Vous êtes sur la page 1sur 477

3.28 10.

76
Date- 22.10.2014 - Rev-00 Ambient Conditions
Client:- Earnest Chemists Limited DBT WBT RH Gr/lb `
Contractor:- Fabtech International Limited Summer 102 F 64% 200
Location:- Ghana Monsoon 81 F 76% 121
Equipment Load
Room Dimension Room Conditions Fresh Air Estimation Flow Estimation Ahu Specication Ahu Filtration Terminals
Estimation Dust Cooling Heating
Sr. Room Area Room Area Volume Temperatur Relative Occupanc Equipmen Diversit Final Class At Room Exfiltratio Dehumidifie Scavanging Selected Return Bleed Supply Static
AHU No.. Room Name Length Width Height Height ACPH ACPH Infiltration Exhaust Collectio Fresh Air System Type Coil Coil Fresh Air Post Bleed
No. e Humidity y t Load y Load Rest Pressure n d Air Air Air Air Air Air Pressure Pre Filter Supply Return
n Filter Filter Filter
Mt Mt Mt Ft Mt Sq.ft Mt C % Hp % HP Pascal CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM MM TR KW

1 Active Dispensing 4.19 4.57 3.00 9.84 19.13 205.80 57.38 222C NMT 55 1 5 70 3.5 Class D 25 25 20 119 0 0 1005 844 1005 1124 Hepa Riser
AHU-01 350 44 1480 125 Recirculation 6.38 2.69 G-4 F-5 F-8 H-12
2 Common Airlock for Dispensing 4.19 2.24 3.00 9.84 9.39 100.99 28.16 222C NMT 55 0 70 0.0 Class D 25 26 30 0 425 0 412 431 431 6 Hepa Hepa Box

Total 28.51 85.54 5 3.5 119 425 0 350 1417 1274 1436 1130 44 1480 6.38 2.69

1 AHU-02 Excipient Dispensing 4.19 5.99 3.00 9.84 25.09 269.97 75.27 222C NMT 55 1 5 70 3.5 Class D 25 25 20 119 0 0 110 960 1107 1107 1226 229 1336 125 Recirculation 2.89 2.69 G-4 F-5 F-8 H-12 Hepa Riser

Total 25.09 75.27 5 3.5 119 0 0 110 960 1107 1107 1226 229 1336 2.89 2.69

1 Sifting 1 3.19 5.34 4.00 13.12 17.03 183.22 68.11 222C NMT 55 1 5 70 3.5 Class D 25 25 25 304 0 0 150 1369 1002 1369 1523 Hepa Riser
2 AHU-03 Sifting 1 Material Airlock 1.85 2.15 3.00 9.84 3.98 42.84 11.94 222C NMT 55 0 70 0.0 Class D 25 53 35 0 370 0 455 281 372 372 2 1 1985 125 Recirculation 8.29 4.00 G-4 F-5 F-8 H-12 Hepa Hepa Box
3 Sifting 1 Man Airlock 1.28 2.15 3.00 9.84 2.75 29.63 8.26 222C NMT 55 0 70 0.0 Class D 25 50 35 0 238 0 195 243 243 5 Hepa Hepa Box

TOTAL 23.76 88.32 5 3.5 304 608 0 455 1845 1617 1984 1530 1 1985 8.29 4.00

15.80 5.34 5.00 16.40


1 Wet Granulation 1 111.21 1196.65 556.07 222C NMT 55 4 75 50 37.5 Class D 25 25 25 320 0 0 300 8420 8177 8420 8440 Hepa Riser
12.23 2.20 5.00 16.40
AHU-04 900 280 9344 125 Recirculation 24.81 28.85 G-4 F-5 F-8 H-12
2 Wet Granulation 1 Material Airlock 2.10 2.15 3.00 9.84 4.51 48.54 13.53 222C NMT 55 0 70 0.0 Class D 25 51 35 0 402 0 227 406 406 4 Hepa Hepa Box
3 Wet Granulation 1 Man Airlock 1.37 2.15 3.00 9.84 2.94 31.62 8.82 222C NMT 55 0 70 0.0 Class D 25 46 35 0 238 0 148 239 239 1 Hepa Hepa Box

Total 118.66 578.41 75 37.50 320 640 0 900 8795 8822 9064 8444 280 9344 24.81 28.85

1 12.63 5.35 4.5 14.76


Wet Granulation 2 88.32 950.35 397.45 222C NMT 55 4 50 50 25 Class D 25 25 25 304 0 0 300 5799 5845 5845 5849 Hepa Riser
9.45 2.20 4.5 14.76
AHU-05 650 46 6519 125 Recirculation 17.63 19.23 G-4 F-5 F-8 H-12
2 Wet Granulation 2 Material Airlock 1.83 2.15 3.0 9.84 3.92 42.22 11.77 222C NMT 55 0 70 0.0 Class D 25 55 35 0 370 0 176 381 381 11 Hepa Hepa Box
3 Wet Granulation 2 Man Airlock 1.26 2.15 3.0 9.84 2.70 29.03 8.09 222C NMT 55 0 70 0.0 Class D 25 52 35 0 238 0 121 248 248 10 Hepa Hepa Box

Total 94.94 510.82 50 25.00 304 608 0 650 6097 6473 6473 5869 46 6519 17.63 19.23

1 Dispensed Material Store 5.07 10.11 3.0 9.84 51.24 551.37 153.73 222C NMT 55 0 70 0.0 Class D 25 25 10 227 0 0 1129 2261 2261 2488 Hepa Hepa Box
41.91 2.50 3.0 9.84
2.50 25.13 3.0 9.84
2 Process Corridor 242.73 2611.72 728.18 222C NMT 55 0 70 0.0 Class D 25 25 25 2989 2358 0 5347 10708 10708 11339 Hepa Hepa Box
15.66 2.50 3.0 9.84
14.39 2.50 3.0 9.84
3 Used Equipments 3.55 7.55 3.0 9.84 26.80 288.39 80.41 222C NMT 55 0 70 0.0 Class D 25 25 5 284 0 1466 590 1182 1182 0 Hepa Hepa Box
4 Cleaned Equipments 2.88 3.95 3.0 9.84 11.34 122.04 34.03 222C NMT 55 0 70 0.0 Class D 25 27 40 0 521 0 250 540 540 19 Hepa Hepa Box
5 Production Office 1 4.38 2.91 3.0 9.84 12.74 137.04 38.21 222C NMT 55 3 0 70 0.0 Class D 25 25 10 145 0 0 281 562 562 707 Hepa Hepa Box
AHU-06 2300 3030 25971 125 Recirculation 47.06 14.00 G-4 F-5 F-8 H-12
6 IPQC 1 4.38 2.94 3.0 9.84 12.85 138.21 38.54 222C NMT 55 4 2 70 1.4 Class D 25 25 10 145 0 0 358 567 567 712 Hepa Hepa Box
7 Blend Store 7.68 5.98 3.0 9.84 45.91 494.01 137.74 222C NMT 55 0 70 0.0 Class D 25 25 10 227 0 0 1011 2025 2025 2252 Hepa Hepa Box
8 House Keeping 2.53 2.23 3.0 9.84 5.62 60.45 16.85 222C NMT 55 0 70 0.0 Class D 25 25 10 145 0 0 124 248 248 393 Hepa Hepa Box
9 Production Manager 2.53 3.26 3.0 9.84 8.22 88.49 24.67 222C NMT 55 2 1 70 0.7 Class D 25 25 10 145 0 0 219 363 363 508 Hepa Hepa Box
10 Common Corridor for Tablet compression 14.34 2.50 3.0 9.84 35.86 385.80 107.57 222C NMT 55 0 70 0.0 Class D 25 25 25 1520 0 0 790 1582 1582 3102 Hepa Hepa Box
11 Uncoated Tablets 5.11 5.53 3.0 9.84 28.26 304.11 84.79 222C NMT 55 0 70 0.0 Class D 25 25 10 227 0 0 623 1247 1247 1474 Hepa Hepa Box
12 Equipment Wash 1 6.55 3.55 3.0 9.84 23.25 250.20 69.76 222C NMT 55 2 5 70 3.5 Class D 25 25 5 237 0 1263 700 1026 1026 0 Hepa Hepa Box
13 Equipment Drying 1 3.63 3.95 3.0 9.84 14.30 153.87 42.90 222C NMT 55 1 5 70 3.5 Class D 25 25 20 284 237 0 503 631 631 678 Hepa Hepa Box

Total 519.12 1971.23 13 9.10 6575 3116 2729 2300 11925 22941 22941 23671 3030 25971 47.06 14.00

1 Equipment Storage 5.90 3.38 3.0 9.84 19.91 214.26 59.74 222C NMT 55 0 70 0.0 Class D 25 25 40 0 489 0 462 878 878 389 Hepa Hepa Box
2 Production Office 2 2.94 3.16 3.0 9.84 9.29 99.99 27.88 222C NMT 55 3 0 70 0.0 Class D 25 25 10 145 0 0 216 410 410 555 Hepa Hepa Box
3 IPQC 2 2.91 3.16 3.0 9.84 9.21 99.14 27.64 222C NMT 55 3 3 70 2.1 Class D 25 25 10 145 0 0 330 406 406 551 Hepa Hepa Box
4 Coated tablets Storage 9.53 5.50 3.0 9.84 52.45 564.32 157.34 222C NMT 55 0 70 0.0 Class D 25 25 10 227 0 0 1217 2314 2314 2541 Hepa Hepa Box
5 Dies & Punches Room 4.51 3.16 3.0 9.84 14.28 153.63 42.83 222C NMT 55 0 70 0.0 Class D 25 25 10 227 0 0 331 630 630 857 Hepa Hepa Box
6 Tool Room 3.78 3.16 3.0 9.84 11.95 128.58 35.85 222C NMT 55 0 70 0.0 Class D 25 25 10 227 0 0 277 527 527 754 Hepa Hepa Box
7 Equipment Wash 2 5.90 3.52 3.0 9.84 20.76 223.40 62.29 222C NMT 55 3 3 70 2.1 Class D 25 25 5 489 0 1405 598 916 916 0 Hepa Hepa Box
AHU-6A 1600 2777 18862 125 Recirculation 34.07 11.70 G-4 F-5 F-8 H-12
9 Equipment Drying 2 5.90 2.45 3.0 9.84 14.46 155.54 43.37 222C NMT 55 1 3 70 2.1 Class D 25 25 20 262 227 0 452 638 638 673 Hepa Hepa Box
10 PPM Day Store 5.93 3.55 3.0 9.84 21.03 226.34 63.10 222C NMT 55 3 70 2.1 Class D 25 25 10 227 0 0 605 928 928 1155 Hepa Hepa Box
11 ALU/PVC Store Room 3.00 3.16 3.0 9.84 9.49 102.10 28.47 222C NMT 55 0 70 0.0 Class D 25 25 10 227 0 0 220 419 419 646 Hepa Hepa Box
2.50 27.63 3.0
36.20 2.50 3.0
12 Process Corridor 9.84 181.77 1955.85 545.31 222C NMT 55 0 70 0 Class D 25 25 25 3583 2461 0 4217 8019 8019 9141 Hepa Hepa Box
1.51 5.08 3.0
1.51 9.60 3.0

Total 364.61 1093.82 12 8.40 5759 3177 1405 1600 8926 16085 16085 17262 2777 18862 34.07 11.70

7.88 4.29 4.0


1 Dry Granulation 13.12 41.36 445.05 165.44 222C NMT 55 2 15 70 10.5 Class D 25 25 25 304 0 0 150 2341 2433 2433 2587 Hepa Riser
4.51 1.69 4.0
AHU-07 455 1 3046 125 Recirculation 9.54 8.08 G-4 F-5 F-8 H-12
2 Dry Granulation Material Airlock 2.03 1.64 3.0 9.84 3.32 35.71 9.96 222C NMT 55 0 70 0.0 Class D 25 64 35 0 370 0 140 375 375 5 Hepa Hepa Box
3 Dry Granulation Man Airlock 1.25 1.64 3.0 9.84 2.04 21.96 6.12 222C NMT 55 0 70 0.0 Class D 25 66 35 0 238 0 86 238 238 0 Hepa Hepa Box

Total 46.72 181.52 15 10.50 304 608 0 455 2567 3045 3045 2591 1 3046 9.54 8.08

4.90 4.20 4.5


1 Tablet Compression 1 14.76 23.39 251.68 105.26 222C NMT 55 2 10 70 7 Class D 25 25 25 304 0 0 150 1631 1548 1631 1785 Hepa Riser
1.67 1.70 4.5
AHU-08 455 1 2241 125 Recirculation 8.44 5.38 G-4 F-5 F-8 H-12
2 Tablet Compression 1 Material Airlock 1.83 1.65 3.0 9.84 3.01 32.36 9.02 222C NMT 55 0 70 0.0 Class D 25 70 35 0 370 0 166 372 372 2 Hepa Hepa Box
3 Tablet Compression 1 Man Airlock 1.30 1.65 3.0 9.84 2.14 23.05 6.43 222C NMT 55 0 70 0.0 Class D 25 63 35 0 238 0 118 238 238 0 Hepa Hepa Box

Total 28.54 120.71 10 7.00 304 608 0 455 1915 2158 2240 1786 1 2241 8.44 5.38

4.97 4.19 4.5


1 Tablet compression 2 14.76 23.80 256.06 107.09 222C NMT 55 2 10 70 7 Class D 25 25 25 304 0 0 150 1641 1575 1641 1795 Hepa Riser
1.75 1.71 4.5
AHU-09 455 1 2256 125 Recirculation 8.46 5.38 G-4 F-5 F-8 H-12
2 Tablet compression 2 Material Airlock 1.83 1.66 3.0 9.84 3.03 32.58 9.08 222C NMT 55 0 70 0.0 Class D 25 70 35 0 370 0 166 374 374 4 Hepa Hepa Box
3 Tablet compression 2 Man Airlock 1.30 1.66 3.0 9.84 2.16 23.21 6.47 222C NMT 55 0 70 0.0 Class D 25 63 35 0 238 0 118 240 240 2 Hepa Hepa Box

Total 28.98 122.64 10 7.00 304 608 0 455 1925 2189 2255 1801 1 2256 8.46 5.38

4.90 4.20 4.5


1 Tablet Compression 3 14.76 23.27 250.35 104.70 222C NMT 55 2 10 70 7 Class D 25 25 25 304 0 0 150 1622 1540 1622 1776 Hepa Riser
1.60 1.71 4.5
AHU-10 455 1 2236 125 Recirculation 8.44 5.38 G-4 F-5 F-8 H-12
2 Tablet compression 3 Material Airlock 1.88 1.66 3.0 9.84 3.11 33.47 9.33 222C NMT 55 0 70 0.0 Class D 25 68 35 0 370 0 172 373 373 3 Hepa Hepa Box
3 Tablet compression 3 Man Airlock 1.33 1.66 3.0 9.84 2.20 23.65 6.59 222C NMT 55 0 70 0.0 Class D 25 62 35 0 238 0 121 240 240 2 Hepa Hepa Box

Total 28.58 120.62 10 7.00 304 608 0 455 1915 2153 2235 1781 1 2236 8.44 5.38

4.90 4.20 4.5


1 Tablet compression 4 14.76 23.27 250.35 104.70 222C NMT 55 2 10 70 7 Class D 25 25 25 304 0 0 150 1622 1540 1622 1776 Hepa Riser
1.60 1.71 4.5
AHU-11 455 1 2236 125 Recirculation 8.44 5.38 G-4 F-5 F-8 H-12
2 Tablet Compression 4 Material Airlock 1.88 1.66 3.0 9.84 3.11 33.47 9.33 222C NMT 55 0 70 0.0 Class D 25 68 35 0 370 0 172 373 373 3 Hepa Hepa Box
3 Tablet Compression 4 Man Airlock 1.33 1.66 3.0 9.84 2.20 23.65 6.59 222C NMT 55 0 70 0.0 Class D 25 62 35 0 238 0 121 240 240 2 Hepa Hepa Box

Total 28.58 120.62 10 7.00 304 608 0 455 1915 2153 2235 1781 1 2236 8.44 5.38

4.45 4.20 4.5


1 Tablet compression Future 14.76 20.63 222.01 92.85 222C NMT 55 2 10 70 7 Class D 25 25 25 304 0 0 150 1706 1365 1706 1860 Hepa Riser
1.15 1.71 4.5
AHU-12 455 1 2321 125 Recirculation 8.67 5.38 G-4 F-5 F-8 H-12
2 Tablet Compression Future Material Airlock 1.88 1.66 3.0 9.84 3.11 33.47 9.33 222C NMT 55 0 70 0.0 Class D 25 68 35 0 370 0 204 373 373 3 Hepa Hepa Box
3 Tablet Compression Future Man Airlock 1.33 1.66 3.0 9.84 2.20 23.65 6.59 222C NMT 55 0 70 0.0 Class D 25 62 35 0 238 0 144 240 240 2 Hepa Hepa Box

Total 25.94 108.78 10 7.00 304 608 0 455 2055 1979 2320 1866 1 2321 8.67 5.38

1 Solution Preparation 1 2.53 2.64 3.0 9.84 6.66 71.67 19.98 222C NMT 55 1 5 70 3.5 Class D 25 25 10 145 0 1175 1030 294 1030 0 Hepa Riser
2 Material Airlock 1.73 1.48 3.0 9.84 2.55 27.39 7.64 222C NMT 55 0 70 0.0 Class D 25 83 35 0 370 0 332 373 373 3 Hepa Hepa Box
3 AHU-14 Persoanl Airlock 1.32 1.48 3.0 9.84 1.95 21.01 5.86 222C NMT 55 0 70 0.0 Class D 25 70 35 0 238 0 1500 255 241 255 17 21 5836 125 Recirculation 26.73 20.00 G-4 F-5 F-8 H-12 Hepa Hepa Box
6.59 3.85 4.0
4 Film Coating 1 13.12 30.60 329.27 122.41 222C NMT 55 1 5 70 3.5 Class D 25 25 25 304 145 0 4157 1800 4157 4316 Hepa Riser
3.44 1.53 4.0

Total 41.76 155.88 10 7.00 449 753 1175 1500 5775 2708 5815 4336 21 5836 26.73 20.00

1 Solution Preparation 2 2.53 2.69 3.0 9.84 6.79 73.03 20.36 222C NMT 55 1 3 70 2.1 Class D 25 25 10 145 0 1083 938 299 938 0 Hepa Riser
2 Material Airlock 1.73 1.40 3.0 9.84 2.42 25.99 7.25 222C NMT 55 0 70 0.0 Class D 25 87 35 0 370 0 300 371 371 1 Hepa Hepa Box
3 AHU-15 Persoanl Airlock 1.30 1.40 3.0 9.84 1.82 19.58 5.46 222C NMT 55 0 70 0.0 Class D 25 74 35 0 238 0 1400 226 238 238 0 13 5361 125 Recirculation 24.72 20.00 G-4 F-5 F-8 H-12 Hepa Hepa Box
6.40 3.93 3.0
4 Film Coating 2 9.84 29.85 321.20 89.55 222C NMT 55 1 3 70 2.1 Class D 25 25 25 304 145 0 3802 1317 3802 3961 Hepa Riser
3.27 1.45 3.0

Total 40.87 122.62 6 4.20 449 753 1083 1400 5265 2225 5348 3961 13 5361 24.72 20.00
3.28 10.76
Date- 22.10.2014 - Rev-00 Ambient Conditions
Client:- Earnest Chemists Limited DBT WBT RH Gr/lb `
Contractor:- Fabtech International Limited Summer 102 F 64% 200
Location:- Ghana Monsoon 81 F 76% 121
Equipment Load
Room Dimension Room Conditions Fresh Air Estimation Flow Estimation Ahu Specication Ahu Filtration Terminals
Estimation Dust Cooling Heating
Sr. Room Area Room Area Volume Temperatur Relative Occupanc Equipmen Diversit Final Class At Room Exfiltratio Dehumidifie Scavanging Selected Return Bleed Supply Static
AHU No.. Room Name Length Width Height Height ACPH ACPH Infiltration Exhaust Collectio Fresh Air System Type Coil Coil Fresh Air Post Bleed
No. e Humidity y t Load y Load Rest Pressure n d Air Air Air Air Air Air Pressure Pre Filter Supply Return
n Filter Filter Filter
Mt Mt Mt Ft Mt Sq.ft Mt C % Hp % HP Pascal CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM MM TR KW
3.28 10.76
Date- 22.10.2014 - Rev-00 Ambient Conditions
Client:- Earnest Chemists Limited DBT WBT RH Gr/lb `
Contractor:- Fabtech International Limited Summer 102 F 64% 200
Location:- Ghana Monsoon 81 F 76% 121
Equipment Load
Room Dimension Room Conditions Fresh Air Estimation Flow Estimation Ahu Specication Ahu Filtration Terminals
Estimation Dust Cooling Heating
Sr. Room Area Room Area Volume Temperatur Relative Occupanc Equipmen Diversit Final Class At Room Exfiltratio Dehumidifie Scavanging Selected Return Bleed Supply Static
AHU No.. Room Name Length Width Height Height ACPH ACPH Infiltration Exhaust Collectio Fresh Air System Type Coil Coil Fresh Air Post Bleed
No. e Humidity y t Load y Load Rest Pressure n d Air Air Air Air Air Air Pressure Pre Filter Supply Return
n Filter Filter Filter
Mt Mt Mt Ft Mt Sq.ft Mt C % Hp % HP Pascal CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM MM TR KW
1 Solution Preparation 2.55 2.53 3.0 9.84 6.44 69.28 19.32 222C NMT 55 1 3 70 2.1 Class D 25 25 10 145 0 880 735 284 735 0 Hepa Riser
2 Material Airlock 1.75 1.40 3.0 9.84 2.45 26.36 7.35 222C NMT 55 0 70 0.0 Class D 25 86 35 0 370 0 244 372 372 2 Hepa Hepa Box
3 AHU-16 Persoanl Airlock 1.30 1.40 3.0 9.84 1.82 19.58 5.46 222C NMT 55 0 70 0.0 Class D 25 75 35 0 238 0 1200 181 241 241 3 16 4748 125 Recirculation 21.26 16.00 G-4 F-5 F-8 H-12 Hepa Hepa Box
5.28 5.53 3.0
4 Sugar Coating Room 9.84 33.08 355.95 99.24 222C NMT 55 1 3 70 2 Class D 25 25 25 304 145 0 3384 1459 3384 3543 Hepa Riser
2.60 1.50 3.0

Total 43.79 131.37 6 4.20 449 753 880 1200 4544 2356 4732 3548 16 4748 21.26 16.00

5.93 5.10 4.5


1 Dry Syrup manufacturing 14.76 44.39 477.65 199.76 222C NMT 55 2 8 70 5.6 Class D 25 25 25 304 0 0 150 2009 2938 2938 3092 Hepa Riser
4.24 3.35 4.5
AHU-17 450
2 Dry Syrup manufacturing Material Airlock 1.64 2.03 3.0 9.84 3.33 35.78 9.98 222C NMT 55 0 70 0.0 Class D 25 63 35 0 370 0 125 370 370 0 223 3768 125 Recirculation 9.99 4.31 G-4 F-5 F-8 H-12 Hepa Hepa Box
3 Dry Syrup manufacturing Man AirLock 1.64 1.23 3.0 9.84 2.01 21.64 6.03 222C NMT 55 0 70 0.0 Class D 25 67 35 0 238 0 76 238 238 0 Hepa Hepa Box
8 Dry Syrup Blend Store 5.93 2.87 3.0 9.84 17.03 183.22 51.08 222C NMT 55 0 70 0.0 Class D 25 25 10 227 0 0 641 751 0 227 Hepa Hepa Box

Total 66.76 266.85 8 5.60 531 608 0 450 2850 4296 3545 3318 223 3768 9.99 4.31

1 ORS Blend Store 5.90 3.88 3.0 9.84 22.89 246.25 68.66 222C NMT 30 0 70 0.0 Class D 25 25 10 227 0 0 150 1079 1010 1079 1156 Hepa Hepa Box
5.90 5.09 4.5
2 ORS Manufacturing 14.76 44.06 474.13 198.29 222C NMT 30 2 10 70 7 Class D 25 25 25 304 0 0 2315 2916 2916 3220 Hepa Riser
AHU-18 4.18 3.36 4.5 455 228 4838 125 Recirculation 22.84 5.38 G-4 EU-4 F-8 H-12
3 ORS Manufacturing Material Airlock 1.67 2.03 3.0 9.84 3.37 36.30 10.12 222C NMT 30 0 70 0.0 Class D 25 63 35 0 370 0 159 375 375 5 Hepa Hepa Box
4 ORS Manufacturing Man AirLock 1.67 1.24 3.0 9.84 2.06 22.16 6.18 222C NMT 30 0 70 0.0 Class D 25 66 35 0 238 0 97 240 240 2 Hepa Hepa Box

Total 72.38 283.24 10 7.00 531 608 0 455 3650 4540 4610 4383 228 4838 22.84 5.38

1 AHU-19 Bottle Cleaning 5.93 6.15 3.0 9.84 36.43 391.96 109.28 222C NMT 55 2 2 70 1.4 Class D 25 25 10 227 0 1847 1650 1620 1607 1620 0 30 1650 125 Once through 8.47 4.00 G-4 F-5 F-8 H-12 Hepa Riser

Total 36.43 109.28 2 1.40 227 0 1847 1650 1620 1607 1620 0 30 1650 8.47 4.00

5.90 5.50 3.0 9.84


1 Dry Syrup filling & Sealing 39.83 428.57 119.49 222C NMT 55 2.00 3.00 70 2 Class D 25 25 25 304 0 0 1427 1757 1757 2061 Hepa Riser
4.10 1.80 3.0 9.84
AHU-20 350 46 2413 125 Recirculation 6.74 2.00 G-4 F-5 F-8 H-12
2 Dry Syrup filling & Sealing Material Airlock 1.70 1.70 3.0 9.84 2.89 31.10 8.67 222C NMT 55 0 70 0.0 Class D 25 73 35 0 370 0 96 372 372 2 Hepa Hepa Box
3 Dry Syrup filling & Sealing Man AirLock 1.49 1.35 3.0 9.84 2.01 21.64 6.03 222C NMT 55 0 70 0.0 Class D 25 67 35 0 238 0 67 238 238 0 Hepa Hepa Box

Total 44.73 134.19 3 2.10 304 608 0 350 1590 2367 2367 2063 46 2413 6.74 2.00

1 Empty Capsule Day Store 3.00 4.87 3.0 9.84 14.61 157.17 43.82 222C NMT 45 0 0 70 0.0 Class D 25 25 10 227 0 0 479 644 644 871 Hepa Hepa Box
2 Material Airlock 1.75 1.40 3.0 9.84 2.45 26.36 7.35 222C NMT 45 70 0.0 Class D 25 86 35 0 370 0 80 372 372 2 Hepa Hepa Box
3 Persoanl Airlock 1.30 1.40 3.0 9.84 1.82 19.57 5.46 222C NMT 45 70 0.0 Class D 25 75 35 0 238 0 60 241 241 3 Hepa Hepa Box
AHU-21 400 42 2947 125 Recirculation 11.75 2.69 G-4 F-5 F-8 H-12
6.73 3.42 3.0
4 Capsule Filling & Inspection 9.84 28.19 303.35 84.58 222C NMT 45 4 5 70 3.5 Class D 25 25 25 435 0 0 150 1048 1244 1244 1529 Hepa Riser
3.58 1.45 3.0
5 Filled Capsules Room 2.90 3.16 3.0 9.84 9.17 98.70 27.52 222C NMT 45 70 0.0 Class D 25 25 30 0 262 0 301 405 405 143 Hepa Hepa Box

Total 56.24 184.29 5 3.50 662 870 0 400 1967 2905 2905 2547 42 2947 11.75 2.69

1 Return Change Room Gents 3.29 5.08 3.0 9.84 16.71 179.82 50.14 222C NMT 55 3 70 2.1 Class D 25 25 15 119 145 0 590 737 737 711 Hepa Hepa Box
2 Secondary Change Room Ladies 3.29 4.01 3.0 9.84 13.21 142.12 39.62 222C NMT 55 0 70 0.0 Class D 25 25 15 0 145 0 360 583 583 438 Hepa Hepa Box
AHU-22 350 8 3375 125 Recirculation 7.81 3.23 G-4 F-5 F-8 H-12
3 Return Change Room Ladies 3.29 4.03 3.0 9.84 13.25 142.62 39.76 222C NMT 55 3 70 2.1 Class D 25 25 15 119 145 0 495 585 585 559 Hepa Hepa Box
4 Secondary Change Room Gents 6.03 5.50 3.0 9.84 33.14 356.62 99.43 222C NMT 55 0 70 0.0 Class D 25 25 15 0 145 0 904 1462 1462 1317 Hepa Hepa Box

Total 76.32 228.95 6 4.20 238 580 0 350 2349 3367 3367 3025 8 3375 7.81 3.23

1 Material Airlock 1.69 1.40 3.0 9.84 2.37 25.47 7.10 222C NMT 55 70 0.0 Class D 25 89 35 0 370 0 183 372 372 2 Hepa Hepa Box
2 Persoanl Airlock 1.34 1.40 3.0 9.84 1.87 20.14 5.62 222C NMT 55 70 0.0 Class D 25 72 35 0 238 0 144 238 238 0 Hepa Hepa Box
AHU-23 725 23 3170 125 Recirculation 13.05 7.00 G-4 F-5 F-8 H-12
4.57 6.00 3.0
3 Blister Packing 1 9.84 29.49 317.34 88.48 222C NMT 55 2 8 70 5.6 Class D 25 25 25 304 398 0 2537 1301 2537 2443 Hepa Riser
1.44 1.45 3.0

Total 33.73 107.47 8 5.60 304 1006 0 725 2864 1911 3147 2445 23 3170 13.05 7.00

1 Material Airlock 1.69 1.40 3.0 9.84 2.37 25.47 7.10 222C NMT 55 70 0.0 Class D 25 89 35 0 370 0 187 372 372 2 Hepa Hepa Box
2 Persoanl Airlock 1.34 1.40 3.0 9.84 1.87 20.14 5.62 222C NMT 55 70 0.0 Class D 25 72 35 0 238 0 148 238 238 0 Hepa Hepa Box
AHU-24 725 23 3149 125 Recirculation 13.02 7.00 G-4 F-5 F-8 H-12
4.45 6.00 3.0
3 Blister Packing 2 9.84 28.60 307.73 85.80 222C NMT 55 2 8 70 5.6 Class D 25 25 25 304 398 0 2516 1262 2516 2422 Hepa Riser
1.32 1.45 3.0

Total 32.84 104.27 8 5.60 304 1006 0 725 2850 1871 3126 2424 23 3149 13.02 7.00

1 Material Airlock 1.69 1.40 3.0 9.84 2.37 25.47 7.10 222C NMT 55 70 0.0 Class D 25 89 35 0 370 0 184 372 372 2 Hepa Hepa Box
2 Persoanl Airlock 1.34 1.40 3.0 9.84 1.87 20.14 5.62 222C NMT 55 70 0.0 Class D 25 72 35 0 238 0 146 238 238 0 Hepa Hepa Box
AHU-25 725 23 3162 125 Recirculation 13.04 7.00 G-4 F-5 F-8 H-12
4.53 6.00 3.0
3 Blister Packing 3 9.84 29.16 313.72 87.47 222C NMT 55 2 8 70 5.6 Class D 25 25 25 304 398 0 2529 1286 2529 2435 Hepa Riser
1.40 1.45 3.0

Total 33.40 106.26 8 5.60 304 1006 0 725 2859 1896 3139 2437 23 3162 13.04 7.00

1 Material Airlock 1.69 1.40 3.0 9.84 2.37 25.47 7.10 222C NMT 55 70 0.0 Class D 25 89 35 0 370 0 187 372 372 2 Hepa Hepa Box
2 Persoanl Airlock 1.34 1.40 3.0 9.84 1.87 20.14 5.62 222C NMT 55 70 0.0 Class D 25 72 35 0 238 0 148 238 238 0 Hepa Hepa Box
AHU-26 725 23 3149 125 Recirculation 13.02 7.00 G-4 F-5 F-8 H-12
4.45 6.00 3.0
3 Strip packing 9.84 28.60 307.73 85.80 222C NMT 55 2 8 70 5.6 Class D 25 25 25 304 398 0 2516 1262 2516 2422 Hepa Riser
1.32 1.45 3.0

Total 32.84 104.27 8 5.60 304 1006 0 725 2850 1871 3126 2424 23 3149 13.02 7.00

1 Material Airlock 1.69 1.40 3.0 9.84 2.37 25.47 7.10 222C NMT 55 70 0.0 Class D 25 89 35 0 370 0 200 372 372 2 Hepa Hepa Box
2 Persoanl Airlock 1.34 1.40 3.0 9.84 1.87 20.14 5.62 222C NMT 55 70 0.0 Class D 25 72 35 0 238 0 158 238 238 0 Hepa Hepa Box
AHU-27 725 23 3209 125 Recirculation 13.17 9.00 G-4 F-5 F-8 H-12
4.45 6.00 3.0
3 Bulk Packing 9.84 28.60 307.73 85.80 222C NMT 55 2 5 70 3.5 Class D 25 25 25 304 398 0 2577 1262 2577 2483 Hepa Riser
1.32 1.45 3.0

Total 32.84 104.27 5 3.50 304 1006 0 725 2934 1871 3186 2484 23 3209 13.17 9.00

1 Material Airlock 1.69 1.40 3.0 9.84 2.37 25.47 7.10 222C NMT 30 70 0.0 Class D 25 89 35 0 370 0 124 372 372 2 Hepa Hepa Box
2 Persoanl Airlock 1.34 1.40 3.0 9.84 1.87 20.14 5.62 222C NMT 30 70 0.0 Class D 25 72 35 0 238 0 98 238 238 0 Hepa Hepa Box
AHU-28 725 23 2176 125 Recirculation 17.53 2.69 G-4 F-5 F-8 H-12
4.38 6.00 3.0
3 Satchet Filling 1 9.84 28.04 301.72 84.12 222C NMT 30 2 5 70 3.5 Class D 25 25 25 304 398 0 1543 1237 1543 1449 Hepa Riser
1.25 1.45 3.0

Total 32.28 102.26 5 3.50 304 1006 0 725 1765 1847 2153 1451 23 2176 17.53 2.69

1 Material Airlock 1.32 1.40 3.0 9.84 1.85 19.91 5.55 222C NMT 30 70 0.0 Class D 25 115 35 0 370 0 95 376 376 6 Hepa Hepa Box
2 Persoanl Airlock 1.71 1.40 3.0 9.84 2.39 25.68 7.16 222C NMT 30 70 0.0 Class D 25 57 35 0 238 0 122 240 240 2 Hepa Hepa Box
AHU-29 725 23 2186 125 Recirculation 17.53 2.69 G-4 F-5 F-8 H-12
4.47 6.00 3.0 0
3 Satchet Filling 2 9.84 28.73 309.09 86.18 222C NMT 30 2 5 70 3.5 Class D 25 25 25 304 398 1548 1267 1548 1454 Hepa Riser
1.34 1.45 3.0 0

Total 32.96 104.72 5 3.50 304 1006 0 725 1765 1883 2163 1461 23 2186 17.53 2.69

1 Material Airlock 1.32 1.40 3.0 9.84 1.84 19.81 5.52 222C NMT 30 70 0.0 Class D 25 114 35 0 370 0 94 370 370 0 Hepa Hepa Box
2 Persoanl Airlock 1.69 1.40 3.0 9.84 2.36 25.43 7.09 222C NMT 30 70 0.0 Class D 25 57 35 0 238 0 120 238 238 0 Hepa Hepa Box
AHU-30 725 23 2182 125 Recirculation 17.53 2.69 G-4 F-5 F-8 H-12
4.51 6.00 3.0
3 Satchet Filling 3 9.84 29.07 312.76 87.20 222C NMT 30 2 5 70 3.5 Class D 25 25 25 304 398 0 1551 1282 1551 1457 Hepa Riser
1.41 1.45 3.0

Total 33.27 105.93 5 3.50 304 1006 0 725 1765 1890 2159 1457 23 2182 17.53 2.69

1 Material Airlock 1.73 1.48 3.0 9.84 2.55 27.39 7.64 222C NMT 55 0 70 0.0 Class D 25 83 35 0 370 0 211 373 373 3 Hepa Hepa Box
2 Persoanl Airlock 1.30 1.48 3.0 9.84 1.92 20.62 5.75 222C NMT 55 70 0.0 Class D 25 71 35 0 238 0 159 240 240 2 Hepa Hepa Box
AHU-31 350 46 2163 125 Recirculation 7.30 6.00 G-4 F-5 F-8 H-12
4.51 3.34 3.0
3 Tablet Inspection 9.84 17.21 185.21 51.64 222C NMT 55 4 2 70 1.4 Class D 25 25 25 304 0 0 1504 759 1504 1808 Hepa Riser
1.39 1.53 3.0

Total 21.67 71.38 2 1.40 304 608 0 350 1874 1372 2117 1813 46 2163 7.30 6.00

1 Gents Air Lock 2.35 2.48 3.0 9.84 5.83 62.71 17.48 232C NMT 60 0 70 0 5 25 5 0 252 0 102 257 257 5 Diffuser Diffuser
2 Ladies Air Lock 2.35 2.48 3.0 9.84 5.83 62.71 17.48 232C NMT 60 0 70 0 5 25 5 0 252 0 102 257 257 5 Diffuser Diffuser
3 Office & Documentation 4.86 2.55 3.0 9.84 12.38 133.24 37.15 232C NMT 60 2 1 70 1 5 5 0 0 0 0 285 109 285 285 Diffuser Diffuser
4 Batch Printing 4.86 2.59 3.0 9.84 12.55 135.07 37.66 232C NMT 60 2 1 70 1 5 5 0 0 0 0 287 111 287 287 Diffuser Diffuser
5 Tool Room for Secondary packing 4.86 2.59 3.0 9.84 12.55 135.07 37.66 232C NMT 60 0 70 0 Filtered 5 5 0 0 0 0 219 111 219 219 Diffuser Diffuser
AHU-32 36.20 12.55 3.8 Unclassifie 1000 4266 23670 80 Recirculation 41.25 39.54 G-4 F-5 F-8 F-8
6 Secondary Packing Hall 12.46 524.00 5638.26 1991.21 232C NMT 60 48 100 50 50 5 5 0 3184 0 0 14041 5856 14041 17225 Diffuser Diffuser
5.93 11.78 3.8 d
7 Secondary Packing Material Day Store 5.44 3.44 3.0 9.84 18.71 201.30 56.12 232C NMT 60 0 70 0 5 5 0 0 0 0 326 165 326 326 Diffuser Diffuser
44.15 2.00 3.0 9.84
8 Packing Corridor 214.13 2304.05 642.39 232C NMT 60 70 0 5 5 0 586 0 0 3732 1889 3732 4318 Diffuser Diffuser
2.10 60.00 3.0 9.84
9 Primary Scrap 3.29 1.45 3.0 9.84 4.78 51.45 14.34 232C NMT 60 0 70 0 5 5 0 0 0 0 0 0 0 0 Diffuser Diffuser
3.28 10.76
Date- 22.10.2014 - Rev-00 Ambient Conditions
Client:- Earnest Chemists Limited DBT WBT RH Gr/lb `
Contractor:- Fabtech International Limited Summer 102 F 64% 200
Location:- Ghana Monsoon 81 F 76% 121
Equipment Load
Room Dimension Room Conditions Fresh Air Estimation Flow Estimation Ahu Specication Ahu Filtration Terminals
Estimation Dust Cooling Heating
Sr. Room Area Room Area Volume Temperatur Relative Occupanc Equipmen Diversit Final Class At Room Exfiltratio Dehumidifie Scavanging Selected Return Bleed Supply Static
AHU No.. Room Name Length Width Height Height ACPH ACPH Infiltration Exhaust Collectio Fresh Air System Type Coil Coil Fresh Air Post Bleed
No. e Humidity y t Load y Load Rest Pressure n d Air Air Air Air Air Air Pressure Pre Filter Supply Return
n Filter Filter Filter
Mt Mt Mt Ft Mt Sq.ft Mt C % Hp % HP Pascal CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM MM TR KW

