capture and remove flue gases and residual
space or room in which the exhaust fan is vapors from cooking equipment.

80
EXHAUST SYSTEMS 511.2 512.3

511.2.3 A hood exhaust fan(s) shall continue to 511.5 Solid-Fuel Air Movement Requirements.
operate after the extinguishing system has been Where solid-fuel cooking equipment is used, exhaust
activated, unless fan shutdown is required by a and replacement air also shall comply with Section 517.0.
listed component of the ventilation system or by 512.0 Auxiliary Equipment.
the design of the extinguishing system. It shall
not be required to restart the hood exhaust fan 512.1 Dampers. Dampers shall not be installed in
when the extinguishing system is activated if the exhaust ducts or exhaust duct systems.
exhaust fan and all cooking equipment served Exception: Where specifically listed for such use
by the fan had previously been shut down. or where required as part of a listed or approved
511.3 Replacement Air. Replacement air quantity device or system.
shall be adequate to prevent negative pressures in the 512.2 Electrical Equipment.
commercial cooking area(s) from exceeding 0.02 inch 512.2.1 Wiring systems of any type shall not be
water column (4.98 kPa). installed in ducts.
Exceptions: 512.2.2 Motors, lights, and other electrical
(1) When its fire-extinguishing system devices shall not be installed in ducts or hoods
discharges, makeup air supplied or located in the path of travel of exhaust
internally to a hood shall be shut off. products.
(2) Compensating hoods shall meet the Exception: Where specifically approved for
airflow requirements specified in such use.
Sections 508.4.1.3 through 508.4.1.5. 512.2.3 Lighting units in hoods shall be listed
Compensating hoods shall extract at for use over commercial cooking appliances
least 20 percent of their required exhaust and installed in accordance with the terms of
airflow from the kitchen area. their listing.
511.4 Common Duct (Manifold) Systems. 512.2.4 Lighting units on hoods shall not be
511.4.1 Master kitchen exhaust ducts that serve located in concealed spaces.
multiple tenants shall include provision to bleed Exceptions:
air from outdoors or from adjacent spaces into the (1) Where part of a listed exhaust hood.
master exhaust duct where required to maintain
(2) Where specifically listed for such use
the necessary minimum air velocity in the master
and installed in accordance with the terms
exhaust duct. of the listing.
511.4.2 This bleed-air duct shall connect to the 512.2.5 All electrical equipment shall be installed
top or side of the master exhaust duct. in accordance with the California Electrical Code,
511.4.3 The bleed-air duct shall have a fire with due regard to the effects of heat, vapor, and
damper at least twelve (12) inches (304.8 mm) grease on the equipment.
from the exhaust duct connection. 512.3 Other Equipment.
511.4.4 The bleed-air duct shall have the same 512.3.1 Fume incinerators, thermal recovery
construction and clearance requirements as the units, air pollution control devices, or other
main exhaust duct from the connection to the devices shall be permitted to be installed in
exhaust duct to at least twelve (12) inches (304.8 ducts or hoods or located in the path of travel of
mm) on both sides of the fire damper. exhaust products where specifically approved
511.4.5 Each bleed air duct shall have a means for such use. Downgrading other parts of the
of adjusting (e.g., using volume dampers) the exhaust system due to the installation of these
bleed-air quantity. approved devices, whether listed or not, shall
511.4.6 Such means shall be installed in between not be allowed.
the fire damper and the source of bleed air. 512.3.2 Any equipment, listed or otherwise, that
511.4.7 A bleed air duct shall not be used for the provides secondary filtration or air pollution
exhaust of grease-laden vapors and shall be so control and that is installed in the path of travel of
labeled. exhaust products shall be provided with an
approved automatic fire-extinguishing system for
511.4.8 Unused tenant exhaust connections to
the protection of the component sections of the
the master exhaust duct that are not used as
equipment and shall include protection of the
bleed air connections shall be disconnected and
ductwork downstream of the equipment,
sealed at the main duct. whether or not the equipment is provided with a

81
512.3 513.2 2007 CALIFORNIA MECHANICAL CODE

damper. If the equipment can be a source of Exception 1: Automatic fire-extinguishing


