A1 A1

ONE LAMP MAGNETIC BALLAST

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHITE WHT/BLK
COMMON
BALLAST RED OR
WHT/BLK RED/BLK(+)
CHARGE
BLUE/WHT WHT/RED INDICATOR
A.C.
BLACK BLUE BLUE
BALLAST
SWITCHED OR YELLOW WHT/BLK
UNSWITCHED
LINE YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

*LAMP
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

1LMB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A2 A2
ONE LAMP HIGH POWER FACTOR MAGNETIC BALLAST

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHT/BLK
COMMON WHITE
BALLAST RED OR
WHT/BLK RED/BLK(+)

CHARGE
WHITE BLUE/WHT WHT/RED INDICATOR
A.C.
BLACK BLUE BLUE
BALLAST
SWITCHED OR YELLOW WHT/BLK
UNSWITCHED
LINE YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

*LAMP
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

1LHPFMB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A3 A3
ONE LAMP ELECTRONIC BALLAST

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHT/BLK
COMMON WHITE
BALLAST RED OR
WHT/BLK RED/BLK(+)

CHARGE
WHITE RED BLUE/WHT WHT/RED INDICATOR
A.C.
BLACK BALLAST BLUE BLUE
SWITCHED OR YELLOW WHT/BLK
UNSWITCHED
LINE YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

*LAMP SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD


DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

1LEB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A4 A4
TWO LAMP ELECTRONIC BALLAST

BLK (120V) TEST


UNSWITCHED LINE SWITCH
ORG (277V)
EMERGENCY
WHITE

WHITE WHT/BLK
COMMON
BALLAST
WHT/BLK
RED OR
RED/BLK(+)

CHARGE
WHITE BLACK BLUE/WHT WHT/RED INDICATOR
A.C.
BLACK BALLAST WHITE BLUE
SWITCHED OR YELLOW WHT/BLK
UNSWITCHED
LINE YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

LAMP *LAMP
WHT SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
BLACK DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
*AC/EMERGENCY LAMP
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

2LEB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A5 A5
TWO LAMP PARALLEL MAGNETIC BALLAST

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHT/BLK
COMMON WHITE
BALLAST
WHT/BLK
RED OR
RED/BLK(+)

BLUE/WHT CHARGE
WHT/RED INDICATOR
A.C.
BLACK BALLAST BLUE BLUE
SWITCHED OR YELLOW WHT/BLK
UNSWITCHED
LINE YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

LAMP *LAMP SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD


DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
RED
*AC/EMERGENCY LAMP
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

2LPMB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A6 A6
TWO LAMP PARALLEL HIGH POWER FACTOR MAGNETIC BALLAST

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHT/BLK
COMMON WHITE
BALLAST RED OR
WHT/BLK RED/BLK(+)

CHARGE
WHITE BLUE/WHT WHT/RED INDICATOR
A.C.
BLACK BALLAST BLUE BLUE
SWITCHED OR YELLOW WHT/BLK
UNSWITCHED
LINE YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

LAMP *LAMP SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD


DO NOT MATE CONNECTOR UNTIL INSTALLATION
BLUE IS COMPLETE AND A.C. POWER IS SUPPLIED.

*AC/EMERGENCY LAMP TEST ACCESSORY LEADS-REFER TO INSTALLATION


INSTRUCTIONS FOR PROPER POLARITY WIRING.

2LPHPFMB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A7 A7
TWO LAMP SERIES MAGNETIC BALLAST

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHT/BLK
COMMON WHITE BALLAST
WHT/BLK
RED OR
RED/BLK(+)

CHARGE
A.C. BLUE BLUE WHT/RED INDICATOR
BLACK BALLAST WHT BLUE/WHT
SWITCHED OR YELLOW WHT/BLK
UNSWITCHED
LINE YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

LAMP *LAMP SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD


DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
*AC/EMERGENCY LAMP INSTRUCTIONS FOR PROPER POLARITY WIRING.

2LSMB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A8 A8
TWO LAMP SERIES HIGH POWER FACTOR MAGNETIC BALLAST

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHT/BLK
COMMON WHITE
BALLAST RED OR
WHT/BLK RED/BLK(+)
CHARGE
WHITE BLUE/WHT WHT/RED INDICATOR
A.C.
BLACK BALLAST BLUE BLUE
SWITCHED OR YELLOW WHT/BLK
UNSWITCHED
LINE YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

LAMP *LAMP SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD


DO NOT MATE CONNECTOR UNTIL INSTALLATION
RED IS COMPLETE AND A.C. POWER IS SUPPLIED.

*AC/EMERGENCY LAMP
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

2LSHPFMB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A9 A9
TWO NORMAL POWER FACTOR MAGNETIC BALLASTS

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHT/BLK
COMMON WHITE
BALLAST RED OR
WHT/BLK RED/BLK(+)
CHARGE
BLUE/WHT WHT/RED INDICATOR
SWITCHED OR A.C.
UNSWITCHED BLACK BALLAST BLUE BLUE
LINE #1 YELLOW WHT/BLK
YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

A.C.
BLACK
BALLAST BLUE
#2 LAMP *LAMP SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
*AC/EMERGENCY LAMP TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

2NPFMB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A10 A10
TWO HIGH POWER FACTOR MAGNETIC BALLASTS

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHT/BLK
COMMON WHITE
BALLAST RED OR
WHT/BLK RED/BLK(+)
WHITE BLUE/WHT CHARGE
WHT/RED
SWITCHED OR A.C. INDICATOR
UNSWITCHED BLACK BALLAST BLUE BLUE
LINE #1 YELLOW WHT/BLK
YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR
BLACK A.C.
BALLAST BLUE
WHITE
#2 LAMP *LAMP SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
*AC/EMERGENCY LAMP
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

2HPFMB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A11 A11
EMERGENCY OPERATION ONLY

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHITE WHT/BLK
COMMON
BALLAST RED OR

WHT/BLK RED/BLK(+)
BLUE/WHT CHARGE
WHT/RED INDICATOR
BLUE
YELLOW WHT/BLK
YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

*LAMP SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD


DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

1LMB_EO

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A12 A12
ONE LAMP FULLHAM BALLAST

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHT/BLK
COMMON WHITE
BALLAST RED OR
WHT/BLK RED/BLK(+)
CHARGE
WHITE YELLOW BLUE/WHT WHT/RED INDICATOR
BLACK A.C. RED BLUE
SWITCHED OR BALLAST RED
UNSWITCHED YELLOW WHT/BLK
LINE YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

*LAMP SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD


DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

1LFB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A13 A13
TWO LAMP FULLHAM BALLAST

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
COMMON WHITE WHT/BLK
BALLAST RED OR
WHT/BLK RED/BLK(+)
WHITE CHARGE
RED BLUE/WHT WHT/RED INDICATOR
A.C.
BLACK BALLAST RED BLUE
SWITCHED OR YELLOW WHT/BLK
UNSWITCHED
LINE YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

LAMP *LAMP
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
YELLOW *AC/EMERGENCY LAMP TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

2LFB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A14 A14
TWO LAMP FULLHAM BALLAST

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHT/BLK
COMMON WHITE
BALLAST
WHT/BLK
RED OR
RED/BLK(+)

BLUE/WHT CHARGE
WHITE RED WHT/RED INDICATOR
BLACK A.C. YEL BLUE
SWITCHED OR BALLAST YELLOW WHT/BLK
UNSWITCHED
LINE YEL/BLK WHT/BLK
UNIT
FLEX B CONNECTOR
FLEX A

LAMP *LAMP SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD


DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
RED
TEST ACCESSORY LEADS-REFER TO INSTALLATION
*AC/EMERGENCY LAMP INSTRUCTIONS FOR PROPER POLARITY WIRING.

2LFB_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A15 A15
TWO LAMP MAGNETIC BALLAST

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHITE WHT/BLK
COMMON
BALLAST RED OR
WHT/BLK RED/BLK(+)
CHARGE
BLUE/WHT WHT/RED INDICATOR
A.C.
BLACK BLUE BLUE
BALLAST
SWITCHED OR YELLOW WHT/BLK
UNSWITCHED
LINE YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

*LAMP *LAMP
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

2LMB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


A16 A16
TWO LAMP PARALLEL ELECTRONIC BALLAST

BLK (120V) TEST


UNSWITCHED LINE WHITE SWITCH
ORG (277V)
EMERGENCY
WHT/BLK
COMMON WHITE
BALLAST RED OR
WHT/BLK RED/BLK(+)

CHARGE
WHITE RED BLUE/WHT WHT/RED INDICATOR
A.C.
BLACK BALLAST BLUE BLUE
SWITCHED OR YELLOW WHT/BLK
UNSWITCHED
LINE YEL/BLK WHT/BLK
UNIT
FLEX A FLEX B CONNECTOR

SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD


LAMP *LAMP
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

2LPEB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB1 AB1
ONE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
UNIT LINE
CONNECTOR
BLACK BLUE BLUE BRN
WHITE BLUE BLUE/WHT
A.C. RED/WHT EMERGENCY
BLACK
RED BLK/ORG (110-277V)
RED Ballast RED BALLAST UNSWITCHED
YELLOW WHITE
COMMON

WHT/RED

VIOLET

VIOLET
RED/BLK
RED OR
*LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
LPTS VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

