Vous êtes sur la page 1sur 16

1 of 16

Info

Cond. Size Length Library


Cond./
ID kV / Code
Phase mm m Frequency
Cable Source Conductor Insulation
Hertz
C-132kV GIS-1-T1 0 1 50
C-132kV GIS-1-T2 0 1 50
C-OFFTAKER L1-132kV GIS- 0 1 2150
C-T1-33kV SWGR-1 33 4 1/C 630 630 50 BS6622 50 CU XLPE 90C
C-T1-T1N 33 1 1/C 300 300 50 BS6622 50 CU XLPE 90C
C-T1N-LV SWGR-1 1 2 1/C 300 300 50 BS5467 50 CU XLPE 90C
C-T1N-LV SWGR-2 1 2 1/C 300 300 50 BS5467 50 CU XLPE 90C
C-T2-33kV SWGR-2 33 4 1/C 630 630 50 BS6622 50 CU XLPE 90C
C-T2-T2N 33 1 1/C 300 300 50 BS6622 50 CU XLPE 90C
OFFTAKER L2-132kV GIS-1 0 1 2150
2 of 16

Physical

Insulation Shield Sheath Armor Jacket


Cond.
Cond./ Cond./ Size O.D. Thick. Thick. Thick. Thick. Thick.
ID kV Code
Phase Cable Type Y/N Type Type Type
mm cm mm mm mm mm mm

C-132kV GIS-1-T1 132 1 2.832 8 Yes 0.127 None 0 Aluminum Armor 2.5 PVC 2.9
C-132kV GIS-1-T2 132 1 2.832 8 Yes 0.127 None 0 Aluminum Armor 2.5 PVC 2.9
C-OFFTAKER L1-132kV GIS-1 132 1 2.832 8 Yes 0.127 None 0 Aluminum Armor 2.5 PVC 2.9
C-T1-33kV SWGR-1 33 4 1/C 630 630 2.832 XLPE 8 Yes 0.127 None 0 Aluminum Armor 2.5 PVC 2.9
C-T1-T1N 33 1 1/C 300 300 1.954 XLPE 8 Yes 0.127 None 0 Aluminum Armor 2.5 PVC 2.6
C-T1N-LV SWGR-1 1 2 1/C 300 300 1.954 XLPE 1.8 No 0 None 0 Aluminum Armor 1.6 PVC 1.9
C-T1N-LV SWGR-2 1 2 1/C 300 300 1.954 XLPE 1.8 No 0 None 0 Aluminum Armor 1.6 PVC 1.9
C-T2-33kV SWGR-2 33 4 1/C 630 630 2.832 XLPE 8 Yes 0.127 None 0 Aluminum Armor 2.5 PVC 2.9
C-T2-T2N 33 1 1/C 300 300 1.954 XLPE 8 Yes 0.127 None 0 Aluminum Armor 2.5 PVC 2.6
OFFTAKER L2-132kV GIS-1 132 1 2.832 8 Yes 0.127 None 0 Aluminum Armor 2.5 PVC 2.9
3 of 16

Cable
O.D.
cm

6.42
6.42
6.42
6.42
5.44
3.35
3.35
6.42
5.44
6.42
4 of 16

Impedance

Z
Frequenc
Cond./ Cond./ Length Size y Z R X
ID kV
Phase Cable (m) mm Hertz Ohms / Unit Ohms / Unit Ohms / Unit
Length Length Length

C-132kV GIS-1-T1 132 1 1/C 50 630 50 0.40838 0.0335 0.407


C-132kV GIS-1-T2 132 1 1/C 50 630 50 0.40838 0.0335 0.407
C-OFFTAKER L1-132kV GIS-1 132 1 1/C 2150 630 50 0.40838 0.0335 0.407
C-OFFTAKER L2-132kV GIS-1 132 1 1/C 2150 630 50 0.40838 0.0335 0.407
C-T1-33kV SWGR-1 33 4 1/C 50 630 50 0.35812 0.0283 0.357
C-T2-33kV SWGR-2 33 4 1/C 50 630 50 0.35812 0.0283 0.357
C-T1-T1N 33 1 1/C 50 300 50 0.39856 0.0601 0.394
C-T2-T2N 33 1 1/C 50 300 50 0.39856 0.0601 0.394
C-T1N-LV SWGR-1 1 2 1/C 50 300 50 0.11967 0.08 0.089
C-T1N-LV SWGR-2 1 2 1/C 50 300 50 0.11967 0.08 0.089
5 of 16