ignition, it shall be provided with appropriate equipment provided as part of listed
detection to operate the fire-extinguishing system. recirculating systems complying with
512.3.3 Where a cooking exhaust system standard UL 197, Standard for Safety
Commercial Electric Cooking Appliances.
employs an air pollution control device that
[NFPA 96:10.2.5]
recirculates air into the building, the provisions
of Section 516.0 shall apply. Exception 2: Public schools, kitchens, without
deep-fat fryers, shall be upgraded to a UL 300
512.4 Solid-Fuel Auxiliary Equipment. Where solid-
compliant system during state funded
fuel cooking comprises any part of a cooking operation,
modernization projects that are under the
additional provisions and equipment as described in jurisdiction of the Division of the State Architect.
Section 517.0 shall be used where required.
513.2.3 In existing systems, when changes in the
cooking media, positioning, or replacement of
513.0 Fire-Extinguishing Equipment. cooking equipment occur, the fire-extinguishing
513.1 General Requirements. system shall be made to comply with 513.2.2.
513.1.1 Fire-extinguishing equipment for the [NFPA 96 10.2.3.1]
protection of grease removal devices, hood 513.2.4 Modification of Existing Hood
exhaust plenums, and exhaust duct systems Systems
shall be provided. 513.2.4.1 Any abandoned pipe or conduit
513.1.2 Cooking equipment that produces from a previous installation shall be
grease-laden vapors (such as, but not limited to, removed from within the hood, plenum,
deep-fat fryers, ranges, griddles, broilers, woks, and exhaust duct. [NFPA 96 10.2.7.1]
tilting skillets, and braising pans) shall be 513.2.4.2 Penetrations and holes resulting
protected by fire-extinguishing equipment. from the removal of conduit or piping shall
513.2 Types of Equipment. be sealed with listed or equivalent liquid
513.2.1 Fire-extinguishing equipment shall tight sealing devices. [NFPA 96 10.2.7.2]
include both automatic fire-extinguishing 513.2.4.3 The addition of obstructions to
systems as primary protection and portable fire spray patterns from the cooking appliance
extinguishers as secondary backup. [NFPA nozzle(s) such as baffle plates, shelves, or
96:10.2.1] any modification shall not be permitted.
513.2.1.1 A placard identifying the use of [NFPA 96 10.2.7.3]
the extinguisher as secondary backup means 513.2.4.4 Changes or modifications to the
to the automatic fire suppression system hazard after installation of the fire-
shall be conspicuously placed near each extinguishing systems shall result in
portable fire extinguisher in the cooking reevaluation of the system design by a
area. [NFPA 96:10.2.2] properly trained and qualified person(s) or
513.2.2 Commercial cooking equipment that produce company. [NFPA 96 10.2.7.4]
grease laden vapors shall be provided with a Type I 513.2.5 Fixed Baffle Hoods with Water Wash.
Hood, in accordance with this Code, and an Grease removal devices, hood exhaust plenums,
automatic fire extinguisher system that is listed and and exhaust ducts requiring protection in
labeled for its intended use as follows: accordance with Section 513.1.1 shall be
1. Wet chemical extinguishing system (NFPA 17A, permitted to be protected by a listed fixed baffle
Standard for Wet Chemical Extinguishing hood containing a constant or fire-actuated
Systems), complying with UL 300. water-wash system that is listed and in
compliance with UL 300 or other equivalent
2. Carbon dioxide extinguishing systems (NFPA standards and shll be installed in accordance
12, Standard on Carbon Dioxide Extinguishing with the requirements of their listing. [NFPA 96:
Systems), 10.2.8.1]
3. Automatic fire sprinkler systems (NFPA 13, 513.2.5.1 The water for listed, fixed baffle
Standard for the Installation of Sprinkler hood assemblies shall be permitted to be
Systems). supplied from the domestic water supply
All existing dry chemical and wet chemical extinguishing when the minimum water pressure and
systems shall comply with UL 300, no later than the flow are provided in accordance with the
second required servicing of the system following the terms of the listing. [NFPA 96: 10.2.8.3]
effective date of this section. 513.2.5.2 The water supply shall be

82
EXHAUST SYSTEMS 513.2 513.9

monitored by an annunciated low water 513.5.2 The means for manual actuator(s) shall
pressure switch. be mechanical and shall not rely on electrical
513.2.5.3 The water wash in the fixed baffle power for actuation.
hood shall be activated by the cooking Exception: Electrical power shall be
equipment extinguishing system. permitted to be used for manual activation if
513.3 Simultaneous Operation. Fixed-pipe a standby power supply is provided or if
extinguishing systems in a single hazard area shall supervision is provided as per 513.7.1.
be arranged for simultaneous automatic operation 513.6 System Annunciation.
upon actuation of any one of the systems. 513.6.1 Upon activation of an automatic fire-
Exception No. 1: Where the fixed-pipe extinguishing system, an audible alarm or visual
extinguishing system is an automatic sprinkler indicator shall be provided to show that the
system. system has activated.
Exception No. 2: A dry or wet chemical system 513.6.2 Where a fire alarm signaling system is
shall be permitted to be used to protect common serving the occupancy where the extinguishing
exhaust ductwork by the methods specified in system is located, the activation of the automatic
NFPA 17A, Standard for Wet Chemical fire-extinguishing system shall activate the fire
Extinguishing Systems, in lieu of simultaneous alarm signaling system.
automatic operation. 513.7 System Supervision.
513.4 Fuel Shutoff. 513.7.1 Where electrical power is required to
513.4.1 Upon activation of any fire-extinguishing operate the automatic fire-extinguishing system,
system for a cooking operation, all sources of fuel it shall be monitored by a supervisory alarm,
with a standby power supply provided.
and electric power that produce heat to all
equipment requiring protection by that system Exceptions:
shall automatically shut off. (1) Where automatic fire-extinguishing
Exception No. 1: Steam supplied from an systems include automatic mechanical
external source. detection and actuation as a backup
detection system.
Exception No. 2: Solid-fuel cooking operations.
(2) Where fire-extinguishing systems are
513.4.2 Any gas appliance not requiring
interconnected or interlocked with the
protection, but located under the same ventila- cooking equipment power sources so that
ting equipment, shall also automatically shut off if the fire-extinguishing system becomes
upon activation of any extinguishing system. inoperable due to power failure, all sources
513.4.3 Shutoff devices shall require manual reset. of fuel or electric power that produce heat
513.5 Manual Activation. to all cooking equipment serviced by that
hood shall automatically shut off.
513.5.1 A readily accessible means for manual
activation shall be located between forty-two (42) 513.8 Special Design and Application.
inches and sixty (60) inches (1,067 mm and 1,524 513.8.1 Hoods containing automatic fire-
mm) above the floor, located in a path of exit or extinguishing systems are protected areas;
egress, and clearly identify the hazard protected. therefore, these hoods are not considered
The automatic and manual means of system obstructions to overhead sprinkler systems and
activation external to the control head or releasing shall not require floor coverage underneath.
device shall be separate and independent of each 513.8.2 A single listed detection device shall be
other so that failure of one will not impair the permitted for more than one appliance when
operation of the other. installed in accordance with the terms of the listing.
Exceptions: 513.9 Review and Certification.
(1) The manual means of system activation 513.9.1 Where required, complete drawings of
shall be permitted to be common with the system installation, including the hood(s),
the automatic means if the manual exhaust duct(s), and appliances, along with the
activation device is located between the interface of the fire-extinguishing system
control head or releasing device and the detectors, piping, nozzles, fuel shutoff devices,
first fusible link. agent storage container(s), and manual actuation
(2) An automatic sprinkler system. device(s), shall be provided.

