CONTRACTS AM-CO630
6305-EL-ETP-7080-A00
POWER AND LIGHTING SYSTEMS - MAITENES
DISCHARGE ZONE
EMERGENCY GENERATOR DIESEL SETS
TECHNICAL SPECIFICATION
Modifications:
6305-EL-ETP-7080-A00
POWER AND LIGHTING SYSTEMS
EMERGENCY DIESEL GENERATOR SETS
TECHNICAL SPECIFICATION
Table of Contents
1. INTRODUCTION .................................................................................................. 3
2. SCOPE ................................................................................................................. 3
3. STANDARDS........................................................................................................ 3
4. SERVICE CONDITIONS....................................................................................... 4
5. EMERGENCY GENERATOR ............................................................................... 4
5.1 DESIGN AND CONSTRUCTIONAL DETAILS: .......................................... 4
5.1.1 Plates : ........................................................................................... 4
1.1 Scope ......................................................................................................... 4
1.2 Functions, Layout, Performance ................................................................. 5
1.3 Design Requirements ................................................................................. 5
1.3.1 General .......................................................................................... 5
1.3.2 Diesel Engine ................................................................................. 5
1.3.3 Governor ........................................................................................ 6
1.3.4 Cooling System .............................................................................. 6
1.3.5 Fuel Oil System .............................................................................. 6
1.3.6 Lubricating Oil System ................................................................... 7
1.3.7 Combustion Air System.................................................................. 7
1.3.8 Exhaust System ............................................................................. 7
1.3.9 Noise Level .................................................................................... 7
1.3.10 Generator ....................................................................................... 7
1.3.11 Control Panels ............................................................................... 9
1.3.12 Battery Starting System ............................................................... 10
1.4 Control and Monitoring ............................................................................. 10
1.5 Tests ......................................................................................................... 10
1.5.1 Workshop Tests ........................................................................... 10
1.5.2 Site Tests ..................................................................................... 11
1.6 Spare Parts and Special Tools ................................................................. 11
1.6.1 Spare Parts .................................................................................. 11
1.6.2 Tools ............................................................................................ 12
1.7 Documents and Drawings ......................................................................... 12
Page2 of 13
6305-EL-ETP-7080-A00
POWER AND LIGHTING SYSTEMS
EMERGENCY DIESEL GENERATOR SETS
TECHNICAL SPECIFICATION
1. INTRODUCTION
The electrical station systems shall be required to provide the voltage classes
indicated in Table 1.1. for operation of various plant equipment operating
mechanisms, plants, control and communication systems:
2. SCOPE
This specification covers manufacture, assembly and testing at manufacturers
works, supply and delivery on site of the Emergency Generator Diesel for the
Discharge Chanel Modification loads belonging to the Surface Works Las Lajas.
3. STANDARDS
The equipment shall comply in all respects with the latest edition of relevant Indian
Standard Specifications and IEC except for the modifications specified herein. A
Photo copy of such standards in English shall be enclosed with the offer.
Page3 of 13
6305-EL-ETP-7080-A00
POWER AND LIGHTING SYSTEMS
EMERGENCY DIESEL GENERATOR SETS
TECHNICAL SPECIFICATION
4. SERVICE CONDITIONS
The ambient environmental conditions for the transmission lines are as follows.
5. EMERGENCY GENERATOR
1.1 Scope
a) One (1) 75 kVA (60 kW) standby Diesel generator set connected to
the 400 VAC distribution system of the diversion weir (power intake)
including fuel storage tank of 1,000 liters;
All including:
The combustion and cooling air supply and exhaust system;
The battery starting system;
The fuel oil system;
The generator and engine control, excitation, protection and
monitoring equipment;
All necessary accessories, wiring and cabling, cubicles, etc. to make
it a complete system;
The fuel oil and all consumable products for the tests and the first
filling of the fuel oil main storage tanks after the tests;
The spare parts and special tools.
Page4 of 13
6305-EL-ETP-7080-A00
POWER AND LIGHTING SYSTEMS
EMERGENCY DIESEL GENERATOR SETS
TECHNICAL SPECIFICATION
1.3.1 General
The equipment shall comply with the following standards:
ISO 3046/II and III: Diesel engines;
DIN 25467: Emergency generating stations with Diesel engines;
design; safety requirements;
IEC 60034.1 and 60034.5 for Generator.
