Académique Documents
Professionnel Documents
Culture Documents
by Nigel Potter
CONTENTS
COVER PHOTOGRAPH: ANTHONY WELLER, ARCHIMAGE
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form
or by any means electronic or mechanical including photocopying, recording or otherwise without prior written
permission of the publisher.
BSRIA TN 19/01 October 2001 ISBN 0-86022-592-5 Printed by the Chameleon Press Ltd Air Tightness Testing 03
BSRIA TN 19/2001
BUILDING AIR TIGHTNESS:THE FACTS
THE FACTS
In April 2002 the Building Regulations will
demand that all new buildings in England
and Wales with a gross floor area above
PHOTOGRAPH: RODERIC BUNN
BSRIA operates a special fleet of Fan Rovers. Each fan unit unit is
designed to supply air at flow rates up to 33 m3/s. This is the first time that legislation has
been introduced to prevent the
construction of leaky buildings.
04
04 Air Tightness Testing
BSRIA TN 19/2001
BUILDING AIR TIGHTNESS:THE FACTS
The urgent need to save energy particularly on cold and windy days. Regulations will be the same for all
and reduce global emissions of In summer, air conditioning systems building types. A warehouse unit
carbon dioxide demands that build- will be unable to stop hot air with simple frost protection, for
ings are designed and constructed to entering the building, leading to example, will require the same air
be more airtight. warm conditions and unhappy tightness as a fully air conditioned
The logical place to start is with workers. office building.
the integrity of the building fabric. From 2002 most new commercial Over the last 15 years BSRIA has
Why is this important? It is important and industrial buildings will need to pressure-tested over 1000 buildings,
because the air infiltration or comply with a maximum air and has amassed plenty of experi-
ventilation heat loss is proportional to permeability of 10 m3/(h.m2) of the ence in identifying air leaks and how
the air tightness of the building. The building envelope. This means that the problems can be solved.
more air tight the building, the lower buildings will need to be tested This BSRIA guide to building air
the air infiltration rate. The more during construction to ensure that tightness testing contains all a client
leaky the building, the greater the the standard is being met, and if not, or contractor needs to know about
heat loss. that remedial works are carried out the air tightness criteria, and presents
In winter, heating systems will and the building re-tested. some of the pitfalls to avoid during
struggle to maintain temperatures, Compliance with the Building design and construction.
Analysis of a building's air tightness performance is carried out inside one of BSRIA's specially adapted
Fan Rovers. Each smoke test takes only a few minutes, and enables the pressure test engineers to check
that any unintentional gaps in the building fabric have been adequately sealed.
Air
Air Tightness
Tightness Testing 05
BSRIA TN 19/2001
HOW TO COMPLY WITH BUILDING REGULATIONS
BUILDING REGULATIONS
From March 2002, Approved Pressure testing commercial and industrial
Document L2 of the Building
Regulations will require all new
buildings with a gross floor area
buildings is no longer an option the
above 1000 m2 to be tested for Government has introduced legislation that will
air permeability.
Air permeability is the total enforce standards of building air tightness.
flow rate of air needed to
pressurise a building to a test
pressure of 50 pascals divided by
the envelope area of the build-
ing. The envelope area is defined
as the area of the ground floor This will affect everyone involved in the construction
plus the area of the external walls
and roof. process, including clients, consultants and contractors.
This definition of envelope
area is in accord with a new
standard, BS EN 13829:2001(1).
The procedure referred to in the
Building Regulations is CIBSE
Technical Memorandum 23, but the
technicalities of both methods
are identical.
For 18 months after Part L2
comes in to effect, the Govern-
ment is prepared to accept a
standard of reasonable compli-
ance. If the building fails the
first test, then reasonable provi-
sion would be demonstrated if a
building conforms to one of two
performance criteria:
air permeability has been
improved by 75% of the
difference between the first test
and the target standard of 10 m3/
(h.m2) at 50 pascals.
the air permeability on re-
testing is within 15% of 10 m3/
(h.m2) at 50 pa.
1
BS EN 13829:2001 Thermal performance of
buildings: Determination of air permeability of
buildings - Fan pressurisation method.
06 Air
Air Tightness
Tightness Testing
Testing
BSRIA TN 19/2001
HOW TO COMPLY WITH BUILDING REGULATIONS
30 First
test
Air permeability in m3/(h.m2)
25 First
test
20
First
test
15
Second
10 Second test
Second test
test
Initial test result
5
Interim acceptable standard
ABOVE: How reasonable compliance will work. Whatever the ABOVE: Tight and constricted access need not be a problem for the BSRIA pressure
performance level reached on the first test, it will have to be improved by test rig, which is able to squeeze into the narrowest of city streets.
