Académique Documents
Professionnel Documents
Culture Documents
1002
PAGE
1002-1. General Requirements. The equipment under this Specification will be used at
2301115 kV, 230/69 kV and 115 kV substations ofEGAT power system. The
equipment 'will be extended to the existing equipment or newly constructed as
indicated on the drawings for each substation. The Contractor shall furnish,
assemble and wire all instruments, control and instrument switches,
annunciators, protective relays and other equipment mounted on the panels.
All equipment must meet the requirements as defined in this Specification.
1002-2. Information Required of the Bidder. The Bidder shall submit with his bid the
name of the manufacturer, and the type or model of the equipment offered.
Technical data, descriptive information, drawings and catalogs showing all
significant characteristics and details, principles of operation, general
arrangement and dimensions, shall also be included to enable EGAT to
determine the suitability of the equipment for its purposes. Where Proposal
Data Forms are provided, the Bidders shall enter all information as directed.
These requirements from the Bidders are very essential, and failure of any
Bidder to comply with these requirements may constitute reasonable cause for
EGAT to cancel a part or all the Proposal from that Bidder.
1002-3. Codes and Standards. All equipment, materials, fabrication and testing under
this Specification shall conform to the latest applicable standard specifications
and codes contained in the following list, or to equivalent applicable standard
specifications and codes established and approved in the country of
manufacturer of the equipment. Where standards are mentioned by name,
equivalent applicable standards may be used.
Any details not specifically covered by these standards shall be subject to the
approval of EGAT. In the event of contradictory requirements between such
standards and this Specification, the terms of the Specification shall govern.
1002-5. Special Climatic Treatment. All materials shall be selected and especially
treated so that they will be satisfactory for use under the following climatic
conditions:
1002-6. Arrangement. The main control boards shall be of either the duplex type,
enclosed type, dual type or swing rack type as required and specified for each
substation in the drawings entitled : "Main Control Board Equipment Layout".
The main control boards under this Specification shall be designed for the
control and protection as indicated by the drawings and bill of materials, and as
specified herein. Protective relays and their associated auxiliary relays shall
perform the functions as sho\\-n on the drawing entitled : "Protective Device
Functions", for each substation. The Contractor shall furnish any necessary
control and protection functions indicated, mounted and wired as required,
whether such devices are itemized herein or not.
1002-7.1 Duplex Main Control Boards. The duplex main control board shall
consist of basic panel assemblies placed back-to-back at sufficient
distance to provide a tunnel-type walkway between the assemblies.
Bolted on floor channels, top sheets, wiring trays, left and right end
trims with access doors shall be provided to form a complete duplex
control board with uninterrupted walkway running the entire length of
the structure. The access doors shall be equipped with lock, latches
and fully concealed hinges, and with handles for opening from the
exterior and interior. End trims with access doors shall be readily
removable so as to permit future boards to be installed at both ends.
The duplex main control board panel size shall be 1,830 mm deep and
the height shall be 2,300 mm plus a 40 mm channel base. Panel
widths shall be as indicated on Drawings entitled : "Main Control
Board Equipment Layout", for each substation.
1002-7.2 Dual Main Control Boards. Each dual main control board shall
consist of basic panel assemblies placed back-to-back and necessary
bolted-on floor channels, top sheet, wiring trays and enclosed at both
ends. The front panel shall be hinged panel equipped with handle,
lock, latches and fully concealed hinges. The rear panel shall be
fixed. Each end trim shall be readily removable so as to permit future
board to be installed at both ends.
The dual control board panel size shall be 1,000 mm deep and the
height shall be 2,300 mm plus a 40 mm channel base. Panel widths
shall be as indicated on Drawings entitled : "Main Control Board
Equipment Layout", for each substation.
Each basic panel assembly for duplex and dual main control board
shall be a self-contained unit with factory wiring complete to
conveniently located terminal blocks for the incoming cables. Each
shall have vertical side members, which include vertical raceways and
raceway covers for factory wiring, and shall be bolted to the right and
left sides of the basic panel. These side members shall provide
separate raceways to house, protect, and conceal the incoming cables
and interpanelleads. Terminal blocks shall be furnished and mounted
in vertical rows on both sides of the basic panel assembly.
Suitable wire slots with rubber bushings in vertical rows on both sides
of the basic panel assembly near terminal blocks shall be provided for
outgoing leads.
