Vous êtes sur la page 1sur 14

Engineering Structures 22 (2000) 755768

www.elsevier.com/locate/engstruct

The influence of the thermal expansion of beams on the structural


behaviour of columns in steel-framed structures during a fire
*
C.G. Bailey
Building Research Establishment, Centre for Steel Construction, Garston, Watford WD2 7JR, UK

Received 18 December 1998; accepted 11 March 1999

Abstract

In the UK, new design guidance is currently being developed for the behaviour of steel-framed buildings when subjected to fire.
This is primarily based on recent research that considers the structural behaviour of all horizontal members, without applied fire
protection, acting as a complete entity within the building. This guidance assumes that columns designed to current design procedures
will always be adequate when used within this new design philosophy. For bare steel columns these existing design methods usually
consist of applying some form of passive fire protection.
Presented in this paper is an analytical investigation of the structural behaviour of columns when subjected to various structural
and fire scenarios. The results from this study do not endorse the view that current fire design methods for columns are adequate.
These design methods will require revision if instability of columns during a fire is to be avoided. In most cases this will result
in the need for additional passive fire protection to be applied to the steel columns. 2000 Published by Elsevier Science Ltd.
All rights reserved.

Keywords: Fire; Columns; Stability; Thermal expansion

1. Introduction iour of isolated members. Results from the tests sup-


ported this theory, and together with supplementary
Recent research [14] into the behaviour of steel- computer modelling design guidance is now being
framed buildings during a fire has begun to consider the developed based on whole building performance during
structural response of the building in its entirety instead a fire.
of considering structural members in isolation. In the UK The major aims of fire design, once ignition occurs,
the nucleus of this research [1] is the recently completed is to contain the fire within the compartment of origin
fire tests, conducted on a full-scale eight-storey steel- and to limit structural damage so that overall collapse is
framed building constructed at the Building Research avoided. Before the Cardington fire tests were conducted
Establishment (BRE) Laboratory in Cardington, it was generally agreed, by the Research Organisations
Bedford. [1] involved, that to meet these criteria the bare steel
A total of six compartment fire tests were carried out columns would need to be designed to current practice
[3], two by BRE and four by British Steel. The major [58] (i.e., treated as isolated members). This involved
aim of the tests was to provide quality data to validate applying passive fire protection to the columns. This
and develop computer models, which will enable differ- effectively resulted in only the horizontal members being
ent structural and fire scenarios to be investigated. tested. Since the limit in terms of load-carrying capacity
Before the Cardington tests, it was felt that existing of these members in fire was unknown, it was decided
design guidance on horizontal spanning structural mem- to protect the columns to a higher standard than that
bers was too conservative, since it is based on the behav- given by current design methods, to ensure that the col-
umns did not fail first. This is based on the assumption
that columns designed to current UK practice will per-
* Tel.: 44-1923-664619; fax: 44-1923-664096; e-mail: form adequately in a fire, and therefore do not need to
baileyc@bre.co.uk be tested to their limit in the full-scale fire tests.

0141-0296/00/$ - see front matter 2000 Published by Elsevier Science Ltd. All rights reserved.
PII: S 0 1 4 1 - 0 2 9 6 ( 9 9 ) 0 0 0 2 8 - 0
756 C.G. Bailey / Engineering Structures 22 (2000) 755768

The design guidance, which is currently being with the steel beams and underside of the steel trap-
developed, based on the Cardington test results, is effec- ezoidal deck unprotected. To highlight the behaviour of
tively a hybrid design philosophy. The design of the the columns the results from two of the tests are briefly
beams (which could possibly be unprotected) and slabs presented, one conducted by BRE, the other by British
is based on the behaviour of the structure as a whole, Steel. The locations of these tests are shown in Fig. 1
whereas the columns are based on current design prac- and are situated in the corner bays of the frame. The
tice by treating them as a series of isolated members. following description of the tests concentrates on the
This paper investigates the validity of this approach and behaviour of the columns. A more detailed description
raises questions about its safety in relation to the overall of the overall structural behaviour is presented else-
stability of the structure. where [1,2].

