Académique Documents
Professionnel Documents
Culture Documents
iPASOLINK 100E
SECTION II OPERATION
CONTENTS
Operation NWD-142957-01E
-6-
NWD-142957-01E Operation
-7-
Operation NWD-142957-01E
-8-
NWD-142957-01E Operation
DOCUMENT WARRANTY -5-
DOCUMENT WARRANTY
Operation NWD-142957-01E
-6- DOCUMENT WARRANTY
NWD-142957-01E Operation
Getting Started 1-1
1. GETTING STARTED
1.2.1 Communications
The local craft terminal is a useful tool to the installation and maintenance.
iPASOLINK supply users GUI environment through WEB browser. Moreover, this
tool supports remote connection.
Operation NWD-142957-01E
1-2 Getting Started
Use LAN Cable connected to the LCT Port at the front of equipment.
When protected system is requested, it needs other iPASOLINK menu, for example,
200, 400, and 1000.
NWD-142957-01E Operation
Installation of LCT 2-1
2. INSTALLATION OF LCT
* Windows Vista
Item Required Recommend
CPU Intel Core2 Duo 1.6 GHz
RAM 1 GB
HDD 40 GB
Display Color LCD (1024x768)
LAN Port 10/100BASE-T(X)
USB Port
* Windows 7
Item Required Recommend
CPU Intel Core2 Duo 1.6 GHz
RAM 1 GB
HDD 40 GB
Display Color LCD (1024x768)
LAN Port 10/100BASE-T(X)
USB Port
Operation NWD-142957-01E
2-2 Installation of LCT
Note: Using Zoom function of browsers is not recommended, it may cause issues.
NWD-142957-01E Operation
Installation of LCT 2-3
2. Select Start -> Settings -> Control Panel from the Start menu of the
Windows.
Operation NWD-142957-01E
2-4 Installation of LCT
1. Tools -> Internet Options -> General -> Tabs Settings from the Tool Bar menu
of the Internet Explorer 8.
NWD-142957-01E Operation
Installation of LCT 2-5
1. Tools -> Internet Options -> Security -> Security Level for this zone Custom
level from the Tool Bar menu of the Internet Explorer 8.
Operation NWD-142957-01E
2-6 Installation of LCT
NWD-142957-01E Operation
Installation of LCT 2-7
2.4.2 Firefox 9
1. Tools -> Options from the Tool Bar menu of the Firefox.
Operation NWD-142957-01E
2-8 Installation of LCT
NWD-142957-01E Operation
System Configuration 3-1
3. SYSTEM CONFIGURATION
3.1 General
iPASOLINK 100E is a basic configuration for nodal application in the wireless
iPASOLINK family and providing up to 460 Mbps with flexible native Ethernet
transmission and advanced adaptive modulation scheme operating in 6, 7, 8, 10, 11,
13, 15, 18, 23, 26, 28, 32,38 or 42 GHz bands.
The iPASOLINK consists of antenna, outdoor unit (ODU) and indoor unit (IDU) like
as PASOLINK series and accedes to very high performance and ultra high reliability
gained through NECs rigid TQC activities and vast experience in wired and wireless
communication fields.
Operation NWD-142957-01E
3-2 System Configuration
NWD-142957-01E Operation
System Configuration 3-3
- Flexible configuration for ODU and antenna, direct mount / remote mount.
- 19 inches one rack unit and half rack width size compact IDU,
- Small and light weight ODU for easy handling and installation.
13-42GHz
Operation NWD-142957-01E
3-4 System Configuration
NWD-142957-01E Operation
System Configuration 3-5
3.4 Interfaces
Operation NWD-142957-01E
3-6 System Configuration
The local craft terminal is a useful tool to the installation and maintenance.
iPASOLINK supply users GUI environment through WEB browser. Moreover, this
tool supports remote connection.
This port is used to connect with the NMS server through the network.
- TNC female
NWD-142957-01E Operation
System Configuration 3-7
3.5.1 General
NO Item IDU
Operation:-5 to +50 deg.C (ETSI EN300019-1-3 class 3.1E)
Humidity: 95% (at 50 deg.C, No condensing)
(Workable: -10 to +55 deg.C)
Transportation ETSI EN300019-1-2 class 2.3
1 Environmental condition Storage ETSI EN300019-1-1 class 1.2
Non-weather protection (IEC 60529 IP66)
Note: Allowable High Temperature depends on installation type.
Be careful to refer the Safety Information on Instruction Manual
before installation.
Power consumption of
2 25W
IDU without options
Power consumption of
3 3W
Option clock board
4 IDU Size 200(W)x41.6(H)x230(D) mm, 2kg Approx.
5 EMC Conforms to EN301489-4, Class B
6 Safety Conforms to EN60950-1
RJ-45 x 2 Ports;
Main Signal 10/100BASE-T(X)(standard), 10/100/1000 BASE-T(X) (option)
2 LAN
Interface SFP x 2 Ports;
1000BASE-SX/LX (LC) / 10/100/1000BASE-T(X) (RJ-45)
4 Power Line Requirement -48 VDC (-40.5 to -57 VDC) , Conforms to EN300 132-2
Operation NWD-142957-01E
3-8 System Configuration
NO Item IDU
QPSK/ 16QAM/ 32QAM/ 64QAM/ 128QAM/ 256QAM :
Adaptive modulation
5 6 modulation schemes changeable
(AMR)
Ingress
QoS Class Classification: VLAN CoS/IPv4
DSCP/IPv6 DSCP/MPLS EXP/ETH Port, VLAN ID
Support
SyncE
NWD-142957-01E Operation
System Configuration 3-9
NO Item IDU
1 port, 10/100 Base-T RJ45 (inband or outband connection available)
8 NMS interface
SNMPv1/v2c/v3, https, sftp
Radius, local
10 User Authentication
PMON Items;
a) OFS, b) BBE, c) ES, d) SES, e) SEP, f) UAS
Operation NWD-142957-01E
3-10 System Configuration
NWD-142957-01E Operation
NE Setup 4-1
4. NE SETUP
4.1 Login/Logout/Exit
4.1.1 Login NE
Users are registered by means of login name and password. To protect the network
and network management system from unauthorized access or unauthorized
modifications, three levels (refer to the table shown in section 4.3.2 User Account
Management) of users are defined with different privileges. The functions available
in the window depend on the users access level. Therefore, some of the functions
may or may not be carried out.
The highest or administrator level (Admin) has full access to the network and
network management system.
Procedure 4-1
3. Select Start -> Programs -> Internet Explorer from start menu.
4. The Internet Explorer window appears. Input the IP address of the NE and
WebLCT in URL Address box as shown below.
Ex: http://172.17.254.253/weblct/
Operation NWD-142957-01E
4-2 NE Setup
5. The WebLCT login window appears. Input user name and password in User
Name and Password textbox then press OK.
The following is the default user name and password for iPASOLINK 200:
Password: 12345678
6. After user name and password are successfully entered, System Status box
appears.
NWD-142957-01E Operation
NE Setup 4-3
7. After the login completed, the System Status box automatically closed. Or
you may click OK button to close the box quickly.
Operation NWD-142957-01E
4-4 NE Setup
4.1.2 Logout NE
Procedure 4-2
1. Click Logout button in the right top of the WebLCT main window.
NWD-142957-01E Operation
NE Setup 4-5
Select File (F) -> Exit from the Internet Explorer menu bar.
Operation NWD-142957-01E
4-6 NE Setup
Click Refresh button to update the current status of the WebLCT main
window.
NWD-142957-01E Operation
NE Setup 4-7
This part shows a list of NE on the opposite site, user can select the NE from the
pull down list to log in to the specified NE on the opposite site.
Click the corresponding tab to switch among the different event log view.
This part shows the tree view of the relevant configuration and provisioning
menu of the equipment.
Select this menu to show the equipment current status or history events for
each part of the NE (Active Alarm, Event Log, ODU, and IDU).
Follow the Easy Setup Wizard to setup the basic configuration of the
equipment. The wizard includes ODU and IDU package registering,
removing function. This wizard provides a easier way to setup cross connect,
VLAN service and other necessary configuration for a new equipment.
Select this menu to register or remove ODU and IDU package and other
relevant configuration.
(d) Provisioning
Select this menu to configure the detail settings of the IDU and ODU.
Operation NWD-142957-01E
4-8 NE Setup
Select this menu to browse the report of Current, History, PMON and
RMON. User can also export the data to external storage (Local PC). (For
more details, refer to Maintenance Manual)
(h) Metering
Select this menu to measure the real time TX power, RX level, ODU power
supply and BER.
Select this menu to add, remove and modify user account of the equipment,
and setup user account security.
(k) Inventory
Select this menu to browse inventory information about the Equipment and
Software License.
NWD-142957-01E Operation
NE Setup 4-9
Access Level
There are three user access levels with different privilege in iPASOLINK as
shown in the following table. For details of available operations of each access
level, refer to Table 4-3 User Access Privilege Levels.
Note: About the terms Upload and Download mentioned in the table above,
refer to the following description.
1. Upload means copy the file from NE to external storage, such as WebLCT
PC.
2. Download means copy the file from external storage to the equipment
internal storage.
User Group
User Group configuration allow user to manage the Protocol Type and Access
Level for each group.
The user that assigned to the specified user group in iPASOLINK will be
assigned with pre-defined protocol and access level of the group.
Beside of the three default user groups, user can add up to six user groups
additionally. The default user groups are shown below.
Note: User can not change the options of default user group.
Operation NWD-142957-01E
4-10 NE Setup
NWD-142957-01E Operation
NE Setup 4-11
Operation NWD-142957-01E
4-12 NE Setup
NWD-142957-01E Operation
NE Setup 4-13
Operation NWD-142957-01E
4-14 NE Setup
Procedure 4-3
2. Select Login User List from the User Account/Security Setting sub
menu.
Note: This function is available for Admin access level user only.
Authentication Setting
NWD-142957-01E Operation
NE Setup 4-15
Procedure 4-4
Operation NWD-142957-01E
4-16 NE Setup
4. The Authentication Setting dialog box appears. Enter the proper value for each
parameter.
NWD-142957-01E Operation
NE Setup 4-17
Procedure 4-5
Operation NWD-142957-01E
4-18 NE Setup
4. The Privilege ID dialog box appears. Enter the proper value for each parameter.
NWD-142957-01E Operation
NE Setup 4-19
Operation NWD-142957-01E
4-20 NE Setup
This function is for registering new user accounts, modifying and deleting existing
user account in iPASOLINK.
Note: This function is available for Admin access level user only.
This function is for registering the new user account other than the existing user
account.
Note: Up to nine user accounts can be added beside of the three default user
accounts.