1002-7.4
Swing Rack Type Protective Relay Switchboards. Each protective
relay switchboard shall be of the swing rack type, consisting of a
swing rack assembly, top sheet and rear enclosure covering the back
and ends of the entire structure. Each panel shall have a front cover
door equipped with a glass window for viewing all targets and
indications. The panel door shall be equipped with locking handle,
latches, fully concealed hinges, and complete with screened louvers at
the top and bottom.
The panel door shall be hinged on the right hand side, front view. The
relay rack assembly shall be hinged on the left hand side, front view.
Each panel shall be designed for mounting standard 19-inch wide
rack-mounted relays.
Each relay rack assembly shall be arranged to swing through not less
The switchboard size shall be 800 mm wide, 610 mm deep and the
height shall be 2,300 mm plus a 40 mm channel bases.
Each panel shall be 900 mm wide, 1,000 mm deep and the height
shall be 2,300 mm plus a 40 mm channel base.
Each panel shall have vertical side members, which include vertical
raceways and raceway covers for factory wiring, and shall be bolted
to the right and left sides of the panel. These side members shall
provide separate raceways to house, protect, and conceal the
incoming cables and interpanelleads.
Each panel shall be provided with cable entrance at the bottom of the
panel.
1002-7.6
Transducer Panels. Each transducer panel shall be provided with
transducers for substation metering and for use with the remote
terminal unit (RTU). All transducers shall be furnished, mounted and
completely wired.
Each transducer panel shall be 900 mm wide, 1,000 mm deep and the
height shall be 2,300 mm plus a 40 mm channel base.
Each panel shall have vertical side members, which include vertical
raceways and raceway covers for factory wiring, and shall be bolted
to the right and left sides of the panel. These side members shall
provide separate raceways to house, protect, and conceal the
incoming cables and interpanel leads.
Each panel shall be provided with cable entrance at the bottom of the
panel.
Each panel shall have vertical side members, which include vertical
raceways and raceway covers for factory wiring, and shall be bolted
to the right and left sides of the panel. These side members shall
provide separate raceways to house, protect, and conceal the
incoming cables and interpanelleads.
Each panel shall be provided with cable entrance at the bottom of the
panel.
1002-8. Drawings and Data Requirements. The Contractor shall submit for approval
the following drawings and data, sufficient to demonstrate fully that the
equipment to be furnished will conform to the requirements and intent of this
Specification.
1002-8.1 Metering and Relaying Diagrams. The metering and relaying single
line diagrams of each substation are included in this Specification.
The Contractor shall supply single line diagrams showing conformity
with the specified requirements indicating clearly changes
necessitated by the proposed equipment.
1002-8.2 Three Line Diagrams. Each three line diagram shall show voltage
and current connections to all metering and relaying equipment.
1002-8.4 DC Schematic Diagrams. All diagrams shall show the DC wiring for
control, indication, annunciation, protection, etc., arranged in a
schematic form and shall include the necessary wiring of all power
circuit breakers that received a trip signal from the protective relays
that are listed in the drawings, "Protective Device Functions", for
each substation.
1002-8.5 Logic Diagrams. Logic diagrams shall show details of the logic
circuits for each individual relay. These diagrams shall be required
for the system as a whole as well as for each individual relay and
component.
1002-8.10
Equipment Layout Diagrams of Switchboards and Panels. Each
equipment layout diagram shall show dimensions, location, and
general layout of all panels and all equipment to be located on the
panels.
The switchboards and panels proposed shall give the best optimum
result as called for in this Specification, and as basically required by
standard electrical engineering practice.
1002-10. Wiring. All wiring used within the main control boards, control switchboards,
protective relay switchboards, metering panels, interposing relay panels,
transducer panels, and marshalling panels shall conform to the NEC and
NEMA standards and shall be rated 600V, tinned, stranded copper switchboard
wire, polyethylene insulated and in gray color. All wiring shall be 1.5 mm2
except for current transformer circuits which shall be 2.5 mm2 • All hinged
wiring shall be extra flexible. After assembly, all control wiring shall be given
a dielectric test of 1,500 V between live parts and ground, and between
opposite polarities. Internal wiring of each basic panel assembly and each panel
shall be neatly and carefully installed in suitable wiring ducts with removable
covers and complete to conveniently located terminal blocks for connecting to
incoming and outgoing leads.
Before connected to the terminal blocks, all wiring shall be terminated with
blade-type cable rugs. Multiple wires in one cable rug shall not be acceptable.
The cable rugs shall perfectly match the terminal blocks and shall be plugged
in without any modifications to the cable rugs.