2.1. BRE corner fire test


2. Review of the full-scale fire tests conducted on
the Cardington frame
In the BRE corner fire test, situated between second
The full-scale eight-storey steel-framed test building and third floor levels, the columns were extensively
[9] was designed and constructed to resemble a typical instrumented, which allowed their behaviour during the
modern UK city centre eight-storey office development. test to be investigated. Figs. 2 and 3 show the maximum
On plan (Fig. 1), the building covers an area of 21 m recorded test moments (calculated from the strain
45 m with an overall height of 33 m. There are five gauges) about the minor and major axes at various pos-
equally spaced bays along the length of the building. itions along the length of the columns, between the first
Across the width there are three bays spaced 6 m, 9 m and fourth floors. In the figures the notation (?) rep-
and 6 m. Placed centrally, on the footprint of the build- resents strain gauges that failed during the test. However,
ing, is a 9 m 2.5 m lift core with two 4.5 m 4.5 it was possible in most cases to identify the trend of
m stairwells placed at each end. The structure is the moments from the strain gauges at these locations,
designed as a braced frame with lateral restraint provided which allowed the sign of the moment to be identified
by cross-bracing around the three vertical access shafts. and the full column moment pattern estimated.
The beams are designed as simply supported acting com- From the test results it can be seen that the columns
positely (via shear studs) with the supported floor slab. are subjected to significant moments about both axes
The composite floor slab is 130 mm deep and consists during the fire test. The pattern of the recorded moments
of a steel trapezoidal deck, with lightweight concrete and suggests that the columns are displaced laterally at third
anti-crack mesh. floor level in the minor axis direction and, for perimeter
Six compartment fire tests were conducted on the columns (depending on their orientation), in the major
frame at various locations throughout the building. In all axis direction. This was caused by the thermal expansion
the tests the columns were protected using ceramic fibre, of the connected heated beams and has been proved by

Fig. 1. Location of corner compartment fire tests.


C.G. Bailey / Engineering Structures 22 (2000) 755768 757

Fig. 3. Maximum recorded major axis moments during the BRE cor-
Fig. 2. Maximum recorded minor axis moments during the BRE cor- ner fire test.
ner fire test.

previous analytical work [10] and validated by test


measurements.
One visual phenomenon of the structural behaviour of
the BRE corner test was that no local buckling of the
beams occurred. In all the other fire tests local buckling
occurred in a large number of beams in the proximity
of the beam-to-column connections. It is felt that this
local buckling was caused by the restraint to thermal
expansion of the beams together with the negative
moment caused by the rotational restraint of the connec-
tion [11]. To investigate if local buckling of the beams
reduces the column moments the corner compartment
fire test conducted by British Steel, where extensive
local buckling of the beams occurred, was investigated.

2.2. British Steel corner fire test


Fig. 4. Position of local buckling in the steel beams during the British
Steel corner fire test.
Fig. 4 shows the locations of beam local buckling in
the British Steel corner fire test, which was carried out
between first and second floors. The major axis moments relation to the temperature of the connecting beam, for
of column E/1 were recorded at a position 500 mm column E/1 about the major axis, is shown in Fig. 6.
above the second floor and are shown in Fig. 5. The Also shown in this figure is the horizontal displacement
maximum recorded major axis moment of 343 kNm in for column E/4 (Fig. 1) recorded during the BRE fire
column E/1 is in good agreement with the maximum test. It can be seen that the horizontal displacement is
recorded major axis moment of 316 kNm in column E/4 similar for both tests but the temperatures of the con-
(Fig. 3). The horizontal displacement at floor level, in necting beam are different. Although local buckling in
758 C.G. Bailey / Engineering Structures 22 (2000) 755768

Fig. 5. Recorded major axis moment for column E/1 during the British Steel corner compartment fire test (measured 500 mm above second floor).