NISD80_1

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB2 AB2
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
UNIT LINE
CONNECTOR
BLACK BLUE BLUE BRN
WHITE BLUE BLUE/WHT
A.C. RED/WHT EMERGENCY
BLACK
YELLOW RED BLK/ORG (110-277V)
YELLOW Ballast RED
RED BALLAST UNSWITCHED
YELLOW WHITE
COMMON

RED/BLK (+)
LAMP

VIOLET

VIOLET
WHT/RED
DO NOT MATE CONNECTOR UNTIL

RED OR
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
COMMON LPTS
TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

NISD80_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB3 AB3
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNIT UNSWITCHED
BLACK BLUE/WHT BLUE CONNECTOR LINE
BRN
WHITE BLUE/WHT BLUE/WHT
BLUE
BLUE
A.C. RED/WHT EMERGENCY
BLACK
RED
YELLOW Ballast RED
RED BALLAST
BLK/ORG (110-277V)
UNSWITCHED
YELLOW YELLOW WHITE
COMMON
LAMP

RED/BLK (+)

VIOLET

VIOLET
DO NOT MATE CONNECTOR UNTIL

WHT/RED
*LAMP INSTALLATION IS COMPLETE AND

RED OR
AC POWER IS SUPPLIED.
LAMP LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
COMMON LPTS TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

NISD80_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB4 AB4
ONE LAMP INSTANT START BALLAST

SWITCHED OR
UNIT UNSWITCHED
CONNECTOR LINE
BLUE BLUE BRN
BLACK BLUE/WHT
WHITE A.C. RED/WHT EMERGENCY
BLACK

RED Ballast RED BALLAST BLK/ORG (110-277V)


UNSWITCHED
YELLOW WHITE
COMMON

RED/BLK (+)

VIOLET

VIOLET
DO NOT MATE CONNECTOR UNTIL

WHT/RED

RED OR
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
LPTS
COMMON CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
*AC / EMERGENCY
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

NISD80_4

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB5 AB5
TWO LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
UNIT LINE
CONNECTOR
BLUE BLUE BRN
BLUE/WHT BLACK
BLACK A.C. RED/WHT EMERGENCY
BLK/ORG (110-277V)
WHITE Ballast RED RED BALLAST UNSWITCHED
YELLOW WHITE
COMMON

RED/BLK (+)

VIOLET

VIOLET
LAMP
DO NOT MATE CONNECTOR UNTIL

WHT/RED
RED OR
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
COMMON LPTS CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

NISD80_5

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB6 AB6
TWO LAMP INSTANT START BALLAST

SWITCHED OR
UNIT UNSWITCHED
CONNECTOR LINE
BLACK BLUE BLUE BRN
WHITE BLUE/WHT
A.C. RED/WHT EMERGENCY
BLACK

RED Ballast BLUE


RED BALLAST BLK/ORG (110-277V)
UNSWITCHED
YELLOW WHITE
COMMON
LAMP

RED/BLK (+)

VIOLET

VIOLET
DO NOT MATE CONNECTOR UNTIL

WHT/RED
*LAMP INSTALLATION IS COMPLETE AND

RED OR
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
COMMON LPTS CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

NISD80_6

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB7 AB7
THREE LAMP INSTANT START BALLAST

SWITCHED OR
UNIT UNSWITCHED
CONNECTOR LINE
BLACK BLUE BLUE BRN
WHITE BLUE/WHT
A.C. BLUE RED/WHT EMERGENCY
BLACK

RED Ballast BLUE


RED BALLAST BLK/ORG (110-277V)
UNSWITCHED
YELLOW WHITE
COMMON
LAMP

RED/BLK (+)
VIOLET

VIOLET
DO NOT MATE CONNECTOR UNTIL

WHT/RED
INSTALLATION IS COMPLETE AND

RED OR
LAMP
AC POWER IS SUPPLIED.
*LAMP LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.

COMMON
LPTS CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
*AC / EMERGENCY
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

NISD80_7

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB8 AB8
FOUR LAMP INSTANT START BALLAST

SWITCHED OR
UNIT UNSWITCHED
CONNECTOR LINE
BLACK BLUE BLUE BRN
WHITE BLUE BLUE/WHT
YELLOW
A.C. RED RED/WHT EMERGENCY
BLACK

YELLOW
Ballast RED
RED BALLAST
BLK/ORG (110-277V)
UNSWITCHED
YELLOW WHITE
COMMON
LAMP

RED/BLK (+)

VIOLET

VIOLET
DO NOT MATE CONNECTOR UNTIL

WHT/RED
LAMP INSTALLATION IS COMPLETE AND

RED OR
AC POWER IS SUPPLIED.
LAMP
LAMP SELECTOR LEADSREFER
*LAMP TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
COMMON LPTS CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
*AC / EMERGENCY
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

NISD80_8

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB9 AB9
TWO LAMP RAPID START BALLAST W/ TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNIT UNSWITCHED
CONNECTOR LINE
BLACK BLUE BLUE BRN
WHITE BLUE BLUE/WHT
A.C. RED/WHT EMERGENCY
BLACK
YELLOW RED
YELLOW Ballast RED
RED BALLAST
BLK/ORG (110-277V)
UNSWITCHED
YELLOW WHITE
COMMON

RED/BLK (+)
*LAMP

VIOLET

VIOLET

WHT/RED
DO NOT MATE CONNECTOR UNTIL

RED OR
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS
COMMON LPTS
TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

NISD80_9

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB10 AB10
TWO LAMP INSTANT START BALLAST W/ TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNIT UNSWITCHED
CONNECTOR LINE
BLACK BLUE BLUE BRN
WHITE BLUE/WHT
A.C. RED/WHT EMERGENCY
BLACK

RED Ballast BLUE RED BALLAST BLK/ORG (110-277V) UNSWITCHED


YELLOW WHITE
COMMON
*LAMP

RED/BLK (+)

VIOLET

VIOLET
DO NOT MATE CONNECTOR UNTIL

WHT/RED
*LAMP

RED OR
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS
LPTS
COMMON CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

NISD80_10

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB11 AB11
FOUR LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
UNIT
LINE
BLACK BLUE CONNECTOR
RED
BRN
WHITE RED BLUE/WHT
YELLOW
YELLOW
A.C. BLUE/WHT
BLUE/WHT
RED/WHT EMERGENCY BLACK
RED BALLAST
BROWN
BROWN
Ballast BLUE YELLOW
BLK/ORG (110-277V)
WHITE
UNSWITCHED
BLUE COMMON

RED/BLK (+)
DO NOT MATE CONNECTOR UNTIL

VIOLET

VIOLET
WHT/RED
LAMP

RED OR
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

*LAMP
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
*LAMP
LAMP OPERATION SECTION FOR
LPTS VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

NISD80_11

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB12 AB12
THREE LAMP INSTANT START BALLAST TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNIT UNSWITCHED
CONNECTOR LINE
BLACK BLUE BLUE BRN
WHITE BLUE/WHT
A.C. BLUE RED/WHT EMERGENCY
BLACK

RED
Ballast BLUE
RED BALLAST BLK/ORG (110-277V)
UNSWITCHED
YELLOW WHITE
COMMON
LAMP

RED/BLK (+)
VIOLET

VIOLET
DO NOT MATE CONNECTOR UNTIL

WHT/RED
INSTALLATION IS COMPLETE AND

RED OR
*LAMP
AC POWER IS SUPPLIED.
*LAMP LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.

COMMON
LPTS CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.
*AC / EMERGENCY
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

NISD80_12

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB13 AB13
THREE LAMP RAPID START BALLAST TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNIT UNSWITCHED
BLACK BLUE/WHT BLUE CONNECTOR LINE
BRN
WHITE BLUE/WHT BLUE/WHT
BLUE
BLUE
A.C. RED/WHT EMERGENCY
BLACK
RED
YELLOW Ballast RED
RED BALLAST BLK/ORG (110-277V)
UNSWITCHED
YELLOW YELLOW WHITE
COMMON
*LAMP

RED/BLK (+)

VIOLET

VIOLET
DO NOT MATE CONNECTOR UNTIL

WHT/RED
*LAMP INSTALLATION IS COMPLETE AND

RED OR
AC POWER IS SUPPLIED.
LAMP LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
COMMON LPTS
TEST ACCESSORY LEADS-REFER
*AC / EMERGENCY TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

NISD80_13

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB14 AB14
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
UNIT LINE
CONNECTOR
BLACK BLUE BLUE BRN
WHITE BLUE BLUE/WHT
A.C. RED/WHT EMERGENCY
BLACK
YELLOW RED BLK/ORG (110-277V)
YELLOW Ballast RED
RED BALLAST UNSWITCHED
YELLOW WHITE
COMMON

RED/BLK (+)
LAMP

VIOLET

VIOLET
WHT/RED
DO NOT MATE CONNECTOR UNTIL

RED OR
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
COMMON LPTS
TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

NISD80_14

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB15 AB15
ONE LAMP EMERGENCY ONLY

UNIT
CONNECTOR
BLUE BLACK
BLUE/WHT BRN
RED/WHT EMERGENCY
BLK/ORG (110-277V)
RED BALLAST UNSWITCHED
YELLOW WHITE
COMMON

WHT/RED

VIOLET

VIOLET
RED/BLK
RED OR
*LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
*AC / EMERGENCY
LAMP OPERATION SECTION FOR
LPTS VARIOUS OPTIONS.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.
CAP UNUSED LEADS.

