following conditions. The initiating signal in each case actuates both the channels. MS TEMPERATURE LOW Temp. less than 4500C (Arming at 5100C) CONDENSER PRESSURE PROTECTION When condenser pressure greater than 0.3kg/cm2. LUBE OIL PRESSURELOW The protection acts if the lube oil pressure before thrust bearing decreases to 1.2Kg/Cm. The trip signal is initiated by three pressure transmitters in 2-out- of-3-logic. FIRE PROTECTION Fire protection is basically is a protection against oil leakage rather than fire. Because oil leakage may lead to fire, the fire protection is used. HP EXHAUST TEMP. HIGH The HP exhaust steam temp. protection circuit. protects the exhaust section of the Turbine, the blading & extraction points against overheating. During start up/shutdown or load rejections, there can be long period during which steam turbines are operated at very low volumetric flows and relatively high back pressure i.e. the mech. Energy transmitted by the turbine shaft is converted to thermal energy, which in turn result in an increase in the temp. of both the exhaust steam and turbine components . This temp. is required to be monitored to avoid any deformation in the casing or blades. The temp is measured by means of three Thermocouples and protection criteria is derived in 2 out of 3 logics. AXIAL SHIFT VERY HIGH (THRUST BRG TRIP) A too high axial displacement of the turbine shaft may cause damage to the turbine blades. This protection trips the turbine in case the axial shift of the shaft exceeds the limits set during erection . The axial shift is measured in both directions () using three proximity probes. These measured signals are fed to a protection circuit designed in 2-out-of -3 logic for further realization. TG BEARIN G METAL TEMP. VERY HIGH The excessive temperature rise of bearings during operation can cause wear to bearing shells. Bearing temperature high trip protects the thrust and journal bearings of the Turbine and Generator against excessive temperatures rise. The temperature of the Babbitt metal temp is measured by means of four thermocouples in the bearing for each bearing at HP front and HP rear Journal bearings and Thrust bearing. In other journal bearings, temperature is measured by means of thermocouples at front and rear end of generator and exciter. Protection criteria are derived in 2 out of 3 logics configurations of each bearings to safe guard the TG set. Automatic Turbine Run up system In a start up or stopping of turbine various parameters like oil pressure, vacuum, warmup conditions, steam and metal temperature, speed etc are involved. The acquisition and analysis of above parameters demand quick decision and action from operator. In order to reduce this arduous task of monitoring various parameters and to start the turbine in proper sequence and to avoid human error automatic turbine run up system is introduced. The ATRS is based on Functional group control philosophy. The main plant is divided in clearly defined functional group 1) Turbine 2) Oil supply 3) Condensate and evacuation Each functional group is organised and arranged in 1) Sub group control (SGC) 2) Sub loop Control (SLC) 3) Control Interface (CI) Functional Group Control: - It continues to function automatically all the time demanding enable criteria based on process requirement and from neighboring functional group if required. In the absence of required data system will act to ensure safety of the main equipment. Sub group Control (SGC) : - It executes command to bring equipment at desired state and contains the start up and shutdown program of respective group. SGC issues command either to SLC or control interface. The program comprises of steps. For each step there is provision for monitoring and waiting time. Waiting time implies that the subsequent step could not be executed unless the specific time elapsed. The time between command signal and appearance of feed back is monitoring time. If monitoring time exceeds alarm is initiated and program does not proceed. Bypass facility is provided to enable switching on program after completing certain criteria manually if so desired. Operator guide mode:- This mode receives the data from the plant but issues no command. The commands to control interface are issued manually. SGC Oil system:- The main task of this control is to bring the turbine oil system to the desired level of operation enabling machine to be put on barring gear. SGC Evacuation :- Its objective is to raise the vacuum in the condenser to the desired level so that turbine can be rolled and synchronised. The system takes care of condensate pumps and ejector or vacuum pump SGC Turbine system :- The major functions of this system are 1) warming up 2) Quick speed raising limited to permissible TSE 3) Steam and metal temperature matching 4) Auto synchronising and loading upto 10% load Sub loop control:- When SLC is switched ON, it actuates the connected mechanical equipment to the required operating condition as per process condition. No sequence logic is involved. SLC can be switched ON/OFF either manually or through SGC. Drain valve, warmup valves, starting device of turbine, speed and load set point of EHC, and auto synchroniser