Fig. 6. Recorded lateral displacement of column E/1 (British Steel test) and column E4 (BRE test).

the beams should, in part, alleviate the lateral displace- lar beams in the BRE and British Steel tests. However,
ment of the columns, results from all the fire tests indi- both tests have shown that high moments are induced
cate that local buckling does not occur until beam steel into the columns owing to thermal expansion of the con-
temperatures in excess of 500C are reached. From Fig. necting beams. This paper presents the possible conse-
6 it can be seen that the difference in displacements quence of this thermal expansion on the behaviour of the
occurs at the start of the test and continued throughout columns and considers the influence of different fire and
the duration of the test. This difference could be due to structural scenarios.
either one of the following, or a combination of the two
(together with local buckling at higher temperatures):
3. Behaviour of steel columns due to lateral
1. The beam in the BRE test was only heated from one
displacement caused by thermal expansion of the
side and was partially protected by the compartment
connecting beams
wall [2].
2. The restraint from the composite floor was different
The results from the Cardington fire tests have shown
in each test, due to the different timetemperature
that the internal and external columns are subjected to
relationship of the tests, as shown in Fig. 7.
high moments caused by expansion of the connecting
Further analytical work is required to obtain definitive beams during a fire. If these moments were simply
explanations for the different thermal expansion of simi- included within the present member design procedure
C.G. Bailey / Engineering Structures 22 (2000) 755768 759

Fig. 7. Maximum atmosphere temperatures recorded in the BRE and British Steel corner fire tests.

outlined in BS5950 Part 8 [6] or EC3 Part 1.2 [7], the


calculations would show that the columns would fail
during the fire owing to local plasticity. However, in the
case of a braced frame a large amount of redundancy
exists and it should be possible for the induced column
moments to cause high localised stresses, resulting in
plastic hinges at floor level, without causing overall col-
lapse. This assumes that the columns are restrained hori-
zontally at floor level. Owing to its good inherent fire
resistance the composite floor should provide this
restraint during a fire. Although it is assumed that local-
ised plasticity can be accommodated, the influence of
expanding beams on the overall stability of the column
must be checked during a fire.
The simple model shown in Fig. 8 was developed to
investigate the stability of columns, during a fire, which
are subjected to both static axial load and moments
caused by the expansion of the connected steel beams.
The following modelling assumptions apply:
1. The floor slab is ignored, but the heated beams are
restrained axially to provide lateral restraint to the
columns.
2. No static load is applied to the beams.
3. The beams are heated such that the top flange is 80%
of the temperature of the web and lower flange, which
causes the beams to deflect vertically owing to ther-
mal curvature.
4. The column is subjected to a concentric static load,
with the bottom 4185 mm uniformly heated.
5. The column has no axial restraint to thermal expan-
sion (except that provided by the flexural stiffness of
the connecting beams).
6. The column has an imperfection of L/1000 about the
minor axis.
Some of the above assumptions require further expla- Fig. 8. Simple model used in parametric study.
760 C.G. Bailey / Engineering Structures 22 (2000) 755768