The terminal arrangement shall group all leads for each particular function to
facilitate connections to the incoming and outgoing cables. The arrangement
shall be subject to the approval of EGAT. Terminals for each CT circuit shall
be grouped together and separated from terminals for other CT circuits. At least
25 per cent spare terminals shall be provided on each group of terminal blocks
for terminating spare conductors in control cables and for future use, however a
minimum of one spare terminal shall be provided on each group of terminal
blocks.
All incoming and outgoing cables shall enter the switchboards and the panels
through cable slots in the floor underneath the switchboards and the panels.
Any control boards or panels that are split for shipment shall have terminal
blocks adjacent to the split and shall be provided with wiring required to
interconnect the split units.
1002-11. Power Supply Disconnects. Power supplies for panel mounted devices shall be
provided with miniature circuit breaker (MCB) connected to isolate the devices
from power supplies in the tripped or open condition. MCB shall be located
within the panels. Engraved nameplates shall be installed beside each set of
MCB for identification.
Except for voltage supply of the potential transformer secondary which supplies
to primary pilot relaying in Article 1002-11.3.3, 1002-11.3.4 and 1002-11.3.6,
sliding switch bridge terminal block shall be required instead ofMCB.
Power supply to each nature of control circuit and the potential transformer
secondary supply to each metering circuit shall be separated and required MCB
protection provided, including, but not limited to the following:
1002-11.1.1 Control circuit, including relay trip circuit, for each power
circuit breaker.
1002-11.1.4 Two control circuits for each 230 kV line protective relaying
scheme, one for pilot relaying scheme and the other for backup
relaying scheme.
1002-11.1.5 Control circuit for each 115 kV line protective relaying scheme
1002-11.1.10 Control circuit for each set of breaker failure relaying scheme
Detail circuit arrangements and MCB protection shall be approved by EGAT at the
time approval drawings are submitted by the Contractor.
1002-12. Terminal Block, Wire and Device Designations. Every point of terminal block
and wire shall be assigned a designation, with identical designation on each
corresponding terminal block and wire. This same designation shall also be
indicated in the schematic and wiring diagrams. As a rule, a designation will
not change until the wire is terminated or connected to other equipment. All
wiring shall be designated at both ends by printing on wire designation sleeves.
The name of ANSI standard device number of each device shall be marked on
the rear of the panels directly behind or adjacent to the corresponding device.
1002-13. Instrument Transformer Secondary Ratings and Station Service Power Supply
Ratings. Ratings of instrument transformers and station service power supply
will be indicated in bill of materials, and except as otherwise specified, all
equipment shall be designed and supplied to the following ratings:
Secondary Ratings
Current Transformer SA
Secondary Ratings
CPT and CT ratios will be indicated in the drawings and bill of materials)
1002-15. Indicating Lamps. All indicating and pilot lamp assemblies shall be of the light
emitting diode (LED), 125 V, switchboard type with color caps. The color caps
shall be red, green, white, blue or yellow as required. All lamp bulbs shall be
interchangeable, and shall be replaceable from the front of the panels.
1002-16. Light Boxes. Each light box, for indication of energized line or bus, shall be
the light emitting diode (LED), switchboard type. Each light box shall have a
white translucent nameplate with machine-engraved, black lettering
illuminated by the back light. Each nameplate shall be engraved in accordance
with the drawing entitled: "Main Control Board Nameplate Schedule".
All lamp bulbs shall be interchangeable, and shall be replaceable from the front
of the panels.
t002-17. Test Switches. Test switches shall be of the built-in type or separate type as
specified. Separate test switches shall be of the switchboard, back-connected
type, finished in dull black for front-of-panel mounting. All test switches shall
be arranged to completely isolate the instruments from the instrument
transformers and other external circuits and to provide means for testing either
from an external source of energy or from the instrument transformers by
means of multipole test plugs which shall be provided for the purpose. A
sufficient number of test plugs to make a complete test on one meter,
instrument, or relay shall be furnished for each type of test switch. All test
switches shall be arranged so that the current transformer secondary circuits
cannot be open-circuited in any position while the test plugs or cover plugs are
being inserted or removed.
Test switches and multipole test plugs shall be ABB, flexitest switches, type
FT-lor equivalent.
The tenninal blocks provided for CT circuits shall be of the spring-loaded screw
on type or screw-on type. The tenninal blocks provided for control, protection
circuits and other circuits shall be of the spring loaded screw-on type, screw-on
type or screwless type. The screw-on type tenninals shall be designed in such a
way that after the tenninal block is unscrewed, the wire is still engaged to the
tenninal block. The screwless type tenninals shall be designed to clamp the wire
automatically after releasing or withdrawing the screwdriver. The tenninal blocks
provided for marshalling panels shall be of the knife disconnect type.