Total 810.77 2851.50 102 51.40 3770 504 0 1000 19093 8756 19404 22670 4266 23670 41.25 39.54
3.28 10.76
Date- 22.10.2014 - Rev-00 Ambient Conditions
Client:- Earnest Chemists Limited DBT WBT RH Gr/lb `
Contractor:- Fabtech International Limited Summer 102 F 64% 200
Location:- Ghana Monsoon 81 F 76% 121
Equipment Load
Room Dimension Room Conditions Fresh Air Estimation Flow Estimation Ahu Specication Ahu Filtration Terminals
Estimation Dust Cooling Heating
Sr. Room Area Room Area Volume Temperatur Relative Occupanc Equipmen Diversit Final Class At Room Exfiltratio Dehumidifie Scavanging Selected Return Bleed Supply Static
AHU No.. Room Name Length Width Height Height ACPH ACPH Infiltration Exhaust Collectio Fresh Air System Type Coil Coil Fresh Air Post Bleed
No. e Humidity y t Load y Load Rest Pressure n d Air Air Air Air Air Air Pressure Pre Filter Supply Return
n Filter Filter Filter
Mt Mt Mt Ft Mt Sq.ft Mt C % Hp % HP Pascal CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM MM TR KW
16.70 8.01 7.8 25.58
1 Finished Goods Store 155.43 1672.39 1212.32 232C NMT 60 0 70 0 3 2 0 0 0 0 1990 1426 1990 1990 Jet Diffuser Grille
6.05 3.57 7.8 25.58
Filtered
14.72 9.18 7.8 25.58
2 AHU-33 Finished Goods Quarantine 152.53 1641.23 1189.74 232C NMT 60 0 70 0 Unclassifie 3 2 0 0 0 0 500 1953 1400 1953 1953 500 5191 80 Recirculation 12.16 7.00 G-4 F-5 F-8 F-8 Jet Diffuser Grille
5.46 3.18 7.8 25.58
d
5.08 10.07 7.8 25.58
3 Transition Zone 58.42 628.60 455.68 232C NMT 60 2 0 70 0 3 2 0 0 0 0 748 536 748 748 Jet Diffuser Grille
2.10 3.49 7.8 25.58

Total 366.38 2857.74 0 0.00 0 0 0 500 4691 3362 4691 4691 500 5191 12.16 7.00

1 Sampling Room 1 Man Airlock 1.97 1.23 3.0 9.84 2.41 25.98 7.24 222C NMT 55 0 70 0.0 Class D 25 68 20 0 290 0 231 290 290 0 Hepa Hepa Box
2 AHU-34 Sampling Room 1 Material Airlock 1.97 1.82 3.0 9.84 3.60 38.68 10.79 222C NMT 55 0 70 0.0 Class D 25 72 20 0 454 0 400 344 457 457 3 28 1965 125 Recirculation 7.57 6.00 G-4 F-5 F-8 H-12 Hepa Hepa Box
3 Sampling Room 1 3.84 3.10 3.0 9.84 11.91 128.18 35.74 222C NMT 55 2 2 70 1.1 Class D 25 25 5 372 0 0 1190 526 1190 1562 Hepa Riser

Total 17.92 53.77 2 1.05 372 744 0 400 1765 1937 1565 28 1965 7.57 6.00

1 Sampling Room 2 Material Airlock 1.97 1.78 3.0 9.84 3.51 37.77 10.53 222C NMT 55 0 70 0.0 Class D 25 74 20 0 454 0 361 458 458 4 Hepa Hepa Box
2 AHU-35 Sampling Room 2 Man Airlock 1.97 1.23 3.0 9.84 2.42 26.02 7.26 222C NMT 55 0 70 0.0 Class D 25 68 20 0 290 0 400 249 290 290 0 28 2038 125 Recirculation 7.79 6.50 G-4 F-5 F-8 H-12 Hepa Hepa Box
3 Sampling Room 2 3.84 3.06 3.0 9.84 11.75 126.40 35.24 222C NMT 55 2 2 70 1.1 Class D 25 25 5 372 0 0 1261 518 1261 1633 Hepa Riser

Total 17.68 53.03 2 1.05 372 744 0 400 1871 1267 2010 1638 28 2038 7.79 6.50

1 Cap Storage 4.47 5.05 7.80 25.58 22.58 242.92 176.09 232C NMT 60 0 70 0 10 2 5 0 0 0 319 207 319 319 Jet Diffuser Grille
2 RM Staging Room 8.18 6.21 7.80 25.58 50.79 546.50 396.16 232C NMT 60 0 70 0 10 2 5 744 131 0 717 466 717 1330 Jet Diffuser Grille
3 RM Quarantine 15.18 5.48 7.80 25.58 83.10 894.14 648.17 232C NMT 60 0 70 0 10 2 5 0 131 0 1173 763 1173 1042 Jet Diffuser Grille
4 Empty Capsule Store 7.15 5.05 7.80 25.58 36.08 388.26 281.45 232C NMT 60 0 70 0 10 2 5 0 0 0 509 331 509 509 Jet Diffuser Grille
18.09 13.95 7.80 25.58
5 Approved RM Material Store 6.36 5.10 7.80 25.58 315.81 3398.07 2463.28 232C NMT 60 0 70 0 10 2 5 0 0 0 4458 2898 4458 4458 Jet Diffuser Grille
4.03 7.72 7.80 25.58 Filtered
AHU-36 2.53 27.30 7.80 25.58 Unclassifie 600 343 11690 80 Recirculation 22.58 17.50 G-4 F-5 F-8 F-8
6 RM Corridor 12.07 2.50 7.80 25.58 122.74 1320.69 957.38 232C NMT 60 0 70 0 d 10 2 5 0 739 0 1733 1126 1733 994 Jet Diffuser Grille
2.00 11.80 7.80 25.58
5.43 9.25 7.80 25.58
7 PVC/ALU Storage 62.16 668.88 484.88 232C NMT 60 0 70 0 10 2 5 0 0 0 878 570 878 878 Jet Diffuser Grille
3.38 3.54 7.80 25.58
8 Bottle Storage 6.49 9.25 7.80 25.58 60.00 645.65 468.04 232C NMT 60 0 70 0 10 2 5 0 0 0 847 551 847 847 Jet Diffuser Grille
9 Equiupment Wash 2 4.19 2.19 3.0 9.84 9.17 98.69 27.52 232C NMT 60 5 70 4 10 2 5 0 0 0 503 32 503 503 Diffuser Diffuser
10 PPM Dispensing 4.19 3.55 3.0 9.84 14.86 159.93 44.59 232C NMT 60 1 0 70 0 10 2 5 0 0 0 210 52 210 210 Diffuser Diffuser

Total 777.30 6955.67 5 70 4 744 1001 0 600 11347 6997 11347 11090 343 11690 22.58 17.50

1 Gents Change Room 2.45 4.71 2.8 9.18 11.54 124.17 32.31 222C NMT 55 0 0.00 70 0.00 10 10 5 84 84 0 201 190 201 201 Diffuser Diffuser
2 Registry 2.13 3.01 2.8 9.18 6.41 68.94 17.94 222C NMT 55 2 2.00 70 1.40 10 10 5 84 0 0 225 106 225 309 Diffuser Diffuser
3 Ladies Change Room 2.40 5.60 2.8 9.18 13.44 144.61 37.63 222C NMT 55 0 0.00 70 0.00 10 10 5 84 84 0 235 221 235 235 Diffuser Diffuser
4 Wet lab 7.74 4.71 2.8 9.18 36.45 392.21 102.06 222C NMT 55 4 3.00 70 2.10 10 10 5 131 0 0 806 600 806 937 Diffuser Diffuser
5 Chemical Store 2.68 4.71 2.8 9.18 12.62 135.82 35.34 222C NMT 55 1 0.50 70 0.35 10 10 5 84 0 0 249 208 249 333 Diffuser Diffuser
6 Glass Ware Store 3.40 4.71 2.8 9.18 16.01 172.31 44.84 222C NMT 55 0 0.00 70 0.00 10 10 5 84 0 0 280 264 280 364 Diffuser Diffuser
7 QC Staff & Documents 4.00 4.71 2.8 9.18 18.85 202.82 52.78 222C NMT 55 6 2.50 70 1.75 10 10 5 84 0 0 470 310 470 554 Diffuser Diffuser
8 Stability 5.00 4.71 2.8 9.18 23.55 253.40 65.94 222C NMT 55 1 8.00 70 5.60 10 10 5 131 0 0 863 388 863 994 Diffuser Diffuser
9 Wash & Deactivation Room 2.92 4.71 2.8 9.18 13.75 147.98 38.51 222C NMT 55 1 1.00 70 0.70 10 10 5 84 0 0 297 227 297 381 Diffuser Diffuser
2.95 1.20 2.8 9.18 0 0.00 70 0.00 Diffuser Diffuser
Filtered
10 AHU-37 Incubation 4.05 4.40 2.8 9.18 24.65 265.19 69.01 222C NMT 55 1 4.00 70 2.80 10 10 10 0 84 0 656 406 656 572 Diffuser Diffuser
Unclassifie 900 9 9266 80 Recirculation 24 17 G-4 F-5 F-8 F-8
2.77 1.19 2.8 9.18 0 0.00 70 0.00 Diffuser Diffuser
d
11 Incubation Airlock 1.20 1.12 2.8 9.18 1.34 14.45 3.76 222C NMT 55 0 0.00 70 0.00 10 10 5 168 0 0 23 22 23 191 Diffuser Diffuser
12 Instruments 2 6.10 5.60 2.8 9.18 34.13 367.23 95.56 222C NMT 55 0 3.00 70 2.10 10 10 5 84 0 0 765 562 765 849 Diffuser Diffuser
13 Instruments 1 7.00 5.60 2.8 9.18 39.17 421.42 109.66 222C NMT 55 0 0.50 70 0.35 10 10 5 84 0 0 712 645 712 796 Diffuser Diffuser
14 QC Manager 3.20 5.60 2.8 9.18 17.90 192.65 50.13 222C NMT 55 2 0.25 70 0.18 10 10 5 84 0 0 327 295 327 411 Diffuser Diffuser
15 QA Manager 2.42 5.60 2.8 9.18 13.54 145.69 37.91 222C NMT 55 2 0.25 70 0.18 10 10 5 84 0 0 250 223 250 334 Diffuser Diffuser
2.02 34.48 2.8 9.18 222C NMT 55 0 0.00 70 0.00 10 10 0 Diffuser Diffuser
17 Common Corridor 2.00 6.81 2.8 9.18 84.88 913.36 237.68 222C NMT 55 0 0.00 70 0.00 10 10 10 435 1670 0 1482 1398 1482 247 Diffuser Diffuser
1.34 1.20 2.8 9.18 222C NMT 55 0 0.00 70 0.00 10 10 0 Diffuser Diffuser
18 Control Samples 8.08 5.60 2.8 9.18 45.21 486.43 126.58 222C NMT 55 1 0.00 70 0.00 10 10 5 0 131 0 789 745 789 658 Diffuser Diffuser
19 Hot Zone 3.50 4.71 2.8 9.18 16.49 177.38 46.16 222C NMT 56 2 6.00 70 4.20 10 10 5 84 0 711 627 272 626.93 0 Diffuser Diffuser

TOTAL 429.93 1301.03 31 21.70 1873 2053 900 9257 7081 9257 8366 9266 24.30 16.70

3.93 4.40 2.8 9.18


1 Media Prepration 20.52 220.83 57.47 222C NMT 55 1 3 70 2.1 CLASS D 25 25 30 0 84 0 763 845 845 761 Hepa Riser
AHU-38 2.73 1.19 2.8 9.18 150 912 125 Recirculation 3.00 1.60 G-4 F-5 F-8 F-8
2 Media Prepration Airlock 1.12 1.13 2.8 9.18 1.26 13.56 3.53 222C NMT 55 0 0.00 70 0.00 CLASS D 25 30 25 84 145 0 40 62 62 1 Hepa Riser

TOTAL 21.78 60.99 3 2.10 84 229 150 803 907 907 762 912 3.00 1.60

1 MLT Room 3.30 3.78 2.8 9.18 12.44 133.84 34.83 222C NMT 55 1 8 70 5.6 CLASS C 40 40 50 0 168 0 973 819 973 805 Hepa Riser
2 Airlock 3 2.18 1.42 2.8 9.18 3.09 33.23 8.65 222C NMT 55 0 70 0.0 CLASS C 40 40 45 84 119 0 158 203 203 168 Hepa Hepa Box
3 AHU-39 Airlock 2 2.18 1.42 2.8 9.18 3.09 33.23 8.65 222C NMT 55 0 70 0.0 CLASS C 40 40 35 119 119 0 250 158 203 203 203 1806 125 Recirculation 5.43 4.30 G-4 F-5 F-8 F-8 Hepa Hepa Box
4 Airlock 1 1.67 1.46 2.8 9.18 2.44 26.24 6.83 222C NMT 55 0 70 0.0 CLASS C 40 40 25 286 145 0 125 161 161 302 Hepa Hepa Box
5 Return Airlock 1.67 1.46 2.8 9.18 2.44 26.24 6.83 222C NMT 55 0 70 0.0 CLASS C 40 40 45 84 167 0 125 161 161 78 Hepa Hepa Box

TOTAL 23.49 65.78 8 5.60 573 718 250 1539 1548 1701 1556 1806 5.43 4.30

1 Media Storage 2.88 3.13 2.8 9.18 8.99 96.77 25.18 222C NMT 55 0 4.00 70 2.80 CLASS D 25 25 30 0 84 0 508 370 508 424 Hepa Hepa Box
AHU-40 150 581 125 Recirculation 2.70 2.20 G-4 F-5 F-8 F-8
2 Media Storage Airlock 1.45 1.12 2.8 9.18 1.63 17.51 4.56 222C NMT 55 0 0.00 70 0.00 CLASS D 25 25 25 84 145 0 69 67 69 8 Hepa Hepa Box

TOTAL 10.62 29.74 4 2.80 84 229 150 576 576 431 581 2.70 2.20

2.75 4.70 3.00 9.84


1 Workmen Entry & Corridor 98.61 1060.99 295.82 0.00 70 0.00 10 10 NA NA NA NA NA NA 1740 1740 Diffuser Diffuser
2.40 35.70 3.00 9.84
2 Tiffin Storage 2.75 1.93 3.00 9.84 5.29 56.96 15.88 0.00 70 0.00 10 10 NA NA NA NA NA NA 93 93 Diffuser Diffuser
3 Ladies Staff Shoe Rack 2.40 5.42 3.00 9.84 13.00 139.84 38.99 0.00 70 0.00 10 10 NA NA NA NA NA NA 229 229 Diffuser Diffuser
4 Ladies Staff Change Room 3.20 5.42 3.00 9.84 17.33 186.45 51.98 0.00 70 0.00 10 10 NA NA NA NA NA NA 306 306 Diffuser Diffuser
5 Linen Room 1 2.35 2.94 3.00 9.84 6.90 74.21 20.69 0.00 70 0.00 10 10 NA NA NA NA NA NA 122 122 Diffuser Diffuser
6 Linen Room 2 2.35 2.80 3.00 9.84 6.58 70.80 19.74 0.00 70 0.00 10 10 NA NA NA NA NA NA 116 116 Diffuser Diffuser
Filtered
7 Gents Staff Shoe Rack 2.35 5.42 3.00 9.84 12.73 136.92 38.18 0.00 70 0.00 10 10 NA NA NA NA NA NA 225 225 Diffuser Diffuser
VENTILATION-01 Ambient Ambient Unclassifie 5000 NA NA 5000 65 ONCE THROUGH NA NA G-4 F-8 NA
8 Gents Staff Change Room 3.20 5.42 3.00 9.84 17.33 186.45 51.98 0.00 70 0.00 10 10 NA NA NA NA NA NA 306 306 Diffuser Diffuser
d
9 Visitor Change 2.63 5.47 3.00 9.84 14.36 154.47 43.07 0.00 70 0.00 10 10 NA NA NA NA NA NA 253 253 Diffuser Diffuser
10 Ladies Workers Shoe Rack 2.45 5.40 3.00 9.84 13.25 142.59 39.75 0.00 70 0.00 10 10 NA NA NA NA NA NA 234 234 Diffuser Diffuser
11 Ladies Worker Change Room 4.35 5.42 3.00 9.84 23.58 253.69 70.73 0.00 70 0.00 10 10 NA NA NA NA NA NA 416 416 Diffuser Diffuser
12 Gents Worker Shoe Rack 2.35 5.42 3.00 9.84 12.73 136.92 38.18 0.00 70 0.00 10 10 NA NA NA NA NA NA 225 225 Diffuser Diffuser
13 Housekeeping to Canteen 1.45 2.57 3.00 9.84 3.72 40.03 11.16 0.00 70 0.00 10 10 NA NA NA NA NA NA 66 66 Diffuser Diffuser
14 Housekeeping to Packing 1.45 2.63 3.00 9.84 3.82 41.06 11.45 0.00 70 0.00 10 10 NA NA NA NA NA NA 67 67 Diffuser Diffuser
15 Gents Worker Change Room 5.05 5.42 3.00 9.84 27.35 294.24 82.04 0.00 70 0.00 10 10 NA NA NA NA NA NA 483 483 Diffuser Diffuser

TOTAL 276.55 2975.63 1086.68 0.00 0.00 0 0 5000 0 4880 4880 0 5000

1 Ladies Toilet Staff 4.20 2.81 3.00 9.84 11.81 127.08 35.43 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 208 208 Diffuser
2 Toilet1 1.20 1.70 3.00 9.84 2.04 21.95 6.12 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 36 36 Diffuser
3 Toilet2 1.20 1.70 3.00 9.84 2.04 21.95 6.12 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 36 36 Diffuser
4 Toilet3 1.20 1.70 3.00 9.84 2.04 21.95 6.12 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 36 36 Diffuser
5 Wash 1.65 1.70 3.00 9.84 2.81 30.18 8.42 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 49 49 Diffuser
6 Ladied Toilet 5.48 2.81 3.00 9.84 15.42 165.93 46.26 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 272 272 Diffuser
7 Toilet1 1.18 1.70 3.00 9.84 2.01 21.58 6.02 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 35 35 Diffuser
8 Toilet2 1.20 1.70 3.00 9.84 2.04 21.95 6.12 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 36 36 Diffuser
9 Wash 1.67 1.70 3.00 9.84 2.84 30.55 8.52 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 50 50 Diffuser
10 Gents Toilet 6.53 2.81 3.00 9.84 18.35 197.49 55.06 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 324 324 Diffuser
NA
11 VENTILATION-02 Toilet1 1.20 1.70 3.00 9.84 2.04 21.95 6.12 Ambient Ambient 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 36 36 2000 NA NA 25 100 % EXHAUST NA NA NA NA NA NA NA Diffuser
12 Toilet2 1.20 1.70 3.00 9.84 2.04 21.95 6.12 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 36 36 Diffuser
13 Toilet3 1.20 1.70 3.00 9.84 2.04 21.95 6.12 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 36 36 Diffuser
14 Toilet4 1.20 1.70 3.00 9.84 2.04 21.95 6.12 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 36 36 Diffuser
15 Wash 1.50 1.70 3.00 9.84 2.55 27.44 7.65 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 45 45 Diffuser
16 Gents Staff Toilet 4.55 2.81 3.00 9.84 12.79 137.67 38.38 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 226 226 Diffuser
17 Toilet1 1.20 1.70 3.00 9.84 2.04 21.95 6.12 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 36 36 Diffuser
18 Toilet2 1.20 1.70 3.00 9.84 2.04 21.95 6.12 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 36 36 Diffuser
19 Wash 2.00 1.70 3.00 9.84 3.40 36.58 10.20 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 60 60 Diffuser
20 Visitor Toilet 2.11 2.81 3.00 9.84 5.93 63.81 17.79 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 105 105 Diffuser
21 Toilet1 2.10 1.70 3.00 9.84 3.57 38.41 10.71 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 63 63 Diffuser
3.28 10.76
Date- 22.10.2014 - Rev-00 Ambient Conditions
Client:- Earnest Chemists Limited DBT WBT RH Gr/lb `
Contractor:- Fabtech International Limited Summer 102 F 64% 200
Location:- Ghana Monsoon 81 F 76% 121
Equipment Load
Room Dimension Room Conditions Fresh Air Estimation Flow Estimation Ahu Specication Ahu Filtration Terminals
Estimation Dust Cooling Heating
Sr. Room Area Room Area Volume Temperatur Relative Occupanc Equipmen Diversit Final Class At Room Exfiltratio Dehumidifie Scavanging Selected Return Bleed Supply Static
AHU No.. Room Name Length Width Height Height ACPH ACPH Infiltration Exhaust Collectio Fresh Air System Type Coil Coil Fresh Air Post Bleed
No. e Humidity y t Load y Load Rest Pressure n d Air Air Air Air Air Air Pressure Pre Filter Supply Return
n Filter Filter Filter
Mt Mt Mt Ft Mt Sq.ft Mt C % Hp % HP Pascal CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM MM TR KW
TOTAL 101.88 305.64 0.00 0.00 0 0 0 0 1798 1798 2000 0
3.28 10.76
Date- 22.10.2014 - Rev-00 Ambient Conditions
Client:- Earnest Chemists Limited DBT WBT RH Gr/lb `
Contractor:- Fabtech International Limited Summer 102 F 64% 200
Location:- Ghana Monsoon 81 F 76% 121
Equipment Load
Room Dimension Room Conditions Fresh Air Estimation Flow Estimation Ahu Specication Ahu Filtration Terminals
Estimation Dust Cooling Heating
Sr. Room Area Room Area Volume Temperatur Relative Occupanc Equipmen Diversit Final Class At Room Exfiltratio Dehumidifie Scavanging Selected Return Bleed Supply Static
AHU No.. Room Name Length Width Height Height ACPH ACPH Infiltration Exhaust Collectio Fresh Air System Type Coil Coil Fresh Air Post Bleed
No. e Humidity y t Load y Load Rest Pressure n d Air Air Air Air Air Air Pressure Pre Filter Supply Return
n Filter Filter Filter
Mt Mt Mt Ft Mt Sq.ft Mt C % Hp % HP Pascal CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM MM TR KW
16.68 5.20 7.80 25.58 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 5578 5578
1 Secondary Packing Material Store 121.57 1308.05 948.21 Jet Diffuser Grille
6.70 5.20 7.80 25.58 NA NA NA NA NA NA 0 0
2 Secondary Packing Material Quarantine 6.00 9.64 7.80 25.58 57.82 622.16 451.01 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 2653 2653 Jet Diffuser Grille
3 Dedusting Room 2 FG/SPM 4.50 3.08 7.80 25.58 13.87 149.28 108.21 2 0.70 70 0.49 10 10 NA NA NA NA NA NA NA 637 637 Jet Diffuser Grille
4 Dedusting Room 1 RM/PPM 4.50 3.00 7.80 25.58 13.50 145.21 105.26 2 0.70 70 0.49 Filtered 10 10 NA NA NA NA NA NA NA 619 619 Jet Diffuser Grille
5 VENTILATION-03 Rejected Material Store 3.45 5.55 7.80 25.58 19.15 206.03 149.35 Ambient Ambient 0.00 70 0.00 Unclassifie 10 10 NA NA NA NA NA NA NA 878 878 NA NA 17500 65 ONCE THROUGH NA NA G-4 F-8 NA Jet Diffuser Grille
6 Overprinting Room 5.95 5.18 7.80 25.58 30.83 331.70 240.45 2 0.00 70 0.00 d 10 10 NA NA NA NA NA NA NA 1414 1414 Jet Diffuser Grille
2.10 30.00 7.80 25.58
7 SPM Corridor 2.20 16.70 7.80 25.58 114.54 1232.45 893.41 0.00 70 0 10 10 NA NA NA NA NA NA NA 5255 5255 Jet Diffuser Grille
2.00 7.40 7.80 25.58
8 Bottle decartoning 5.90 3.90 3.00 9.84 23.01 247.59 69.03 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 406 406 Diffuser Diffuser

TOTAL 394.28 2964.94 1.40 0.98 0 0 0 0 17440 17440 0 17500

Filtered
1 Airlock for Dining Area 2.75 2.58 3.00 9.84 7.10 76.34 21.29 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 125 125 Diffuser Diffuser
VENTILATION-04 Dinning Hall, Hand Wash, Dish Wash, Food Ambient Ambient Unclassifie NA NA 2500 65 ONCE THROUGH NA NA G-4 F-8 NA
2 10.35 12.72 3.00 9.84 131.69 1417.02 395.08 40 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 2324 2324 Diffuser Diffuser
Serving d

TOTAL 138.79 416.37 0.00 0.00 0 0 0 0 2449 2449 0 2500

1 Ladies Toilet Staff 2.11 2.81 2.80 9.18 5.93 63.81 16.61 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 98 98 Diffuser
2 Toilet1 2.10 1.70 2.80 9.18 3.57 38.41 10.00 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 59 59 Diffuser
3 Gents Toilet 4.55 2.81 2.80 9.18 12.79 137.67 35.82 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 211 211 Diffuser
VENTILATION-05 Ambient Ambient NA 500 NA NA 25 100 % EXHAUST NA NA NA NA NA NA NA
4 Toilet1 1.18 1.70 2.80 9.18 2.01 21.58 5.62 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 33 33 Diffuser
5 Toilet2 1.20 1.70 2.80 9.18 2.04 21.95 5.71 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 34 34 Diffuser
6 Wash 2.00 1.70 2.80 9.18 3.40 36.58 9.52 0.00 70 0.00 10 10 NA NA NA NA NA NA NA 56 56 Diffuser

TOTAL 29.74 83.28 0.00 0.00 0 0 0 0 490 490 500 0

1 VENTILATION-06 Hot Zone 3.50 4.71 2.80 9.18 16.49 177.38 46.16 Ambient Ambient 8.00 70 5.60 NA 10 10 NA NA NA NA NA NA NA 600 600 600 NA NA 25 100 % EXHAUST NA NA NA NA NA NA NA Diffuser

TOTAL 16.49 46.16 8.00 5.60 0 0 0 0 600 600 600 0

1 VENTILATION-07 Technical Area for AHUs 51.30 57.50 5.00 16.40 2949.75 31739.3 ### Ambient Ambient 3 506.00 70 354.20 NA 5 5 NA NA NA NA NA NA NA 45000 NA NA 45000 25 ONCE THROUGH NA NA G-4 NA NA NA NA

TOTAL 2949.75 ### 506.00 354.20 0 0 0 0 45000 0 45000

1 SPILT AC Recall Material Store 4.00 5.09 3.00 9.84 20.38 219.2 61.13 242C NMT 55 NA NA NA NA NA NA NA NA NA NA NA NA 398 NA 398 398 NA 398 NA HI-WALL 1.00 NA NA NA NA NA NA NA

2 SPILT AC Stronge Room 3.39 3.11 3.00 9.84 10.55 113.5 31.64 242C NMT 55 NA NA NA NA NA NA NA NA NA NA NA NA 230 NA 230 230 NA 230 NA HI-WALL 1.00 NA NA NA NA NA NA NA

3 SPILT AC FG Office 4.00 4.01 3.00 9.84 16.04 172.6 48.12 242C NMT 55 2 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 371 NA 371 371 NA 371 NA HI-WALL 1.00 NA NA NA NA NA NA NA

4 SPILT AC RM Office 4.03 3.45 3.00 9.84 13.89 149.4 41.66 242C NMT 55 2 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 390 NA 390 390 NA 390 NA HI-WALL 1.00 NA NA NA NA NA NA NA

5 SPILT AC Reception & Stair Case 2.63 5.47 3.00 9.84 14.36 154.5 43.07 242C NMT 55 70 0.00 NA NA NA NA NA NA NA NA NA 405 NA 405 405 NA 405 NA HI-WALL 1.00 NA NA NA NA NA NA NA

6 SPILT AC Discussion Room 1 3.14 3.50 2.8 9.18 10.97 118.1 30.72 242C NMT 55 2 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 276 NA 276 276 NA 276 NA HI-WALL 1.00 NA NA NA NA NA NA NA

7 SPILT AC Discussion Room 2 3.25 3.50 2.8 9.18 11.37 122.4 31.84 242C NMT 55 2 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 288 NA 288 288 NA 288 NA HI-WALL 1.00 NA NA NA NA NA NA NA

8 SPILT AC Conference ( 2 SPILT AC ) 10.39 5.90 2.8 9.18 61.28 659.3 171.58 242C NMT 55 16 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 874 NA 874 874 NA 874 NA HI-WALL 1.74 NA NA NA NA NA NA NA

9 SPILT AC Director Office 3.90 5.90 2.8 9.18 23.01 247.6 64.43 242C NMT 55 1 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 396 NA 396 396 NA 396 NA HI-WALL 1.00 NA NA NA NA NA NA NA

10 SPILT AC Secretory Office 3.90 5.90 2.8 9.18 23.01 247.6 64.43 242C NMT 55 2 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 420 NA 420 420 NA 420 NA HI-WALL 1.00 NA NA NA NA NA NA NA

11 SPILT AC Accounts Office 3.90 5.90 2.8 9.18 23.01 247.6 64.43 242C NMT 55 2 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 521 NA 521 521 NA 521 NA HI-WALL 1.00 NA NA NA NA NA NA NA

12 SPILT AC Business Development 3.90 5.90 2.8 9.18 23.01 247.6 64.43 242C NMT 55 2 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 521 NA 521 521 NA 521 NA HI-WALL 1.00 NA NA NA NA NA NA NA

13 SPILT AC HR 3.90 5.90 2.8 9.18 23.01 247.6 64.43 242C NMT 55 2 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 521 NA 521 521 NA 521 NA HI-WALL 1.00 NA NA NA NA NA NA NA

14 SPILT AC Admin 3.93 4.57 2.8 9.18 17.95 193.1 50.26 242C NMT 55 2 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 473 NA 473 473 NA 473 NA HI-WALL 1.00 NA NA NA NA NA NA NA

15 SPILT AC QA Director 3.93 4.57 2.8 9.18 17.95 193.1 50.26 242C NMT 55 1 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 473 NA 473 473 NA 473 NA HI-WALL 1.00 NA NA NA NA NA NA NA

16 SPILT AC QA Office 3.93 4.57 2.8 9.18 17.95 193.1 50.26 242C NMT 55 2 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 473 NA 473 473 NA 473 NA HI-WALL 1.00 NA NA NA NA NA NA NA

17 SPILT AC Documentation Room 3.93 4.57 2.8 9.18 17.95 193.1 50.26 242C NMT 55 1 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 473 NA 473 473 NA 473 NA HI-WALL 1.00 NA NA NA NA NA NA NA

18 SPILT AC Spare Office 1 3.90 5.90 2.8 9.18 23.01 247.6 64.43 242C NMT 55 2 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 521 NA 521 521 NA 521 NA HI-WALL 1.00 NA NA NA NA NA NA NA

19 SPILT AC Spare Office 2 3.90 5.90 2.8 9.18 23.01 247.6 64.43 242C NMT 55 2 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 521 NA 521 521 NA 521 NA HI-WALL 1.00 NA NA NA NA NA NA NA

20 SPILT AC Spare Office 3 3.08 5.90 2.8 9.18 18.17 195.5 50.87 242C NMT 55 2 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 533 NA 533 533 NA 533 NA HI-WALL 1.00 NA NA NA NA NA NA NA

21 SPILT AC Waiting Room ( 2 SPILT AC ) 6.46 9.14 2.8 9.18 59.04 635.3 165.32 242C NMT 55 3 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 1030 NA 1030 1030 NA 1030 NA HI-WALL 1.40 NA NA NA NA NA NA NA

22 SPILT AC IT Room 3.93 4.57 2.8 9.18 17.95 193.1 50.26 242C NMT 55 1 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 473 NA 473 473 NA 473 NA HI-WALL 1.00 NA NA NA NA NA NA NA

23 SPILT AC Server Room ( 1 WORKING + 1 STAND BY ) 3.08 4.57 2.8 9.18 14.08 151.5 39.42 242C NMT 55 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 479 NA 479 479 NA 479 NA HI-WALL 1.00 NA NA NA NA NA NA NA

24 SPILT AC Training Room ( 3 SPILT AC ) 6.61 8.29 2.8 9.18 54.76 589.3 153.34 242C NMT 55 1.00 70 0.70 NA NA NA NA NA NA NA NA NA 1310 NA 1310 1310 NA 1310 NA HI-WALL 2.24 NA NA NA NA NA NA NA

DUCTABLE SPILT
25 SPILT AC RO Plant & Distribution Room 19.59 10.00 5 16.40 195.90 2107.9 979.50 242C NMT 55 2 15.00 70 10.50 NA NA NA NA NA NA NA NA NA 5625 NA 5625 5625 NA 5625 NA 7.05 NA NA NA NA NA NA NA
AC
CFM DISTRIBUTION FOR ERNEST,GHANA

AHU - 01
Total Area in sq.ft. 306.8
Total TR 6.38
Dehumidified CFM 1417
Total equipmentt load(H.P.) 3.50
Room TR 5.64
TR / sq.ft 54.38
CFM / TR 222.02
Total equipment TR 0.74
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
1 Active Dispensing 205.80 9.84 2025.09 25 3.78 1.00 5.00 70.00 3.50 0.74 4.53 1005 844 1005
2 Common Airlock for Dispensing 100.99 9.84 993.70 26 1.86 0.00 0.00 70.00 0.00 0.00 1.86 412 431 431

TOTAL 306.79 3018.79 5.64 1.00 5.00 3.50 0.74 6.38 1417 1274 1436 0.00 0.00 0.00 0.00

AHU - 2
Total Area in sq.ft. 269.97
Total TR 2.89
Dehumidified CFM 960
Total equipmentt load(H.P.) 3.50
Room TR 2.15
TR / sq.ft 125.74
CFM / TR 332.38
Total equipment TR 0.74
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
3 Excipient Dispensing 269.97 9.84 2656.52 25 2.15 1.00 5.00 70.00 3.50 0.74 2.89 960 1107 1107

TOTAL 269.97 2656.52 2.15 1.00 5.00 3.50 0.74 2.89 960.39 1106.88 1106.88 0.00 0.00 0.00 0.00

AHU - 3
Total Area in sq.ft. 255.69
Total TR 8.29
Dehumidified CFM 1845
Total equipmentt load(H.P.) 3.50
Room TR 7.55
TR / sq.ft 33.87
CFM / TR 222.52
Total equipment TR 0.74
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
4 Sifting 1 183 13.12 2403.88 25 5.41 1.00 5.00 70.00 3.50 0.74 6.15 1369 1002 1369
5 Sifting 1 Material Airlock 43 9.84 421.55 53 1.26 0.00 0.00 70.00 0.00 0.00 1.26 281 372 372
6 Sifting 1 Man Airlock 30 9.84 291.51 50 0.87 0.00 0.00 70.00 0.00 0.00 0.87 195 243 243

TOTAL 255.69 3116.95 7.55 1.00 5.00 3.50 0.74 8.29 1845.10 1616.92 1984.28 0.00 0.00 0.00 0.00

AHU - 4
Total Area in sq.ft. 1276.81
Total TR 24.81
Dehumidified CFM 8795
Total equipmentt load(H.P.) 37.50
Room TR 16.86
TR / sq.ft 75.73
CFM / TR 354.42
Total equipment TR 7.95
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
7 Wet Granulation 1 1196.65 16.40 19625.11 25 15.80 4.00 75.00 50.00 37.50 7.95 23.76 8420 8177 8420

8 Wet Granulation 1 Material Airlock 48.54 9.84 477.59 51 0.64 0.00 0.00 70.00 0.00 0.00 0.64 227 406 406
9 Wet Granulation 1 Man Airlock 31.62 9.84 311.18 46 0.42 0.00 0.00 70.00 0.00 0.00 0.42 148 239 239

TOTAL 1276.81 20413.88 16.86 4.00 75.00 37.50 7.95 24.81 8794.71 8821.65 9064.05 0.00 0.00 0.00 0.00

AHU - 5
Total Area in sq.ft. 1021.61
Total TR 17.63
Dehumidified CFM 6097
Total equipmentt load(H.P.) 25.00
Room TR 12.33
TR / sq.ft 82.86
CFM / TR 345.79
Total equipment TR 5.30
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
10 Wet Granulation 2 950.35 14.76 14027.21 25 11.47 4.00 50.00 50.00 25.00 5.30 16.77 5799 5845 5845

11 Wet Granulation 2 Material Airlock 42.22 9.84 415.44 55 0.51 0.00 0.00 70.00 0.00 0.00 0.51 176 381 381
12 Wet Granulation 2 Man Airlock 29.03 9.84 285.69 52 0.35 0.00 0.00 70.00 0.00 0.00 0.35 121 248 248

TOTAL 1021.61 14728.33 12.33 4.00 50.00 25.00 5.30 17.63 6096.56 6473.08 6473.08 0.00 0.00 0.00 0.00

AHU - 6
Total Area in sq.ft. 5585.70
Total TR 47.06
Dehumidified CFM 11925
Total equipmentt load(H.P.) 9.10
Room TR 45.13
TR / sq.ft 123.78
CFM / TR 253.41
Total equipment TR 1.93
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
13 Dispensed Material Store 551.37 9.84 5425.47 25 4.45 0.00 0.00 70.00 0.00 0.00 4.45 1129 2261 2261
14 Process Corridor 2611.72 9.84 25699.33 25 21.10 0.00 0.00 70.00 0.00 0.00 21.10 5347 10708 10708
0.00 0.00 9.84 0.00 0 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
0.00 0.00 9.84 0.00 0 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
0.00 0.00 9.84 0.00 0 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
15 Used Equipments 288.39 9.84 2837.81 25 2.33 0.00 0.00 70.00 0.00 0.00 2.33 590 1182 1182
16 Cleaned Equipments 122.04 9.84 1200.86 27 0.99 0.00 0.00 70.00 0.00 0.00 0.99 250 540 540
17 Production Office 1 137.04 9.84 1348.43 25 1.11 3.00 0.00 70.00 0.00 0.00 1.11 281 562 562
18 IPQC 1 138.21 9.84 1360.01 25 1.12 4.00 2.00 70.00 1.40 0.30 1.41 358 567 567
19 Blend Store 494.01 9.84 4861.08 25 3.99 0.00 0.00 70.00 0.00 0.00 3.99 1011 2025 2025
20 House Keeping 60.45 9.84 594.84 25 0.49 0.00 0.00 70.00 0.00 0.00 0.49 124 248 248
21 Production Manager 88.49 9.84 870.74 25 0.71 2.00 1.00 70.00 0.70 0.15 0.86 219 363 363
22 Common Corridor for Tablet compression 385.80 9.84 3796.27 25 3.12 0.00 0.00 70.00 0.00 0.00 3.12 790 1582 1582
23 Uncoated Tablets 304.11 9.84 2992.44 25 2.46 0.00 0.00 70.00 0.00 0.00 2.46 623 1247 1247
24 Equipment Wash 1 250.20 9.84 2461.94 25 2.02 2.00 5.00 70.00 3.50 0.74 2.76 700 1026 1026
25 Equipment Drying 1 153.87 9.84 1514.13 25 1.24 1.00 5.00 70.00 3.50 0.74 1.99 503 631 631