Configuration

Main Cable Aux Cable

Cond./ Cond./ Size Phase Neutral PE Neutral PE


ID kV Code
Phase Cable Armor Sheath Structure
mm mm mm mm mm mm

C-132kV GIS-1-T1 0 1 0- No No No
C-132kV GIS-1-T2 0 1 0- No No No
C-OFFTAKER L1-132kV GIS- 0 1 0- No No No
C-T1-33kV SWGR-1 33 4 1/C 630 630 12 - 630 No No No
C-T1-T1N 33 1 1/C 300 300 3 - 300 No No No
C-T1N-LV SWGR-1 1 2 1/C 300 300 6 - 300 No No No
C-T1N-LV SWGR-2 1 2 1/C 300 300 6 - 300 No No No
C-T2-33kV SWGR-2 33 4 1/C 630 630 12 - 630 No No No
C-T2-T2N 33 1 1/C 300 300 3 - 300 No No No
OFFTAKER L2-132kV GIS-1 0 1 0- No No No
6 of 16

Ampacity - Capacity

Base Operating Operating / FLA


Cond./ Cond./ Base Alert Allowable
ID kV Code Standard Installation Ta Tc Rho Ta Tc Rho
Phase Cable Size Amp Option Amp Amp %
oC oC C.cm / W oC oC C.cm / W
mm
C-132kV GIS-1-T1 0 1 0 IEEE 399 U/G Duct 35 90 90 Derated 0 0
C-132kV GIS-1-T2 0 1 0 IEEE 399 U/G Duct 35 90 90 Derated 0 0
C-OFFTAKER L1-132kV GIS- 0 1 0 IEEE 399 U/G Duct 35 90 90 Derated 0 0
C-T1-33kV SWGR-1 33 4 1/C 630 630 2440 IEEE 399 U/G Duct 15 90 120 35 90 90 Derated 2199.5 0 0
C-T1-T1N 33 1 1/C 300 300 490 IEEE 399 U/G Duct 15 90 120 35 90 90 Derated 441.7 0 0
C-T1N-LV SWGR-1 1 2 1/C 300 300 0 IEC 60364 A/G Trays 30 90 35 90 Derated 0 0
C-T1N-LV SWGR-2 1 2 1/C 300 300 0 IEC 60364 A/G Trays 30 90 35 90 Derated 0 0
C-T2-33kV SWGR-2 33 4 1/C 630 630 2440 IEEE 399 U/G Duct 15 90 120 35 90 90 Derated 2199.5 0 0
C-T2-T2N 33 1 1/C 300 300 490 IEEE 399 U/G Duct 15 90 120 35 90 90 Derated 441.7 0 0
OFFTAKER L2-132kV GIS-1 0 1 0 IEEE 399 U/G Duct 35 90 90 Derated 0 0
7 of 16

Sizing - Phase

Operating Constraints Optimal

Overload SC 3rd
Cond. / Cond./ Other
ID kV Code Size Loading Vd Vst Nom. In Current Harm. Cond. / Size
Phase Cable Harm.
mm Amps % % kA kA % Phase mm
(Cf)

C-132kV GIS-1-T1 0 1 0
C-132kV GIS-1-T2 0 1 0
C-OFFTAKER L1-132kV GIS- 0 1 0
C-T1-33kV SWGR-1 33 4 1/C 630 630 0
C-T1-T1N 33 1 1/C 300 300 0
C-T1N-LV SWGR-1 1 2 1/C 300 300 0
C-T1N-LV SWGR-2 1 2 1/C 300 300 0
C-T2-33kV SWGR-2 33 4 1/C 630 630 0
C-T2-T2N 33 1 1/C 300 300 0
OFFTAKER L2-132kV GIS-1 0 1 0
8 of 16