NISD80_15

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB16 AB16
FOUR LAMP RAPID START BALLAST

UNIT
SWITCHED OR
CONNECTOR
YELLOW BLUE UNSWITCHED
YELLOW BLUE/WHT BRN LINE
BLACK BROWN RED/WHT BLACK
WHITE A.C. BROWN RED
EMERGENCY
BALLAST
BLK/ORG (110-277V)
UNSWITCHED
Ballast
BLU/WHT BLUE YELLOW WHITE
BLU/WHT BLUE COMMON
ORANGE

RED/BLK (+)
RED

VIOLET

VIOLET
WHT/RED
ORANGE RED

RED OR
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP
LPTS
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
*LAMP
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.

COMMON TEST ACCESSORY LEADS-REFER


TO INSTALLATION INSTRUCTIONS
*AC / EMERGENCY FOR PROPER POLARITY WIRING.

NISD80_16

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB17 AB17
THREE LAMP RAPID START BALLAST

ORANGE
ORANGE UNIT SWITCHED OR
CONNECTOR UNSWITCHED
BLACK RED BLUE LINE
WHITE
A.C. RED BLUE/WHT BRN
YELLOW
BLUE Ballast YELLOW RED/WHT EMERGENCY
BLACK
BLUE BLK/ORG (110-277V)
BLU/WHT BROWN RED BALLAST UNSWITCHED
BLU/WHT BROWN YELLOW WHITE
COMMON
LAMP

RED/BLK (+)

VIOLET

VIOLET
DO NOT MATE CONNECTOR UNTIL

WHT/RED
*LAMP INSTALLATION IS COMPLETE AND

RED OR
AC POWER IS SUPPLIED.
LAMP LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
COMMON LPTS TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

NISD80_17

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB18 AB18
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNIT UNSWITCHED
BLACK BLUE/WHT BLUE CONNECTOR LINE
BRN
WHITE BLUE/WHT BLUE/WHT
BLUE
BLUE
A.C. RED/WHT EMERGENCY
BLACK
RED
YELLOW Ballast RED
RED BALLAST
BLK/ORG (110-277V)
UNSWITCHED
YELLOW YELLOW WHITE
COMMON
LAMP

RED/BLK (+)

VIOLET

VIOLET
DO NOT MATE CONNECTOR UNTIL

WHT/RED
*LAMP INSTALLATION IS COMPLETE AND

RED OR
AC POWER IS SUPPLIED.
LAMP LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
COMMON LPTS TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

NISD80_18

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB19 AB19
FOUR LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
UNIT
LINE
BLACK BLUE CONNECTOR
RED
BRN
WHITE RED BLUE/WHT
YELLOW
YELLOW
A.C. BLUE/WHT
BLUE/WHT
RED/WHT EMERGENCY BLACK
RED BALLAST
BROWN
BROWN
Ballast BLUE YELLOW
BLK/ORG (110-277V)
WHITE
UNSWITCHED
BLUE COMMON

RED/BLK (+)
DO NOT MATE CONNECTOR UNTIL

VIOLET

VIOLET
WHT/RED
LAMP

RED OR
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

*LAMP
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
*LAMP
LAMP OPERATION SECTION FOR
LPTS VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

NISD80_19

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AB20 AB20
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE BROWN LINE
BLUE BLUE/WHT
WHITE RED RED/WHT
YELLOW A.C. RED RED
EMERGENCY BLK
BLK/ORG (110-277V)
YELLOW Ballast BROWN
BROWN
YELLOW BALLAST
WHITE
UNSWITCHED
COMMON
BLU/WHT ORANGE
BLU/WHT DO NOT MATE CONNECTOR UNTIL

VIOLET
VIOLET
ORANGE

RED/BLK (+)
UNIT INSTALLATION IS COMPLETE AND

WHT/RED
CONNECTOR AC POWER IS SUPPLIED.

RED OR
LAMP LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
LAMP
VARIOUS OPTIONS.

*LAMP
LPTS TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
COMMON
POLARITY WIRING.
*AC / EMERGENCY

NISD80_20

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AC1 AC1
ONE LAMP RAPID START BALLAST

UNSWITCHED BLK (120V)


LINE ORG (277V)
VIOLET
SWITCHED OR WHITE VIOLET
UNSWITCHED COMMON
LINE BLK/ORG OR BLK/BRN
FLEX A EMERGENCY FLEX B RED OR RED/BLK(+)
BLK/ORG OR BLK/BRN WHT/RED TBTS
COMMON BALLAST
BLUE BLUE WHT/BLK
BLACK ONE LAMP BLUE BLU/WHT WHT/BLK UNIT CONNECTOR
WHITE A.C. RED BROWN
BALLAST RED BROWN
YELLOW
SELECT PROPER VOLTAGE LEAD, CAP UNUSED LEAD
YELLOW LAMP SELECTOR LEADS. REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER APPLICATION.
RED/WHT
RED
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.

TEST ACCESSORY LEAD - REFER TO INSTALLATION


INSTRUCTIONS FOR PROPER POLARITY WIRING.
LAMP
NO POLARITY ON BLACK LEADS - USE EITHER LEAD
FOR CONNECTION TO THE AC CIRCUIT AND BALLAST.

1LRSB42A_AC

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AC2 AC2
TWO LAMP RAPID START BALLAST

UNSWITCHED BLK (120V)


LINE ORG (277V)
VIOLET
SWITCHED OR WHITE VIOLET
UNSWITCHED COMMON
LINE BLK/ORG OR BLK/BRN
FLEX A EMERGENCY FLEX B RED OR RED/BLK(+)
BLK/ORG OR BLK/BRN WHT/RED TBTS
COMMON BALLAST
BLUE BLUE WHT/BLK
BLACK BLUE BLU/WHT WHT/BLK UNIT CONNECTOR
WHITE TWO LAMP YELLOW BROWN
A.C. YELLOW
BALLAST BROWN SELECT PROPER VOLTAGE LEAD, CAP UNUSED LEAD
RED
RED YELLOW LAMP SELECTOR LEADS. REFER TO INSTALLATION
YELLOW INSTRUCTIONS FOR PROPER APPLICATION.

RED/WHT DO NOT MATE CONNECTOR UNTIL INSTALLATION


IS COMPLETE AND A.C. POWER IS SUPPLIED.
RED
TEST ACCESSORY LEAD - REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
LAMP *LAMP
NO POLARITY ON BLACK LEADS - USE EITHER LEAD
FOR CONNECTION TO THE AC CIRCUIT AND BALLAST.

*A.C./EMERGENCY LAMP

2LRSB42A_AC

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AC3 AC3
TWO LAMP RAPID START BALLAST TWO LAMP EMERGENCY OPERATION

UNSWITCHED BLK (120V)


LINE ORG (277V)
VIOLET
SWITCHED OR WHITE VIOLET
UNSWITCHED COMMON
LINE BLK/ORG OR BLK/BRN
FLEX A EMERGENCY FLEX B RED OR RED/BLK(+)
BLK/ORG OR BLK/BRN WHT/RED TBTS
COMMON BALLAST
BLUE BLUE WHT/BLK
BLACK BLUE BLU/WHT WHT/BLK UNIT CONNECTOR
WHITE TWO LAMP RED BROWN
A.C. RED BROWN
BALLAST SELECT PROPER VOLTAGE LEAD, CAP UNUSED LEAD
YELLOW
YELLOW LAMP SELECTOR LEADS. REFER TO INSTALLATION
YELLOW YELLOW INSTRUCTIONS FOR PROPER APPLICATION.

RED/WHT DO NOT MATE CONNECTOR UNTIL INSTALLATION


IS COMPLETE AND A.C. POWER IS SUPPLIED.
RED
TEST ACCESSORY LEAD - REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
*LAMP *LAMP NO POLARITY ON BLACK LEADS - USE EITHER LEAD
FOR CONNECTION TO THE AC CIRCUIT AND BALLAST.

*A.C./EMERGENCY LAMP

2LRSB42A_AC_2LEO

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AC4 AC4
TWO LAMP RAPID START BALLAST

UNSWITCHED BLK (120V)


LINE ORG (277V)
VIOLET
SWITCHED OR WHITE VIOLET
UNSWITCHED COMMON
LINE BLK/ORG OR BLK/BRN EMERGENCY
FLEX A FLEX B RED OR RED/BLK(+)
BLK/ORG OR BLK/BRN WHT/RED TBTS
COMMON BALLAST
BLUE BLUE WHT/BLK
BLACK BLUE BLU/WHT WHT/BLK UNIT CONNECTOR
WHITE TWO LAMP YELLOW BROWN
A.C. YELLOW
BALLAST BROWN SELECT PROPER VOLTAGE LEAD, CAP UNUSED LEAD
RED
RED YELLOW LAMP SELECTOR LEADS. REFER TO INSTALLATION
YELLOW INSTRUCTIONS FOR PROPER APPLICATION.

RED/WHT DO NOT MATE CONNECTOR UNTIL INSTALLATION


IS COMPLETE AND A.C. POWER IS SUPPLIED.
RED
TEST ACCESSORY LEAD - REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
LAMP *LAMP
NO POLARITY ON BLACK LEADS - USE EITHER LEAD
FOR CONNECTION TO THE AC CIRCUIT AND BALLAST.

*A.C./EMERGENCY LAMP CAP UNUSED LEADS.

