Académique Documents
Professionnel Documents
Culture Documents
This article looks at the calculation of short circuit currents for bolted three-phase and single-phase
to earth faults in a power system. A short circuit in a power system can cause very high currents to
flow to the fault location. The magnitude of the short circuit current depends on the impedance of
system under short circuit conditions. In this calculation, the short circuit current is estimated using
the guidelines presented in IEC 60909.
Calculating the prospective short circuit levels in a power system is important for a number of
reasons, including:
To specify fault ratings for electrical equipment (e.g. short circuit withstand ratings)
To help identify potential problems and weaknesses in the system and assist in
system planning
The calculation can be done after preliminary system design, with the following pre-requisite
documents and design tasks completed:
Calculation Methodology
This calculation is based on IEC 60909-0 (2001, c2002), "Short-circuit currents in three-phase a.c.
systems - Part 0: Calculation of currents" and uses the impedance method (as opposed to the per-
unit method). In this method, it is assumed that all short circuits are of negligible impedance (i.e. no
arc impedance is allowed for).
Step 1: Construct the system model and collect the relevant equipment parameters
Step 2: Calculate the short circuit impedances for all of the relevant equipment
The first step is to construct a model of the system single line diagram, and then collect the relevant
equipment parameters. The model of the single line diagram should show all of the major system
buses, generation or network connection, transformers, fault limiters (e.g. reactors), large cable
interconnections and large rotating loads (e.g. synchronous and asynchronous motors).
Network feeders: fault capacity of the network (VA), X/R ratio of the network
Asynchronous motors: full load current (A), locked rotor current (A), rated power
(W), full load power factor (pu), starting power factor (pu)
Fault limiting reactors: reactor impedance voltage (%), rated current (A)
Network Feeders
Given the approximate fault level of the network feeder at the connection point (or point of
common coupling), the impedance, resistance and reactance of the network feeder is calculated as
follows:
The sub-transient reactance and resistance of a synchronous generator or motor (with voltage
regulation) can be estimated by the following:
is the X/R ratio, typically 20 for 100MVA, 14.29 for 100MVA, and 6.67
for all generators with nominal voltage 1kV
is a voltage factor which accounts for the maximum system voltage (1.05 for voltages
<1kV, 1.1 for voltages >1kV)
is the power factor of the generator (pu)
For the negative sequence impedance, the quadrature axis sub-transient reactance can be
applied in the above equation in place of the direct axis sub-transient reactance .
The zero-sequence impedances need to be derived from manufacturer data, though the voltage
correction factor also applies for solid neutral earthing systems (refer to IEC 60909-0 Clause
3.6.1).
Transformers
For the calculation of impedances for three-winding transformers, refer to IEC 60909-0 Clause
3.3.2. For network transformers (those that connect two separate networks at different voltages), an
impedance correction factor must be applied (see IEC 60909-0 Clause 3.3.3).
The negative sequence impedance is equal to positive sequence impedance calculated above. The
zero sequence impedance needs to be derived from manufacturer data, but also depends on the
winding connections and fault path available for zero-sequence current flow (e.g. different neutral
earthing systems will affect zero-sequence impedance).
Cables
Cable impedances are usually quoted by manufacturers in terms of Ohms per km. These need to be
converted to Ohms based on the length of the cables:
The negative sequence impedance is equal to positive sequence impedance calculated above. The
zero sequence impedance needs to be derived from manufacturer data. In the absence of
manufacturer data, zero sequence impedances can be derived from positive sequence impedances
via a multiplication factor (as suggested by SKM Systems Analysis Inc) for magnetic cables:
Asynchronous Motors
The negative sequence impedance is equal to positive sequence impedance calculated above. The
zero sequence impedance needs to be derived from manufacturer data.
The impedance of fault limiting reactors is as follows (note that the resistance is neglected):
Positive, negative and zero sequence impedances are all equal (assuming geometric symmetry).
Other Equipment
Static converters feeding rotating loads may need to be considered, and should be treated similarly
to asynchronous motors.
Line capacitances, parallel admittances and non-rotating loads are generally neglected as per IEC
60909-0 Clause 3.10. Effects from series capacitors can also be neglected if voltage-limiting
devices are connected in parallel.
Where there are multiple voltage levels, the equipment impedances calculated earlier need to be
converted to a reference voltage (typically the voltage at the fault location) in order for them to be
used in a single equivalent circuit.