Thermal Sizing - Input


Leakag
Groun e
d Disc. Temp. Main Temp. Aux Temp. Curren
Factor k
Cond. / Cond./ Size Fault Time Cable Cable Armor/Sheath t
ID kV Code
Phase Cable kA s mA
mm Initial Final Initial Final Initial Final Main CableAux Cable
C-132kV GIS-1-T1 0 1
C-132kV GIS-1-T2 0 1
C-OFFTAKER L1-132kV GIS-1 0 1
C-T1-33kV SWGR-1 33 4 1/C 630 630
C-T1-T1N 33 1 1/C 300 300
C-T1N-LV SWGR-1 1 2 1/C 300 300 Formula Formula 0
C-T1N-LV SWGR-2 1 2 1/C 300 300 Formula Formula 0
C-T2-33kV SWGR-2 33 4 1/C 630 630
C-T2-T2N 33 1 1/C 300 300
OFFTAKER L2-132kV GIS-1 0 1
9 of 16

Thermal Sizing - Results

PE Aux PE Armor Sheath K2S2


Size
Cond. / Cond./ mm mm mm mm kA2s
ID kV Code
Phase Cable
mm ExistingRequired Existing Required Existing Required Existing RequiredMain CableAux CableArmor Sheath

C-132kV GIS-1-T1 0 1
C-132kV GIS-1-T2 0 1
C-OFFTAKER L1-132kV GIS- 0 1
C-T1-33kV SWGR-1 33 4 1/C 630 630
C-T1-T1N 33 1 1/C 300 300
C-T1N-LV SWGR-1 1 2 1/C 300 300
C-T1N-LV SWGR-2 1 2 1/C 300 300
C-T2-33kV SWGR-2 33 4 1/C 630 630
C-T2-T2N 33 1 1/C 300 300
OFFTAKER L2-132kV GIS-1 0 1
10 of 16

Shock Protection Input

Resistance
Cond. / Cond./ Size Load al h Permissible
ID kV Code
Phase Cable Type Vt
mm Ohms Ohms
C-132kV GIS-1-T1 0 1
C-132kV GIS-1-T2 0 1
C-OFFTAKER L1-132kV GIS- 0 1
C-T1-33kV SWGR-1 33 4 1/C 630 630
C-T1-T1N 33 1 1/C 300 300
C-T1N-LV SWGR-1 1 2 1/C 300 300 Distribution Circuit 0 0 BS 7671
C-T1N-LV SWGR-2 1 2 1/C 300 300 Distribution Circuit 0 0 BS 7671
C-T2-33kV SWGR-2 33 4 1/C 630 630
C-T2-T2N 33 1 1/C 300 300
OFFTAKER L2-132kV GIS-1 0 1
11 of 16

Shock Protection -Results

Loop Current Disconnect Time Loop Z Touch Voltage (TN or IT 1st Fault)
IT 2nd Fault Touch Voltage
Cond. / Cond./ Size
ID kV Code Calculated Permissible d Permissible Calculated Permissible Calculated Permissible Calculated Permissible
Phase Cable
mm kA kA s s Ohms Ohms V V V V
C-132kV GIS-1-T1 0 1
C-132kV GIS-1-T2 0 1
C-OFFTAKER L1-132kV GIS-1 0 1
C-T1-33kV SWGR-1 33 4 1/C 630 630
C-T1-T1N 33 1 1/C 300 300
C-T1N-LV SWGR-1 1 2 1/C 300 300
C-T1N-LV SWGR-2 1 2 1/C 300 300
C-T2-33kV SWGR-2 33 4 1/C 630 630
C-T2-T2N 33 1 1/C 300 300
OFFTAKER L2-132kV GIS-1 0 1
Cable Schedule Summary Cable Configur
Cable General Info
Size Length Lib. Freq. Phase
Cond. / Cond./ Lib. Cond. Insul.
ID kV Code mm m Hertz Phase Connection mm
Phase Cable Source Type Type

