Overview of NFPA 502 Standard for Road Tunnels, Bridges and

Other Limited Access Highways, 2008 Edition

William Connell
Parsons Brinckerhoff, Inc., Boston, Massachusetts
Jason R. Gamache
National Fire Protection Agency, Quincy, Massachusetts

ABSTRACT: NFPA 502, Standard for Road Tunnels, Bridges and Other Limited Access Highways estab-
lishes minimum re protection and re life safety requirements for road tunnels, bridges and other roadways
where access by emergency responders is physically limited.
The 2008 edition of NFPA 502 represents the Technical Committees consensus of current best practice for
re protection and life safety requirements for road tunnels, bridges and similarly limited access highways.
Research of national and international test programs, design guidelines and regulating standards was per-
formed and considered in an effort to establish a singular, comprehensive document representing a recognized
base threshold of re safety in these type facilities.
This paper provides an overview of the more signicant revisions including the application of xed re
suppression systems, guidance on tenable environment, protection of structure and dangerous goods transport.

INTRODUCTION added and expanded to share relevant information


and source material related to specic provisions.
In recent years road tunnel res and subsequent
international research projects suggest that vehicle
res within tunnels are likely to develop more rap- APPLICATION OF FIXED FIRE
idly than expected, degrade the tenability of an envi- SUPPRESSION SYSTEMS
ronment more quickly than originally calculated,
The use and effectiveness of xed water-based re
and have the potential to burn for longer periods of
suppression systems in road tunnels is still not uni-
time and at higher temperatures that may resist inter-
versally accepted. However, recent research through
vention of re ghting operations.
full-scale testing and real life operational experience
In light of this the NFPA Technical Committee
has demonstrated that xed re ghting systems can
on Road Tunnel and Highway Fire Protection deter-
be effective in controlling vehicle res in road tun-
mined it timely for NFPA 502 Standard for Road
nels by limiting the spread of the re, reducing the
Tunnels, Bridges and Other Limited Access High-
temperature of surrounding air and surfaces, and
ways to revisit a number of its provisions with
reducing the re heat release rate.
respect to res in road tunnels. The 2008 edition
One of the reasons why many countries have
includes revisions that further clarify the categoriza-
been reluctant to use xed re suppression systems
tion of road tunnels, a revision of the discussion top-
in road tunnels is that most vehicle res start in the
ics in the Annex on xed re suppression systems,
motor compartment,, and xed re suppression sys-
and revisions regarding tenable environment, protec-
tems are of limited use in suppressing the re until
tion of structure and the transport of potentially dan-
the re is out in the open. Fixed re suppression
gerous cargoes.
systems can be used, however, to cool down vehi-
In particular there has been a broad reconsider-
cles, to stop the re from spreading to other vehi-
ation of the requirements and recommendations for:
cles (i.e., to diminish the re area and property
damage), and to stop secondary res in tunnel lin-
Application of xed water-based re suppres-
ing materials. Experiences in Japan and Australia
sion systems
show that xed re suppression systems are effec-
Protection of structure and structural elements
tive in cooling down the area around the re site, so
Maintaining a tenable environment
that re ghting can be performed more effectively.
Transport of regulated and unregulated cargoes
The 2008 Edition of NFPA 502 now includes
guidance for the installation of xed water-based
Several other modications have been made
re suppression systems and has revised annex lan-
throughout the Standard that are intended to capture
guage which acknowledges the potential benets of
the latest thinking on the best practices for re and
xed re ghting systems in road tunnel application.
life safety provisions. Annex material has been

189
Specically, Annex E now suggests the consider- would be located away from the re scene,
ation of xed re suppression systems when it can producing a cooling effect that would tend to
be shown by engineering analysis that the level of draw this stratied layer of smoke down
safety can be equal or exceeded by their use as part toward the roadway level, thus impeding the
of an integrated approach to the management of life rescue and re ghting effort.
safety. Annex E also addresses, as follows, the previ-
ously listed concerns which had been expressed by Independent laboratories have commented
tunnel designers, engineers and worldwide (authori- that they do not observe smoke stratication.
ties) regarding the application of xed re ghting Any activated xed re ghting system, not
system in road tunnels: over the re, would cool the tunnel to help
rescue services to intervene. Zoned systems
Concern (1) Typically res in road tunnels are released by a detection system that is
usually occur inside vehicles or inside pas- accurate even with forced ventilation.
senger or engine compartments designed to
be waterproof from above; therefore, xed Concern (5) Water spraying from the ceiling
re ghting systems might not have an extin- of a subaqueous tunnel could suggest tunnel
guishing effect. failure and induce panic in motorists.

It is now recognized that the purpose of a This was a theoretical concern not borne out
xed re ghting re suppression system is to in practice. In the event of re motorists are
prevent re spread to other vehicles so that likely to recognize water spraying from noz-
the re does not grow to a size that cannot be zles as a re safety measure. Behavioral
attacked by the re service. studies have shown that people do not panic
in a re, even when they are unable to see.
Concern (2) If any delay occurs between
ignition and xed re ghting system activa- Concern (6) The use of sprinklers could
tion, a thin water spray on a very hot re cause the delamination of the smoke layer
could produce large quantities of super- and induce turbulence and mixing of the air
heated steam without material suppressing and smoke, thus further threatening the
the re. safety of persons in the tunnel.