The terminal blocks ofRTU circuits in each protective relay switchboard shall be
of the knife disconnect type.
All CT tenninals and distance relays' PT tenninals shall be provided with sliding
switch bridge and test socket screws. All CT and PT wires, as well as control and
protection circuits shall be tenninated with ferrules.
The tenninal blocks shall be sized and rated in accordance with current carrying
capacity of wires. The tenninals for power and CT circuits shall be sized to accept
2x6 rnrn2 conductors, and those for PT and control circuits shall be sized for 2x4
rnrn2 conductors. The tenninals for alarm/status circuits, RTU circuits and
marshalling panel shall be sized for 2x2.5 rnrn2 conductors.
Terminal blocks for blank panels will not be required; however, mounting
brackets for these future blocks shall be provided.
1002-20. Symbols and Mimic Buses. All symbols, devices and painted mimic buses, 10
mm in width, shall be provided on the main control board to form single line
diagrams which will simulate actual electrical connections as indicated on the
drawing entitled "Main Control Board Equipment Layout". Mimic disconnect
devices for disconnect switches shall be manually operated. Mimic disconnect
devices for line ground switches shall be electrically operated to automatically
position themselves in accordance with their respective line ground switches.
The mimic buses shall be painted on the front of the panels with lacquer or
enamel. Color of mimic buses shall be as follows:
1002-21. Control and Instrument Switches. The control and instrument switches shall be
of the multistage, rotary type, rated 600 V, 10 A, continuous duty, for both AC
The types of control switch handles and colors preferred shall be provided as
follows:
Circuit breaker control switches - pistol grip (black)
Discrepancy control switches - bar (black)
Instrument selector switches - round notched (black)
Synchronizing switches - oval removable (yellow or white)
Trip transfer switches - oval (black)
Recloser cut-off switches - oval (black)
Raise-lower control - oval (black)
Control selector switches - oval (black)
Other cut-off switches - oval (black)
If the schemes for control, protection and other equipment as proposed by the
Contractor and approved by EGAT, require additional contacts than those
listed in this Specification and shown in the above drawing, the Contractor
shall furnish these extra contacts and contact arrangements without additional
cost to EGAT.
1002-21.1 Breaker Control Switches (CS). Each breaker control switch shall be
of the momentary contact type, with fixed, modern, pistol grip, black
handle with red and green mechanical target indicator to show the last
function of the switch. Each switch shall be furnished with separately
mounted red and green indicating lights. Breaker control switches
shall be suitable for use with rec10sing equipment.
1002-21.4 Recloser Cut-off Switches (79CO). Each recloser cut-off switch shall
be of the momentary contact type with fixed, modem, oval black
handle.
1002-21.7 Trip Transfer Switches (43). Each trip transfer switch shall be of the
maintained contact type, with fixed, modem, oval black handle. The
trip transfer switch function is to permit the operation in order to
transfer the tripping, reclosing, and synchronizing functions to the bus
tie breaker.
1002-21.9 Carrier Cut-off Switch (85CO). Each carrier cut-off switch shall be
of the maintained contact type, with fixed, modem, oval black handle.
1002-21.12 Permissive Transfer Trip Cut-off Switch (PTTCO). Each carrier cut
off switch shall be of the maintained contact type, with fixed, modem,
oval black handle.
1002-21.13 Stub Protection Cut-off Switches (51 S-CO). Each differential cut-off
switch shall be of the maintained contact type, with fixed, oval black
handle and complete with separately mounted red indicating lamp
assembly.
Scale plates shall have a permanent white fmish with black graduations and
numerals. Varmeter scale plates shall be marked II _ IN(-)" at the left of the
scale, "-0-" at the center and" _(+) OUT" at the right. The scale range and
other details of each indicating instrument shall be as specified in the bills of
materials.
1002-23. Grid TOU Energy Meters. Each three-phase, high precision or grid energy
meter shall be inspected according to lEe standard or equality international
standard with aging reliability, safety and accuracy. Each energy meter shall
comprise kilowatt-hours meter and kilovar-hours meter integrally mounted in
the same enclosure. Each energy meter shall be the solid-state type and the
accuracy class is 0.2S for the kilowatt-hours meter and class 0.5 for the
kilovar-hours meter. Each energy meter shall be 19 inches rack mounted, back
connected with essailec connectors, dustproof, fully tropicalized, switchboard
type, and completed with accessories for mounting. Each shall be suitable for
operation with the instrument transformers. Both kilowatt-hours and kilovar
hours meters shall be display not less than 7 digits. Programming facilities
shall be provided with each meter for any parameter setting. The meter shall
have a case, which can be sealed in such a way that the internal parts of meter
are accessible only after breaking the seal.