Procedure 4-6
NWD-142957-01E Operation
NE Setup 4-21
3. The User Account Management window appears. Click Add User button.
Add User button
4. The User Setting dialog box appears. Enter the proper value for each
parameter.
Operation NWD-142957-01E
4-22 NE Setup
5. Click Set Password in the User Setting dialog box. The Set Password
box appears. Enter the same password into New Password and Re-Enter
boxes and then click OK button.
NWD-142957-01E Operation
NE Setup 4-23
6. The User Setting dialog box appears again. Click OK button to close the
dialog box.
Note: Selection of Auth / Priv Algorithm will change according to the security
level below.
Operation NWD-142957-01E
4-24 NE Setup
Security Level
NWD-142957-01E Operation
NE Setup 4-25
Operation NWD-142957-01E
4-26 NE Setup
For AuthPriv, Auth Algorithm, Auth key and Pri Algorithm Priv Key are
selectable.
NWD-142957-01E Operation
NE Setup 4-27
8. Click OK button after specifying the proper value for each parameter.
10. The User Account Management window appears again. Confirm the user
account information displayed.
Operation NWD-142957-01E
4-28 NE Setup
Procedure 4-7
3. The User Account Management window appears. Click the desired user
account.
User Account
4. The User Setting box appears. Specify the proper value of each parameter.
NWD-142957-01E Operation
NE Setup 4-29
Select the user group from Group Name dropdown list to change the user
group of the user.
Click Set Password on the top of the User Setting box to change the current
password. Enter the new password into New Password and Re-Enter on the
Set PassWord box.
5. The User Setting dialog box appears again. Click OK button after inputting all
the information.
Operation NWD-142957-01E
4-30 NE Setup
7. The User Account Management window appears again. Confirm the modified
user account information displayed.
Procedure 4-8
NWD-142957-01E Operation
NE Setup 4-31
4. The User Setting box appears. Select the user account from drop-down list and
click OK button.
5. The Confirmation box appears. Confirm the user name being deleted and then
click OK button.
Operation NWD-142957-01E
4-32 NE Setup
7. The User Account Management window appears again. Confirm that the
user has been deleted.
This setting is for registering and modifying the user group profiles.
The privilege of iPASOLINK user is subject to change according to the assigned user
access level and protocols that specified in the User Group Profile.
This function is for registering the new User Group Profile other than the default
User Group Profile.
Note: Up to six User Group Profiles can be registered beside of the three default
User Group Profiles.
NWD-142957-01E Operation
NE Setup 4-33
This function is for modifying the existing User Group Profile (Access Level and
Protocol).
Procedure 4-9
3. Click Add Group on the top of the User Group Profile Configuration
window.
Add Group button
4. The Group Setting box appears. Specify the proper value for each parameter
and the click OK button.
Operation NWD-142957-01E
4-34 NE Setup
NWD-142957-01E Operation
NE Setup 4-35
Procedure 4-10
2. Select User Group Profile Configuration from the User Account/Security Setting
sub menu.
3. The User Group Profile Configuration window appears. Click the desired
Group Name.
Group Name
4. The Group Setting box appears. Modify the parameters accordingly and then
click OK button.
Operation NWD-142957-01E
4-36 NE Setup
Select the proper Access Level from drop-down list to change the access level of
the user group.
NWD-142957-01E Operation
NE Setup 4-37
7. The User Group Profile Configuration window appears again. Confirm the
user group profile information displayed.
Note: A user group can be deleted only when no user account has been
assigned to the user group.
Procedure 4-11
Operation NWD-142957-01E
4-38 NE Setup
4. The Group Setting box appears. Select the Group profile name from the
drop-down list.
5. The Confirmation box appears. Confirm that the User Group name is deleted
and then click OK button.
NWD-142957-01E Operation
NE Setup 4-39
7. The User Group Profile Configuration window appears again. Confirm the
User Group Profile information displayed.
Operation NWD-142957-01E
4-40 NE Setup
- GET/SET of MIB
By default iPASOLINK uses the port 161 to receive the SNMP request UDP. If
user wants to use the pot other than the default one, it can be changed via the
WebLCT.
NWD-142957-01E Operation
NE Setup 4-41
- Send Trap
iPASOLINK can send SNMPv1 trap activity to UDP port 162, and up to three
destination IP addresses can be registered in advance. User also can specify the
community name and PDU type.
Operation NWD-142957-01E
4-42 NE Setup
- GET/SET of MIB
By default iPASOLINK uses the port 161 to receive the SNMP request UDP. If
user wants to use the pot other than the default one, it can be changed via the
WebLCT.
- Send Trap
iPASOLINK can send SNMPv2 trap activity to UDP port 162, and up to three
destination IP addresses can be registered in advance. User also can specify the
community name and PDU type.
NWD-142957-01E Operation
NE Setup 4-43
Operation NWD-142957-01E
4-44 NE Setup
- GET/SET of MIB
Response the request of PDU (Protocol Data Unit) that correspond by SNMPv3
- Send Trap
Available to send SNMPv3-Trap and destination UDP Port No. are 162 among
SNMPv1, v2c, v3.
SNMP, IP address of entity, security level, and user name will require for setting
destination of Trap for SNMPv3.
User authentication will be execute if send the SNMP request that security level
is authNoPriv or authPriv.
NWD-142957-01E Operation
NE Setup 4-45
This protocol is for synchronizing the time between server and client connecting
in network and specified by the following RFC.
iPASOLINK uses NTP Client and Server to provide the following functions:
- As NTP Client
In case that the unicast mode is selected on NTP Client, client sends a request of
the current time to the pre-configured server and then sets the time according to
information in the reply. Up to four NTP severs can be registered via the
WebLCT.
In case that the multicast mode is selected on NTP Client, client will listen the
broadcast of the time server and then set the time according to the first received
valid broadcast and ignore the broadcasts from other servers if any.
NTP Client received neither reply nor broadcasts which cause synchronization
cannot be accomplished, and current time of the equipment will be used.
Operation NWD-142957-01E
4-46 NE Setup
- As NTP Server
In case that the unicast mode is selected on NTP server, server will reply the
client with his time information.
In case the multicast mode is selected, server will broadcast his time information
periodically.
This protocol is for transferring the file among network equipments, and
specified by the following RFC.
Provide the data upload and download service; however data download is
available only when user is assigned with the proper privilege (refer to 4.3.1
User Access Levels).
The files and the directories that can be accessed via FTP protocol are
predetermined as well as the file name and type which will be downloaded.
- Session management
Accept the connection from external device then conduct Login Authentication
process. Anonymous user is not available.
Using the default TCP port 21 for listening and transferring the file on TCP port
20, user can change the default setting by the WebLCT. When Passive Mode is
selected, the port number is decided by the equipment automatically.
NWD-142957-01E Operation
NE Setup 4-47
HTTP is the protocol for transferring data between Web server and client
(WebLCT).
- WebLCT
- Session Management
Accepts the connection from external device then conduct Login Authentication
process. Anonymous user is not available.
The default port number of HTTP service is 80, and user can change it on the
WebLCT.
Operation NWD-142957-01E
4-48 NE Setup
Procedure 4-12
3. Select Service Status Setting from the Security Management sub menu.
4. The Service Status Setting window appears. Confirm the status of each
Service.
NWD-142957-01E Operation
NE Setup 4-49
Operation NWD-142957-01E
4-50 NE Setup
4.3.4.2 SNMP
Procedure 4-13
3. Select Service Status Setting from the Security Management sub menu.
Click SNMP.
NWD-142957-01E Operation
NE Setup 4-51
5. The SNMP Setting box appears. Specify a proper value for each parameter.
Caution
You must reboot the CPU for applying the value properly after changing the UDP port
number.
Operation NWD-142957-01E
4-52 NE Setup
NWD-142957-01E Operation
NE Setup 4-53
Registers, modifies, or deletes the SNMP Manager information. Only the registered
SNMP managers have the right to access to the equipment. Up to ten servers can be
registered.
Procedure 4-14
3. Select Service Status Setting from the Security Management sub menu.
4. The Service Status Setting window appears. Click Community No. of the
SNMP Community field.
Community No.
Operation NWD-142957-01E
4-54 NE Setup
NWD-142957-01E Operation
NE Setup 4-55
8. The Service Status Setting window appears again. Confirm the he newly
added SNMP community information displayed.
Procedure 4-15
3. Select Service Status Setting from the Security Management sub menu.
Community No.
Operation NWD-142957-01E
4-56 NE Setup
NWD-142957-01E Operation
NE Setup 4-57
8. The Service Status Setting window appears again. Confirm the SNMP
Community information displayed.
Procedure 4-16
3. Select Service Status Setting from the Security Management sub menu.
Operation NWD-142957-01E
4-58 NE Setup
4. Click Delete SNMP Community on the top of the Service Status Setting
window.
Delete SNMP Community
5. The Delete SNMP Community box appears. Select the SNMP Community
No. from the drop-down list, and then click OK button.
NWD-142957-01E Operation
NE Setup 4-59
8. The Service Status Setting window appears again. Confirm the SNMP
Community information displayed.
Procedure 4-17
3. Select Service Status Setting from the Security Management sub menu.
Operation NWD-142957-01E
4-60 NE Setup
4. The Service Status Setting window appears. Click SNMP Trap Entry No.
of the SNMP Trap Entry field.
SNMP Trap Entry No.
5. The SNMP Trap Entry box appears. Specify a proper value for each parameter.
(a) SNMPv1
NWD-142957-01E Operation
NE Setup 4-61
(b) SNMPv2c
(c) SNMPv3
Operation NWD-142957-01E
4-62 NE Setup
NWD-142957-01E Operation
NE Setup 4-63
8. The Service Status Setting window appears again. Confirm newly added
SNMP trap entry information displayed.
Procedure 4-18
3. Select Service Status Setting from the Security Management sub menu.
Operation NWD-142957-01E
4-64 NE Setup
4. The Service Status Setting window appears. Click SNMP Trap Entry No.
of the SNMP Trap Entry field.
SNMP Trap Entry No.
5. The SNMP Trap Entry box appears. Modify the parameters accordingly.
NWD-142957-01E Operation
NE Setup 4-65
8. The Service Status Settings window appears again. Confirm the SNMP trap
entry information displayed.
Procedure 4-19
3. Select Service Status Setting from the Security Management sub menu.
Operation NWD-142957-01E
4-66 NE Setup
4. The Service Status Setting window appears. Click Delete SNMP Trap
Entry.
Delete SNMP Trap Entry
5. The Delete SNMP Trap Entry box appears. Select the SNMP Trap Entry
No. from the drop-down list, and then click OK button.