TOTAL 5585.70 54963.33 45.13 12.00 13.00 9.10 1.93 47.06 ### ### 22941.42 0.00 0.00 0.00 0.00

AHU - 6A
Total Area in sq.ft. 3923.15
Total TR 34.07
Dehumidified CFM 8926
Total equipmentt load(H.P.) 8.40
Room TR 32.29
TR / sq.ft 121.50
CFM / TR 261.98
Total equipment TR 1.78
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
26 Equipment Storage 214 9.84 2108.30 25 1.76 0.00 0.00 70.00 0.00 0.00 1.76 462 878 878
27 Production Office 2 100 9.84 983.92 25 0.82 3.00 0.00 70.00 0.00 0.00 0.82 216 410 410
28 IPQC 2 99 9.84 975.54 25 0.82 3.00 3.00 70.00 2.10 0.45 1.26 330 406 406
29 Coated tablets Storage 564 9.84 5552.96 25 4.64 0.00 0.00 70.00 0.00 0.00 4.64 1217 2314 2314
30 Dies & Punches Room 154 9.84 1511.71 25 1.26 0.00 0.00 70.00 0.00 0.00 1.26 331 630 630
31 Tool Room 129 9.84 1265.23 25 1.06 0.00 0.00 70.00 0.00 0.00 1.06 277 527 527
32 Equipment Wash 2 223 9.84 2198.26 25 1.84 3.00 3.00 70.00 2.10 0.45 2.28 598 916 916
34 Equipment Drying 2 156 9.84 1530.47 25 1.28 1.00 3.00 70.00 2.10 0.45 1.73 452 638 638
35 PPM Day Store 226 9.84 2227.14 25 1.86 0.00 3.00 70.00 2.10 0.45 2.31 605 928 928
36 ALU/PVC Store Room 102 9.84 1004.68 25 0.84 0.00 0.00 70.00 0.00 0.00 0.84 220 419 419
37 Process Corridor 1956 9.84 19245.60 25 16.10 0.00 0.00 70.00 0.00 0.00 16.10 4217 8019 8019
0.00 0 0.00 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0
0.00 0 0.00 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0
0.00 0 0.00 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 3923.15 38603.81 32.29 10.00 12.00 8.40 1.78 34.07 8925.73 ### 16084.92 0.00 0.00 0.00

AHU - 7
Total Area in sq.ft. 502.72 46.72073
Total TR 9.54
Dehumidified CFM 2567 20.73405
Total equipmentt load(H.P.) 10.50
Room TR 7.31
TR / sq.ft 68.77
CFM / TR 269.18
Total equipment TR 2.23
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
38 Dry Granulation 445 13.12 5839.01 25 6.47 2.00 15.00 70.00 10.50 2.23 8.70 2341 2433 2433
0.00 0 0.00 0.00 25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
39 Dry Granulation Material Airlock 36 9.84 351.41 64 0.52 0.00 0.00 70.00 0.00 0.00 0.52 140 375 375
40 Dry Granulation Man Airlock 22 9.84 216.05 66 0.32 0.00 0.00 70.00 0.00 0.00 0.32 86 238 238

TOTAL 502.72 6406.47 7.31 2.00 15.00 10.50 2.23 9.54 2567.06 3045.41 3045.41 0.00 0.00 0.00

AHU - 8
Total Area in sq.ft. 307.10
Total TR 8.44
Dehumidified CFM 1915
Total equipmentt load(H.P.) 7.00
Room TR 6.95
TR / sq.ft 44.16
CFM / TR 226.98
Total equipment TR 1.48
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
41 Tablet Compression 1 251.68 14.76 3714.87 25 5.70 2.00 10.00 70.00 7.00 1.48 7.18 1631 1548 1631
0.00 0.00 0.00 0.00 25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
42 Tablet Compression 1 Material Airlock 32.36 9.84 318.44 70 0.73 0.00 0.00 70.00 0.00 0.00 0.73 166 372 372
43 Tablet Compression 1 Man Airlock 23.05 9.84 226.83 63 0.52 0.00 0.00 70.00 0.00 0.00 0.52 118 238 238

TOTAL 307.10 4260.14 6.95 2.00 10.00 7.00 1.48 8.44 1915.42 2157.55 2240.29 0.00 0.00 0.00

AHU - 9
Total Area in sq.ft. 311.84
Total TR 8.46
Dehumidified CFM 1925
Total equipmentt load(H.P.) 7.00
Room TR 6.97
TR / sq.ft 44.73
CFM / TR 227.63
Total equipment TR 1.48
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
44 Tablet compression 2 256.06 14.76 3779.46 25 5.72 2.00 10.00 70.00 7.00 1.48 7.21 1641 1575 1641
0.00 0.00 0.00 0.00 25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
45 Tablet compression 2 Material Airlock 32.58 9.84 320.57 70 0.73 0.00 0.00 70.00 0.00 0.00 0.73 166 374 374
46 Tablet compression 2 Man Airlock 23.21 9.84 228.35 63 0.52 0.00 0.00 70.00 0.00 0.00 0.52 118 240 240

TOTAL 311.84 4328.37 6.97 2.00 10.00 7.00 1.48 8.46 1924.85 2188.53 2254.73 0.00 0.00 0.00

AHU - 10
Total Area in sq.ft. 307.47
Total TR 8.44
Dehumidified CFM 1915
Total equipmentt load(H.P.) 7.00
Room TR 6.95
TR / sq.ft 44.22
CFM / TR 226.92
Total equipment TR 1.48
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
47 Tablet Compression 3 250.35 14.76 3695.10 25 5.66 2.00 10.00 70.00 7.00 1.48 7.15 1622 1540 1622
0.00 0.00 0.00 0.00 25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
48 Tablet compression 3 Material Airlock 33.47 9.84 329.35 68 0.76 0.00 0.00 70.00 0.00 0.00 0.76 172 373 373
49 Tablet compression 3 Man Airlock 23.65 9.84 232.74 62 0.53 0.00 0.00 70.00 0.00 0.00 0.53 121 240 240

TOTAL 307.47 4257.18 6.95 2.00 10.00 7.00 1.48 8.44 1914.66 2153.38 2235.30 0.00 0.00 0.00

AHU - 11
Total Area in sq.ft. 307.47
Total TR 8.44
Dehumidified CFM 1915
Total equipmentt load(H.P.) 7.00
Room TR 6.95
TR / sq.ft 44.22
CFM / TR 226.92
Total equipment TR 1.48
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
50 Tablet compression 4 250.35 14.76 3695.10 25 5.66 2.00 10.00 70.00 7.00 1.48 7.15 1622 1540 1622
0.00 0.00 0.00 0.00 25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
51 Tablet Compression 4 Material Airlock 33.47 9.84 329.35 68 0.76 0.00 0.00 70.00 0.00 0.00 0.76 172 373 373
52 Tablet Compression 4 Man Airlock 23.65 9.84 232.74 62 0.53 0.00 0.00 70.00 0.00 0.00 0.53 121 240 240

TOTAL 307.47 4257.18 6.95 2.00 10.00 7.00 1.48 8.44 1914.66 2153.38 2235.30 0.00 0.00 0.00

AHU - 12
Total Area in sq.ft. 279.13
Total TR 8.67
Dehumidified CFM 2055
Total equipmentt load(H.P.) 7.00
Room TR 7.19
TR / sq.ft 38.84
CFM / TR 236.95
Total equipment TR 1.48
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
53 Tablet compression Future 222.01 14.76 3276.90 25 5.72 2.00 10.00 70.00 7.00 1.48 7.20 1706 1365 1706
0.00 0.00 0.00 0.00 25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
54 Tablet Compression Future Material Airlock 33.47 9.84 329.35 68 0.86 0.00 0.00 70.00 0.00 0.00 0.86 204 373 373
55 Tablet Compression Future Man Airlock 23.65 9.84 232.74 62 0.61 0.00 0.00 70.00 0.00 0.00 0.61 144 240 240

TOTAL 279.13 3838.99 7.19 2.00 10.00 7.00 1.48 8.67 2054.77 1979.13 2320.02 0.00 0.00 0.00

AHU - 14
Total Area in sq.ft. 449.35
Total TR 26.73
Dehumidified CFM 5775
Total equipmentt load(H.P.) 7.00
Room TR 25.24
TR / sq.ft 17.80
CFM / TR 216.08
Total equipment TR 1.48
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
56 Solution Preparation 1 71.67 9.84 705.25 25 4.03 1.00 5.00 70.00 3.50 0.74 4.77 1030 294 1030
57 Material Airlock 27.39 9.84 269.55 83 1.54 0.00 0.00 70.00 0.00 0.00 1.54 332 373 373
58 Persoanl Airlock 21.01 9.84 206.77 70 1.18 0.00 0.00 70.00 0.00 0.00 1.18 255 241 255
59 Film Coating 1 329.27 13.12 4320.03 25 18.50 1.00 5.00 70.00 3.50 0.74 19.24 4157 1800 4157
0.00 0.00 13.12 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 449.35 5501.60 25.24 2.00 10.00 7.00 1.48 26.73 5774.95 2707.98 5815.33 0.00 0.00 0.00

AHU - 15
Total Area in sq.ft. 439.80
Total TR 24.72
Dehumidified CFM 5265
Total equipmentt load(H.P.) 4.20
Room TR 23.83
TR / sq.ft 18.45
CFM / TR 212.97
Total equipment TR 0.89
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
60 Solution Preparation 2 73.03 9.84 718.62 25 3.96 1.00 3.00 70.00 2.10 0.45 4.40 938 299 938
61 Material Airlock 25.99 9.84 255.70 87 1.41 0.00 0.00 70.00 0.00 0.00 1.41 300 371 371
62 Persoanl Airlock 19.58 9.84 192.70 74 1.06 0.00 0.00 70.00 0.00 0.00 1.06 226 238 238
63 Film Coating 2 321.20 9.84 3160.59 25 17.41 1.00 3.00 70.00 2.10 0.45 17.85 3802 1317 3802
0.00 0.00 9.84 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 439.80 4327.61 23.83 2.00 6.00 4.20 0.89 24.72 5265.17 2224.76 5347.70 0.00 0.00 0.00

AHU - 16
Total Area in sq.ft. 471.18
Total TR 21.26
Dehumidified CFM 4544
Total equipmentt load(H.P.) 4.20
Room TR 20.37
TR / sq.ft 23.13
CFM / TR 213.75
Total equipment TR 0.89
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
64 Solution Preparation 69.28 9.84 681.72 25 2.99 1.00 3.00 70.00 2.10 0.45 3.44 735 284 735
65 Material Airlock 26.36 9.84 259.40 86 1.14 0.00 0.00 70.00 0.00 0.00 1.14 244 372 372
66 Persoanl Airlock 19.58 9.84 192.70 75 0.85 0.00 0.00 70.00 0.00 0.00 0.85 181 241 241
67 Sugar Coating Room 355.95 9.84 3502.60 25 15.39 1.00 3.00 70.00 2.10 0.45 15.83 3384 1459 3384
0.00 0.00 9.84 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 471.18 4636.42 20.37 2.00 6.00 4.20 0.89 21.26 4543.91 2356.15 4732.07 0.00 0.00 0.00

AHU - 17
Total Area in sq.ft. 718.29
Total TR 9.99
Dehumidified CFM 2850
Total equipmentt load(H.P.) 5.60
Room TR 8.80
TR / sq.ft 81.64
CFM / TR 285.43
Total equipment TR 1.19
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
68 Dry Syrup manufacturing 477.65 14.76 7050.11 25 5.85 2.00 8.00 70.00 5.60 1.19 7.04 2009 2938 2938
0.00 0.00 14.76 0.00 25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
69 Dry Syrup manufacturing Material Airlock 35.78 9.84 352.05 63 0.44 0.00 0.00 70.00 0.00 0.00 0.44 125 370 370
70 Dry Syrup manufacturing Man AirLock 21.64 9.84 212.97 67 0.27 0.00 0.00 70.00 0.00 0.00 0.27 76 238 238
Dry Syrup Blend Store 183.22 9.84 1802.93 25 2.24 0.00 0.00 70.00 0.00 0.00 2.24 641 751 751

TOTAL 718.29 9418.06 8.80 2.00 8.00 5.60 1.19 9.99 2850.35 4296.23 4296.23 0.00 0.00 0.00

AHU - 18
Total Area in sq.ft. 778.84
Total TR 22.84
Dehumidified CFM 3650
Total equipmentt load(H.P.) 7.00
Room TR 21.36
TR / sq.ft 36.47
CFM / TR 159.81
Total equipment TR 1.48
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
71 ORS Blend Store 246.25 9.84 2423.14 25 6.75 0.00 0.00 70.00 0.00 0.00 6.75 1079 1010 1079
72 ORS Manufacturing 474.13 14.76 6998.13 25 13.00 2.00 10.00 70.00 7.00 1.48 14.48 2315 2916 2916
0.00 0.00 14.76 0.00 25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
73 ORS Manufacturing Material Airlock 36.30 9.84 357.20 63 1.00 0.00 0.00 70.00 0.00 0.00 1.00 159 375 375
74 ORS Manufacturing Man AirLock 22.16 9.84 218.02 66 0.61 0.00 0.00 70.00 0.00 0.00 0.61 97 240 240

TOTAL 778.84 9996.49 21.36 2.00 10.00 7.00 1.48 22.84 3650.00 4540.41 4609.82 0.00 0.00 0.00

AHU - 19
Total Area in sq.ft. 391.96
Total TR 8.47
Dehumidified CFM 1620
Total equipmentt load(H.P.) 1.40
Room TR 8.18
TR / sq.ft 47.94
CFM / TR 191.21
Total equipment TR 0.30
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
75 Bottle Cleaning 391.96 9.84 3856.87 25 8.18 2.00 2.00 70.00 1.40 0.30 8.47 1620 1607 1620

TOTAL 391.96 3856.87 8.18 2.00 2.00 1.40 0.30 8.47 1620.05 1607.03 1620.05 0.00 0.00 0.00

AHU - 20
Total Area in sq.ft. 481.31
Total TR 6.74
Dehumidified CFM 1590
Total equipmentt load(H.P.) 2.10
Room TR 6.29
TR / sq.ft 76.52
CFM / TR 236.02
Total equipment TR 0.45
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
76 Dry Syrup filling & Sealing 428.57 9.84 4217.14 25 5.60 2.00 3.00 70.00 2.10 0.45 6.05 1427 1757 1757
0.00 0.00 9.84 0.00 25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
77 Dry Syrup filling & Sealing Material Airlock 31.10 9.84 305.99 73 0.41 0.00 0.00 70.00 0.00 0.00 0.41 96 372 372
78 Dry Syrup filling & Sealing Man AirLock 21.64 9.84 212.97 67 0.28 0.00 0.00 70.00 0.00 0.00 0.28 67 238 238

TOTAL 481.31 4736.10 6.29 2.00 3.00 2.10 0.45 6.74 1589.75 2367.25 2367.25 0.00 0.00 0.00

AHU - 21
Total Area in sq.ft. 605.15
Total TR 11.75
Dehumidified CFM 1967
Total equipmentt load(H.P.) 3.50
Room TR 11.01
TR / sq.ft 54.98
CFM / TR 167.42
Total equipment TR 0.74
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N.Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
79 Empty Capsule Day Store 157.17 9.84 1546.57 25 2.86 0.00 0.00 70.00 0.00 0.00 2.86 479 644 644
80 Material Airlock 26.36 9.84 259.40 86 0.48 0.00 0.00 70.00 0.00 0.00 0.48 80 372 372
81 Persoanl Airlock 19.57 9.84 192.55 75 0.36 0.00 0.00 70.00 0.00 0.00 0.36 60 241 241
82 Capsule Filling & Inspection 303.35 9.84 2984.99 25 5.52 4.00 5.00 70.00 3.50 0.74 6.26 1048 1244 1244
0.00 0.00 0.00 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0
83 Filled Capsules Room 98.70 9.84 971.19 25 1.80 0.00 0.00 70.00 0.00 0.00 1.80 301 405 405

TOTAL 605.15 5954.69 11.01 4.00 5.00 3.50 0.74 11.75 1967.13 2905.31 2905.31 0.00 0.00 0.00

AHU - 22
Total Area in sq.ft. 821.18
Total TR 7.81
Dehumidified CFM 2349
Total equipmentt load(H.P.) 4.20
Room TR 6.91
TR / sq.ft 118.77
CFM / TR 300.91
Total equipment TR 0.89
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
84 Return Change Room Gents 179.82 9.84 1769.44 25 1.51 0.00 3.00 70.00 2.10 0.45 1.96 590 737 737
85 Secondary Change Room Ladies 142.12 9.84 1398.47 25 1.20 0.00 0.00 70.00 0.00 0.00 1.20 360 583 583
86 Return Change Room Ladies 142.62 9.84 1403.35 25 1.20 0.00 3.00 70.00 2.10 0.45 1.65 495 585 585
87 Secondary Change Room Gents 356.62 9.84 3509.18 25 3.00 0.00 0.00 70.00 0.00 0.00 3.00 904 1462 1462

TOTAL 821.18 8080.43 6.91 0.00 6.00 4.20 0.89 7.81 2348.64 3366.85 3366.85 0.00 0.00 0.00

AHU - 23
Total Area in sq.ft. 362.95
Total TR 13.05
Dehumidified CFM 2864
Total equipmentt load(H.P.) 5.60
Room TR 11.86
TR / sq.ft 30.60
CFM / TR 219.49
Total equipment TR 1.19
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
88 Material Airlock 25.47 9.84 250.66 89 0.83 0.00 0.00 70.00 0.00 0.00 0.83 183 372 372
89 Persoanl Airlock 20.14 9.84 198.18 72 0.66 0.00 0.00 70.00 0.00 0.00 0.66 144 238 238
90 Blister Packing 1 317.34 9.84 3122.63 25 10.37 2.00 8.00 70.00 5.60 1.19 11.56 2537 1301 2537
0 0.00 0.00 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 362.95 3571.47 11.86 2.00 8.00 5.60 1.19 13.05 2864.12 1910.72 3146.56 0.00 0.00 0.00

AHU - 24
Total Area in sq.ft. 353.34
Total TR 13.02
Dehumidified CFM 2850
Total equipmentt load(H.P.) 5.60
Room TR 11.84
TR / sq.ft 29.85
CFM / TR 218.87
Total equipment TR 1.19
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
91 Material Airlock 25.47 9.84 250.66 89 0.85 0.00 0.00 70.00 0.00 0.00 0.85 187 372 372
92 Persoanl Airlock 20.14 9.84 198.18 72 0.67 0.00 0.00 70.00 0.00 0.00 0.67 148 238 238
93 Blister Packing 2 307.73 9.84 3028.03 25 10.31 2.00 8.00 70.00 5.60 1.19 11.50 2516 1262 2516
0 0.00 9.84 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0
TOTAL 353.34 3476.87 11.84 2.00 8.00 5.60 1.19 13.02 2850.30 1871.30 3125.53 0.00 0.00 0.00

AHU - 25
Total Area in sq.ft. 359.33
Total TR 13.04
Dehumidified CFM 2859
Total equipmentt load(H.P.) 5.60
Room TR 11.85
TR / sq.ft 30.32
CFM / TR 219.26
Total equipment TR 1.19
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
94 Material Airlock 25.47 9.84 250.66 89 0.84 0.00 0.00 70.00 0.00 0.00 0.84 184 372 372
95 Persoanl Airlock 20.14 9.84 198.18 72 0.66 0.00 0.00 70.00 0.00 0.00 0.66 146 238 238
96 Blister Packing 3 313.72 9.84 3087.01 25 10.35 2.00 8.00 70.00 5.60 1.19 11.53 2529 1286 2529
0.00 0.00 9.84 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 359.33 3535.85 11.85 2.00 8.00 5.60 1.19 13.04 2858.91 1895.88 3138.69 0.00 0.00 0.00

AHU - 26
Total Area in sq.ft. 353.34
Total TR 13.02
Dehumidified CFM 2850
Total equipmentt load(H.P.) 5.60
Room TR 11.84
TR / sq.ft 29.85
CFM / TR 218.87
Total equipment TR 1.19
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
97 Material Airlock 25.47 9.84 250.66 89 0.85 0.00 0.00 70.00 0.00 0.00 0.85 187 372 372
98 Persoanl Airlock 20.14 9.84 198.18 72 0.67 0.00 0.00 70.00 0.00 0.00 0.67 148 238 238
99 Strip packing 307.73 9.84 3028.03 25 10.31 2.00 8.00 70.00 5.60 1.19 11.50 2516 1262 2516
0.00 0.00 9.84 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 353.34 3476.87 11.84 2.00 8.00 5.60 1.19 13.02 2850.30 1871.30 3125.53 0.00 0.00 0.00

AHU - 27
Total Area in sq.ft. 353.34
Total TR 13.17
Dehumidified CFM 2934
Total equipmentt load(H.P.) 3.50
Room TR 12.42
TR / sq.ft 28.44
CFM / TR 222.84
Total equipment TR 0.74
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
100 Material Airlock 25.47 9.84 250.66 89 0.90 0.00 0.00 70.00 0.00 0.00 0.90 200 372 372
101 Persoanl Airlock 20.14 9.84 198.18 72 0.71 0.00 0.00 70.00 0.00 0.00 0.71 158 238 238
102 Bulk Packing 307.73 9.84 3028.03 25 10.82 2.00 5.00 70.00 3.50 0.74 11.56 2577 1262 2577
0.00 0.00 9.84 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 353.34 3476.87 12.42 2.00 5.00 3.50 0.74 13.17 2934.23 1871.30 3186.42 0.00 0.00 0.00

AHU - 28
Total Area in sq.ft. 347.33
Total TR 17.53
Dehumidified CFM 1765
Total equipmentt load(H.P.) 3.50
Room TR 16.79
TR / sq.ft 20.69
CFM / TR 100.68
Total equipment TR 0.74
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
103 Material Airlock 25.47 9.84 250.66 89 1.23 0.00 0.00 70.00 0.00 0.00 1.23 124 372 372
104 Persoanl Airlock 20.14 9.84 198.18 72 0.97 0.00 0.00 70.00 0.00 0.00 0.97 98 238 238
105 Satchet Filling 1 301.72 9.84 2968.90 25 14.58 2.00 5.00 70.00 3.50 0.74 15.33 1543 1237 1543
0.00 0.00 9.84 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 347.33 3417.74 16.79 2.00 5.00 3.50 0.74 17.53 1765.00 1846.67 2152.65 0.00 0.00 0.00

AHU - 29
Total Area in sq.ft. 354.69
Total TR 17.53
Dehumidified CFM 1765
Total equipmentt load(H.P.) 3.50
Room TR 16.79
TR / sq.ft 21.13
CFM / TR 100.68
Total equipment TR 0.74
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
106 Material Airlock 19.91 9.84 195.96 115 0.94 0.00 0.00 70.00 0.00 0.00 0.94 95 376 376
107 Persoanl Airlock 25.68 9.84 252.73 57 1.22 0.00 0.00 70.00 0.00 0.00 1.22 122 240 240
108 Satchet Filling 2 309.09 9.84 3041.43 25 14.63 2.00 5.00 70.00 3.50 0.74 15.37 1548 1267 1548
0.00 0.00 9.84 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 354.69 3490.12 16.79 2.00 5.00 3.50 0.74 17.53 1765.00 1882.95 2163.38 0.00 0.00 0.00

AHU - 30
Total Area in sq.ft. 358.00
Total TR 17.53
Dehumidified CFM 1765
Total equipmentt load(H.P.) 3.50
Room TR 16.79
TR / sq.ft 21.33
CFM / TR 100.68
Total equipment TR 0.74
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
109 Material Airlock 19.81 9.84 194.92 114 0.93 0.00 0.00 70.00 0.00 0.00 0.93 94 370 370
110 Persoanl Airlock 25.43 9.84 250.21 57 1.19 0.00 0.00 70.00 0.00 0.00 1.19 120 238 238
111 Satchet Filling 3 312.76 9.84 3077.59 25 14.67 2.00 5.00 70.00 3.50 0.74 15.41 1551 1282 1551
0.00 0.00 9.84 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 358.00 3522.72 16.79 2.00 5.00 3.50 0.74 17.53 1765.00 1890.38 2159.47 0.00 0.00 0.00

AHU - 31
Total Area in sq.ft. 233.22
Total TR 7.30
Dehumidified CFM 1874
Total equipmentt load(H.P.) 1.40
Room TR 7.01
TR / sq.ft 33.28
CFM / TR 256.52
Total equipment TR 0.30
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
112 Material Airlock 27.39 9.84 269.55 83 0.82 0.00 0.00 70.00 0.00 0.00 0.82 211 373 373
113 Persoanl Airlock 20.62 9.84 202.87 71 0.62 0.00 0.00 70.00 0.00 0.00 0.62 159 240 240
114 Tablet Inspection 185.21 9.84 1822.49 25 5.57 4.00 2.00 70.00 1.40 0.30 5.86 1504 759 1504
0.00 0.00 9.84 0.00 25 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 233.22 2294.91 7.01 4.00 2.00 1.40 0.30 7.30 1873.80 1372.31 2116.68 0.00 0.00 0.00

AHU - 32
Total Area in sq.ft. 8672.40
Total TR 41.25
Dehumidified CFM 19093
Total equipmentt load(H.P.) 51.40
Room TR 30.35
TR / sq.ft 285.74
CFM / TR 462.84
Total equipment TR 10.90
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N.Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
115 Gents Air Lock 62.71 9.84 617.06 25 0.22 0.00 0.00 70.00 0.00 0.00 0.22 102 257 257 1
116 Ladies Air Lock 62.71 9.84 617.06 25 0.22 0.00 0.00 70.00 0.00 0.00 0.22 102 257 257 1
117 Office & Documentation 133.24 9.84 1311.07 5 0.47 2.00 1.00 70.00 0.70 0.15 0.61 285 109 285 1
118 Batch Printing 135.07 9.84 1329.07 5 0.47 2.00 1.00 70.00 0.70 0.15 0.62 287 111 287 1
119 Tool Room for Secondary packing 135.07 9.84 1329.07 5 0.47 0.00 0.00 70.00 0.00 0.00 0.47 219 111 219 1
120 Secondary Packing Hall 5638.26 12.46 70275.22 5 19.73 48.00 100.00 50.00 50.00 10.60 30.34 14041 5856 14041 22
0.00 0.00 0.00 0.00 5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
121 Secondary Packing Material Day Store 201.30 9.84 1980.79 5 0.70 0.00 0.00 70.00 0.00 0.00 0.70 326 165 326 1
122 Packing Corridor 2304.05 9.84 22671.89 5 8.06 0.00 0.00 70.00 0.00 0.00 8.06 3732 1889 3732 13
0.00 0.00 9.84 0.00 5 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 8672.40 ### 30.35 52.00 102.00 51.40 10.90 41.25 ### 8755.64 19403.64 0.00 22.00 0.00 19.00

AHU - 33
Total Area in sq.ft. 3942.22
Total TR 12.16
Dehumidified CFM 4691
Total equipmentt load(H.P.) 0.00
Room TR 12.16
TR / sq.ft 324.13
CFM / TR 385.67
Total equipment TR 0.00
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
123 Finished Goods Store 1672.39 25.58 42786.33 2 5.16 0.00 0.00 70.00 0.00 0.00 5.16 1990 1426 1990
0.00 0.00 25.58 0.00 2 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0
124 Finished Goods Quarantine 1641.23 25.58 41989.30 2 5.06 0.00 0.00 70.00 0.00 0.00 5.06 1953 1400 1953
0.00 0.00 25.58 0.00 2 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0
125 Transition Zone 628.60 25.58 16082.17 2 1.94 2.00 0.00 70.00 0.00 0.00 1.94 748 536 748
0.00 0.00 25.58 0.00 2 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0

TOTAL 3942.22 ### 12.16 2.00 0.00 0.00 0.00 12.16 4690.65 3361.93 4690.65 0.00 0.00 0.00 0.00

AHU - 34
Total Area in sq.ft. 192.84
Total TR 7.57
Dehumidified CFM 1765
Total equipmentt load(H.P.) 1.05
Room TR 7.35
TR / sq.ft 26.24
CFM / TR 233.06
Total equipment TR 0.22
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
126 Sampling Room 1 Man Airlock 25.98 9.84 255.64 68 0.99 0.00 0.00 70.00 0.00 0.00 0.99 231 290 290
127 Sampling Room 1 Material Airlock 38.68 9.84 380.64 72 1.47 0.00 0.00 70.00 0.00 0.00 1.47 344 457 457
128 Sampling Room 1 128.18 9.84 1261.28 25 4.89 2.00 1.50 70.00 1.05 0.22 5.11 1190 526 1190

TOTAL 192.84 1897.57 7.35 2.00 1.50 1.05 0.22 7.57 1764.81 1272.03 1936.94 0.00 0.00 0.00

AHU - 35
Total Area in sq.ft. 190.19
Total TR 7.79
Dehumidified CFM 1871
Total equipmentt load(H.P.) 1.05
Room TR 7.56
TR / sq.ft 25.15
CFM / TR 240.31
Total equipment TR 0.22
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
129 Sampling Room 2 Material Airlock 37.77 9.84 371.67 74 1.50 0.00 0.00 70.00 0.00 0.00 1.50 361 458 458
130 Sampling Room 2 Man Airlock 26.02 9.84 256.06 68 1.03 0.00 0.00 70.00 0.00 0.00 1.03 249 290 290
131 Sampling Room 2 126.40 9.84 1243.78 25 5.03 2.00 1.50 70.00 1.05 0.22 5.25 1261 518 1261

TOTAL 190.19 1871.51 7.56 2.00 1.50 1.05 0.22 7.79 1870.86 1266.83 2009.89 0.00 0.00 0.00

AHU - 36
Total Area in sq.ft. 8363.72
Total TR 22.58
Dehumidified CFM 11347
Total equipmentt load(H.P.) 3.50
Room TR 21.83
TR / sq.ft 383.07
CFM / TR 502.61
Total equipment TR 0.74
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N.Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
132 Cap Storage 242.92 25.58 6214.75 2 0.63 0.00 0.00 70.00 0.00 0.00 0.63 319 207 319
133 RM Staging Room 546.50 25.58 13981.64 2 1.43 0.00 0.00 70.00 0.00 0.00 1.43 717 466 717
134 RM Quarantine 894.14 25.58 22875.62 2 2.33 0.00 0.00 70.00 0.00 0.00 2.33 1173 763 1173
135 Empty Capsule Store 388.26 25.58 9933.33 2 1.01 0.00 0.00 70.00 0.00 0.00 1.01 509 331 509
136 Approved RM Material Store 3398.07 25.58 86936.11 2 8.87 0.00 0.00 70.00 0.00 0.00 8.87 4458 2898 4458
0.00 0.00 25.58 0.00 2 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0
0.00 0.00 25.58 0.00 2 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0
137 RM Corridor 1320.69 25.58 33788.45 2 3.45 0.00 0.00 70.00 0.00 0.00 3.45 1733 1126 1733
0.00 0.00 25.58 0.00 2 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0
0.00 0.00 25.58 0.00 2 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0
138 PVC/ALU Storage 668.88 25.58 17112.73 2 1.75 0.00 0.00 70.00 0.00 0.00 1.75 878 570 878
0.00 0.00 25.58 0.00 2 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0
139 Bottle Storage 645.65 25.58 16518.34 2 1.69 0.00 0.00 70.00 0.00 0.00 1.69 847 551 847
140 Equiupment Wash 2 98.69 9.84 971.09 2 0.26 0.00 5.00 70.00 3.50 0.74 1.00 503 32 503 1
141 PPM Dispensing 159.93 9.84 1573.69 2 0.42 1.00 0.00 70.00 0.00 0.00 0.42 210 52 210 1

TOTAL 8363.72 ### 21.83 1.00 5.00 3.50 0.74 22.58 ### 6996.86 11346.76 0.00 0.00 1.00 1.00

AHU - 37
Total Area in sq.ft. 4448.68
Total TR 24.31
Dehumidified CFM 9257
Total equipmentt load(H.P.) 17.50
Room TR 20.60
TR / sq.ft 215.97
CFM / TR 380.78
Total equipment TR 3.71
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
142 Gents Change Room 124.17 9.18 1140.33 10 0.57 0.00 0.00 70.00 0.00 0.00 0.57 219 190 219 1
143 Registry 68.94 9.18 633.14 10 0.32 2.00 2.00 70.00 1.40 0.30 0.62 235 106 235 1
144 Ladies Change Room 144.61 9.18 1328.14 10 0.67 0.00 0.00 70.00 0.00 0.00 0.67 255 221 255 3
145 Wet lab 392.21 9.18 3602.05 10 1.82 4.00 3.00 70.00 2.10 0.45 2.26 861 600 861 1
146 Chemical Store 135.82 9.18 1247.38 10 0.63 1.00 0.50 70.00 0.35 0.07 0.70 268 208 268 1
147 Glass Ware Store 172.31 9.18 1582.50 10 0.80 0.00 0.00 70.00 0.00 0.00 0.80 304 264 304 2
148 QC Staff & Documents 202.82 9.18 1862.70 10 0.94 6.00 2.50 70.00 1.75 0.37 1.31 499 310 499 2
149 Stability 253.40 9.18 2327.21 10 1.17 1.00 8.00 70.00 5.60 1.19 2.36 899 388 899 1
150 Wash & Deactivation Room 147.98 9.18 1359.09 10 0.69 1.00 1.00 70.00 0.70 0.15 0.83 317 227 317 2
151 Incubation 265.19 9.18 2435.48 #REF! 1.23 0.00 0.00 70.00 0.00 0.00 1.23 468 #REF! #REF!
0.00 0.00 9.18 0.00 10 0.00 1.00 4.00 70.00 2.80 0.59 0.59 226 0 226
152 0.00 0.00 9.18 0.00 0 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0 1
153 Incubation Airlock 14.45 9.18 132.70 10 0.07 0.00 0.00 70.00 0.00 0.00 0.07 25 22 25 3
154 Instruments 2 367.23 9.18 3372.67 10 1.70 0.00 3.00 70.00 2.10 0.45 2.15 817 562 817 3
155 Instruments 1 421.42 9.18 3870.28 10 1.95 0.00 0.50 70.00 0.35 0.07 2.03 771 645 771 1
156 QC Manager 192.65 9.18 1769.27 10 0.89 2.00 0.25 70.00 0.18 0.04 0.93 354 295 354 1
157 QA Manager 145.69 9.18 1338.01 10 0.67 2.00 0.25 70.00 0.18 0.04 0.71 271 223 271 4
158 Common Corridor 913.36 9.18 8388.29 10 4.23 0.00 0.00 70.00 0.00 0.00 4.23 1610 1398 1610
0.00 0.00 9.18 0.00 10 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0
0.00 0.00 9.18 0.00 10 0.00 0.00 0.00 70.00 0.00 0.00 0.00 0 0 0
159 Control Samples 486.43 9.18 4467.41 10 2.25 1.00 0.00 70.00 0.00 0.00 2.25 858 745 858 3

TOTAL 4448.68 40856.65 20.60 21.00 25.00 17.50 3.71 24.31 9256.93 #REF! #REF! 0.00 14.00 16.00

AHU - 38
Total Area in sq.ft. 234.39
Total TR 3.09
Dehumidified CFM 803
Total equipmentt load(H.P.) 2.10
Room TR 2.65
TR / sq.ft 88.52
CFM / TR 259.55
Total equipment TR 0.45
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
124 Media Prepration 220.83 9.18 2028.14 25 2.49 1.00 3.00 70.00 2.10 0.45 2.94 763 845 845
0.00 0.00 9.18 0.00 25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
125 Media Prepration Airlock 13.56 9.18 124.51 30 0.15 0.00 0.00 70.00 0.00 0.00 0.15 40 62 62

TOTAL 234.39 2152.66 2.65 1.00 3.00 2.10 0.45 3.09 802.83 907.32 907.32 0.00 0.00 0.00

AHU - 39
Total Area in sq.ft. 252.77
Total TR 5.43
Dehumidified CFM 1539
Total equipmentt load(H.P.) 5.60
Room TR 4.24
TR / sq.ft 59.61
CFM / TR 283.45
Total equipment TR 1.19
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
126 MLT Room 133.84 9.18 1229.18 40 2.25 1.00 8.00 70.00 5.60 1.19 3.43 973 819 973
127 Airlock 3 33.23 9.18 305.21 40 0.56 0.00 0.00 70.00 0.00 0.00 0.56 158 203 203
128 Airlock 2 33.23 9.18 305.21 40 0.56 0.00 0.00 70.00 0.00 0.00 0.56 158 203 203
129 Airlock 1 26.24 9.18 240.94 40 0.44 0.00 0.00 70.00 0.00 0.00 0.44 125 161 161
130 Return Airlock 26.24 9.18 240.94 40 0.44 0.00 0.00 70.00 0.00 0.00 0.44 125 161 161

TOTAL 252.77 2321.48 4.24 1.00 8.00 5.60 1.19 5.43 1538.68 1547.65 1701.30 0.00 0.00 0.00

AHU - 40
Total Area in sq.ft. 114.28
Total TR 2.66
Dehumidified CFM 576
Total equipmentt load(H.P.) 2.80
Room TR 2.06
TR / sq.ft 55.44
CFM / TR 217.06
Total equipment TR 0.59
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
126 Media Storage 96.77 9.18 888.74 25 1.75 0.00 4.00 70.00 2.80 0.59 2.34 508 370 508
127 Media Storage Airlock 17.51 9.18 160.78 25 0.32 0.00 0.00 70.00 0.00 0.00 0.32 69 67 69

TOTAL 114.28 1049.52 2.06 0.00 4.00 2.80 0.59 2.66 576.36 437.30 576.36 0.00 0.00 0.00

V- 01
Total Area in sq.ft. 2975.63
Total TR 0.54
Dehumidified CFM 405
Total equipmentt load(H.P.) 0.00
Room TR 0.54
TR / sq.ft 5482.59
CFM / TR 745.60
Total equipment TR 0.00
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
131 Workmen Entry & Corridor 1060.99 9.84 10440.14 10 0.00 0.00 70.00 0.00 0.00 0.00 0 1740 1740 1
0.00 0.00 9.84 0.00 10 0 0 4
132 Tiffin Storage 56.96 9.84 560.49 10 0.00 0.00 70.00 0.00 93 93 1
133 Ladies Staff Shoe Rack 139.84 9.84 1376.00 10 0.00 0.00 70.00 0.00 229 229 1
134 Ladies Staff Change Room 186.45 9.84 1834.66 10 0.00 0.00 70.00 0.00 306 306 1
135 Linen Room 1 74.21 9.84 730.27 10 0.00 0.00 70.00 0.00 122 122 1
136 Linen Room 2 70.80 9.84 696.68 10 0.00 0.00 70.00 0.00 116 116 1
137 Gents Staff Shoe Rack 136.92 9.84 1347.33 10 0.00 0.00 70.00 0.00 225 225 1
138 Gents Staff Change Room 186.45 9.84 1834.66 10 0.00 0.00 70.00 0.00 306 306 1
139 Visitor Change 154.47 9.84 1520.00 10 0.00 0.00 70.00 0.00 253 253 1
140 Ladies Workers Shoe Rack 142.59 9.84 1403.06 10 0.00 0.00 70.00 0.00 234 234 1
141 Ladies Worker Change Room 253.69 9.84 2496.29 10 0.00 0.00 70.00 0.00 416 416 1
142 Gents Worker Shoe Rack 136.92 9.84 1347.33 10 0.00 0.00 70.00 0.00 225 225 1
143 Housekeeping to Canteen 40.03 9.84 393.94 10 0.00 0.00 70.00 0.00 66 66 1
144 Housekeeping to Packing 41.06 9.84 404.07 10 0.00 0.00 70.00 0.00 67 67 1
145 Gents Worker Change Room 294.24 9.84 2895.32 10 0.00 0.00 70.00 0.00 483 483 1

TOTAL 2975.63 29280.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4880.04 4880.04 0.00 0.00 0.00 19.00

V - 02
Total Area in sq.ft. 1096.23
Total TR 0.62
Dehumidified CFM 398
Total equipmentt load(H.P.) 0.00
Room TR 0.62
TR / sq.ft 1761.39
CFM / TR 640.23
Total equipment TR 0.00
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
146 Ladies Toilet Staff 127.08 9.84 1250.47 10 0.00 0.00 70.00 0.00 0.00 0.00 0 208 208 1
147 Toilet1 21.95 9.84 215.99 10 0.00 0.00 70.00 0.00 36 36 1
148 Toilet2 21.95 9.84 215.99 10 0.00 0.00 70.00 0.00 36 36 1
149 Toilet3 21.95 9.84 215.99 10 0.00 0.00 70.00 0.00 36 36 1
Wash 30.18 9.84 296.99 10 0.00 0.00 70.00 0.00 49 49 1
Ladied Toilet 165.93 9.84 1632.75 10 0.00 0.00 70.00 0.00 272 272 1
Toilet1 21.58 9.84 212.39 10 0.00 0.00 70.00 0.00 35 35 1
Toilet2 21.95 9.84 215.99 10 0.00 0.00 70.00 0.00 36 36 1
Wash 30.55 9.84 300.59 10 0.00 0.00 70.00 0.00 50 50 1
Gents Toilet 197.49 9.84 1943.28 10 0.00 0.00 70.00 0.00 324 324 1
Toilet1 21.95 9.84 215.99 10 0.00 0.00 70.00 0.00 36 36 1
Toilet2 21.95 9.84 215.99 10 0.00 0.00 70.00 0.00 36 36 1
Toilet3 21.95 9.84 215.99 10 0.00 0.00 70.00 0.00 36 36 1
Toilet4 21.95 9.84 215.99 10 0.00 0.00 70.00 0.00 36 36 1
Wash 27.44 9.84 269.99 10 0.00 0.00 70.00 0.00 45 45 1
Gents Staff Toilet 137.67 9.84 1354.67 10 0.00 0.00 70.00 0.00 226 226 1
Toilet1 21.95 9.84 215.99 10 0.00 0.00 70.00 0.00 36 36 1
Toilet2 21.95 9.84 215.99 10 0.00 0.00 70.00 0.00 36 36 1
Wash 36.58 9.84 359.99 10 0.00 0.00 70.00 0.00 60 60 1
Visitor Toilet 63.81 9.84 627.91 10 0.00 0.00 70.00 0.00 105 105 1
Toilet1 38.41 9.84 377.99 10 0.00 0.00 70.00 0.00 63 63 1
1
TOTAL 1096.23 10786.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1797.82 1797.82 0.00 0.00 0.00