The standby Diesel generator units shall be designed for continuous
operation and for long periods of standstill.
The diesel Generator units shall be provided to start/operate/stop in
complete autonomy with their own automatic/manual starting systems
and with independent ventilation and cooling systems.
Page5 of 13
6305-EL-ETP-7080-A00
POWER AND LIGHTING SYSTEMS
EMERGENCY DIESEL GENERATOR SETS
TECHNICAL SPECIFICATION
cooled closed circuit with radiator, battery starting, four stroke, multi-
cylinder with changeable cylinder liners, forced oil lubrication with cooler,
mechanical or hydraulic governor, suitable flywheel for flicker-free
operation, exhaust silencer with necessary piping.
1.3.3 Governor
Between 10 and 100% of the rated output, the steady load speed band
shall not exceed 1% of the rated speed.
External means of adjustment of the nominal speed setting by 5% at all
loads between 0 and 100% load shall be provided.
Page6 of 13
6305-EL-ETP-7080-A00
POWER AND LIGHTING SYSTEMS
EMERGENCY DIESEL GENERATOR SETS
TECHNICAL SPECIFICATION
1.3.10 Generator
1.3.10.1 General
The AC generator shall be of constant voltage, 60 Hz, three-phase, air
cooled, self-excited type. Damper windings shall be uniformly distributed
around the rotor.
The star-point of the generator shall be grounded through a contactor.
The contactor must be opened during test run in parallel operation with
the normal AC supply system (star-point grounded) for preventing flow of
third harmonic currents. During isolated operation of the Diesel unit the
contactor must be closed. The same procedure is also valid for the
Page7 of 13
6305-EL-ETP-7080-A00
POWER AND LIGHTING SYSTEMS
EMERGENCY DIESEL GENERATOR SETS
TECHNICAL SPECIFICATION
Voltage variation between 0 and 100% of rated load: < 2.5% of rated
voltage;
The generator shall be able to withstand 1.2 times the rated speed;
Protection index of the enclosure: IP56 (weather protective
enclosure);
Type of duty : continuous running duty type S1 as per IEC 60034-1.
1.3.10.3 Ratings
Diversion weir
Voltage 400 V
Phases 3-phase, 4
wire
Neutral solidly
grounded via
contactor
Frequency 60 Hz
Page8 of 13
6305-EL-ETP-7080-A00
POWER AND LIGHTING SYSTEMS
EMERGENCY DIESEL GENERATOR SETS
TECHNICAL SPECIFICATION
Page9 of 13
6305-EL-ETP-7080-A00
POWER AND LIGHTING SYSTEMS
EMERGENCY DIESEL GENERATOR SETS
TECHNICAL SPECIFICATION
1.5 Tests
Page10 of 13
6305-EL-ETP-7080-A00
POWER AND LIGHTING SYSTEMS
EMERGENCY DIESEL GENERATOR SETS
TECHNICAL SPECIFICATION
4) Overspeed Test
The engine shall be operated for a period of three minutes at 110% of
the normal speed.
5) Generator
Temperature rise test;
Dielectric test;
Determination of losses and efficiency;
AVR tests to determine the performances of the voltage regulator.
Page11 of 13
6305-EL-ETP-7080-A00
POWER AND LIGHTING SYSTEMS
EMERGENCY DIESEL GENERATOR SETS
TECHNICAL SPECIFICATION
1.6.2 Tools
A complete set of tools for maintenance and overhauling the engine and
its accessories shall be supplied, in particular:
Crank deflection gauges;
Thickness gauges;
Nozzle tester with pressure gauges;
Torque wrenches;
Cylinder maximum pressure indicator.
Page12 of 13
6305-EL-ETP-7080-A00
POWER AND LIGHTING SYSTEMS
EMERGENCY DIESEL GENERATOR SETS
TECHNICAL SPECIFICATION
Loading drawings A
Stress analysis for main components A
Electrical calculations and characteristics A
Design drawings and assembly drawings A
Diagrams, lists and schedules:
single line diagrams A
circuit diagrams A
terminal diagrams I
block diagrams A
logic diagrams A
protection coordination diagrams A
instrumentation diagrams A
consumer schedules I
feeder data schedules I
signal lists I
setting and alarm list A
P&I diagrams A
cable lists I
Lists of tools and appliances A
Spare part lists A
List of EDS identification numbers I
Specification for rating plates and labels, including list of A
inscriptions
Page13 of 13