nation in relation to the observed structural behaviour


during the full-scale fire tests. By ignoring the floor slab
the lateral displacement of the column due to the thermal
expansion of the beams will be higher. However, test
results and previous modelling [10] have shown that the
overall displacement of the columns is caused by the
floors above and below the fire compartment being dis-
placed in opposite directions. This causes a higher over-
all lateral displacement compared to the lateral displace-
ment at one floor level only. In the absence of modelling
the whole frame (which must include the bracing) it is
assumed that by ignoring the floor slab in the simple
model conservative lateral displacements will be esti-
mated.
By applying no static load, the vertical displacement
of the beams remains very small, with only thermal cur-
vature being modelled. If the vertical displacement of
the beams becomes significantly large it will alleviate
the column lateral displacement. However, it was
decided not to include this behaviour, in the simple Fig. 10. Structural behaviour leading to either beam or column fail-
model, for two reasons. Firstly, it has been shown by ure.
tests [2] that beams parallel to the compartment per-
imeter have nominal vertical displacement, since they
The frame shown in Fig. 8 was analysed with the axial
are directly above a compartment wall. Secondly, in a
restraint at one end of the heated beams fully fixed. The
fire situation it cannot be guaranteed that all beams are
column was subjected to an axial load of 2944 kN. Fire
subjected to the assumed design-imposed loads.
design codes [68] represent the load at the fire limit
Considering the simple model it can be seen that the
state in terms of Load Ratio, Load Level or Degree of
following parameters require investigation:
Utilisation. These terms correspond to the capacity of
1. Beam to column heating rates the member at ambient temperature divided by the load
2. Beam size on the member at the fire limit state. The load of 2944
3. Column size kN on the column corresponds to a Load Ratio of 0.6.
4. Beam-to-column connection rigidity This assumes a column effective length of 0.85 times
5. Axial restraint at one end of the heated beams the system length. To find the worst heating scenario the
6. Span of beams differential heating rate between the column and beams
7. Base rigidity of the heated column was varied. These heating rates will cover the cases
8. Column axial load where the columns are protected with the connecting

Fig. 9. Failure of structure for varying column-to-beam temperature ratios.


C.G. Bailey / Engineering Structures 22 (2000) 755768 761

Fig. 11. Lateral displacement of column about minor axis.

Fig. 12. Predicted minor axis column moments.

Fig. 13. Column minor axis moments at varying column temperatures.


762 C.G. Bailey / Engineering Structures 22 (2000) 755768

Fig. 14. Predicted lateral displacement of column about minor axis.

beams protected, partially protected or unprotected. Fig. is approached the column deflected shape suggests that
9 shows the failure temperatures for the beam and col- instability is occurring. The minor axis moments, for the
umn for varying column-to-beam temperature ratios. It same analysis, are shown in Fig. 12. These indicate that
can be seen that if the column is protected from the fire, the moment at point C (floor level) reverses sign to a
so that its maximum temperature is less than 60% of restraining moment prior to instability. Both the pre-
the temperature of the beam, then failure is by beam dicted displacements and moments strongly indicate that
squashing. This is caused by axial restraint to thermal column instability occurs and not numerical instability
expansion of the beam by the sway stiffness of the col- of the computer model.
umn. If the column reaches higher temperatures then The predicted moments along the length of the column
failure is by column instability. Fig. 10 shows a simpli- are shown in Fig. 13, for varying temperatures. From
fied representation of the type of structural behaviour this figure it can be seen that plastic hinges have formed
that causes either beam or column failure. in the bottom and in the centre of the heated column,
Considering the behaviour of the column, Fig. 9 indi- with a third plastic hinge beginning to form at the top
cates that the worst scenario is when the column reaches of the heated column as the moment reverses direction
a temperature of 509C and the beam reaches a tempera- to a restraining moment. The formation of these hinges
ture of 848C. This failure temperature increases to is caused by column instability.
528C when the beams and column are heated at the Considering the structural behaviour of the column,
same rate. If the column was heated, and the beams the effect of the expanding beams causes the column to
remained at 20C, it was shown that failure of the col- deflect into double curvature with high localised stresses
umn would occur at 541C. This corresponds well with occurring at the top and bottom of the column. This
the BS5950 Part 8 [6] Limiting Temperature (failure should not cause instability, due to the restraint present
temperature) value of 540C. Therefore considering the at floor level. Therefore, instability of the column must
results presented in Fig. 9, the Limiting Temperature of be initiated by the P effect of the applied axial load
the column should be reduced from 541C to 509C if and forced displacement of the column. To investigate
the beams are unprotected, so that they can reach tem- this argument the same previous analysis, where the col-
peratures of 848C or higher. This will ensure stability umn was heated at 70% of the beam, was repeated
of the columns during any fire scenario. If the beams are except that the axial load in the column was assumed to
protected to the same degree as the columns, then the be zero. Compressive failure of the beams was identified
Limiting Temperature should be reduced from 541C when they reached 730C, with the column at 511C.
to 528C. To investigate the behaviour of the column for higher
It is important to investigate the results presented in temperatures the beam was replaced by a 914 419
Fig. 9, in more detail, to ensure that column instability 388UB. The column minor axis displacements are shown
is occurring and failure in modelling terms is not in Fig. 14. Instability of the column did not occur. This
caused by numerical instability. The column displace- can be seen clearly from Fig. 15, which indicates that a
ments about the minor axis, for the analysis where the nominal moment occurs at the centre of the column. This
column was heated at 70% of the beam temperature, are figure also indicates that a plastic hinge forms at the top
shown in Fig. 11. As the failure temperature of 514C and bottom of the heated column, which reduces in
C.G. Bailey / Engineering Structures 22 (2000) 755768 763

