ELEVATOR REMOTE CONTROL CARD
USER'S MANUAL
www.konelsan.com.tr
LIST OF PARAMETERS
00: LANGUAGE SELECTION
(TURKISH/ENGLISH) 01: ELEVATOR TYPE
02: REMOTE CONTROL
TYPE 03: NUMBER OF STOPS
04: NUMBER OF
BASEMENTS 05: DOOR TYPE
06: BUSY-STATE DURATION
07: LOCK WAITING TIME
08: WAITING TIME ON EACH FLOOR
9: HIGH SPEED DURATION
10: LOW SPEED DURATION
11: DOOR MAXIMUM DURATION
12: PARKING LOT COURSE DURATION
13: PARKING LOT STOP
14: FIRE STOP
15: DIRECTION ARROW FLASH
16: CHANGE PASSWORD
17: CANCEL PASSWORD
18: MAINTENANCE CONDUCTED
19: MAINTENANCE DURATION
20: ERROR LIST
21: DIGITAL ADJUSTMENT
22: DOOR SPECIAL ADJUSTMENT
23: SAVING (ACTIVE/CANCEL)
24: DUBLEX SELECTION
25: CALL TRANSFER
26: PHASE PROTECTION (ACTIVE/CANCEL)
27: PTC (ACTIVE/CANCEL)
28: CABINET SERIAL CARD (ACTIVE/CANCEL)
29: AUTOMATIC DOOR OPENING DURATION
30:SINGLE DOOR FULLY AUTOMATIC
31: RP DELAY =======> (For VVVF with Rope and Hydraulic elevators)
32: REVISION COURSE OF ACTION
33: EARLY DOOR OPENING
TECHNICAL
SPECIFICATIONS:
Sizes
267 / 201 / 35
Lenght * Width * Height (mm)
Operation temperature 0 - +60 C
Protection class IP20
Moisture <95%
Network Control Entries 3 x 380V, 50Hz, N
Control Supply Voltage 24 5 Vdc
Power consumption Max. 400mA 10W, for 24VDC
Security Circuit Voltage At maximum 230Vac
(For Hydraulic elevators, 24Vdc in emergency descending!!!)
Control Signal Entries 24 5 Vdc
Control Signal Exits 24 5 Vdc
Short-Circuit Protected
EVO PRO +A3 When the system is energized, on the LCD screen, screen we call
SERIAL NO : "START UP SCREEN" appears. On this screen, software version
XXXXX and serial number of the card you are using are shown. After
waiting for two seconds, the screen passes on to the screen called
"HOME SCREEN".
MAIN SCREEN
RECORD WAITING... In the main screen, supply voltage of remote control card (100) and
D:15 +25.4 V stop number where elevator is located are shown.
RECORD WAITING...
If numerator type encoder numerator is selected
D:15 +24.0 V 01981
Revision from By pressing exit button for 2 seconds, change status of elevator to revision
Card D:15 +24.0 and move through up and down buttons.
V
Manual Recording Manual record screen will be shown when pressed Up and
==>10 Down buttons. By selecting the stop, push the enter button.
D:15 +24.0 V
Group (AB----) P - Status of six units of panels are provided on the screen as follows.
A D:15 24.0 V
ENTERING
THE MENU
00:Language To enter the menu, press the ENTER button for 3 seconds. If any
Selection passwords are not specified for entry permit, (00000: start up
Turkish password), the first parameter on the screen, "LANGUAGE" note
will appear.
If any other password is specified previously, enter the right
Password ? 00000 password by using UP and DOWN buttons. Then press the
Serial.code "ENTER" button to confirm password. If the password is right,
(ABGFY) the first parameter will appear on the screen. If it is wrong, the
warning on the screen will appear saying "WRONG
PASSWORD !! ENTRY MADE" and the card will return to
main screen, wrong password entry does not block your card. In
order to learn the only true password, you can retrieve the
password by contacting our company.
In order navigate through program parameters, UP and DOWN buttons are used and
to change parameter values, ENTER and EXIT buttons are used.