NWD-142957-01E Operation
NE Setup 4-67
8. The Service Status Setting window appears again. Confirm the SNMP Trap
Entry information displayed.
4.3.4.5 NTP
Procedure 4-20
3. Select Service Status Setting from the Security Management sub menu.
Operation NWD-142957-01E
4-68 NE Setup
Click NTP.
5. The NTP Setting box appears. Assign a proper value for each parameter.
NWD-142957-01E Operation
NE Setup 4-69
Note for NTP Client Mode: Only the bridge 1 can receive NTP multicast message and
synchronize to NTP multicast server
Operation NWD-142957-01E
4-70 NE Setup
8. The Service Status Setting window appears again. Confirm the NTP
configuration displayed.
NWD-142957-01E Operation
NE Setup 4-71
Procedure 4-21
3. Select Service Status Setting from the Security Management sub menu.
4. The Service Status Setting window appears. Click NTP Server No. of the
NTP Server Address field.
Operation NWD-142957-01E
4-72 NE Setup
5. The NTP Server Address Setting box appears. Assign a proper value for
each parameter.
NWD-142957-01E Operation
NE Setup 4-73
8. The Service Status Setting window appears. Confirm newly added NTP
Server Address information displayed.
Procedure 4-22
3. Select Service Status Setting from the Security Management sub menu.
Operation NWD-142957-01E
4-74 NE Setup
4. Service Status Setting window appears. Click the NTP Server No. of the
NTP Server Address field.
5. The NTP Server Address Setting box appears. Modify the parameters
accordingly.
NWD-142957-01E Operation
NE Setup 4-75
8. The Service Status Setting window appears again. Confirm the NTP Server
Address information displayed.
Operation NWD-142957-01E
4-76 NE Setup
Procedure 4-23
3. Select Service Status Setting from the Security Management sub menu.
4. The Service Status Setting window appears. Click Clear NTP Server.
5. The Clear NTP Server box appears. Select the NTP Server Address number
from drop-down list, and then click OK button.
NWD-142957-01E Operation
NE Setup 4-77
8. The Service Status Setting window appears again. Confirm the NTP Server
Address information displayed.
Operation NWD-142957-01E
4-78 NE Setup
4.3.4.7 FTP
Procedure 4-24
3. Select Service Status Setting from the Security Management sub menu.
5. The FTP Setting box appears. Assign a proper value for each parameter.
NWD-142957-01E Operation
NE Setup 4-79
Operation NWD-142957-01E
4-80 NE Setup
8. The Service Status Setting window appears again. Confirm the FTP
information displayed.
NWD-142957-01E Operation
NE Setup 4-81
4.3.4.8 SFTP
Procedure 4-25
3. Select Service Status Setting from the Security Management sub menu.
Click SFTP.
Operation NWD-142957-01E
4-82 NE Setup
8. The Service Status Setting window appears again. Confirm the displayed
SFTP information.
NWD-142957-01E Operation
NE Setup 4-83
4.3.4.9 HTTP
Procedure 4-26
3. Select Service Status Setting from the Security Management sub menu.
Operation NWD-142957-01E
4-84 NE Setup
Click HTTP.
5. The HTTP Setting box appears. Assign a proper value for each parameter.
NWD-142957-01E Operation
NE Setup 4-85
8. The Service Status Setting window appears again. Confirm the HTTP
information displayed.
Operation NWD-142957-01E
4-86 NE Setup
4.3.4.10 HTTPS
Procedure 4-27
2. Expand Security Management from the User Account/Security Setting sub menu.
3. Select Service Status Setting from the Security Management sub menu.
NWD-142957-01E Operation
NE Setup 4-87
8. The Service Status Setting window appears again. Confirm the displayed
HTTPS information.
Operation NWD-142957-01E
4-88 NE Setup
Note: This function is available for Admin access level user only.
RADIUS Setting
Procedure 4-28
RADIUS link
NWD-142957-01E Operation
NE Setup 4-89
5. The RADIUS Setting dialog box appears. Enter the proper value for each
parameter.
Operation NWD-142957-01E
4-90 NE Setup
Procedure 4-29
NWD-142957-01E Operation
NE Setup 4-91
5. The RADIUS Server Setting box appears. Enter the proper value for each
parameter.
6. Click Set Secret Key in the RADIUS Server Setting dialog box. The Set
Secret Key box appears. Enter the same password into New Secret Key and
Re-Enter boxes and then click OK button.
Operation NWD-142957-01E
4-92 NE Setup
7. The RADIUS Server Setting dialog box appears again. Click OK button to
close the dialog box.
10. The RADIUS Setting window appears again. Confirm RADIUS Server
information displayed.
NWD-142957-01E Operation
NE Setup 4-93
Procedure 4-30
4. Click Clear RADIUS Server on the top of the RADIUS Setting window.
5. The Clear SNMP Server box appears. Select the RADIUS Server No. from
the drop-down list, and then click OK button
Operation NWD-142957-01E
4-94 NE Setup
8. The RADIUS Setting window appears again. Confirm the RADIUS Server
information displayed.
NWD-142957-01E Operation
NE Setup 4-95
Easy Setup
MODEM Setup
AMR Setup
Management Setup
Setting for IP address, Subnet mask and default gateway for NE.
ETH Setup
Operation NWD-142957-01E
4-96 NE Setup
The easy setup is a wizard that guides the user to set up the basic configuration by
following the correct sequences.
Procedure 4-31
2. Select the Easy Setup from the Easy Setup Wizard sub menu.
Setup button.
NWD-142957-01E Operation
NE Setup 4-97
4. The Easy Setup - Step1 window appears. Enter the equipment name then
click Next button.
Next button
Note
The left part of the window shows the current setup while on the right part of
the window, user can edit the configuration.
Operation NWD-142957-01E
4-98 NE Setup
NWD-142957-01E Operation
NE Setup 4-99
6. The Easy Setup Step3 window appears. Confirm the value of the
parameters and then click OK button.
9. The MODEM Setup wizard appears. Refer to the next sub section for details.
Operation NWD-142957-01E
4-100 NE Setup
Procedure 4-32
1. After Easy Setup wizard is completed or MODEM Setup is selected from the
Easy Setup Wizard sub menu, click the Setup button.
2. The MODEM Setup - Step1 window appears. Assign a proper value for each
parameter.
NWD-142957-01E Operation
NE Setup 4-101
4. The MODEM Setup - Step2 window appears. The parameters that have been
modified will be marked with blue background. Confirm the value of the
parameters and then click OK button.
Operation NWD-142957-01E
4-102 NE Setup
7. The Management Setup wizard appears. Refer to the next sub section for
details.
NWD-142957-01E Operation
NE Setup 4-103
Procedure 4-33
1. After the MODEM Setup wizard is completed, the Step1 AMR Operation box
appears.
2. Specify AMR range by clicking the proper radio buttons for reference
modulation (QPSK to 256QAM, Used). Click Next button.
Operation NWD-142957-01E
4-104 NE Setup
6. The Management Setup wizard appears. Proceed to the next sub section.
NWD-142957-01E Operation
NE Setup 4-105
Note: The Warning box appears. Click Maintenance button on the top of the
LCT window to turn on maintenance mode.
Procedure 4-34
3. Click OK button.
Operation NWD-142957-01E
4-106 NE Setup
5. The Management Setup wizard appears. Refer to the next sub section for
details.
NWD-142957-01E Operation
NE Setup 4-107
Procedure 4-35
Next button
Operation NWD-142957-01E
4-108 NE Setup
Notes
1. EPL (Ethernet Private Line)
EPL is a data service defined by the Metro Ethernet Forum, providing a
point-to-point Ethernet connection between a pair of dedicated
User-Network Interfaces (UNIs), with a high degree of transparency.
EPL service is specified using an E-Line service type, with an expectation of
low Frame Delay, Frame Delay Variation and Frame Loss Ratio. EPL is
implemented as a point-to-point Ethernet Virtual Connection (EVC) which,
unlike Ethernet Virtual Private Line (EVPL), does not allow for Service
Multiplexing, i.e., a dedicated UNI (physical interface) is used to accept all
service frames and map them to a single EVC (a.k.a. All-to-one bundling).
Due to a high degree of transparency, EPL is often used to provide
point-to-point Transparent LAN Service (TLS), where the Service Frames
header and payload are identical at both the source and destination UNI.
EPL is not fully transparent, as it must filter IEEE 802.3x Pause frames.
2. EVPL (Ethernet Virtual Private Line)
Ethernet Virtual Private Line (EVPL) is a data service defined by the Metro
Ethernet Forum, providing a point-to-point Ethernet connection between a
pair of User-Network Interfaces (UNIs).
EVPL service is specified using an E-Line service type, very similar to a
Ethernet Private Line (EPL) service, via a point-to-point Ethernet Virtual
Connection (EVC). However, unlike EPL, EVPL allows for Service
Multiplexing, i.e., multiple EVCs or Ethernet services per UNI.
The other difference between the EVPL and EPL is the degree of
transparency - while EPL is highly transparent, filtering only the Pause
frames, EVPL is required to either peer or drop most of the Layer 2 Control
Protocols.
NWD-142957-01E Operation
NE Setup 4-109
OK button
Operation NWD-142957-01E
4-110 NE Setup
Notes
1. Ethernet Private LAN (EPLAN) is a Metro Ethernet service type defined by
the Metro Ethernet Forum.
Because E-LAN services implement multipoint-to-multipoint Ethernet virtual
connections (EVC), multiple locations can be interconnected using an
EPLAN service. However, each location can be a member of one and only
one EVC. If a given location requires connection to a second EVC, it will
require a second UNI.
Because there is only one EVC per UNI, the EVC can be invisible to the
customer (e.g., the customer will not see an 802.1p VLAN tag).
2. Ethernet Virtual Private LAN (EVPLAN) is a Metro Ethernet service type
defined by the Metro Ethernet Forum.
Because E-LAN services implement multipoint-to-multipoint Ethernet virtual
connections (EVC), this service provides Metro Ethernet with a multipoint
service that can support multiple overlapping closed-user groups. For
example, a district school system with elementary, middle, and high schools
could put on of the high schools on one EVC , all of the middle schools on a
second EVC, and all of the elementary schools on a third EVC, using
EPLAN services at each school. The district data center and administrative
offices could have EVPLAN service and be made a member of all three
EVCs without the need for three UNIs.
Because there are multiple EVCs per UNI in an EVPLAN service, the EVCs
must be visible to the customer. To do this, the service provider expects
customer traffic to have an appropriate 802.1p VLAN tag when submitted.
The network will also deliver tagged traffic to that location so that the
customer knows which EVC traffic is arriving from.