83
513.9 514.3 2007 CALIFORNIA MECHANICAL CODE

513.9.2 Installation of systems shall be 514.1.6 Cooking equipment shall not be operated
performed only by persons properly trained and while its fire-extinguishing system or exhaust
qualified to install the specific system being system is nonoperational or otherwise impaired.
provided. The installer shall provide certification 514.1.7 Secondary filtration and pollution
that the installation is in agreement with the control equipment shall be operated in
terms of the listing and the manufacturer's accordance with the terms of their listing and the
instructions and/or approved design. manufacturer's recommendations. [NFPA 96:
513.10 Portable Fire Extinguishers. 11.1.7]
513.10.1 Portable fire extinguishers shall be 514.1.8 Inspection and maintenance of
installed in kitchen cooking areas in accordance equipment allowed in Section 512.3.1 shall be
with Chapter 3, Title 19 California Code of conducted by properly trained and qualified
Regulations. Such extinguishers shall use agents per-sons at a frequency determined by the
that saponify upon contact with hot grease, such manufacturer's instructions or equipment listing.
as sodium bicarbonate and potassium bicar- [NFPA 96: 11.1.8]
bonate dry chemical and potassium carbonate 514.2 Inspection. Maintenance of the fire-
solutions. Class B gas-type portables such as CO2 extinguishing system and listed exhaust hoods
and halon shall not be permitted in kitchen containing a constant or fire-actuated water system
cooking areas. Manufacturer's recommendations that is listed to extinguish a fire in the grease
shall be followed. removal devices, hood exhaust plenums, and
513.10.1.1 Portable fire extinguishers listed exhaust ducts shall be made by properly trained,
specifically for use in the kitchen cooking qualified, and certified person(s) or company
areas shall also be permitted. acceptable to the Authority Having Jurisdiction at
513.10.2 Other fire extinguishers in the kitchen least every six (6) months. [NFPA 96 11.2.1]
area shall be installed in accordance with Chapter 514.2.1 All actuation components, including
3, TItle 19 California Code of Regulations. remote manual pull stations, mechanical or
513.11 Solid-Fuel Fire-Extinguishing Equipment. electrical devices, detectors, actuators, and fire-
actuated dampers, shall be checked for proper
Where solid-fuel cooking equipment is served by fire-
operation during the inspection in accordance
extinguishing equipment, the provisions of Section
with the manufacturer's listed procedures. In
517.0 shall apply.
addition to these requirements, the specific
inspection requirements of the applicable NFPA
514.0 Procedures for the Use and Maintenance of standard shall also be followed. [NFPA 96:11.2.2
Equipment. &11.2.3]
514.1 Operating Procedures. 514.2.2 Fusible links (including fusible links on
514.1.1 Exhaust systems shall be operated fire damper assemblies) and automatic sprinkler
whenever cooking equipment is turned on. heads shall be replaced at least semiannually, or
more frequently if necessary where required by
514.1.2 Filter-equipped exhaust systems shall
the manufacturer. [NFPA 96: 11.2.4]
not be operated with filters removed.
514.2.3 If required, certificates of inspection and
514.1.3 Openings provided for replacing air
maintenance shall be provided.
exhausted through ventilating equipment shall
not be restricted by covers, dampers, or any 514.3 Cleaning.
other means that would reduce the operating 514.3.1 Hoods, grease removal devices, fans,
efficiency of the exhaust system. ducts, and other appurtenances shall be cleaned
514.1.4 Instructions for manually operating the to bare metal or the original factory coating at
fire-extinguishing system shall be posted frequent intervals prior to surfaces becoming
conspicuously in the kitchen and shall be heavily contaminated with grease or oily
reviewed periodically with employees by the sludge. After the exhaust system is cleaned, it
management. shall not be coated with powder or other
substance. The entire exhaust system shall be
514.1.5 Listed exhaust hoods shall be operated
inspected by a properly trained, qualified, and
in accordance with the terms of their listings and
certified company or person(s) in accordance
the manufacturer's instructions.
with Table 5-4.