Each energy meter shall have the following characteristics and requirements:
1002-23.2 Accuracy. The meter shall have accuracy class 0.2S according to IEC
62052-11 and 62053-22 for active energy (kilowatt-hours) and 0.5 for
reactive energy (kilovar-hours).
1002-23.3 Minimum display requirement. The meter shall measure and display
at least the following electric values:
- Active Energy
- Reactive Energy
- Apparent Energy
- Maximum Demand Active Energy
- Current L 1, L2, L3
1002-23.4 Calibration. The meter shall be calibrated andlor tested using the
pulse stream from LEDs or infrared on the front panel that has rate
proportional to the measured power. EGAT shall be able to adjust the
percentage error manually or via software program. If the meter has
never used in EGAT before, the calibration software shall be
provided.
1002-23.10 Data storage. The minimum requirement of data storage of each meter
shall be stored 4 values of above load profile in 30 minutes time
interval and shall not less than 150 days.
1002-23.16 Software(s). The meter shall deliver to EGAT with the software(s) as
the following characteristics:
Calibration software
- The bidder shall supply the meter calibration software (the
percentage error adjustment of the meter) to calibrate all applied
meters in case of the applied meters could not be calibrated by
EGAT existing software.
- The calibration software shall be the version without expiration,
the bidder has to provide the official confirmation letter or
document related to the expiration of this calibration software as
the part of bidding documents.
Software manual(s)
- All of above software shall deliver to EGAT with complete set of
instruction manuals both in English and Thai language.
- The instruction manuals shall comprise theory of operation and
applications, installation and system arrangement, spare part lists,
and detailed circuit diagram as necessary for repair and
maintenance.
- The Thai language instruction manuals shall be approved by
EGAT before delivering all copies of them.
- The instruction manuals shall be both in hard copy and electronic
files in CD-ROM.
1002-23.17 Certification.
- The type test of the meter shall be certified according to class O.2S
(kWh) ofIEC 60687 or lEe 62052-11 and IEC 62053-22 standard,
by the third party who have been authorized by ISO/IEC 17025
standard or equivalent. The bidder shall supply the type test report
to EGAT during bid evaluation period. The meter shall not be
acceptable if those type test is not available.
- The factory test report of active and reactive energy of every
energy meter shall be supplied with the meter at the time deliver to
EGAT.
1002-24.1 Minimum twenty (20) pulse inputs and complete with pulse
supervlsIOn. Each instrument shall be expandable up to forty (40)
inputs.
1002-24.7 Billing control shall be provided with each instrument and operated
by an external control signal and by means of a pushbutton on the
instrument. Each instrument shall also have automatic billing control.
1002-25 Fast Receipt printer. Each printer shall be 9 pin, dot matrix type and shall have
memory at least at 4 kByte. Each shall include connection ports both RS232C
serial port and parallel port centronics parallel. Power feeder system of each
printer shall be continuous paper type, width 76.0±0.5(W) x diameter 83.0 rnrn
and thick 0.065-0.085 rnrn Power supply shall be 220-240 V AC, 50 Hz, 30W.
1002-26.1.1 Burden
Voltage circuit Max 4 VA per element
Current circuit Max 0.8 VA per element
1002-26.1.6 Adjustment
Zero control range ±2%
Calibrate control range ±1O%
1002-26.1. 7 Environment
Operating temperature +20°C to +70°C
range
Operating humidity oto 95%
Temperature range :
1002-28. Relays. All relays shall be designed for continuous operation at any voltage
from 80 per cent to 115 per cent of rated DC voltage as specified and at a range
of ambient temperatures of 10°C to 55°C. All binary inputs shall be triggered
by any voltage over a range from 80 per cent to 115 per cent of the rated DC
voltage only. Each protective relay shall be suitable for operation with
instrument transformer ratios and connections as shown on the metering and
relaying diagrams under both normal and short circuit conditions.
All relays contacts for tripping duty shall be rated to carry lOA, 300V for 1
second, 4A, 300V at continuous duty, and be capable of interrupting of 0.2A of
inductive current (LIR :::;40 ms) in a 125 V DC control circuit.
