Vous êtes sur la page 1sur 9

Electric Power Systems Research 79 (2009) 8088

Contents lists available at ScienceDirect

Electric Power Systems Research


journal homepage: www.elsevier.com/locate/epsr

Active power lters for harmonic cancellation in conventional and advanced


aircraft electric power systems
A. Eid a , M. Abdel-Salam b, , H. El-Kishky c , T. El-Mohandes a
a
South Valley University, Egypt
b
Electrical Engineering Department, Assiut University, Al-Gamaa street, Assiut 71518, Egypt
c
University of Texas at Tyler, USA

a r t i c l e i n f o a b s t r a c t

Article history: Conventional and advanced civil aircraft electric power systems are simulated and controlled to be within
Received 20 September 2007 standards regarding the voltage magnitude and frequency everywhere in the system at different loading
Received in revised form 7 February 2008 scenarios. Harmonics in conventional and advanced aircraft power systems are calculated and reduced
Accepted 21 May 2008
using a well-designed active power lter. The control circuit of the lter is based on the perfect harmonic
Available online 7 July 2008
cancellation method. The designed lter results in bringing the harmonics in both aircraft systems down
to be within the standard limits of IEEE-519 and MIL-STD-704E.
Keywords: 2008 Elsevier B.V. All rights reserved.
Conventional and advanced aircrafts
Active power lter
THD

1. Introduction three-phase distribution lines and AC and DC loads (Fig. 1). The
equivalent electrical loads were represented by three-phase loads
High-current harmonics can cause severe voltage distortion, (A, B and C) and single-phase load (D) as lumped resistive and
unbalance in the aircraft electric power system and can lead to inductive components (Fig. 1). The DC loads (E and F) were repre-
interference with the aircraft communication system as well as sented by resistive load. The DC voltage was obtained by connecting
sensitive control and navigation equipment. Compensation of the two TRUs in series to obtain 12-pulse rectications to minimize the
higher current harmonics generated in the aircraft electric power harmonic contents in the output DC voltage as well as in the input
system, by different nonlinear loads and power electronic convert- AC current [3].
ers, is of great interest. Aircraft electrical power system (EPS) often The frequency was regulated by regulating the DC motor speed
consists of two or more engine-driven-generators to supply the AC by using proportional-integral (PI) controller. Sensing the motor
loads throughout the aircraft. All aircraft systems needs AC and DC shaft speed and comparing it to the reference speed results in a
power altogether. The DC power comes from rectication of the AC speed error which is processed to control the full-bridge chopper
power using transformer rectier units (TRUs). These units are nor- which affects the input DC voltage of the DC motor. The magnitude
mally 12-pulse conguration [1]. Due to cyclic operation of these of the phase voltage of the generator, was controlled by compar-
units, they are considered as harmonic sources in the aircraft EPS. ing it to the reference voltage (115 VAC) using another PI controller
These units can increase the voltage distortion and the harmonic which controls the eld current of the synchronous generator. The
contents into the AC side of the aircraft EPS. generator output voltage magnitude and frequency complied with
the standards of MIL-STD-704F [4] and IEEE Std. 519 [5], which spec-
1.1. Conventional aircraft EPS ify the voltage and frequency allowable limits during transient and
steady-state conditions. Meeting the standard limits for 28 VDC,
A simplied conventional aircraft electric system was consid- 115 VAC voltages and frequency were explored in detail in [2]. This
ered in [2] consisting of one motor (representing the engine) simplied system does not include the external power (used for
driven generator for generating a three-phase source with constant charging batteries at airport) and battery charge/discharge system.
frequency and constant voltage and radial systems consisting of
1.2. Advanced aircraft EPS

Corresponding author. Tel.: +20 88 2334688; fax: +20 88 2332553. The EPS consists of two independent channels, according to
E-mail address: mazen2000as@yahoo.com (M. Abdel-Salam). the number of starter/generators in the aircraft. An auxiliary/