NWD-142957-01E Operation
NE Setup 4-111
Operation NWD-142957-01E
4-112 NE Setup
Equipment Configuration
Radio Configuration
AMR Configuration
Setting for IP Address of each port and functions that mounted at the front face
of iPASOLINK
NWD-142957-01E Operation
NE Setup 4-113
Procedure 4-36
Setup button
Operation NWD-142957-01E
4-114 NE Setup
4. The Step1 window appears. Input Equipment Name and then click Next
button.
Note
The left part of the window shows the current setup while on the right part of the
window, user can edit the configuration.
NWD-142957-01E Operation
NE Setup 4-115
5. The Step2 window appears, Assign the MODEM usage., and click Next button.
Operation NWD-142957-01E
4-116 NE Setup
6. The Step3 window appears, input necessary parameter, Confirm the value of the
parameters and then click OK button.
OK button
NWD-142957-01E Operation
NE Setup 4-117
Operation NWD-142957-01E
4-118 NE Setup
Procedure 4-37
Setup button
NWD-142957-01E Operation
NE Setup 4-119
4. The Step1 window appears. Input all necessary parameters and click Next
button.
Next button
Operation NWD-142957-01E
4-120 NE Setup
6. The Step2 window appears. Confirm that the setup parameter changes to blue
then click OK button.
NWD-142957-01E Operation
NE Setup 4-121
Operation NWD-142957-01E
4-122 NE Setup
Procedure 4-38
2. The Step1 AMR Operation window appears. Assign a proper value for each
parameter.
NWD-142957-01E Operation
NE Setup 4-123
4. The Step2 window appears. Confirm that the fields of modified parameters
change to blue, and click OK button.
Operation NWD-142957-01E
4-124 NE Setup
7. The AMR Configuration window appears. Confirm that all parameters are set.
NWD-142957-01E Operation
NE Setup 4-125
In this menu execute the setting of function for each port mounted on front face of
iPASOLINK.
General Setting
In order to connect the iPASOLINK and NMS, execute the setting for using/un
using of NMS Port and IP Address.
Routing Setting
This setting allows to give out IP addresses to a user port. via In-band VLAN.
Procedure 4-39
1. Click the Maintenance button on the top of the LCT window to turn on the
maintenance mode.
2. Expand Equipment Setup from the WebLCT menu.
Operation NWD-142957-01E
4-126 NE Setup
NWD-142957-01E Operation
NE Setup 4-127
9. The General Setting window appears again. Confirm that all parameters are
set.
10. After finishing General Setting, click Maintenance button on the top of the
WebLCT window to exit maintenance mode.
Operation NWD-142957-01E
4-128 NE Setup
Procedure 4-40
1. Click the Maintenance button on the top of the LCT window to turn on the
maintenance mode.
NWD-142957-01E Operation
NE Setup 4-129
Setup button
Operation NWD-142957-01E
4-130 NE Setup
6. The General Setting (Detail) box appears. Assign a proper value for each
parameter.
NWD-142957-01E Operation
NE Setup 4-131
Operation NWD-142957-01E
4-132 NE Setup
Notes:
1. When this function is enabled, bandwidth of traffic from CPU is reserved.
2. Even as the ETH side is 4-Class mode, the M-Plane Mode can be selected
from 5 to 7.
4-Class: M-Plane (7, 6) > User (3), M-Plane (5) > User (2)
3. In the case the radio transmission band is occupied by delay sensitive user
traffic, such as PWE, decrease the M-Plane Priority if the Bandwidth
Limitation is disabled.
NWD-142957-01E Operation
NE Setup 4-133
8. The General Setting (Detail) box appears again. Click Bridge No. of the NE
Branch Setting field.
Bridge
No.
Operation NWD-142957-01E
4-134 NE Setup
9. The IP Address Setting box appears. Input the IP address and the subnet
mask, and then click OK button.
13. The General Setting (Detail) window appears again. Confirm that all
parameter are set.
14. After finishing General Setting (Detail), click Maintenance button on the top
of the WebLCT window to exit maintenance mode.
NWD-142957-01E Operation
NE Setup 4-135
Root NE
PNMSj
Modem 1
NMS
Bridge 1
Bridge 2 Primary IP
Secondary IP
This function provide user to specify the static route for the particular network or
IP address.
Procedure 4-41
1. Click the Maintenance button on the top of the LCT window to turn on the
maintenance mode.
Operation NWD-142957-01E
4-136 NE Setup
7. The Routing Setting (Add) box appears. Input the IP Address, Subnet Mask,
and Gateway, and then click OK button.
NWD-142957-01E Operation
NE Setup 4-137
8. The Routing Setting box appears again. Confirm the newly added route
information displayed.
Operation NWD-142957-01E
4-138 NE Setup
12. The Routing Setting window appears again. Confirm that the newly added
route information displayed.
13. After finishing Routing Setting, click Maintenance button on the top of the
WebLCT window to exit maintenance mode.
1. Click the Maintenance button on the top of the LCT window to turn on the
maintenance mode.
NWD-142957-01E Operation
NE Setup 4-139
7. The Routing Setting (Modify) box appears. Modify the IP Address, subnet
mask and gateway accordingly then click OK button.
Operation NWD-142957-01E
4-140 NE Setup
8. The Routing Setting box appears again. Confirm the route information
displayed.
NWD-142957-01E Operation
NE Setup 4-141
12. The Routing Setting window appears again. Confirm the route information
displayed.
13. After finishing Routing Setting, click Maintenance button on the top of the
WebLCT window to exit maintenance mode.
Procedure 4-42
1. Click the Maintenance button on the top of the LCT window to turn on the
maintenance mode.
Operation NWD-142957-01E
4-142 NE Setup
Setup button
Delete button
NWD-142957-01E Operation
NE Setup 4-143
7. The Routing Setting (Delete) box appears. Enter the network address
displayed in the list, and then click OK button.
8. The Routing Setting box appears again. Confirm that the specified network
has been deleted, then click OK button.
Operation NWD-142957-01E
4-144 NE Setup
11. The Routing Setting window appears again. Confirm the route information
displayed.
12. After finishing Routing Setting, click Maintenance button on the top of the
WebLCT window to exit maintenance mode.
Procedure 4-43
1. Click the Maintenance button on top of the LCT window to put the system into
the maintenance mode.
NWD-142957-01E Operation
NE Setup 4-145
5. Select Input Filter List tab, and click Add Entry button.
6. The Input Filter Entry (Add) option box appears. Specify the filter condition,
then click OK button.
Operation NWD-142957-01E
4-146 NE Setup
Note: Filter entries are not applied to traffic from the LCT port.
For inband interface, filter entries are applied to only traffic towards the CPU
of the IDU, transit traffic is sent to next hop.
NWD-142957-01E Operation
NE Setup 4-147
7. The IP Access Control Setting window appears again. Confirm that the
newly added filter information displayed.
Procedure 4-44
1. Click the Maintenance button on the top of the LCT window to put the system
into the maintenance mode.
Operation NWD-142957-01E
4-148 NE Setup
Entry
No
6. The Input Filter Entry (Modify) option box appears. Specify the filter
condition, then click OK button.
NWD-142957-01E Operation
NE Setup 4-149
Operation NWD-142957-01E
4-150 NE Setup
8. The IP Access Control Setting window appears again. Confirm that the
modified filter information is displayed.
Procedure 4-45
1. Click the Maintenance button on the top of the LCT window to put the system
into the maintenance mode.
NWD-142957-01E Operation
NE Setup 4-151
5. Select Input Filter List tab, and click Delete Entry button.
6. The Input Filter Entry (Delete) option box appears. Enter the Entry No. of
the filter to be deleted, and then click OK button.
Operation NWD-142957-01E
4-152 NE Setup
9. The IP Access Control Setting window appears again. Confirm that the
selected filter information is removed.
NWD-142957-01E Operation
NE Setup 4-153
Procedure 4-46
1. Click the Maintenance button on the top of the LCT window to put the system
into the maintenance mode.
5. Select Input Filter List tab, and click Modify Rule button.
Operation NWD-142957-01E
4-154 NE Setup
6. The Input Filter Rule option box appears. Specify the filter condition then
click OK button.
NWD-142957-01E Operation
NE Setup 4-155
8. The IP Access Control Setting window appears again. Confirm that the
modified filter information is displayed.
Procedure 4-47
1. Click the Maintenance button on the top of the LCT window to put the system
into the maintenance mode.
Operation NWD-142957-01E
4-156 NE Setup
5. Select Forwarding Filter List tab, and click Add Entry button.
6. The Forwarding Filter Entry (Add) option box appears. Specify the filter
condition, then click OK button.
NWD-142957-01E Operation
NE Setup 4-157
Operation NWD-142957-01E
4-158 NE Setup
8. The IP Access Control Setting window appears again. Confirm that the
newly added filter information is displayed.
Procedure 4-48
1. Click the Maintenance button on the top of the LCT window to put the system
into the maintenance mode.
NWD-142957-01E Operation
NE Setup 4-159
Entry No.
6. The Forwarding Filter Entry (Modify) option box appears. Modify the
filter condition, then click OK button.
Operation NWD-142957-01E
4-160 NE Setup
NWD-142957-01E Operation
NE Setup 4-161
8. The IP Access Control Setting window appears again. Confirm the display
for the modified filter information.
Procedure 4-49
1. Click the Maintenance button on the top of the LCT window to put the system
into the maintenance mode.
Operation NWD-142957-01E
4-162 NE Setup
5. Select Forwarding Filter List tab, and click Delete Entry button.
6. The Forwarding Filter Entry (Delete) option box appears. Enter the Entry
No. of the filter to be deleted, and then click OK button.
NWD-142957-01E Operation
NE Setup 4-163
9. The IP Access Control Setting window appears again. Confirm that the
selected filter information is removed.
Procedure 4-50
1. Click the Maintenance button on the top of the LCT window to put the system
into the maintenance mode.
Operation NWD-142957-01E
4-164 NE Setup
5. Select Forwarding Filter List tab, and click Modify Rule button.
6. The Forwarding Filter Rule option box appears. Modify the filter condition,
then click OK button.
NWD-142957-01E Operation
NE Setup 4-165
8. The IP Access Control Setting window appears again. Confirm the display
for the modified filter information.
Operation NWD-142957-01E
4-166 NE Setup
Procedure 4-51
1. Expand Equipment Setup from the WebLCT menu.
NWD-142957-01E Operation
NE Setup 4-167
4. The DHCP Server / Relay Setting window appears. Click 0l in the DHCP
No. column.
DHCP No.