V- 03
Total Area in sq.ft. 4242.46
Total TR 0.39
Dehumidified CFM 229
Total equipmentt load(H.P.) 1.40
Room TR 0.10
TR / sq.ft 44462.00
CFM / TR 582.90
Total equipment TR 0.30
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
151 Secondary Packing Material Store 1308.05 25.58 33465.05 10 0.00 0.00 70.00 0.00 0.00 0.00 0 5578 5578
5
152 0.00 0.00 25.58 0.00 10 0.00 0.00 70.00 0.00 0 0
153 Secondary Packing Material Quarantine 622.16 25.58 15917.46 10 2.00 1.00 70.00 0.70 2653 2653 3
154 Dedusting Room 2 FG/SPM 149.28 25.58 3819.15 10 2.00 1.00 70.00 0.70 637 637 1
155 Dedusting Room 1 RM/PPM 145.21 25.58 3715.09 10 0.00 0.00 70.00 0.00 619 619 1
156 Rejected Material Store 206.03 25.58 5271.00 10 2.00 0.00 70.00 0.00 878 878 1
Overprinting Room 331.70 25.58 8486.16 10 1414 1414 3
SPM Corridor 1232.45 25.58 31531.01 10 5255 5255
0.00 0.00 25.58 0.00 10 0 0 7
0.00 0.00 25.58 0.00 10 0 0
Bottle decartoning 247.59 9.84 2436.26 10 406 406 1

TOTAL 4242.46 ### 0.00 6.00 2.00 1.40 0.00 0.00 0.00 ### 17440.20 9.00 9.00 4.00

V- 04
Total Area in sq.ft. 1493.36
Total TR 0.38
Dehumidified CFM 276
Total equipmentt load(H.P.) 3.50
Room TR -0.36
TR / sq.ft -4162.54
CFM / TR 720.16
Total equipment TR 0.74
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
158 Airlock for Dining Area 76.34 9.84 751.21 10 0.00 0.00 70.00 0.00 0.00 0.00 0 125 125 1
159 Dinning Hall, Hand Wash, Dish Wash, Food Se 1417.02 9.84 13943.49 10 40.00 5.00 70.00 3.50 2324 2324 4

TOTAL 1493.36 14694.69 0.00 40.00 5.00 3.50 0.00 0.00 0.00 2449.12 2449.12 0.00 4.00 0.00 1.00

V- 05
Total Area in sq.ft. 320.01
Total TR 0.40
Dehumidified CFM 288
Total equipmentt load(H.P.) 0.00
Room TR 0.40
TR / sq.ft 802.57
CFM / TR 723.46
Total equipment TR 0.00
Scavenging CFM
Dehumidified CFM 1090cfm 757cfm 484cfm 272cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300 225 x 225
160 Ladies Toilet Staff 63.81 9.18 586.05 10 0.00 0.00 70.00 0.00 0.00 0.00 0 98 98 1
Toilet1 38.41 9.18 352.79 10 0.00 0.00 70.00 0.00 0.00 0.00 0 59 59
Gents Toilet 137.67 9.18 1264.36 10 0.00 0.00 70.00 0.00 0.00 0.00 0 211 211
Toilet1 21.58 9.18 198.23 10 0.00 0.00 70.00 0.00 0.00 0.00 0 33 33
Toilet2 21.95 9.18 201.59 10 0.00 0.00 70.00 0.00 0.00 0.00 0 34 34
161 Wash 36.58 9.18 335.99 10 0.00 0.00 70.00 0.00 0.00 0.00 0 56 56 1

TOTAL 320.01 2939.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 489.84 489.84 0.00 0.00 2.00

V- 06
Total Area in sq.ft. 177.38
Total TR 1.74
Dehumidified CFM 874
Total equipmentt load(H.P.) 5.60
Room TR 0.56
TR / sq.ft 319.48
CFM / TR 501.47
Total equipment TR 1.19
Scavenging CFM
Dehumidified CFM 630cfm 440cfm 280cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300
162 Hot Zone 177.38 9.18 1629.05 10 4.00 8.00 70.00 5.60 0.00 0 272 272

TOTAL 177.38 1629.05 0.00 4.00 8.00 5.60 0.00 0.00 0.00 271.51 271.51 0.00 0.00 0.00

V- 07
Total Area in sq.ft. 31633.13
Total TR
Dehumidified CFM 396
Total equipmentt load(H.P.) 354.20
Room TR -75.12
TR / sq.ft -421.10
CFM / TR #DIV/0!
Total equipment TR 75.12
Scavenging CFM
Dehumidified CFM 630cfm 440cfm 280cfm
DIFFUSER
S.N. Description of area Area sq.ft. Ht ft volume ACPH Area TRoccupancyEqpt LoadDiversityFinal equip load Eqpt TR Total TR Deh CFM Scav CFMSelected CFM450 x 450 375 x 375 300 x 300
163 Technical Area for AHUs 31633.13 16.40 ### 5 3.00 506.00 70.00 354.20 0.00 0 43232 43232

TOTAL 31633.13 ### 0.00 3.00 506.00 354.20 0.00 0.00 0.00 ### 43231.94 0.00 0.00 0.00

582.8

fire damper #REF! total cfm #REF! 9.0 49.0 23.0


vcd #REF! duct #REF!

9 49 23
9 49 23
Selected
#REF!
Cfm sqft / grill
Preinsulate
#REF! for ahus
d duct 2.17 1.51 0.96
fire Total 39.06 147.98 44.16
#REF!
damper
vcd #REF!

Riser grill
2.90 1.93 1.45
63.80 50.18 117.45

Total

39.06 27.18 7.68

Total

Total

Total

Total

Total
supply n return
225 x 225

supply n return
225 x 225

supply n return
225 x 225

supply n return
225 x 225

225 x 225

225 x 225
225 x 225

225 x 225

225 x 225

225 x 225

225 x 225
225 x 225

225 x 225

225 x 225

225 x 225

225 x 225

225 x 225
225 x 225

225 x 225

225 x 225

225 x 225

225 x 225

225 x 225

225 x 225
225 x 225

225 x 225

225 x 225

225 x 225

225 x 225

225 x 225
225 x 225

225 x 225

200cfm 200cfm
JET DIFFUSER RETURN GRILLE
DIA 200 225 x 225
10 10

14 14

3 4

27.00 28.00

225 x 225

225 x 225

JET DIFFUSER RETURN GRILLE


225 x 225
2 1 DIA 200
2 2 DIA 250
3 6 DIA 250
3 4 DIA
23 14 DIA
DIA
DIA
8 8 DIA
DIA
DIA
2 DIA
DIA
2 DIA
DIA
DIA
DIA
45.00 35.00

225 x 225

225 x 225

225 x 225

225 x 225

225 x 225
225 x 225

225 x 225

225 x 225

225 x 225
Supply
Return

Total
231.2

0.96 TOTAL
16.32 247.75
B.T.U. ESTIMATION FORM
Summer AHU 1 Date:
Client: CONDITIONS DB
Area(sq.ft) 306.79 Height 9.84 Outside 102
Volume(Cu.ft): 3019 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3019 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1274
Glass(S) 0 12 0.56 0 CFM 350
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 30307
wall (W) 0 27 0.15 0 RTH 34479
wall (S) 135 31 0.15 629
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 307 25 0.11 844 19.8
Floor 0 25 0.50 0 DE AIR CFM 1417
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.11211551
outside air DB diff BF 1.08
350 30 0.1 1.08 1134
INTERNAL HEAT
People 1.0 People X 337 337
HP 3.50 HP 2545 8908
Blower HP 2.0 2545 5068
Miscell 2.0 3410 6820 Heater 2.0
Lights 613.6 Watts 3.41 2615
ROOM SENSIBLE HEAT SUB TOTAL 26354
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 3953
TOTAL ROOM SENSIBLE HEAT (RSH) 30307
LATENT HEAT
cfm Gr/lb BF
350 142 0.1 0.68 3380
People 1.0 People X 413 413
Steam 0 lb/hr X
Appliances 0
permeation load 0 0
ROOM LATENT HEAT SUB TOTAL 3793
Supply duct Safety
leakage loss % + Factor 10% 379
TOTAL ROOM LATENT HEAT 4172
ROOM TOTAL HEAT(RTH) 34479
OUTDOOR AIR HEAT
Sensible 350 30 0.9 10206
Latent 350 142 0.9 30416
GRAND TOTAL HEAT SUB TOTAL 75101
2% 1502
GRAND TOTAL HEAT 76603
TR 6.38

B.T.U. ESTIMATION FORM


WINTER AHU 1 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 306.78808704 Height 9.84 outside 81
Volume(Cu.ft): 3019 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3019 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1274
Glass(S) 0 12 0.56 0 CFM 350
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 28089
wall (W) 0 6 0.15 0 RTH 30193
wall (S) 135 10 0.15 203
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 307 4 0.11 135 18.72
Floor 0 4 0.5 0 DE AIR CFM 1389
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.09020735
outside air DB diff BF 1.08
350 9 0.1 1.08 340
INTERNAL HEAT
People 1.0 People X 337 337
HP 3.50 HP 2545 8908
Blower HP 2.0 2545 5068
Miscell 2 3410 6820 Heater 2.0
Lights 613.6 Watts 3.41 2615
ROOM SENSIBLE HEAT SUB TOTAL 24426
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 3664
TOTAL ROOM SENSIBLE HEAT (RSH) 28089
LATENT HEAT
cfm Gr/lb BF
350 63 0.1 0.68 1499
People 1.0 People X 413 413
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 11423
ROOM LATENT HEAT SUB TOTAL 1912
Supply duct Safety
leakage loss % + Factor 10% 191
TOTAL ROOM LATENT HEAT 2104
ROOM TOTAL HEAT(RTH) 30193
OUTDOOR AIR HEAT
Sensible 350 9 0.9 3062
Latent 350 63 0.9 13495
GRAND TOTAL HEAT SUB TOTAL 46749
2% 935
GRAND TOTAL HEAT 47684
TR 3.97
22/10/2014 March rh % gr/lb
WB %RH Gr/lb highest 102 64
64 200 avg high 88 64
50 58 mean 95 64 161
XXX 142

VENTILATION
25.00 X ACPH

127

SENSIBLE HEAT FACTOR

(From tables/chart) `

DEHUMIDIFIED AIR

2.69
KW 4.69
22/10/2014 rh % gr/lb
WB %RH Gr/lb lowest 64 58
76 121 avg low 77 58
50 58 mean 70.5 58 63
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
3.3498067346
B.T.U. ESTIMATION FORM
Summer AHU 2 Date:
Client: CONDITIONS DB
Area(sq.ft) 269.97 Height 9.84 Outside 102
Volume(Cu.ft): 2657 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2657 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1107
Glass(S) 0 12 0.56 0 CFM 110
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTO
wall (E) 0 33 0.15 0 RSH 19603
wall (W) 0 27 0.15 0 RTH 21226
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.92
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 270 25 0.11 742 18.9
Floor 0 25 0.50 0 DE AIR CFM 960
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.86764778
outside air DB diff BF 1.08
110 30 0.1 1.08 356
INTERNAL HEAT
People 1.0 People X 337 337
HP 3.50 HP 2545 8908
Blower HP 1.7 2545 4402
Miscell 0.0 3410 0 Heater 0.0
Lights 539.9 Watts 3.41 2302
ROOM SENSIBLE HEAT SUB TOTAL 17046
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 2557
TOTAL ROOM SENSIBLE HEAT (RSH) 19603
LATENT HEAT
cfm Gr/lb BF
110 142 0.1 0.68 1062
People 1.0 People X 413 413
Steam 0 lb/hr X
Appliances 0
permeation load 0 0
ROOM LATENT HEAT SUB TOTAL 1475
Supply duct Safety
leakage loss % + Factor 10% 148
TOTAL ROOM LATENT HEAT 1623
ROOM TOTAL HEAT(RTH) 21226
OUTDOOR AIR HEAT
Sensible 110 30 0.9 3208
Latent 110 142 0.9 9559
GRAND TOTAL HEAT SUB TOTAL 33993
2% 680
GRAND TOTAL HEAT 34673
TR 2.89

B.T.U. ESTIMATION FORM


WINTER AHU 2 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 269.97171408 Height 9.84 outside 81
Volume(Cu.ft): 2657 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2657 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1107
Glass(S) 0 12 0.56 0 CFM 110
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTO
wall (E) 0 12 0.15 0 RSH 18599
wall (W) 0 6 0.15 0 RTH 19572
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.95
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.5
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 270 4 0.11 119 18.45
Floor 0 4 0.5 0 DE AIR CFM 933
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.84328525
outside air DB diff BF 1.08
110 9 0.1 1.08 107
INTERNAL HEAT
People 1.0 People X 337 337
HP 3.50 HP 2545 8908
Blower HP 1.7 2545 4402
Miscell 0 3410 0 Heater 0.0
Lights 539.9 Watts 3.41 2302
ROOM SENSIBLE HEAT SUB TOTAL 16173
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 2426
TOTAL ROOM SENSIBLE HEAT (RSH) 18599
LATENT HEAT
cfm Gr/lb BF
110 63 0.1 0.68 471
People 1.0 People X 413 413
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 7891
ROOM LATENT HEAT SUB TOTAL 884
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 973
ROOM TOTAL HEAT(RTH) 19572
OUTDOOR AIR HEAT
Sensible 110 9 0.9 962
Latent 110 63 0.9 4241
GRAND TOTAL HEAT SUB TOTAL 24775
2% 496
GRAND TOTAL HEAT 25271
TR 2.11
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

111

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

2.69
KW 2.69
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW

2.3141026197
B.T.U. ESTIMATION FORM
Summer AHU 3 Date:
Client: CONDITIONS DB
Area(sq.ft) 255.69 Height 13.12/9.84 Outside 102
Volume(Cu.ft): 3117 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3117 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1617
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 39456
wall (W) 0 27 0.15 0 RTH 44743
wall (S) 137 31 0.15 638
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.15 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 256 25 0.11 703 19.8
Floor 0 25 0.50 0 DE AIR CFM 1845
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.14112
outside air DB diff BF 1.08
455 30 0.1 1.08 1474
INTERNAL HEAT
People 1.0 People X 337 337
HP 3.50 HP 2545 8908
Blower HP 2.5 2545 6430
Miscell 4.0 3410 13640 Heater 4.0
Lights 511.4 Watts 3.41 2180
ROOM SENSIBLE HEAT SUB TOTAL 34309
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5146
TOTAL ROOM SENSIBLE HEAT (RSH) 39456
LATENT HEAT
cfm Gr/lb BF
455.0 142 0.1 0.68 4393
People 1 People X 413 413
Steam 0 lb/hr X
Appliances 0
Miscell 0 0
ROOM LATENT HEAT SUB TOTAL 4806
Supply duct Safety
leakage loss % + Factor 10% 481
TOTAL ROOM LATENT HEAT 5287
ROOM TOTAL HEAT(RTH) 44743
OUTDOOR AIR HEAT
Sensible 455 30 0.9 13268
Latent 455 142 0.9 39541
GRAND TOTAL HEAT SUB TOTAL 97552
2% 1951
GRAND TOTAL HEAT 99503
TR 8.29

B.T.U. ESTIMATION FORM


MONSOON AHU 3 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 255.68904072 Height 13.12/9.84 outside 81
Volume(Cu.ft): 3117 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3117 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1617
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 37093
wall (W) 0 6 0.15 0 RTH 39691
wall (S) 137 10 0.15 206
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 256 4 0.11 113 18.72
Floor 0 4 0.5 0 DE AIR CFM 1835
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.13467
outside air DB diff BF 1.08
455.0 9 0.1 1.08 442
INTERNAL HEAT
People 1.0 People X 337 337
HP 4 HP 2545 8908
Blower HP 2.5 2545 6430
Miscell 4 3410 13640 Heater 4.0
Lights 511.4 Watts 3.41 2180
ROOM SENSIBLE HEAT SUB TOTAL 32255
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4838
TOTAL ROOM SENSIBLE HEAT (RSH) 37093
LATENT HEAT
cfm Gr/lb BF
455 63 0.1 0.68 1949
People 1.0 People X 413 413
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 13350
ROOM LATENT HEAT SUB TOTAL 2362
Supply duct Safety
leakage loss % + Factor 10% 236
TOTAL ROOM LATENT HEAT 2598
ROOM TOTAL HEAT(RTH) 39691
OUTDOOR AIR HEAT
Sensible 455 9 0.9 3980
Latent 455 63 0.9 17543
GRAND TOTAL HEAT SUB TOTAL 61214
2% 1224
GRAND TOTAL HEAT 62439
TR 5.20
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

162

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

2.69
KW 6.69
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
3.915068635
B.T.U. ESTIMATION FORM
Summer AHU 4 Date:
Client: CONDITIONS DB
Area(sq.ft) 1276.81 Height 9.84 Outside 102
Volume(Cu.ft): 20414 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 20414 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 8822
Glass(S) 0 12 0.56 0 CFM 900
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 176098
wall (W) 0 27 0.15 0 RTH 187475
wall (S) 850 31 0.15 3951
Roof sun 0 50 0.50 0 SHF 0.94
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.4
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 1277 25 0.11 3511 18.54
Floor 0 25 0.50 0 DE AIR CFM 8795
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.99695
outside air DB diff BF 1.08
900 30 0.1 1.08 2916
INTERNAL HEAT
People 4.0 People X 337 1348
HP 37.5 HP 2545 95438 7.953125
Blower HP 13.8 2545 35080 2.9233201853
Miscell 0.0 3410 0 Heater 0.0
Lights 2553.6 Watts 3.41 10885
ROOM SENSIBLE HEAT SUB TOTAL 153129
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 22969
TOTAL ROOM SENSIBLE HEAT (RSH) 176098
LATENT HEAT
cfm Gr/lb BF
900 142 0.1 0.68 8690
People 4.0 People X 413 1652
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 10342
Supply duct Safety
leakage loss % + Factor 10% 1034
TOTAL ROOM LATENT HEAT 11377
ROOM TOTAL HEAT(RTH) 187475
OUTDOOR AIR HEAT
Sensible 900 30 0.9 26244 2.187
Latent 900 142 0.9 78214 6.5178
GRAND TOTAL HEAT SUB TOTAL 291932
2% 5839
GRAND TOTAL HEAT 297771
TR 24.81

B.T.U. ESTIMATION FORM


WINTER AHU 4 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 1276.8123736 Height 9.84 outside 81
Volume(Cu.ft): 20414 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 20414 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 8822
Glass(S) 0 12 0.56 0 CFM 900
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 171202
wall (W) 0 6 0.15 0 RTH 177260
wall (S) 850 10 0.15 1275
Roof sun 0 29 0.5 0 SHF 0.97
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.9
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 1277 4 0.11 562 18.09
Floor 0 4 0.5 0 DE AIR CFM 8763
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.99334
outside air DB diff BF 1.08
900 9 0.1 1.08 875
INTERNAL HEAT
People 4.0 People X 337 1348
HP 37.5 HP 2545 95438
Blower HP 13.8 2545 35080
Miscell 1 3410 3410 Heater 1.0
Lights 2553.6 Watts 3.41 10885
ROOM SENSIBLE HEAT SUB TOTAL 148871
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 22331
TOTAL ROOM SENSIBLE HEAT (RSH) 171202
LATENT HEAT
cfm Gr/lb BF
900 63 0.1 0.68 3856
People 4.0 People X 413 1652
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 179075
ROOM LATENT HEAT SUB TOTAL 5508
Supply duct Safety
leakage loss % + Factor 10% 551
TOTAL ROOM LATENT HEAT 6058
ROOM TOTAL HEAT(RTH) 177260
OUTDOOR AIR HEAT
Sensible 900 9 0.9 7873
Latent 900 63 0.9 34700 2.8917
GRAND TOTAL HEAT SUB TOTAL 219834
2% 4397
GRAND TOTAL HEAT 224231
TR 18.69
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

882

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

28.85
KW 29.85
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 5 Date:
Client: CONDITIONS DB
Area(sq.ft) 1021.61 Height 9.84 Outside 102
Volume(Cu.ft): 14728 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 14728 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 6473
Glass(S) 0 12 0.56 0 CFM 650
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 123258
wall (W) 0 27 0.15 0 RTH 131979
wall (S) 611 31 0.15 2843
Roof sun 0 50 0.50 0 SHF 0.93
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 1022 25 0.11 2809 18.72
Floor 0 25 0.50 0 DE AIR CFM 6097
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.94183
outside air DB diff BF 1.08
650 30 0.1 1.08 2106
INTERNAL HEAT
People 4.0 People X 337 1348
HP 25.0 HP 2545 63625
Blower HP 10.1 2545 25741
Miscell 0.0 3410 0 Heater 0.0
Lights 2043.2 Watts 3.41 8709
ROOM SENSIBLE HEAT SUB TOTAL 107181
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 16077
TOTAL ROOM SENSIBLE HEAT (RSH) 123258
LATENT HEAT
cfm Gr/lb BF
650 142 0.1 0.68 6276
People 4.0 People X 413 1652
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 7928
Supply duct Safety
leakage loss % + Factor 10% 793
TOTAL ROOM LATENT HEAT 8721
ROOM TOTAL HEAT(RTH) 131979
OUTDOOR AIR HEAT
Sensible 650 30 0.9 18954
Latent 650 142 0.9 56488
GRAND TOTAL HEAT SUB TOTAL 207421
2% 4148
GRAND TOTAL HEAT 211569
TR 17.63

B.T.U. ESTIMATION FORM


WINTER AHU 5 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 1021.60551 Height 9.84 outside 81
Volume(Cu.ft): 14728 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 14728 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 6473
Glass(S) 0 12 0.56 0 CFM 650
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 118595
wall (W) 0 6 0.15 0 RTH 123475
wall (S) 611 10 0.15 917
Roof sun 0 29 0.5 0 SHF 0.96
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.7
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 1022 4 0.11 450 18.27
Floor 0 4 0.5 0 DE AIR CFM 6010
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.92852
outside air DB diff BF 1.08
650 9 0.1 1.08 632
INTERNAL HEAT
People 4.0 People X 337 1348
HP 25.0 HP 2545 63625
Blower HP 10.1 2545 25741
Miscell 0.5 3410 1705 Heater 0.5
Lights 2043.2 Watts 3.41 8709
ROOM SENSIBLE HEAT SUB TOTAL 103126
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 15469
TOTAL ROOM SENSIBLE HEAT (RSH) 118595
LATENT HEAT
cfm Gr/lb BF
650 63 0.1 0.68 2785
People 4.0 People X 413 1652
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 108812
ROOM LATENT HEAT SUB TOTAL 4437
Supply duct Safety
leakage loss % + Factor 10% 444
TOTAL ROOM LATENT HEAT 4880
ROOM TOTAL HEAT(RTH) 123475
OUTDOOR AIR HEAT
Sensible 650 9 0.9 5686
Latent 650 63 0.9 25061
GRAND TOTAL HEAT SUB TOTAL 154223
2% 3084
GRAND TOTAL HEAT 157307
TR 13.11
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

647

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

19.23
KW 19.73
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 6 Date:
Client: CONDITIONS DB
Area(sq.ft) 5585.70 Height 9.84 Outside 102
Volume(Cu.ft): 54963 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 54963 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 22941
Glass(S) 0 12 0.56 0 CFM 2300
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 253267
wall (W) 0 27 0.15 0 RTH 266731
wall (S) 490 31 0.15 2277
Roof sun 0 50 0.50 0 SHF 0.95
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.52
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 5586 25 0.11 15361 19.808256
Floor 0 25 0.50 0 DE AIR CFM 11839
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.52
outside air DB diff BF 1.08
2300 30 0.0328 1.08 2444
INTERNAL HEAT
People 12.0 People X 337 4044
HP 9.1 HP 2545 23160
Blower HP 35.8 2545 91228
Miscell 10.0 3410 34100 Heater 10.0
Lights 11171.4 Watts 3.41 47618
ROOM SENSIBLE HEAT SUB TOTAL 220232
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 33035
TOTAL ROOM SENSIBLE HEAT (RSH) 253267
LATENT HEAT
cfm Gr/lb BF
2300 142 0.0328 0.68 7284
People 12.0 People X 413 4956
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 12240
Supply duct Safety
leakage loss % + Factor 10% 1224
TOTAL ROOM LATENT HEAT 13465
ROOM TOTAL HEAT(RTH) 266731
OUTDOOR AIR HEAT
Sensible 2300 30 0.9672 72076 6.006312
Latent 2300 142 0.9672 214804 17.9002928
GRAND TOTAL HEAT SUB TOTAL 553610
2% 11072
GRAND TOTAL HEAT 564683
TR 47.06

B.T.U. ESTIMATION FORM


WINTER AHU 6 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 5585.70449368 Height 9.84 outside 81
Volume(Cu.ft): 54963 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 54963 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 22941
Glass(S) 0 12 0.56 0 CFM 2300
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 250372
wall (W) 0 6 0.15 0 RTH 259379
wall (S) 490 10 0.15 735
Roof sun 0 29 0.5 0 SHF 0.97
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.9
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 5586 4 0.11 2458 19.44072
Floor 0 4 0.5 0 DE AIR CFM 11925
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.52
outside air DB diff BF 1.08
2300 9 0.0328 1.08 733
INTERNAL HEAT
People 12.0 People X 337 4044
HP 9.1 HP 2545 23160
Blower HP 35.8 2545 91228
Miscell 14 3410 47740 Heater 14.0
Lights 11171.4 Watts 3.41 47618
ROOM SENSIBLE HEAT SUB TOTAL 217715
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 32657
TOTAL ROOM SENSIBLE HEAT (RSH) 250372
LATENT HEAT
cfm Gr/lb BF
2300 63 0.0328 0.68 3232
People 12.0 People X 413 4956
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 271995
ROOM LATENT HEAT SUB TOTAL 8188
Supply duct Safety
leakage loss % + Factor 10% 819
TOTAL ROOM LATENT HEAT 9007
ROOM TOTAL HEAT(RTH) 259379
OUTDOOR AIR HEAT
Sensible 2300 9 0.9672 21623 1.8018936
Latent 2300 63 0.9672 95300 7.9416792
GRAND TOTAL HEAT SUB TOTAL 376302
2% 7526
GRAND TOTAL HEAT 383828
TR 31.99
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

2294

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

7.00
KW 21.00
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 6A Date:
Client: CONDITIONS DB
Area(sq.ft) 3923.15 Height 9.84 Outside 102
Volume(Cu.ft): 38604 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 38604 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 16085
Glass(S) 0 12 0.56 0 CFM 1600
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 191134
wall (W) 0 27 0.15 0 RTH 201251
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.95
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.5
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 3923 25 0.11 10789 19.8276
Floor 0 25 0.50 0 DE AIR CFM 8926
Partition 316 25 0.11 869 NOTES
INFILTRATION & OUTSIDE AIR 0.55491
outside air DB diff BF 1.08
1600 30 0.0328 1.08 1700
INTERNAL HEAT
People 10.0 People X 337 3370
HP 8.4 HP 2545 21378
Blower HP 25.1 2545 63963
Miscell 9.0 3410 30690 Heater 9.0
Lights 7846.3 Watts 3.41 33445
ROOM SENSIBLE HEAT SUB TOTAL 166203
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 24931
TOTAL ROOM SENSIBLE HEAT (RSH) 191134
LATENT HEAT
cfm Gr/lb BF
1600 142 0.0328 0.68 5067
People 10.0 People X 413 4130
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 9197
Supply duct Safety
leakage loss % + Factor 10% 920
TOTAL ROOM LATENT HEAT 10117
ROOM TOTAL HEAT(RTH) 201251
OUTDOOR AIR HEAT
Sensible 1600 30 0.9672 50140
Latent 1600 142 0.9672 149429
GRAND TOTAL HEAT SUB TOTAL 400819
2% 8016
GRAND TOTAL HEAT 408836
TR 34.07

B.T.U. ESTIMATION FORM


WINTER AHU 6A Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 3923.15131716 Height 9.84 outside 81
Volume(Cu.ft): 38604 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 38604 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 16085
Glass(S) 0 12 0.56 0 CFM 1600
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 189092
wall (W) 0 6 0.15 0 RTH 196108
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.96
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.7
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 3923 4 0.11 1726 19.63416
Floor 0 4 0.5 0 DE AIR CFM 8917
Partition 316 4 0.11 139 NOTES
INFILTRATION & OUTSIDE AIR 0.55439
outside air DB diff BF 1.08
1600 9 0.0328 1.08 510
INTERNAL HEAT
People 10.0 People X 337 3370
HP 8.4 HP 2545 21378
Blower HP 25.1 2545 63963
Miscell 11.7 3410 39897 Heater 11.7
Lights 7846.3 Watts 3.41 33445
ROOM SENSIBLE HEAT SUB TOTAL 164428
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 24664
TOTAL ROOM SENSIBLE HEAT (RSH) 189092
LATENT HEAT
cfm Gr/lb BF
1600 63 0.0328 0.68 2248
People 10.0 People X 413 4130
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 179470
ROOM LATENT HEAT SUB TOTAL 6378
Supply duct Safety
leakage loss % + Factor 10% 638
TOTAL ROOM LATENT HEAT 7016
ROOM TOTAL HEAT(RTH) 196108
OUTDOOR AIR HEAT
Sensible 1600 9 0.9672 15042
Latent 1600 63 0.9672 66296
GRAND TOTAL HEAT SUB TOTAL 277446
2% 5549
GRAND TOTAL HEAT 282995
TR 23.58
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

1608

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

6.46 9
KW 18.16 18
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 7 Date:
Client: CONDITIONS DB
Area(sq.ft) 502.72 Height 9.84 Outside 102
Volume(Cu.ft): 6406 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 6406 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 3045
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 53646
wall (W) 0 27 0.15 0 RTH 59388
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.90
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50.5
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 503 25 0.11 1382 19.35
Floor 0 25 0.50 0 DE AIR CFM 2567
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.84293
outside air DB diff BF 1.08
455 30 0.1 1.08 1474
INTERNAL HEAT
People 2.0 People X 337 674
HP 10.5 HP 2545 26723
Blower HP 4.8 2545 12110
Miscell 0.0 3410 0 Heater 0.0
Lights 1005.4 Watts 3.41 4286
ROOM SENSIBLE HEAT SUB TOTAL 46649
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 6997
TOTAL ROOM SENSIBLE HEAT (RSH) 53646
LATENT HEAT
cfm Gr/lb BF
455 142 0.1 0.68 4393
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 5219
Supply duct Safety
leakage loss % + Factor 10% 522
TOTAL ROOM LATENT HEAT 5741
ROOM TOTAL HEAT(RTH) 59388
OUTDOOR AIR HEAT
Sensible 455 30 0.9 13268
Latent 455 142 0.9 39541
GRAND TOTAL HEAT SUB TOTAL 112197
2% 2244
GRAND TOTAL HEAT 114441
TR 9.54

B.T.U. ESTIMATION FORM


WINTER AHU 7 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 502.715001 Height 9.84 outside 81
Volume(Cu.ft): 6406 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 6406 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 3045
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 51124
wall (W) 0 6 0.15 0 RTH 54177
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.94
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.4
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 503 4 0.11 221 18.54
Floor 0 4 0.5 0 DE AIR CFM 2553
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.83839
outside air DB diff BF 1.08
455 9 0.1 1.08 442
INTERNAL HEAT
People 2.0 People X 337 674
HP 10.5 HP 2545 26723
Blower HP 4.8 2545 12110
Miscell 0 3410 0 Heater 0.0
Lights 1005.4 Watts 3.41 4286
ROOM SENSIBLE HEAT SUB TOTAL 44456
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 6668
TOTAL ROOM SENSIBLE HEAT (RSH) 51124
LATENT HEAT
cfm Gr/lb BF
455 63 0.1 0.68 1949
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 55105
ROOM LATENT HEAT SUB TOTAL 2775
Supply duct Safety
leakage loss % + Factor 10% 278
TOTAL ROOM LATENT HEAT 3053
ROOM TOTAL HEAT(RTH) 54177
OUTDOOR AIR HEAT
Sensible 455 9 0.9 3980
Latent 455 63 0.9 17543
GRAND TOTAL HEAT SUB TOTAL 75700
2% 1514
GRAND TOTAL HEAT 77214
TR 6.43
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

305

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

8.08
KW 8.08
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 8 Date:
Client: CONDITIONS DB
Area(sq.ft) 307.10 Height 9.84 Outside 102
Volume(Cu.ft): 4260 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4260 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 2158
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 40728
wall (W) 0 27 0.15 0 RTH 46469
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 307 25 0.11 845 19.8
Floor 0 25 0.50 0 DE AIR CFM 1905
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.88275
outside air DB diff BF 1.08
455 30 0.1 1.08 1474
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 3.4 2545 8580
Miscell 1.0 3410 3410 Heater 1.0
Lights 614.2 Watts 3.41 2618
ROOM SENSIBLE HEAT SUB TOTAL 35415
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5312
TOTAL ROOM SENSIBLE HEAT (RSH) 40728
LATENT HEAT
cfm Gr/lb BF
455 142 0.1 0.68 4393
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 5219
Supply duct Safety
leakage loss % + Factor 10% 522
TOTAL ROOM LATENT HEAT 5741
ROOM TOTAL HEAT(RTH) 46469
OUTDOOR AIR HEAT
Sensible 455 30 0.9 13268
Latent 455 142 0.9 39541
GRAND TOTAL HEAT SUB TOTAL 99278
2% 1986
GRAND TOTAL HEAT 101264
TR 8.44

B.T.U. ESTIMATION FORM


WINTER AHU 8 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 307.09864216 Height 9.84 outside 81
Volume(Cu.ft): 4260 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4260 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 2158
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 38725
wall (W) 0 6 0.15 0 RTH 41778
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 307 4 0.11 135 18.72
Floor 0 4 0.5 0 DE AIR CFM 1915
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.88777
outside air DB diff BF 1.08
455 9 0.1 1.08 442
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 3.4 2545 8580
Miscell 1 3410 3410 Heater 1.0
Lights 614.2 Watts 3.41 2618
ROOM SENSIBLE HEAT SUB TOTAL 33674
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5051
TOTAL ROOM SENSIBLE HEAT (RSH) 38725
LATENT HEAT
cfm Gr/lb BF
455 63 0.1 0.68 1949
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 37654
ROOM LATENT HEAT SUB TOTAL 2775
Supply duct Safety
leakage loss % + Factor 10% 278
TOTAL ROOM LATENT HEAT 3053
ROOM TOTAL HEAT(RTH) 41778
OUTDOOR AIR HEAT
Sensible 455 9 0.9 3980
Latent 455 63 0.9 17543
GRAND TOTAL HEAT SUB TOTAL 63301
2% 1266
GRAND TOTAL HEAT 64567
TR 5.38
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

216

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

5.38
KW 6.38
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 9 Date: 22/10/2014
Client: CONDITIONS DB WB %RH Gr/lb
Area(sq.ft) 311.84 Height 9.84 Outside 102 64 200
Volume(Cu.ft): 4328 Inside 72 50 58
Difference 30 XXX 142
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4328 Cu.ft 25.00 X ACPH
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 2189
Glass(S) 0 12 0.56 0 CFM 455 219
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 40931
wall (W) 0 27 0.15 0 RTH 46672
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50 (From tables/chart)
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 312 25 0.11 858 19.8
Floor 0 25 0.50 0 DE AIR CFM 1914
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.8746
outside air DB diff BF 1.08
455 30 0.1 1.08 1474
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 3.4 2545 8703 5.38
Miscell 1.0 3410 3410 Heater 1.0 KW 6.38
Lights 623.7 Watts 3.41 2658
ROOM SENSIBLE HEAT SUB TOTAL 35592
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5339
TOTAL ROOM SENSIBLE HEAT (RSH) 40931
LATENT HEAT
cfm Gr/lb BF
455 142 0.1 0.68 4393
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 5219
Supply duct Safety
leakage loss % + Factor 10% 522
TOTAL ROOM LATENT HEAT 5741
ROOM TOTAL HEAT(RTH) 46672
OUTDOOR AIR HEAT
Sensible 455 30 0.9 13268
Latent 455 142 0.9 39541
GRAND TOTAL HEAT SUB TOTAL 99481
2% 1990
GRAND TOTAL HEAT 101471
TR 8.46
B.T.U. ESTIMATION FORM
WINTER AHU 9 Date: 22/10/2014
Client: 0 CONDITIONS DB WB %RH Gr/lb
Area (sq.ft.) 311.84487816 Height 9.84 outside 81 76 121
Volume(Cu.ft): 4328 inside 72 50 58
Difference 9 XXX XXX 63
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4328 Cu.ft 25 X ACPH
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 2189
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 38916
wall (W) 0 6 0.15 0 RTH 41968
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2 (From tables/chart)
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 312 4 0.11 137 18.72
Floor 0 4 0.5 0 DE AIR CFM 1925
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.87951
outside air DB diff BF 1.08
455 9 0.1 1.08 442
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 3.4 2545 8703
Miscell 1 3410 3410 Heater 1.0 KW
Lights 623.7 Watts 3.41 2658
ROOM SENSIBLE HEAT SUB TOTAL 33840
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5076
TOTAL ROOM SENSIBLE HEAT (RSH) 38916
LATENT HEAT
cfm Gr/lb BF
455 63 0.1 0.68 1949
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 37820
ROOM LATENT HEAT SUB TOTAL 2775
Supply duct Safety
leakage loss % + Factor 10% 278
TOTAL ROOM LATENT HEAT 3053
ROOM TOTAL HEAT(RTH) 41968
OUTDOOR AIR HEAT
Sensible 455 9 0.9 3980
Latent 455 63 0.9 17543
GRAND TOTAL HEAT SUB TOTAL 63492
2% 1270
GRAND TOTAL HEAT 64762
TR 5.40
B.T.U. ESTIMATION FORM
Summer AHU 10 Date:
Client: CONDITIONS DB
Area(sq.ft) 307.47 Height 9.84 Outside 102
Volume(Cu.ft): 4257 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4257 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 2153
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 40713
wall (W) 0 27 0.15 0 RTH 46455
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 307 25 0.11 846 19.8
Floor 0 25 0.50 0 DE AIR CFM 1904
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.88415
outside air DB diff BF 1.08
455 30 0.1 1.08 1474
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 3.4 2545 8563
Miscell 1.0 3410 3410 Heater 1.0
Lights 614.9 Watts 3.41 2621
ROOM SENSIBLE HEAT SUB TOTAL 35403
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5310
TOTAL ROOM SENSIBLE HEAT (RSH) 40713
LATENT HEAT
cfm Gr/lb BF
455 142 0.1 0.68 4393
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 5219
Supply duct Safety
leakage loss % + Factor 10% 522
TOTAL ROOM LATENT HEAT 5741
ROOM TOTAL HEAT(RTH) 46455
OUTDOOR AIR HEAT
Sensible 455 30 0.9 13268
Latent 455 142 0.9 39541
GRAND TOTAL HEAT SUB TOTAL 99264
2% 1985
GRAND TOTAL HEAT 101249
TR 8.44