0378-7796/$ see front matter 2008 Elsevier B.V. All rights reserved.
doi:10.1016/j.epsr.2008.05.005
A. Eid et al. / Electric Power Systems Research 79 (2009) 8088 81

Table 1
Loading scenarios

Case No. AC loads DC loads

1 Load E
2 Loads E, F
3 Load A Load E
4 Loads A, B Load E
5 Load C Load F
6 Loads C, D Load F
7 All Loads E, F
Fig. 1. Simulated structure for conventional aircraft electric power system.

emergency power unit contains an additional auxiliary starter/ The appropriate phase currents, phase resistance and inductance
generator. Either three-phase synchronous machines or switched- were then calculated based on the kVA rating and the xed PF
reluctance machines may be used as starter/generators in a for each phase. The different loads rating and parameters for the
more-electric aircraft [68]. The power control units are used to simulated B767 aircraft were listed in Ref. [2].
transform the wild frequency AC power produced by the syn-
chronous generators into 270 V DC power. The following reasons 1.3. Harmonics level mitigation in aircraft EPS
motivated the choice of the 270 V DC distribution bus [9]: It is a
good voltage source for inverters that power motor loads of the air- The compensation of harmonic and reactive currents becomes
craft, it is easy to provide uninterruptible power on the bus by using increasingly important owing to the wide use of power electronic
a battery back-up and regenerative power from electrical actuators equipments in aircraft EPS. Traditionally, passive LC tuned shunt
that can be easily returned to the bus. lters have been used [1015] to eliminate line current harmonics
The advanced aircraft EPS is more sophisticated than the con- due to nonlinear loads and to increase the power factor. How-
ventional one. To simulate the advanced aircraft electrical system, ever, in practical applications these passive lters showed many
the battery and the external power system are neglected as the case drawbacks [16], such as aging and tuning problems, series and par-
for the conventional system. The advanced aircraft system used for allel resonances, bulk passive components and xed compensation
simulation is shown in Fig. 2. The motor-generator set is the same characteristics.
as the conventional case to provide the 115 VAC at 400 Hz generator The active power lter (APF) is considered a feasible solution to
bus under the same AC and DC loads. In advanced aircraft EPS, the the problems created by nonlinear loads. The APF is used to elim-
270 VDC voltage is usually obtained by using 12-pulse converter to inate the undesired harmonics and improve power factor (PF) by
reduce the characteristic harmonics, the same as in conventional injecting equal but opposite compensation currents. Therefore, an
EPS. In this case, two 6-pulse thyristor bridges are connected in APF looks like a controlled current source, connected in parallel
series to obtain the 12-pulse rectication, similar to the conven- with the nonlinear load to generate the required compensation cur-
tional aircraft EPS. A PI controller is used to drive the 12-pulse rents. Thus, the supply (mains) only needs to feed the fundamental
converter to regulate the DC voltage at 270 V. currents. The APF can also keep the power system balanced even
The peak-to-peak ripple voltage is 3.7 V and the ripple factor is with unbalanced and nonlinear loads as the case in the aircraft
0.28% at the 270 VDC bus, which are lower than the standard val- power system. In this case, the APF supplies harmonic, reactive,
ues of 6 V and 1.5% [4], respectively. The DC loads are connected fundamental negative sequence and zero sequence current com-
to the 270 VDC bus through DC/DC forward chopper to provide ponents.
the required 28 VDC feeding the DC loads. For supplying the same
AC loads as in conventional case, two 6-pulse PWM inverters are
1.4. Paper objectives
connected in parallel to provide a smoothed 12-pulse voltage wave-
form. For this system, the aircraft standard limits for the 270 VDC
In this paper, the performance of the conventional and advanced
bus voltage, 115 VAC voltage, the AC system frequency and 28 VDC
aircraft power systems are investigated under conditions of
ripple voltage are met. The 28 VDC bus has peak-to-peak ripple
constant-voltage, constant-frequency source and lumped DC and
amplitude of 0.79 V and a ripple factor of 0.46% compared to the
AC loads. An efcient controlled APF is shunt connected to mitigate
standards of 1.5 V and 3.5% [4], respectively. Meeting the standard
harmonics, improving PF and removing imbalance in conventional
limits for 270, 28, and 115 VAC voltages and generator frequency
and advanced aircraft EPSs.
were explored in detail in Ref. [2].
The equivalent EPS for Boeing 767 aircraft either conventional or
advanced was estimated from that of the C130E aircraft [2,3]. The 2. Simulation of conventional aircraft EPS
loading kVA of the B767 aircraft is 2.25 times that of C130E aircraft.
2.1. Harmonics levels

