Vous êtes sur la page 1sur 3

SITE INSPECTION AND TEST RECORD

Description : Order No.: Sheet: 1


13. 8 KV SWITCHGEAR CT SECONDARY CIRCUIT INJECTION TEST 33060201001
Contractor: End Client.: Contract No:

NCC SEC-EOA 30631035/00


Site : Panel No:
NEW 115/13.8 KV HAFAR AL BATEN S/S-1. HA14 (A304)

Feeder No. : + HA 14 (B304) CT Ratio /Class/Burden :4000/5A/TPS(Core 2)


Feeder Name : BUS TIE Shorting / isolating/ bypass facility checked : OK
CT Identification No. : T061/ T062/T063 (Core2) Function of CT : PROTECTION
Drawing Ref./Sheet : : EA- 036897/1 of 5
Secondary Measured Current (A) : Core 2
Panel :+HA14 Panel : +HA14
Phase Injected Location/TB No. :FT2 Location : F2
Secondary R (3) Y (7) B(11) N(15) R Phase Y Phase B Phase N Phase
Current (A)
2.5 2.49 1997.9
R
5.0 5.00
3998.9

2.5 2.49
Y 1997.9
5.0 5.00 3997.8
2.5 2.49
1998.4
B
5.0 5.00
3999.2

2.5 2.49
1997.6
N
5.0 5.00 3998.8

Tested by: Witnessed by:


M. SAIFUL ISLAM GARVIE GARCIA
Sig. & Date: Sig. & Date:
SITE INSPECTION AND TEST RECORD
Description : Order No.: Sheet: 2
13. 8 KV SWITCHGEAR CT SECONDARY CIRCUIT INJECTION TEST 33060201001
Contractor: End Client.: Contract No:

NCC SEC-EOA 30631035/00


Site : Panel No:
NEW 115/13.8 KV HAFAR AL BATEN S/S-1. HA14 (A304)

Secondary Measured Current (A) : Core 2


Panel :+HA14 Panel : +HA14
Phase Injected Location/TB No. :F10 Location : F10
Secondary R (41) Y (43) B(45) N(47) R Phase Y Phase B Phase N Phase
Current (A)
R 2.5 2.49 1998.9
5.0 5.00
3999.9
Y 2.5 2.49
1996.3
5.0 5.00 3999.8
B 2.5 2.49
1997.4

5.0 5.00 3999.2
N 2.5 2.49
1998.6
5.0 5.00 3998.8

Tested by: Witnessed by:


M. SAIFUL ISLAM GARVIE GARCIA
Sig. & Date: Sig. & Date:
SITE INSPECTION AND TEST RECORD
Description : Order No.: Sheet: 3
13. 8 KV SWITCHGEAR CT SECONDARY CIRCUIT INJECTION TEST 33060201001
Contractor: End Client.: Contract No:

NCC SEC-EOA 30631035/00


Site : Panel No:
NEW 115/13.8 KV HAFAR AL BATEN S/S-1. HA14 (A304)

Secondary Measured Current (A) : Core 2


Panel :+HA14 Panel : +HA14
Phase Injected Location/TB No. :F10 Location : FT2
Secondary R (42) Y (44) B(46) N(48) R (1) Y (5) B (9) N (13)
Current (A)
2.5 2.49 2.49
R
5.0
5.00 5.00
2.5
Y 2.49 2.49
5.0 5.00 5.00
2.5
B 2.49 2.49

5.0 5.00 5.00
2.5
2.49 2.49
N
5.0 5.00 5.00

Tested by: Witnessed by:


M. SAIFUL ISLAM GARVIE GARCIA
Sig. & Date: Sig. & Date:

Vous aimerez peut-être aussi