Operation NWD-142957-01E
4-168 NE Setup
5. DHCP Server / Relay Setting (DHCP No.01) box appears. Select DHCP
Server from the Server / Relay pull down menu. Then, specify a proper value
for each parameter then click OK button.
NWD-142957-01E Operation
NE Setup 4-169
6. Click Detail button. DHCP Server Detail Setting (DHCP No.01) box
appears. Then, specify a proper value for each parameter, then click OK button.
Operation NWD-142957-01E
4-170 NE Setup
7. The Forwarding Filter Rule option box appears. Modify the filter condition,
then click OK button.
8. Repeat the above step for DHCP No.02 and 03 if its needed.
9. If the above given out IP address is assigned to DHCP client, the IP address is
shown in the DHCP Client Table in the DHCP Server / Relay Setting
window.
Figure 4-246 DHCP Server / Relay Setting Window (Given out IP Address)
NWD-142957-01E Operation
NE Setup 4-171
Procedure 4-52
1. Expand Equipment Setup from the WebLCT menu.
4. The DHCP Server / Relay Setting window appears. Click 02 in the DHCP
No. column.
5. DHCP Server / Relay Setting (DHCP No.02) box appears. Select DHCP
Relay from the Server / Relay pull down menu. Then, specify a proper value
for each parameter then click OK button.
Operation NWD-142957-01E
4-172 NE Setup
NWD-142957-01E Operation
NE Setup 4-173
Procedure 4-53
5. Confirm that the DHCP No.01 tab is active, and click Add MAC Address
button.
Add MAC Address button
Figure 4-249 DHCP Server / Relay Setting Window - Add MAC Address
Operation NWD-142957-01E
4-174 NE Setup
NWD-142957-01E Operation
NE Setup 4-175
9. The DHCP Server / Relay Setting window appears. Confirm the MAC
address is added in the Registered MAC Address Table.
Operation NWD-142957-01E
4-176 NE Setup
NWD-142957-01E Operation
System Operation 5-1
5. SYSTEM OPERATION
5.1 Provisioning
This setup is for further system fundamental configuration after the equipment setup.
The setting items are listed as follows:
User can configure the Ethernet port, VLAN ETH OAM, RSTP, QOS, link loss
forwarding and so on.
Alarm Setting
PMON/RMON Setting
User can configure the threshold of PMON (except Ethernet)/ RMON (Ethernet).
TX Power Setting
Operation NWD-142957-01E
5-2 System Operation
Specify the ATPC power mode and ALM mode when ODU communication
fails.
AMR Setting
Procedure 5-1
3. Select MODEM Port Setting from the MODEM Function Setting sub menu.
4. The MODEM Port Setting window appears. Click the desired MODEM to
configure.
NWD-142957-01E Operation
System Operation 5-3
5. The MODEM Port Setting dialog box appears. Assign a proper value for each
parameter.
Operation NWD-142957-01E
5-4 System Operation
8. The MODEM Port Setting window appears again. Confirm the displayed
parameters.
NWD-142957-01E Operation
System Operation 5-5
Procedure 5-2
3. Select TX Power Setting from the MODEM Function Setting sub menu.
4. The TX Power Setting window appears. Click the desired MODEM No. (or
SW GRP1) to configure.
5. The TX Power Setting dialog box appears. Assign a proper value for each
parameter.
Operation NWD-142957-01E
5-6 System Operation
ATPC Range (MIN) -30.5 to 0.0 dBm Set ODU minimum TX power level in ATPC mode
MTPC TX Power -30 to 0 dBm Not select
RX Threshold -95 - -30 dBm Set threshold of RX LEVEL in ATPC mode
NWD-142957-01E Operation
System Operation 5-7
Procedure 5-3
3. Select TX Power Setting from the MODEM Function Setting sub menu.
4. The TX Power Setting window appears. Click the desired MODEM No. (or
SW GRP1) to configure.
5. The TX Power Setting dialog box appears. Assign a proper value for each
parameter.
Operation NWD-142957-01E
5-8 System Operation
NWD-142957-01E Operation
System Operation 5-9
Specify the ATPC power mode and ALM mode when ODU communication fails.
Procedure 5-4
3. Select ALM Mode Setting from the MODEM Function Setting sub menu.
4. The ALM Mode Setting window appears. Click the desired MODEM No. (or
SW GRP1) to configure.
5. The ALM Mode Setting dialog box appears. Assign a proper value for each
parameter.
Operation NWD-142957-01E
5-10 System Operation
Note: In case user has selected MTPC, ATPC Power Mode will be Invalid.
8. The ALM Mode Setting window appears again. Confirm the displayed
parameters.
NWD-142957-01E Operation
System Operation 5-11
Procedure 5-5
3. Select AMR Setting from the MODEM Function Setting sub menu.
6. The AMR Setting dialog box appears. Assign a proper value for each parameter.
Operation NWD-142957-01E
5-12 System Operation
NWD-142957-01E Operation
System Operation 5-13
Bridge Setting
Bridge function also known as switching function that enable the device in the
multiple network segments can communicate with each other. User can
configure the FDB (forward database) aging time, default VLAN ID and VLAN
mode here.
This function provide user the abilities that configure the attributes of the
Ethernet port on the front panel of iPASOLINK, including port name, line speed,
Mode, Flow Control etc.
VLAN Setting
VLAN (Virtual Local Area Network) enable multiple devices which separated
physically can communicate as they are located in a same broadcast domain and
also protect the data from send to other domain even they may connected
physically.
This function provide user the abilities of create, configure and delete the VLAN.
FDB Setting
iPASOLINK can learn the MAC address of the Ethernet frame dynamically and
save the port MAC address mapping information into FDB (Forwarding
DataBase) based on IEEE802.1d for each VLAN. User can also add the static
mapping information manually by this function.
RSTP Setting
User can set the priority of the bridge; specify the role of the Ethernet port and
other parameters.
Operation NWD-142957-01E
5-14 System Operation
MSTP Setting
The MSTP (Multiple Spanning Tree Protocol) defined in the IEEE802.1s is the
spanning tree protocol work with logical instances. One instance can include
multiple VLANs. Blocking port is decided per logical instance, then physically
configured redundant Ethernet topology can be utilized efficiently.
Note: MSTP and ETH-Ring functions are not configured at the same time.
Link Aggregation achieves high capacity and resiliency transport with bundling
several radio links. The distribution algorithm distributes the packet according
to:
L2 based: Source & Destination MAC, VLAN ID, Ethernet type, Physical
Port ID
L3&L4 based: Source & Destination IP, Source & Destination TCP/UDP
Port Number
Also, ETH Ports support Both of LACP and Non-LACP operation with carrier
class 1:1 LACP Protection.
ERP Setting
Load balancing works under the normal operation, and the higher priority
traffic can be secured by QoS management.
Administrative operation
Forced switching
Manual switching
Revertive / Non-revertive
NWD-142957-01E Operation
System Operation 5-15
The combination of logical ring set-up and load balancing achieves double
capacity transmission.
QoS/Classification Setting
Filter Setting
Port Mirroring enables to monitor the traffic at another (mirrored) port without
traffic of source port interruption. Ingress, egress or both direction of the port to
be mirrored to the destination port can be specified
Port isolation can restrict the transmission even within the same VLAN. Ports
which are configured as port isolation cannot communicate with another same
VLAN port. Also, broadcast traffic is not transmitted. This function can protect
the user traffic from the attacks such as being executed from inside own network
(same subnet).
LLF Setting
LLF (Link Loss Forwarding) is the function that mandatory shutdown the port on
the opposite device when local device detected unidirectional link problem.
Operation NWD-142957-01E
5-16 System Operation
Procedure 5-6
3. Select Bridge Setting from the ETH Function Setting sub menu.
Modify button
NWD-142957-01E Operation
System Operation 5-17
5. The Bridge Setting dialog box appears. Assign a proper value for each
parameter.
Operation NWD-142957-01E
5-18 System Operation
8. The Bridge Setting window appears again. Confirm the displayed parameters.
Procedure 5-7
3. Select ETH Port Setting from the ETH Function Setting sub menu.
4. The ETH Port Setting window appears. Click the desired Port No. to
configure.
NWD-142957-01E Operation
System Operation 5-19
Port No.
5. The ETH Port Setting dialog box appears. Assign a proper value for each
parameter.
Operation NWD-142957-01E
5-20 System Operation
*1 When Auto of Speed is selected, Duplex and MDI and MDIX are not selectable.
8. The ETH Port Setting window appears again. Confirm the displayed
parameters.
NWD-142957-01E Operation
System Operation 5-21
Procedure 5-8
3. Select VLAN Setting from the ETH Function Setting sub menu.
Operation NWD-142957-01E
5-22 System Operation
5. The VLAN List tab appears. Click Add VLAN ID button to create a new
VLAN ID.
VLAN ID button
6. The Add VLAN ID dialog box appears. Refer to the table below to assign a
proper value for each parameter accordingly.
NWD-142957-01E Operation
System Operation 5-23
Note: Plural VLAN IDs can be entered using comma(s) and/or hyphen in
the following patterns.
VLAN ID: 1,2,3,1000-4094
LAN Service Name: VLAN Name
(1) Plural IDs can be registered by using comma(s) and/or a hyphen, and in the above
example, VLAN IDs 1, 2, 3, and 1000 to 4094 are registered (totally 3098 IDs).
Entering 1000-4094,1,2,3 is also possible.
(2) The maximum input number of characters for the VLAN Service Name is 27
characters.
(3) If there is a VLAN ID already registered in the range of registeration, a new VLAN
ID can be registered in a skip number.
(4) The VLAN Service Name of the skipped VLAN ID is not overwritten.
(5) When VLAN IDs are entered in a range, register the VLAN Service Name, adding
a suffix -xxxx (xxxx=0001-4094) to the entered value.
(6) When the VLAN Service Name is already registered, the new VLAN Service
Name should be blank.
(7) When VLAN IDs are not entered in a range, the name that was registered in the
VLAN Service Name field should be registered as-is.
Operation NWD-142957-01E
5-24 System Operation
9. The VLAN Setting window appears again. Confirm the displayed parameters.
Procedure 5-9
3. Select VLAN Setting from the ETH Function Setting sub menu.
NWD-142957-01E Operation
System Operation 5-25
5. The VLAN List tab appears. Click the VLAN Service Name to be modified.
Operation NWD-142957-01E
5-26 System Operation
6. The Modify VLAN Service Name box appears. Modify the VLAN Service
Name accordingly.
9. The VLAN List tab appears again. Confirm the modified VLAN Service Name.
NWD-142957-01E Operation
System Operation 5-27
Procedure 5-10
3. Select VLAN Setting from the ETH Function Setting sub menu.
Operation NWD-142957-01E
5-28 System Operation
6. The Delete VLAN ID box appears. Input the VLAN ID or VLAN Service Name
to be deleted.