Using of a 12-pulse converter to obtain the DC voltage generates


dominant harmonics of the order 11th, 13th, 23rd and 25th. A load-
ing scenario (Table 1) is adopted from various combinations of the
AC and DC loads to study the harmonic contents in each case. The
total harmonic distortion of current and voltage, THDi and THDv
for some cases exceeded the standard harmonic levels which is 5%
[4,17]. Due to load unbalance, neutral generator current ows. This
is in addition to drawbacks resulting from loads of low power factor
for some cases in Table 1. An APF is designed to: (i) compensate the
reactive power components, (ii) make the PF near to unity and (iii)
Fig. 2. Simulated structure for advanced aircraft electric power system. balance the generator phases currents.
82 A. Eid et al. / Electric Power Systems Research 79 (2009) 8088

Fig. 5. Principle of hysteresis band current controller.

Table 2
APF parameters
Fig. 3. Three-phase active power lter conguration. Generator line voltage 200 Vrms
Generator frequency 400 Hz
Filter inductance, Lf 0.11 mH
The APF in general consists of a power circuit, smoothing Filter inductor resistance 0.01 
Filter capacitance 50 F
inductors Lf , smoothing high-frequency lter capacitors, Chf , a DC Filter DC capacitor, Cdc 1.5 mF
capacitor, Cdc (Fig. 3) and a control circuit (Fig. 4). The power cir- DC reference voltage, Vdcr 400 V
cuit for a three phase six-pulse inverter is shown in Fig. 3. The DC
capacitor located in the DC bus of the voltage-source inverter serves
as an energy storage element. For a lossless APF at steady state,
the real power supplied from the generator side equals to the real
power of the load. The lter capacitance is used to mitigate the
high-frequency ripple components and thus reducing the switch-
ing stress on the APF switches. More details on the EPS models can
be found in Appendices AC and Ref. [2].

2.2. Control method

Although the instantaneous reactive power theory (pq the-


ory) is widely used in APF control circuitry to calculate the desired
compensation current [1822], the pq theory is very sensitive
to distortion and imbalance that may occur in the voltage at
Fig. 6. APF effects on THDi at PCC.

the point of common coupling (PCC) [23]. The unity power fac-
tor control method [24,25] does not work well in presence of
zero sequence voltage components [23]. The id iq control method
[26,27] is also very sensitive to distortion and imbalance as the
pq control strategy. In order to seek compliance with harmonics
standards, imbalance elimination and reactive power compensa-
tion, the perfect harmonic cancellation (PHC) [23,24] is the only
control strategy which is capable of correct action under any con-
ditions. This is achieved through two-stage procedure. In the rst

Fig. 4. APF control circuit conguration using PHC method. Fig. 7. APF effects on THDv at PCC.
A. Eid et al. / Electric Power Systems Research 79 (2009) 8088 83

Fig. 8. Case No. 2: load current (iLa ), source voltage (Vsa ), source current (isa ) and lter current (ifa ) for phase a.