84
EXHAUST SYSTEMS Table 5-4 515.3

TABLE 5-4 514.4 Operation, Maintenance, and Inspection of


Exhaust System Inspection Schedule Solid-Fuel Cooking Equipment.
Where solid-fuel cooking equipment is used, the
special provisions of Section 517.0 shall apply.
Type or Volume of Cooking Frequency
Frequency
Systems serving solid-fuel cooking operations Monthly
515.0 Minimum Safety Requirements for Cooking
Equipment.
Systems serving high-volume cooking Quarterly
515.1 Cooking Equipment.
operations such as 24-hour cooking,
515.1.1 Cooking equipment shall be approved
charbroiling, or wok cooking based on one of the following criteria:
Systems serving moderate- Semiannually (A) Listings by a testing laboratory.
volume cooking operations (B) Test data acceptable to the Authority
Systems serving low-volume cooking Annually Having Jurisdiction.
operations, such as churches, day camps, 515.1.2 Installation.
seasonal businesses, or senior centers 515.1.2.1 All listed appliances shall be
installed in accordance with the terms of
514.3.1.1 Upon inspection, if found to be
their listings and the manufacturer's
contaminated with deposits from grease-
instructions.
laden vapors, the contaminated portions of
the exhaust system shall be cleaned by a 515.1.2.2 Cooking appliances requiring
properly trained, qualified, and certified protection shall not be moved, modified, or
company or person(s) acceptable to the rearranged without prior reevaluation of the
Authority Having Jurisdiction in accordance fire-extinguishing system by the system
with Section 514.3. [NFPA 96: 11.4.1] installer or servicing agent, unless otherwise
allowed by the design of the fire-
514.3.1.2 When a vent-cleaning service is
extinguishing system.
used, a certificate showing date of inspection
or cleaning shall be maintained on the Exception: Cooking appliances moved
premises. After cleaning is completed, the to perform maintenance and cleaning,
vent-cleaning contractor shall place or provided the appliances are returned to
display within the kitchen area a label their original positioning prior to
indicating the date cleaned and the name of cooking operations, and any dis-
the servicing company. It shall also indicate connected fire-extinguishing system
areas not cleaned. nozzles attached to the appliances are
reconnected in accordance with the
514.3.2 Flammable solvents or other flammable
manufacturer's listed design manual.
cleaning aids shall not be used.
515.1.2.3 All deep-fat fryers shall be
514.3.3 At the start of the cleaning process,
installed with at least a sixteen (16) inch
electrical switches that could be activated
(406.4 mm) space between the fryer and
accidentally shall be locked out.
surface flames from adjacent cooking
514.3.4 Components of the fire suppression equipment.
system shall not be rendered inoperable during
the cleaning process. Exception: Where a steel or tempered
glass baffleplate is installed at a
Exception: Servicing by properly trained
minimum eight (8) inches (203 mm) in
and qualified persons in accordance with
height between the fryer and surface
Section 514.2.
flames of the adjacent appliance.
514.3.5 Care shall be taken not to apply cleaning
515.2 Operating Controls. Deep-fat fryers shall be
chemicals on fusible links or other detection
equipped with a separate high-limit control in
devices of the automatic extinguishing system.
addition to the adjustable operating control
514.3.6 When cleaning procedures are completed, (thermostat) to shut off fuel or energy when the fat
all electrical switches and system components temperature reaches 475F (246C) at one (1) inch
shall be returned to an operable state. All access (25.4 mm) below the surface.
panels (doors) and cover plates shall be
replaced. Dampers and diffusers shall be 515.3 Cooking Equipment Maintenance. [NFPA
positioned for proper airflow. 96: 11.5]