Fig. 15. Predicted minor axis column moments.

capacity as the column is heated and thus reduces in umn instability occurred. The analyses indicate that the
strength. beam has an important effect and for a connecting beam
Comparison of these analyses show that instability of of size 914 419 388UB the column Limiting Tem-
the column occurs due to a combination of the axial load perature should be reduced to 430C. However, it should
in the column and its deflected shape caused by the be noted that this beam-to-column size combination is
expansion of the connecting beams. highly unrealistic and the only purpose of these analyses
is to investigate the effect of the beam size. From these
3.1. Effect of beam size results it can be concluded that increasing the size of the
connecting beams has a detrimental effect on the stab-
The previous analyses (where the Load Ratio in the ility of the columns.
column was 0.6) were repeated with the beams increased
to 914 419 388UBs. Fig. 16 shows the failure tem- 3.2. Effect of column size
peratures of the simple structural model for different
beam-to-column temperature ratios. It can be seen that The above analyses were repeated with the column
increasing the beam size increased the beam-to-column size reduced to a 152 152 23UC. This had the
temperature range (i.e. from 0.4 to 1.0) over which col- effect of increasing the slenderness of the column from

Fig. 16. Failure of structure for varying column-to-beam temperature ratios (beam 914 419 388UB; column 305 305 37UC).
764 C.G. Bailey / Engineering Structures 22 (2000) 755768

Fig. 17. Failure of structure for varying column-to-beam temperature ratios (beam 914 419 388UB; column 152 152 237UC).

the previous value of 45.4 to 96.1. The applied axial load beam forcing the column into a deflected shape. This
was 254 kN, which gave a Load Ratio of 0.6 (assuming causes the P effects to become significant and ulti-
an effective length of 0.85 times the system length). For mately leads to column instability.
the worst scenario (Fig. 17) the failure temperature of
the column is 430C, which is the same value predicted 3.3. Effect of beam-to-column connection rigidity
for the above analyses where the column size was 305
305 37UC. When the column was heated and the The original analyses (Fig. 9), where the beams were
beams remained at ambient temperature column insta- 356 171 51UB and the column was 305 305
bility occurred at 590C, significantly higher than the 37UC, were repeated with the beam-to-column connec-
temperature of 541C predicted in the above analyses. tions assumed as fully rigid. The predicted failure tem-
This phenomenon has been shown previously by various peratures are shown in Fig. 18 and comparison with Fig.
researchers [12,13] and is due to the beneficial end 9 indicates that the results are very similar. This implies
restraint for slender columns. that the rotational stiffness and moment capacity of the
The effect of column slenderness does not seem to be beam-to-column connection has nominal effect on the
significant for the worst fire scenario, indicating that the behaviour of the column. This can be attributed to the
dominant behaviour is caused by the expansion of the following:

Fig. 18. Failure of structure for varying column-to-beam temperature ratios (rigid beam-to-column connection).
C.G. Bailey / Engineering Structures 22 (2000) 755768 765

1. The beams are heated, and at temperatures of 800C


they have nominal stiffness and strength. Therefore
they cannot provide significant restraining moments
when instability of the column occurs.
2. The amount of rotation stiffness required for a heated
column to tend towards the behaviour of a fully fixed-
ended strut is significantly less than the rotational
restraint provided by the continuation of the column
above the fire, which remains cold. This is clearly
indicated from the results of the analyses shown in
Fig. 19.