B.T.U. ESTIMATION FORM


WINTER AHU 10 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 307.46790384 Height 9.84 outside 81
Volume(Cu.ft): 4257 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4257 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 2153
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 38710
wall (W) 0 6 0.15 0 RTH 41763
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 307 4 0.11 135 18.72
Floor 0 4 0.5 0 DE AIR CFM 1915
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.88914
outside air DB diff BF 1.08
455 9 0.1 1.08 442
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 3.4 2545 8563
Miscell 1 3410 3410 Heater 1.0
Lights 614.9 Watts 3.41 2621
ROOM SENSIBLE HEAT SUB TOTAL 33661
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5049
TOTAL ROOM SENSIBLE HEAT (RSH) 38710
LATENT HEAT
cfm Gr/lb BF
455 63 0.1 0.68 1949
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 37641
ROOM LATENT HEAT SUB TOTAL 2775
Supply duct Safety
leakage loss % + Factor 10% 278
TOTAL ROOM LATENT HEAT 3053
ROOM TOTAL HEAT(RTH) 41763
OUTDOOR AIR HEAT
Sensible 455 9 0.9 3980
Latent 455 63 0.9 17543
GRAND TOTAL HEAT SUB TOTAL 63286
2% 1266
GRAND TOTAL HEAT 64552
TR 5.38
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

215

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

5.38
KW 6.38
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 11 Date:
Client: CONDITIONS DB
Area(sq.ft) 307.47 Height 9.84 Outside 102
Volume(Cu.ft): 4257 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4257 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 2153
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 40713
wall (W) 0 27 0.15 0 RTH 46455
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 307 25 0.11 846 19.8
Floor 0 25 0.50 0 DE AIR CFM 1904
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.88415
outside air DB diff BF 1.08
455 30 0.1 1.08 1474
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 3.4 2545 8563
Miscell 1.0 3410 3410 Heater 1.0
Lights 614.9 Watts 3.41 2621
ROOM SENSIBLE HEAT SUB TOTAL 35403
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5310
TOTAL ROOM SENSIBLE HEAT (RSH) 40713
LATENT HEAT
cfm Gr/lb BF
455 142 0.1 0.68 4393
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 5219
Supply duct Safety
leakage loss % + Factor 10% 522
TOTAL ROOM LATENT HEAT 5741
ROOM TOTAL HEAT(RTH) 46455
OUTDOOR AIR HEAT
Sensible 455 30 0.9 13268
Latent 455 142 0.9 39541
GRAND TOTAL HEAT SUB TOTAL 99264
2% 1985
GRAND TOTAL HEAT 101249
TR 8.44

B.T.U. ESTIMATION FORM


WINTER AHU 11 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 307.46790384 Height 9.84 outside 81
Volume(Cu.ft): 4257 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4257 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 2153
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 38710
wall (W) 0 6 0.15 0 RTH 41763
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 307 4 0.11 135 18.72
Floor 0 4 0.5 0 DE AIR CFM 1915
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.88914
outside air DB diff BF 1.08
455 9 0.1 1.08 442
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 3.4 2545 8563
Miscell 1 3410 3410 Heater 1.0
Lights 614.9 Watts 3.41 2621
ROOM SENSIBLE HEAT SUB TOTAL 33661
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5049
TOTAL ROOM SENSIBLE HEAT (RSH) 38710
LATENT HEAT
cfm Gr/lb BF
455 63 0.1 0.68 1949
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 6756
ROOM LATENT HEAT SUB TOTAL 2775
Supply duct Safety
leakage loss % + Factor 10% 278
TOTAL ROOM LATENT HEAT 3053
ROOM TOTAL HEAT(RTH) 41763
OUTDOOR AIR HEAT
Sensible 455 9 0.9 3980
Latent 455 63 0.9 17543
GRAND TOTAL HEAT SUB TOTAL 63286
2% 1266
GRAND TOTAL HEAT 64552
TR 5.38
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

215

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

5.38
KW 6.38
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 12 Date:
Client: CONDITIONS DB
Area(sq.ft) 279.13 Height 9.84 Outside 102
Volume(Cu.ft): 3839 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3839 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1979
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 43471
wall (W) 0 27 0.15 0 RTH 49212
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 279 25 0.11 768 19.8
Floor 0 25 0.50 0 DE AIR CFM 2033
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.02715
outside air DB diff BF 1.08
455 30 0.1 1.08 1474
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 3.1 2545 7870
Miscell 2.0 3410 6820 Heater 2.0
Lights 558.3 Watts 3.41 2380
ROOM SENSIBLE HEAT SUB TOTAL 37801
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5670
TOTAL ROOM SENSIBLE HEAT (RSH) 43471
LATENT HEAT
cfm Gr/lb BF
455 142 0.1 0.68 4393
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 5219
Supply duct Safety
leakage loss % + Factor 10% 522
TOTAL ROOM LATENT HEAT 5741
ROOM TOTAL HEAT(RTH) 49212
OUTDOOR AIR HEAT
Sensible 455 30 0.9 13268
Latent 455 142 0.9 39541
GRAND TOTAL HEAT SUB TOTAL 102021
2% 2040
GRAND TOTAL HEAT 104062
TR 8.67

B.T.U. ESTIMATION FORM


WINTER AHU 12 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 279.134844 Height 9.84 outside 81
Volume(Cu.ft): 3839 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3839 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1979
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 41542
wall (W) 0 6 0.15 0 RTH 44595
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 279 4 0.11 123 18.72
Floor 0 4 0.5 0 DE AIR CFM 2055
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08 1.03821
455 9 0.1 1.08 442
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 3.1 2545 7870
Miscell 2 3410 6820 Heater 2.0
Lights 558.3 Watts 3.41 2380
ROOM SENSIBLE HEAT SUB TOTAL 36124
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5419
TOTAL ROOM SENSIBLE HEAT (RSH) 41542
LATENT HEAT
cfm Gr/lb BF
455 63 0.1 0.68 1949
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 45523
ROOM LATENT HEAT SUB TOTAL 2775
Supply duct Safety
leakage loss % + Factor 10% 278
TOTAL ROOM LATENT HEAT 3053
ROOM TOTAL HEAT(RTH) 44595
OUTDOOR AIR HEAT
Sensible 455 9 0.9 3980
Latent 455 63 0.9 17543
GRAND TOTAL HEAT SUB TOTAL 66118
2% 1322
GRAND TOTAL HEAT 67441
TR 5.62
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

198

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

5.38
KW 7.38
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 14 Date:
Client: CONDITIONS DB
Area(sq.ft) 449.35 Height 9.84 Outside 102
Volume(Cu.ft): 5502 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 5502 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 2708
Glass(S) 0 12 0.56 0 CFM 1500
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 123491
wall (W) 0 27 0.15 0 RTH 140332
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 449 25 0.11 1236 19.8
Floor 0 25 0.50 0 DE AIR CFM 5775
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 2.13257
outside air DB diff BF 1.08
1500 30 0.1 1.08 4860
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 4.2 2545 10768
Miscell 20.0 3410 68200 Heater 20.0
Lights 898.7 Watts 3.41 3831
ROOM SENSIBLE HEAT SUB TOTAL 107384
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 16108
TOTAL ROOM SENSIBLE HEAT (RSH) 123491
LATENT HEAT
cfm Gr/lb BF
1500 142 0.1 0.68 14484
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 15310
Supply duct Safety
leakage loss % + Factor 10% 1531
TOTAL ROOM LATENT HEAT 16841
ROOM TOTAL HEAT(RTH) 140332
OUTDOOR AIR HEAT
Sensible 1500 30 0.9 43740
Latent 1500 142 0.9 130356 10.863
GRAND TOTAL HEAT SUB TOTAL 314428
2% 6289
GRAND TOTAL HEAT 320717
TR 26.73

B.T.U. ESTIMATION FORM


WINTER AHU 14 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 449.349167 Height 9.84 outside 81
Volume(Cu.ft): 5502 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 5502 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 2708
Glass(S) 0 12 0.56 0 CFM 1500
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 114856
wall (W) 0 6 0.15 0 RTH 122833
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.94
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.4
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 449 4 0.11 198 18.54
Floor 0 4 0.5 0 DE AIR CFM 5736
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 2.11824
outside air DB diff BF 1.08
1500 9 0.1 1.08 1458
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 4.2 2545 10768
Miscell 19.1 3410 65131 Heater 19.1
Lights 898.7 Watts 3.41 3831
ROOM SENSIBLE HEAT SUB TOTAL 99875
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 14981
TOTAL ROOM SENSIBLE HEAT (RSH) 114856
LATENT HEAT
cfm Gr/lb BF
1500 63 0.1 0.68 6426
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 127978
ROOM LATENT HEAT SUB TOTAL 7252
Supply duct Safety
leakage loss % + Factor 10% 725
TOTAL ROOM LATENT HEAT 7977
ROOM TOTAL HEAT(RTH) 122833
OUTDOOR AIR HEAT
Sensible 1500 9 0.9 13122
Latent 1500 63 0.9 57834 4.8195
GRAND TOTAL HEAT SUB TOTAL 193789
2% 3876
GRAND TOTAL HEAT 197665
TR 16.47
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

271

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

5.38
KW 25.38
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 15 Date:
Client: CONDITIONS DB
Area(sq.ft) 439.80 Height 9.84 Outside 102
Volume(Cu.ft): 4328 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4328 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 2225
Glass(S) 0 12 0.56 0 CFM 1400
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 112590
wall (W) 0 27 0.15 0 RTH 128369
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 440 25 0.11 1209 19.8
Floor 0 25 0.50 0 DE AIR CFM 5265
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 2.36662
outside air DB diff BF 1.08
1400 30 0.1 1.08 4536
INTERNAL HEAT
People 2.0 People X 337 674
HP 4.2 HP 2545 10689
Blower HP 3.5 2545 8847
Miscell 20.0 3410 68200 Heater 20.0
Lights 879.6 Watts 3.41 3749
ROOM SENSIBLE HEAT SUB TOTAL 97905
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 14686
TOTAL ROOM SENSIBLE HEAT (RSH) 112590
LATENT HEAT
cfm Gr/lb BF
1400 142 0.1 0.68 13518
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 14344
Supply duct Safety
leakage loss % + Factor 10% 1434
TOTAL ROOM LATENT HEAT 15779
ROOM TOTAL HEAT(RTH) 128369
OUTDOOR AIR HEAT
Sensible 1400 30 0.9 40824
Latent 1400 142 0.9 121666
GRAND TOTAL HEAT SUB TOTAL 290859
2% 5817
GRAND TOTAL HEAT 296676
TR 24.72

B.T.U. ESTIMATION FORM


WINTER AHU 15 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 439.797515 Height 9.84 outside 81
Volume(Cu.ft): 4328 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4328 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 2225
Glass(S) 0 12 0.56 0 CFM 1400
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 105810
wall (W) 0 6 0.15 0 RTH 113316
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 440 4 0.11 194 18.72
Floor 0 4 0.5 0 DE AIR CFM 5234
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 2.35241
outside air DB diff BF 1.08
1400 9 0.1 1.08 1361
INTERNAL HEAT
People 2.0 People X 337 674
HP 4.2 HP 2545 10689
Blower HP 3.5 2545 8847
Miscell 19.5 3410 66495 Heater 19.5
Lights 879.6 Watts 3.41 3749
ROOM SENSIBLE HEAT SUB TOTAL 92008
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 13801
TOTAL ROOM SENSIBLE HEAT (RSH) 105810
LATENT HEAT
cfm Gr/lb BF
1400 63 0.1 0.68 5998
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 118057
ROOM LATENT HEAT SUB TOTAL 6824
Supply duct Safety
leakage loss % + Factor 10% 682
TOTAL ROOM LATENT HEAT 7506
ROOM TOTAL HEAT(RTH) 113316
OUTDOOR AIR HEAT
Sensible 1400 9 0.9 12247
Latent 1400 63 0.9 53978
GRAND TOTAL HEAT SUB TOTAL 179541
2% 3591
GRAND TOTAL HEAT 183132
TR 15.26
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

222

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

3.23
KW 23.23
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 16 Date:
Client: CONDITIONS DB
Area(sq.ft) 471.18 Height 9.84 Outside 102
Volume(Cu.ft): 4636 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4636 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 2356
Glass(S) 0 12 0.56 0 CFM 1200
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 97167
wall (W) 0 27 0.15 0 RTH 110821
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 471 25 0.11 1296 19.8
Floor 0 25 0.50 0 DE AIR CFM 4544
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.92853
outside air DB diff BF 1.08
1200 30 0.1 1.08 3888
INTERNAL HEAT
People 2.0 People X 337 674
HP 4.2 HP 2545 10689
Blower HP 3.7 2545 9369
Miscell 16.0 3410 54560 Heater 16.0
Lights 942.4 Watts 3.41 4017
ROOM SENSIBLE HEAT SUB TOTAL 84493
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 12674
TOTAL ROOM SENSIBLE HEAT (RSH) 97167
LATENT HEAT
cfm Gr/lb BF
1200 142 0.1 0.68 11587
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 12413
Supply duct Safety
leakage loss % + Factor 10% 1241
TOTAL ROOM LATENT HEAT 13655
ROOM TOTAL HEAT(RTH) 110821
OUTDOOR AIR HEAT
Sensible 1200 30 0.9 34992
Latent 1200 142 0.9 104285
GRAND TOTAL HEAT SUB TOTAL 250098
2% 5002
GRAND TOTAL HEAT 255100
TR 21.26

B.T.U. ESTIMATION FORM


WINTER AHU 16 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 471.180938 Height 9.84 outside 81
Volume(Cu.ft): 4636 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4636 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 2356
Glass(S) 0 12 0.56 0 CFM 1200
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 91217
wall (W) 0 6 0.15 0 RTH 97780
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 471 4 0.11 207 18.72
Floor 0 4 0.5 0 DE AIR CFM 4512
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.91488
outside air DB diff BF 1.08
1200 9 0.1 1.08 1166
INTERNAL HEAT
People 2.0 People X 337 674
HP 4.2 HP 2545 10689
Blower HP 3.7 2545 9369
Miscell 15.6 3410 53196 Heater 15.6
Lights 942.4 Watts 3.41 4017
ROOM SENSIBLE HEAT SUB TOTAL 79319
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 11898
TOTAL ROOM SENSIBLE HEAT (RSH) 91217
LATENT HEAT
cfm Gr/lb BF
1200 63 0.1 0.68 5141
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 101714
ROOM LATENT HEAT SUB TOTAL 5967
Supply duct Safety
leakage loss % + Factor 10% 597
TOTAL ROOM LATENT HEAT 6563
ROOM TOTAL HEAT(RTH) 97780
OUTDOOR AIR HEAT
Sensible 1200 9 0.9 10498
Latent 1200 63 0.9 46267
GRAND TOTAL HEAT SUB TOTAL 154545
2% 3091
GRAND TOTAL HEAT 157636
TR 13.14
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

236

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

3.23
KW 19.23
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 17 Date:
Client: CONDITIONS DB
Area(sq.ft) 718.29 Height 9.84 Outside 102
Volume(Cu.ft): 9418 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 9418 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 4296
Glass(S) 0 12 0.56 0 CFM 450
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 59567
wall (W) 0 27 0.15 0 RTH 65255
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.91
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50.5
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 718 25 0.11 1975 19.35
Floor 0 25 0.50 0 DE AIR CFM 2850
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.66345
outside air DB diff BF 1.08
450 30 0.1 1.08 1458
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 6.7 2545 17084
Miscell 3.0 3410 10230 Heater 3.0
Lights 1436.6 Watts 3.41 6123
ROOM SENSIBLE HEAT SUB TOTAL 51797
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 7770
TOTAL ROOM SENSIBLE HEAT (RSH) 59567
LATENT HEAT
cfm Gr/lb BF
450 142 0.1 0.68 4345
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 5171
Supply duct Safety
leakage loss % + Factor 10% 517
TOTAL ROOM LATENT HEAT 5688
ROOM TOTAL HEAT(RTH) 65255
OUTDOOR AIR HEAT
Sensible 450 30 0.9 13122
Latent 450 142 0.9 39107
GRAND TOTAL HEAT SUB TOTAL 117484
2% 2350
GRAND TOTAL HEAT 119833
TR 9.99

B.T.U. ESTIMATION FORM


WINTER AHU 17 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 718.29469988 Height 9.84 outside 81
Volume(Cu.ft): 9418 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 9418 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 4296
Glass(S) 0 12 0.56 0 CFM 450
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 56485
wall (W) 0 6 0.15 0 RTH 59514
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.95
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.4
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 718 4 0.11 316 18.54
Floor 0 4 0.5 0 DE AIR CFM 2821
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.65661
outside air DB diff BF 1.08
450 9 0.1 1.08 437
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 6.7 2545 17084
Miscell 3 3410 10230 Heater 3.0
Lights 1436.6 Watts 3.41 6123
ROOM SENSIBLE HEAT SUB TOTAL 49117
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 7368
TOTAL ROOM SENSIBLE HEAT (RSH) 56485
LATENT HEAT
cfm Gr/lb BF
450 63 0.1 0.68 1928
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 60421
ROOM LATENT HEAT SUB TOTAL 2754
Supply duct Safety
leakage loss % + Factor 10% 275
TOTAL ROOM LATENT HEAT 3029
ROOM TOTAL HEAT(RTH) 59514
OUTDOOR AIR HEAT
Sensible 450 9 0.9 3937
Latent 450 63 0.9 17350
GRAND TOTAL HEAT SUB TOTAL 80801
2% 1616
GRAND TOTAL HEAT 82417
TR 6.87
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

430

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

4.31
KW 7.31
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 18 Date:
Client: CONDITIONS DB
Area(sq.ft) 778.84 Height 9.84 Outside 102
Volume(Cu.ft): 9996 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 9996 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 4540
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 53820
wall (W) 0 27 0.15 0 RTH 60582
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.89
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 779 25 0.11 2142 16.2
Floor 0 25 0.50 0 DE AIR CFM 3076
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.6775
outside air DB diff BF 1.08
455 30 0.1 1.08 1474
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 7.1 2545 18055
Miscell 3410 0 Heater 0.0
Lights 1557.7 Watts 3.41 6640
ROOM SENSIBLE HEAT SUB TOTAL 46800
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 7020
TOTAL ROOM SENSIBLE HEAT (RSH) 53820
LATENT HEAT
cfm Gr/lb BF
455 172 0.1 0.68 5322
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 6148
Supply duct Safety
leakage loss % + Factor 10% 615
TOTAL ROOM LATENT HEAT 6762
ROOM TOTAL HEAT(RTH) 60582
OUTDOOR AIR HEAT
Sensible 455 30 0.9 13268
Latent 455 172 0.9 47895
GRAND TOTAL HEAT SUB TOTAL 121745
2% 2435
GRAND TOTAL HEAT 124180
TR 10.35

B.T.U. ESTIMATION FORM


WINTER AHU 18 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 778.839466 Height 9.84 outside 81
Volume(Cu.ft): 9996 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 9996 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 4540
Glass(S) 0 12 0.56 0 CFM 455
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 53309
wall (W) 0 6 0.15 0 RTH 57383
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 779 4 0.11 343 16.2
Floor 0 4 0.5 0 DE AIR CFM 3047
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.67107
outside air DB diff BF 1.08
455 9 0.1 1.08 442
INTERNAL HEAT
People 2.0 People X 337 674
HP 7.0 HP 2545 17815
Blower HP 7.1 2545 18055
Miscell 0.7 3410 2387 Heater 0.7
Lights 1557.7 Watts 3.41 6640
ROOM SENSIBLE HEAT SUB TOTAL 46356
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 6953
TOTAL ROOM SENSIBLE HEAT (RSH) 53309
LATENT HEAT
cfm Gr/lb BF
455 93 0.1 0.68 2877
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 57289
ROOM LATENT HEAT SUB TOTAL 3703
Supply duct Safety
leakage loss % + Factor 10% 370
TOTAL ROOM LATENT HEAT 4074
ROOM TOTAL HEAT(RTH) 57383
OUTDOOR AIR HEAT
Sensible 455 9 0.9 3980
Latent 455 93 0.9 25897
GRAND TOTAL HEAT SUB TOTAL 87260
2% 1745
GRAND TOTAL HEAT 89005
TR 7.42
22/10/2014
WB %RH Gr/lb
64 200
25 28
XXX 172

`
VENTILATION
25.00 X ACPH `

454

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

5.38
KW 6.08
22/10/2014
WB %RH Gr/lb
76 121
25 28
XXX XXX 93

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
outside monsoon conditio 86 167.2 Fresh Air 78
inside condition 73.4 15.8 Deh. CFM 3076
151.4
DEHUMDIFIER CALCULATION

PERMEATION LOAD
VOL GR DIFF F1 F2 F3 F4
2717 151.40 3.74 0.65 0.67

DOOR LOAD
NO.OF
OP/HR AREA GR DIFF F1 DOORS
1 42 151.40 3.74 2
0 34 151.40 3.74 2
PEOPLE LOAD
NO. OF PEOPLE F5
2 2540

FIXED OPENING

SAFETY FACTOR 5%

TOTAL ROOM LOAD

7.88 CFM REQD


1847.77 1848 REQUIRED CFM

MAKE UP AIR LOAD


15444

TOTAL GRAINS PER HOUR

MIXING GRAINS
ROOM AIR 1848 DESIGN GR 15.8
FA 78 AMBIENT GR 62
DEH I/L GR 17.7
DESIGN T( F ) 73.4
PRE COOL T( F ) 54
DEH I/L T( F ) 72.6
DEH I/L T( C ) 22.6
DEH SIZING
10.9021 2694 CFM
4580 CMH
SELECTED MODEL FLP 6200 CMH

CFM 588 Temp 108.5 gr/lb 17.404


CFM 381 Temp 72 gr/lb 46.570

TEMP 94.15 gr/lb 28.87


3647.06

occupant
occupant doing doing
Occupan
Dry bulb temperature light physical heavy
ts at rest
exertion physical
Exertion
F (gr/hr) (gr/hr) (gr/hr)
60 400 1300 1960 INTERPOLAT
65 530 1630 2400 X1
70 670 2060 2920 X2
75 900 2540 3450 X3
80 1180 3040 3950
85 1525 3550 4450
90 1870 4000 5000
4462
GR/HR

47857 3569 CFM/ 73.4 F/ 15.8 Gr/lb

6795 SELECTED MODEL 6200


0

0
5080

0 3569.1 CFM/ 73.4 F/ 15.8 Gr/lb

2987

62719 78 CFM/ 54 F/ 62 Gr/lb


fix fix

PRE COOLING COIL


value
2.2571 23 1 7.0
15444

78163

value
2.5245 23.000 1.45 10.2
INTERPOLATION
70 Y1 2060
72 Y2 2252.00
75 Y3 2540
78 CFM

4540 CFM/ 58 F/ 11 Gr/lb


ROOM
3647

893 CFM/ 73.4 F/ 15.8 Gr/lb AFTER COOLING COIL

3647
0 CFM/ 73.4 F/ 15.80 Gr/lb

3647.1 CFM/ 73.0 F/ 16.8 Gr/lb

DEHUMIDIFIER
3647.1 CFM/ 106 F/ 10.18 Gr/lb

value
2.398 22.8 1.35 9.45
PRE COOLING COIL temp 41

78 CFM/ 86 F/ 167 Gr/lb

PCC 5.84 ENTHALPY DIFF.


ACC 17.00 TEMP DIFF.
CFM/ 54.0 F/ 10.18 Gr/lb

R COOLING COIL

CFM/ ### F/ 10.18 Gr/lb

5577
B.T.U. ESTIMATION FORM
Summer AHU 19 Date:
Client: CONDITIONS DB
Area(sq.ft) 391.96 Height 9.84 Outside 102
Volume(Cu.ft): 3857 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3857 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1607
Glass(S) 0 12 0.56 0 CFM 1650
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 36060
wall (W) 0 27 0.15 0 RTH 42227
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.85
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 49.1
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 392 25 0.11 1078 20.61
Floor 0 25 0.50 0 DE AIR CFM 1620
Partition 388 25 0.11 1066 NOTES
INFILTRATION & OUTSIDE AIR 1.0081
outside air DB diff BF 1.08
1650 30 0.1 1.08 1604
INTERNAL HEAT
People 2.0 People X 337 674
HP 1.4 HP 2545 3563
Blower HP 2.5 2545 6390
Miscell 4.0 3410 13640 Heater 4.0
Lights 783.9 Watts 3.41 3341
ROOM SENSIBLE HEAT SUB TOTAL 31357
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4704
TOTAL ROOM SENSIBLE HEAT (RSH) 36060
LATENT HEAT
cfm Gr/lb BF
1650 142 0.1 0.68 4780
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 5606
Supply duct Safety
leakage loss % + Factor 10% 561
TOTAL ROOM LATENT HEAT 6166
ROOM TOTAL HEAT(RTH) 42227
OUTDOOR AIR HEAT
Sensible 1650 30 0.9 14434
Latent 1650 142 0.9 43017
GRAND TOTAL HEAT SUB TOTAL 99678
2% 1994
GRAND TOTAL HEAT 101672
TR 8.47

B.T.U. ESTIMATION FORM


WINTER AHU 19 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 391.95819992 Height 9.84 outside 81
Volume(Cu.ft): 3857 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3857 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1607
Glass(S) 0 12 0.56 0 CFM 1650
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 32698
wall (W) 0 6 0.15 0 RTH 35939
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.91
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50.8
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 392 4 0.11 172 19.08
Floor 0 4 0.5 0 DE AIR CFM 1587
Partition 388 4 0.11 171 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08 0.98741
1650 9 0.1 1.08 481
INTERNAL HEAT
People 2.0 People X 337 674
HP 1.4 HP 2545 3563
Blower HP 2.5 2545 6390
Miscell 4 3410 13640 Heater 4.0
Lights 783.9 Watts 3.41 3341
ROOM SENSIBLE HEAT SUB TOTAL 28433
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4265
TOTAL ROOM SENSIBLE HEAT (RSH) 32698
LATENT HEAT
cfm Gr/lb BF
1650 63 0.1 0.68 2121
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 37028
ROOM LATENT HEAT SUB TOTAL 2947
Supply duct Safety
leakage loss % + Factor 10% 295
TOTAL ROOM LATENT HEAT 3241
ROOM TOTAL HEAT(RTH) 35939
OUTDOOR AIR HEAT
Sensible 1650 9 0.9 4330
Latent 1650 63 0.9 19085
GRAND TOTAL HEAT SUB TOTAL 59355
2% 1187
GRAND TOTAL HEAT 60542
TR 5.05
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

161

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

1.08
KW 5.08
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 20 Date:
Client: CONDITIONS DB
Area(sq.ft) 481.31 Height 9.84 Outside 102
Volume(Cu.ft): 4736 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4736 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 2367
Glass(S) 0 12 0.56 0 CFM 350
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 33995
wall (W) 0 27 0.15 0 RTH 38621
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 481 25 0.11 1324 19.8
Floor 0 25 0.50 0 DE AIR CFM 1590
Partition 272 25 0.11 748 NOTES
INFILTRATION & OUTSIDE AIR 0.67156
outside air DB diff BF 1.08
350 30 0.1 1.08 1134
INTERNAL HEAT
People 2.0 People X 337 674
HP 2.1 HP 2545 5345
Blower HP 3.7 2545 9414
Miscell 2.0 3410 6820 Heater 2.0
Lights 962.6 Watts 3.41 4103
ROOM SENSIBLE HEAT SUB TOTAL 29561
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4434
TOTAL ROOM SENSIBLE HEAT (RSH) 33995
LATENT HEAT
cfm Gr/lb BF
350 142 0.1 0.68 3380
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 4206
Supply duct Safety
leakage loss % + Factor 10% 421
TOTAL ROOM LATENT HEAT 4626
ROOM TOTAL HEAT(RTH) 38621
OUTDOOR AIR HEAT
Sensible 350 30 0.9 10206
Latent 350 142 0.9 30416
GRAND TOTAL HEAT SUB TOTAL 79244
2% 1585
GRAND TOTAL HEAT 80829
TR 6.74

B.T.U. ESTIMATION FORM


WINTER AHU 20 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 481.31094 Height 9.84 outside 81
Volume(Cu.ft): 4736 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 4736 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 2367
Glass(S) 0 12 0.56 0 CFM 350
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 31081
wall (W) 0 6 0.15 0 RTH 33639
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.92
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 481 4 0.11 212 18.9
Floor 0 4 0.5 0 DE AIR CFM 1523
Partition 272 4 0.11 120 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08 0.64323
350 9 0.1 1.08 340
INTERNAL HEAT
People 2.0 People X 337 674
HP 2.1 HP 2545 5345
Blower HP 3.7 2545 9414
Miscell 2 3410 6820 Heater 2.0
Lights 962.6 Watts 3.41 4103
ROOM SENSIBLE HEAT SUB TOTAL 27027
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4054
TOTAL ROOM SENSIBLE HEAT (RSH) 31081
LATENT HEAT
cfm Gr/lb BF
350 63 0.1 0.68 1499
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 34143
ROOM LATENT HEAT SUB TOTAL 2325
Supply duct Safety
leakage loss % + Factor 10% 233
TOTAL ROOM LATENT HEAT 2558
ROOM TOTAL HEAT(RTH) 33639
OUTDOOR AIR HEAT
Sensible 350 9 0.9 3062
Latent 350 63 0.9 13495
GRAND TOTAL HEAT SUB TOTAL 50195
2% 1004
GRAND TOTAL HEAT 51199
TR 4.27
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
10 X ACPH `

237

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

1.62
KW 3.62
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
10 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 21 Date:
Client: CONDITIONS DB
Area(sq.ft) 605.15 Height 9.84 Outside 102
Volume(Cu.ft): 5955 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 5955 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 2905
Glass(S) 0 12 0.56 0 CFM 400
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 34417
wall (W) 0 27 0.15 0 RTH 40842
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.84
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 605 25 0.11 1664 16.2
Floor 0 25 0.50 0 DE AIR CFM 1967
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.67708
outside air DB diff BF 1.08
400 30 0.1 1.08 1296
INTERNAL HEAT
People 4.0 People X 337 1348
HP 3.5 HP 2545 8908
Blower HP 4.5 2545 11553
Miscell 3410 0 Heater 0.0
Lights 1210.3 Watts 3.41 5159
ROOM SENSIBLE HEAT SUB TOTAL 29928
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4489
TOTAL ROOM SENSIBLE HEAT (RSH) 34417
LATENT HEAT
cfm Gr/lb BF
400 154 0.1 0.68 4189
People 4.0 People X 413 1652
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 5841
Supply duct Safety
leakage loss % + Factor 10% 584
TOTAL ROOM LATENT HEAT 6425
ROOM TOTAL HEAT(RTH) 40842
OUTDOOR AIR HEAT
Sensible 400 30 0.9 11664
Latent 400 154 0.9 37699
GRAND TOTAL HEAT SUB TOTAL 90205
2% 1804
GRAND TOTAL HEAT 92009
TR 7.67

B.T.U. ESTIMATION FORM


WINTER AHU 21 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 605.15189032 Height 9.84 outside 81
Volume(Cu.ft): 5955 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 5955 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 2905
Glass(S) 0 12 0.56 0 CFM 400
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 34119
wall (W) 0 6 0.15 0 RTH 38180
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.89
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 605 4 0.11 266 16.2
Floor 0 4 0.5 0 DE AIR CFM 1950
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.67122
outside air DB diff BF 1.08
400 9 0.1 1.08 389
INTERNAL HEAT
People 4.0 People X 337 1348
HP 3.5 HP 2545 8908
Blower HP 4.5 2545 11553
Miscell 0.6 3410 2046 Heater 0.6
Lights 1210.3 Watts 3.41 5159
ROOM SENSIBLE HEAT SUB TOTAL 29669
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4450
TOTAL ROOM SENSIBLE HEAT (RSH) 34119
LATENT HEAT
cfm Gr/lb BF
400 75 0.1 0.68 2040
People 4.0 People X 413 1652
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 37618
ROOM LATENT HEAT SUB TOTAL 3692
Supply duct Safety
leakage loss % + Factor 10% 369
TOTAL ROOM LATENT HEAT 4061
ROOM TOTAL HEAT(RTH) 38180
OUTDOOR AIR HEAT
Sensible 400 9 0.9 3499
Latent 400 75 0.9 18360
GRAND TOTAL HEAT SUB TOTAL 60039
2% 1201
GRAND TOTAL HEAT 61240
TR 5.10
22/10/2014
WB %RH Gr/lb
64 200
40 46
XXX 154

`
VENTILATION
25.00 X ACPH `

291

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

2.69
KW 3.29
22/10/2014
WB %RH Gr/lb
76 121
40 46
XXX XXX 75

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
outside monsoon conditio 102 200
inside condition 72 46
154
DEHUMDIFIER CALCULATION

PERMEATION LOAD
VOL GR DIFF F1 F2
5955 154.00 3.8 0.65

DOOR LOAD
OP/HR AREA GR DIFF F1
2 21 154.00 3.8
2 34 154.00 3.8
PEOPLE LOAD
NO. OF PEOPLE F5
4 2255

FIXED OPENING

SAFETY FACTOR 5%

TOTAL ROOM LOAD

16.57 CFM REQD


883.54 884

MAKE UP AIR LOAD


27429

TOTAL GRAINS PER HOUR

MIXING GRAINS
ROOM AIR 884 DESIGN GR 46
FA 400 AMBIENT GR 62
DEH I/L GR 51.0
DESIGN T( F ) 72
PRE COOL T( F ) 54
DEH I/L T( F ) 66.4
DEH I/L T( C ) 19.1
DEH SIZING
18.9586212 1012 CFM
1720 CMH
SELECTED MODEL FLP 2000 CMH

CFM 588 Temp 108.5


CFM 381 Temp 72
TEMP ###
Fresh Air 400
Deh. CFM 1967

LCULATION 2505
GR/HR

F3,F4
0.5 80895 1566

NO.OF DOORS
3 10534 SELECTED MODEL
1 5685

9020

0 776.5

5307

111440 400

REQUIRED CFM

6.571428571
27429

HOUR 138868

7.283744576

gr/lb ###
gr/lb ###
gr/lb 28.87

1176.47058824
CFM/ 72 F/ 46 Gr/lb ROOM

2000 939 CFM/

790
790 CFM/

CFM/ 72 F/ 46 Gr/lb
### CFM/ 65.9 F/

DEHUMIIFIER

CFM/ 54 F/ 62 Gr/lb
fix fix
PRE COOLING
COIL
value
22.22222222 1.9 ### 400 CFM/ 102 F/

value PCC 4.71


22.222 2.2 ### ACC 7.05
400 CFM

2905 CFM/ 60 F/ 35
ROOM

72 F/ 46 Gr/lb AFTER COOLING COIL

72.0 F/ 46.00 Gr/lb

51.4 Gr/lb

DEHUMIIFIER
1176.5 CFM/ 108.5 F/ 19.319

value
7.348571429### 2.25
temp

200 Gr/lb

ENTHALPY DIFF.
TEMP DIFF.
Gr/lb

1966 CFM/ ### F/ ### Gr/lb

OLING COIL

1966 CFM/ ### F/ ### Gr/lb

Gr/lb

15.75 789
42.5
B.T.U. ESTIMATION FORM
Summer AHU 22 Date:
Client: CONDITIONS DB
Area(sq.ft) 821.18 Height 9.84 Outside 102
Volume(Cu.ft): 8080 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 8080 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 3367
Glass(S) 0 12 0.56 0 CFM 350
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 47484
wall (W) 0 27 0.15 0 RTH 51201
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.93
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 821 25 0.11 2258 18.72
Floor 0 25 0.50 0 DE AIR CFM 2349
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.69758
outside air DB diff BF 1.08
350 30 0.1 1.08 1134
INTERNAL HEAT
People 0.0 People X 337 0
HP 4.2 HP 2545 10689
Blower HP 5.3 2545 13388
Miscell 2.0 3410 6820 Heater 2.0
Lights 1642.4 Watts 3.41 7001
ROOM SENSIBLE HEAT SUB TOTAL 41290
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 6194
TOTAL ROOM SENSIBLE HEAT (RSH) 47484
LATENT HEAT
cfm Gr/lb BF
350 142 0.1 0.68 3380
People 0.0 People X 413 0
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 3380
Supply duct Safety
leakage loss % + Factor 10% 338
TOTAL ROOM LATENT HEAT 3718
ROOM TOTAL HEAT(RTH) 51201
OUTDOOR AIR HEAT
Sensible 350 30 0.9 10206
Latent 350 142 0.9 30416
GRAND TOTAL HEAT SUB TOTAL 91824
2% 1836
GRAND TOTAL HEAT 93660
TR 7.81

B.T.U. ESTIMATION FORM


WINTER AHU 22 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 821.18219648 Height 9.84 outside 81
Volume(Cu.ft): 8080 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 8080 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 3367
Glass(S) 0 12 0.56 0 CFM 350
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 44390
wall (W) 0 6 0.15 0 RTH 46039
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.96
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.7
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 821 4 0.11 361 18.27
Floor 0 4 0.5 0 DE AIR CFM 2250
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.66818
outside air DB diff BF 1.08
350 9 0.1 1.08 340
INTERNAL HEAT
People 0.0 People X 337 0
HP 4.2 HP 2545 10689
Blower HP 5.3 2545 13388
Miscell 2 3410 6820 Heater 2.0
Lights 1642.4 Watts 3.41 7001
ROOM SENSIBLE HEAT SUB TOTAL 38600
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5790
TOTAL ROOM SENSIBLE HEAT (RSH) 44390
LATENT HEAT
cfm Gr/lb BF
350 63 0.1 0.68 1499
People 0.0 People X 413 0
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 47451
ROOM LATENT HEAT SUB TOTAL 1499
Supply duct Safety
leakage loss % + Factor 10% 150
TOTAL ROOM LATENT HEAT 1649
ROOM TOTAL HEAT(RTH) 46039
OUTDOOR AIR HEAT
Sensible 350 9 0.9 3062
Latent 350 63 0.9 13495
GRAND TOTAL HEAT SUB TOTAL 62595
2% 1252
GRAND TOTAL HEAT 63847
TR 5.32
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

337

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

3.23
KW 5.23
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 23 Date:
Client: CONDITIONS DB
Area(sq.ft) 362.95 Height 9.84 Outside 102
Volume(Cu.ft): 3571 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3571 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1911
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 60761
wall (W) 0 27 0.15 0 RTH 69370
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 363 25 0.11 998 19.8
Floor 0 25 0.50 0 DE AIR CFM 2841
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.48709
outside air DB diff BF 1.08
725 30 0.1 1.08 2349
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 3.0 2545 7598
Miscell 7.0 3410 23870 Heater 7.0
Lights 725.9 Watts 3.41 3094
ROOM SENSIBLE HEAT SUB TOTAL 52835
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 7925
TOTAL ROOM SENSIBLE HEAT (RSH) 60761
LATENT HEAT
cfm Gr/lb BF
725 142 0.1 0.68 7001
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 7827
Supply duct Safety
leakage loss % + Factor 10% 783
TOTAL ROOM LATENT HEAT 8609
ROOM TOTAL HEAT(RTH) 69370
OUTDOOR AIR HEAT
Sensible 725 30 0.9 21141
Latent 725 142 0.9 63005
GRAND TOTAL HEAT SUB TOTAL 153516
2% 3070
GRAND TOTAL HEAT 156587
TR 13.05

B.T.U. ESTIMATION FORM


WINTER AHU 23 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 362.9543832 Height 9.84 outside 81
Volume(Cu.ft): 3571 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3571 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1911
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 57906
wall (W) 0 6 0.15 0 RTH 62231
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 363 4 0.11 160 18.72
Floor 0 4 0.5 0 DE AIR CFM 2864
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
725 9 0.1 1.08 705
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 3.0 2545 7598
Miscell 7 3410 23870 Heater 7.0
Lights 725.9 Watts 3.41 3094
ROOM SENSIBLE HEAT SUB TOTAL 50353
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 7553
TOTAL ROOM SENSIBLE HEAT (RSH) 57906
LATENT HEAT
cfm Gr/lb BF
725 63 0.1 0.68 3106
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 64248
ROOM LATENT HEAT SUB TOTAL 3932
Supply duct Safety
leakage loss % + Factor 10% 393
TOTAL ROOM LATENT HEAT 4325
ROOM TOTAL HEAT(RTH) 62231
OUTDOOR AIR HEAT
Sensible 725 9 0.9 6342
Latent 725 63 0.9 27953
GRAND TOTAL HEAT SUB TOTAL 96526
2% 1931
GRAND TOTAL HEAT 98457
TR 8.20
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