85
515.3 516.3 2007 CALIFORNIA MECHANICAL CODE

515.3.1 An inspection and servicing of the substitution or exchange of cooking appliances,


cooking equipment shall be made at least filter components, blower components, or fire-
annually by properly trained and qualified extinguishing system components that would
persons. [NFPA 96: 11.5.1] violate the listing of the appliance.
515.3.2 Cooking equipment that collects grease 516.2.3 A recirculating system shall not use
below the surface, behind the equipment, or in cooking equipment that exceeds that
cooking equipment flue gas exhaust, such as recirculating system's labeled maximum limits
griddles or charbroilers, shall be inspected and, for that type of equipment, stated in maximum
if found with grease accumulation, cleaned by a energy input, maximum cooking temperature,
properly trained, qualified, and certified person and maximum square area of cooking surface or
acceptable to the authority having jurisdiction. cubic volume of cooking cavity. [NFPA
[NFPA 96: 11.5.2] 96:13.2.6]
516.2.4 A fire-actuated damper shall be installed
516.0 Recirculating Systems. at the exhaust outlet of the system. The damper
shall be constructed of at least the same gauge as
516.1 General Requirements. Recirculating the shell. The actuation device shall have a
systems containing or for use with appliances used maximum temperature rating of 375F (190C).
in processes producing smoke or grease-laden
vapors shall be equipped with components 516.2.5 No electrical wiring shall be installed
in the interior sections of the hood plenum that
complying with the following:
might become exposed to grease.
(A) The clearance requirements of Section 507.2.
Exception: As permitted by California
(B) A hood complying with the requirements of Electrical Code.
Section 508.0.
516.2.6 The power supply of any electrostatic
(C) Grease removal devices complying with precipitator (ESP) shall be of the "cold spark,"
Section 509.0. ferro-resonant type in that the voltage falls off as
(D) The air movement requirements of Sections the current draw of a short increases.
511.2.1 and 511.2.2. 516.2.7 Listing evaluation shall include the
(E) Auxiliary equipment (such as particulate following:
and odor removal devices) complying with (A) Capture and containment of vapors at
Section 512.0. published and labeled airflows.
(F) Fire-extinguishing equipment complying (B) Grease discharge at the exhaust outlet
with the requirements of Section 513.0. of the system not to exceed an average
Exception: References to ducts in of 5 mg/m3 of exhausted air sampled
Sections 513.1.1 and 513.5.1. from that equipment at maximum
amount of product that is capable of
(G) The use and maintenance requirements of being processed over a continuous eight
514.0. (8) hour test per EPA Test Method 202,
(H) The minimum safety requirements of Determination of Condensable Par-
Section 515.0. ticulate Emissions for Stationary
(I) All the requirements of this chapter. Sources, with the system operating at its
minimum listed airflow.
516.2 Design Restrictions. All recirculating
systems shall comply with Section 516.2. (C) Listing and labeling of clearance to
combustibles from all sides, top, and
516.2.1 Only gas- or electrically fueled cooking
bottom.
appliances shall be used. Gas-fueled appliances
shall not have the combustion flue outlet(s) (D) Electrical connection in the field in
directly connected to the recirculating system. Gas- accordance with California Electrical Code.
fueled appliances shall have a minimum eighteen (E) Interlocks on all removable components
(18) inch (457.2 mm) clearance from the flue outlet that lie in the path of airflow within the
to the filter inlet in accordance with Section 509.2.2 unit to ensure that they are in place during
and shall meet the installation requirements of operation of the cooking appliance.
NFPA 54, National Fuel Gas Code, or NFPA 58, 516.3 Interlocks. The recirculating system shall be
Liquefied Petroleum Gas Code. provided with interlocks of all critical components
516.2.2 Recirculating systems shall be listed and operations as indicated in Sections 516.3.1
with a testing laboratory. There shall be no through 516.3.4 such that, if any of these interlocks

86
EXHAUST SYSTEMS 516.3 517.2

are interrupted, the cooking appliance shall not be with the manufacturer's instructions shall be
able to operate. performed by qualified service personnel a
516.3.1 All closure panels encompassing minimum of once every six (6) months, or more
airflow sections shall have interlocks to ensure frequently if required.
the panels are in place and fully sealed. Exception: Fire-extinguishing equipment
516.3.2 Each filter component (grease and odor) shall be inspected in accordance with
Section 514.2.
shall have an interlock to prove the component
is in place. 516.6.6 A signed and dated log of maintenance
as performed in accordance with Sections 516.6.4
516.3.3 Each ESP shall have a sensor to prove its
and 516.6.5 shall be available on the premises for
performance is as designed, with no interruption
use by the Authority Having Jurisdiction.
of the power to exceed two (2) minutes. This
sensor shall be a manual reset device or circuit.
516.3.4 An airflow switch or transducer shall be 517.0 Solid-Fuel Cooking Operations.
provided after the last filter component to 517.1 Venting Application. Venting requirements
ensure that a minimum airflow is maintained. of solid-fuel cooking operations shall be determined
This device opens the interlock circuit when the in accordance with Sections 517.1.1 through 517.1.6.
airflow falls 25 percent below the system's 517.1.1 Where solid-fuel cooking equipment is
normal operating flow or 10 percent below its required by the manufacturer to have a natural
listed minimum rating, whichever is lower. This draft, the vent shall comply with Section 517.4.
switch or transducer shall be a manual reset
device or circuit. 517.1.2 Where the solid-fuel cooking equipment
has a self-contained top, is the only appliance to
516.4 Location and Application Restrictions. The
be vented in an isolated space (except for a single
location of recirculating systems shall be approved by
water heater with its own separate vent), has a
the Authority Having Jurisdiction. Items to be reviewed
separate makeup-air system, and is provided
in the fire risk assessment shall include, but not be
limited to, life safety, combustibility of surroundings, with supply and return air (not supplied or
proximity to air vents, and total fuel load. returned from other spaces), the system shall
comply with Sections 517.4 and 517.6.
516.5 Additional Fire Safety Requirements.
517.1.3 Where the solid-fuel cooking equipment
516.5.1 In addition to the appliance nozzle(s), a
recirculating system shall be listed with the is located in a space with other vented
appropriate fire protection for grease filters, equipment, all vented equipment shall have an
grease filtration, odor filtration units, and exhaust system interlocked with a makeup-air
ductwork where applicable. system for the space as per Section 517.6.
516.5.2 In addition to any other fire-extinguishing 517.1.4 Natural draft ventilation systems and
system actuation device, there shall be a fire- power-exhausted ventilation systems shall
extinguishing system actuation device installed comply with Sections 517.3, 517.4, and 517.6.
downstream of any ESP. 517.1.5 Where a solid-fuel cooking appliance
516.5.3 The requirements of Section 513.6 shall allows effluent to escape from the appliance
also apply to recirculating system locations. opening, this opening shall be covered by a hood
516.6 Use and Maintenance. and an exhaust system that meets the
516.6.1 Automatic or manual covers on cooking requirements of Sections 517.3, 517.4, and 517.6.
appliances, especially fryers, shall not interfere 517.1.6 Solid-fuel cooking operations shall have
with the application of the fire suppression system. spark arresters to minimize the passage of
516.6.2 All filters shall be cleaned or replaced in airborne sparks and embers into plenums and
accordance with the manufacturer's instructions. ducts. Where the solid-fuel cooking operation is
516.6.3 All ESPs shall be cleaned a minimum of not located under a hood, a spark arrester shall
once per week following manufacturer's be provided to minimize the passage of sparks
cleaning instructions. and embers into flues and chimneys.
516.6.4 The entire hood plenum and the blower 517.2 Location of Appliances.
section shall be cleaned a minimum of once
517.2.1 Every appliance shall be located with
every three (3) months.
respect to building construction and other
516.6.5 Inspection and testing of the total equipment so as to permit access to the appliance.
operation and all safety interlocks in accordance

