7/16"
2-1/4" (11,1 mm) 4
(57,2 mm) NOMINAL
MAKE-IN 2
1-9/16" 2-3/16" 3
(39,7 mm) WRENCH (55,6 mm)
FLATS 1
7
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 1/2" NPT **
7/16" 5
2-3/16" (11,1 mm)
(55,6 mm) NOMINAL 4
MAKE-IN
1-1/2" 2
2-3/16"
(38,1 mm) WRENCH (55,6 mm)
FLATS 3
1
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 1/2" NPT **
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
DuPont Registered Trademark
7/16" 5
2-3/16" (11,1 mm)
(55,6 mm) NOMINAL 4
MAKE-IN
1-1/2" 2
2-3/16"
(38,1 mm) WRENCH (55,6 mm)
FLATS 3
1
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 1/2" NPT **
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
1/2" 5
2-5/16" (12,7 mm)
(58,7 mm) NOMINAL 4
MAKE-IN
2
1-9/16" 2-1/4"
(39,7 mm) WRENCH (57,2 mm)
FLATS 3
1
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 3/4" NPT **
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
SPRINKLER FINISH (See Note 7) inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
K TYPE TEMP. BULB NATURAL CHROME WHITE*** (13,4 to 26,8 Nm). A maximum of 30
LIQUID BRASS PLATED POLYESTER ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
135F/57C Orange nections. Higher levels of torque may
PENDENT distort the sprinkler inlet and cause
155F/68C Red
(TY1231) 1, 2, 3, 5 leakage or impairment of the sprinkler.
and 175F/79C Yellow
UPRIGHT
Do not attempt to make-up for insuffi-
200F/93C Green cient adjustment in the escutcheon
(TY1131)
2.8 286F/141C Blue plate by under- or over-tightening the
1/2" sprinkler. Readjust the position of the
NPT 135F/57C Orange sprinkler fitting to suit.
RECESSED
155F/68C Red The Series TY-FRB Pendent and Up-
PENDENT
(TY1231)* 175F/79C Yellow right Sprinklers must be installed in
accordance with the following instruc-
Figure 5 200F/93C Green 1, 2, 5 tions.
135F/57C Orange Step 1. Pendent sprinklers are to be
RECESSED installed in the pendent position, and
155F/68C Red
PENDENT upright sprinklers are to be installed in
(TY1231)** 175F/79C Yellow the upright position.
Figure 6 200F/93C Green Step 2. With pipe thread sealant ap-
135F/57C Orange plied to the pipe threads, hand tighten
PENDENT
the sprinkler into the sprinkler fitting.
155F/68C Red
(TY2231) Step 3. Tighten the sprinkler into the
and 175F/79C Yellow sprinkler fitting using only the W-Type
UPRIGHT 200F/93C Green
6 Sprinkler Wrench (Ref. Figure 13).
(TY2131) With reference to Figures 1, 2, 3, and
4.2 286F/141C Blue 4, the W-Type 6 Sprinkler Wrench is to
1/2" 1, 2
135F/57C Orange
be applied to the sprinkler wrench
NPT flats.
RECESSED
155F/68C Red
PENDENT
(TY2231)* 175F/79C Yellow The Series TY-FRB Recessed Pen-
Figure 7 dent Sprinklers must be installed in
200F/93C Green
accordance with the following instruc-
135F/57C Orange tions.
RECESSED Step A. After installing the Style 10.
155F/68C Red
PENDENT 20, 30, or 40 Mounting Plate, as appli-
(TY2231)** 175F/79C Yellow
cable, over the sprinkler threads and
Figure 8 200F/93C Green with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
NOTES: kler into the sprinkler fitting.
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Step B. Tighten the sprinkler into the
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response
Sprinklers.
sprinkler fitting using only the W-Type
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin- 7 Recessed Sprinkler Wrench (Ref.
klers. Figure 14). With reference to Figure 1,
5. Approved by the City of New York under MEA 354-01-E. 2, 3, and 4, the W-Type 7 Recessed
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin- Sprinkler Wrench is to be applied to
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers. the sprinkler wrench flats.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Step C. After the ceiling has been in-
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
stalled or the finish coat has been ap-
Recessed Escutcheon, as applicable. plied, slide on the Style 10, 20, 30, or
*** Frame and Deflector only. Listings and approvals apply to color (Special Order). 40 Closure over the Series TY-FRB
N/A: Not Available Sprinkler and push the Closure over
the Mounting Plate until its flange
TABLE A comes in contact with the ceiling.