191

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

4.31
KW 11.31
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 24 Date:
Client: CONDITIONS DB
Area(sq.ft) 353.34 Height 9.84 Outside 102
Volume(Cu.ft): 3477 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3477 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1871
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 60456
wall (W) 0 27 0.15 0 RTH 69065
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 353 25 0.11 972 19.8
Floor 0 25 0.50 0 DE AIR CFM 2827
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.51079
outside air DB diff BF 1.08
725 30 0.1 1.08 2349
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 2.9 2545 7441
Miscell 7.0 3410 23870 Heater 7.0
Lights 706.7 Watts 3.41 3012
ROOM SENSIBLE HEAT SUB TOTAL 52570
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 7886
TOTAL ROOM SENSIBLE HEAT (RSH) 60456
LATENT HEAT
cfm Gr/lb BF
725 142 0.1 0.68 7001
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 7827
Supply duct Safety
leakage loss % + Factor 10% 783
TOTAL ROOM LATENT HEAT 8609
ROOM TOTAL HEAT(RTH) 69065
OUTDOOR AIR HEAT
Sensible 725 30 0.9 21141
Latent 725 142 0.9 63005
GRAND TOTAL HEAT SUB TOTAL 153211
2% 3064
GRAND TOTAL HEAT 156276
TR 13.02

B.T.U. ESTIMATION FORM


WINTER AHU 24 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 353.340108 Height 9.84 outside 81
Volume(Cu.ft): 3477 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3477 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1871
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 57626
wall (W) 0 6 0.15 0 RTH 61951
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 353 4 0.11 155 18.72
Floor 0 4 0.5 0 DE AIR CFM 2850
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
725 9 0.1 1.08 705
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 2.9 2545 7441
Miscell 7 3410 23870 Heater 7.0
Lights 706.7 Watts 3.41 3012
ROOM SENSIBLE HEAT SUB TOTAL 50110
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 7516
TOTAL ROOM SENSIBLE HEAT (RSH) 57626
LATENT HEAT
cfm Gr/lb BF
725 63 0.1 0.68 3106
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 63969
ROOM LATENT HEAT SUB TOTAL 3932
Supply duct Safety
leakage loss % + Factor 10% 393
TOTAL ROOM LATENT HEAT 4325
ROOM TOTAL HEAT(RTH) 61951
OUTDOOR AIR HEAT
Sensible 725 9 0.9 6342
Latent 725 63 0.9 27953
GRAND TOTAL HEAT SUB TOTAL 96247
2% 1925
GRAND TOTAL HEAT 98172
TR 8.18
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

187

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

4.31
KW 11.31
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 25 Date:
Client: CONDITIONS DB
Area(sq.ft) 359.33 Height 9.84 Outside 102
Volume(Cu.ft): 3536 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3536 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1896
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 60646
wall (W) 0 27 0.15 0 RTH 69255
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 359 25 0.11 988 19.8
Floor 0 25 0.50 0 DE AIR CFM 2836
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.4959
outside air DB diff BF 1.08
725 30 0.1 1.08 2349
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 3.0 2545 7539
Miscell 7.0 3410 23870 Heater 7.0
Lights 718.7 Watts 3.41 3063
ROOM SENSIBLE HEAT SUB TOTAL 52736
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 7910
TOTAL ROOM SENSIBLE HEAT (RSH) 60646
LATENT HEAT
cfm Gr/lb BF
725 142 0.1 0.68 7001
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 7827
Supply duct Safety
leakage loss % + Factor 10% 783
TOTAL ROOM LATENT HEAT 8609
ROOM TOTAL HEAT(RTH) 69255
OUTDOOR AIR HEAT
Sensible 725 30 0.9 21141
Latent 725 142 0.9 63005
GRAND TOTAL HEAT SUB TOTAL 153402
2% 3068
GRAND TOTAL HEAT 156470
TR 13.04

B.T.U. ESTIMATION FORM


WINTER AHU 25 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 359.33399828 Height 9.84 outside 81
Volume(Cu.ft): 3536 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3536 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1896
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 57800
wall (W) 0 6 0.15 0 RTH 62125
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 359 4 0.11 158 18.72
Floor 0 4 0.5 0 DE AIR CFM 2859
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.50796
outside air DB diff BF 1.08
725 9 0.1 1.08 705
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 3.0 2545 7539
Miscell 7 3410 23870 Heater 7.0
Lights 718.7 Watts 3.41 3063
ROOM SENSIBLE HEAT SUB TOTAL 50261
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 7539
TOTAL ROOM SENSIBLE HEAT (RSH) 57800
LATENT HEAT
cfm Gr/lb BF
725 63 0.1 0.68 3106
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 64143
ROOM LATENT HEAT SUB TOTAL 3932
Supply duct Safety
leakage loss % + Factor 10% 393
TOTAL ROOM LATENT HEAT 4325
ROOM TOTAL HEAT(RTH) 62125
OUTDOOR AIR HEAT
Sensible 725 9 0.9 6342
Latent 725 63 0.9 27953
GRAND TOTAL HEAT SUB TOTAL 96421
2% 1928
GRAND TOTAL HEAT 98349
TR 8.20
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

190

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

4.31
KW 11.31
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 25 Date:
Client: CONDITIONS DB
Area(sq.ft) 359.33 Height 9.84 Outside 102
Volume(Cu.ft): 3536 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3536 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1896
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 33195
wall (W) 0 27 0.15 0 RTH 42455
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.78
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 359 25 0.11 988 16.2
Floor 0 25 0.50 0 DE AIR CFM 1897
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.00076
outside air DB diff BF 1.08
725 30 0.1 1.08 2349
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 3.0 2545 7539
Miscell 3410 0 Heater 0.0
Lights 718.7 Watts 3.41 3063
ROOM SENSIBLE HEAT SUB TOTAL 28866
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4330
TOTAL ROOM SENSIBLE HEAT (RSH) 33195
LATENT HEAT
cfm Gr/lb BF
725 154 0.1 0.68 7592
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 8418
Supply duct Safety
leakage loss % + Factor 10% 842
TOTAL ROOM LATENT HEAT 9260
ROOM TOTAL HEAT(RTH) 42455
OUTDOOR AIR HEAT
Sensible 725 30 0.9 21141
Latent 725 154 0.9 68330
GRAND TOTAL HEAT SUB TOTAL 131926
2% 2639
GRAND TOTAL HEAT 134565
TR 11.21

B.T.U. ESTIMATION FORM


WINTER AHU 25 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 359.33399828 Height 9.84 outside 81
Volume(Cu.ft): 3536 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3536 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1896
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 32311
wall (W) 0 6 0.15 0 RTH 37286
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.87
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 359 4 0.11 158 16.2
Floor 0 4 0.5 0 DE AIR CFM 1847
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.97408
outside air DB diff BF 1.08
725 9 0.1 1.08 705
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 3.0 2545 7539
Miscell 0.5 3410 1705 Heater 0.5
Lights 718.7 Watts 3.41 3063
ROOM SENSIBLE HEAT SUB TOTAL 28096
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4214
TOTAL ROOM SENSIBLE HEAT (RSH) 32311
LATENT HEAT
cfm Gr/lb BF
725 75 0.1 0.68 3698
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 38653
ROOM LATENT HEAT SUB TOTAL 4524
Supply duct Safety
leakage loss % + Factor 10% 452
TOTAL ROOM LATENT HEAT 4976
ROOM TOTAL HEAT(RTH) 37286
OUTDOOR AIR HEAT
Sensible 725 9 0.9 6342
Latent 725 75 0.9 33278
GRAND TOTAL HEAT SUB TOTAL 76906
2% 1538
GRAND TOTAL HEAT 78444
TR 6.54
22/10/2014
WB %RH Gr/lb
64 200
40 46
XXX 154

`
VENTILATION
25.00 X ACPH `

190

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

4.31
KW 4.81
22/10/2014
WB %RH Gr/lb
76 121
40 46
XXX XXX 75

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
outside monsoon conditio 102 200 Fresh Air 725
inside condition 72 46 Deh. CFM 1897
154
DEHUMDIFIER CALCULATION

PERMEATION LOAD
VOL GR DIFF F1 F2 F3,F4
3536 154.00 3.8 0.65 0.5

DOOR LOAD
NO.OF
OP/HR AREA GR DIFF F1 DOORS
2 21 154.00 3.8 1
2 34 154.00 3.8 1
PEOPLE LOAD
NO. OF PEOPLE F5
2 2255

FIXED OPENING

SAFETY FACTOR 5%

TOTAL ROOM LOAD

16.885 CFM REQD


519.54 520 REQUIRED CFM

MAKE UP AIR LOAD


49714

TOTAL GRAINS PER HOUR

MIXING GRAINS
ROOM AIR 520 DESIGN GR 46
FA 725 AMBIENT GR 62
DEH I/L GR 55.3
DESIGN T( F ) 72
PRE COOL T( F ) 54
DEH I/L T( F ) 61.5
DEH I/L T( C ) 16.4
DEH SIZING
21.9121 800 CFM
1360 CMH
SELECTED MODEL FLP 1500 CMH

CFM 588 Temp 108.5 gr/lb 17.404


CFM 381 Temp 72 gr/lb 46.570

TEMP 94.15 gr/lb 28.87


1175
GR/HR

48034 1175 CFM/ 72 F/ 46

3511 SELECTED MODEL 1500


5685

1018
4510

0 157.4 CFM/ 72 F/ 46

3087

64827 725 CFM/ 54 F/ 62


fix fix

value
6.57143 22.2222 1.95 13.7
49714

114542

value
7.90296 22.222 2.6 18.2
725 CFM

Gr/lb ROOM

0 CFM/ 72 F/ 46

1018 CFM/ 72.0 F/ 46.00

Gr/lb
882.4 CFM/ 57.2 F/ 59.1 Gr/lb

DEHUMIIFIER

Gr/lb

PRE COOLING COIL

725 CFM/ 102 F/ 200 Gr/lb

PCC 8.54 ENTHALPY DIFF.


ACC 5.59 TEMP DIFF.
1900 CFM/ 55 F/ 34 Gr/lb

1900 CFM/ 55.0 F/

Gr/lb AFTER COOLING COIL

1900 CFM/ 87.7 F/


Gr/lb

882.4 CFM/ 105.8 F/ 19.1447 Gr/lb

value
8.44952 14.0 2.1 14.7
temp 41
33.53 Gr/lb

33.53 Gr/lb

5577
B.T.U. ESTIMATION FORM
Summer AHU 26 Date:
Client: CONDITIONS DB
Area(sq.ft) 353.34 Height 9.84 Outside 102
Volume(Cu.ft): 3477 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3477 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1871
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 60456
wall (W) 0 27 0.15 0 RTH 69065
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 353 25 0.11 972 19.8
Floor 0 25 0.50 0 DE AIR CFM 2827
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.51079
outside air DB diff BF 1.08
725 30 0.1 1.08 2349
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 2.9 2545 7441
Miscell 7.0 3410 23870 Heater 7.0
Lights 706.7 Watts 3.41 3012
ROOM SENSIBLE HEAT SUB TOTAL 52570
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 7886
TOTAL ROOM SENSIBLE HEAT (RSH) 60456
LATENT HEAT
cfm Gr/lb BF
725 142 0.1 0.68 7001
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 7827
Supply duct Safety
leakage loss % + Factor 10% 783
TOTAL ROOM LATENT HEAT 8609
ROOM TOTAL HEAT(RTH) 69065
OUTDOOR AIR HEAT
Sensible 725 30 0.9 21141
Latent 725 142 0.9 63005
GRAND TOTAL HEAT SUB TOTAL 153211
2% 3064
GRAND TOTAL HEAT 156276
TR 13.02

B.T.U. ESTIMATION FORM


WINTER AHU 26 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 353.340108 Height 9.84 outside 81
Volume(Cu.ft): 3477 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3477 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1871
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 57626
wall (W) 0 6 0.15 0 RTH 61951
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 353 4 0.11 155 18.72
Floor 0 4 0.5 0 DE AIR CFM 2850
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
725 9 0.1 1.08 705
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 2.9 2545 7441
Miscell 7 3410 23870 Heater 7.0
Lights 706.7 Watts 3.41 3012
ROOM SENSIBLE HEAT SUB TOTAL 50110
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 7516
TOTAL ROOM SENSIBLE HEAT (RSH) 57626
LATENT HEAT
cfm Gr/lb BF
725 63 0.1 0.68 3106
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 63969
ROOM LATENT HEAT SUB TOTAL 3932
Supply duct Safety
leakage loss % + Factor 10% 393
TOTAL ROOM LATENT HEAT 4325
ROOM TOTAL HEAT(RTH) 61951
OUTDOOR AIR HEAT
Sensible 725 9 0.9 6342
Latent 725 63 0.9 27953
GRAND TOTAL HEAT SUB TOTAL 96247
2% 1925
GRAND TOTAL HEAT 98172
TR 8.18
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

187

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

4.31
KW 11.31
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 26 Date:
Client: CONDITIONS DB
Area(sq.ft) 353.34 Height 9.84 Outside 102
Volume(Cu.ft): 3477 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3477 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1871
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 33005
wall (W) 0 27 0.15 0 RTH 42265
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.78
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 353 25 0.11 972 16.2
Floor 0 25 0.50 0 DE AIR CFM 1886
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.00809
outside air DB diff BF 1.08
725 30 0.1 1.08 2349
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 2.9 2545 7441
Miscell 3410 0 Heater 0.0
Lights 706.7 Watts 3.41 3012
ROOM SENSIBLE HEAT SUB TOTAL 28700
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4305
TOTAL ROOM SENSIBLE HEAT (RSH) 33005
LATENT HEAT
cfm Gr/lb BF
725 154 0.1 0.68 7592
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 8418
Supply duct Safety
leakage loss % + Factor 10% 842
TOTAL ROOM LATENT HEAT 9260
ROOM TOTAL HEAT(RTH) 42265
OUTDOOR AIR HEAT
Sensible 725 30 0.9 21141
Latent 725 154 0.9 68330
GRAND TOTAL HEAT SUB TOTAL 131736
2% 2635
GRAND TOTAL HEAT 134371
TR 11.20

B.T.U. ESTIMATION FORM


WINTER AHU 26 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 353.340108 Height 9.84 outside 81
Volume(Cu.ft): 3477 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3477 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1871
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 32136
wall (W) 0 6 0.15 0 RTH 37112
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.87
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 353 4 0.11 155 16.2
Floor 0 4 0.5 0 DE AIR CFM 1837
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
725 9 0.1 1.08 705
INTERNAL HEAT
People 2.0 People X 337 674
HP 5.6 HP 2545 14252
Blower HP 2.9 2545 7441
Miscell 0.5 3410 1705 Heater 0.5
Lights 706.7 Watts 3.41 3012
ROOM SENSIBLE HEAT SUB TOTAL 27945
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4192
TOTAL ROOM SENSIBLE HEAT (RSH) 32136
LATENT HEAT
cfm Gr/lb BF
725 75 0.1 0.68 3698
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 38479
ROOM LATENT HEAT SUB TOTAL 4524
Supply duct Safety
leakage loss % + Factor 10% 452
TOTAL ROOM LATENT HEAT 4976
ROOM TOTAL HEAT(RTH) 37112
OUTDOOR AIR HEAT
Sensible 725 9 0.9 6342
Latent 725 75 0.9 33278
GRAND TOTAL HEAT SUB TOTAL 76732
2% 1535
GRAND TOTAL HEAT 78267
TR 6.52
22/10/2014
WB %RH Gr/lb
64 200
40 46
XXX 154

`
VENTILATION
25.00 X ACPH `

187

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

4.31
KW 4.81
22/10/2014
WB %RH Gr/lb
76 121
40 46
XXX XXX 75

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
outside monsoon conditio 102 200 Fresh Air 725
inside condition 72 46 Deh. CFM 1886
154
DEHUMDIFIER CALCULATION

PERMEATION LOAD
VOL GR DIFF F1 F2 F3,F4
3477 154.00 3.8 0.65 0.5

DOOR LOAD
NO.OF
OP/HR AREA GR DIFF F1 DOORS
2 21 154.00 3.8 1
2 34 154.00 3.8 1
PEOPLE LOAD
NO. OF PEOPLE F5
2 2255

FIXED OPENING

SAFETY FACTOR 5%

TOTAL ROOM LOAD

16.885 CFM REQD


512.80 513 REQUIRED CFM

MAKE UP AIR LOAD


49714

TOTAL GRAINS PER HOUR

MIXING GRAINS
ROOM AIR 513 DESIGN GR 46
FA 725 AMBIENT GR 62
DEH I/L GR 55.4
DESIGN T( F ) 72
PRE COOL T( F ) 54
DEH I/L T( F ) 61.5
DEH I/L T( C ) 16.4
DEH SIZING
21.9171 793 CFM
1348 CMH
SELECTED MODEL FLP 1500 CMH

CFM 588 Temp 108.5 gr/lb 17.404


CFM 381 Temp 72 gr/lb 46.570

TEMP 94.15 gr/lb 28.87


1175
GR/HR

47233 1175 CFM/ 72 F/ 46

3511 SELECTED MODEL 1500


5685

1018
4510

0 157.4 CFM/ 72 F/ 46

3047

63986 725 CFM/ 54 F/ 62


fix fix

value
6.57143 22.2222 1.95 13.7
49714

113700

value
7.91021 22.222 2.6 18.2
725 CFM

Gr/lb ROOM

0 CFM/ 72 F/ 46

1018 CFM/ 72.0 F/ 46.00

Gr/lb
882.4 CFM/ 57.2 F/ 59.1 Gr/lb

DEHUMIIFIER

Gr/lb

PRE COOLING COIL

725 CFM/ 102 F/ 200 Gr/lb

PCC 8.54 ENTHALPY DIFF.


ACC 5.59 TEMP DIFF.
1900 CFM/ 55 F/ 34 Gr/lb

1900 CFM/ 55.0 F/

Gr/lb AFTER COOLING COIL

1900 CFM/ 87.7 F/


Gr/lb

882.4 CFM/ 105.8 F/ 19.1447 Gr/lb

value
8.44952 14.0 2.1 14.7
temp 41
33.53 Gr/lb

33.53 Gr/lb

5577
B.T.U. ESTIMATION FORM
Summer AHU 27 Date:
Client: CONDITIONS DB
Area(sq.ft) 353.34 Height 9.84 Outside 102
Volume(Cu.ft): 3477 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3477 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1871
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 62153
wall (W) 0 27 0.15 0 RTH 70762
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 353 25 0.11 972 19.8
Floor 0 25 0.50 0 DE AIR CFM 2907
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.5532
outside air DB diff BF 1.08
725 30 0.1 1.08 2349
INTERNAL HEAT
People 2.0 People X 337 674
HP 3.5 HP 2545 8908
Blower HP 2.9 2545 7441
Miscell 9.0 3410 30690 Heater 9.0
Lights 706.7 Watts 3.41 3012
ROOM SENSIBLE HEAT SUB TOTAL 54046
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 8107
TOTAL ROOM SENSIBLE HEAT (RSH) 62153
LATENT HEAT
cfm Gr/lb BF
725 142 0.1 0.68 7001
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 7827
Supply duct Safety
leakage loss % + Factor 10% 783
TOTAL ROOM LATENT HEAT 8609
ROOM TOTAL HEAT(RTH) 70762
OUTDOOR AIR HEAT
Sensible 725 30 0.9 21141
Latent 725 142 0.9 63005
GRAND TOTAL HEAT SUB TOTAL 154908
2% 3098
GRAND TOTAL HEAT 158006
TR 13.17

B.T.U. ESTIMATION FORM


WINTER AHU 27 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 353.340108 Height 9.84 outside 81
Volume(Cu.ft): 3477 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3477 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1871
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 59323
wall (W) 0 6 0.15 0 RTH 63648
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 353 4 0.11 155 18.72
Floor 0 4 0.5 0 DE AIR CFM 2934
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.56801
outside air DB diff BF 1.08
725 9 0.1 1.08 705
INTERNAL HEAT
People 2.0 People X 337 674
HP 3.5 HP 2545 8908
Blower HP 2.9 2545 7441
Miscell 9 3410 30690 Heater 9.0
Lights 706.7 Watts 3.41 3012
ROOM SENSIBLE HEAT SUB TOTAL 51585
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 7738
TOTAL ROOM SENSIBLE HEAT (RSH) 59323
LATENT HEAT
cfm Gr/lb BF
725 63 0.1 0.68 3106
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 65665
ROOM LATENT HEAT SUB TOTAL 3932
Supply duct Safety
leakage loss % + Factor 10% 393
TOTAL ROOM LATENT HEAT 4325
ROOM TOTAL HEAT(RTH) 63648
OUTDOOR AIR HEAT
Sensible 725 9 0.9 6342
Latent 725 63 0.9 27953
GRAND TOTAL HEAT SUB TOTAL 97944
2% 1959
GRAND TOTAL HEAT 99902
TR 8.33
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

187

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

2.69
KW 11.69
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 27 Date:
Client: CONDITIONS DB
Area(sq.ft) 353.34 Height 9.84 Outside 102
Volume(Cu.ft): 3477 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3477 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1871
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 26859
wall (W) 0 27 0.15 0 RTH 36119
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.74
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 353 25 0.11 972 16.2
Floor 0 25 0.50 0 DE AIR CFM 1535
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.82037
outside air DB diff BF 1.08
725 30 0.1 1.08 2349
INTERNAL HEAT
People 2.0 People X 337 674
HP 3.5 HP 2545 8908
Blower HP 2.9 2545 7441
Miscell 3410 0 Heater 0.0
Lights 706.7 Watts 3.41 3012
ROOM SENSIBLE HEAT SUB TOTAL 23356
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 3503
TOTAL ROOM SENSIBLE HEAT (RSH) 26859
LATENT HEAT
cfm Gr/lb BF
725 154 0.1 0.68 7592
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 8418
Supply duct Safety
leakage loss % + Factor 10% 842
TOTAL ROOM LATENT HEAT 9260
ROOM TOTAL HEAT(RTH) 36119
OUTDOOR AIR HEAT
Sensible 725 30 0.9 21141
Latent 725 154 0.9 68330
GRAND TOTAL HEAT SUB TOTAL 125590
2% 2512
GRAND TOTAL HEAT 128102
TR 10.68

B.T.U. ESTIMATION FORM


WINTER AHU 27 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 353.340108 Height 9.84 outside 81
Volume(Cu.ft): 3477 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3477 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1871
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 26775
wall (W) 0 6 0.15 0 RTH 31750
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.84
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 353 4 0.11 155 16.2
Floor 0 4 0.5 0 DE AIR CFM 1530
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.81779
outside air DB diff BF 1.08
725 9 0.1 1.08 705
INTERNAL HEAT
People 2.0 People X 337 674
HP 3.5 HP 2545 8908
Blower HP 2.9 2545 7441
Miscell 0.7 3410 2387 Heater 0.7
Lights 706.7 Watts 3.41 3012
ROOM SENSIBLE HEAT SUB TOTAL 23282
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 3492
TOTAL ROOM SENSIBLE HEAT (RSH) 26775
LATENT HEAT
cfm Gr/lb BF
725 75 0.1 0.68 3698
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 33117
ROOM LATENT HEAT SUB TOTAL 4524
Supply duct Safety
leakage loss % + Factor 10% 452
TOTAL ROOM LATENT HEAT 4976
ROOM TOTAL HEAT(RTH) 31750
OUTDOOR AIR HEAT
Sensible 725 9 0.9 6342
Latent 725 75 0.9 33278
GRAND TOTAL HEAT SUB TOTAL 71370
2% 1427
GRAND TOTAL HEAT 72798
TR 6.07
22/10/2014
WB %RH Gr/lb
64 200
40 46
XXX 154

`
VENTILATION
25.00 X ACPH `

187

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

2.69
KW 3.39
22/10/2014
WB %RH Gr/lb
76 121
40 46
XXX XXX 75

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
outside monsoon conditio 102 200 Fresh Air 725
inside condition 72 46 Deh. CFM 1535
154
DEHUMDIFIER CALCULATION

PERMEATION LOAD
VOL GR DIFF F1 F2 F3,F4
3477 154.00 3.8 0.65 0.5

DOOR LOAD
NO.OF
OP/HR AREA GR DIFF F1 DOORS
2 21 154.00 3.8 1
2 34 154.00 3.8 1
PEOPLE LOAD
NO. OF PEOPLE F5
2 2255

FIXED OPENING

SAFETY FACTOR 5%

TOTAL ROOM LOAD

16.885 CFM REQD


512.80 513 REQUIRED CFM

MAKE UP AIR LOAD


49714

TOTAL GRAINS PER HOUR

MIXING GRAINS
ROOM AIR 513 DESIGN GR 46
FA 725 AMBIENT GR 62
DEH I/L GR 55.4
DESIGN T( F ) 72
PRE COOL T( F ) 54
DEH I/L T( F ) 61.5
DEH I/L T( C ) 16.4
DEH SIZING
21.9171 793 CFM
1348 CMH
SELECTED MODEL FLP 1500 CMH

CFM 588 Temp 108.5 gr/lb 17.404


CFM 381 Temp 72 gr/lb 46.570

TEMP 94.15 gr/lb 28.87


1175
GR/HR

47233 810 CFM/ 72 F/ 46

3511 SELECTED MODEL 1500


5685

653
4510

0 157.4 CFM/ 72 F/ 46

3047

63986 725 CFM/ 54 F/ 62


fix fix

value
6.57143 22.2222 1.95 13.7
49714

113700

value
7.91021 22.222 2.6 18.2
725 CFM

Gr/lb ROOM

365 CFM/ 72 F/ 46

653 CFM/ 72.0 F/ 46.00

Gr/lb
882.4 CFM/ 57.2 F/ 59.1 Gr/lb

DEHUMIIFIER

Gr/lb

PRE COOLING COIL

725 CFM/ 102 F/ 200 Gr/lb

PCC 8.54 ENTHALPY DIFF.


ACC 6.40 TEMP DIFF.
1900 CFM/ 57 F/ 34 Gr/lb

1535 CFM/ 54.0 F/

Gr/lb AFTER COOLING COIL

1535 CFM/ 91.4 F/


Gr/lb

882.4 CFM/ 105.8 F/ 19.1447 Gr/lb

value
8.44952 14.0 2.1 14.7
temp 41
30.57 Gr/lb

30.57 Gr/lb

5577
B.T.U. ESTIMATION FORM
Summer AHU 28 Date:
Client: CONDITIONS DB
Area(sq.ft) 347.33 Height 9.84 Outside 102
Volume(Cu.ft): 3418 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3418 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1847
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 26669
wall (W) 0 27 0.15 0 RTH 36905
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.72
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 347 25 0.11 955 16.2
Floor 0 25 0.50 0 DE AIR CFM 1524
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.82541
outside air DB diff BF 1.08
725 30 0.1 1.08 2349
INTERNAL HEAT
People 2.0 People X 337 674
HP 3.5 HP 2545 8908
Blower HP 2.9 2545 7343
Miscell 3410 0 Heater 0.0
Lights 694.7 Watts 3.41 2961
ROOM SENSIBLE HEAT SUB TOTAL 23190
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 3479
TOTAL ROOM SENSIBLE HEAT (RSH) 26669
LATENT HEAT
cfm Gr/lb BF
725 172 0.1 0.68 8480
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 9306
Supply duct Safety
leakage loss % + Factor 10% 931
TOTAL ROOM LATENT HEAT 10236
ROOM TOTAL HEAT(RTH) 36905
OUTDOOR AIR HEAT
Sensible 725 30 0.9 21141
Latent 725 172 0.9 76316
GRAND TOTAL HEAT SUB TOTAL 134362
2% 2687
GRAND TOTAL HEAT 137049
TR 11.42

B.T.U. ESTIMATION FORM


WINTER AHU 28 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 347.331186 Height 9.84 outside 81
Volume(Cu.ft): 3418 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3418 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1847
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 26600
wall (W) 0 6 0.15 0 RTH 32552
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.82
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 347 4 0.11 153 16.2
Floor 0 4 0.5 0 DE AIR CFM 1520
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08 0.82329
725 9 0.1 1.08 705
INTERNAL HEAT
People 2.0 People X 337 674
HP 3.5 HP 2545 8908
Blower HP 2.9 2545 7343
Miscell 0.7 3410 2387 Heater 0.7
Lights 694.7 Watts 3.41 2961
ROOM SENSIBLE HEAT SUB TOTAL 23130
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 3470
TOTAL ROOM SENSIBLE HEAT (RSH) 26600
LATENT HEAT
cfm Gr/lb BF
725 93 0.1 0.68 4585
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 32942
ROOM LATENT HEAT SUB TOTAL 5411
Supply duct Safety
leakage loss % + Factor 10% 541
TOTAL ROOM LATENT HEAT 5952
ROOM TOTAL HEAT(RTH) 32552
OUTDOOR AIR HEAT
Sensible 725 9 0.9 6342
Latent 725 93 0.9 41264
GRAND TOTAL HEAT SUB TOTAL 80158
2% 1603
GRAND TOTAL HEAT 81762
TR 6.81
22/10/2014
WB %RH Gr/lb
64 200
25 28
XXX 172

`
VENTILATION
25.00 X ACPH `

185

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

2.69
KW
22/10/2014
WB %RH Gr/lb
76 121
25 28
XXX XXX 93

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
outside monsoon conditio 102 200 Fresh Air 725
inside condition 72 28 Deh. CFM 1524
172
DEHUMDIFIER CALCULATION

PERMEATION LOAD
VOL GR DIFF F1 F2 F3,F4
3418 172.00 4.23 0.65 0.5

DOOR LOAD
NO.OF
OP/HR AREA GR DIFF F1 DOORS
2 21 172.00 4.23 1
2 34 172.00 4.23 1
PEOPLE LOAD
NO. OF PEOPLE F5
2 2255

FIXED OPENING

SAFETY FACTOR 5%

TOTAL ROOM LOAD

9.1 CFM REQD


954.96 955 REQUIRED CFM

MAKE UP AIR LOAD


105643

TOTAL GRAINS PER HOUR

MIXING GRAINS
ROOM AIR 955 DESIGN GR 28
FA 725 AMBIENT GR 62
DEH I/L GR 42.7
DESIGN T( F ) 72
PRE COOL T( F ) 54
DEH I/L T( F ) 64.2
DEH I/L T( C ) 17.9
DEH SIZING
14.9773 1542 CFM
2621 CMH
SELECTED MODEL FLP 3000 CMH

CFM 588 Temp 108.5 gr/lb 17.404


CFM 381 Temp 72 gr/lb 46.570

TEMP 94.15 gr/lb 28.87


1125
GR/HR

57725 1040 CFM/ 72 F/ 28

4365 SELECTED MODEL 3000


7068

0
4510

0 1039.7 CFM/ 72 F/ 28

3683

77351 725 CFM/ 54 F/ 62


fix fix

value
4 22.2222 1 7.0
105643

182994

value
6.09614 22.222 1.7 11.9
725 CFM

Gr/lb ROOM

85 CFM/ 72 F/ 28

0 CFM/ 72.0 F/ 28.00

Gr/lb
1764.7 CFM/ 64.6 F/ 42.0 Gr/lb

DEHUMIIFIER

Gr/lb

PRE COOLING COIL

725 CFM/ 102 F/ 200 Gr/lb

PCC 9.30 ENTHALPY DIFF.


ACC 8.23 TEMP DIFF.
1850 CFM/ 56 F/ 14 Gr/lb

1765 CFM/ 55.0 F/

Gr/lb AFTER COOLING COIL

1765 CFM/ 105.8 F/


Gr/lb

1764.7 CFM/ 105.8 F/ 13.0168 Gr/lb

value
5.99548 18.1 1.4 9.8
temp 41
13.02 Gr/lb

13.02 Gr/lb

5577
B.T.U. ESTIMATION FORM
Summer AHU 29 Date:
Client: CONDITIONS DB
Area(sq.ft) 354.69 Height 9.84 Outside 102
Volume(Cu.ft): 3490 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3490 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1883
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 26930
wall (W) 0 27 0.15 0 RTH 37166
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.72
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 355 25 0.11 975 16.2
Floor 0 25 0.50 0 DE AIR CFM 1539
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.81744
outside air DB diff BF 1.08
725 30 0.1 1.08 2349
INTERNAL HEAT
People 2.0 People X 337 674
HP 3.5 HP 2545 8908
Blower HP 2.9 2545 7488
Miscell 3410 0 Heater 0.0
Lights 709.4 Watts 3.41 3024
ROOM SENSIBLE HEAT SUB TOTAL 23417
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 3513
TOTAL ROOM SENSIBLE HEAT (RSH) 26930
LATENT HEAT
cfm Gr/lb BF
725 172 0.1 0.68 8480
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 9306
Supply duct Safety
leakage loss % + Factor 10% 931
TOTAL ROOM LATENT HEAT 10236
ROOM TOTAL HEAT(RTH) 37166
OUTDOOR AIR HEAT
Sensible 725 30 0.9 21141
Latent 725 172 0.9 76316
GRAND TOTAL HEAT SUB TOTAL 134623
2% 2692
GRAND TOTAL HEAT 137316
TR 11.44

B.T.U. ESTIMATION FORM


WINTER AHU 29 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 354.68706632 Height 9.84 outside 81
Volume(Cu.ft): 3490 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3490 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1883
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 26842
wall (W) 0 6 0.15 0 RTH 32794
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.82
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 355 4 0.11 156 16.2
Floor 0 4 0.5 0 DE AIR CFM 1534
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.81477
outside air DB diff BF 1.08
725 9 0.1 1.08 705
INTERNAL HEAT
People 2.0 People X 337 674
HP 3.5 HP 2545 8908
Blower HP 2.9 2545 7488
Miscell 0.7 3410 2387 Heater 0.7
Lights 709.4 Watts 3.41 3024
ROOM SENSIBLE HEAT SUB TOTAL 23341
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 3501
TOTAL ROOM SENSIBLE HEAT (RSH) 26842
LATENT HEAT
cfm Gr/lb BF
725 93 0.1 0.68 4585
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 33184
ROOM LATENT HEAT SUB TOTAL 5411
Supply duct Safety
leakage loss % + Factor 10% 541
TOTAL ROOM LATENT HEAT 5952
ROOM TOTAL HEAT(RTH) 32794
OUTDOOR AIR HEAT
Sensible 725 9 0.9 6342
Latent 725 93 0.9 41264
GRAND TOTAL HEAT SUB TOTAL 80400
2% 1608
GRAND TOTAL HEAT 82008
TR 6.83
22/10/2014
WB %RH Gr/lb
64 200
25 28
XXX 172

`
VENTILATION
25.00 X ACPH `

188

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

2.69
KW 3.39
22/10/2014
WB %RH Gr/lb
76 121
25 28
XXX XXX 93

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
outside monsoon conditio 102 200 Fresh Air 725
inside condition 72 28 Deh. CFM 1539
172
DEHUMDIFIER CALCULATION

PERMEATION LOAD
VOL GR DIFF F1 F2 F3,F4
3490 172.00 4.23 0.65 0.5

DOOR LOAD
NO.OF
OP/HR AREA GR DIFF F1 DOORS
2 21 172.00 4.23 1
2 34 172.00 4.23 1
PEOPLE LOAD
NO. OF PEOPLE F5
2 2255

FIXED OPENING

SAFETY FACTOR 5%

TOTAL ROOM LOAD

9.1 CFM REQD


970.80 971 REQUIRED CFM

MAKE UP AIR LOAD


105643

TOTAL GRAINS PER HOUR

MIXING GRAINS
ROOM AIR 971 DESIGN GR 28
FA 725 AMBIENT GR 62
DEH I/L GR 42.5
DESIGN T( F ) 72
PRE COOL T( F ) 54
DEH I/L T( F ) 64.3
DEH I/L T( C ) 17.9
DEH SIZING
14.9636 1559 CFM
2651 CMH
SELECTED MODEL FLP 3000 CMH

CFM 588 Temp 108.5 gr/lb 17.404


CFM 381 Temp 72 gr/lb 46.570

TEMP 94.15 gr/lb 28.87


1165
GR/HR

58947 1040 CFM/ 72 F/ 28

4365 SELECTED MODEL 3000


7068

0
4510

0 1039.7 CFM/ 72 F/ 28

3745

78635 725 CFM/ 54 F/ 62


fix fix

value
4 22.2222 1 7.0
105643

184278

value
6.07656 22.222 1.7 11.9
725 CFM

Gr/lb ROOM

125 CFM/ 72 F/ 28

0 CFM/ 72.0 F/ 28.00

Gr/lb
1764.7 CFM/ 64.6 F/ 42.0 Gr/lb

DEHUMIIFIER

Gr/lb

PRE COOLING COIL

725 CFM/ 102 F/ 200 Gr/lb

PCC 9.30 ENTHALPY DIFF.


ACC 8.23 TEMP DIFF.
1890 CFM/ 56 F/ 14 Gr/lb

1765 CFM/ 55.0 F/

Gr/lb AFTER COOLING COIL

1765 CFM/ 105.8 F/


Gr/lb

1764.7 CFM/ 105.8 F/ 13.0168 Gr/lb

value
5.99548 18.1 1.4 9.8
temp 41
13.02 Gr/lb

13.02 Gr/lb

5577
B.T.U. ESTIMATION FORM
Summer AHU 30 Date:
Client: CONDITIONS DB
Area(sq.ft) 358.00 Height 9.84 Outside 102
Volume(Cu.ft): 3523 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3523 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1890
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 27007
wall (W) 0 27 0.15 0 RTH 37243
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.73
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 358 25 0.11 985 16.2
Floor 0 25 0.50 0 DE AIR CFM 1544
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.81655
outside air DB diff BF 1.08
725 30 0.1 1.08 2349
INTERNAL HEAT
People 2.0 People X 337 674
HP 3.5 HP 2545 8908
Blower HP 3.0 2545 7517
Miscell 3410 0 Heater 0.0
Lights 716.0 Watts 3.41 3052
ROOM SENSIBLE HEAT SUB TOTAL 23484
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 3523
TOTAL ROOM SENSIBLE HEAT (RSH) 27007
LATENT HEAT
cfm Gr/lb BF
725 172 0.1 0.68 8480
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 9306
Supply duct Safety
leakage loss % + Factor 10% 931
TOTAL ROOM LATENT HEAT 10236
ROOM TOTAL HEAT(RTH) 37243
OUTDOOR AIR HEAT
Sensible 725 30 0.9 21141
Latent 725 172 0.9 76316
GRAND TOTAL HEAT SUB TOTAL 134700
2% 2694
GRAND TOTAL HEAT 137394
TR 11.45

B.T.U. ESTIMATION FORM


WINTER AHU 30 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 358.00045768 Height 9.84 outside 81
Volume(Cu.ft): 3523 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 3523 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1890
Glass(S) 0 12 0.56 0 CFM 725
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 26910
wall (W) 0 6 0.15 0 RTH 32862
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.82
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 358 4 0.11 158 16.2
Floor 0 4 0.5 0 DE AIR CFM 1538
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.81362
outside air DB diff BF 1.08
725 9 0.1 1.08 705
INTERNAL HEAT
People 2.0 People X 337 674
HP 3.5 HP 2545 8908
Blower HP 3.0 2545 7517
Miscell 0.7 3410 2387 Heater 0.7
Lights 716.0 Watts 3.41 3052
ROOM SENSIBLE HEAT SUB TOTAL 23400
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 3510
TOTAL ROOM SENSIBLE HEAT (RSH) 26910
LATENT HEAT
cfm Gr/lb BF
725 93 0.1 0.68 4585
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 33252
ROOM LATENT HEAT SUB TOTAL 5411
Supply duct Safety
leakage loss % + Factor 10% 541
TOTAL ROOM LATENT HEAT 5952
ROOM TOTAL HEAT(RTH) 32862
OUTDOOR AIR HEAT
Sensible 725 9 0.9 6342
Latent 725 93 0.9 41264
GRAND TOTAL HEAT SUB TOTAL 80468
2% 1609
GRAND TOTAL HEAT 82078
TR 6.84
22/10/2014
WB %RH Gr/lb
64 200
25 28
XXX 172

`
VENTILATION
25.00 X ACPH `

189

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

2.69
KW 3.39
22/10/2014
WB %RH Gr/lb
76 121
25 28
XXX XXX 93

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
outside monsoon conditio 102 200 Fresh Air 725
inside condition 72 28 Deh. CFM 1544
172
DEHUMDIFIER CALCULATION

PERMEATION LOAD
VOL GR DIFF F1 F2 F3,F4
3523 172.00 4.23 0.65 0.5

DOOR LOAD
NO.OF
OP/HR AREA GR DIFF F1 DOORS
2 21 172.00 4.23 1
2 34 172.00 4.23 1
PEOPLE LOAD
NO. OF PEOPLE F5
2 2255

FIXED OPENING

SAFETY FACTOR 5%

TOTAL ROOM LOAD

9.1 CFM REQD


977.94 978 REQUIRED CFM

MAKE UP AIR LOAD


105643

TOTAL GRAINS PER HOUR

MIXING GRAINS
ROOM AIR 978 DESIGN GR 28
FA 725 AMBIENT GR 62
DEH I/L GR 42.5
DESIGN T( F ) 72
PRE COOL T( F ) 54
DEH I/L T( F ) 64.3
DEH I/L T( C ) 18.0
DEH SIZING
14.9575 1567 CFM
2665 CMH
SELECTED MODEL FLP 3000 CMH

CFM 588 Temp 108.5 gr/lb 17.404


CFM 381 Temp 72 gr/lb 46.570

TEMP 94.15 gr/lb 28.87


1165
GR/HR

59498 1040 CFM/ 72 F/ 28

4365 SELECTED MODEL 3000


7068

0
4510

0 1039.7 CFM/ 72 F/ 28

3772

79213 725 CFM/ 54 F/ 62


fix fix

value
4 22.2222 1 7.0
105643

184856

value
6.06785 22.222 1.7 11.9
725 CFM

Gr/lb ROOM

125 CFM/ 72 F/ 28

0 CFM/ 72.0 F/ 28.00

Gr/lb
1764.7 CFM/ 64.6 F/ 42.0 Gr/lb

DEHUMIIFIER

Gr/lb

PRE COOLING COIL

725 CFM/ 102 F/ 200 Gr/lb

PCC 9.30 ENTHALPY DIFF.