87
517.2 517.7 2007 CALIFORNIA MECHANICAL CODE

517.2.2 Solid-fuel cooking appliances shall not these sparks and embers into the grease removal
be installed in confined spaces. The space or device and into the hood and duct system.
room shall be of ample size to permit adequate 517.5.2 Filters shall be a minimum of four (4)
circulation of heated air. feet (1.2 m) above the appliance cooking surface.
Exception: Solid-fuel cooking appliances 517.6 Air Movement for Solid-Fuel Cooking.
listed for installation in confined spaces Exhaust system requirements shall comply with the
such as alcoves shall be installed in provisions of the code for hooded operation or shall
accordance with the terms of the listing and be installed in accordance with the manufacturer's
the manufacturer's instructions. recommendation for unhooded applications.
517.2.3 Solid-fuel cooking appliances shall not 517.6.1 A replacement or makeup-air system
be installed in any location where gasoline or shall be provided to ensure a positive supply of
any other flammable vapors or gases are likely replacement air at all times during cooking
to be present. operations.
517.3 Hoods for Solid-Fuel Cooking. 517.6.2 Makeup-air systems serving solid-fuel
517.3.1 Hoods shall be sized and located in a cooking operations shall be interlocked with the
exhaust-air system and powered, if necessary, to
manner capable of capturing and containing all
prevent the space from attaining a negative pressure
of the effluent discharging from the appliances.
while the solid-fuel appliance is in operation.
The hood and its exhaust system shall comply
with the provisions of the code. 517.7 Fire-Extinguishing Equipment for Solid-
Fuel Cooking.
517.3.2 All solid-fuel cooking equipment
served by hood and duct systems shall be 517.7.1 Approved fire-extinguishing equipment
separate from all other exhaust systems. shall be provided to protect all solid-fuel-
burning cooking appliances that might be a
Exception: Cooking equipment not requiring source of ignition of grease in the hood, grease
automatic fire-extinguishing equipment (as removal device, or duct.
per the provisions of Section 510.0) shall be
Exception: If acceptable to the Authority
permitted to be installed under a common
Having Jurisdiction, solid-fuel-burning
hood with solid-fuel cooking equipment that
cooking appliances constructed of solid
is served by a duct system separate from all
masonry or reinforced portland or refractory
other exhaust systems.
cement concrete and vented in accordance
517.4 Exhaust Systems for Solid-Fuel Cooking. with NFPA 211, Standard for Chimneys,
Where a hood is not required, in buildings where the Fireplaces, Vents, and Solid FuelBurning
duct system is three stories or less in height, a duct Appliances, Chapters 3 and 4, shall not require
complying with Section 510.0 shall be provided. fixed automatic fire-extinguishing equipment.
517.4.1 If a hood is used, the duct system shall 517.7.2 Approved fire-extinguishing equipment
conform with the Section 510.0. shall be provided for the protection of grease
517.4.2 A listed or approved grease duct system removal devices, hoods, and duct systems.
shall be provided for solid-fuel cooking exhaust Exception: If acceptable to the Authority
systems that are four stories in height or greater. Having Jurisdiction, solid-fuel-burning
517.4.3 Where a hood is used, the duct system cooking appliances constructed of solid
shall conform with the requirements of Section masonry or reinforced portland or refractory
510.0. cement concrete and vented in accordance
with NFPA 211, Standard for Chimneys,
517.4.4 Wall terminations of solid-fuel exhaust Fireplaces, Vents, and Solid FuelBurning
systems shall be prohibited. Appliances, Chapters 3 and 4, shall not require
517.5 Grease Removal Devices for Solid-Fuel automatic fire-extinguishing equipment.
Cooking. Grease removal devices shall be 517.7.3 Approved fire-extinguishing equipment
constructed of steel or stainless steel or be approved for solid-fuel-burning cooking appliances, where
for solid-fuel cooking. required, shall comply with NFPA 211 and shall
517.5.1 If airborne sparks and embers can be be comprised of water-based agents.
generated by the solid-fuel cooking operation, 517.7.4 Fire-extinguishing equipment shall be
spark arrester devices shall be used prior to the rated and designed to extinguish solid-fuel
grease removal device to minimize the entrance of cooking fires, in accordance with the manufacturer's