are operated through SLC Control Interface:- It is the lowest in the hierarchical structure of the control system. Each control drive has control interface module which acts as interface between command transmitter and actuator. Protective logic is incorporated in this module. It gives feed back signal to the FGC. Turbine Governing system :- Oil from AOP/MOP goes to oil header. Through filter it goes to starting device and through remote trip solenoids into Main turbine trip valve This oil is control oil (code colour yellow) Control oil in starting device generates start up oil (Grey colour) and auxiliary oil. Start up oil goes to Stop valve through Test valve (changeover valve).start up oil pressure keeps the stop valve in close position. Auxiliary start up oil goes to auxiliaries like main trip valve and tripping and tripping device. Control Oil going to main trip valve generates trip oil (Red colour) and auxiliary trip oil (Red-white colour). Trip oil goes to stop valve through test valve, Hydraulic controller and Electro Hydraulic controller. Auxiliary trip oil goes to auxiliaries i.e. trip devices Trip oil going to hydraulic and electro hydraulic controller generates secondary oil (blue colour) which goes to HP and IP control valve to control valve opening. Speeder gear which is linked with starting device generates auxiliary secondary oil (blue-white colour) which goes to hydraulic controller as controller signal. Primary oil (Green colour) from MOP comes as speed signal feed back for speed control. Electrical signal from PCR goes to electro hydraulic controller. Both Hydraulic and and electro hydraulic controller are in parallel with minimum gate. Hydraulic controller has 5 to 10% higher signal so that in normal case EHC signal extends to control valve When starting device is brought to '0' position, start up and auxiliary start up oil is build up to reset stop valve, main trip valve and hydraulic trip device. Raising starting device depressurises start up and auxiliary start up oil to open stop valve and producing auxiliary secondary oil Tripping of MTV through remote trip valve :- when remote trip solenoid valve operates its spool gets lifted and control oil to main trip valve gets depressurise through drain. As such main trip valve spool gets lifted and trip and auxiliary trip oil gets drained which closes all the stop valves. Tripping of MTV through hydraulic trip device when this operates, auxiliary trip oil in MTV gets drained and spool in MTV comes down causing trip oil to drain. Resetting of remote trip solenoid valve, hydraulic trip device, and main trip valve. As the remote trip valve de-energises control oil extends to MTV and starting device. As the starting device spool gets lifted upward due to control oil pressure, it generates start up oil and auxiliary start up oil. Auxiliary trip oil resets MTV and hydraulic trip device. As MTV resets, it generates trip oil and auxiliary trip oil. Start up oil from starting device extends to stop valve through test valve. Auxiliary trip oil goes to trip device and trip oil through test device goes to Main stop valve. Subsequently stop valve closes and turbine gets resetted. Automatic Turbine TRIP Tester To increase the reliability of tripping device from turbine safety point of view without interrupting operation of turbine this facility is provided. This confirms functioning of stop valves, control valves and tripping devices. To avoid turbine output changes and initial pressure variations due to closure of stop valve and control valve during testing, the electro hydraulic controller must be in operation prior to testing. To enable initial pressure to be maintained constant, turbine output should be below certain value The ATT has been divided into subgroup safety devices and sub group Control valve. Only one sub group can be selected at a time. The test program will be discontinued in case of any fault and automatically revert back (reset). Sub group safety device incorporate sub test for a) 1st remote trip solenoid valve b) 2nd remote trip solenoid valve c) Over speed trip device d) Hydraulic vacuum trip e) Thrust bearing trip (Axial shift) device. An alternative trip oil circuit is established for duration of testing of the safety device in order to ensure tripping of the turbine if called for during testing. The successful completion of the test are concluded from check back signal of oil pressure and other conditions. Associated annunciations are also activated enabling alarm testing also. Sub group HP/IP valves: - The stop and control valves are the final control elements of the safety devices and hence their reliability of operation is as important as that of tripping devices. Sub group HP/IP valves consists of sub test of HP stop and control valve-1, HP stop and control valve 2 IP stop and control valve-1, IP stop and control valve 2 One of the major test requirement is that output of turbo set must be less than maximum load as it calls for closing of one valve at a time. The test begins with the selection of valve test sub group. This is performed by pressing on/off push button. The sub group remains in on position until it is switched off or test program of that