2LRSB42A_AC_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AC5 AC5
ONE LAMP INSTANT START FULHAM BALLAST

UNSWITCHED BLK (120V)


LINE ORG (277V)
VIOLET
SWITCHED OR WHITE VIOLET
UNSWITCHED COMMON
LINE BLK/ORG OR BLK/BRN
FLEX A EMERGENCY FLEX B RED OR RED/BLK(+)
BLK/ORG OR BLK/BRN WHT/RED TBTS
COMMON BALLAST
RED BLUE WHT/BLK
BLACK ONE LAMP RED BLU/WHT WHT/BLK UNIT CONNECTOR
WHITE A.C. YELLOW BROWN
BALLAST BROWN
YELLOW
SELECT PROPER VOLTAGE LEAD, CAP UNUSED LEAD
YELLOW LAMP SELECTOR LEADS. REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER APPLICATION.
RED/WHT
RED
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.

TEST ACCESSORY LEAD - REFER TO INSTALLATION


INSTRUCTIONS FOR PROPER POLARITY WIRING.
LAMP
NO POLARITY ON BLACK LEADS - USE EITHER LEAD
FOR CONNECTION TO THE AC CIRCUIT AND BALLAST.

1LRSB42A_AC_F

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AC6 AC6
ONE LAMP INSTANT START FULHAM BALLAST

UNSWITCHED BLK (120V)


LINE ORG (277V)
VIOLET
SWITCHED OR WHITE VIOLET
UNSWITCHED COMMON
LINE BLK/ORG OR BLK/BRN
FLEX A EMERGENCY FLEX B RED OR RED/BLK(+)
COMMON
BLK/ORG OR BLK/BRN WHT/RED TBTS
BALLAST
RED BLUE WHT/BLK
BLACK ONE LAMP BLU/WHT WHT/BLK UNIT CONNECTOR
WHITE A.C. YELLOW BROWN
BALLAST RED BROWN
YELLOW
SELECT PROPER VOLTAGE LEAD, CAP UNUSED LEAD
YELLOW LAMP SELECTOR LEADS. REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER APPLICATION.
RED/WHT
RED
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.

TEST ACCESSORY LEAD - REFER TO INSTALLATION


INSTRUCTIONS FOR PROPER POLARITY WIRING.
LAMP
NO POLARITY ON BLACK LEADS - USE EITHER LEAD
FOR CONNECTION TO THE AC CIRCUIT AND BALLAST.

1LRSB42A_AC_F_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AC7 AC7
TWO LAMP INSTANT START FULHAM BALLAST

UNSWITCHED BLK (120V)


LINE ORG (277V)
VIOLET
SWITCHED OR WHITE VIOLET
UNSWITCHED COMMON
LINE BLK/ORG OR BLK/BRN
FLEX A EMERGENCY FLEX B RED OR RED/BLK(+)
COMMON
BLK/ORG OR BLK/BRN WHT/RED TBTS
BALLAST
RED BLUE WHT/BLK
BLACK BLU/WHT WHT/BLK UNIT CONNECTOR
WHITE TWO LAMP YELLOW BROWN
A.C.
BALLAST BROWN SELECT PROPER VOLTAGE LEAD, CAP UNUSED LEAD
RED
YELLOW LAMP SELECTOR LEADS. REFER TO INSTALLATION
YELLOW INSTRUCTIONS FOR PROPER APPLICATION.

RED/WHT DO NOT MATE CONNECTOR UNTIL INSTALLATION


IS COMPLETE AND A.C. POWER IS SUPPLIED.
RED
TEST ACCESSORY LEAD - REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
LAMP *LAMP
NO POLARITY ON BLACK LEADS - USE EITHER LEAD
FOR CONNECTION TO THE AC CIRCUIT AND BALLAST.

*A.C./EMERGENCY LAMP

2LRSB42A_AC_F

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AC8 AC8
TWO LAMP INSTANT START FULHAM BALLAST TWO LAMP EMERGENCY OPERATION

UNSWITCHED BLK (120V)


LINE ORG (277V)
VIOLET
SWITCHED OR WHITE VIOLET
UNSWITCHED COMMON
LINE BLK/ORG OR BLK/BRN
FLEX A EMERGENCY FLEX B RED OR RED/BLK(+)
BLK/ORG OR BLK/BRN WHT/RED TBTS
COMMON BALLAST
RED BLUE WHT/BLK
BLACK BLU/WHT WHT/BLK UNIT CONNECTOR
WHITE TWO LAMP RED BROWN
A.C. BROWN
BALLAST SELECT PROPER VOLTAGE LEAD, CAP UNUSED LEAD
YELLOW YELLOW LAMP SELECTOR LEADS. REFER TO INSTALLATION
YELLOW INSTRUCTIONS FOR PROPER APPLICATION.

RED/WHT DO NOT MATE CONNECTOR UNTIL INSTALLATION


IS COMPLETE AND A.C. POWER IS SUPPLIED.
RED
TEST ACCESSORY LEAD - REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
*LAMP *LAMP NO POLARITY ON BLACK LEADS - USE EITHER LEAD
FOR CONNECTION TO THE AC CIRCUIT AND BALLAST.

*A.C./EMERGENCY LAMP

2LRSB42A_AC_2LEO_F

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AC9 AC9
ONE LAMP EMERGENCY ONLY

UNSWITCHED BLK (120V)


LINE ORG (277V)
VIOLET
COMMON WHITE VIOLET
BLK/ORG OR BLK/BRN
FLEX A EMERGENCY FLEX B RED OR RED/BLK(+)
BLK/ORG OR BLK/BRN WHT/RED TBTS
BALLAST
BLUE WHT/BLK
BLU/WHT WHT/BLK UNIT CONNECTOR
BROWN
BROWN
YELLOW
SELECT PROPER VOLTAGE LEAD, CAP UNUSED LEAD
YELLOW LAMP SELECTOR LEADS. REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER APPLICATION.
RED/WHT
RED
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.

TEST ACCESSORY LEAD - REFER TO INSTALLATION


INSTRUCTIONS FOR PROPER POLARITY WIRING.
LAMP

1LEO_AC_F

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AC10 AC10
THREE LAMP FULHAM BALLAST

UNSWITCHED BLK (120V)


LINE ORG (277V)
VIOLET
SWITCHED OR WHITE VIOLET
UNSWITCHED COMMON
LINE BLK/ORG OR BLK/BRN EMERGENCY RED OR RED/BLK(+)
FLEX A FLEX B
BLK/ORG OR BLK/BRN WHT/RED TBTS
BALLAST
BLUE WHT/BLK
BLACK BLU/WHT WHT/BLK UNIT CONNECTOR
WHITE A.C. BROWN
COMMON RED
BALLAST SELECT PROPER VOLTAGE LEAD, CAP UNUSED LEAD
RED BROWN
YELLOW
RED YELLOW LAMP SELECTOR LEADS. REFER TO INSTALLATION
YELLOW INSTRUCTIONS FOR PROPER APPLICATION.

RED/WHT DO NOT MATE CONNECTOR UNTIL INSTALLATION


IS COMPLETE AND A.C. POWER IS SUPPLIED.
RED
TEST ACCESSORY LEAD - REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.

LAMP LAMP *LAMP NO POLARITY ON BLACK LEADS - USE EITHER LEAD


FOR CONNECTION TO THE AC CIRCUIT AND BALLAST.

*A.C./EMERGENCY LAMP

3LISFB42A_AC

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AC11 AC11
TWO LAMP INSTANT START FULHAM WORKHORSE III BALLAST

UNSWITCHED BLK (120V)


LINE ORG (277V)
VIOLET
SWITCHED OR WHITE VIOLET
UNSWITCHED COMMON
LINE BLK/ORG OR BLK/BRN
FLEX A EMERGENCY FLEX B RED OR RED/BLK(+)
COMMON
BLK/ORG OR BLK/BRN WHT/RED TBTS
BALLAST
RED BLUE WHT/BLK
BLACK BLU/WHT WHT/BLK UNIT CONNECTOR
WHITE TWO LAMP RED BROWN
A.C. BROWN
BALLAST SELECT PROPER VOLTAGE LEAD, CAP UNUSED LEAD
YELLOW YELLOW LAMP SELECTOR LEADS. REFER TO INSTALLATION
YELLOW INSTRUCTIONS FOR PROPER APPLICATION.
RED

RED

RED/WHT DO NOT MATE CONNECTOR UNTIL INSTALLATION


IS COMPLETE AND A.C. POWER IS SUPPLIED.
RED
TEST ACCESSORY LEAD - REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
*LAMP LAMP NO POLARITY ON BLACK LEADS - USE EITHER LEAD
FOR CONNECTION TO THE AC CIRCUIT AND BALLAST.

*A.C./EMERGENCY LAMP

2LRSB42A_AC_2LEO_F_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AC12 AC12
TWO LAMP EMERGENCY OPERATION ONLY

UNSWITCHED BLK (120V)


LINE ORG (277V)
VIOLET
COMMON WHITE VIOLET
BLK/ORG OR BLK/BRN
FLEX A EMERGENCY FLEX B RED OR RED/BLK(+)
BLK/ORG OR BLK/BRN WHT/RED TBTS
BALLAST
BLUE WHT/BLK
BLU/WHT WHT/BLK UNIT CONNECTOR
BROWN
BROWN
SELECT PROPER VOLTAGE LEAD, CAP UNUSED LEAD
YELLOW LAMP SELECTOR LEADS. REFER TO INSTALLATION
YELLOW INSTRUCTIONS FOR PROPER APPLICATION.

