Type of Occupancy: Educational

Automatic Fire Suppression System(AFSS)


a. Building is 15 mt or more in height
b. Basement used as a classroom or laboratory
Standpipe System
a. WET for 4 or more storeys in height
b. DRY All buildings with required enclosed stairway or smoke-proof enclosure
Fire Detection Alarm and Communication System
a. MANUAL Every educational building
b. AUTOMATIC If building is protected with AFSS
Portable Fire Extinguisher
REQUIRED

DEFECTS/DEFICIENCIES NOTED DURING INSPECTION


I. GRADE SCHOOL DEPARTMENT
1. De Gryse building (3-Storey)
a. Downgraded 1 unit Fire ext 3rd floor - Recondition (1 unit)
b. No emergency light -2nd and 3rd floor - Provide (2 units)
2. Jurgens building (4-Storey)
a. No wet standpipe system installed - Install
b. No emergency light 2nd and 4th floor - Provide (2units)
c. Closed alternate fire exit ladder - Open
3. St. Alloysius building 3-Storey
4. John Paul building (3-Storey)
a. No emergency light -2nd and 3rd floor - Provide (2 units)

II. HIGH SCHOOL DEPARTMENT


1. Florentina building (4-storey)
a. No wet standpipe system installed - To Install
b. Defective emergency light 2nd and 3rd floor - replace 2 units
2. Administration building (3-storey)
a. Insufficient Fire fighting appliance at the computer lab. - Add/install 1 unit
HCFC123 Fire Extinguisher
III. COLLEGE DEPARTMENT
1. JVD building (5-storey)
a. No wet standpipe installed - Install
b. Insufficient no. of emergency lights - provide
c. Fire Extinguisher problem - recondition
d. No Luminous exit signs - provide
e. No Evacuation diagram - provide
2. Tonus Gymnasium (3-storey mezzanine)
a. No cover of panel board/ improper electrical wiring at main switch - rectify
b. No ventilation in stock room - provide ventilation
c. Fire extinguisher problem - recondition
3. CL building (3-storey)
a. Fire extinguisher - recondition
4. RT building (4-storey)
a. No wet standpipe system - install
b. No emergency lights in all floor - provide
5. JVB building (4-storey)
a. No wet standpipe system - install
b. Inadequate emergency lights - provide
c. No luminous exit signs - provide
d. No smoke detectors installed - install
e. Fire extinguisher problem - recondition
6. Jubilee Library (4-storey)
a. No wet standpipe system - install
b. Inadequate emergency lights - provide
c. No luminous exit signs - provide
d. No smoke detectors installed - install
e. Fire extinguisher problem - recondition
7. Constant Jurgens (3-storey)
a. Fire Extinguisher problem - recondition
8. Lambrecht building (2-storey)
a. NO Violation
9. Apo Pilo building (4-storey)
a. No wet standpipe system installed - install
b. No emergency lights - provide
10.Hantson building (5-storey)
a. No wet standpipe system installed - install
b. No fire alarm system - install
c. Fire extinguisher problem - recondition
11.Gomburza building (2-storey)
a. Defective 2 units emergency light - replace
12.Chapel (2-storey)
a. Inadequate fire fighting appliance - provide
13.Engg Workshop / S-Lab (1-storey)
a. One unit fire fighting appliance - recondition
14.RS building (2-storey)
a. Defective fire alarm system - replace
b. No emergency lights installed - provide
c. Fire extinguisher problem - recondition
15.Mauritz Van Overbergh building (2-storey)
a. No fire alarm system installed - install
b. No emergency lights installed - provide
c. No luminous fire exit signs - provide
16.Pharma/Medtech building
a. No violation
17.HRM Extension building
a. No violation
ST. MARYS UNIVERSITY
Bayombong, Nueva Vizcaya
PHYSICAL PLANT, PROPERTIES DEVELOPMENT & MAINTENANCE OFFICE
SUMMARY
Grade High JVD Gy CL RT JVB Jubile U A A H S Chape Engg R CNS Pharm HRM
School School m e B P l W/Sho S (New a Ext
p )
1 1 I 1 1 1 1 1
WET -Jurgens -Florenti
STANDPIPE na
EMERGENCY III + II II IIII II I I I I I I
LIGHTS

EVACUATION 1
PLAN

LUMINOUS 1 I I I
SIGNS

FIRE I I IIII II I I I I I I I I
EXTINGUISH
ER

SMOKE III I
DETECTOR

I I I
FIRE ALARM

ELECTRICAL I
PROBLEM