Design calculation sheet

PEACE VECTOR VII, PKG B, CAIRO


WEST
Project no.: Date: 15/07/2014 Sheet no.: 1 of 1 Computed by: Tamer Hassan
Air Base, Egypt

Checked by:
Subject: Rotating Beacon Foundation
Approved by:

Footings Subjected to Uniaxial or Biaxial Moment


Footing ID: F1
Input Data:
CA = 0.45 m (dimension parallel to A direction)
CB = 0.45 m (dimension parallel to B direction)
A= 4 m (Long dimension of footing or dimension resisting moment in case of uniaxial moment)
B= 4 m (Short dimension of footing)
t= 2 m (Total thickness of footing)
Foundation depth = 2 m (Distance measured from foundation level to finished ground level )
Gs = 1.8 t/m3 (Specific gravity of soil)
qall(net) = 20 t/m2 (Net bearing capacity)
Type of stress used : NET ("Net" or "Gross" )
% Taken of Backfilling = 0 % (Considered in checking overturning and sliding)
PC = -1.5 t (Total column service load (-ve) value for compression & (+ve) value for tension)
Pw&g.b = 0 t (Total load of walls, grade beams and any additional load)
HA = 1.44 t (Total horizontal force parallel to A direction) (0.09 t/m * 16.00 m)
HB = 0 t (Total horizontal force parallel to B direction)
Arm for Horizontal Force = 10 m (Lever arm of horizontal force)
MB MA
MA(add) = 0 mt (Total additional moment in A direction)
MB(add) = 0 mt (Total additional moment in B direction)
HA
MA (Total ) = 14.40 mt (Total moment in A direction) HB
MB (Total) = 0.00 mt (Total moment in B direction)
Output Data:
Lever arm of
Po.w = -22.40 t (Net O.W of footing) 2
2
horizontal force
qall(gross) = 23.60 t/m (Gross bearing capacity)
Area = 16.00 m2 (Spread area of footing) CB CA 3
m4 t
IA = 21.33 (Inertia resisting M A ) 1
4
IB = 21.33 m (Inertia resisting M B )
4 A
Pb.f = 0.00 t (Load of backfilling)
B

Check of Overturning Due to Total Load:


Pserv = -81.5 t (Total service load)
eA = 0.177 m (e<L/3 Safe ) eB = 0.000 m (e<L/3 Safe )
(eA/A)^2+(eB/B)^2 = 0.002 <1/9 (Overturning is Safe)

Stresses on Soil Due to Total Load :


Backfilling is taken as 0% in Net stesses and 100% in Gross stresses
Pserv = -23.90 t (Total service load for net stesses)
F1 = -0.14 t/m2 (Safe) F3 = -2.84 t/m2 (Safe)
F2 = -2.84 t/m2 (Safe) F4 = -0.14 t/m2 (Safe)

*Redistribution of Stresses Due to Total Load:


eA1 /A = 0.044 eA1= 0.177 m eB1= 0.000 m
eB1 /B = 0.000
C3 = N.A. (Fintel Coefficient For Stress Distribution)
2
Fmax = -2.84 t/m (Safe) (No redistribution of stresses )

Check of sliding Due to Total Load (Passive earth pressure is neglected)


Pserv = -81.50 t (Total service load)
coefficient of friction() = 0.3 F.S against sliding = 16.98 >=1.5 (Safe)