C-132kV GIS-1-T1 0 1 50 AC - 3P ABCN 0-


C-132kV GIS-1-T2 0 1 50 AC - 3P ABCN 0-
C-OFFTAKER L1-132kV GIS- 0 1 2150 AC - 3P ABCN 0-
C-T1-33kV SWGR-1 33 4 1/C 630 630 50 BS6622 50 CU XLPE 90C AC - 3P ABCN 12 - 630
C-T1-T1N 33 1 1/C 300 300 50 BS6622 50 CU XLPE 90C AC - 3P ABCN 3 - 300
C-T1N-LV SWGR-1 1 2 1/C 300 300 50 BS5467 50 CU XLPE 90C AC - 3P ABCN 6 - 300
C-T1N-LV SWGR-2 1 2 1/C 300 300 50 BS5467 50 CU XLPE 90C AC - 3P ABCN 6 - 300
C-T2-33kV SWGR-2 33 4 1/C 630 630 50 BS6622 50 CU XLPE 90C AC - 3P ABCN 12 - 630
C-T2-T2N 33 1 1/C 300 300 50 BS6622 50 CU XLPE 90C AC - 3P ABCN 3 - 300
OFFTAKER L2-132kV GIS-1 0 1 2150 AC - 3P ABCN 0-
Cable Configuration Cable Protection Cable Capacity/Ampacity
Configuration Protective Device (PD) Phase Capaci
Neutral PE Aux Neutral Aux PE
Armor Sheath Overload Overcurrent GFCI / RCD Base
mm mm mm mm Structure Standard
Device Device Device Amp

No No No None User-Defined None 0 IEEE 399


No No No None User-Defined None 0 IEEE 399
No No No None User-Defined None 0 IEEE 399
No No No None User-Defined None 2440 IEEE 399
No No No None User-Defined None 490 IEEE 399
No No No None User-Defined None 0 IEC 60364
No No No None User-Defined None 0 IEC 60364
No No No None User-Defined None 2440 IEEE 399
No No No None User-Defined None 490 IEEE 399
No No No None User-Defined None 0 IEEE 399
e Capacity/Ampacity Phase Constraints Optimal Phase
Phase Capacity / Ampacity Operating Values Phase Conductor - Sizing Constraints Phase - Optimal
Operating Operating Overload Overload SC OC Device Size
Allowable Loading Vd 3rd Harm. Cond./
Installation Tc Ta Type Nom. Amp Op. kA Current Time
Amp Amp % % Phase mm
C C In I2 kA sec
U/G Duct 35 90 0 0 FLA 0 0
U/G Duct 35 90 0 0 FLA 0 0
U/G Duct 35 90 0 0 FLA 0 0
U/G Duct 35 90 2199.5 0 FLA 0 0
U/G Duct 35 90 441.7 0 FLA 0 0
A/G Trays 35 90 0 0 FLA 0 0
A/G Trays 35 90 0 0 FLA 0 0
U/G Duct 35 90 2199.5 0 FLA 0 0
U/G Duct 35 90 441.7 0 FLA 0 0
U/G Duct 35 90 0 0 FLA 0 0
timal Phase Earthing - Existing Earthing - Required Electric Shock
Phase - Optimal Ground/Earth Conductors - Existing Ground/Earth Conductors - Required Electric Shock
PE Armor Sheath Aux PE Short Circuit Disconnect PE Armor Sheath Aux PE Loop Disconnect
Derated Vd Earthing
mm mm mm mm Current Time mm mm mm mm Current Time
Amp % Type
kA sec kA sec

Not Applicable
Not Applicable
Electric Shock
Permissible Loop
Loop Z
Time Permissible Z
Ohms
sec Ohms