NWD-142957-01E Operation
System Operation 5-29
10. The VLAN List tab appears again. Confirm the VLAN ID has been deleted.
Operation NWD-142957-01E
5-30 System Operation
Procedure 5-11
3. Select VLAN Setting from the ETH Function Setting sub menu.
5. The VLAN Setting window appears. Assign a proper value for each VLAN
Assignment field parameter.
Note: The views are different according to the configuration (Access/ Tunnel/
Trunk).
NWD-142957-01E Operation
System Operation 5-31
Access
Tunnel
Operation NWD-142957-01E
5-32 System Operation
Trunk
NWD-142957-01E Operation
System Operation 5-33
8. The VLAN Setting window appears again. Confirm the parameters displayed.
Operation NWD-142957-01E
5-34 System Operation
Procedure 5-12
3. Select FDB Setting from the ETH Function Setting sub menu.
Equipment
NWD-142957-01E Operation
System Operation 5-35
5. The FDB Setting (Equipment) dialog box appears. Assign a proper value for
each parameter.
Operation NWD-142957-01E
5-36 System Operation
8. The FDB Setting tab window appears again. Confirm the displayed parameters.
Procedure 5-13
3. Select FDB Setting from the ETH Function Setting sub menu.
NWD-142957-01E Operation
System Operation 5-37
4. The FDB Setting window appears. Click on the desired VLAN ID No. to
configure in the Service tab in the FDB Setting tab.
V LAN ID
5. The FDB Setting box appears. Assign a proper value for each parameter.
Operation NWD-142957-01E
5-38 System Operation
NWD-142957-01E Operation
System Operation 5-39
8. The FDB Setting tab appears again. Confirm the displayed parameters.
Procedure 5-14
3. Select FDB Setting from the ETH Function Setting sub menu.
Operation NWD-142957-01E
5-40 System Operation
NWD-142957-01E Operation
System Operation 5-41
Procedure 5-15
3. Select FDB Port Setting from the ETH Function Setting sub menu.
4. The FDB Setting window appears. Click the Static Entry tab.
Operation NWD-142957-01E
5-42 System Operation
Add button
6. The Static Entry (Add) dialog box appears. Refer to the table below to assign
a proper value for each parameter accordingly.
NWD-142957-01E Operation
System Operation 5-43
9. The Static Entry tab appears again. Confirm the displayed parameters.
Operation NWD-142957-01E
5-44 System Operation
Procedure 5-16
3. Select FDB Port Setting from the ETH Function Setting sub menu.
4. The FDB Setting window appears. Click the Static Entry tab.
NWD-142957-01E Operation
System Operation 5-45
5. The Static Entry tab appears. Click the desired Entry No. to configure.
Entry No.
6. The Static Entry dialog box appears. Modify the MAC address accordingly.
Operation NWD-142957-01E
5-46 System Operation
9. The Static Entry tab appears again. Confirm the modified parameters of the
MAC address.
Procedure 5-17
3. Select FDB Port Setting from the ETH Function Setting sub menu.
NWD-142957-01E Operation
System Operation 5-47
4. The FDB Setting window appears. Click the Static Entry tab.
Delete button
Operation NWD-142957-01E
5-48 System Operation
6. The Static Entry (Delete) dialog box appears. Check the static entry No. to
be deleted.
NWD-142957-01E Operation
System Operation 5-49
10. The Static Entry tab appears again. Confirm the static entry No. has been
deleted.
Procedure 5-18
3. Select ETH OAM Setting from the ETH Function Setting sub menu.
Operation NWD-142957-01E
5-50 System Operation
4. The ETH OAM Setting window appears. Click the OAM MEG tab.
5. The OAM MEG tab appears. Click the Add MEG button.
6. The OAM MEG Setting (Add) box appears. Refer to the table below to assign
a proper value for each parameter accordingly.
NWD-142957-01E Operation
System Operation 5-51
Operation NWD-142957-01E
5-52 System Operation
9. The OAM MEG tab appears again. Confirm the newly added MEG Index
information displayed.
Procedure 5-19
3. Select ETH OAM Setting from the ETH Function Setting sub menu.
4. The ETH OAM Setting window appears. Click the OAM MEG tab.
NWD-142957-01E Operation
System Operation 5-53
5. The OAM MEG tab appears. Click the Delete MEG button.
6. The OAM MEG Setting (Delete) box appears. Select the OAM MEG Index
No. to be deleted.
7. Click OK button.
Operation NWD-142957-01E
5-54 System Operation
10. The OAM MEG tab appears again. Confirm the OAM MEG has been deleted.
Procedure 5-20
3. Select ETH OAM Setting from the ETH Function Setting sub menu.
NWD-142957-01E Operation
System Operation 5-55
4. The ETH OAM Setting window appears. Click Add MEP button in the OAM
MEP tab.
5. The OAM MEP Setting (Add) dialog box appears. Select the Enable radio
button in the MEG Configuration field.
Operation NWD-142957-01E
5-56 System Operation
6. Click Add Peer MEP button in the Peer MEP Configuration field.
7. The Peer MEP Add box appears. Input the Peer MEP ID.
NWD-142957-01E Operation
System Operation 5-57
9. The OAM MEP Setting (Add) dialog box appears again. Refer to the table
below to assign a proper value for each parameter accordingly.
Operation NWD-142957-01E
5-58 System Operation
NWD-142957-01E Operation
System Operation 5-59
13. The OAM MEP tab appears again. Confirm the newly added MEP Index
information displayed.
Procedure 5-21
3. Select ETH OAM Setting from the ETH Function Setting sub menu.
Operation NWD-142957-01E
5-60 System Operation
4. The ETH OAM Setting window appears. Click the MEP Index No. to be
modified in the OAM MEP tab.
5. The OAM MEP Setting (Modify) dialog box appears. Modify the parameter
accordingly.
NWD-142957-01E Operation
System Operation 5-61
Operation NWD-142957-01E
5-62 System Operation
9. The OAM MEP tab appears again. Confirm the modified parameters of the
OAM MEP Index information displayed.
Procedure 5-22
3. Select ETH OAM Setting from the ETH Function Setting sub menu.
4. The ETH OAM Setting window appears. Click Delete MEP button in the
OAM MEP tab.
NWD-142957-01E Operation
System Operation 5-63
5. The OAM MEP Setting (Delete) box appears. Select the OAM MEP Index No.
to be deleted.
6. Click OK button.
Operation NWD-142957-01E
5-64 System Operation
Note: In case that CCM Transmit / CCM Receive is enabled, if user try to
delete the MEP Index the following error message will appears:
Follow the procedure of (2) Modify OAM MEP Index, disable CCM
Transmit / CCM Receive first and then delete the MEP Index.
9. The OAM MEP tab appears again. Confirm the OAM MEP has been deleted.
NWD-142957-01E Operation
System Operation 5-65
Procedure 5-23
3. Select ETH OAM Setting from the ETH Function Setting sub menu.
4. The ETH OAM Setting window appears. Click the OAM MIP tab.
Operation NWD-142957-01E
5-66 System Operation
6. The OAM MIP Setting (Add) box appears. Refer to the table below to assign a
proper value for each parameter accordingly.
NWD-142957-01E Operation
System Operation 5-67
9. The OAM MIP tab appears again. Confirm the newly added OAM MIP
information displayed.
Procedure 5-24
3. Select ETH OAM Setting from the ETH Function Setting sub menu.
Operation NWD-142957-01E
5-68 System Operation
4. The ETH OAM Setting window appears. Click the OAM MIP tab.
5. The OAM MIP tab appears. Click the desired MIP Index No. to configure.
NWD-142957-01E Operation
System Operation 5-69
6. The OAM MIP Setting (Modify) box appears. Modify the parameter
accordingly.
Operation NWD-142957-01E
5-70 System Operation
9. The OAM MIP tab appears again. Confirm the modified parameters of the OAM
MIP information displayed.
Procedure 5-25
3. Select ETH OAM Setting from the ETH Function Setting sub menu.
NWD-142957-01E Operation
System Operation 5-71
4. The ETH OAM Setting window appears. Click the OAM MIP tab.
6. The OAM MIP Setting (Delete) box appears. Select the OAM MIP Index No.
to be deleted.
7. Click OK button.
Operation NWD-142957-01E
5-72 System Operation
10. The OAM MIP tab appears again. Confirm the OAM MIP Index has been
deleted.
NWD-142957-01E Operation
System Operation 5-73
This equipment can confirm the status of the contiguous equipment and
intervening equipment using the following four functions as the Link OAM
function (IEEE 802.3ah).
a. Discovery
b. Remote Failure (Dying Gasp, Critical Event)
c. Remote Loopback
d. Event Notification
Also, the Link OAM function can work with LLF (Refer to LLF Setting).
Here, description is given for using the Link OAM function. This sample is
showing the case that ETH ports are connected to opposite equipment which link
OAM function is already enabled.
Procedure 5-26
1. Before using the Link OAM tab, set the equipment as follows:
4. Select ETH OAM Setting from the ETH Function Setting sub menu.
5. The ETH OAM Setting window appears. Click the Link OAM tab.
Operation NWD-142957-01E
5-74 System Operation
6. Click the Port01 in the Port column. The Link OAM Setting (Main Board -
Port 01) box appears.
Figure 5-122 Link OAM Setting (Main Board - Port 01) Box
7. Click Enable radio button at the Link OAM, and then the following three items
will become active: Link OAM Mode, Dying Gasp, and Critical Event.
8. Click the above three items (radio buttons) to Active, Enable, and Enable,
respectively.
10. Click the OK button. The ETH OAM Setting window (Link OAM tab)
appears.
NWD-142957-01E Operation
System Operation 5-75
11. Confirm that the Operational status is Up and the Loopback status is Off.
12. For succeeding operation for loopback, refer to the 7. Loopback, Maintenance
Manual.
The Link OAM loopback differs from the Service OAM loopback.
Operation NWD-142957-01E
5-76 System Operation
Note STP/RSTP tunnel enable function is not supported for RSTP enabled
port.
Procedure 5-27
3. Select RSTP / MSTP Setting from the ETH Function Setting sub menu.
4. The RSTP / MSTP Setting window appears. Click Modify STP Mode button.
STP Mode Setting box appears.
NWD-142957-01E Operation
System Operation 5-77
5. Select RSTP from the STP Mode pull down menu. RSTP / MSTP Setting
(RSTP Mode) window appears.
7. The STP Port Setting (STP Mode: RSTP) window appears. Assign a proper
value for each parameter.