88
EXHAUST SYSTEMS 517.7 517.8

recommendations. The fire-extinguishing devices of any type in any portion of the


equipment shall be of sufficient size to totally appliance, flue pipe, and chimney of a natural
extinguish fire in the entire hazard area and draft solid-fuel operation.
prevent reignition of the fuel. 517.8.4 No solid-fuel cooking device of any
517.7.5 All solid-fuel appliances (whether or not type shall be permitted for deep-fat frying
under a hood) with fireboxes of 5 ft.3 (0.14 m3) involving more than one (1) quart of liquid
volume or less shall at least have a listed 2-A- shortening, nor shall any solid-fuel cooking
rated water-type fire extinguisher or a 1.6 gal (6 device be permitted within three (3) feet (0.92 m)
L) wet chemical fire extinguisher listed for Class of any deep-fat frying unit.
K fires in accordance with NFPA 10, in the
immediate vicinity of the appliance. [NFPA
96:14.7.8]
517.7.6 Solid-fuel appliances with fireboxes
exceeding 5 ft.3 (0.14 m3) shall be provided with a
fixed-water-pipe system with a hose in the
immediate vicinity of the appliance. [NFPA
96:14.7.9.1] The hose shall be equipped with an
adjustable nozzle capable of producing a fine to
medium spray or mist. [NFPA 96 14.7.9.1.1] The
nozzle shall be of the type that cannot produce a
straight stream. [NFPA 96 14.7.9.1.2] The system
shall have a minimum operating pressure of 40 psi
(275.8 kPa) and shall provide a minimum of 5 gpm.
[NFPA 96:14.7.9.2]
517.7.7 Fire suppression for fuel storage areas
shall comply with Section 517.9.
517.7.8 In addition to the requirements of
Sections 517.7.5 or 517.7.6, where any solid-fuel
cooking appliance is also provided with
auxiliary electric, gas, oil, or other fuel for
ignition or supplemental heat and the appliance
is also served by any portion of a fire-
extinguishing system complying with Section
513.0, such auxiliary fuel shall be shut off upon
actuation of the fire-extinguishing system.
517.8 Other Safety Requirements.
517.8.1 Metal-fabricated solid-fuel cooking
appliances shall be listed for the application
where produced in practical quantities or shall be
approved by the Authority Having Jurisdiction.
When listed, they shall be installed in accordance
with the terms of their listings and with the
applicable requirements of this standard.
517.8.2 Site-built solid-fuel cooking appliances
shall be submitted for approval to the Authority
Having Jurisdiction before being considered for
installation. All units shall be installed, operated,
and maintained in accordance with the
approved terms of the manufacturer's instruc-
tions and any additional requirements set forth
by the Authority Having Jurisdiction.
517.8.3 Except for the spark arrester required in
Section 517.1.6, there shall be no additional

89
Table 5-5 2007 CALIFORNIA MECHANICAL CODE

TABLE 5-5
Minimum Sheet Metal Thickness for Round Ducts for Product-Conveying System Ducts

Reinf. Class 1
Negative Spacing
Pressure (Inches) Up to 7" 8" to 11" 12" to 15" 16" to 19" 20" to 23" 24" to 35" 36" to 47" 48" to 59" 60"

To 7" 0 .021 (24 ga.) .021 (24 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .127 (10 ga.)
96 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.)
48 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.)
24 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.)

8" to 11" 0 .021 (24 ga.) .027 (22 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.)
96 .021 (24 ga.) .027 (22 ga.) .027 (22 ga.) .044 (18 ga.) .044 (18 ga.) .044 (18 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
48 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.)
24 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .027 (22 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.)

12" to 15" 0 .021 (24 ga.) .033 (20 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
96 .021 (24 ga.) .027 (22 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .097 (12 ga.) .112 (11 ga.) .112 (11 ga.)
48 .021 (24 ga.) .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.)
24 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .027 (22 ga.) .027 (22 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

16" to 20" 0 .021 (24 ga.) .044 (18 ga.) .068 (14 ga.) .097 (12 ga.) .112 (11 ga.)
96 .021 (24 ga.) .033 (20 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.)
48 .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .112 (11 ga.)
24 .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.)
Class 2
To 7" 0 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .127 (10 ga.)
96 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.)
48 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)
24 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

8" to 11" 0 .027 (22 ga.) .027 (22 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.)
96 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .044 (18 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
48 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.)
24 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

12" to 15" 0 .027 (22 ga.) .033 (20 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
96 .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .097 (12 ga.) .112 (11 ga.) .112 (11 ga.)
48 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.)
24 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

16" to 20" 0 .027 (22 ga.) .044 (18 ga.) .068 (14 ga.) .097 (12 ga.) .112 (11 ga.)
96 .027 (22 ga.) .033 (20 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.)
48 .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.)
24 .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

Class 3
To 7" 0 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .127 (10 ga.)
96 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)
48 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)
24 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)

8" to 11" 0 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.)
96 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
48 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)
24 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)

90
EXHAUST SYSTEMS Table 5-5 Table 5-6

TABLE 5-5 (Continued)


Minimum Sheet Metal Thickness for Round Ducts for Product-Conveying System Ducts
Reinf. Class 3
Negative Spacing
Pressure (Inches) Up to 7" 8" to 11" 12" to 15" 16" to 19" 20" to 23" 24" to 35" 36" to 47" 48" to 59" 60"
12" to 15" 0 .033 (20 ga.) .033 (20 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
96 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .097 (12 ga.) .112 (11 ga.) .112 (11 ga.)
48 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)
24 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068(14 ga.) .068 (14 ga.)