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint
should be present. The diameter of the should be obtained with a torque of 7
air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
(1,6 mm) for the 135F/57C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque
inch (2,4 mm) for the 286F/141C may be used to install sprinklers with
temperature ratings. 1/2 NPT connections. A leak tight 3/4
TFP171 Page 5 of 8
135F/57C Orange
PENDENT
155F/68C Red
(TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5
and 175F/79C Yellow
UPRIGHT 200F/93C Green
(TY3131)
5.6 286F/141C Blue
1/2"
NPT 135F/57C Orange
RECESSED
155F/68C Red
PENDENT 1, 2, 4, 5 N/A
(TY3231)* 175F/79C Yellow
Figure 9 200F/93C Green
135F/57C Orange
RECESSED
155F/68C Red
PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A
(TY3231)** 175F/79C Yellow
Figure 10 200F/93C Green
135F/57C Orange
PENDENT
155F/68C Red
(TY4231) 1, 2, 5
and 175F/79C Yellow 1, 2, 3, 4, 5, 6, 7
UPRIGHT 200F/93C Green
(TY4131)
8.0 286F/141C Blue
3/4"
NPT 135F/57C Green
RECESSED
155F/68C Orange
PENDENT 1, 2, 4, 5 N/A
(TY4231)* 175F/79C Red
Figure 11 200F/93C Yellow
135F/57C Orange
RECESSED
155F/68C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4231)** 175F/79C Yellow
Figure 12 200F/93C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
*** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Page 6 of 8 TFP171
MOUNTING
MOUNTING SURFACE
SURFACE
FIGURE 5 FIGURE 6
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT 2.8 K-FACTOR, 1/2 INCH NPT
MOUNTING
MOUNTING SURFACE
SURFACE
SERIES 1-1/4" (31,8 mm) SERIES 1-1/4" (31,8 mm)
CLOSURE CLOSURE
TY-FRB 3/4" (19,1 mm) TY-FRB 1" (25,4 mm)
FIGURE 7 FIGURE 8
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT
used to cover a clearance hole, may and after installation. Sprinklers dam-
Care and delay the time to sprinkler operation in aged by dropping, striking, wrench
a fire situation. twist/slippage, or the like, must be re-
Maintenance Sprinklers that are found to be leaking
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
The Series TY-FRB Sprinklers must be or exhibiting visible signs of corrosion
liquid from its bulb. (Ref. Installation
maintained and serviced in accord- must be replaced.
Section).
ance with the following instructions: Automatic sprinklers must never be
Frequent visual inspections are rec-
painted, plated, coated or otherwise
NOTES ommended to be initially performed for
altered after leaving the factory. Modi-
Before closing a fire protection system corrosion resistant coated sprinklers,
fied sprinklers must be replaced.
main control valve for maintenance after the installation has been com-
Sprinklers that have been exposed to
work on the fire protection system that pleted, to verify the integrity of the cor-
corrosive products of combustion, but
it controls, permission to shut down the rosion resistant coating. Thereafter,
have not operated, should be replaced
affected fire protection system must be annual inspections per NFPA 25
if they cannot be completely cleaned
obtained from the proper authorities should suffice; however, instead of in-
by wiping the sprinkler with a cloth or
and all personnel who may be affected specting from the floor level, a random
by brushing it with a soft bristle brush.
by this action must be notified. sampling of close-up visual inspec-
Care must be exercised to avoid dam- tions should be made, so as to better
Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi-
TFP171 Page 7 of 8
MOUNTING
MOUNTING SURFACE
SURFACE
SERIES 1-1/4" (31,8 mm) SERIES 1-1/4" (31,8 mm)
CLOSURE CLOSURE
TY-FRB 3/4" (19,1 mm) TY-FRB 1" (25,4 mm)
FIGURE 9 FIGURE 10
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT 5.6 K-FACTOR, 1/2 INCH NPT
MOUNTING
MOUNTING SURFACE
SURFACE
CLOSURE SERIES 1-5/16" (33,3 mm) CLOSURE SERIES 1-5/16" (33,3 mm)
TY-FRB 13/16" (20,6 mm) TY-FRB 1-1/16" (27,0 mm)
FIGURE 11 FIGURE 12
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT 8.0 K-FACTOR, 3/4 INCH NPT
TABLE C
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446