RED/WHT DO NOT MATE CONNECTOR UNTIL INSTALLATION


IS COMPLETE AND A.C. POWER IS SUPPLIED.
RED
TEST ACCESSORY LEAD - REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
*LAMP *LAMP NO POLARITY ON BLACK LEADS - USE EITHER LEAD
FOR CONNECTION TO THE AC CIRCUIT AND BALLAST.

*A.C./EMERGENCY LAMP

2LRSB42A_AC_2LEO_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


AC13 AC13
THREE LAMP RAPID START BALLAST

UNSWITCHED BLK (120V)


LINE ORG (277V)
VIOLET
SWITCHED OR WHITE VIOLET
UNSWITCHED COMMON
LINE BLK/ORG OR BLK/BRN EMERGENCY
FLEX A FLEX B RED OR RED/BLK(+)
BLK/ORG OR BLK/BRN WHT/RED TBTS
COMMON BALLAST
BLUE BLUE WHT/BLK
BLACK BLUE BLUE WHT/BLK UNIT CONNECTOR
WHITE BLU/WHT BROWN
BLU/WHT BROWN
A.C. SELECT PROPER VOLTAGE LEAD, CAP UNUSED LEAD
BALLAST
YELLOW YELLOW LAMP SELECTOR LEADS. REFER TO INSTALLATION
YELLOW YELLOW INSTRUCTIONS FOR PROPER APPLICATION.
RED RED/WHT DO NOT MATE CONNECTOR UNTIL INSTALLATION
RED IS COMPLETE AND A.C. POWER IS SUPPLIED.
RED
TEST ACCESSORY LEAD - REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
LAMP LAMP *LAMP
NO POLARITY ON BLACK LEADS - USE EITHER LEAD
FOR CONNECTION TO THE AC CIRCUIT AND BALLAST.

*A.C./EMERGENCY LAMP

3LRSB42A_AC

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


FC1 FC1
TWO LAMP INSTANT START BALLAST

BLUE BLUE
BLACK BLUE VIOLET BLK/ORG

EMERGENCY
WHITE BLUE/WHT
BLK/ORG
SWITCHED OR

BALLAST
A.C. RED/WHT UNSWITCHED
LINE
BALLAST RED BRN/WHT
VIO/WHT WHITE
COMMON
BRN
LAMP*

RED
ORG (277V) UNSWITCHED
LAMP* LINE
YELLOW BLK (120V)

* OPERATES IN A.C. AND

RED/BLK (+)
EMERGENCY MODE.

WHT/RED
CONNECTOR

RED OR
LEAD.
SELECT PROPER VOLTAGE
CAP UNUSED LEADS.

DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE
CHARGE INDICATOR

AND A.C. POWER IS SUPPLIED.

PIGTAIL LEADS TOGETHER.


TEST ACCESSORY LEADS - REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY LEAD WIRING.

NO POLARITY ON BLK/ORG LEADS.


SWITCHED OR UNSWITCHED LINE-
REFER TO INSTALLATION MANUAL
FOR HOT AND TEST SWITCH PLACEMENT.

2LISB_232_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


FC2 FC2
TWO LAMP RAPID START BALLAST

BLUE BLUE
BLACK BLUE BLUE/WHT BLK/ORG

EMERGENCY
WHITE RED VIOLET
A.C. BLK/ORG SWITCHED OR

BALLAST
UNSWITCHED
RED VIO/WHT
BALLAST
YELLOW BRN LINE
YELLOW LAMP* BRN/WHT WHITE
COMMON
RED

LAMP* RED/WHT
ORG (277V)
UNSWITCHED
YELLOW LINE
BLK (120V)
* OPERATES IN A.C. AND

RED/BLK (+)
EMERGENCY MODE.

WHT/RED

RED OR
CONNECTOR

SELECT PROPER VOLTAGE


LEAD. CAP UNUSED LEADS.

DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE CHARGE INDICATOR

AND A.C. POWER IS SUPPLIED.

TEST ACCESSORY LEADS - REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY LEAD WIRING.

NO POLARITY ON BLK/ORG LEADS.


SWITCHED OR UNSWITCHED LINE-
REFER TO INSTALLATION MANUAL
FOR HOT AND TEST SWITCH PLACEMENT.

2LRSB_232_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


FC3 FC3
THREE LAMP INSTANT START BALLAST

BLUE BLUE
BLACK BLUE VIOLET BLK/ORG
WHITE BLUE BLUE/WHT

EMERGENCY
BLK/ORG
SWITCHED OR
RED/WHT UNSWITCHED

BALLAST
A.C. RED
LINE
BALLAST BRN/WHT
WHITE
LAMP
VIO/WHT COMMON
BRN
LAMP* ORG (277V)
UNSWITCHED
LINE
RED BLK (120V)
LAMP*
* OPERATES IN A.C. AND YELLOW

EMERGENCY MODE.

RED/BLK (+)
WHT/RED

RED OR
CONNECTOR
LEAD.
SELECT PROPER VOLTAGE
CAP UNUSED LEADS.

DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE CHARGE INDICATOR
AND A.C. POWER IS SUPPLIED.

PIGTAIL LEADS TOGETHER.


TEST ACCESSORY LEADS - REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY LEAD WIRING.

NO POLARITY ON BLK/ORG LEADS.


SWITCHED OR UNSWITCHED LINE-
REFER TO INSTALLATION MANUAL
FOR HOT AND TEST SWITCH PLACEMENT.

3LISB_232_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


FC4 FC4
THREE LAMP RAPID START BALLAST

RED BLUE
BLACK RED BLUE/WHT BLK/ORG

EMERGENCY
WHITE BLUE/WHT VIOLET
BLK/ORG
SWITCHED OR

BALLAST
A.C. BLUE/WHT VIO/WHT UNSWITCHED
LINE
BALLAST BLUE
WHITE
LAMP COMMON
BLUE BRN
YELLOW
YELLOW
LAMP*
BRN/WHT
RED
ORG (277V)
UNSWITCHED
LINE
RED/WHT BLK (120V)
LAMP*
YELLOW

* OPERATES IN A.C. AND

RED/BLK (+)
WHT/RED
EMERGENCY MODE. CONNECTOR

RED OR
LEAD.
SELECT PROPER VOLTAGE
CAP UNUSED LEADS.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE
CHARGE INDICATOR

AND A.C. POWER IS SUPPLIED.

TEST ACCESSORY LEADS - REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY LEAD WIRING.

NO POLARITY ON BLK/ORG LEADS.


SWITCHED OR UNSWITCHED LINE-
REFER TO INSTALLATION MANUAL
FOR HOT AND TEST SWITCH PLACEMENT.

3LRSB_232_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


FC5 FC5
FOUR LAMP INSTANT START BALLAST

BLUE BLUE
BLACK BLUE VIOLET BLK/ORG
WHITE RED BLUE/WHT

EMERGENCY
BLK/ORG
SWITCHED OR
RED RED/WHT

BALLAST
A.C. UNSWITCHED
LINE
BALLAST LAMP BRN/WHT
YELLOW

YELLOW LAMP VIO/WHT WHITE


COMMON

LAMP*
BRN
RED
ORG (277V)
UNSWITCHED
LAMP* BLK (120V) LINE
YELLOW

RED/BLK (+)
* OPERATES IN A.C. AND

WHT/RED

RED OR
EMERGENCY MODE. CONNECTOR

LEAD.
SELECT PROPER VOLTAGE
CAP UNUSED LEADS.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE
CHARGE INDICATOR

AND A.C. POWER IS SUPPLIED.

PIGTAIL LEADS TOGETHER.


TEST ACCESSORY LEADS - REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY LEAD WIRING.

NO POLARITY ON BLK/ORG LEADS.


SWITCHED OR UNSWITCHED LINE-
REFER TO INSTALLATION MANUAL
FOR HOT AND TEST SWITCH PLACEMENT.
4LISB_232_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


FC6 FC6
FOUR LAMP RAPID START BALLAST

BLACK
RED
RED
BLUE
BLUE/WHT
BLK/ORG
WHITE BLUE/WHITE VIOLET BLK/ORG SWITCHED OR

EMERGENCY
UNSWITCHED
BLUE/WHITE VIO/WHT

BALLAST
YELLOW A.C. LINE
YELLOW BALLAST BLUE RED/WHT WHITE
COMMON
BROWN BLUE RED
BROWN
BRN/WHT
ORG (277V)
UNSWITCHED
LINE
BRN BLK (120V)

YELLOW
LAMP
OPERATES IN A.C. AND
* EMERGENCY MODE

RED/BLK (+)
WHT/RED
LAMP

RED OR
CONNECTOR
LAMP* SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEADS.
LAMP*
CHARGE INDICATOR/
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE
TBTS
AND A.C. POWER IS SUPPLIED.

TEST ACCESSORY LEADS - REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

NO POLARITY ON BLK/ORG LEADS.


SWITCHED OR UNSWITCHED LINE-
REFER TO INSTALLATION MANUAL
FOR HOT AND TEST SWITCH PLACEMENT.

4LRSB_232_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


FC7 FC7
FOUR LAMP RAPID START BALLAST

BLACK
BLUE/WHITE
BLUE/WHITE
BLUE
BLUE/WHT
BLK/ORG
WHITE RED/WHITE VIOLET BLK/ORG SWITCHED OR

EMERGENCY
UNSWITCHED
RED/WHITE VIO/WHT

BALLAST
YELLOW A.C. LINE
YELLOW BALLAST BLUE RED/WHT WHITE
COMMON
BLUE
RED
RED
RED
BRN/WHT
ORG (277V)
UNSWITCHED
LINE
BRN BLK (120V)

YELLOW
LAMP
OPERATES IN A.C. AND

RED/BLK (+)
* EMERGENCY MODE

WHT/RED
LAMP

RED OR
CONNECTOR
LAMP*
SELECT PROPER VOLTAGE
LAMP* LEAD. CAP UNUSED LEADS.