Each relaying system shall be provided with test facilities for secondary
injection testing and for isolating the DC supply, current circuits, potential
circuits, tripping circuits, and all other output contacts. All test switches shall
Relays utilizing voltage divider type regulated power supplies shall not be
accepted.
All modules of static, digital or numerical type protective relays shall consist of
highly reliable logic circuits and circuit components. All modules shall be
mounted on plug-in circuit cards. Wiring boards shall be epoxy-fiberglass
construction. Printed circuit wiring shall be employed with soldered or welded
connections to circuit components. Wiring board shall be provided with heavy
duty circuit connectors with gold-plated contacts.
Each digital or numerical relay shall have provisions for monitoring any hardware
failures so they can be repaired before they affect relay operation. These
provisions shall also include output contacts for initiating the remote tenninal unit
(RTU). All output contacts shall be electrically separate nonnally open contacts.
The protective relays offered shall be products of the approved protective relay
manufacturers listed as follows: ABB (Sweden, Switzerland, U.S.A.), GE
(U.S.A., Canada, Spain), AREVA (U.K., France), Reyrolle (U.K.), Siemens
(Germany) , SEL (USA), or TOSHIBA (Japan).
The procedures for being listed in EGA T' s Specification and EGAT
ACCEPTED Main RELAY LIST can be requested from Transmission System
Engineering Division.
Each relay shall include the instantaneous trip unit to ensure high
speed operation on heavy internal faults. Each relay shall incorporate
current taps or separate auxiliary current transformers to compensate
for main current transformer mismatch. A cut-off switch (87K-CO)
with a separate red indicating lamp shall be provided with each set of
relays, to segregate the auxiliary tripping relay from the differential
relays as necessary to prevent false tripping due to the bypassing of
the current transformers. The red lamp shall light to indicate that the
trip circuit from the differential relays to the auxiliary tripping relay is
closed. Each cut-off switch shall be in accordance with the
requirements of Article 1002-21.
Low impedance type bus differential relay shall include Ethernet rear
port type RJ45 for the data communication between the relays at
remote substations and the PC at the central office.
Each bus differential relay shall be furnished with at least two (2)
electrically separate normally open contacts in addition to those
required by the bus differential protection functions. These contacts
shall be : one contact shall be wired to initiate the remote terminal
unit (RTU) and one contact shall be wired to the fault.
1002-28.4 Auxiliarv Tripping and Lockout Relays (86K, 86B, 86DTT, 86BF).
Auxiliary tripping and lockout relays shall be provided with
transformer protection, bus protection, direct transfer tripping and
Overcurrent relay shall include Ethernet rear port type RJ45 for the
data communication between the relays at remote substations and the
PC at the central office.
Overcurrent relay shall include Ethernet rear port type RJ45 for the
data communication between the relays at remote substations and the
PC at the central office.
Overcurrent relay shall include Ethernet rear port type RJ45 for the
data communication between the relays at remote substations and the
PC at the central office.
1002-28.9 Loss of DC Alarm Relays with Special Provision for Slow Dropout
(27XB, 27XR). All DC control circuits for protective relaying
systems and power circuit breakers shall be monitored by a loss of
DC alarm relay. Each shall be auxiliary relay, standard speed with
slow dropout characteristics. Each relay shall be furnished with two
(2) electrically separate normally closed contacts. These contacts shall
be : one contact shall be wired to initiate the remote terminal unit
(RTU) and the other shall be wired to terminal blocks for future use.
Each relay shall also be furnished with two (2) electrically separate
normally open contacts for future use.
1002-29.1 Relay Line Terminal Utilizing Distance Protection. Each relay line
terminal shall utilize directional comparison permissive transfer trip
scheme via a power line carrier or fiber optic cable with backup
relaying to achieve primary and secondary protection. The primary
pilot relaying system shall use frequency shift keyed audio tone
teleprotection equipment. The primary and secondary protection shall
each be a distance protection scheme.
Each relaying system shall have at least four distance zones with
individual and independent measuring units with programmable
directionality for protection against phase and ground faults.
Each relay line terminal shall include single pole and three-pole
tripping and reclosing protection scheme. The three-pole reclosure
shall be done through a synchro-check relay.
Each backup distance relays for protection against phase and ground
faults. Each distance relay shall be of the non-switched type. Each
relay line terminal shall be provided breaker failure or local backup
protection for each circuit breaker.
Each relay line terminal shall include single pole and three-pole
tripping and reclosing protection scheme. The three-pole reclosure
shall be done through a synchro-check relay.