ACC 8.23 TEMP DIFF.
1890 CFM/ 56 F/ 14 Gr/lb

1765 CFM/ 55.0 F/

Gr/lb AFTER COOLING COIL

1765 CFM/ 105.8 F/


Gr/lb

1764.7 CFM/ 105.8 F/ 13.0168 Gr/lb

value
5.99548 18.1 1.4 9.8
temp 41
13.02 Gr/lb

13.02 Gr/lb

5577
B.T.U. ESTIMATION FORM
Summer AHU 31 Date:
Client: CONDITIONS DB
Area(sq.ft) 233.22 Height 9.84 Outside 102
Volume(Cu.ft): 2295 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2295 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1372
Glass(S) 0 12 0.56 0 CFM 350
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 39780
wall (W) 0 27 0.15 0 RTH 45315
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 233 25 0.11 641 19.8
Floor 0 25 0.50 0 DE AIR CFM 1860
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.35559
outside air DB diff BF 1.08
350 30 0.1 1.08 1134
INTERNAL HEAT
People 4.0 People X 337 1348
HP 1.4 HP 2545 3563
Blower HP 2.1 2545 5457
Miscell 6.0 3410 20460 Heater 6.0
Lights 466.4 Watts 3.41 1988
ROOM SENSIBLE HEAT SUB TOTAL 34592
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5189
TOTAL ROOM SENSIBLE HEAT (RSH) 39780
LATENT HEAT
cfm Gr/lb BF
350 142 0.1 0.68 3380
People 4.0 People X 413 1652
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 5032
Supply duct Safety
leakage loss % + Factor 10% 503
TOTAL ROOM LATENT HEAT 5535
ROOM TOTAL HEAT(RTH) 45315
OUTDOOR AIR HEAT
Sensible 350 30 0.9 10206
Latent 350 142 0.9 30416
GRAND TOTAL HEAT SUB TOTAL 85938
2% 1719
GRAND TOTAL HEAT 87656
TR 7.30

B.T.U. ESTIMATION FORM


WINTER AHU 31 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 233.22209616 Height 9.84 outside 81
Volume(Cu.ft): 2295 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2295 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1372
Glass(S) 0 12 0.56 0 CFM 350
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 38248
wall (W) 0 6 0.15 0 RTH 41715
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.92
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 233 4 0.11 103 18.9
Floor 0 4 0.5 0 DE AIR CFM 1874
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.36544
outside air DB diff BF 1.08
350 9 0.1 1.08 340
INTERNAL HEAT
People 4.0 People X 337 1348
HP 1.4 HP 2545 3563
Blower HP 2.1 2545 5457
Miscell 6 3410 20460 Heater 6.0
Lights 466.4 Watts 3.41 1988
ROOM SENSIBLE HEAT SUB TOTAL 33259
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4989
TOTAL ROOM SENSIBLE HEAT (RSH) 38248
LATENT HEAT
cfm Gr/lb BF
350 63 0.1 0.68 1499
People 4.0 People X 413 1652
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 41310
ROOM LATENT HEAT SUB TOTAL 3151
Supply duct Safety
leakage loss % + Factor 10% 315
TOTAL ROOM LATENT HEAT 3467
ROOM TOTAL HEAT(RTH) 41715
OUTDOOR AIR HEAT
Sensible 350 9 0.9 3062
Latent 350 63 0.9 13495
GRAND TOTAL HEAT SUB TOTAL 58271
2% 1165
GRAND TOTAL HEAT 59436
TR 4.95
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

137

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

1.08
KW 7.08
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 32 Date:
Client: CONDITIONS DB
Area(sq.ft) 8672.40 Height 9.84 Outside 102
Volume(Cu.ft): 100131 Inside 73
Difference 29
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 100131 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 8756
Glass(S) 0 12 0.56 0 CFM 1000
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 1937 32 0.35 21692 RSH 341467
wall (W) 0 26 0.15 0 RTH 375114
wall (S) 68 30 0.15 305
Roof sun 0 49 0.50 0 SHF 0.91
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.6
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 8672 24 0.11 22895 16.56
Floor 0 24 0.50 0 DE AIR CFM 19093
Partition 2176 24 0.11 5744 NOTES
INFILTRATION & OUTSIDE AIR 2.1806
outside air DB diff BF 1.08
1000 29 0.1 1.08 3132
INTERNAL HEAT
People 52.0 People X 337 17524
HP 51.4 HP 2545 130813
Blower HP 8.2 2545 20890
Miscell 0.0 3410 0 Heater 0.0
Lights 17344.8 Watts 3.41 73932
ROOM SENSIBLE HEAT SUB TOTAL 296928
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 44539
TOTAL ROOM SENSIBLE HEAT (RSH) 341467
LATENT HEAT
cfm Gr/lb BF
1000 134 0.1 0.68 9112
People 52.0 People X 413 21476
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 30588
Supply duct Safety
leakage loss % + Factor 10% 3059
TOTAL ROOM LATENT HEAT 33647
ROOM TOTAL HEAT(RTH) 375114
OUTDOOR AIR HEAT
Sensible 1000 29 0.9 28188 2.349
Latent 1000 134 0.9 82008 6.834
GRAND TOTAL HEAT SUB TOTAL 485310
2% 9706
GRAND TOTAL HEAT 495016
TR 41.25

B.T.U. ESTIMATION FORM


WINTER AHU 32 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 8672.40230144 Height 9.84 outside 81
Volume(Cu.ft): 100131 inside 73
Difference 8
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 100131 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 8756
Glass(S) 0 12 0.56 0 CFM 1000
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -3 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 1937 11 0.15 3196 RSH 337543
wall (W) 0 5 0.15 0 RTH 365281
wall (S) 68 9 0.15 92
Roof sun 0 28 0.5 0 SHF 0.92
Roof insulated 0 28 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.8
All glass 0 8 1.13 0
Partition glass 0 3 0.8 0 DEHUMIDIFIED AIR
Ceiling 8672 3 0.11 2862 16.38
Floor 0 3 0.5 0 DE AIR CFM 19081
Partition 2176 3 0.11 718 NOTES
INFILTRATION & OUTSIDE AIR 2.17923
outside air DB diff BF 1.08
1000 8 0.1 1.08 864
INTERNAL HEAT
People 52.0 People X 337 17524
HP 51.4 HP 2545 130813
Blower HP 8.2 2545 20890
Miscell 12.5 3410 42625 Heater 12.5
Lights 17344.8 Watts 3.41 73932
ROOM SENSIBLE HEAT SUB TOTAL 293516
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 44027
TOTAL ROOM SENSIBLE HEAT (RSH) 337543
LATENT HEAT
cfm Gr/lb BF
1000 55 0.1 0.68 3740
People 52.0 People X 413 21476
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 345319
ROOM LATENT HEAT SUB TOTAL 25216
Supply duct Safety
leakage loss % + Factor 10% 2522
TOTAL ROOM LATENT HEAT 27738
ROOM TOTAL HEAT(RTH) 365281
OUTDOOR AIR HEAT
Sensible 1000 8 0.9 7776 0.648
Latent 1000 55 0.9 33660 2.805
GRAND TOTAL HEAT SUB TOTAL 406717
2% 8134
GRAND TOTAL HEAT 414851
TR 34.57
22/10/2014
WB %RH Gr/lb
64 200
55 66
XXX 134

`
VENTILATION
X ACPH `

876 780

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

39.54
KW 52.04
22/10/2014
WB %RH Gr/lb
76 121
55 66
XXX XXX 55

VENTILATION
0 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 33 Date:
Client: CONDITIONS DB
Area(sq.ft) 3942.22 Height 9.84 Outside 102
Volume(Cu.ft): 100858 Inside 73
Difference 29
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 100858 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 3362
Glass(S) 0 12 0.56 0 CFM 500
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 1235 18 0.15 3336 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 82068
wall (W) 1073 26 0.15 4183 RTH 87988
wall (S) 0 30 0.15 0
Roof sun 0 49 0.50 0 SHF 0.93
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 55
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 3942 24 0.11 10407 16.2
Floor 0 24 0.50 0 DE AIR CFM 4691
Partition 3624 24 0.11 9568 NOTES
INFILTRATION & OUTSIDE AIR 1.39523
outside air DB diff BF 1.08
500 29 0.1 1.08 1566
INTERNAL HEAT
People 2.0 People X 337 674
HP 0.0 HP 2545 0
Blower HP 3.2 2545 8021
Miscell 3410 0 Heater 0.0
Lights 7884.4 Watts 3.41 33607
ROOM SENSIBLE HEAT SUB TOTAL 71363
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 10704
TOTAL ROOM SENSIBLE HEAT (RSH) 82068
LATENT HEAT
cfm Gr/lb BF
500 134 0.1 0.68 4556
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 5382
Supply duct Safety
leakage loss % + Factor 10% 538
TOTAL ROOM LATENT HEAT 5920
ROOM TOTAL HEAT(RTH) 87988
OUTDOOR AIR HEAT
Sensible 500 29 0.9 14094
Latent 500 134 0.9 41004
GRAND TOTAL HEAT SUB TOTAL 143086
2% 2862
GRAND TOTAL HEAT 145948
TR 12.16

B.T.U. ESTIMATION FORM


WINTER AHU 33 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 3942.22212596 Height 9.84 outside 81
Volume(Cu.ft): 100858 inside 73
Difference 8
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 100858 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 3362
Glass(S) 0 12 0.56 0 CFM 500
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 1235 -3 0.15 -556 SENSIBLE HEAT FACTOR
wall (E) 0 11 0.15 0 RSH 79753
wall (W) 1073 5 0.15 805 RTH 82718
wall (S) 0 9 0.15 0
Roof sun 0 28 0.5 0 SHF 0.96
Roof insulated 0 28 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 55.4
All glass 0 8 1.13 0
Partition glass 0 3 0.8 0 DEHUMIDIFIED AIR
Ceiling 3942 3 0.11 1301 15.84
Floor 0 3 0.5 0 DE AIR CFM 4662
Partition 3624 3 0.11 1196 NOTES
INFILTRATION & OUTSIDE AIR 1.38669
outside air DB diff BF 1.08
500 8 0.1 1.08 432
INTERNAL HEAT
People 2.0 People X 337 674
HP 0.0 HP 2545 0
Blower HP 3.2 2545 8021
Miscell 7 3410 23870 Heater 7.0
Lights 7884.4 Watts 3.41 33607
ROOM SENSIBLE HEAT SUB TOTAL 69350
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 10403
TOTAL ROOM SENSIBLE HEAT (RSH) 79753
LATENT HEAT
cfm Gr/lb BF
500 55 0.1 0.68 1870
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 83641
ROOM LATENT HEAT SUB TOTAL 2696
Supply duct Safety
leakage loss % + Factor 10% 270
TOTAL ROOM LATENT HEAT 2966
ROOM TOTAL HEAT(RTH) 82718
OUTDOOR AIR HEAT
Sensible 500 8 0.9 3888
Latent 500 55 0.9 16830
GRAND TOTAL HEAT SUB TOTAL 103436
2% 2069
GRAND TOTAL HEAT 105505
TR 8.79
22/10/2014
WB %RH Gr/lb
64 200
55 66
XXX 134

`
VENTILATION
X ACPH `

336

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

0.00
KW 7.00
22/10/2014
WB %RH Gr/lb
76 121
55 66
XXX XXX 55

VENTILATION
0 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 34 Date:
Client: CONDITIONS DB
Area(sq.ft) 192.84 Height 9.84 Outside 102
Volume(Cu.ft): 1898 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1898 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1272
Glass(S) 0 12 0.56 0 CFM 400
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 37502
wall (W) 0 27 0.15 0 RTH 42659
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 193 25 0.11 530 19.8
Floor 0 25 0.50 0 DE AIR CFM 1754
Partition 100 25 0.11 275 NOTES
INFILTRATION & OUTSIDE AIR 1.37868
outside air DB diff BF 1.08
400 30 0.1 1.08 1296
INTERNAL HEAT
People 2.0 People X 337 674
HP 1.1 HP 2545 2672
Blower HP 2.0 2545 5058
Miscell 6.0 3410 20460 Heater 6.0
Lights 385.7 Watts 3.41 1644
ROOM SENSIBLE HEAT SUB TOTAL 32610
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4892
TOTAL ROOM SENSIBLE HEAT (RSH) 37502
LATENT HEAT
cfm Gr/lb BF
400 142 0.1 0.68 3862
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 4688
Supply duct Safety
leakage loss % + Factor 10% 469
TOTAL ROOM LATENT HEAT 5157
ROOM TOTAL HEAT(RTH) 42659
OUTDOOR AIR HEAT
Sensible 400 30 0.9 11664
Latent 400 142 0.9 34762
GRAND TOTAL HEAT SUB TOTAL 89084
2% 1782
GRAND TOTAL HEAT 90866
TR 7.57

B.T.U. ESTIMATION FORM


WINTER AHU 34 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 192.8421726 Height 9.84 outside 81
Volume(Cu.ft): 1898 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1898 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1272
Glass(S) 0 12 0.56 0 CFM 400
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 35680
wall (W) 0 6 0.15 0 RTH 38474
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 193 4 0.11 85 18.72
Floor 0 4 0.5 0 DE AIR CFM 1765
Partition 100 4 0.11 44 NOTES
INFILTRATION & OUTSIDE AIR 1.38739
outside air DB diff BF 1.08
400 9 0.1 1.08 389
INTERNAL HEAT
People 2.0 People X 337 674
HP 1.1 HP 2545 2672
Blower HP 2.0 2545 5058
Miscell 6 3410 20460 Heater 6.0
Lights 385.7 Watts 3.41 1644
ROOM SENSIBLE HEAT SUB TOTAL 31026
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4654
TOTAL ROOM SENSIBLE HEAT (RSH) 35680
LATENT HEAT
cfm Gr/lb BF
400 63 0.1 0.68 1714
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 39179
ROOM LATENT HEAT SUB TOTAL 2540
Supply duct Safety
leakage loss % + Factor 10% 254
TOTAL ROOM LATENT HEAT 2794
ROOM TOTAL HEAT(RTH) 38474
OUTDOOR AIR HEAT
Sensible 400 9 0.9 3499
Latent 400 63 0.9 15422
GRAND TOTAL HEAT SUB TOTAL 57395
2% 1148
GRAND TOTAL HEAT 58543
TR 4.88
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

127

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

0.81
KW 6.81
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 35 Date:
Client: CONDITIONS DB
Area(sq.ft) 190.19 Height 9.84 Outside 102
Volume(Cu.ft): 1872 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1872 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1267
Glass(S) 0 12 0.56 0 CFM 400
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 40007
wall (W) 0 27 0.15 0 RTH 45164
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.89
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 190 25 0.11 523 19.8
Floor 0 25 0.50 0 DE AIR CFM 1871
Partition 291 25 0.11 799 NOTES
INFILTRATION & OUTSIDE AIR 1.4768
outside air DB diff BF 1.08
400 30 0.1 1.08 1296
INTERNAL HEAT
People 2.0 People X 337 674
HP 1.1 HP 2545 2672
Blower HP 2.0 2545 5038
Miscell 6.5 3410 22165 Heater 6.5
Lights 380.4 Watts 3.41 1621
ROOM SENSIBLE HEAT SUB TOTAL 34788
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 5218
TOTAL ROOM SENSIBLE HEAT (RSH) 40007
LATENT HEAT
cfm Gr/lb BF
400 142 0.1 0.68 3862
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 4688
Supply duct Safety
leakage loss % + Factor 10% 469
TOTAL ROOM LATENT HEAT 5157
ROOM TOTAL HEAT(RTH) 45164
OUTDOOR AIR HEAT
Sensible 400 30 0.9 11664
Latent 400 142 0.9 34762
GRAND TOTAL HEAT SUB TOTAL 91589
2% 1832
GRAND TOTAL HEAT 93421
TR 7.79

B.T.U. ESTIMATION FORM


WINTER AHU 35 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 190.19410432 Height 9.84 outside 81
Volume(Cu.ft): 1872 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1872 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1267
Glass(S) 0 12 0.56 0 CFM 400
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 37686
wall (W) 0 6 0.15 0 RTH 40480
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 190 4 0.11 84 18.72
Floor 0 4 0.5 0 DE AIR CFM 1864
Partition 291 4 0.11 128 NOTES
INFILTRATION & OUTSIDE AIR 1.47141
outside air DB diff BF 1.08
400 9 0.1 1.08 389
INTERNAL HEAT
People 2.0 People X 337 674
HP 1.1 HP 2545 2672
Blower HP 2.0 2545 5038
Miscell 6.5 3410 22165 Heater 6.5
Lights 380.4 Watts 3.41 1621
ROOM SENSIBLE HEAT SUB TOTAL 32771
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4916
TOTAL ROOM SENSIBLE HEAT (RSH) 37686
LATENT HEAT
cfm Gr/lb BF
400 63 0.1 0.68 1714
People 2.0 People X 413 826
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 41185
ROOM LATENT HEAT SUB TOTAL 2540
Supply duct Safety
leakage loss % + Factor 10% 254
TOTAL ROOM LATENT HEAT 2794
ROOM TOTAL HEAT(RTH) 40480
OUTDOOR AIR HEAT
Sensible 400 9 0.9 3499
Latent 400 63 0.9 15422
GRAND TOTAL HEAT SUB TOTAL 59401
2% 1188
GRAND TOTAL HEAT 60589
TR 5.05
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

127

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

0.81
KW 7.31
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 36 Date:
Client: CONDITIONS DB
Area(sq.ft) 8363.72 Height 9.84 Outside 102
Volume(Cu.ft): 209906 Inside 73
Difference 29
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 209906 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 6997
Glass(S) 0 12 0.56 0 CFM 600
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 193008
wall (W) 2258 26 0.35 20545 RTH 199477
wall (S) 1734 30 0.35 18207
Roof sun 0 49 0.50 0 SHF 0.97
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 55.5
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 8364 24 0.11 22080 15.75
Floor 0 24 0.50 0 DE AIR CFM 11347
Partition 2986 24 0.11 7883 NOTES
INFILTRATION & OUTSIDE AIR 1.62169
outside air DB diff BF 1.08
600 29 0.1 1.08 1879
INTERNAL HEAT
People 1.0 People X 337 337
HP 3.5 HP 2545 8908
Blower HP 6.6 2545 16694
Miscell 3410 0 Heater 0.0
Lights 16727.4 Watts 3.41 71301
ROOM SENSIBLE HEAT SUB TOTAL 167833
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 25175
TOTAL ROOM SENSIBLE HEAT (RSH) 193008
LATENT HEAT
cfm Gr/lb BF
600 134 0.1 0.68 5467
People 1.0 People X 413 413
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 5880
Supply duct Safety
leakage loss % + Factor 10% 588
TOTAL ROOM LATENT HEAT 6468
ROOM TOTAL HEAT(RTH) 199477
OUTDOOR AIR HEAT
Sensible 600 29 0.9 16913
Latent 600 134 0.9 49205
GRAND TOTAL HEAT SUB TOTAL 265594
2% 5312
GRAND TOTAL HEAT 270906
TR 22.58

B.T.U. ESTIMATION FORM


WINTER AHU 36 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 8363.71922776 Height 9.84 outside 81
Volume(Cu.ft): 209906 inside 73
Difference 8
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 209906 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 6997
Glass(S) 0 12 0.56 0 CFM 600
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -3 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 11 0.15 0 RSH 189994
wall (W) 2258 5 0.15 1693 RTH 192917
wall (S) 1734 9 0.15 2341
Roof sun 0 28 0.5 0 SHF 0.98
Roof insulated 0 28 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 55.6
All glass 0 8 1.13 0
Partition glass 0 3 0.8 0 DEHUMIDIFIED AIR
Ceiling 8364 3 0.11 2760 15.66
Floor 0 3 0.5 0 DE AIR CFM 11234
Partition 2986 3 0.11 985 NOTES
INFILTRATION & OUTSIDE AIR 1.60554
outside air DB diff BF 1.08
600 8 0.1 1.08 518
INTERNAL HEAT
People 1.0 People X 337 337
HP 3.5 HP 2545 8908
Blower HP 6.6 2545 16694
Miscell 17.5 3410 59675 Heater 17.5
Lights 16727.4 Watts 3.41 71301
ROOM SENSIBLE HEAT SUB TOTAL 165212
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 24782
TOTAL ROOM SENSIBLE HEAT (RSH) 189994
LATENT HEAT
cfm Gr/lb BF
600 55 0.1 0.68 2244
People 1.0 People X 413 413
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 194660
ROOM LATENT HEAT SUB TOTAL 2657
Supply duct Safety
leakage loss % + Factor 10% 266
TOTAL ROOM LATENT HEAT 2923
ROOM TOTAL HEAT(RTH) 192917
OUTDOOR AIR HEAT
Sensible 600 8 0.9 4666 0.3888
Latent 600 55 0.9 20196 1.683
GRAND TOTAL HEAT SUB TOTAL 217778
2% 4356
GRAND TOTAL HEAT 222134
TR 18.51
22/10/2014
WB %RH Gr/lb
64 200
55 66
XXX 134

`
VENTILATION
X ACPH `

10495.3
700

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

2.69
KW 20.19
22/10/2014
WB %RH Gr/lb
76 121
55 66
XXX XXX 55

VENTILATION
0 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 37 Date:
Client: CONDITIONS DB
Area(sq.ft) 4626.06 Height 9.18 Outside 102
Volume(Cu.ft): 42486 Inside 73
Difference 29
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 75.3 14 0.56 590 42486 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 7081
Glass(S) 0 12 0.56 0 CFM 900
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 1035 18 0.35 6521 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 167358
wall (W) 0 26 0.15 0 RTH 186828
wall (S) 0 30 0.15 0
Roof sun 0 49 0.50 0 SHF 0.90
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.4
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 4626 24 0.11 12213 16.74
Floor 0 24 0.50 0 DE AIR CFM 9257
Partition 1544 24 0.11 4077 NOTES
INFILTRATION & OUTSIDE AIR 1.3073
Outside air DB diff BF 1.08
900 29 0.1 1.08 2819
INTERNAL HEAT
People 23.0 People X 337 7751
HP 21.7 HP 2545 55227
Blower HP 6.6 2545 16895
Miscell 0.0 3410 0 Heater 0.0
Lights 9252.1 Watts 3.41 39437
ROOM SENSIBLE HEAT SUB TOTAL 145529
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 21829
TOTAL ROOM SENSIBLE HEAT (RSH) 167358
LATENT HEAT
cfm Gr/lb BF
900 134 0.1 0.68 8201
People 23.0 People X 413 9499
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 17700
Supply duct Safety
leakage loss % + Factor 10% 1770
TOTAL ROOM LATENT HEAT 19470
ROOM TOTAL HEAT(RTH) 186828
OUTDOOR AIR HEAT
Sensible 900 29 0.9 25369
Latent 900 134 0.9 73807
GRAND TOTAL HEAT SUB TOTAL 286004
2% 5720
GRAND TOTAL HEAT 291724
TR 24.31

B.T.U. ESTIMATION FORM


WINTER AHU 37 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 4626.05566624 Height 9.18 outside 81
Volume(Cu.ft): 42486 inside 73
Difference 8
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 75.3 14 0.56 590 42486 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 7081
Glass(S) 0 12 0.56 0 CFM 900
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 1035 -3 0.15 -466 SENSIBLE HEAT FACTOR
wall (E) 0 11 0.15 0 RSH 162936
wall (W) 0 5 0.15 0 RTH 177087
wall (S) 0 9 0.15 0
Roof sun 0 28 0.5 0 SHF 0.92
Roof insulated 0 28 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.8
All glass 75.3 8 1.13 681
Partition glass 0 3 0.8 0 DEHUMIDIFIED AIR
Ceiling 4626 3 0.11 1527 16.38
Floor 0 3 0.5 0 DE AIR CFM 9210
Partition 1544 3 0.11 510 NOTES
INFILTRATION & OUTSIDE AIR 1.30073
outside air DB diff BF 1.08
900 8 0.1 1.08 778
INTERNAL HEAT
People 23.0 People X 337 7751
HP 21.7 HP 2545 55227
Blower HP 6.6 2545 16895
Miscell 5.5 3410 18755 Heater 5.5
Lights 9252.1 Watts 3.41 39437
ROOM SENSIBLE HEAT SUB TOTAL 141683
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 21253
TOTAL ROOM SENSIBLE HEAT (RSH) 162936
LATENT HEAT
cfm Gr/lb BF
900 55 0.1 0.68 3366
People 23.0 People X 413 9499
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 169934
ROOM LATENT HEAT SUB TOTAL 12865
Supply duct Safety
leakage loss % + Factor 10% 1287
TOTAL ROOM LATENT HEAT 14152
ROOM TOTAL HEAT(RTH) 177087
OUTDOOR AIR HEAT
Sensible 900 8 0.9 6998
Latent 900 55 0.9 30294
GRAND TOTAL HEAT SUB TOTAL 214380
2% 4288
GRAND TOTAL HEAT 218667
TR 18.22
22/10/2014
WB %RH Gr/lb
64 200
55 66
XXX 134

VENTILATION
10.00 X ACPH

708 270

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

16.69
KW 22.19
22/10/2014
WB %RH Gr/lb
76 121
55 66
XXX XXX 55

VENTILATION
10 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 38 Date:
Client: CONDITIONS DB
Area(sq.ft) 234.39 Height 9.184 Outside 102
Volume(Cu.ft): 2153 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2153 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 907
Glass(S) 0 12 0.56 0 CFM 150
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 172 33 0.35 1983 RSH 16934
wall (W) 0 27 0.15 0 RTH 18981
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.89
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50.3
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 234 25 0.11 645 19.53
Floor 0 25 0.50 0 DE AIR CFM 803
Partition 117 25 0.11 323 NOTES
INFILTRATION & OUTSIDE AIR 0.88484
outside air DB diff BF 1.08
150 30 0.1 1.08 486
INTERNAL HEAT
People 1.0 People X 337 337
HP 2.1 HP 2545 5345
Blower HP 1.4 2545 3608
Miscell 0.0 3410 0 Heater 0.0
Lights 468.8 Watts 3.41 1998
ROOM SENSIBLE HEAT SUB TOTAL 14725
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 2209
TOTAL ROOM SENSIBLE HEAT (RSH) 16934
LATENT HEAT
cfm Gr/lb BF
150 142 0.1 0.68 1448
People 1.0 People X 413 413
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 1861
Supply duct Safety
leakage loss % + Factor 10% 186
TOTAL ROOM LATENT HEAT 2048
ROOM TOTAL HEAT(RTH) 18981
OUTDOOR AIR HEAT
Sensible 150 30 0.9 4374
Latent 150 142 0.9 13036
GRAND TOTAL HEAT SUB TOTAL 36391
2% 728
GRAND TOTAL HEAT 37119
TR 3.09

B.T.U. ESTIMATION FORM


WINTER AHU 38 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 234.392074 Height 9.184 outside 81
Volume(Cu.ft): 2153 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2153 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 907
Glass(S) 0 12 0.56 0 CFM 150
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 172 12 0.15 309 RSH 14466
wall (W) 0 6 0.15 0 RTH 15628
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.93
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.2
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 234 4 0.11 103 18.72
Floor 0 4 0.5 0 DE AIR CFM 716
Partition 117 4 0.11 52 NOTES
INFILTRATION & OUTSIDE AIR 0.78863
outside air DB diff BF 1.08
150 9 0.1 1.08 146
INTERNAL HEAT
People 1.0 People X 337 337
HP 2.1 HP 2545 5345
Blower HP 1.4 2545 3608
Miscell 0.2 3410 682 Heater 0.2
Lights 468.8 Watts 3.41 1998
ROOM SENSIBLE HEAT SUB TOTAL 12579
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 1887
TOTAL ROOM SENSIBLE HEAT (RSH) 14466
LATENT HEAT
cfm Gr/lb BF
150 63 0.1 0.68 643
People 1.0 People X 413 413
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 15779
ROOM LATENT HEAT SUB TOTAL 1056
Supply duct Safety
leakage loss % + Factor 10% 106
TOTAL ROOM LATENT HEAT 1161
ROOM TOTAL HEAT(RTH) 15628
OUTDOOR AIR HEAT
Sensible 150 9 0.9 1312
Latent 150 63 0.9 5783
GRAND TOTAL HEAT SUB TOTAL 22723
2% 454
GRAND TOTAL HEAT 23178
TR 1.93
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

1.62
KW 1.82
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 39 Date:
Client: CONDITIONS DB
Area(sq.ft) 252.77 Height 9.184 Outside 102
Volume(Cu.ft): 2321 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2321 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 1548
Glass(S) 0 12 0.56 0 CFM 250
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 121 19 0.35 801 SENSIBLE HEAT FACTOR
wall (E) 205 33 0.35 2366 RSH 31707
wall (W) 0 27 0.15 0 RTH 34847
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.91
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50.8
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 253 25 0.11 695 19.08
Floor 0 25 0.50 0 DE AIR CFM 1539
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.9942
outside air DB diff BF 1.08
250 30 0.1 1.08 810
INTERNAL HEAT
People 1.0 People X 337 337
HP 5.6 HP 2545 14252
Blower HP 2.4 2545 6154
Miscell 3410 0 Heater 0.0
Lights 505.5 Watts 3.41 2155
ROOM SENSIBLE HEAT SUB TOTAL 27571
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 4136
TOTAL ROOM SENSIBLE HEAT (RSH) 31707
LATENT HEAT
cfm Gr/lb BF
250 142 0.1 0.68 2414
People 1.0 People X 441 441
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 2855
Supply duct Safety
leakage loss % + Factor 10% 286
TOTAL ROOM LATENT HEAT 3141
ROOM TOTAL HEAT(RTH) 34847
OUTDOOR AIR HEAT
Sensible 250 30 0.9 7290
Latent 250 142 0.9 21726
GRAND TOTAL HEAT SUB TOTAL 63863
2% 1277
GRAND TOTAL HEAT 65140
TR 5.43

B.T.U. ESTIMATION FORM


WINTER AHU 39 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 252.774189 Height 9.184 outside 81
Volume(Cu.ft): 2321 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2321 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 1548
Glass(S) 0 12 0.56 0 CFM 250
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 121 -2 0.15 -36 SENSIBLE HEAT FACTOR
wall (E) 205 12 0.15 369 RSH 30260
wall (W) 0 6 0.15 0 RTH 31923
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.95
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.5
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 253 4 0.11 111 18.45
Floor 0 4 0.5 0 DE AIR CFM 1519
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 0.98124
outside air DB diff BF 1.08
250 9 0.1 1.08 243
INTERNAL HEAT
People 1.0 People X 337 337
HP 5.6 HP 2545 14252
Blower HP 2.4 2545 6154
Miscell 0.8 3410 2728 Heater 0.8
Lights 505.5 Watts 3.41 2155
ROOM SENSIBLE HEAT SUB TOTAL 26313
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 3947
TOTAL ROOM SENSIBLE HEAT (RSH) 30260
LATENT HEAT
cfm Gr/lb BF
250 63 0.1 0.68 1071
People 1.0 People X 441 441
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 32447
ROOM LATENT HEAT SUB TOTAL 1512
Supply duct Safety
leakage loss % + Factor 10% 151
TOTAL ROOM LATENT HEAT 1663
ROOM TOTAL HEAT(RTH) 31923
OUTDOOR AIR HEAT
Sensible 250 9 0.9 2187
Latent 250 63 0.9 9639
GRAND TOTAL HEAT SUB TOTAL 43749
2% 875
GRAND TOTAL HEAT 44624
TR 3.72
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25/40/60 X ACPH `

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

4.31
KW 5.11
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25/40/60 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer AHU 40 Date:
Client: CONDITIONS DB
Area(sq.ft) 114.28 Height 9.184 Outside 102
Volume(Cu.ft): 1050 Inside 72
Difference 30
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1050 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 437
Glass(S) 0 12 0.56 0 CFM 150
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 12235
wall (W) 0 27 0.15 0 RTH 13829
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 50
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 114 25 0.11 314 19.8
Floor 0 25 0.50 0 DE AIR CFM 572
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.30842
outside air DB diff BF 1.08
150 30 0.1 1.08 486
INTERNAL HEAT
People 0.0 People X 413 0
HP 2.8 HP 2545 7126
Blower HP 0.7 2545 1739
Miscell 0.0 3410 0 Heater 0.0
Lights 228.6 Watts 3.41 974
ROOM SENSIBLE HEAT SUB TOTAL 10639
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 1596
TOTAL ROOM SENSIBLE HEAT (RSH) 12235
LATENT HEAT
cfm Gr/lb BF
150 142 0.1 0.68 1448
People 0.0 People X 413 0
Steam 0 lb/hr X
Appliances 0
Permeation Loa 0 0
ROOM LATENT HEAT SUB TOTAL 1448
Supply duct Safety
leakage loss % + Factor 10% 145
TOTAL ROOM LATENT HEAT 1593
ROOM TOTAL HEAT(RTH) 13829
OUTDOOR AIR HEAT
Sensible 150 30 0.9 4374
Latent 150 142 0.9 13036
GRAND TOTAL HEAT SUB TOTAL 31238
2% 625
GRAND TOTAL HEAT 31863
TR 2.66

B.T.U. ESTIMATION FORM


WINTER AHU 40 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 114.27688128 Height 9.184 outside 81
Volume(Cu.ft): 1050 inside 72
Difference 9
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1050 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 437
Glass(S) 0 12 0.56 0 CFM 150
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 -2 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 12 0.15 0 RSH 11541
wall (W) 0 6 0.15 0 RTH 12247
wall (S) 0 10 0.15 0
Roof sun 0 29 0.5 0 SHF 0.94
Roof insulated 0 29 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 51.4
All glass 0 9 1.13 0
Partition glass 0 4 0.8 0 DEHUMIDIFIED AIR
Ceiling 114 4 0.11 50 18.54
Floor 0 4 0.5 0 DE AIR CFM 576
Partition 0 4 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 1.31799
outside air DB diff BF 1.08
150 9 0.1 1.08 146
INTERNAL HEAT
People 0.0 People X 413 0
HP 2.8 HP 2545 7126
Blower HP 0.7 2545 1739
Miscell 3410 0 Heater
Lights 228.6 Watts 3.41 974
ROOM SENSIBLE HEAT SUB TOTAL 10035
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % 15% 1505
TOTAL ROOM SENSIBLE HEAT (RSH) 11541
LATENT HEAT
cfm Gr/lb BF
150 63 0.1 0.68 643
People 0.0 People X 413 0
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 12853
ROOM LATENT HEAT SUB TOTAL 643
Supply duct Safety
leakage loss % + Factor 10% 64
TOTAL ROOM LATENT HEAT 707
ROOM TOTAL HEAT(RTH) 12247
OUTDOOR AIR HEAT
Sensible 150 9 0.9 1312
Latent 150 63 0.9 5783
GRAND TOTAL HEAT SUB TOTAL 19343
2% 387
GRAND TOTAL HEAT 19730
TR 1.64
22/10/2014
WB %RH Gr/lb
64 200
50 58
XXX 142

`
VENTILATION
25.00 X ACPH `

SENSIBLE HEAT FACTOR `

(From tables/chart)

DEHUMIDIFIED AIR

2.15
KW 2.15
22/10/2014
WB %RH Gr/lb
76 121
50 58
XXX XXX 63

VENTILATION
25 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-1 - RECEIPTION Date:
Client: CONDITIONS DB
Area(sq.ft) 154.47 Height 9.84 Outside 102
Volume(Cu.ft): 1520 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1520 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 127
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 178 19 0.15 506 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 5900
wall (W) 0 27 0.15 0 RTH 6385
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.92
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 154 25 0.11 425 13.5
Floor 0 25 0.50 0 DE AIR CFM 405
Partition 473 25 0.11 1301 NOTES
INFILTRATION & OUTSIDE AIR 3.194766
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 1.0 People X 309 309
HP 0.5 HP 2545 1273
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 308.9 Watts 3.41 1317
ROOM SENSIBLE HEAT SUB TOTAL 5131
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 770
TOTAL ROOM SENSIBLE HEAT (RSH) 5900
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 1.0 People X 441 441
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 441
Supply duct Safety
leakage loss % + Factor 10% 44
TOTAL ROOM LATENT HEAT 485
ROOM TOTAL HEAT(RTH) 6385
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 6385
2% 128
GRAND TOTAL HEAT 6513
TR 0.54

B.T.U. ESTIMATION FORM


WINTER SAC-1 - RECEIPTION Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 154.471905 Height 9.84 outside 101
Volume(Cu.ft): 1520 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1520 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 127
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 178 18 0.15 479 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 5790
wall (W) 0 26 0.15 0 RTH 6275
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.92
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 154 24 0.11 408 15.624
Floor 0 24 0.5 0 DE AIR CFM 343
Partition 473 24 0.11 1249 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 1.0 People X 309 309
HP 0.5 HP 2545 1273
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 308.9 Watts 3.41 1317
ROOM SENSIBLE HEAT SUB TOTAL 5035
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 755
TOTAL ROOM SENSIBLE HEAT (RSH) 5790
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 1.0 People X 441 441
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 5790
ROOM LATENT HEAT SUB TOTAL 441
Supply duct Safety
leakage loss % + Factor 10% 44
TOTAL ROOM LATENT HEAT 485
ROOM TOTAL HEAT(RTH) 6275
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 6275
2% 126
GRAND TOTAL HEAT 6401
TR 0.53
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.25
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-2 - F G OFFICE Date:
Client: CONDITIONS DB
Area(sq.ft) 149.42 Height 9.84 Outside 102
Volume(Cu.ft): 1470 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1470 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 123
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 111 33 0.15 551 RSH 5919
wall (W) 0 27 0.15 0 RTH 6890
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.86
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 55.6
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 149 25 0.11 411 14.76
Floor 0 25 0.50 0 DE AIR CFM 371
Partition 371 25 0.11 1021 NOTES
INFILTRATION & OUTSIDE AIR 3.030782
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 0.5 HP 2545 1273
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 298.8 Watts 3.41 1274
ROOM SENSIBLE HEAT SUB TOTAL 5147
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 772
TOTAL ROOM SENSIBLE HEAT (RSH) 5919
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 6890
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 6890
2% 138
GRAND TOTAL HEAT 7027
TR 0.59