3.4. Effect of horizontal restraint to the heated beams

In all the previous analyses the beams were restrained


horizontally at the opposite end to the heated column.
To investigate the effect of varying the horizontal
restraint the original analyses (Fig. 9) were repeated with
a horizontal restraint of 33841 N mm for the 6.0 m span
beam and 22072 N mm for the 9.0 m span beam. This
represents the restraint from the unbraced structure
shown in Fig. 20.
Comparison between Figs. 9 and 21 shows that there
is nominal difference between the failure temperatures
of the column when infinite or finite horizontal restraint
is provided to the heated beams. However, only one
example is presented and further studies are required to
investigate a wider range of restraining stiffness.

3.5. Effect of beam span


Fig. 20. Structural model to represent restraint to heated beams.
The original analyses (Fig. 9) were repeated with the
9.0 m span beam increased to 15.0 m. Fig. 22 shows
that by increasing the span of the beam from 9.0 m to 3.6. Effect of rotational restraint to the heated column
15.0 m the column Limiting Temperature should be
reduced to 440C to maintain stability. This represents The original analyses (Fig. 9) were repeated with a
a reduction of 100C, which will significantly increase pinned connection assumed for the base of the heated
the amount of fire protection required for the column. column. This effectively models a lower storey column

Fig. 19. Effect of rotational restraint on column failure temperatures.


766 C.G. Bailey / Engineering Structures 22 (2000) 755768

Fig. 21. Failure of structure with varying column-to-beam temperature ratios (spring stiffness used to represent horizontal restraint to heated
beams).

Fig. 22. Failure of structure for varying column-to-beam temperature ratios (beam spans 15.0 m and 6.0 m).

with a pinned base. The applied static load to the column 3.7. Effect of column load ratio
was reduced to 2728 kN, assuming an effective length
equal to the system length. Fig. 23 shows that the worst The original analyses (Fig. 9) were repeated, with the
scenario is when the column is heated at 40% of the Load Ratio of the column varied between 0.7 and 0.2.
temperature of the beam. To ensure column stability the Fig. 24 shows that the worst case is when the column
Limiting Temperature of the column should be reduced is subjected to a Load Ratio of 0.7 (as expected since it
to 330C. This represents a reduction of 196C. How- represents the highest axial load in the column). With
ever, it should be noted that a nominally pinned base this level of applied static load the column Limiting
will provide some rotational restraint and it may be poss- Temperature should be reduced from 510C to 425C.
ible to increase the failure temperature of the column. As the Load Ratio becomes smaller the reduction in
Further studies are required to investigate this possi- Limiting Temperature also reduces. For the structural
bility. layout used in this analyses, the required reduction in
C.G. Bailey / Engineering Structures 22 (2000) 755768 767

Fig. 23. Failure of structure for varying column-to-beam temperature ratios (column base pinned).

Fig. 24. Failure of structure for varying column-to-beam temperature ratios and varying Load Ratios.