1002-31. 230 kV Bus Protection. 230 kV substation buses shall be protected by bus
differential relays. A separate auxiliary tripping & lockout relay shall be
provided for each zone of bus protection.
1002-32. 230 kV Breaker Failure Protection. The necessary relays shall be provided so
that upon failure of a circuit breaker to trip within its normal time, the trip
circuit of all the appropriate circuit breakers necessary to isolate the faulted line
shall be energized to trip and lockout. Lockout relays shall be provided to
1002-32.1 Current Detector Relays (SOBF). Each current detector relay shall be
non-directional instantaneous overcurrent relay with fast-resetting
time of less than 30 milliseconds when the current drops from S times
of the pickup to zero. Each relay shall be of the numerical type. Each
shall contain two or three phase units and one ground unit with O.S-1 OA
pickup range. The setting for the phase and ground units shall be
independently adjustable. The indicating target shall be provided with
each relay.
1002-32.2 Breaker Failure Timer (62BF). Each timer shall be a time delay relay
with timing range of O.OS to 1.0 second and shall be continuously
adjustable. An output contact with an indicating target shall be
provided with each timer. The timer may be included with the current
detector relay.
Current detector relay and breaker failure timer shall be especially designed for
the breaker failure function and it is unnecessary to create any logic to form the
breaker failure function.
1002-33. 230 kV Direct Transfer Tripping System. When the breaker failure protection
at the local end operates, the breaker failure protection shall transmit the trip
command to the remote end via a communication channel to trip and lockout
the remote end power circuit breaker instantaneously as sho\\'TI in Drawing No.
TP-E-6.3.
1002-34. 115 kV Transmission Line Protection. For 115 kV substation, the protection
on each transmission line shall be a distance protection with carrier transfer
trip. The type carrier transfer trip relay is of the permissive transfer trip
scheme. Each relay line terminal shall include three-pole tripping and
rec1osing. The three-pole reclosure shall be done through a synchro-check
relay.
1002-34.1 Distance Relays (21P). Each distance relay system shall be used to
provide complete protection for all combinations of phase faults and
ground faults. Each distance relay shall be of the three-phase,
numerical type with separate measuring elements for each type of
faults and shall be of the non-switched type. Each distance relay shall
be of the integral type with all the main and auxiliary units mounted
Each distance relay shall operate correctly for all types of evolving
faults. This shall include phase-ground faults evolving to phase
phase-ground faults, phase-phase faults evolving to phase-phase
ground faults, phase-phase faults evolving to three-phase faults, and
external faults evolving to internal faults.
All relays contacts for tripping duty shall have an operating time
including bouncing time not exceeding 10 milliseconds at 250 Watt
load.
Each distance relay shall provide the same functions as listed in the
Article 1002-29.1.1.1.
1002-34.3 Automatic Reclosing Relays (79). Each relay shall be of the static,
digital or numerical type. Each shall be provided one high-speed,
single-shot, 3-pole reclosure for first zone faults and for remote
carrier trip signal. Each reclosing operation shall be initiated by a
contact of the primary protective relays. The dead time setting range
shall be adjustable between 1-15 seconds. The reclaim time setting
range shall be adjustable between 1 to 30 seconds. Each shall be
provided with two electrically separate nonnally open contacts, one
for annunciation of recloser operation and the other for annunciation
of recloser lockout.
Provision shall also be made with each line relaying for selection of pilot
scheme modes of operation as specified above.
1002-35. 115 kV Transformer and Local Line Protection. For 115 kV substations, each
transformer and local line protection shall consist of the following
components:
1002-36. 115 kV Bus Protection. 115 kV substation buses shall be protected by bus
differential relays. Each bus protection shall consist of the following
components:
1002-36.2 Bus Differential Auxiliary Tripping & Lockout Relays (86B). Each
bus differential auxiliary tripping & lockout relay shall be in
accordance with the requirements of Article 1002-28.4.
Any additional equipment required for complete functions of the bus protection
shall also be included with each bus protective relaying.
1002-37. 115 kV Breaker Failure Protection. Each 115 kV breaker failure protection
shall be in accordance with the requirements of Article 1002-32.
1002-38. Auxiliary and Control Relays. Additional auxiliary and control relays shall be
Auxiliary and control relays shall be of the semi-flush mounted type if feasible,
otherwise of the surface mounted, switchboard type, with a removable cover
and transparent window, where applicable, and shall be finished dull black.
There shall be coil transient suppression device in order to protect the relay coil
from electromotive force.