Operation NWD-142957-01E
5-78 System Operation
10. The RSTP / MSTP Setting window appears again. Confirm the parameters
displayed.
NWD-142957-01E Operation
System Operation 5-79
Procedure 5-28
3. Select RSTP / MSTP Setting from the ETH Function Setting sub menu.
4. The RSTP / MSTP Setting window appears. Click Modify Detail STP
Parameter button.
5. The Detail STP Parameter Setting box appears. Assign a proper value for
each parameter.
Operation NWD-142957-01E
5-80 System Operation
8. The RSTP / MSTP Setting window appears again. Confirm the parameters
displayed.
NWD-142957-01E Operation
System Operation 5-81
Procedure 5-29
[Sample Configuration]
First referring to VLAN Setting, set VLAN ID=10 and 20 for Port 01 and Port 02 at
local and remote equipments:
VLAN ID=10 for Port 01, Port 02 for both local and remote terminals
VLAN ID=20 for Port 02 for both local and remote terminals
Connect the same port numbers each other using LAN cables.
3. Select RSTP / MSTP Setting from the ETH Function Setting sub menu.
5. Click Modify STP Mode button. STP Mode Setting box appears
Operation NWD-142957-01E
5-82 System Operation
6. Select the MSTP from the pull-down menu. RSTP / MSTP Setting (STP
Mode: MSTP) window appears. Click Modify STP Port button.
NWD-142957-01E Operation
System Operation 5-83
7. STP Port Setting box (STP Mode: MSTP, IST tab) appears. Assign a proper
value for each parameter.
Operation NWD-142957-01E
5-84 System Operation
9. In STP Port Setting box - IST tab, set Enable for Port 01 to Port 03.
NWD-142957-01E Operation
System Operation 5-85
10. In STP Port Setting boxMSTI1 tab, set MSTI1 to Enable, and check the
Enable check box for Port 01 and Port 02.
Operation NWD-142957-01E
5-86 System Operation
11. In STP Port Setting box - MSTI2 tab, set MSTI2 to Enable, and check the
Enable check box for Port 01 and Port 03.
NWD-142957-01E Operation
System Operation 5-87
12. Click the OK button. The RSTP / MSTP Setting windowIST tab appears
again. Confirm the Status column for Port01 and Port02 of both iPASOLINKs.
Operation NWD-142957-01E
5-88 System Operation
Procedure 5-30
4. The ERP Setting windows appears. Click Modify ERP Mode button.
5. ERP Mode Setting box appears. Click the Enable radio button. Then click
OK button.
NWD-142957-01E Operation
System Operation 5-89
7. In the ERP Setting window, Add ERP button becomes valid. Click Add ERP
button.
Operation NWD-142957-01E
5-90 System Operation
8. Step1 ERP Setting box will appear. Assign a proper value for each parameter
NWD-142957-01E Operation
System Operation 5-91
9. Click Next button. Step2 ERP VLAN Setting box appears. Assign a proper
value for each parameter.
Operation NWD-142957-01E
5-92 System Operation
10. Click Next button. Step3 ERP LOC Detection MEP Index Setting box
appears. Assign a proper value for each parameter.
Figure 5-147 Step3 ERP LOC Detection MEP Index Setting Box
NWD-142957-01E Operation
System Operation 5-93
Table 5-25 Step2 ERP LOC Detection MEP Index Setting Box
Item Parameter Description
LOC Detection Enable / Disable Enables failure detection and switching of the
ring using ETH-CC. For fast switching under
50ms, this setting is required with 3.3ms
ETH-CC setting.
Ring Port 0
LOC Detection MEP Index Check / Uncheck Specify the MEP index to be used.
Ring Port 1
LOC Detection MEP Index Check / Uncheck Specify the MEP index to be used.
Operation NWD-142957-01E
5-94 System Operation
14. ERP Setting window appears again. Confirm the displayed parameters
NWD-142957-01E Operation
System Operation 5-95
Procedure 5-31
3. Select Link Aggregation Setting from the ETH Function Setting sub
menu.
4. The Link Aggregation Setting window appears. Click Add LAG button.
Operation NWD-142957-01E
5-96 System Operation
5. Add LAG window appears. Assign a proper value for each parameter.
NWD-142957-01E Operation
System Operation 5-97
Operation NWD-142957-01E
5-98 System Operation
(c) Modify
Procedure 5-32
3. Select Link Aggregation Setting from the ETH Function Setting sub
menu.
5. Link Aggregation Setting box appears. Assign proper value for each
parameter.
10. Click OK button. The Link Aggregation Setting window appears again.
11. Click OK button. The Link Aggregation Setting window appears again.
Confirm the displayed parameters.
Procedure 5-33
3. Select Link Aggregation Setting from the ETH Function Setting sub
menu.
NWD-142957-01E Operation
System Operation 5-99
5. Delete LAG box appears. Click the check box of LAG to be deleted.
13. Click OK button. The Link Aggregation Setting window appears again.
Confirm the LAG item(s) after deletion.
iPASOLINK supports QoS based on MEF10 and REC4115 which classify the
traffic into eight classes with the proper Internal Priority according to the
predetermined Policer. Except the default Policer, user can configure up to three
additional Policer which provide user the capability of realizing the
user-orientation QoS strategy flexibly. The Internal Priority is used for following
purpose:
2) Mapping the eight classes of ingress traffic to four classes when queueing the
Egress traffic.
3) Copy the original internal priority to the capsulated frame to prevent the
traffic priority from changing unexpectedly. (VLAN c-tag CoS/VLAN s-tag
CoS)
Operation NWD-142957-01E
5-100 System Operation
Ingress
At the Ingress of the traffic, assign the internal priority and then perform flow
control according to the predetermined policer, coloring the frame with Yellow
or Green which decide the QoS queue at the egress, discarding the frames of the
traffic that exceed the designated bandwidth (EIR, Excess Information Rate).
Egress
Queueing the frame according to the internal priority and the color assigned at
ingress, determine forwarding or discarding the frame.
Procedure 5-34
NWD-142957-01E Operation
System Operation 5-101
Operation NWD-142957-01E
5-102 System Operation
Procedure 5-35
NWD-142957-01E Operation
System Operation 5-103
Operation NWD-142957-01E
5-104 System Operation
6. The Classify Entry Setting box appears. Assign a proper value for each
parameter.
NWD-142957-01E Operation
System Operation 5-105
Operation NWD-142957-01E
5-106 System Operation
Procedure 5-36
NWD-142957-01E Operation
System Operation 5-107
6. The Delete Entry box appears. Assign a proper value for each parameter and
then click OK button.
Operation NWD-142957-01E
5-108 System Operation
NWD-142957-01E Operation
System Operation 5-109
Procedure 5-37
Operation NWD-142957-01E
5-110 System Operation
5. The Select profile No. box appears. Assign a proper value for drop-down list.
NWD-142957-01E Operation
System Operation 5-111
Procedure 5-38
Operation NWD-142957-01E
5-112 System Operation
5. The Classification Mode window appears. Select the Port Based QoS
Mode
NWD-142957-01E Operation
System Operation 5-113
Procedure 5-39
5. The Port Classification Mode Setting window appears. Select the object
from Port Classification Mode drop-down list and Assign a proper value for
Default Port Priority.
Operation NWD-142957-01E
5-114 System Operation
Procedure 5-40
3. Select QoS/Classification Setting from the ETH Function Setting sub menu.
NWD-142957-01E Operation
System Operation 5-115
Operation NWD-142957-01E
5-116 System Operation
NWD-142957-01E Operation
System Operation 5-117
Procedure 5-41
3. Select QoS / Classification Setting from the ETH Function Setting sub
menu.
Operation NWD-142957-01E
5-118 System Operation
Figure 5-182 QoS / Classification [VLAN ID Based QoS Mode] Setting Window
NWD-142957-01E Operation
System Operation 5-119
8. The Default Priority Setting box appears. Specify the priority from 0 to 7.
10. Click Entry No. to be set. The VLAN Classification Mode Setting box
appears. Set the parameters.
Operation NWD-142957-01E
5-120 System Operation
NWD-142957-01E Operation
System Operation 5-121
Figure 5-186 QoS / Classification Setting Window (VLAN ID Based QoS Mode)
Procedure 5-42
Operation NWD-142957-01E
5-122 System Operation
NWD-142957-01E Operation
System Operation 5-123
5. The Ingress Setting tab appears. Click the Add Policer Index button.
6. The Add Policer Index box appears. Assign a proper value for each parameter.
Operation NWD-142957-01E
5-124 System Operation
8. The Ingress Policer Profile Detail Setting box appears. Assign a proper
value for each parameter
Note You need to set EBS value bigger than MTU size of the policer applying
port.
NWD-142957-01E Operation
System Operation 5-125
11. The Add Policer Index box appears again. Click OK Button.
Operation NWD-142957-01E
5-126 System Operation
13. The Ingress Setting tab appears again. Confirm the newly added Ingress
Policer Index information displayed
Procedure 5-43
NWD-142957-01E Operation
System Operation 5-127
5. The Ingress Setting tab appears. Click the Ingress Policer Profile Setting
button.
Operation NWD-142957-01E
5-128 System Operation
6. The Ingress Policer Profile Setting box appears. Click the desired Ingress
Policer Index No. to configure.
7. The Ingress Policer Profile Detail Setting box appears. Assign a proper
value for each parameter
NWD-142957-01E Operation
System Operation 5-129
10. The Ingress Policer Profile Setting box appears again. Click Close button.
Operation NWD-142957-01E
5-130 System Operation
11. The Ingress Setting tab appears again. Confirm the parameters displayed.
Procedure 5-44
NWD-142957-01E Operation
System Operation 5-131
Operation NWD-142957-01E
5-132 System Operation
5. The Ingress Setting tab appears. Click the desired Pollcer Index No to
configure.
6. The Ingress Policer Setting box appears. Modify the parameter accordingly.
NWD-142957-01E Operation
System Operation 5-133
9. The Ingress Setting tab appears again. Confirm the modified parameters of
the Ingress Policer Index information displayed.
Operation NWD-142957-01E
5-134 System Operation
Procedure 5-45
NWD-142957-01E Operation
System Operation 5-135
5. The Ingress Setting tab appears. Click Delete Policer Index button.
6. The Delete Policer Index box appears. Input the Ingress Pollcer Index No.
to be deleted.
7. Click OK button.
Operation NWD-142957-01E
5-136 System Operation
NWD-142957-01E Operation
System Operation 5-137
10. The Ingress Setting tab appears again. Confirm the Ingress Policer Index
No. has been deleted
Procedure 5-46
Operation NWD-142957-01E
5-138 System Operation
5. The Port Setting tab appears. Click the desired Main Board or MODEM
Port No. to configure.