Fire tests have now shown this concern not This has been shown not to be a valid con-
to be valid. A properly design xed re ght- cern. Fire tests have demonstrated that
ing system suppresses the re and cools the smoke does not usually form a layer at the
tunnel environment. Since a heavy goods top of the tunnel but quickly lls the cross-
vehicle re only needs 10 minutes to exceed section. Normal air movement in the tunnel
100 MW and 1200C, which are fatal condi- accelerates this process. A xed re ghting
tions, it is important to operate the re sup- re suppression system reduces temperatures
pression system as soon as possible. and the risk of re spread to other vehicles.

Concern (3) Tunnels are very long and nar- Concern (7) Testing of a xed re ghting
row, often sloped laterally and longitudi- system on a periodic basis to determine its
nally, vigorously ventilated, and never state of readiness could be impractical and
subdivided, so heat normally will not be costly. Inspection can be performed when
localized over a re. other facilities are inspected.

Nevertheless advances in re detection tech- A full discharge test is normally only per-
nology have now made it possible to pinpoint formed at system commissioning. During
the location of a re in a tunnel with suf- routine testing the system can be congured
cient accuracy to operate a zoned xed re to discharge ow to the drainage system.
ghting system.
PROTECTION OF STRUCTURE AND
Concern (4) Because of stratication of the
STRUCTURAL ELEMENTS
hot gas plume along the tunnel ceiling, a
number of the activated sprinklers would not, In the last edition (2004) NFPA 502 introduced new
in all probability, be located over the re. A requirements for the protection of structural ele-
large number of the activated sprinklers ments within road tunnels. The 2008 edition has

190
been signicantly revised to provide specic guid- ii. It shall not produce toxic smoke or fumes
ance for the evaluation structural reproong under re exposure in accordance with
requirements. The following requirements have been ASTM E 84 or equal international standard.
included to further support road tunnel design iii. It shall meet the re protection require-
requirements as they pertain to both life safety and ments with <5% humidity by weight and
protection of property: also when fully saturated with water in
accordance with RWS Fire Test Proce-
Regardless of tunnel length, all primary struc- dure 1998-CVB-R1161 (Rev 1).
tural concrete and steel elements shall be pro- Any re protection material should satisfy
tected in accordance with this standard in the following performance criteria:
order to: i. Be resistant to freezing and thawing
Maintain life safety and provide a tenable ii. Withstand dynamic suction and pressure
environment. loads
Mitigate structural damage and prevent pro- iii. Withstand both hot and cold thermal
gressive structural collapse. shock from re exposure and hose
Minimize economic impact. streams
The structure shall be capable of withstanding iv. Meet all applicable Health and Safety
the Rijkswaterstaat (RWS) (Netherlands) time / Standards
temperature curve, or other curve that is accept- v. Not itself become a hazard during a re
able to the Authority Having Jurisdiction. vi. Be resistant to water ingress
The level of re resistance of structures and
The time/temperature development is shown in equipment must be proven by testing or ref-
the table below: erence to previous testing. Fire test reports
are based on the following requirements:
Time Temp
i. Concrete slabs used for the application of
(Minutes) C F re protection materials for re testing
0 20 68 purposes have dimensions of at least
3 890 1634 14001400 mm and a nominal thickness
5 1140 2084 of 150 mm.
10 1200 2192 ii. The exposed surface will be approxi-
30 1300 2372 mately 12001200 mm.
60 1350 2462 iii. The re protection material must be xed
90 1300 2372 to the concrete slab using the same xa-
120 1200 2192
tion material (anchors, wire mesh, etc.)
as will be used during the actual installa-
tion in the tunnel.
After 120-minute period of re exposure, the
iv. In the case of board protection, minimum
following failure criteria shall be satised:
one joint in between two panels must be
Tunnels with cast in-situ concrete structural
created, in view to judge if any thermal
elements shall be protected such that:
leaks will occur in the case of a real re
i. The temperature of the concrete surface
in the tunnel.
does not exceed 380C (716F).
v. In case of spray materials, the number of
ii. The temperature of the steel reinforce-
applications (amount of layers) must be
ment within the concrete (assuming a
registered when preparing the test speci-
minimum cover of 25mm (1 in.) does not
men. This amount of layers must be
exceed 250C (482F).
respected while applying the spray mate-
Tunnels with pre-cast, high-strength concrete
rial in a real tunnel.
elements shall be protected such that explo-
vi. Temperature recordings by thermocou-
sive spalling is prevented.
ples located:
Steel or cast iron tunnel linings shall be pro-
a. At the interface in between the con-
tected such that the lining temperature shall
crete and the re protection material
not exceed 300C (572F).
b. At the bottom of the reinforcement
Structural re protection material shall be
c. On the non-exposed face of the con-
non-combustible in accordance with ASTM
crete slab
E 136 or equal international standard.
i. It shall have a minimum melting temper-
ature of 1350C (2462F).