The coils of relays shall be suitable for continuous duty at their normal
operating voltage. All contacts shall be of the renewable type with ample
current-carrying and interrupting capacity for the application, and shall
withstand at least 30 A, 600 V at 3 seconds and 5 A, 600 V at continuous duty.
Auxiliary relays of the mechanically latched-in type shall have manual reset
devices operable from the front of the panel and shall have an operating time
not to exceed 30 milliseconds. Auxiliary relays of the self-reset, standard-speed
type shall have an operating time not to exceed 40 milliseconds. Auxiliary
relays of the self-reset, medium speed type shall have an operating time not
exceeding 30 milliseconds. Auxiliary relays of the self-reset, high speed type
shall have an operating time including bouncing time not exceeding 20·
milliseconds.
1002-39. Interposing Relays. Interposing relays shall be used for substation control,
indication, and annunciation functions. Where necessary, interposing relay
shall be of the latched-in type especially for those concerning the mode
selection functions. Each Interposing relays shall be in accordance with the
requirements of Article 1002-38.
A red group pilot lamp for indication of annunciator operation and a white
indicating lamp assembly for monitoring availability of annunciator potential
shall be furnished, separately mounted, with each annunciator system. They
shall be suitable for mounting on the control board panel face.
The alarm hom shall be of the vibrating type, and shall be suitable for surface
mounting inside the control board.
Each power supply shall be of the DC-to-DC converter regulated type and
designed to protect it from high voltage and surge and to provide transient
surge isolation between the station battery and the sensitive electronic
components of the annunciator system. Each power supply shall be provided
with necessary equipment to protect it from overloads that occur on the output
side of the power supply. Each power supply shall include input reversed
polarity protection and overvoltage and short circuit protection on the logic
voltage supply. In the event of a short circuit on the power supply output, no
damage will occur to the power supply.
Solid-state alarm modules shall consist of highly reliable logic circuits and
circuit components. All modules shall be mounted on plug-in circuit cards.
All signal inputs and outputs of annunciator modules shall be provided with
optical couplers and RC filter circuits for high voltage and surge protection.
All annunciator systems to be furnished shall have the same numbers of alarm
points per alarm module and all alarm modules shall be interchangeable.
Visual
Designated Event Audible
Annunciator Group Pilot
Lamps Lamp
Each annunciator shall be designed so that the closing of a trouble contact shall
flash the annunciator lamp, light the group pilot lamp and sound the alann.
The operator shall then be able to silence the alann, stop flashing and
extinguish the group pilot lamp by pressing the horn reset pushbutton and
extinguish the annunciator lamp by pressing the lamp reset pushbutton,
provided the trouble contact has been opened.
Operation of the lamp reset pushbutton shall not cause the alann to sound.
Release of the pushbutton shall not cause the alann to sound again whether or
not any trouble contacts are still closed. Operation of an annunciator lamp shall
not interfere with or cause false operation of any other annunciator lamp
whether operated simultaneously or in sequence.
Wrong operation of any pushbutton shall not cause malfunction to the correct
operation of the system.
1002-41. Size of Drawings. All drawings and transparent reproducibles of all final
approved drawings of metering and relaying diagrams, main control board
equipment layout, AC schematic, DC schematic, internal wiring diagram of
each panel, and nameplate and annunciator schedules shall be as follows:
1002-42. Factory Tests. After the s\\-itchboard and panel structures have been fabricated
and all components assembled, the complete gear including instruments, relays
and devices shall be given standard factory tests and all others in accordance
with the latest applicable standards of NEMA and ANSI. These tests shall
include, but not be limited to, the following:
1002-43. Finishing and Painting. Finished panel surfaces shall be free from waves,
bellies, or other imperfections. Exterior and interior surfaces shall be cleaned
by sanding and steam cleaning, ground smooth, filled, primed, sanded and shall
be finish-painted inside and outside with ANSI 61 medium gray (RAL 7036
full gloss).
One quart of matching paint shall be furnished under each item of equipment
for touching up damaged places.
1002-44. Spare Parts List. A list of spare parts shall be provided with the type number,
style number, and catalog number of each spare part as required for each type
of relays, instruments, meters, and auxiliary devices based upon 50 hertz
operation and the voltages as applied to the circuit.
1002-45. Tools and Accessories. All special tools and accessories required for
installation and normal operation and maintenance of the equipment shall be
furnished to the System Protection Department. The notebook computer,
software (stored in diskette or CD-ROM), manual to used the software and
connector links between relays and PC should be furnished to the System
Protection Department for each substation which relays protection can be
connect by the computer. The specification of notebook computer should be
clarified by user of the System Protection Department.