NWD-142957-01E Operation
System Operation 5-139
6. The Qos Port Setting box appears. Assign a proper value for each parameter.
7. Click the desired Class No. of the Egress Class Setting Information field.
8. The Egress Class Setting box appears. Assign a proper value for each
parameter.
Operation NWD-142957-01E
5-140 System Operation
NWD-142957-01E Operation
System Operation 5-141
Class 3
SP
DWRR
Operation NWD-142957-01E
5-142 System Operation
11. The QoS Port Setting box appears again. Click OK button after setting the
parameters.
NWD-142957-01E Operation
System Operation 5-143
13. The Port Setting tab appears again. Confirm the parameters displayed.
Procedure 5-47
Operation NWD-142957-01E
5-144 System Operation
5. The Port Setting tab appears. Click the Class Mode in the QoS Port Setting
List.
6. Class Mode Setting box appears. Select 8 Classes QoS from Class
Mode: Then click OK button..
7. Click the desired Port No. in the QoS/Classification Setting window. QoS
Port Setting box appears.
NWD-142957-01E Operation
System Operation 5-145
9. Egress Class Setting box appears. Assign a proper value for each parameter
Operation NWD-142957-01E
5-146 System Operation
NWD-142957-01E Operation
System Operation 5-147
Operation NWD-142957-01E
5-148 System Operation
12. The QoS Port Setting box appears again. Click OK button after confirming
the parameter.
NWD-142957-01E Operation
System Operation 5-149
14. The Port Setting tab appears again. Confirm the displayed parameters.
Procedure 5-48
3. Select Filter Setting from the ETH Function Setting sub menu.
Operation NWD-142957-01E
5-150 System Operation
4. The Filter Setting window appears. Click the Filter List tab.
NWD-142957-01E Operation
System Operation 5-151
6. The Add Filter Entry box appears. Refer to the table below to assign a proper
value for each parameter.
Operation NWD-142957-01E
5-152 System Operation
Procedure 5-49
3. Select Filter Setting from the ETH Function Setting sub menu.
NWD-142957-01E Operation
System Operation 5-153
4. The Filter Setting window appears. Click the Filter List tab.
5. Click desired Entry Index number to configure. Modify Filter dialog box
appears. Modify parameter(s).
Operation NWD-142957-01E
5-154 System Operation
Procedure 5-50
3. Select Filter Setting from the ETH Function Setting sub menu.
4. The Filter Setting window appears. Click the Filter List tab.
NWD-142957-01E Operation
System Operation 5-155
Operation NWD-142957-01E
5-156 System Operation
10. The Filter Setting (Filter List tab) window appears again.
Procedure 5-51
3. Select Filter Setting from the ETH Function Setting sub menu.
4. The Filter Setting window appears. Click the Profile List tab.
NWD-142957-01E Operation
System Operation 5-157
5. The Profile List tab appears. Click Add button to create a new profile list
6. The Add Filter Profile box appears. Select the Entry Index number to add
filter(s).
Operation NWD-142957-01E
5-158 System Operation
Procedure 5-52
3. Select Filter Setting from the ETH Function Setting sub menu.
NWD-142957-01E Operation
System Operation 5-159
4. The Filter Setting window appears. Click the Profile List tab.
Operation NWD-142957-01E
5-160 System Operation
NWD-142957-01E Operation
System Operation 5-161
Procedure 5-53
3. Select Filter Setting from the ETH Function Setting sub menu.
4. The Filter Setting window appears. Click the desired Port number to be set.
Operation NWD-142957-01E
5-162 System Operation
5. The Ingress Filter Setting box appears. Click the pull-down menu.
Note: In the above box, the second to fifth items are made by the prior
procedures.
6. Select the desired Profile Index from the items. Click OK button.
NWD-142957-01E Operation
System Operation 5-163
Operation NWD-142957-01E
5-164 System Operation
Procedure 5-54
NWD-142957-01E Operation
System Operation 5-165
Operation NWD-142957-01E
5-166 System Operation
Note STP/RSTP tunnel enabling function is not supported for RSTP enabled
port.
NWD-142957-01E Operation
System Operation 5-167
Procedure 5-55
3. Select Port Isolate Setting from the ETH Function Setting sub menu.
4. The Port Isolate Setting window appears. Click the Port number to be
isolated.
5. The Port Isolate Setting box appears. Click Enable radio button.
Operation NWD-142957-01E
5-168 System Operation
8. Confirm the value of the Port Isolate of the changed port(s) is turned to
Enable.
NWD-142957-01E Operation
System Operation 5-169
Procedure 5-56
3. Select LLF Setting from the ETH Function Setting sub menu.
Operation NWD-142957-01E
5-170 System Operation
5. The LLF Setting (Add) box appears. Refer to the table below to assign a
proper value for each parameter accordingly
NWD-142957-01E Operation
System Operation 5-171
9. The LLF Setting window appears again. Confirm the newly added LLF Setting
information displayed.
Operation NWD-142957-01E
5-172 System Operation
Procedure 5-57
3. Select LLF Setting from the ETH Function Setting sub menu.
4. The LLF Setting window appears. Click the desired LLF GRP ID to configure.
LLF GRP ID
NWD-142957-01E Operation
System Operation 5-173
5. The LLF Setting (Modify) box appears. Modify the parameter accordingly.
Operation NWD-142957-01E
5-174 System Operation
9. The LLF Setting window appears again. Confirm the modified parameters of
the LLF GRP information displayed.
Procedure 5-58
3. Select LLF Setting from the ETH Function Setting sub menu.
NWD-142957-01E Operation
System Operation 5-175
5. The LLF Setting (Delete) box appears. Select the LLF GRP ID to be deleted.
Operation NWD-142957-01E
5-176 System Operation
9. The LLF Setting window appears again. Confirm the LLF GRP has been
deleted.
Procedure 5-59
3. Select Broadcast Storm Control from the ETH Function Setting sub
menu.
NWD-142957-01E Operation
System Operation 5-177
5. The Broadcast Storm Control Rate dialog box appears. Enter storm control
rate 1 to 1000 Mbps.
6. Click OK button. The Broadcast Storm Control Rate dialog box closes. The
entered rate is indicated at the right field of the Broadcast Storm Control
Rate button.
Operation NWD-142957-01E
5-178 System Operation
7. Click Port No at the Item/Port Information for Main Board or MODEM1/2. The
Broadcast Storm Control (Main Board Port-0x) or (MODEM
Port-0x) dialog box appears.
Figure 5-280 Broadcast Storm Control Rate Dialog Box (Main Board)
9. Click OK button. The dialog box closes, and the Broadcast Storm Control
Setting window appears again.
NWD-142957-01E Operation
System Operation 5-179
Procedure 5-60
Operation NWD-142957-01E
5-180 System Operation
5. The Equipment Clock Setting dialog box appears. Assign a proper value for
each parameter.
Figure 5-283 Equipment Clock Setting Dialog Box (with CLK2M-C Card)
Figure 5-284 Equipment Clock Setting Dialog Box (without CLK2M-C Card)
NWD-142957-01E Operation
System Operation 5-181
Operation NWD-142957-01E
5-182 System Operation
NWD-142957-01E Operation
System Operation 5-183
7. Warning box will appear for the clock source modification. Click OK button.
9. The Equipment Clock Setting window appears again. Confirm the displayed
parameters.
Operation NWD-142957-01E
5-184 System Operation
Correlation Setting
User can specify the alarm severity among critical, major, and minor, and
warning for each alarm reported by iPASOLINK.
BER Threshold
Procedure 5-61
Modify button
NWD-142957-01E Operation
System Operation 5-185
5. The Correlation Setting dialog box appears. Assign a proper value for each
parameter.
Operation NWD-142957-01E
5-186 System Operation
Procedure 5-62
4. The Alarm Severity Setting window appears. Click the MODEM tab.
Modify button
NWD-142957-01E Operation
System Operation 5-187
7. Select the desired alarm status from the drop down list of Alarm Status.
8. Set the alarm status for each Alarm Item, and then repeat the procedures for
other tabs.
Operation NWD-142957-01E
5-188 System Operation
Procedure 5-63
3. Select BER Threshold Setting from the Alarm/AIS Setting sub menu.
4. The BER Threshold Setting window appears. Click the MODEM No.
MODEM No.
NWD-142957-01E Operation
System Operation 5-189
Operation NWD-142957-01E
5-190 System Operation
8. The BER Threshold Setting window appears again. Confirm the displayed
parameters.
PMON Other
RMON Other
NWD-142957-01E Operation
System Operation 5-191
Procedure 5-64
4. The PMON Threshold Setting window appears. Select the MODEM1 tab.
Modify button
Operation NWD-142957-01E
5-192 System Operation
6. The RF-MODEM1 dialog box appears. Assign a proper value for each
parameter.
NWD-142957-01E Operation
System Operation 5-193
Operation NWD-142957-01E
5-194 System Operation
Procedure 5-65
NWD-142957-01E Operation
System Operation 5-195
5. The PMON Other Setting dialog box appears. Assign a proper value for each
parameter.
Operation NWD-142957-01E
5-196 System Operation
8. The PMON Other window appears again. Confirm the displayed parameters.
Procedure 5-66
NWD-142957-01E Operation
System Operation 5-197
5. The RMON Threshold Setting dialog box appears. Assign a proper value for
each parameter.
Operation NWD-142957-01E
5-198 System Operation
8. The RMON Threshold Setting window appears again. Confirm the displayed
parameters.
Procedure 5-67
NWD-142957-01E Operation
System Operation 5-199
4. The RMON Other window appears. Click VLAN counter No. in the VLAN
Counter Select tab.
5. The VLAN Counter Select dialog box appears. Assign a proper value for each
parameter.
Operation NWD-142957-01E
5-200 System Operation
8. The RMON Other window appears again. Confirm the displayed parameters.
NWD-142957-01E Operation
System Operation 5-201
Procedure 5-68
4. The RMON Other window appears. Click Delete VLAN Counter button.
5. The Delete VLAN Counter dialog box appears. Select the VLAN Counter
No. to be deleted.
Operation NWD-142957-01E
5-202 System Operation
9. The RMON Other window appears again. Confirm the displayed parameters.
NWD-142957-01E Operation
Abbreviations 6-1
6. ABBREVIATIONS
Operation NWD-142957-01E
6-2 Abbreviations
NWD-142957-01E Operation
Abbreviations 6-3
Operation NWD-142957-01E
6-4 Abbreviations
NWD-142957-01E Operation
Abbreviations 6-5
Operation NWD-142957-01E
6-6 Abbreviations
NWD-142957-01E Operation