After changing parameter value by UP and DOWN buttons, in order to save the change, you
can press ENTER button to change a parameter permanently. If you do not want to change,
you can turn to previous adjustments by pressing EXIT button.
EXIT the MENU In order to exit from the menu, press EXIT button and when
( ENTER ) you see the note "EXIT the MENU", you can exit from the
menu by pressing ENTER button.
- TURKISH: Turkish
- ENGLISH: English
01: Elevator You can adjust the drive type of your elevator by means of this parameter.
Type Double
Speed
- SINGLE SPEED ELEVATOR: For single-speed elevators, this setting should be selected.
- DOUBLE SPEED ELEVATOR: For double-speed elevators, this setting should be selected.
- VVVF WITH ROPE: Stepless geared (asynchronous mechanical) and non-geared (synchronous
mechanical)
- HYDRAULIC: For hydraulic elevators, this setting should be selected.
For elevators, this setting should be selected. Besides, "RECOVERY TYPE" parameter
should be adjusted in accordance with system.
02: Remote You can adjust the remote control type of your elevator by means of this
Control Type parameter.
Simple Control
- SIMPLE REMOTE CONTROL: Cabinet and floor buttons are connected in parallel. Recording
memory are not kept except the single recording.
- MIXED COLLECTING: Cabinet and floor buttons are connected in parallel. Recording memory is
kept.
- COLLECTING AT DESCEND: Cabinet and floor buttons are connected separately. Cabinet
recordings are collected in both directions. Floor calls are collected while cabinet is moving
downwards.
- BOTH DIRECTION COLLECTION: Cabinet records and up and down buttons on
floors are connected separately. Cabinet records and floor calls are collected according to
movement direction.
- DUPLEX SPECIAL: If number of stops in duplex elevators is more than 9, double buttons are used to
conduct collecting.
03: Number of With this parameter, you can adjust the number of stops
Stops D:32 up to 32 for your elevator.
- 2 -32
04: Number of You can adjust the number of basements with this parameter.
Basements If elevator remote control type is done in descend, then
01 for the floor under number of basements, the
collection is made in ascend.
Note: It is used in remote control types except
collecting during descend.
05:Door Type You can adjust open-close signal type for automatic doors by
means of this parameter.
Shock Doors
- STROKE DOORS: They are only used in elevators without automatic doors.
- C.AUTO LIMITED: It is only used in elevators with automated limited cabinet doors.
- C.AUTO UNLIMITED: It is only used in elevators with automated unlimited cabinet doors.
- FULLY AUTO LIMITED: It is only used in elevators with fully automatic limited doors.
- FULLY AUTO UNLIMITED: It is only used in elevators with fully automatic unlimited doors.
As per EN 81-1/2 standards, automatic door should stay inactive only in states
of emergency stop, revision and retrieval.
07: Lock waiting time After receiving door closed signal, the maximum duration to be
8 seconds waited for arrival of lock (140) signal is adjusted with this
parameter. [second]
- 8-30 Seconds
-3.15Seconds
09: High Speed During the movement of cabinet from one floor to another,
Duration maximum allowed journey duration is adjusted by means of
15 Seconds this parameter. If this duration is exceed, the system
automatically stops movement of cabinet and blocked. [second]
- 5-120
Seconds
As per EN 81-1/2 standards, engine operation lapse of time should be provided in
a way not to exceed the minimum values given below:
a.
45 seconds
b. The longest journey length + 10 seconds
c. If the longest journey length is lower than 10 seconds, lapse of time should be at least 20 seconds.
12: Arrival to Park You can adjust the duration of waiting before going to
Duration park stop by means of this parameter. [second]
- 0-250 Seconds
13: Fire Stop You can adjust the fire stop with this parameter. When Fire
(SIDE) entrance is active, elevator directly goes to that floor and
waits with its doors open. With cancelation of fire signal, the
elevator returns to normal operation conditions.
15: Direction You can adjust flashing of direction arrow while the Elevator is in
Arrow Flash motion, by means of this parameter.
16: Change With this parameter, password for entering card is changed or specified.