CHARGE INDICATOR/
TBTS DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE
AND A.C. POWER IS SUPPLIED.

TEST ACCESSORY LEADS - REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

NO POLARITY ON BLK/ORG LEADS.


SWITCHED OR UNSWITCHED LINE-
REFER TO INSTALLATION MANUAL
FOR HOT AND TEST SWITCH PLACEMENT.

4LRSB_232_2_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC1 MC1
ONE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED LINE
WHT/BLK
BLUE BLUE 5 COMMON
BLACK WHITE
BLUE/WHT
WHITE A.C. RED/WHT
EMERGENCY
BALLAST ORG (277V)
6
RED Ballast RED BLK (120V) UNSWITCHED
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
UNIT

WHT/RED
*LAMP CONNECTOR

RED OR
TBTS / CHARGE
COMMON INDICATOR
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION 6 CONNECT BLU/WHT AND
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER RED/WHT WIRES TOGETHER
AC POWER IS SUPPLIED. POLARITY WIRING.
1LISB_E

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC2 MC2
ONE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED LINE
WHT/BLK
BLACK BLUE BLUE 5 COMMON
WHITE
WHITE BLUE BLUE/WHT
A.C. RED/WHT
EMERGENCY
BALLAST
ORG (277V)
RED
RED Ballast RED BLK (120V) UNSWITCHED
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
UNIT
*LAMP

WHT/RED
CONNECTOR

RED OR
TBTS / CHARGE
INDICATOR
COMMON
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER
AC POWER IS SUPPLIED. POLARITY WIRING.
1LRSB_E

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC3 MC3
TWO LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED LINE
WHT/BLK
BLACK BLUE BLUE
WHITE 5 COMMON
WHITE BLUE/WHT
A.C. 6 RED/WHT
EMERGENCY
ORG (277V)
BALLAST
RED Ballast BLUE
RED BLK (120V) UNSWITCHED
YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT

WHT/RED
*LAMP CONNECTOR

RED OR
TBTS / CHARGE
INDICATOR
COMMON
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION 6 CONNECT BLU/WHT AND
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER RED/WHT WIRES TOGETHER
AC POWER IS SUPPLIED. POLARITY WIRING.
2LISB_2_E

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC4 MC4
TWO LAMP INSTANT START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
WHT/BLK UNSWITCHED LINE
BLACK BLUE BLUE WHITE 5 COMMON
WHITE BLUE/WHT EMERGENCY
A.C. RED/WHT
ORG (277V)
6
RED Ballast BLUE RED BALLAST BLK (120V) UNSWITCHED
YELLOW WHT/BLK
*LAMP

VIOLET

VIOLET
RED/BLK (+)
UNIT

WHT/RED
*LAMP

RED OR
CONNECTOR

TBTS / CHARGE
INDICATOR
COMMON
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION 6 CONNECT BLU/WHT AND
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER RED/WHT WIRES TOGETHER
AC POWER IS SUPPLIED. POLARITY WIRING.
2LISB_2LEO_80_E

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC5 MC5
TWO LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED LINE
WHT/BLK
BLACK BLUE BLUE 5 COMMON
WHITE
WHITE BLUE BLUE/WHT
A.C. RED/WHT
EMERGENCY
BALLAST
ORG (277V)
YELLOW RED
YELLOW Ballast RED
RED BLK (120V) UNSWITCHED
YELLOW WHT/BLK

RED/BLK (+)
*LAMP

VIOLET

VIOLET
WHT/RED
UNIT

RED OR
*LAMP CONNECTOR

TBTS / CHARGE
INDICATOR
COMMON
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER
AC POWER IS SUPPLIED. POLARITY WIRING.
2LRSB_2LEO_80_E

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC6 MC6
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED LINE
WHT/BLK
BLACK BLUE BLUE 5 COMMON
WHITE
WHITE BLUE BLUE/WHT
A.C. RED/WHT
EMERGENCY
BALLAST
ORG (277V)
YELLOW RED
YELLOW Ballast RED
RED BLK (120V) UNSWITCHED
YELLOW WHT/BLK

RED/BLK (+)
LAMP

VIOLET

VIOLET
UNIT

WHT/RED
CONNECTOR

RED OR
*LAMP

TBTS / CHARGE
INDICATOR
COMMON
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER
AC POWER IS SUPPLIED. POLARITY WIRING.
2LRSB_E

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC7 MC7
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED LINE
WHT/BLK
BLACK BLUE BLUE 5 COMMON
WHITE
WHITE BLUE BLUE/WHT
A.C. RED
RED/WHT
EMERGENCY
ORG (277V)
BALLAST
YELLOW
YELLOW
Ballast RED
RED BLK (120V) UNSWITCHED
YELLOW WHT/BLK
LAMP

VIOLET

VIOLET
RED/BLK (+)
UNIT

WHT/RED
*LAMP

RED OR
CONNECTOR

TBTS / CHARGE
INDICATOR
COMMON
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER
AC POWER IS SUPPLIED. POLARITY WIRING.
2LRSB_E_4

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC8 MC8
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED LINE
WHT/BLK
BLACK RED BLUE 5 COMMON
RED BLUE/WHT
WHITE
WHITE ORANGE RED/WHT EMERGENCY
BLUE A.C. ORANGE RED
BALLAST
ORG (277V)
BLK (120V) UNSWITCHED
BLUE Ballast YELLOW
YELLOW
YELLOW
WHT/BLK
BLU/WHT BROWN
BLU/WHT

VIOLET
VIOLET
BROWN

RED/BLK (+)
UNIT

WHT/RED
CONNECTOR

RED OR
LAMP

LAMP
TBTS / CHARGE
*LAMP INDICATOR

COMMON
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER
AC POWER IS SUPPLIED. POLARITY WIRING.
3_LRSB_E_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC9 MC9
THREE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED LINE
WHT/BLK
BLACK BLUE BLUE
WHITE COMMON
WHITE BLUE/WHT
A.C. BLUE 6 RED/WHT
EMERGENCY
BALLAST
ORG (277V)

RED Ballast BLUE


RED BLK (120V) UNSWITCHED
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
LAMP

WHT/RED
UNIT

RED OR
LAMP CONNECTOR
*LAMP

TBTS / CHARGE
COMMON INDICATOR
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION 6 CONNECT BLU/WHT AND
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER RED/WHT WIRES TOGETHER
AC POWER IS SUPPLIED. POLARITY WIRING.
3LISB_E

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC10 MC10
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED LINE
WHT/BLK
BLACK BLUE/WHT BLUE 5 COMMON
WHITE WHITE
BLUE/WHT BLUE/WHT
BLUE
BLUE
A.C. RED/WHT EMERGENCY ORG (277V)
RED BALLAST
YELLOW Ballast RED
RED BLK (120V) UNSWITCHED
YELLOW YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT

WHT/RED
*LAMP CONNECTOR

RED OR
LAMP

TBTS / CHARGE
INDICATOR
COMMON
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER
AC POWER IS SUPPLIED. POLARITY WIRING.
3LRSB_E

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC11 MC11
FOUR LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED LINE
WHT/BLK
BLACK BLUE BLUE 5 COMMON
WHITE
WHITE BLUE BLUE/WHT EMERGENCY
YELLOW
A.C. RED 6 RED/WHT BALLAST ORG (277V)

YELLOW
Ballast RED
RED BLK (120V) UNSWITCHED
YELLOW WHT/BLK
LAMP

RED/BLK (+)

VIOLET
VIOLET
WHT/RED
UNIT
LAMP

RED OR
CONNECTOR
LAMP
*LAMP

TBTS / CHARGE
INDICATOR
COMMON
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION 6 CONNECT BLU/WHT AND
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER RED/WHT WIRES TOGETHER
AC POWER IS SUPPLIED. POLARITY WIRING.
4LISB_E

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC12 MC12
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED LINE
WHT/BLKE
BLACK BLUE BLUE 5 COMMON
BLUE BLUE/WHT
WHITE
WHITE EMERGENCY
RED RED/WHT
ORG A.C. RED RED BALLAST
ORG (277V)
BLK (120V) UNSWITCHED
ORG Ballast BROWN
BROWN
YELLOW
WHT/BLK
BLU/WHT YELLOW
BLU/WHT

VIOLET
VIOLET
YELLOW

RED/BLK (+)
UNIT

WHT/RED
CONNECTOR

RED OR
LAMP

LAMP

LAMP
TBTS / CHARGE
*LAMP INDICATOR

COMMON
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER
AC POWER IS SUPPLIED. POLARITY WIRING.
4LRSB_E_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC13 MC13
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED LINE
WHT/BLK
BLACK YELLOW BLUE
YELLOW WHITE 5 COMMON
BLUE/WHT
WHITE BROWN RED/WHT EMERGENCY
BLU/WHT A.C. BROWN RED BALLAST
ORG (277V)
UNSWITCHED
BLK (120V)
BLU/WHT Ballast BLUE
BLUE
YELLOW
WHT/BLK
ORG RED
ORG