stage, the reference lter currents (ifar , ifbr and ifcr ) are obtained. In total active power fed by the source (generator) is the sum of the
the second stage, a PWM hysteresis band current control is used inverter switching loss, psw , and the active power needed by the
to generate the required gat signals (s1 s6 ) for the switches of the load, pL .
inverter. To extract the average (mean) power, a low pass lter (LPF) is
needed. The positive sequence of the voltage at PCC is obtained
2.2.1. The rst control stage from a phase-locked loop (PLL) circuit. The average load power is
The PHC control method is adopted here to generate the required divided by the summation of the squared of the voltage positive
compensation currents for the shunt active power lter. The gen- sequence components to get parameter K. Once, the parameter K is
erator current will therefore be in phase with the fundamental obtained, the source reference currents are calculated by multiply-
positive sequence voltage component at PCC [24]. The complete ing it by the positive sequence components of the voltages, thus, the
control circuit is shown in Fig. 4 and the detailed equations are reference source current is in phase with the voltage. Subtracting
listed in Appendix A. The capacitor voltage, Vdc , is kept constant the load current from the reference source current, the reference
through controlling the switching power loss in the inverter circuit APF (compensation) current, ifr , is obtained, which is input to the
using PI controller which regulates the DC capacitor voltage. The hysteresis PWM current controller.

Fig. 9. Case No. 4: load current (iLa ), source voltage (Vsa ), source current (isa ) and lter current (ifa ) for phase a.
84 A. Eid et al. / Electric Power Systems Research 79 (2009) 8088

Fig. 10. Case No. 7: three phase load currents, source currents and lter currents.

Fig. 13. C-bank effect on THDi at AC load terminals.


Fig. 11. APF effect on THDi at generator terminals.

If ifa < (ifar hb) upper switch is off and lower switch is on for leg
a (switching function of phase a, SA = 1).
2.2.2. The second control stage
If ifa > (ifar + hb) upper switch is on and lower switch is off for leg
The hysteresis band PWM current control [28] is a method of
a (SA = 0).
controlling the inverter so that its output current follows the ref-
erence current waveform. This method controls the switches in an
The switching function SB and SC for phase b and phase c are
inverter asynchronously to ramp the actual current up and down
determined similarly, using the corresponding reference and actual
to follow the reference current when the actual current exceed the
currents and hysteresis band hb.
upper or lower hysteresis limit, the associated switching pattern of
the switch will force the current to get back to the hysteresis band
2.3. Mitigation of harmonic levels
limit. Therefore, the current ramp can be altered by the width of the
hysteresis band (hb) and the switching pattern of the APF devices
The APF with parameters listed in Table 2 is connected in shunt
is formulated as follows [29,30], see Fig. 5:
at PCC as shown in Fig. 3 and controlled using PHC method to
mitigate harmonics, remove imbalance and improve the PF of the

Fig. 12. APF effect on THDv at generator terminals. Fig. 14. C-bank effect on THDv at AC load terminals.
A. Eid et al. / Electric Power Systems Research 79 (2009) 8088 85

Fig. 15. Case No. 4: load current (iLa ), source voltage (Vsa ), source current (isa ), lter current (ifa ), AC load current (IaL ) and AC load voltage (VaL ) for phase a.