Password
17: Cancel With this parameter, you can adjust the duration for engine to wait
Password before passing to triangle connection after finishing star connection
at the start in hydraulic systems. [seconds] [For hydraulic systems]
20: Error list With this parameter, stop names are monitored starting from
the last error till the first one, and then option of error deletion
appears. All errors are deleted by pressing ENTER button.
21: Digital In order to change stop number, while stop number is flashing, using
Adjustment UP-DOWN buttons, find the stop you want to change to. Then, by
pressing ENTER button, enable flashing of digital value. By using UP-
DOWN buttons again, adjust desired digital value for that stop. After
adjusting the value you prefer, press the EXIT button again to exit
adjusting. Or to adjust another stop, press ENTER button to enable
flashing of stop number and repeat the procedures.
24: Duplex You can adjust group identity during group operation of control
Selection panel by means of this parameter. Group identities can be adjusted
as A, B, C, D, E or F. Each elevator should have different identity.
For the records with same distance, priority is for elevators with
lower group identiy.
26: Phase You can use this parameter to activate phase deficiency and
Protection phase order control.
- CANCEL: Deactivated.
- ACTIVE: Phase not lined
- CANCEL: Deactivated.
- ACTIVE: In operation
28: Cabinet Serial With this parameter, it inform the card about attaching
Card serial communication card, if serial card is installed, then
it is ACTIVATED.
29: Auto Door With this parameter, duration from the opening of the door to
Opening Duration stop is entered.
- 05-20 Seconds
29: Single Door Full With this parameter, if elevators with stroke door have only one
Auto automatic door, floors with automatic doors is specified.
31: RP Delay In VVVF systems with rope, main contractor may be demanded to
descend with delay. In such conditions, RP relay exit delay is
adjusted from this parameter. However, in hydraulics elevators, it is
used as engine delay [in milliseconds]
- 00000-25000 Milliseconds
32: Rev. Course of You can adjust the course of action for lower-upper limit breaker
Action in revision with this parameter.
- BY BREAKER: As soon as breakers operate, elevator is stopped before reaching the floor.
- BY THE FLOOR: Even though the breaks operate, elevator reaches its floor.
33: Early Door In order activate early door opening function, this parameter is
Opening used. [For VVVF with Rope and Hydraulic elevators]
(Without activating this parameter, floor adjustment within cabinet cannot
be conducted)
For movement of cabinet while doors are open for early door opening, it is only
allowed under control of card door bridging circuit, if Elevator speed is below 0.15
m/s and on condition they are within the borders of door opening area.
34: Star With this parameter, you can adjust the duration for engine to wait
Triangle before passing to triangle connection after finishing star connection
at the start in hydraulic systems. [seconds] [For hydraulic systems]
- 00000-25000 Milliseconds
35: Engine Valve In hydraulic systems, delay of valves at start up can be adjusted
Duration from this parameter. [seconds] [For hydraulic systems]
- 00000-25000 Milliseconds
35: Door Open Leveling In order to activate level renewal, this parameter is used. [For
VVVF with Rope and Hydraulic elevators]
(Without activating this parameter, floor adjustment within cabinet
cannot be conducted)
37: The This parameter is only used in group operation. If there are stop differences
Bottommost among elevators in the group, with this parameter, first stop adjustment is
Stop conducted. While conducting this adjustment, stop numbers of elevators
should be adjusted separately from the menu. For instance, in a duplex system
with 10 stops, if A elevator does not serve for the bottommost floor and only
B elevator provides service: Both elevators should be adjusted to 10 stops and
first stop adjustment for A elevator should be set up as 2.
38: Early Opening With this parameter, it is adjusted how many millimeter
Way before the automatic door will open (used only when early
door opening is active)
39: Objective Floor When this parameter is active, elevator display will show the floor
Flash elevator is heading on each floor change.
- CANCEL: it is canceled
- ACTIVE: it is activated
40: Display With this parameter, Evo Pro remote control card andevo-serial
Output card's display output adjustments are conducted.
41: Security Delay This parameter is used to delay movement of elevator after
reacing 130 and 140 security circuits.