Limiting Temperature for a Load Ratio of 0.4 or less is that these column moments were caused by the thermal
lower than 10C and can effectively be ignored. expansion of the connecting beams.
To carry out a detailed investigation into the conse-
quence of these column moments, on the overall stability
4. Conclusions of the column, a simple structural model was developed
(Fig. 8). This model represented a continuous column in
Results from the Cardington full-scale fire tests indi- a multi-storey frame, with beams framing into the minor
cated that high moments occurred in the columns during and major axes of the column from one side only. It was
the test. At present these moments are not considered in shown that the column was forced into double curvature
existing design methods. Investigation of the test results, with high localised stresses occurring at the top and bot-
supplemented with computer models [10], concluded tom of the heated column. It was assumed that the col-
768 C.G. Bailey / Engineering Structures 22 (2000) 755768

umn was restrained laterally at floor level. In the simple Acknowledgements


model this was achieved by restraining the heated
beams. In the Cardington frame the composite floor, due The author is grateful for the technical and general
to its good inherent fire resistance, will provide the support from Dr David Moore (Building Research
restraint. Establishment) and Dr Ian Burgess (University of
The analyses presented showed that instability could Sheffield).
occur in the column, even though it was forced into dou-
ble curvature and restrained at floor level. This instability References
was caused by the P effect in the column, which
[1] The behaviour of multi-storey steel framed buildings in fire: a
was enhanced due to the enforced deflected shape of the European Collaborative Research Programme. British Steel
column caused by the expansion of the connecting (submitted for publication).
beams. [2] Bailey CG, Lennon T, Moore DB. The behaviour of full-scale
The analyses showed that column instability was sig- steel-framed buildings subjected to compartment fires. The Struc-
tural Engineer 1999;77(8):1521.
nificantly affected by: [3] Martin DM, Moore DB. Introduction and background to the
research programme and major fire tests at BRE Cardington. In:
1. Beam to column heating rates National Steel Construction Conference, London, May 1997.
2. Beam cross-section size [4] OConnor MA, Martin DM. Behaviour of multi-storey steel
framed building subjected to fire attack. Paper no. 169: Proceed-
3. Span of the beams ings of the Second World Conference on steel in Construction.
4. End rigidity of the heated column Journal of Constructional Steel Research 1998;46(1,3):31525.
5. Column axial load [5] Association of Specialist Fire Protection. Fire protection for
structural steel in buildings, 2nd ed., revised. Ascot (UK): Steel
In addition the analyses showed that the following Construction Institute, 1992.
[6] British Standards Institution. BS5950: Structural use of steelwork
parameters had nominal effect on the behaviour of the in building. Part 8: Code of practice for fire resistant design. Lon-
column: don: BSI, 1990.
[7] European Committee for Standardisation. Eurocode 3: Design of
6. Column cross-section size steel structures. Part 1.2: General rules, structural fire design.
ENV 1993-1-2. ECS, Brussels, 1995.
7. Beam-to-column connection rigidity [8] European Committee for Standardisation. Eurocode 4: Design of
8. Horizontal restraint to the heated beams (provided composite steel and concrete structures. Part 1.2: General rules,
realistic values are chosen) structural fire design. ENV 1994-1-2. ECS, Brussels, 1994.
[9] Armer GST, Moore DB. Full-scale testing on complete multisto-
At present, only a limited parametric study has been rey structures. The Structural Engineer 1994;72(2):301.
[10] Bailey CG, Moore DB, Lennon T. The structural behaviour of
produced. The results from this study have shown poss- steel columns during a compartment fire in a multi-storey braced
ible scenarios where column instability could occur. The steel frame. The Structural Engineer (submitted for publication).
analyses indicate that in certain situations the column [11] Bailey CG. Enhancement of fire resistance of beams by beam-
Limiting Temperature (failure temperature) used in cur- to-column connections. New Steel Construction 1998;6(2):44.
[12] Wang YC, Lennon T, Moore DB. The behaviour of steel frames
rent design methods should be reduced. The required subject to fire. J Construct Steel Research 1995;35:291322.
reduction will range from approximately 35C to 195C [13] Bailey CG. The behaviour of steel column in fire. Document
depending on the parameters explained in (1)(5) above. RT524. Steel Construction Institute, Ascot, March 1996.

Vous aimerez peut-être aussi