generator for the loading scenarios of Table 1. The THDi values for With the APF, Fig. 9 shows the simulation of the loading case
all cases at PCC (see Fig. 3) are calculated and shown in Fig. 6. The No. 4, where DC and AC loads are included. Thus the load cur-
THDv values at the same conditions are shown in Fig. 7. It is clear rent (iLa ) contains reactive and harmonic components which will
that the THD values for both current and voltage at PCC with APF be inversely injected by the APF. Although the load current iLa is
meet the IEEE standards for all loading cases. It is worth to mention a sinusoidally distorted waveform, the source voltage and current
that the maximum THDi and THDv are 2.3% and 2.6% while they are smooth sinusoidal waveforms.
are 3.51% and 3.72%, respectively, in case of using passive harmonic Fig. 10 shows the effectiveness of the designed APF in harmonic
lter [2]. mitigation and improving the PF and removing the imbalance of
With the APF, Fig. 8 shows the simulation of the loading case the generator currents for the loading case No. 7. The gure shows
No. 2 of Table 1, where the DC loads are only applied. From the the three-phase load currents (iLa , iLb and iLc ) and the three-phase
gure, the source voltage Vsa and source current isa for phase a are source currents (isa , isb and isc ) which are harmonic free, bal-
sinusoidal, nearly in phase and with THD less than standard limits anced and in-phase with their respective voltages. The injected
[4,5,17]. The lter current (ifa ) is the harmonic component of the (compensated) APF currents (ifa , ifb and ifc ) are also shown in
load current (iLa ) which results from a 12-pulse rectication bridge. Fig. 10.

Fig. 16. Case No. 6: load current (iLa ), source voltage (Vsa ), source current (isa ), lter current (ifa ), AC load current (IaL ) and AC load voltage (VaL ) for phase a.
86 A. Eid et al. / Electric Power Systems Research 79 (2009) 8088

Fig. 17. Case No. 7: three phase load currents, source currents and lter currents.

3. Simulation of advanced aircraft electric power system shown in Fig. 2, with the same parameters listed in Table 2 to
mitigate harmonics and improve the PF at the generator termi-
3.1. Harmonic levels and mitigation nals.
The THDi values at different loading scenarios with and with-
The presence of both AC/DC and DC/AC converters in the out APF at the generator terminals are shown in Fig. 11 and the
advanced aircraft electrical power system as shown in Fig. 2 corresponding THDv values are shown in Fig. 12. At AC load ter-
produces harmonics at AC load bus and at the generator ter- minals the THDi and THDv with and without C-bank are shown
minals as well. To reduce harmonics at the AC load terminal in Figs. 13 and 14, respectively. From Figs. 11 and 12 with the APF
bus, a capacitor bank (C-bank) is shunt with the load. This C- the THD for both current (THDi) and voltage (THDv) are within the
bank (1.5 mF per phase) at AC load terminal works well for standard limits. From Fig. 13, the THDi is within the standard limits
the voltage and current harmonics at the AC load side. It is with and without C-bank; however the C-bank reduces the THDi
found that harmonics at the generator terminals still exceeding values. For the voltage at the AC load, the THDv is reduced in case
the standards [17] because of the DC/DC and AC/DC conver- of adding a C-bank to nearly a xed value (xed compensation)
sions. An APF is shunt connected at the generator terminals as (Fig. 14).

Fig. 18. Case No. 8: load current (iLa ), source voltage (Vsa ), source current (isa ), lter current (ifa ), AC load current (IaL ) and AC load voltage (VaL ) for phase a.
A. Eid et al. / Electric Power Systems Research 79 (2009) 8088 87

It is worthy to mention that the maximum THDi and THDv in The reference source current is given as
Figs. 1114 are 2.8% and 2.32% against 3.68% and 3.47%, respectively,    
isar u+
in case of using passive harmonic lter [2]. This ensures that the APF a1
isbr =K u+
is more efcient than the passive harmonic lter for conventional b1
iscr u+
and advanced aircraft EPS cases. c1
Figs. 1518 show the waveforms for loading cases Nos. 4, 6, 7 The reference current of the APF is given as
and 8. Case No. 8 is added in advanced aircraft EPS to represent the
case of applying the AC loads only. IaL and VaL represent the AC load ifr = iL isr
current and voltage for phase a. The gures show the effectiveness
of the designed APF in advanced aircraft EPS. It should be noted
Appendix B. DC motor and synchronous generator
that the PF at the generator terminals in near to unity.
mathematical models