sub group is completed. While one valve test sub group is running, other sub groups are blocked. During this time controller compensate for the effects of closure of valve under test on initial pressure or turbine output by additionally opening the other control valves. Program monitors closing of the valve and time required time for closing. If the time for closing exceeds than preset value reset program is automatically initiated Protective device:- During normal operation protective devices act via main trip valve on stop and control valve. Remote trip solenoids, over speed trip device, thrust bearing trip device, and low vacuum trip device actuate main trip valves by operating auxiliary trip oil circuit. For the duration of testing of protective devices a hydraulic test circuit is established. In order to keep trip oil circuit effective, it is isolated from main trip valve by means of changeover valve and supplied with control oil via solenoid valve (during testing). To provide normal protection to turbine during testing any trip signal from protective device will de-energise the solenoid valve for control oil supply during testing and at the same time initiate reset program. This also applies to all normal electrical trip. During testing of protective devices actual tripping is avoided, however all annunciations are activated. After the sub group has been switched on, the protection device to be tested is selected by operating selection push button. A separate selection push button is provided for each individual device. Only one selection may be made at a time. Selection of other program is possible only after previous program is completed. Hydraulic test signal generator:- The function of test signal generator is to activate related protection device. For testing over speed device the associated signal generator generates test pressure slowly and passes it to over speed trip device. For testing vacuum trip an air signal is introduced to device via orifice. And for testing thrust bearing trip control oil signal is passed to test piston of device. Main trip valve :- is kept in its operative position by auxiliary trip oil pressure. If protective device is actuated the auxiliary trip oil circuit is de- pressurised and main trip valve is actuated. This connects trip oil and auxiliary oil to drain and shuts off the oil supply to turbine valves. At the same time limit switch is actuated. Pressure switches in trip oil and auxiliary trip oil circuit monitors actual operation of MTV Auxiliary start up oil pressure forces trip valve to normal position. Consequently trip and auxiliary trip oil pressure is build up and main trip valve gets resetted. Remote trip solenoid valve:- The function of this valve is to de-pressurise trip oil circuit in shortest possible time, thereby bringing main trip valve in to trip position in the event of malfunction requiring electrical trip. In the normal position trip solenoid valve allow control oil to pass through it to main trip valve which generates trip oil and auxiliary trip oil. For testing solenoid valve is energised which shuts off control oil and drains trip oil. Trip initiation is monitored through pressure switches mounted in trip and auxiliary trip oil circuit. In addition initiation of limit switch of main trip valve is observed. Over speed trip device:- The two over speed trips are provided to protect turbine in the event of load rejection with failure of speed governor. As this is important protection of turbine can be tested locally by hand during turbine operation at rated speed with the help of over speed hydraulic test signal generator. When over speed is reached, due to centrifugal force the eccentric flybolt of trip device activates piston to drain auxiliary trip oil, and limit switch to initiate annunciation. This causes trip oil to depressurise and finally trip the turbine. While testing specific force equivalent to centrifugal force at preset over speed is generated through hydraulic test signal generator by test oil to act on flybolt so as to activate trip device Low Vacuum trip:- The function of low vacuum trip is to operate main trip valve if, during normal operation the vacuum in the condenser is too weak for condensation to be properly effected. A spring with specific tension acts against diaphragm. Top side of diaphragm is connected to vacuum. When the vacuum is low below preset value, it cannot counter act spring tension. Spring moves valve downwards. The auxiliary oil pressure beneath adjacent valve gets depressurised through drain which activates MTV to trip the turbine. Thrust bearing trip:- The function of thrust bearing trip is to monitor the shaft position in the bearing pedestal. In case of any fault depressurise auxiliary trip oil and thus the trip oil circuit in shortest time thereby tripping the turbine. To test the thrust bearing trip, associated hydraulic test signal transmitter generates test signal which pass to test piston in device which deflects paul against spring force. Device piston comes to trip position and auxiliary trip oil gets drained. After tripping when starting device is activated auxiliary start up oil brings tripping device to normal position.