Académique Documents
Professionnel Documents
Culture Documents
Sutherland
GE
I
ndustrial power-distribution-system substa- Ground differential protection can be provided
tion transformers and generator step-up by digital overcurrent relays in conjunction with
transformers in power stations (Fig. 1 shown auxiliary ratio matching transformers. Ground dif-
above) often use resistance-grounded wye ferential protection can also be provided in
secondary windings for medium-voltage power multifunction digital relays. Transformer protec-
distribution. The purpose of this is to limit damage tion relays (Fig. 2) may include this feature with one
due to ground-fault currents, while providing suf- of the schemes used with component relays. If a
ficient fault current for the operation of feeder-protection relay is used on the secondary, in
ground-fault relaying. The relaying used to protect some cases, this may have a ground-directional fea-
against ground faults in the system may not pro-
vide sufficient protection of the transformer wind-
ing against internal faults because the backup Peter E. Sutherland is with Power Systems Energy Con-
ground overcurrent relay in the transformer neu- sulting, GE Power Systems of Schenectady, New York.
tral-to- ground connection must be set to coordi- Sutherland is a Senior Member of IEEE. This article ap-
nate with downstream relays. In order to protect peared in its original form at the 2000 Industrial &
the winding itself, special relays are utilized [1]. Commercial Power Systems Technical Conference.
Current (A)
2000
A separately powered solid-state relay [Table 0
I(a)] used in this application may have a typical
burden of <0.1 , regardless of setting. Thus, 2000 0 20 40 0 80 100 120 140
I gd = 3I 0 - I g . (2)
Ie
The residual current 3I0 can be found by look-
ing at the increase in per-unit primary current, Ip, Fig. 5. The knee-point of a CT saturation curve is
due to the fault. If the relay is to protect 95% of the point where a tangent to the curve forms a 45
the winding, this is a small effect, which can usu- angle with the horizontal axis.
Thus, by (3), I2 = 20 A 19 A = 1 A. And, since I2 The slope is set so that the relay will trip for the
is the increased phase current 3I0, the differential minimum differential current at the maximum
current is: line current (full-load current + 3I0):
I gd = 1 19 = 18 A. (5) I gd (6)
Slope = 100%
The relay will be set to pickup at this value. I line
18
= 100% = 3.5%.
521
1200/5 If the 1-A correction had been neglected, the result
would have been essentially the same.
1200/5
The effect of CT error can be evaluated for this
relay. Assuming that saturation effects would oc-
cur only on the resistor-side CT and that the relay
200/5 burden is 0.2 VA, resistive, CT leakage currents
Res. taken from a typical CT saturation curve are shown
in Table II. For the example above, the calculated
Ib I a
slope setting would only be affected by a fraction of
a percentage:
Ig 1200/5
I gd + I leakage (7)
3750 kVA
4160 V Ic Slope = 100%
3I0
I line
18 +0.09
= 100% = 3.5%.
Transformer Protection 521
Relay
Ic Calculate Timer
and 0 - 0.5 s Output
3I 0
I gd
Calculate
l gd > Setpoint
I3I0 - IgI
Ig Measure
Ig
If R CT + Lead (8)
3I 0 = If
CTR R CT + Lead + R Relay
20,000 0.368
= = 70 A.
240 0.44
I gd + I leakage (9)
Slope = 100% RES
I line
18+70 88
= 100% = 100% = 17%.
521 521
1200/5
this dilemma is to design the system to prevent
the line CTs from full saturation during external
phase faults.
1200/5 In order to prevent false tripping due to normal
CT errors, the minimum slope setting in this exam-
ple would be about 4%, but a setting which would
not cause false tripping even under conditions of
200/5
Res.
maximum CT saturation would be about 17%.
These numbers should not be taken as general
400 A
guidelines for appropriate settings. Every particu-
lar case should be evaluated in detail. The 4% slope
setting of the relay will result in the sensitivity de-
51 G
1200/5 creasing slightly as the loading on the transformer
increases. Because the slope is calculated based
(67N) 50 50 50 upon the maximum phase current rather than the
87 G 51 51 51 current into the differential circuit, the percentage
POL
values appear to be lower than with the traditional
(67N)
differential relay, although the effect is similar.
1/6
87 G (Auxiliary Ration The final setting is for time delay. This will be
OP Matching CT) set to allow for instantaneous relays downstream to
clear high current faults. This is a precautionary
Fig. 9. Electromechanical product type relay connected as a differential measure because if the differential functions and
ground relay. their restraint circuits operate correctly, the relay
should not operate for faults outside of the differen-
tial zone.
Voltage
Current
Table III. Performance of 87 tg with High Fault Currents Transformer Protection Relay
Case CT Ratio Avail. Fault Current (kA) CT Current 0.2 VA Relay Relay + CT + Lead Burden (W) Min. CT (V)
(A) Burden (W)
cially designed transformer ground-differential re- [4] D.J. West, Current transformer application guidelines, in
lay, CT saturation does not affect relay operation. Conf. Rec. Industrial and Commercial Power Systems Technical
When evaluating different types of ground-differ- Conference, Pittsburgh, PA, 1977, pp. 110-126.
[5] R.E. Cosse and W. Nichols, II, The practice of ground dif-
ential protection for a range of transformers, the ferential relaying, IEEE Trans. Ind. Applicat., vol. 30, no. 6,
factors relating to CT saturation may be calculated pp. 1472-1479, Nov./Dec. 1994.
and listed in a table that can be used for comparison [6] Transformer Management Relay, SR745, GE Multlin, Inc.,
purposes (Table IV). Markham, Ont., Canada.
The use of digital solid-state relays can result in [7] T. Sezi, A new approach to transformer ground differential
the benefits of ground-differential protection in protection, presented at the 1999 Industrial and Commer-
packaged multifunction relays. Either trans- cial Power Systems Annual Conference, Sparks, NV, 1999.
[8] B. Kasztenny, A. Kulidjian, B. Campbell, and M. Pozzuoli,
former- or feeder-type relays can be utilized, if they
Operate and restraint signals of a transformer differential
contain the necessary functions.
relay, presented at the 54th Annual Georgia Tech Protec-
tive Relaying Conference, Atlanta, GA, 2000.
References [9] N.T. Stringer and G. Dalke, Ground differential protec-
[1] P.E. Sutherland, Application of transformer ground differ- tion: revisited, IEEE Ind. Applicat. Mag., vol. 6, no. 2,
ential relays, IEEE Trans. Ind. Applicat., vol. 36, no. 1,
pp.53-58, Mar./Apr. 2000.
16-21, Jan./Feb. 2000.
[10] IEEE Recommended Practice for Protection and Coordination of
[2] IEEE Guide for the Application of Current Transformers Used for
Protective Relaying Purposes, IEEE Std. C37.110, 1996. Industrial and Commercial Power Systems (IEEE Buff Book),
[3] Standard Requirements for Instrument Transformers, IEEE Std. 242, 1986.
ANSI/IEEE Standard C57.13, 1993. [11] L.J. Powell, Jr., Current transformer burden and satura-
tion, IEEE Trans. Ind. Applicat., vol. IA-15, no. 3, pp.
294-303, May/June 1979.