4. Conclusions Dynamic equations of DC motor model [31]:

Due to nonlinear loads in aircraft, harmonic levels exceed the dia


vt = Ea + ia Ra + La
standard limits which is not suitable for many electronic and sen- dt
sitive circuits in aircraft, thus an efcient APF is aimed at bringing
the harmonics to safe values.
The perfect harmonic cancellation method is suitable to control dif
vf = if Rf + Lf
the APF in aircraft to mitigate the harmonics of the electric sys- dt
tem.
The APF with its control circuit mitigates the harmonics in con-
ventional and advanced aircraft electric power systems to much Ea = km
lower than the IEEE-519 and MIL-STD-704E standards.
Although in advanced aircraft electric power system there is a
DC link separating the AC generation and the AC loads, only one Tem = kia
APF is sufcient at the generator terminals with a small capacitor
bank at the AC load terminals.
In general, the THD values for both current and voltage in dm
J = Tem TL
advanced aircraft electric power system in presence of APF are dt
lower than those for conventional aircraft system.
Active power lters are more efcient and exible than passive where vt , vf , ia and if are the armature and eld winding voltage
harmonic lters in aircraft power systems. and current, respectively. Ea is the back emf, m is the mechanical
speed in rad/s, Tm is the internal developed torque, and TL is the
load torque. The back emf and the internal torque (in steady state)
Appendix A. Perfect harmonic cancellation (PHC) control can be expressed as
method
Ea = Laf if m
If the set of voltages at PCC are ua , ub and uc and the loading
currents are iLa , iLb and iLc , the instantaneous active power of the
load is given by [19,20]: Tem = Laf if ia

pL = ua iLa + ub iLb + uc iLc


where Laf is the mutual inductance between the armature and the
eld windings. It can be calculated based on the rated operating
This power has mean and oscillating values, i.e.
conditions as
pL = p L + p L
(Vt Ia Ra )
Laf =
If m
The reference source current is given by [23]:

isr = Ku+ Synchronous generator model [31]:


1
Stator equations:
di di di
where u+1
is the PCC voltage space vector with a single fundamental vd = Rs id q (Lls + Lmd ) d + Lmd fd + Lmd kd
positive sequence component. dt dt dt
diq di
The power delivered by the source will be: vq = Rs iq + d (Lls + Lmq ) + Lmq fd
dt dt
where
ps = uisr = Ku+2
1 d = (Lls + Lmd )id + Lmd (ifd + ikd )
q = (Lls + Lmq )iq + Lmq ikq
The constant K is determined from the condition that the gen-
Field equation:
erator power equals the dc component of the instantaneous active di di di
power demanded by the load as vfd = Rfd ifd Lmd d + (Llfd + Lmd ) fd + Lmd kd
dt dt dt
Damper winding equations:
p L di di di
K= 0 = Rkd ikd Lmd d + Lmd fd + (Llkd + Lmd ) kd +
u+2
a1
+ u+2
b1
+ u+2
c1 dt dt dt
diq dikq
0 = Rkq ikq Lmq + (Llkq + Lmq )
where p L is extracted from pL using a low-pass lter. dt dt
88 A. Eid et al. / Electric Power Systems Research 79 (2009) 8088