75% or be within 15% of 10 m3/(h.m2) at 50 Pa.
Air
AirTightness
Tightness Testing 07
BSRIA TN 19/2001
GOING FOR QUALITY
QUALITY
Naturally ventilated offices
The air tightness
The air infiltration rate for a naturally ventilated office building
requirements in Part should not greatly exceed the rate of ventilation required for
the occupants during high wind speed conditions. During less
L2 will not be enough than high wind speed conditions, the occupants should be able
to open ventilators or windows to provide adequate ventilation.
for air-conditioned or The ventilation design for naturally ventilated buildings is
actually quite complex, especially during periods of low wind
low energy buildings. speeds and moderate internal/external temperature differences.
However, the openings in the structure should be purpose-
made and mostly limited to occupant control or fixed trickle
ventilator openings.
The air leakage of the structure should be at a sufficiently low
level to avoid causing draughts and discomfort, and increasing
So what's the answer? space heating requirements.
A moderate air leakage index of 10 m3/(h.m2) is
In 1998 BSRIA published Air recommended with all windows and trickle ventilators closed.
Tightness Specifications, 10/98. The If a high surface
specifications were based on air area to volume ratio is
leakage indexes, and the envelope inherent in the design
area does not include the ground of a building, for
floor, in line with UK practice. example by the
With the advent of Part L2 of inclusion of
the Building Regulations, there will courtyards, then a
now be confusion between air tighter specification
permeability, which includes the may be required.
floor area, and air leakage index,
which does not. Unfortunately,
the ratio between the two param-
eters varies depending on the
footprint-height ratio.
As the majority of large UK
buildings have a concrete ground Type Maximum air leakage index
3
Air permeability m /(h.m )
2
Factories/warehouses
Superstores
Dwellings
Cold stores
Builders' shafts
Floor voids
Pressurised stairwells
THERMOGRAPHYSURVEYS
Thermal imaging is
widely used to confirm
the presence and
continuity of thermal
insulation.
Further information ABOVE: Heat losses at the junction of wall and roof.
BS EN 13187:1999, Thermal performance of buildings
Qualitative detection of thermal irregularities in building
envelopes Infrared method.
CHECKLIST
The first issue is to decide which ing envelope and should be air-sealed
BSRIA's key surfaces are to form the airtight accordingly.
membrane. The inside surface of the The following checklist is by no
checklist for structure is usually the airtight means exhaustive, but the points cover
surface. the major issues that need to be addressed
typical air leakage The airtight surface should be brought to ensure a building is airtight.
paths. inside rooms which will be ventilated to
outside such as boiler rooms, plant
It cannot be stressed too highly that
the use of insulation materials , tapes and
rooms, electrical switch rooms and lift expanding foam offer no guarantee of
shafts. air tightness. Indeed, these materials can
Atriums, risers, stairwells and lobbies mask serious gaps in the envelope that
are normally included within the build- can be difficult to identify later.
Blockwork Ceilings
All blockwork leaks, from 01 to 60 m3/(h.m2). For ceilings where concrete is poured on to profiled
Plastered blockwork does not leak and so the quality metal sheeting, the underside will have indents in the
of the blockwork is immaterial. With raised floors and profile. These should be sealed with mastic or similar.
suspended ceilings, the quality of blockwork is
important particularly if these areas are not plastered.
BSRIA has tested over 100 blockwork walls, and so
the manufacturers should have data on the air leakage
of their blockwork. Painting good quality blockwork
Curtain walling systems
reduces air leakage, but painting poor quality Curtain walling systems are usually quite good
blockwork has little effect. between their abutments to each other, but joints to
other building systems need to be sealed. Joins to the
effectively sealed during the laying of the sheets.
Perforated liner sheets and relying on the vapour
barrier should be avoided as they under-perform.
Loading bay doors
Windows and door frames need to be effectively
sealed to the inside surface of the structure and the
cavity preferably sealed before the final finishes are
Water traps & condensate traps
made.
Water traps and condensate traps should be filled
Contact:
Nigel Potter
BSRIA Ltd
Old Bracknell Lane West
Bracknell
Berkshire RG12 7AH
15