DANGER

NO SAFE PPE EXISTS


ENERGIZED WORK PROHIBITED
230 in Arc Flash Boundary
78 cal/cm^2 Incident Energy at 18 in
PPE DO NOT WORK ON LIVE!
360 VAC Shock Risk when cover is removed
00 Glove Class
42 in Limited Approach
12 in Restricted Approach
N/A Minimum Arc Rating
Location: INVERTER
SKM Systems Analysis, Inc.
1 Pearl St.
Redondo Beach, CA 90277
(310) 698-4700
Job#: 15-PF-042 Prepared on: 10/22/15 By: AVOCA
Warning: Changes in equipment settings or system
configuration will invalidate the calculated values and
PPE requirements