Using the winding ratio, impedances (as well as resistances and reactances) can be referred to the
primary (HV) side of the transformer by the following relation:
Conversely, by re-arranging the equation above, impedances can be referred to the LV side:
The system model must first be simplified into an equivalent circuit as seen from the fault location,
showing a voltage source and a set of complex impedances representing the power system
equipment and load impedances (connected in series or parallel).
The next step is to simplify the circuit into a Thvenin equivalent circuit, which is a circuit
containing only a voltage source ( ) and an equivalent short circuit impedance ( ).
This can be done using the standard formulae for series and parallel impedances, keeping in mind
that the rules of complex arithmetic must be used throughout.
If unbalanced short circuits (e.g. single phase to earth fault) will be analysed, then a separate
Thvenin equivalent circuit should be constructed for each of the positive, negative and zero
sequence networks (i.e. finding ( , and ).
The initial symmetrical short circuit current is calculated from IEC 60909-0 Equation 29, as
follows:
is the voltage factor that accounts for the maximum system voltage (1.05 for voltages
<1kV, 1.1 for voltages >1kV)
is the nominal system voltage at the fault location (V)
is the equivalent positive sequence short circuit impedance ()
IEC 60909-0 Section 4.3 offers three methods for calculating peak short circuit currents, but for the
sake of simplicity, we will only focus on the X/R ratio at the fault location method. Using the real
(R) and reactive (X) components of the equivalent positive sequence impedance , we can
calculate the X/R ratio at the fault location, i.e.
The symmetrical breaking current is the short circuit current at the point of circuit breaker opening
(usually somewhere between 20ms to 300ms). This is the current that the circuit breaker must be
rated to interrupt and is typically used for breaker sizing. IEC 60909-0 Equation 74 suggests that the
symmetrical breaking current for meshed networks can be conservatively estimated as follows:
Where is the symmetrical breaking current (A)
For close to generator faults, the symmetrical breaking current will be higher. More detailed
calculations can be made for increased accuracy in IEC 60909, but this is left to the reader to
explore.
The dc component of a short circuit can be calculated according to IEC 60909-0 Equation 64:
Where and are the reactance and resistance, respectively, of the equivalent source
impedance at the fault location ()
is a factor to account for the equivalent frequency of the fault. Per IEC 60909-0 Section
4.4, the following factors should be used based on the product of frequency and time (
):
<1 0.27
<2.5 0.15
<5 0.092
<12.5 0.055
The initial short circuit current for a single phase to earth fault is as per IEC 60909-0 Equation 52:
Where is the initial single phase to earth short circuit current (A)
is the voltage factor that accounts for the maximum system voltage (1.05 for voltages
<1kV, 1.1 for voltages >1kV)
is the nominal voltage at the fault location (Vac)
is the equivalent positive sequence short circuit impedance ()
is the equivalent negative sequence short circuit impedance ()
is the equivalent zero sequence short circuit impedance ()
Worked Example
In this example, short circuit currents will be calculated for a balanced three-phase fault at the main
11kV bus of a simple radial system. Note that the single phase to earth fault currents will not be
calculated in this example.
Equipment Parameters
= 24,150 kVA
= 11,000 V
Generator G1
= 0.255 pu
= 0.85 pu
Length = 30m
= 500 kW
= 11,000 V
= 200.7 A
Motor M1
= 6.5 pu
= 0.85 pu
= 0.30 pu
Length = 150m
= 11,000 V
= 415 V
Transformer TX1
= 0.0625 pu
= 19,000 W
= 0%
Length = 100m
= 90 kW
= 415 V
= 1,217.3 A
Motor M2
= 7 pu
= 0.8 pu
= 0.30 pu
Motor M3
= 150 kW
= 415 V
= 1,595.8 A
= 6.5 pu
= 0.85 pu
= 0.30 pu
Using the patameters above and the equations outlined earlier in the methodology, the following
impedances were calculated:
We will model a fault on the main 11kV bus, so all impedances must be referred to 11kV. The two
low voltage motors need to be referred to this reference voltage. Knowing that the transformer is set
at principal tap, we can calculate the winding ratio and apply it to refer the 415V motors to the
11kV side:
kA
kA
Computer Software
Short circuit calculations are a standard component of power systems analysis software (e.g. ETAP,
PTW, DIgSILENT, etc) and the calculations are far easier to perform with software than by hand.
However manual calculations could be done as a form of verification to confirm that the software
results are reasonable.
What Next?
The results from the short circuit calculations can be used to specify the fault ratings on electrical
equipment (e.g. switchgear, protective devices, etc) and also for protection coordination studies