VIOLET
VIOLET
RED

RED/BLK (+)
UNIT

WHT/RED
CONNECTOR

RED OR
LAMP

LAMP

LAMP
TBTS / CHARGE
*LAMP INDICATOR

COMMON
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER
AC POWER IS SUPPLIED. POLARITY WIRING.
4LRSB_E_4

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC14 MC14
THREE LAMP INSTANT START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
WHT/BLK
BLACK BLUE BLUE 5 COMMON
WHITE
WHITE BLUE/WHT EMERGENCY
A.C. BLUE 6 RED/WHT BALLAST ORG (277V)
RED BLK (120V) UNSWITCHED
RED Ballast BLUE
YELLOW WHT/BLK

RED/BLK (+)
LAMP

VIOLET

VIOLET
WHT/RED
UNIT

RED OR
*LAMP CONNECTOR
*LAMP

TBTS / CHARGE
INDICATOR
COMMON
*AC / EMERGENCY

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION 6 CONNECT BLU/WHT AND
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER RED/WHT WIRES TOGETHER
AC POWER IS SUPPLIED. POLARITY WIRING.
3LISB_2LEO_E

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC15 MC15
FOUR LAMP INSTANT START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
WHT/BLK
BLACK BLUE BLUE WHITE 5 COMMON
BLUE/WHT EMERGENCY
WHITE BLUE
YELLOW
A.C. RED 6 RED/WHT BALLAST
ORG (277V)
UNSWITCHED
BLK (120V)
YELLOW
Ballast RED
RED
YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT

WHT/RED
LAMP

RED OR
CONNECTOR
*LAMP
*LAMP

TBTS / CHARGE
INDICATOR
COMMON
*AC / EMERGENCY
SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION 6 CONNECT BLU/WHT AND
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER RED/WHT WIRES TOGETHER
AC POWER IS SUPPLIED. POLARITY WIRING.
4LISB_2LEO_80E

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC16 MC16
TWO LAMP EMERGENCY ONLY

BLUE WHT/BLK


BLUE/WHT WHITE 5 COMMON
6
RED/WHT EMERGENCY
ORG (277V)
RED
BALLAST BLK (120V) UNSWITCHED
YELLOW WHT/BLK
6


RED/BLK (+)
VIOLET

VIOLET
WHT/RED
UNIT
*LAMP

RED OR
CONNECTOR

*LAMP

*AC / EMERGENCY TBTS / CHARGE


INDICATOR

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION 6 CAP UNUSED LEADS.
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER
AC POWER IS SUPPLIED. POLARITY WIRING.

2LEO_80_E

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


MC17 MC17
ONE LAMP EMERGENCY ONLY

BLUE WHT/BLK


BLUE/WHT WHITE 5 COMMON
6 EMERGENCY
RED/WHT
RED ORG (277V)
BALLAST
BLK (120V) UNSWITCHED
YELLOW
WHT/BLK
6


RED/BLK (+)
VIOLET

VIOLET
*LAMP

WHT/RED
UNIT

RED OR
CONNECTOR

*AC / EMERGENCY

TBTS / CHARGE
INDICATOR

SELECT PROPER VOLTAGE LAMP SELECTOR LEADSREFER 5 USE EITHER WHT/BLK LEAD
LEAD. CAP UNUSED LEAD. REFER TO TO INSTALLATION INSTRUCTIONS, FOR WIRING THE COMMON.
AC INPUT WIRING ON ILLUSTRATION 3 LAMPS OPERATION SECTION FOR REFER TO AC INPUT WIRING
OF INSTALLATION MANUAL FOR PROPER VARIOUS OPTIONS ON ILLUSTRATION 3 OF
INPUT CIRCUIT WIRING. INSTALLATION MANUAL.
TEST ACCESSORY LEADS-
DO NOT MATE CONNECTOR UNTIL REFER TO INSTALLATION 6 CAP UNUSED LEADS.
INSTALLATION IS COMPLETE AND INSTRUCTIONS FOR PROPER
AC POWER IS SUPPLIED. POLARITY WIRING.

1LEO_80_E

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ1 QQ1
ONE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
BLUE BLUE/WHT
UNSWITCHED
WHITE
A.C. RED/WHT EMERGENCY BLK (120V)
RED
RED
Ballast RED BALLAST WHITE COMMON
YELLOW WHT/BLK

RED/BLK (+)
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
*LAMP CONNECTOR
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

TBTS / CHARGE
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
COMMON INDICATOR FOR PROPER POLARITY WIRING.
*AC / EMERGENCY

1LRSB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ2
TWO LAMP RAPID START BALLAST
QQ2
SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE BLUE/WHT
UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW RED
YELLOW Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
LAMP SELECT PROPER VOLTAGE
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
RED OR
*LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
TBTS / CHARGE INSTRUCTIONS FOR PROPER
INDICATOR POLARITY WIRING.
COMMON
*AC / EMERGENCY

2LRSB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ3 QQ3
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
ORG (277V)
WHITE BLUE BLUE/WHT UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW RED
YELLOW Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

TEST ACCESSORY LEADS-
TBTS/CHARGE REFER TO INSTALLATION
INDICATOR INSTRUCTIONS FOR PROPER
COMMON POLARITY WIRING.
*AC / EMERGENCY

2LRSB_2_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ4 QQ4
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
ORG (277V)
WHITE BLUE/WHT BLUE/WHT
UNSWITCHED
BLUE
BLUE
A.C. RED/WHT EMERGENCY BLK (120V)
RED
YELLOW Ballast RED
RED BALLAST WHITE COMMON
YELLOW YELLOW WHT/BLK

RED/BLK (+)
LAMP
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
3 AC POWER IS SUPPLIED.
3 TEST ACCESSORY LEADS-
TBTS / CHARGE REFER TO INSTALLATION
INDICATOR INSTRUCTIONS FOR PROPER
COMMON POLARITY WIRING.
*AC / EMERGENCY

3LRSB_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ5 QQ5
ONE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE ORG (277V)
BLACK BLUE/WHT
UNSWITCHED
WHITE A.C. RED/WHT EMERGENCY BLK (120V)
RED Ballast RED BALLAST WHITE COMMON
YELLOW WHT/BLK

RED/BLK (+)
SELECT PROPER VOLTAGE
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
RED OR
*LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
TBTS / CHARGE TEST ACCESSORY LEADS-
COMMON INDICATOR REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

1LISB_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ6 QQ6
TWO LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE ORG (277V)
BLUE/WHT
UNSWITCHED
BLACK A.C. RED/WHT EMERGENCY BLK (120V)
WHITE Ballast RED RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
LAMP
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
CONNECT BLU/WHT AND RED/WHT
TBTS / CHARGE WIRES TOGETHER.
INDICATOR TEST ACCESSORY LEADS-
COMMON REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LISB_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ7 QQ7
TWO LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE/WHT UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
RED Ballast BLUE
RED BALLAST WHITE COMMON
YELLOW WHT/BLK

RED/BLK (+)
LAMP
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

CONNECT BLU/WHT AND RED/WHT
TBTS / CHARGE WIRES TOGETHER
COMMON
INDICATOR TEST ACCESSORY LEADS-
REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LISB_2_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ8 QQ8
THREE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE/WHT UNSWITCHED
A.C. BLUE RED/WHT EMERGENCY BLK (120V)
RED Ballast BLUE
RED BALLAST WHITE COMMON
YELLOW WHT/BLK

RED/BLK (+)
LAMP SELECT PROPER VOLTAGE
UNIT

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
TBTS / CHARGE
INDICATOR TEST ACCESSORY LEADS-
COMMON REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
*AC / EMERGENCY POLARITY WIRING.

3LISB_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ9 QQ9
FOUR LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE BLUE/WHT UNSWITCHED
YELLOW
A.C. RED RED/WHT EMERGENCY BLK (120V)
YELLOW
Ballast RED
RED BALLAST WHITE COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
LAMP

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*LAMP AC POWER IS SUPPLIED.

CONNECT BLU/WHT AND RED/WHT
TBTS / CHARGE WIRES TOGETHER

COMMON
INDICATOR TEST ACCESSORY LEADS-
REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

4LISB_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ10 QQ10
ONE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
RED BLUE
ORG (277V)
BLACK BLUE/WHT UNSWITCHED
WHITE A.C. RED RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK(+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

CONNECT BLU/WHT AND RED/WHT
TBTS / CHARGE WIRES TOGETHER.
INDICATOR
COMMON TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
*AC / EMERGENCY FOR PROPER POLARITY WIRING.