16" to 20" 0 .033 (20 ga.) .044 (18 ga.) .068 (14 ga.) .097 (12 ga.) .112 (11 ga.)
96 .033 (20 ga.) .033 (20 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11ga.) .112 (11 ga.)
48 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.)
24 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)
Class 4
To 7" 0 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .127 (10 ga.)
96 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
48 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
24 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)

8" to 11" 0 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.)
96 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
48 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
24 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)

12" to 15" 0 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
96 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .112 (11 ga.) .112 (11 ga.)
48 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
24 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)

16" to 20" 0 .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .112 (11 ga.)
96 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.)
48 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
24 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) 0.097 (12 ga.)

TABLE 5-6
Minimum Sheet Metal Thickness for Rectangular Ducts

Longest Side of Duct


Class 1 Class 2
Negative Reinf.
Pressure Spacing Up to 12" 13" to 24" 25" to 36" 37" to 48" 49" to 60" Up to 12" 13" to 24" 25" to 36" 37" to 48" 49" to 60"

To 7" 48 .021 (24 ga.) .033 (20 ga.) .055 (16 ga.) .068 (14 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.)
To 7" 24 .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)
To 7" 12 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

8" to 11" 48 .027 (22 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .033 (20 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
8" to 11" 24 .027 (22 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .033 (20 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.)
8" to 11" 12 .021 (24 ga.) .027 (22 ga.) .027 (22 ga.) .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

12" to 15" 48 .044 (18 ga.) .097 (12 ga.) .044 (18 ga.) .044 (18 ga.)
12" to 15" 24 .044 (18 ga.) .055 (16 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.) .044 (18 ga.) .044 (18 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
12" to 15" 12 .027 (22 ga.) .044 (18 ga.) .044 (18 ga.) .044 (18 ga.) .044 (18 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

16" to 20" 48 .068 (14 ga.) .112 (11 ga.) .068 (14 ga.) .112 (11 ga.)
16" to 20" 24 .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.) .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.)
16" to 20" 12 .033 (20 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .033 (20 ga.) .044 (18 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)
Class 3 Class 4
To 7" 48 .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
To 7" 24 .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
To 7" 12 .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)

8" to 11" 48 .044 (18 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
8" to 11" 24 .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
8" to 11" 12 .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)

12" to 15" 48 .044 (18 ga.) .097 (12 ga.) .055 (16 ga.) .097 (12 ga.)
12" to 15" 24 .044 (18 ga.) .055 (16 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
12" to 15" 12 .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)

16" to 20" 48 .068 (14 ga.) .112 (11 ga.) .055 (16 ga.) .112 (11 ga.)
16" to 20" 24 .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.) .055 (16 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.)
16" to 20" 12 .044 (18 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)

91
Table 5-7 Table 5-8 2007 CALIFORNIA MECHANICAL CODE

TABLE 5-7
Construction, Clearance, and Termination Requirements for Unlisted Single-Wall Metal Chimneys

MINIMUM THICKNESS TERMINATION CLEARANCE


ABOVE ABOVE ANY PART COMBUSTIBLE NONCOMBUSTIBLE
ROOF OF BUILDING WITHIN CONSTRUCTION CONSTRUCTION

CHIMNEYS SERVING WALL LINING OPENING 10' 25' 50' Interior Inst. Exterior Inst. Interior Inst. Exterior Inst.
Building-heating and
industrial-type low-heat 0.127"
appliances (1,000F (Mfs. Std. None 3' 2' 18" 6"
operating-1,400F 10 ga.)
temp. maximum)1 Up to 18" diameter, 2"
Medium-heat industrial- 0.127" Up to 18" Over 18" diameter, 4"
trial-type appliances (Mfrs. Std. dia.2-1/2"
(2,000F maximum)1, 3 10 ga.) Over 18" 10' 10' 36" 24"
4-1/2" on 4-1/2" bed
High-heat industrial- 0.127" 4-1/2" laid
appliances (Mfrs. Std. on 4-1/2" 20' 20' See footnote 3
(Over 2,000F)1, 2 10 ga. ) bed
Residential-type 0.127" (Mfrs.
None 3' 2' Not permitted 18" Not permitted 4"
incinerator4 Std. 10 ga.)

1. Lining shall extend from bottom to top of chimney. inches x 25.4 = mm


2. Lining shall extend from 24 inches (610 mm) below connector to 24 feet (7,315 mm) above. feet x 304.8 = mm
3. Clearance shall be as specified by the design engineer and shall have sufficient clearance from buildings (F - 32) x 5/9 = C
and structures to avoid overheating combustible materials [maximum 160F (71C)].

TABLE 5-8
Vent Selection Chart
Column I
Type B, Gas Column II Column III Column IV
Round or Oval Type BW Gas Type L Plastic Pipe
All listed gas appliances 1. Gas-burning wall 1. Oil-burning appliances 1. Condensing appli-
with draft hoods such as: heaters listed for use listed for use with ances listed for use
with Type BW vents Type L vents with a specific
1. Central furnaces plastic pipe
2. Floor furnaces 2. Gas appliances as recommended
3. Heating boilers shown in column I and identified in the
4. Ranges and ovens manufacturers
5. Recessed wall furnaces installation
instructions
(above wall section)
6. Room and unit heaters
7. Water heaters

92

Vous aimerez peut-être aussi