The parameters and variables (reected to the stator) in the [5] IEEE Std. 128, IEEE guide for aircraft electric systems, 1976.
above equations have the following meanings: is the rotor speed, [6] M.L. Maldonado, N.M. Shah, K.J. Cleek, P.S. Walia, G. Korba, Power Management
and Distribution System for a More Electric Aircraft (MADMEL)-Program Sta-
vd , id and vq , iq are the armature d- and q-axis terminal voltages and tus, in: Proceedings of the 31st Intersociety Energy Conversion Engineering
currents, respectively. vfd and ifd are the eld winding terminal volt- Conference, 1996, pp. 148153.
age and current. ikd and ikq are the d- and q-axis damper winding [7] A. Emadi, M. Ehsani, Aircraft power systems: technology, state of the art, and
future trends, IEEE Aerospace and Electronic Systems Magazine (2000).
currents. d and q are the total armature ux in d- and q-axis. Rs [8] I. Moir, A. Seabridge, Aircraft Systems: Mechanical, Electrical, and Avionics;
and Lls are the armature phase resistance and leakage inductance. Subsystem Integration, American Institute of Aeronautics and Astronautics Inc.,
Lmd and Lmq are the d- and q-axis coupling inductance. Rfd and Llfd Reston, Virginia, 2001.
[9] J.A. Weimer, Power management and distribution for the more electric air-
are the eld winding resistance and leakage inductance. Rkd , Rkq , craft, in: Proceedings of the 30th Intersociety Energy Conversion Engineering
Llkd and Llkq are the d- and q-axis damper winding resistances and Conference, 1995, pp. 273277.
inductances, respectively. [10] H.L. Ginn III, L.S. Czarnecki, An optimization based method for selection of res-
onant harmonic lter branch parameters, IEEE Trans. Power Delivery 21 (3)
(2006).
Appendix C. System parameters and constants [11] B. Singh, G. Bhuvaneswari, V. Garg, Harmonic mitigation using 12-pulse ACDC
converter in vector-controlled induction motor drives, IEEE Trans. Power Deliv-
ery 21 (3) (2006).
Denition Value
[12] L.S. Czarnecki, H.L. Ginn III, The effect of the design method on efciency of
Synchronous generator parameters resonant harmonic lters, IEEE Trans. Power Delivery 20 (1) (2005).
Stator winding resistance 0.05  [13] R.L. Almonte, A.W. Ashley, Harmonics at the utility industrial interface: a real
world example, IEEE Trans. Ind. Appl. 31 (November/December (6)) (1995)
Leakage inductance 5 H
14191426.
d-Axis magnetizing inductance 0.1 mH
[14] S.M. Peeran, C.W.P. Cascadden, Application, design, and specication of har-
q-Axis magnetizing inductance 0.1 mH
monic lters for variable frequency drives, IEEE Trans. Ind. Appl. 31 (July/August
Field winding resistance 0.05  (4)) (1995) 841847.
Field winding leakage inductance 0.1 mH [15] J.A. Bonner, et al., Selecting ratings for capacitors and reactors in applications
Rotor damping cage d-axis resistance 0.1  involving multiple single-tuned lters, IEEE Trans. Power Delivery 10 (January
Rotor damping cage d-axis leakage inductance 50 H (1)) (1995) 547555.
Rotor damping cage q-axis resistance 0.01  [16] D. Gao, Q. Lu, X. Sun, Design and performance of an active power lter for
Rotor damping cage q-axis leakage inductance 50 H unbalanced loads, in: International Conference on Power System Technology
Number of poles 6 Proceeding (PowerCon 2002), vol. 4, 2002, pp. 24962500.
Moment of inertia of the machine 0.1 kg m2 [17] IEEE Std. 519, IEEE Recommended practices and requirements for harmonic
DC motor parameters control in electrical power system, 1992.
Armature winding resistance 0.09  [18] H. Akagi, Y. Kanazawa, A. Nabae, Instantaneous reactive power compensators
Armature winding inductance 30 H comprising switching devices without energy storage components, IEEE Trans.
Ind. Appl. IA-20 (May/June (3)) (1984) 625630.
Field winding resistance 75 
[19] F.-Z. Peng, G.W. Ott, D.J. Adams, Harmonic and reactive power compensation
