S-02

GENERAL NOTES:
ALL DIMENSIONS ARE IN MM

DO NOT SCALE THE DRAWING , ONLY WRITTEN DIMENSIONS ARE TO


BE FOLLOWED.

USE CONCRETE MIX 1 : 1.5 : 3 HAVING CHARACTERTIC COMPRESSIVE


STRENGTH OF CONCRETE = 20 N/ SQMM AS PER IS 456 - 2000.
200 200
750 MM USE STEEL BARS( CONFORMING TO IS 1786) HAVING GUARANTEED
YIELD STRESS OF 415N/MM2

vertical ALL LAP LENGTH SHALL BE PROVIDED 56 TIMES THE DIA OF BARS.

ALL "L" BENDS SHALL BE OF 300 MM (UNLESS NOTED OTHERWISE)

NOMINAL COVER TO REINFORCEMENT (INCLUDING RING) SHALL BE


AS FOLLOWS BUT NOT LESS THAN THE DIA OF MAIN BARS -
WALL - 50 MM; SLABS - 50 MM ;

900 MM
ALL CONSTRUCTION WORK SHALL BE DONE AS PER TENDER
SPECIFICATIONS.
10 # @100 C/C
vertical FOR LOCATION REFER SITE PLAN.

ANY DEVIATION FROM STRUCTURAL DRAWINGS SHALL NOT BE


8 # @150 C/C ALLOWED WITHOUT WRITTEN PERMISSION OF CONSULTING
ENGINEER.

100 200
100 100

8 # @150 C/C P.C.C. M-15 10 # @150 C/C


100mmTHK.

TYPICAL SECTION OF R.C.C.


STORM WATER DRAIN

200 600 MM 200


150 600 MM 150

PROJECT:
INFRASTRUCTURE DEVELOPMENT OF GOVINDPURA

600 MM
10 # @125 C/C INDUSTRIAL AREA, BHOPAL
vertical
750 MM

CLIENT:
A K V N BHOPAL
10 # @100 C/C 8 # @150 C/C
DRAWING:
vertical TYPICAL SECTION OF R.C.C.

100 150
100 100 STORM WATER DRAIN
8 # @150 C/C
DATE - CHECKED BY DRG. NO.
8 # @150 C/C P.C.C. M-15 8 # @150 C/C SCALE - DRAWN BY
100mmTHK.
S - 02
100 200

100 100
TYPICAL SECTION OF R.C.C. THIS DRAWING AND THE DESIGNS ON WHICH IT IS BASED ARE THE COPYRIGHT AND PROPERTY OF MS. MEHTA & ASSOCIATES AND
THEIR USE IS CONDITIONED UPON THE USERS AGREEMENT NOT TO REPRODUCE OR TO USE FOR ANY OTHER PURPOSE WHOLLY OR
P.C.C. M-15 STORM WATER DRAIN IN PART ANY DETAILS THEIRIN WITHOUT THE SPECIFIC WRITTEN PERMISSION OF MEHTA AND ASSOCIATES
8 # @150 C/C 8 # @150 C/C
100mmTHK. ARCHITECT NORTH
TYPICAL SECTION OF R.C.C.
STORM WATER DRAIN
102. !st floor, Navneet Plaza, 5/2, Old Palasia, Indore-452001
Phone : 2561124 ,4065064 Fax- (0731) 4065064
Email : hitendramehta.architect@gmail.com
150 150 150 150 S-02
GENERAL NOTES:
ALL DIMENSIONS ARE IN MM

DO NOT SCALE THE DRAWING , ONLY WRITTEN DIMENSIONS ARE TO


BE FOLLOWED.

USE CONCRETE MIX 1 : 1.5 : 3 HAVING CHARACTERTIC COMPRESSIVE


STRENGTH OF CONCRETE = 20 N/ SQMM AS PER IS 456 - 2000.

USE STEEL BARS( CONFORMING TO IS 1786) HAVING GUARANTEED

1500 TO 2000

1500 TO 2000
10 # @150 C/C 10 # @150 C/C YIELD STRESS OF 415N/MM2
vertical B/F vertical
ALL LAP LENGTH SHALL BE PROVIDED 56 TIMES THE DIA OF BARS.

ALL "L" BENDS SHALL BE OF 300 MM (UNLESS NOTED OTHERWISE)


8 # @150 C/C 8 # @150 C/C
NOMINAL COVER TO REINFORCEMENT (INCLUDING RING) SHALL BE
AS FOLLOWS BUT NOT LESS THAN THE DIA OF MAIN BARS -
2 LAYER 2 LAYER WALL - 50 MM; SLABS - 50 MM ;

ALL CONSTRUCTION WORK SHALL BE DONE AS PER TENDER


SPECIFICATIONS.

FOR LOCATION REFER SITE PLAN.

200

200
ANY DEVIATION FROM STRUCTURAL DRAWINGS SHALL NOT BE
ALLOWED WITHOUT WRITTEN PERMISSION OF CONSULTING

100

100
ENGINEER.
200 300 500 TO 1000 300 200 200 300 1000 TO 1500 300 200
100 100
8 # @150 C/C P.C.C. M-15 10 # @150 C/C 100 8 # @125 C/C P.C.C. M-15 10 # @125 C/C B/F100
100mmTHK. 100mmTHK.

TYPICAL SECTION OF R.C.C. TYPICAL SECTION OF R.C.C.


STORM WATER DRAIN STORM WATER DRAIN
150 150 150 150
2000 TO 2500

2000 TO 2500
PROJECT:
ZEROING-IN ON CRITICAL INFRASTRUCTURE GAP OF
INDUSTRIAL AREA,MANDIDEEP, DIST. RAISEN ( M.P.)
12 # @150 C/C 12 # @150 C/C
B/F vertical vertical
CLIENT:
A K V N BHOPAL
8 # @150 C/C 8 # @150 C/C
DRAWING:
TYPICAL SECTION OF R.C.C.
STORM WATER DRAIN
2 LAYER DATE - CHECKED BY DRG. NO.
2 LAYER
SCALE - DRAWN BY
S - 08
200

200
THIS DRAWING AND THE DESIGNS ON WHICH IT IS BASED ARE THE COPYRIGHT AND PROPERTY OF MS. MEHTA & ASSOCIATES AND
THEIR USE IS CONDITIONED UPON THE USERS AGREEMENT NOT TO REPRODUCE OR TO USE FOR ANY OTHER PURPOSE WHOLLY OR
IN PART ANY DETAILS THEIRIN WITHOUT THE SPECIFIC WRITTEN PERMISSION OF MEHTA AND ASSOCIATES
100

100
ARCHITECT NORTH
200 350 500 TO 1000 350 200 200 350 1000 TO 1500 350 200 100
100 P.C.C. M-15 100 100 P.C.C. M-15
8 # @150 C/C 10 # @125 C/C 8 # @125 C/C 10 # @100 C/C B/F
100mmTHK. 100mmTHK.