- 0000-1000 Milliseconds
43: M. Break If this parameter is active, it is necessary for break monitoring contacts
Monitoring to be connected, in the event of cancellation in machines without gears,
errors will not be detected in the event of a3 turning into involuntary
state. Therefore, it should not be canceled, if it is canceled, our company
is not responsible.
NOTE: If you receive break monitoring error, press exit button for 30
seconds.
- CANCEL: it is canceled
- ACTIVE: it is activated
44: With this parameter, floor sensor selection of the elevator is conducted.
Numerator
Type
- 0000-2000 Milliseconds
46: Photocell With this parameter, it specifies door closing duration with a signal
Duration coming from photocell after opening of door.
49: Position Reset Control card will keep its latest position on its memory even though
network electricity is interrupted. However, in certain special
situations, a position reset may be demanded after retrieval of
elevator electricity. In this case, the elevator will descend until it
reached the bottommost floor 817 breaker. When it reaches the
bottommost floor, floor numerator is reseted. For instance, in systems
with battery recovery units, this parameter can be activated to ensure
position reseting.
52: Floor Descend If elevator numerator type is encoder, this parameter make adjustment
Adjusting for descend floor setup, enter - if elevator is up and + mm if down.
53: Floor Ascend If elevator numerator type is encoder, this parameter make adjustment
Adjusting for ascend floor setup, enter - if elevator is up and + mm if down.
54: Short Floor On this screen, it adjusts slowing down distance when
Path elevator moves a floor distance.
55: Long On this screen, it adjusts slowing down distance when elevator
Floor Path moves a floor distance or more.
58: LCD Thanks to this parameter, LCD contrast control can be made.
Contrast
If this parameter is active, the elevator will start its involuntary
movement test and put the elevator into involuntary state, thus test is
59: Involuntary completed. (To exit from involuntary test, press exit button for 60
S.Test seconds.) This parameter goes into cancel state after deleting the
error.
61: Sak/Kak With this parameter, delay duration of recovery contactor is adjusted.
Duration
62: Factory On this screen, by entering ENTER button, wait until you see OK
Setting warning.
R Mains Supply
S
L3
N Network Neutral
1 Cabinet Supply Entry
2 Cabinet Lamp Supply
LR1 L Opening Magnet Relay Contact Partner
LR2 L Opening Magnet Relay Contact Opening
A3 / B3 L Opening Signal
A5 / B5 K Closing Signal
A15 On/Off Signal Partner
10A Security Circuit Neutral Cycle
120 Stop circuit
130 Plug Contact Circuit Max. 230Vac
140 Lock Circuit
10B Contactors' Neutral Output
RGA Regulator Monitoring Entry Only for VVVF or hydraulic systems
3. FAULT CODES
CODE ERROR
1 STOP CAST
2 PLUG CAST
3 LOCK CAST
4 KRC ERROR
5 PTC ERROR
NUMERATOR ERROR.
7 JF ERROR
8 LOCK NOT GIVEN
9 PLUG NOT GIVEN
10 NO KSR
11 R - PHASE ERROR
S - PHASE ERROR
13 T - PHASE ERROR
14 PHASES GONE
15 LOW VOLTAGE
16 (PRESS EXIT BUTTON FOR 60 SECONDS TO EXIT FAULT SCREEN)
17 (PRESS EXIT BUTTON FOR 60 SECONDS TO EXIT FAULT SCREEN)
18 (PRESS EXIT BUTTON FOR 60 SECONDS TO EXIT FAULT SCREEN)
19 (THIS ERROR EPPEARS IF READING IS 817 OR 818 CUTTING)
20 (IN READING ENCODER DOES NOT COUNT)
21 (PRESS EXIT BUTTON FOR 60 SECONDS TO EXIT FAULT SCREEN)
22
14. PHYSICAL
DIMENSIONS
Front View
LCD indicator
201mm
192m
m
Adjustment Buttons
M3 screw
257mm
267mm
Side View
Cover Screw
Bonnet
Cover extension screw
27mm
35mm
Main card
Card screw
260mm