Field winding inductance 20 H
based on the generalized instantaneous reactive power theory for three-
Rated speed 8000 rpm phase four-wire systems, IEEE Trans. Power Electron 13 (November (6)) (1998)
Rated terminal voltage 600 V 11741181.
Rated armature current 50 A [20] H. Akagi, S. Ogasawara, H. Kim, The theory of instantaneous power in three-
Rated eld current 7.95 A phase four-wire systems: a comprehensive approach, in: Proc. IEEE IAS Annu.
Meeting, 1999, pp. 431439.
Cable parameters
[21] J. Afonso, C. Couto, J. Martins, Active lters with control based on the pq theory,
Resistance per meter 3.71 103 /m IEEE Ind. Electron. Soc. Newslett. (September 2000) 511.
Inductance per meter 3.28 109 H/m [22] M. Aredes, E.H. Watanabe, New control algorithms for series and shunt three-
Capacitance per meter 3.28 1012 F/m phase four-wire active power lters, IEEE Trans. Power Delivery 11 (July (3))
(1995) 16491656.
PI controller parameters
[23] M.I. Montero, R. Cadaval, F.B. Gonzalez, Comparison of control strategies for
Proportional gain for voltage regulator 0.01
shunt active power lters in three-phase four-wire systems, IEEE Trans. Power
Integral gain for voltage regulator 45 Electron. 22 (January (1)) (2007) 229236.
Proportional gain for frequency regulator 0.02 [24] M.-R. Raei, H.A. Toliyat, R. Ghazi, T. Gopalarathanam, An optimal and ex-
Integral gain for frequency regulator 71 ible control strategy for active ltering and power factor correction under
Proportional gain for 270 VDC bus 1/200 nonsinusoidal line voltages, IEEE Trans. Power Delivery 16 (April (2)) (2001)
Integral gain for 270 VDC bus 500 297305.
[25] A. Cavallani, G.C. Montarani, Compensation strategies for shunt-active lter
28 VDC bus smoothing lter parameters control, IEEE Trans. Power Electron. 9 (November (6)) (1994) 587593.
Inductance 0.1 mH [26] A. Nabae, T. Tanaka, A new denition of instantaneous activereactive current
Capacitance 1.1 mF and power based on instantaneous space vectors on polar coordinates in three
phase circuits, IEEE Trans. Power Delivery 11 (July (3)) (1996) 12381243.
[27] V. Soares, P. Verdelho, G.D. Marques, An instantaneous active and reactive cur-
References rent component method for active lters, IEEE Trans. Power Electron. 15 (July
(4)) (2000) 660669.
[1] G. Gong, M. Heldwein, U. Drofenik, J. Minibock, K. Mino, J. Kolar, Compara- [28] G.W. Chang, C.-M. Yeh, W.-C. Chen, Meeting IEEE-519 current harmonics and
tive evaluation of three-phase high-power-factor AC-DC converter concepts for power factor constraints with a three-phase three-wire active power lter
application in future more electric aircraft, IEEE Trans. Ind. Electron. 52 (June under distorted source voltages, IEEE Trans. Power Delivery 21 (July (3)) (1996)
(3)) (2005). 16481654.
[2] A. Eid, M. Abdel-Salam, H. El-Kishky, T. El-Mohandes, Simulation and transient [29] B. Singh, K. AL-Haddad, A. Chandra, A new control approach to three-phase
analysis of conventional and advanced aircraft electric power systems with har- active lter for harmonics and reactive power compensation, IEEE Trans. Power
monic mitigation, Electric Power Systems Research, submitted for publication. System 13 (February (1)) (1998) 133138.
[3] G. Ferland, A. Chikhani, J.C. Cartier, Harmonic and transient analysis of an air- [30] D. Chen, T. Guo, S. Xie, B. Zhou, Shunt active power lters applied in the air-
craft electrical distribution system, in: Canadian Conference on Electrical and craft power utility, in: IEEE 36th Power Electronics Specialists Conference (PESC
Computer Engineering, vol.2, September 1417, 1993, pp. 668671. 2005), 2005, pp. 5063.
[4] MIL-STD-704F, Aircraft electric power characteristics, Military Standard, 2004. [31] P.C. Krause, Analysis of Electric Machinery, McGraw Hill Inc., New York, 1987.

Vous aimerez peut-être aussi