B.T.U. ESTIMATION FORM


WINTER 0 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 149.41605 Height 9.84 outside 101
Volume(Cu.ft): 1470 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1470 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 123
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 111 32 0.15 535 RSH 5834
wall (W) 0 26 0.15 0 RTH 6805
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.86
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 149 24 0.11 394 15.624
Floor 0 24 0.5 0 DE AIR CFM 346
Partition 371 24 0.11 980 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 0.5 HP 2545 1273
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 298.8 Watts 3.41 1274
ROOM SENSIBLE HEAT SUB TOTAL 5073
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 761
TOTAL ROOM SENSIBLE HEAT (RSH) 5834
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 5834
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 6805
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 6805
2% 136
GRAND TOTAL HEAT 6941
TR 0.58
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.25
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-3 - R M OFFICE Date:
Client: CONDITIONS DB
Area(sq.ft) 172.59 Height 9.84 Outside 102
Volume(Cu.ft): 1698 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1698 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 142
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 111 33 0.15 551 RSH 6220
wall (W) 0 27 0.15 0 RTH 7190
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.87
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 55.6
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 173 25 0.11 475 14.76
Floor 0 25 0.50 0 DE AIR CFM 390
Partition 371 25 0.11 1021 NOTES
INFILTRATION & OUTSIDE AIR 2.75702
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 0.5 HP 2545 1273
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 345.2 Watts 3.41 1471
ROOM SENSIBLE HEAT SUB TOTAL 5409
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 811
TOTAL ROOM SENSIBLE HEAT (RSH) 6220
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7190
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7190
2% 144
GRAND TOTAL HEAT 7334
TR 0.61

B.T.U. ESTIMATION FORM


WINTER 0 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 172.5904 Height 9.84 outside 101
Volume(Cu.ft): 1698 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1698 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 142
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 111 32 0.15 535 RSH 6132
wall (W) 0 26 0.15 0 RTH 7102
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.86
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 173 24 0.11 456 15.624
Floor 0 24 0.5 0 DE AIR CFM 363
Partition 371 24 0.11 980 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 0.5 HP 2545 1273
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 345.2 Watts 3.41 1471
ROOM SENSIBLE HEAT SUB TOTAL 5332
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 800
TOTAL ROOM SENSIBLE HEAT (RSH) 6132
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 6132
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7102
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7102
2% 142
GRAND TOTAL HEAT 7244
TR 0.60
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.25
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-4 - RECALL Date:
Client: CONDITIONS DB
Area(sq.ft) 172.59 Height 9.84 Outside 102
Volume(Cu.ft): 1698 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1698 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 142
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 6352
wall (W) 164 27 0.15 666 RTH 7322
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.87
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 55.6
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 173 25 0.11 475 14.76
Floor 0 25 0.50 0 DE AIR CFM 398
Partition 371 25 0.11 1021 NOTES
INFILTRATION & OUTSIDE AIR 2.815487
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 0.5 HP 2545 1273
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 345.2 Watts 3.41 1471
ROOM SENSIBLE HEAT SUB TOTAL 5523
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 828
TOTAL ROOM SENSIBLE HEAT (RSH) 6352
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7322
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7322
2% 146
GRAND TOTAL HEAT 7468
TR 0.62

B.T.U. ESTIMATION FORM


WINTER 0 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 172.5904 Height 9.84 outside 101
Volume(Cu.ft): 1698 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1698 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 142
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 6255
wall (W) 164 26 0.15 641 RTH 7225
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.87
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 173 24 0.11 456 15.624
Floor 0 24 0.5 0 DE AIR CFM 371
Partition 371 24 0.11 980 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 0.5 HP 2545 1273
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 345.2 Watts 3.41 1471
ROOM SENSIBLE HEAT SUB TOTAL 5439
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 816
TOTAL ROOM SENSIBLE HEAT (RSH) 6255
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 6255
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7225
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7225
2% 144
GRAND TOTAL HEAT 7369
TR 0.61
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.25
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-5 - STRONG ROOM Date:
Client: CONDITIONS DB
Area(sq.ft) 113.48 Height 9.84 Outside 102
Volume(Cu.ft): 1117 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1117 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 93
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 3645
wall (W) 0 27 0.15 0 RTH 4616
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.79
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 55.6
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 113 25 0.11 312 14.76
Floor 0 25 0.50 0 DE AIR CFM 229
Partition 0 25 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR 2.457591
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 0.5 HP 2545 1273
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 227.0 Watts 3.41 967
ROOM SENSIBLE HEAT SUB TOTAL 3170
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 475
TOTAL ROOM SENSIBLE HEAT (RSH) 3645
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 4616
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 4616
2% 92
GRAND TOTAL HEAT 4708
TR 0.39

B.T.U. ESTIMATION FORM


WINTER 0 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 113.48107168 Height 9.84 outside 101
Volume(Cu.ft): 1117 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1117 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 93
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 3631
wall (W) 0 26 0.15 0 RTH 4601
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.79
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 113 24 0.11 300 15.624
Floor 0 24 0.5 0 DE AIR CFM 215
Partition 0 24 0.11 0 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 0.5 HP 2545 1273
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 227.0 Watts 3.41 967
ROOM SENSIBLE HEAT SUB TOTAL 3158
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 474
TOTAL ROOM SENSIBLE HEAT (RSH) 3631
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 3631
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 4601
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 4601
2% 92
GRAND TOTAL HEAT 4693
TR 0.39
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.25
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-6 - DISCUSSION 1 Date:
Client: CONDITIONS DB
Area(sq.ft) 118.06 Height 9.84 Outside 102
Volume(Cu.ft): 1162 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1162 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 97
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 4027
wall (W) 0 27 0.15 0 RTH 4512
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.89
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 118 25 0.11 325 13.5
Floor 0 25 0.50 0 DE AIR CFM 276
Partition 214 25 0.11 589 NOTES
INFILTRATION & OUTSIDE AIR 2.852948
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 1.0 People X 309 309
HP 0.5 HP 2545 1273
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 236.1 Watts 3.41 1006
ROOM SENSIBLE HEAT SUB TOTAL 3502
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 525
TOTAL ROOM SENSIBLE HEAT (RSH) 4027
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 1.0 People X 441 441
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 441
Supply duct Safety
leakage loss % + Factor 10% 44
TOTAL ROOM LATENT HEAT 485
ROOM TOTAL HEAT(RTH) 4512
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 4512
2% 90
GRAND TOTAL HEAT 4602
TR 0.38

B.T.U. ESTIMATION FORM


WINTER SAC-6 - DISCUSSION 1 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 118.0641 Height 9.84 outside 101
Volume(Cu.ft): 1162 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1162 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 97
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 3985
wall (W) 0 26 0.15 0 RTH 4470
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.89
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 118 24 0.11 312 15.624
Floor 0 24 0.5 0 DE AIR CFM 236
Partition 214 24 0.11 566 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 1.0 People X 309 309
HP 0.5 HP 2545 1273
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 236.1 Watts 3.41 1006
ROOM SENSIBLE HEAT SUB TOTAL 3465
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 520
TOTAL ROOM SENSIBLE HEAT (RSH) 3985
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 1.0 People X 441 441
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 3985
ROOM LATENT HEAT SUB TOTAL 441
Supply duct Safety
leakage loss % + Factor 10% 44
TOTAL ROOM LATENT HEAT 485
ROOM TOTAL HEAT(RTH) 4470
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 4470
2% 89
GRAND TOTAL HEAT 4559
TR 0.38
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.25
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-7 - DISCUSSION 2 Date:
Client: CONDITIONS DB
Area(sq.ft) 122.36 Height 9.84 Outside 102
Volume(Cu.ft): 1204 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1204 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 100
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 4206
wall (W) 105 27 0.15 427 RTH 4691
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.90
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 122 25 0.11 336 13.5
Floor 0 25 0.50 0 DE AIR CFM 288
Partition 98 25 0.11 269 NOTES
INFILTRATION & OUTSIDE AIR 2.87515
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 1.0 People X 309 309
HP 0.5 HP 2545 1273
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 244.7 Watts 3.41 1043
ROOM SENSIBLE HEAT SUB TOTAL 3657
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 549
TOTAL ROOM SENSIBLE HEAT (RSH) 4206
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 1.0 People X 441 441
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 441
Supply duct Safety
leakage loss % + Factor 10% 44
TOTAL ROOM LATENT HEAT 485
ROOM TOTAL HEAT(RTH) 4691
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 4691
2% 94
GRAND TOTAL HEAT 4785
TR 0.40

B.T.U. ESTIMATION FORM


WINTER SAC-7 - DISCUSSION 2 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 122.35734 Height 9.84 outside 101
Volume(Cu.ft): 1204 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1204 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 100
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 4160
wall (W) 105 26 0.15 411 RTH 4645
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.90
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 122 24 0.11 323 15.624
Floor 0 24 0.5 0 DE AIR CFM 247
Partition 98 24 0.11 258 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 1.0 People X 309 309
HP 0.5 HP 2545 1273
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 244.7 Watts 3.41 1043
ROOM SENSIBLE HEAT SUB TOTAL 3617
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 543
TOTAL ROOM SENSIBLE HEAT (RSH) 4160
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 1.0 People X 441 441
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 4160
ROOM LATENT HEAT SUB TOTAL 441
Supply duct Safety
leakage loss % + Factor 10% 44
TOTAL ROOM LATENT HEAT 485
ROOM TOTAL HEAT(RTH) 4645
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 4645
2% 93
GRAND TOTAL HEAT 4738
TR 0.39
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.25
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-8 - CONFERENCE Date:
Client: CONDITIONS DB
Area(sq.ft) 122.36 Height 9.84 Outside 102
Volume(Cu.ft): 1204 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1204 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 100
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 12743
wall (W) 0 27 0.15 0 RTH 20504
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.62
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 122 25 0.11 336 13.5
Floor 0 25 0.50 0 DE AIR CFM 874
Partition 804 25 0.11 2212 NOTES
INFILTRATION & OUTSIDE AIR 8.710934
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 16.0 People X 309 4944
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 244.7 Watts 3.41 1043
ROOM SENSIBLE HEAT SUB TOTAL 11081
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 1662
TOTAL ROOM SENSIBLE HEAT (RSH) 12743
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 16.0 People X 441 7056
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 7056
Supply duct Safety
leakage loss % + Factor 10% 706
TOTAL ROOM LATENT HEAT 7762
ROOM TOTAL HEAT(RTH) 20504
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 20504
2% 410
GRAND TOTAL HEAT 20915
TR 1.74

B.T.U. ESTIMATION FORM


WINTER SAC-8 - CONFERENCE Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 122.35734 Height 9.84 outside 101
Volume(Cu.ft): 1204 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1204 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 100
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 12626
wall (W) 0 26 0.15 0 RTH 20387
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.62
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 122 24 0.11 323 15.624
Floor 0 24 0.5 0 DE AIR CFM 748
Partition 804 24 0.11 2124 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 16.0 People X 309 4944
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 244.7 Watts 3.41 1043
ROOM SENSIBLE HEAT SUB TOTAL 10979
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 1647
TOTAL ROOM SENSIBLE HEAT (RSH) 12626
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 16.0 People X 441 7056
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 12626
ROOM LATENT HEAT SUB TOTAL 7056
Supply duct Safety
leakage loss % + Factor 10% 706
TOTAL ROOM LATENT HEAT 7762
ROOM TOTAL HEAT(RTH) 20387
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 20387
2% 408
GRAND TOTAL HEAT 20795
TR 1.73
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-9 - DIRECTOR OFFICE Date:
Client: CONDITIONS DB
Area(sq.ft) 247.59 Height 9.84 Outside 102
Volume(Cu.ft): 2436 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 203
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 5772
wall (W) 0 27 0.15 0 RTH 6257
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.92
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 25 0.11 681 13.5
Floor 0 25 0.50 0 DE AIR CFM 396
Partition 235 25 0.11 646 NOTES
INFILTRATION & OUTSIDE AIR 1.950026
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 1.0 People X 309 309
HP 0.5 HP 2545 1273
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 5019
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 753
TOTAL ROOM SENSIBLE HEAT (RSH) 5772
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 1.0 People X 441 441
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 441
Supply duct Safety
leakage loss % + Factor 10% 44
TOTAL ROOM LATENT HEAT 485
ROOM TOTAL HEAT(RTH) 6257
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 6257
2% 125
GRAND TOTAL HEAT 6382
TR 0.53

B.T.U. ESTIMATION FORM


WINTER SAC-9 - DIRECTOR OFFICE Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 247.5876 Height 9.84 outside 101
Volume(Cu.ft): 2436 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 203
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 5711
wall (W) 0 26 0.15 0 RTH 6196
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.92
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 24 0.11 654 15.624
Floor 0 24 0.5 0 DE AIR CFM 338
Partition 235 24 0.11 620 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 1.0 People X 309 309
HP 0.5 HP 2545 1273
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 4966
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 745
TOTAL ROOM SENSIBLE HEAT (RSH) 5711
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 1.0 People X 441 441
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 5711
ROOM LATENT HEAT SUB TOTAL 441
Supply duct Safety
leakage loss % + Factor 10% 44
TOTAL ROOM LATENT HEAT 485
ROOM TOTAL HEAT(RTH) 6196
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 6196
2% 124
GRAND TOTAL HEAT 6320
TR 0.53
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.25
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-10 -SECRETORY OFFICE Date:
Client: CONDITIONS DB
Area(sq.ft) 247.59 Height 9.84 Outside 102
Volume(Cu.ft): 2436 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 203
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 6128
wall (W) 0 27 0.15 0 RTH 7098
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.86
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 25 0.11 681 13.5
Floor 0 25 0.50 0 DE AIR CFM 420
Partition 235 25 0.11 646 NOTES
INFILTRATION & OUTSIDE AIR 2.070074
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 0.5 HP 2545 1273
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 5328
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 799
TOTAL ROOM SENSIBLE HEAT (RSH) 6128
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7098
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7098
2% 142
GRAND TOTAL HEAT 7240
TR 0.60

B.T.U. ESTIMATION FORM


WINTER SAC-10 -SECRETORY OFFICE Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 247.5876 Height 9.84 outside 101
Volume(Cu.ft): 2436 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 203
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 6066
wall (W) 0 26 0.15 0 RTH 7037
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.86
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 24 0.11 654 15.624
Floor 0 24 0.5 0 DE AIR CFM 360
Partition 235 24 0.11 620 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 0.5 HP 2545 1273
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 5275
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 791
TOTAL ROOM SENSIBLE HEAT (RSH) 6066
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 6066
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7037
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7037
2% 141
GRAND TOTAL HEAT 7177
TR 0.60
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.25
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-11 -ACCOUNTS OFFICE Date:
Client: CONDITIONS DB
Area(sq.ft) 247.59 Height 9.84 Outside 102
Volume(Cu.ft): 2436 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 203
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 7591
wall (W) 0 27 0.15 0 RTH 8561
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.89
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 25 0.11 681 13.5
Floor 0 25 0.50 0 DE AIR CFM 521
Partition 235 25 0.11 646 NOTES
INFILTRATION & OUTSIDE AIR 2.564448
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 6601
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 990
TOTAL ROOM SENSIBLE HEAT (RSH) 7591
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 8561
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 8561
2% 171
GRAND TOTAL HEAT 8732
TR 0.73

B.T.U. ESTIMATION FORM


WINTER SAC-11 -ACCOUNTS OFFICE Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 247.5876 Height 9.84 outside 101
Volume(Cu.ft): 2436 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 203
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 7530
wall (W) 0 26 0.15 0 RTH 8500
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.89
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 24 0.11 654 15.624
Floor 0 24 0.5 0 DE AIR CFM 446
Partition 235 24 0.11 620 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 6548
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 982
TOTAL ROOM SENSIBLE HEAT (RSH) 7530
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 7530
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 8500
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 8500
2% 170
GRAND TOTAL HEAT 8670
TR 0.72
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-12 -BUSINESS DEVELOPMENT Date:
Client: CONDITIONS DB
Area(sq.ft) 247.59 Height 9.84 Outside 102
Volume(Cu.ft): 2436 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 203
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 7591
wall (W) 0 27 0.15 0 RTH 8561
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.89
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 25 0.11 681 13.5
Floor 0 25 0.50 0 DE AIR CFM 521
Partition 235 25 0.11 646 NOTES
INFILTRATION & OUTSIDE AIR 2.564448
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 6601
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 990
TOTAL ROOM SENSIBLE HEAT (RSH) 7591
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 8561
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 8561
2% 171
GRAND TOTAL HEAT 8732
TR 0.73

B.T.U. ESTIMATION FORM


WINTER SAC-12 -BUSINESS DEVELOPMENT Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 247.5876 Height 9.84 outside 101
Volume(Cu.ft): 2436 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 203
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 7530
wall (W) 0 26 0.15 0 RTH 8500
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.89
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 24 0.11 654 15.624
Floor 0 24 0.5 0 DE AIR CFM 446
Partition 235 24 0.11 620 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 6548
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 982
TOTAL ROOM SENSIBLE HEAT (RSH) 7530
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 7530
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 8500
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 8500
2% 170
GRAND TOTAL HEAT 8670
TR 0.72
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-13 -HR Date:
Client: CONDITIONS DB
Area(sq.ft) 247.59 Height 9.84 Outside 102
Volume(Cu.ft): 2436 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 203
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 7591
wall (W) 0 27 0.15 0 RTH 8561
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.89
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 25 0.11 681 13.5
Floor 0 25 0.50 0 DE AIR CFM 521
Partition 235 25 0.11 646 NOTES
INFILTRATION & OUTSIDE AIR 2.564448
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 6601
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 990
TOTAL ROOM SENSIBLE HEAT (RSH) 7591
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 8561
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 8561
2% 171
GRAND TOTAL HEAT 8732
TR 0.73

B.T.U. ESTIMATION FORM


WINTER SAC-13 -HR Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 247.5876 Height 9.84 outside 101
Volume(Cu.ft): 2436 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 203
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 7530
wall (W) 0 26 0.15 0 RTH 8500
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.89
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 24 0.11 654 15.624
Floor 0 24 0.5 0 DE AIR CFM 446
Partition 235 24 0.11 620 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 6548
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 982
TOTAL ROOM SENSIBLE HEAT (RSH) 7530
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 7530
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 8500
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 8500
2% 170
GRAND TOTAL HEAT 8670
TR 0.72
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-14- SPARE OFFICE -1 Date:
Client: CONDITIONS DB
Area(sq.ft) 247.59 Height 9.84 Outside 102
Volume(Cu.ft): 2436 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 203
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 7591
wall (W) 0 27 0.15 0 RTH 8561
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.89
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 25 0.11 681 13.5
Floor 0 25 0.50 0 DE AIR CFM 521
Partition 235 25 0.11 646 NOTES
INFILTRATION & OUTSIDE AIR 2.564448
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 6601
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 990
TOTAL ROOM SENSIBLE HEAT (RSH) 7591
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 8561
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 8561
2% 171
GRAND TOTAL HEAT 8732
TR 0.73

B.T.U. ESTIMATION FORM


WINTER SAC-14- SPARE OFFICE -1 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 247.5876 Height 9.84 outside 101
Volume(Cu.ft): 2436 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 203
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 7530
wall (W) 0 26 0.15 0 RTH 8500
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.89
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 24 0.11 654 15.624
Floor 0 24 0.5 0 DE AIR CFM 446
Partition 235 24 0.11 620 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 6548
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 982
TOTAL ROOM SENSIBLE HEAT (RSH) 7530
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 7530
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 8500
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 8500
2% 170
GRAND TOTAL HEAT 8670
TR 0.72
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-15- SPARE OFFICE -2 Date:
Client: CONDITIONS DB
Area(sq.ft) 247.59 Height 9.84 Outside 102
Volume(Cu.ft): 2436 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 203
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 7591
wall (W) 0 27 0.15 0 RTH 8561
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.89
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 25 0.11 681 13.5
Floor 0 25 0.50 0 DE AIR CFM 521
Partition 235 25 0.11 646 NOTES
INFILTRATION & OUTSIDE AIR 2.564448
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 6601
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 990
TOTAL ROOM SENSIBLE HEAT (RSH) 7591
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 8561
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 8561
2% 171
GRAND TOTAL HEAT 8732
TR 0.73

B.T.U. ESTIMATION FORM


WINTER SAC-15- SPARE OFFICE -2 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 247.5876 Height 9.84 outside 101
Volume(Cu.ft): 2436 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 2436 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 203
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 7530
wall (W) 0 26 0.15 0 RTH 8500
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.89
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 248 24 0.11 654 15.624
Floor 0 24 0.5 0 DE AIR CFM 446
Partition 235 24 0.11 620 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 495.2 Watts 3.41 2111
ROOM SENSIBLE HEAT SUB TOTAL 6548
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 982
TOTAL ROOM SENSIBLE HEAT (RSH) 7530
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 7530
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 8500
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 8500
2% 170
GRAND TOTAL HEAT 8670
TR 0.72
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-16- SPARE OFFICE -3 Date:
Client: CONDITIONS DB
Area(sq.ft) 195.47 Height 9.84 Outside 102
Volume(Cu.ft): 1923 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1923 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 160
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 178 33 0.15 880 RSH 7771
wall (W) 0 27 0.15 0 RTH 8741
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.89
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 195 25 0.11 538 13.5
Floor 0 25 0.50 0 DE AIR CFM 533
Partition 186 25 0.11 510 NOTES
INFILTRATION & OUTSIDE AIR 3.325105
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 390.9 Watts 3.41 1666
ROOM SENSIBLE HEAT SUB TOTAL 6757
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 1014
TOTAL ROOM SENSIBLE HEAT (RSH) 7771
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 8741
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 8741
2% 175
GRAND TOTAL HEAT 8916
TR 0.74

B.T.U. ESTIMATION FORM


WINTER SAC-16- SPARE OFFICE -3 Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 195.467236 Height 9.84 outside 101
Volume(Cu.ft): 1923 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1923 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 160
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 178 32 0.15 853 RSH 7692
wall (W) 0 26 0.15 0 RTH 8662
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.89
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 195 24 0.11 516 15.624
Floor 0 24 0.5 0 DE AIR CFM 456
Partition 186 24 0.11 490 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 390.9 Watts 3.41 1666
ROOM SENSIBLE HEAT SUB TOTAL 6688
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 1003
TOTAL ROOM SENSIBLE HEAT (RSH) 7692
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 7692
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 8662
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 8662
2% 173
GRAND TOTAL HEAT 8835
TR 0.74
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-17 - ADMIN Date:
Client: CONDITIONS DB
Area(sq.ft) 193.13 Height 9.84 Outside 102
Volume(Cu.ft): 1900 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1900 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 158
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 118 19 0.15 337 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 6903
wall (W) 0 27 0.15 0 RTH 7873
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 193 25 0.11 531 13.5
Floor 0 25 0.50 0 DE AIR CFM 473
Partition 118 25 0.11 325 NOTES
INFILTRATION & OUTSIDE AIR 2.989683
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 386.3 Watts 3.41 1646
ROOM SENSIBLE HEAT SUB TOTAL 6003
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 900
TOTAL ROOM SENSIBLE HEAT (RSH) 6903
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7873
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7873
2% 157
GRAND TOTAL HEAT 8031
TR 0.67

B.T.U. ESTIMATION FORM


WINTER SAC-17 - ADMIN Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 193.131509 Height 9.84 outside 101
Volume(Cu.ft): 1900 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1900 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 158
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 118 18 0.15 319 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 6843
wall (W) 0 26 0.15 0 RTH 7814
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.88
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 193 24 0.11 510 15.624
Floor 0 24 0.5 0 DE AIR CFM 406
Partition 118 24 0.11 312 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 386.3 Watts 3.41 1646
ROOM SENSIBLE HEAT SUB TOTAL 5951
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 893
TOTAL ROOM SENSIBLE HEAT (RSH) 6843
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 6843
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7814
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7814
2% 156
GRAND TOTAL HEAT 7970
TR 0.66
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-18 - Q A DIRECTOR Date:
Client: CONDITIONS DB
Area(sq.ft) 193.13 Height 9.84 Outside 102
Volume(Cu.ft): 1900 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1900 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 158
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 118 19 0.15 337 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 6903
wall (W) 0 27 0.15 0 RTH 7873
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 193 25 0.11 531 13.5
Floor 0 25 0.50 0 DE AIR CFM 473
Partition 118 25 0.11 325 NOTES
INFILTRATION & OUTSIDE AIR 2.989683
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 386.3 Watts 3.41 1646
ROOM SENSIBLE HEAT SUB TOTAL 6003
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 900
TOTAL ROOM SENSIBLE HEAT (RSH) 6903
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7873
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7873
2% 157
GRAND TOTAL HEAT 8031
TR 0.67

B.T.U. ESTIMATION FORM


WINTER SAC-18 - Q A DIRECTOR Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 193.131509 Height 9.84 outside 101
Volume(Cu.ft): 1900 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1900 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 158
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 118 18 0.15 319 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 6843
wall (W) 0 26 0.15 0 RTH 7814
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.88
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 193 24 0.11 510 15.624
Floor 0 24 0.5 0 DE AIR CFM 406
Partition 118 24 0.11 312 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 386.3 Watts 3.41 1646
ROOM SENSIBLE HEAT SUB TOTAL 5951
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 893
TOTAL ROOM SENSIBLE HEAT (RSH) 6843
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 6843
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7814
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7814
2% 156
GRAND TOTAL HEAT 7970
TR 0.66
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-19 - QA OFFICE Date:
Client: CONDITIONS DB
Area(sq.ft) 193.13 Height 9.84 Outside 102
Volume(Cu.ft): 1900 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1900 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 158
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 118 19 0.15 337 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 6903
wall (W) 0 27 0.15 0 RTH 7873
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 193 25 0.11 531 13.5
Floor 0 25 0.50 0 DE AIR CFM 473
Partition 118 25 0.11 325 NOTES
INFILTRATION & OUTSIDE AIR 2.989683
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 386.3 Watts 3.41 1646
ROOM SENSIBLE HEAT SUB TOTAL 6003
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 900
TOTAL ROOM SENSIBLE HEAT (RSH) 6903
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7873
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7873
2% 157
GRAND TOTAL HEAT 8031
TR 0.67

B.T.U. ESTIMATION FORM


WINTER SAC-19 - QA OFFICE Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 193.131509 Height 9.84 outside 101
Volume(Cu.ft): 1900 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1900 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 158
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 118 18 0.15 319 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 6843
wall (W) 0 26 0.15 0 RTH 7814
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.88
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 193 24 0.11 510 15.624
Floor 0 24 0.5 0 DE AIR CFM 406
Partition 118 24 0.11 312 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 386.3 Watts 3.41 1646
ROOM SENSIBLE HEAT SUB TOTAL 5951
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 893
TOTAL ROOM SENSIBLE HEAT (RSH) 6843
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 6843
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7814
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7814
2% 156
GRAND TOTAL HEAT 7970
TR 0.66
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-20 - DOCUMENTATION Date:
Client: CONDITIONS DB
Area(sq.ft) 193.13 Height 9.84 Outside 102
Volume(Cu.ft): 1900 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1900 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 158
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 118 19 0.15 337 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 6903
wall (W) 0 27 0.15 0 RTH 7873
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 193 25 0.11 531 13.5
Floor 0 25 0.50 0 DE AIR CFM 473
Partition 118 25 0.11 325 NOTES
INFILTRATION & OUTSIDE AIR 2.989683
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 386.3 Watts 3.41 1646
ROOM SENSIBLE HEAT SUB TOTAL 6003
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 900
TOTAL ROOM SENSIBLE HEAT (RSH) 6903
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7873
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7873
2% 157
GRAND TOTAL HEAT 8031
TR 0.67

B.T.U. ESTIMATION FORM


WINTER SAC-20 - DOCUMENTATION Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 193.131509 Height 9.84 outside 101
Volume(Cu.ft): 1900 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1900 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 158
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 118 18 0.15 319 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 6843
wall (W) 0 26 0.15 0 RTH 7814
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.88
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 193 24 0.11 510 15.624
Floor 0 24 0.5 0 DE AIR CFM 406
Partition 118 24 0.11 312 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 386.3 Watts 3.41 1646
ROOM SENSIBLE HEAT SUB TOTAL 5951
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 893
TOTAL ROOM SENSIBLE HEAT (RSH) 6843
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 6843
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7814
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7814
2% 156
GRAND TOTAL HEAT 7970
TR 0.66
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-21 - IT Date:
Client: CONDITIONS DB
Area(sq.ft) 193.13 Height 9.84 Outside 102
Volume(Cu.ft): 1900 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1900 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 158
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 118 19 0.15 337 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 6903
wall (W) 0 27 0.15 0 RTH 7873
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 193 25 0.11 531 13.5
Floor 0 25 0.50 0 DE AIR CFM 473
Partition 118 25 0.11 325 NOTES
INFILTRATION & OUTSIDE AIR 2.989683
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 386.3 Watts 3.41 1646
ROOM SENSIBLE HEAT SUB TOTAL 6003
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 900
TOTAL ROOM SENSIBLE HEAT (RSH) 6903
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7873
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7873
2% 157
GRAND TOTAL HEAT 8031
TR 0.67

B.T.U. ESTIMATION FORM


WINTER SAC-21 - IT Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 193.131509 Height 9.84 outside 101
Volume(Cu.ft): 1900 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1900 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 158
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 118 18 0.15 319 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 6843
wall (W) 0 26 0.15 0 RTH 7814
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.88
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 193 24 0.11 510 15.624
Floor 0 24 0.5 0 DE AIR CFM 406
Partition 118 24 0.11 312 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 386.3 Watts 3.41 1646
ROOM SENSIBLE HEAT SUB TOTAL 5951
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 893
TOTAL ROOM SENSIBLE HEAT (RSH) 6843
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 6843
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7814
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7814
2% 156
GRAND TOTAL HEAT 7970
TR 0.66
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-22 - SERVER ROOM Date:
Client: CONDITIONS DB
Area(sq.ft) 151.50 Height 9.84 Outside 102
Volume(Cu.ft): 1491 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1491 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 124
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 93 19 0.15 264 SENSIBLE HEAT FACTOR
wall (E) 138 33 0.15 682 RSH 6984
wall (W) 0 27 0.15 0 RTH 7954
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.88
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 152 25 0.11 417 13.5
Floor 0 25 0.50 0 DE AIR CFM 479
Partition 93 25 0.11 255 NOTES
INFILTRATION & OUTSIDE AIR 3.855521
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 303.0 Watts 3.41 1292
ROOM SENSIBLE HEAT SUB TOTAL 6073
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 911
TOTAL ROOM SENSIBLE HEAT (RSH) 6984
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7954
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7954
2% 159
GRAND TOTAL HEAT 8113
TR 0.68

B.T.U. ESTIMATION FORM


WINTER SAC-22 - SERVER ROOM Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 151.50367292 Height 9.84 outside 101
Volume(Cu.ft): 1491 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 1491 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 124
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 93 18 0.15 250 SENSIBLE HEAT FACTOR
wall (E) 138 32 0.15 661 RSH 6913
wall (W) 0 26 0.15 0 RTH 7883
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.88
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 152 24 0.11 400 15.624
Floor 0 24 0.5 0 DE AIR CFM 410
Partition 93 24 0.11 245 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 303.0 Watts 3.41 1292
ROOM SENSIBLE HEAT SUB TOTAL 6011
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 902
TOTAL ROOM SENSIBLE HEAT (RSH) 6913
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 6913
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 7883
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 7883
2% 158
GRAND TOTAL HEAT 8041
TR 0.67
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-23 - RECEPTION AND WAITING ROOM Date:
Client: CONDITIONS DB
Area(sq.ft) 635.32 Height 9.84 Outside 102
Volume(Cu.ft): 6252 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 6252 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 521
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 14999
wall (W) 275 27 0.15 1115 RTH 16455
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.91
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 635 25 0.11 1747 13.5
Floor 0 25 0.50 0 DE AIR CFM 1029
Partition 470 25 0.11 1292 NOTES
INFILTRATION & OUTSIDE AIR 1.974746
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 3.0 People X 309 927
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 1270.6 Watts 3.41 5416
ROOM SENSIBLE HEAT SUB TOTAL 13043
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 1956
TOTAL ROOM SENSIBLE HEAT (RSH) 14999
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 3.0 People X 441 1323
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 1323
Supply duct Safety
leakage loss % + Factor 10% 132
TOTAL ROOM LATENT HEAT 1455
ROOM TOTAL HEAT(RTH) 16455
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 16455
2% 329
GRAND TOTAL HEAT 16784
TR 1.40

B.T.U. ESTIMATION FORM


WINTER SAC-23 - RECEPTION AND WAITING ROOM Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 635.317744 Height 9.84 outside 101
Volume(Cu.ft): 6252 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 6252 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 521
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 14812
wall (W) 275 26 0.15 1074 RTH 16267
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.91
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.64
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 635 24 0.11 1677 15.624
Floor 0 24 0.5 0 DE AIR CFM 878
Partition 470 24 0.11 1241 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 3.0 People X 309 927
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 1270.6 Watts 3.41 5416
ROOM SENSIBLE HEAT SUB TOTAL 12880
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 1932
TOTAL ROOM SENSIBLE HEAT (RSH) 14812
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 3.0 People X 441 1323
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 14812
ROOM LATENT HEAT SUB TOTAL 1323
Supply duct Safety
leakage loss % + Factor 10% 132
TOTAL ROOM LATENT HEAT 1455
ROOM TOTAL HEAT(RTH) 16267
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 16267
2% 325
GRAND TOTAL HEAT 16593
TR 1.38
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-24 - RO PLANT Date:
Client: CONDITIONS DB
Area(sq.ft) 2107.88 Height 16.40 Outside 102
Volume(Cu.ft): 34569 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 34569 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 2881
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 82016
wall (W) 0 27 0.15 0 RTH 82986
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.99
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 2108 25 0.11 5797 13.5
Floor 0 25 0.50 0 DE AIR CFM 5625
Partition 3185 25 0.11 8759 NOTES
INFILTRATION & OUTSIDE AIR 1.952677
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 15.0 HP 2545 38175
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 4215.8 Watts 3.41 17970
ROOM SENSIBLE HEAT SUB TOTAL 71318
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 10698
TOTAL ROOM SENSIBLE HEAT (RSH) 82016
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 82986
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 82986
2% 1660
GRAND TOTAL HEAT 84646
TR 7.05

B.T.U. ESTIMATION FORM


WINTER SAC-24 - RO PLANT Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 2107.884 Height 16.4 outside 101
Volume(Cu.ft): 34569 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 34569 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 2881
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 81346
wall (W) 0 26 0.15 0 RTH 82316
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.99
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 2108 24 0.11 5565 13.5
Floor 0 24 0.5 0 DE AIR CFM 5579
Partition 3185 24 0.11 8408 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 2.0 People X 309 618
HP 15.0 HP 2545 38175
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 4215.8 Watts 3.41 17970
ROOM SENSIBLE HEAT SUB TOTAL 70736
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 10610
TOTAL ROOM SENSIBLE HEAT (RSH) 81346
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 2.0 People X 441 882
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 81346
ROOM LATENT HEAT SUB TOTAL 882
Supply duct Safety
leakage loss % + Factor 10% 88
TOTAL ROOM LATENT HEAT 970
ROOM TOTAL HEAT(RTH) 82316
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 82316
2% 1646
GRAND TOTAL HEAT 83963
TR 7.00
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

7.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW
B.T.U. ESTIMATION FORM
Summer SAC-25 - TRAINING ROOM Date:
Client: CONDITIONS DB
Area(sq.ft) 589.26 Height 9.18 Outside 102
Volume(Cu.ft): 5412 Inside 72
Difference 30
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 5412 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 CFM 451
Glass(S) 0 12 0.56 0 CFM
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 19 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 33 0.15 0 RSH 19106
wall (W) 249 27 0.15 1010 RTH 26382
wall (S) 0 31 0.15 0
Roof sun 0 50 0.50 0 SHF 0.72
Roof insulated 0 50 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 30 1.13 0
Partition glass 0 25 0.8 0 DEHUMIDIFIED AIR
Ceiling 589 25 0.11 1620 13.5
Floor 0 25 0.50 0 DE AIR CFM 1310
Partition 647 25 0.11 1780 NOTES
INFILTRATION & OUTSIDE AIR 2.905723
outside air DB diff BF 1.08
0 30 0.1 1.08 0
INTERNAL HEAT
People 15.0 People X 309 4635
HP 1.0 HP 2545 2545
Blower HP 2545 0
Miscell 0.0 3410 0 Heater 0.0
Lights 1178.5 Watts 3.41 5023
ROOM SENSIBLE HEAT SUB TOTAL 16614
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 2492
TOTAL ROOM SENSIBLE HEAT (RSH) 19106
LATENT HEAT
cfm Gr/lb BF
0 130 0.1 0.68 0
People 15.0 People X 441 6615
Steam 0 lb/hr X
Appliances 0
Permeation Load 0 0
ROOM LATENT HEAT SUB TOTAL 6615
Supply duct Safety
leakage loss % + Factor 10% 662
TOTAL ROOM LATENT HEAT 7277
ROOM TOTAL HEAT(RTH) 26382
OUTDOOR AIR HEAT
Sensible 0 30 0.9 0
Latent 0 130 0.9 0
GRAND TOTAL HEAT SUB TOTAL 26382
2% 528
GRAND TOTAL HEAT 26910
TR 2.24

B.T.U. ESTIMATION FORM


WINTER SAC-25 - TRAINING ROOM Date:
Client: 0 CONDITIONS DB
Area (sq.ft.) 589.259026 Height 9.184 outside 101
Volume(Cu.ft): 5412 inside 72
Difference 29
sun gain/
Item Area or Qty(Sq.ft) Factor Btu / Hour
Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 0 14 0.56 0 5412 Cu.ft
Glass(E) 0 12 0.56 0 60
Glass(W) 0 164 0.56 0 451
Glass(S) 0 12 0.56 0 CFM 0
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 0 18 0.15 0 SENSIBLE HEAT FACTOR
wall (E) 0 32 0.15 0 RSH 18907
wall (W) 249 26 0.15 973 RTH 26183
wall (S) 0 30 0.15 0
Roof sun 0 49 0.5 0 SHF 0.72
Roof insulated 0 49 0.45 0
TRANS GAIN EXCEPT WALLS & ROOFS ADP 57
All glass 0 29 1.13 0
Partition glass 0 24 0.8 0 DEHUMIDIFIED AIR
Ceiling 589 24 0.11 1556 13.5
Floor 0 24 0.5 0 DE AIR CFM 1297
Partition 647 24 0.11 1708 NOTES
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
0 29 0.1 1.08 0
INTERNAL HEAT
People 15.0 People X 309 4635
HP 1.0 HP 2545 2545
Blower HP 0.0 2545 0
Miscell 0 3410 0 Heater 3.0
Lights 1178.5 Watts 3.41 5023
ROOM SENSIBLE HEAT SUB TOTAL 16440
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 2466
TOTAL ROOM SENSIBLE HEAT (RSH) 18907
LATENT HEAT
cfm Gr/lb BF
0 218 0.1 0.68 0
People 15.0 People X 441 6615
Steam 0 lb/hr X
Appliances 0
Miscell 0 0 18907
ROOM LATENT HEAT SUB TOTAL 6615
Supply duct Safety
leakage loss % + Factor 10% 662
TOTAL ROOM LATENT HEAT 7277
ROOM TOTAL HEAT(RTH) 26183
OUTDOOR AIR HEAT
Sensible 0 29 0.9 0
Latent 0 218 0.9 0
GRAND TOTAL HEAT SUB TOTAL 26183
2% 524
GRAND TOTAL HEAT 26707
TR 2.23
21/06/2013
WB %RH Gr/lb
64 200
60 70
XXX 130

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

0.5
KW
21/06/2013
WB %RH Gr/lb
93 288
60 70
XXX XXX 218

VENTILATION
5 X ACPH

SENSIBLE HEAT FACTOR

(From tables/chart)

DEHUMIDIFIED AIR

KW