(i) In load case 11,15,19 & 23 impact factor for live load considered is 15%, but as per IS 4651(Part-III), Clause no 5.1.3, it should be 25%.please clarify?? (ii) In load case 43, member load defined as 116 TO 128 UNI GX 2.125, but it should be 97 TO 110 UNI GX 2.125 please modify. (iii) In load case 44, member load defined as 116 TO 128 UNI GZ 2.125, but it should be 97 TO 110 UNI GZ 2.125. please modify. (iv) In load case 81, there is repetition of load defined for members from 227, 214, 201, 188, 175, 162 & 149.please modify. (v) During storms/tsumani, RMQC Cranes are tie down to the berths and it can create horizontal force and vertical load as point loads at tie down locations. But this load case is not considered in load combinations and design. Please clarify?? (vi)In RMQC Extreme condition, Horizontal forces due to RMQC in X and Z directions are not considered in load cases and load combinations, please clarify?? (vii) In Load combinations, FZ horizontal operating with vertical load is considered, but FX horizontal operating with vertical load is not considered. Please clarify (Ex: Load combinations from 102 to 109) ?? (viii) In Load combinations from 205 to 209,302 to 305, 321 to 324,503 to 506,522 to 525, only vertical load due to RMQC is considered, but FX/FZ horizontal operating with vertical live load is not considered. Please clarify?? (ix) In load combination 521, load combination defined as 1 1.0 2 1.0 3 1.0 4 1.0 6 1.0,but it should be 1 1.0 2 1.0 3 1.0 4 1.0 8 1.0. (x) In load case no 93, differential shrinkage of concrete is not considered. Please consider differential shrinkage in terms of temp. difference and apply in staad model as temp.difference. (xi) In load cases, wind load in Z direction considered only, but not considered in X-direction. Please clarify?? (b) STAAD FILE (Main jetty _limit state_1.4 pile dia_Z): In addition to the above comments, the below comments are additional. (i) In load combinations, partial load factor for live load in vertical direction considered as 1.5, but horizontal force due to live load during operating condition taken as 1.0.please clarify?? (For Example load combination 402, partial load factor for load case 11 taken as 1.5, but for load case 13, taken as 1.0). (ii) in earthquake load combinations, live load considered as 50%,but in staad model taken as 100%.please clarify?? (Ex: For load combination 585, partial load factor for load case 11(RMQC Vertical load) taken as 1.2, but as per code, it should be 0.5*1.2=0.6). (c ) Design Document & Drawing: (i) In crack width calculation,Ece taken as Ec/2,but it should be Ec. please clarify?? (ii) In crack width calculation, spacing between bars(s) taken different from design document/drawing. For example, refer page no-21, spacing between bars(s) taken as 98mm, but as per design document, it should be 121.5mm ((1000-2*50-12*2-25)/7).please recalculate the crack width as per actual spacing between bars and dia of bar. (iii) Reinforcement for longitudinal shear in tabular format, area proposed calculations (provide shear reinforcement) are not correct. Please modify. (Example page no-151). (iv) Provide minimum reinforcement in web area as 0.1% of gross cross section on both sides and spacing of bar not exceed 300mm. (v)In drawing, bar mark 4 curtailed at 3.0m from centre of beam, please ensure sufficient development ( Ld) provided or not?? (vi) Please provide the reinforcement detailing of beam at beam and pile junction in plan. (d) Drawing for A1, A2, B1, B2 &C1: (i) in drawing sagging reinforcement bar mark shown as 15 in elevation, but as per cross section it should 27.please modify.
Comments on staad file applicable for remaining Longitudinal beams