191
MAINTAINING A TENABLE Smoke Obscuration Levels
ENVIRONMENT Smoke obscuration levels should be continuously
The 2008 Edition includes a complete revision to the maintained below the point at which a sign internally
annex material relating to tenable environment. This illuminated at 80 lx (7.5 ft-candles) is discernible at
is intended to correlate with similar guidance mate- 30 m (100 ft) and doors and walls are discernible at
rial in NFPA 130, Standard on Fixed Guideway 10 m (33 ft).
Transit and Passenger Rail Systems. The purpose of
the annex is to provide guidelines for the evaluation Air Velocities
of tenability within the tunnel evacuation paths. Cur- Air velocities in the enclosed tramway should be
rent technology is capable of analyzing and evaluat- greater than or equal to 0.76 m/s (150 fpm) and less
ing all unique conditions of each path to provide than or equal to 11.0 m/s (2200 fpm).
proper ventilation for pre-identied emergency con-
ditions. The same ventilating devices might or might Noise Levels
not serve both normal operating conditions and pre- Noise levels should be a maximum of 115 dBA for a
identied emergency requirements. The goals of the few seconds and a maximum of 92 dBA for the remain-
ventilation system, in addition to addressing re and der of the exposure.
smoke emergencies, are to assist in the containment
and purging of hazardous gases and aerosols such as
those that could result from a chemical/biological TRANSPORT OF REGULATED AND
release. UNREGULATED CARGOES
Environmental conditions, geometric consider- Recent road tunnel res suggest that goods tradition-
ations, and time considerations should be taken into ally not characterized as hazardous; i.e. our and
account. Following are some factors that should be con- margarine (1999 Mont Blanc Tunnel), paint (1999
sidered in maintaining a tenable environment for peri- Gothard Tunnel), and tires (2005 Frejus Tunnel),
ods of short duration. may constitute a greater risk to tunnel users and tun-
nel structures than expected. As a result Chapter 13
Heat Effects Control of Hazardous Materials has been re-titled
Exposure to heat can lead to life threat three basic ways: Regulated and Unregulated Cargoes to provide guid-
ance to tunnel operators, rst responders and
Hyperthermia enforcement ofcials on developing rules regarding
Body surface burns any and all cargoes allowed passage through a par-
Respiratory tract burns ticular road tunnel facility.
The authority having jurisdiction must adopt
For use in the modeling of life threat due to heat expo- rules and regulations that apply to the transportation
sure in res, it is necessary to consider only two cri- of regulated and unregulated cargoes. Design and
teriathe threshold of burning of the skin and the planning of the facility must address the potential
exposure at which hyperthermia is sufcient to cause risk presented by regulated and unregulated cargoes.
mental deterioration and thereby threaten survival. When developing vehicle cargo regulations for
a particular road tunnel facility, re, accident, and
Air Carbon Monoxide Content research experience of the vehicles and cargo of the
Air carbon monoxide (CO) content should be as follows: type expected within the tunneland particularly of
goods and vehicles not normally characterized as
Maximum of 2000 ppm for a few seconds hazardous or otherwise regulatedshould be con-
Averaging 1150 ppm or less for the rst 6 minutes sidered. Some types of cargoes not normally consid-
of the exposure ered hazardous may in certain circumstances in
Averaging 450 ppm or less for the rst 15 minutes conned spaces within tunnels behave as, or equiva-
of the exposure lent to, hazardous materials in terms of the rate of
Averaging 225 ppm or less for the rst 30 minutes re growth, the intensity of the re, discharge of
of the exposure noxious materials, destruction to infrastructure, and
Averaging 50 ppm or less for the remainder of the threat to users safety.
exposure In developing regulations, the following must
be addressed:
These values should be adjusted for altitudes above
984 m (3000 ft). 1. Population density
2. Type of highway
3. Types and quantities of hazardous materials

192
4. Emergency response capabilities The NFPA 502 Technical Committee fully
5. Results of consultation with affected persons anticipates that ongoing research programs being
6. Exposure and other risk factors conducted both nationally and internationally such
7. Terrain considerations as The International Road Tunnel Fire Detection
8. Continuity of routes Research Project sponsored by The Fire Protection
9. Alternative routes Research Foundation, the Large-Scale Fire Heat
10. Effects on commerce Release Rate Tests conducted by a variety of consor-
11. Delays in transportation tiums in collaboration with UPTUN and the SP
12. Climatic conditions Swedish National Testing and Research Institute,
13. Congestion and accident history and sprinkler system testing such as that conducted
by The Netherlands Organisation for Applied Scien-
tic Research, will continue to yield valuable infor-
SUMMARY
mation. As the Technical Committee looks forward
The 2008 Edition of NFPA 502 is intended to cor- to the development of the 2011 Edition of NFPA 502
relate the re and life safety provisions that are it fully recognizes that diligent attention to the
based on the latest research, technologies, and real- results of these research programs is necessary so
life lessons learned so that tunnel designers, engi- that fair evaluation and consensus of results can be
neers, rst responders, and operating authorities expeditiously considered for incorporation.
have an immediate source recognized requirements
for creating a re safe road tunnel environment.