1LISB_ISL_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ11 QQ11
ONE LAMP INSTANT START FULLHAM BALLAST

SWITCHED OR
UNSWITCHED
LINE
RED BLUE
ORG (277V)
BLACK BLUE/WHT UNSWITCHED
WHITE A.C. RED
RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR

RED OR
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

CONNECT BLU/WHT AND RED/WHT
TBTS / CHARGE WIRES TOGETHER.
COMMON INDICATOR TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

1LISFB_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ12 QQ12
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK YELLOW BLUE LINE
ORG (277V)
WHITE YELLOW BLUE/WHT UNSWITCHED
BLU/WHT BROWN RED/WHT EMERGENCY BLK (120V)
BLU/WHT
ORG A.C. BROWN
BLUE
RED
YELLOW
BALLAST WHITE
COMMON
ORG
Ballast BLUE WHT/BLK
RED

RED/BLK (+)
UNIT

WHT/RED
RED SELECT PROPER VOLTAGE

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP
TEST ACCESSORY LEADS-
TBTS / CHARGE REFER TO INSTALLATION
INDICATOR INSTRUCTIONS FOR PROPER
*LAMP POLARITY WIRING.
COMMON
*AC / EMERGENCY

4LRSB_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ13 QQ13
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED BLUE LINE
WHITE RED BLUE/WHT ORG (277V)
BLUE ORG RED/WHT UNSWITCHED
BLUE
EMERGENCY
ORG BLK (120V)
BLU/WHT A.C. YELLOW
RED
YELLOW
BALLAST WHITE
COMMON
BLU/WHT
Ballast YELLOW WHT/BLK
BROWN

RED/BLK (+)
SELECT PROPER VOLTAGE

WHT/RED
BROWN UNIT LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP
TEST ACCESSORY LEADS-
*LAMP REFER TO INSTALLATION
TBTS / CHARGE INSTRUCTIONS FOR PROPER
INDICATOR POLARITY WIRING.
COMMON
*AC / EMERGENCY

3LRSB_ISL_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ14 QQ14
TWO LAMP INSTANT START FULLHAM BALLAST

SWITCHED OR
UNSWITCHED
LINE
RED BLUE
ORG (277V)
BLACK RED BLUE/WHT UNSWITCHED
WHITE A.C. RED/WHT EMERGENCY BLK (120V)
RED
YELLOW Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
LAMP CONNECTOR

RED OR
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
CONNECT BLU/WHT AND RED/WHT
TBTS / CHARGE WIRES TOGETHER
INDICATOR
COMMON
*AC / EMERGENCY

2LISFB_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ15 QQ15
SUNPARK TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
ORG (277V)
WHITE BLUE BLUE/WHT UNSWITCHED
BLUE A.C. RED RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast RED
RED BALLAST WHITE
COMMON
RED YELLOW WHT/BLK

RED/BLK (+)
LAMP UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER
TBTS/CHARGE TO INSTALLATION INSTRUCTIONS
INDICATOR FOR PROPER POLARITY WIRING.
COMMON
*AC / EMERGENCY

2LRSB_SP_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ16 QQ16
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK YELLOW BLUE LINE
ORG (277V)
WHITE YELLOW BLUE/WHT UNSWITCHED
BLU/WHT BROWN RED/WHT EMERGENCY BLK (120V)
BLU/WHT
ORG A.C. BROWN
BLUE
RED
YELLOW
BALLAST WHITE
COMMON
ORG
Ballast BLUE WHT/BLK
RED

RED/BLK (+)
UNIT

WHT/RED
RED SELECT PROPER VOLTAGE

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP
TEST ACCESSORY LEADS-
TBTS / CHARGE REFER TO INSTALLATION
INDICATOR INSTRUCTIONS FOR PROPER
*LAMP POLARITY WIRING.
COMMON
*AC / EMERGENCY

4LRSB_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ17 QQ17
TWO LAMP RAPID START BALLAST WITH DUAL EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLUE ORG (277V)
BLUE/WHT
UNSWITCHED
RED/WHT EMERGENCY BLK (120V)
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
BLACK BLUE

A.C.
BLUE SELECT PROPER VOLTAGE

RED/BLK (+)
WHITE
UNIT

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
YELLOW
YELLOW
Ballast RED
RED
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
TBTS / CHARGE AC POWER IS SUPPLIED.
*LAMP INDICATOR
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
*LAMP INSTRUCTIONS FOR PROPER
POLARITY WIRING.
BLUE ORG (277V)
BLUE/WHT
RED/WHT EMERGENCY BLK (120V)
RED BALLAST WHITE
YELLOW WHT/BLK

RED/BLK (+)

WHT/RED

UNIT
RED OR
CONNECTOR

TBTS / CHARGE
INDICATOR
COMMON
*AC / EMERGENCY

2LRSBDUAL_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ18 QQ18
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE LINE
WHITE BLUE BLUE/WHT ORG (277V)
ORG RED RED/WHT
UNSWITCHED
ORG EMERGENCY
BLU/WHT A.C. RED
BROWN
RED BLK (120V)
YELLOW BALLAST WHITE
BLU/WHT
Ballast BROWN
WHT/BLK
COMMON
YELLOW
YELLOW SELECT PROPER VOLTAGE

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP TEST ACCESSORY LEADS-


REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
*LAMP TBTS / CHARGE POLARITY WIRING.
INDICATOR
COMMON
*AC / EMERGENCY

4LRSB_ISL_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ19 QQ19
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE BLUE/WHT
UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW RED
YELLOW Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

*LAMP TEST ACCESSORY LEADS-


TBTS / CHARGE REFER TO INSTALLATION
INDICATOR INSTRUCTIONS FOR PROPER
POLARITY WIRING.
COMMON
*AC / EMERGENCY

2BXLRSB_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ20 QQ20
TWO LAMP RAPID START BALLAST WITH 347V CONVERTER

SWITCHED OR
UNSWITCHED LINE
BLACK BLUE BLUE ORG (277V)

WHITE BLUE BLUE/WHT 347 VOLT
UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
CONVERTER
YELLOW RED
YELLOW Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
LAMP
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

TEST ACCESSORY LEADS-
REFER TO INSTALLATION
TBTS / CHARGE INSTRUCTIONS FOR PROPER
INDICATOR POLARITY WIRING.
COMMON
*AC / EMERGENCY

2LRSB_ISL_347

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ21 QQ21
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE LINE
WHITE BLUE BLUE/WHT ORG (277V)
YELLOW RED RED/WHT
UNSWITCHED
YELLOW EMERGENCY
BLU/WHT A.C. RED
BROWN
RED BLK (120V)
YELLOW BALLAST WHITE
BLU/WHT
Ballast BROWN
WHT/BLK
COMMON
ORANGE
ORANGE SELECT PROPER VOLTAGE

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP TEST ACCESSORY LEADS-


REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
*LAMP TBTS / CHARGE POLARITY WIRING.
INDICATOR
COMMON
*AC / EMERGENCY

4LRSB_ISL_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ22 QQ22
FOUR LAMP RAPID START BALLAST WITH THREE LAMPS ONLY

SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
WHITE ORG (277V)
BLUE/WHT BLUE/WHT
YELLOW/BLK EMERGENCY UNSWITCHED
RED/WHT RED/WHT
BRN/WHT BLK (120V)
BROWN A.C. RED/WHT
BLUE
RED
YELLOW
BALLAST WHITE COMMON
WHT/BLK
YELLOW
Ballast BLUE
RED
UNIT SELECT PROPER VOLTAGE
RED CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
LAMP TBTS / CHARGE INSTALLATION IS COMPLETE AND
INDICATOR AC POWER IS SUPPLIED.
LAMP CONNECT WIRES TOGETHER.
*LAMP

COMMON
*AC / EMERGENCY

4LRSB_ISL_4

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ23 QQ23
FOUR LAMP INSTANT START FULHAM BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
WHITE RED BLUE/WHT UNSWITCHED
YELLOW
A.C. RED RED/WHT EMERGENCY BLK (120V)
Ballast RED
RED BALLAST WHITE COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
LAMP

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*LAMP AC POWER IS SUPPLIED.

CONNECT BLU/WHT AND RED/WHT
TBTS / CHARGE WIRES TOGETHER

COMMON
INDICATOR TEST ACCESSORY LEADS-
REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

4LISFB_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ24 QQ24
TWO BIAX LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE BLUE/WHT
UNSWITCHED
BROWN A.C. RED/WHT EMERGENCY BLK (120V)
RED
ORG
YELLOW
Ballast RED
RED BALLAST WHITE COMMON
YELLOW WHT/BLK

RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
TEST ACCESSORY LEADS-
*LAMP REFER TO INSTALLATION
TBTS / CHARGE INSTRUCTIONS FOR PROPER
INDICATOR POLARITY WIRING.
COMMON
*AC / EMERGENCY

2BXLRSB_2_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ25 QQ25
TWO LAMP FULHAM INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
RED BLUE
ORG (277V)
BLACK BLUE/WHT UNSWITCHED
WHITE A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
LAMP CONNECTOR

RED OR
LEAD. CAP UNUSED LEAD.
*LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
CONNECT BLU/WHT AND RED/WHT
TBTS / CHARGE WIRES TOGETHER.

COMMON
INDICATOR TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
*AC / EMERGENCY FOR PROPER POLARITY WIRING.

2LISB_3_F_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ26 QQ26
TWO BIAX LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
UNSWITCHED
WHITE A.C. BLUE
BLUE/WHT
RED/WHT EMERGENCY BLK (120V)
RED Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

*LAMP CONNECT BLU/WHT AND RED/WHT
TBTS / CHARGE WIRES TOGETHER.
INDICATOR
TEST ACCESSORY LEADS-REFER
COMMON TO INSTALLATION INSTRUCTIONS
*AC / EMERGENCY FOR PROPER POLARITY WIRING.

2LISBX_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ27 QQ27
ONE LAMP EMERGENCY ONLY

BLUE ORG (277V)


UNSWITCHED


BLUE/WHT
RED/WHT EMERGENCY BLK (120V)
RED WHITE
BALLAST COMMON
YELLOW WHT/BLK


RED/BLK (+)
UNIT

WHT/RED
*LAMP SELECT PROPER VOLTAGE

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*AC / EMERGENCY AC POWER IS SUPPLIED.
CAP UNUSED LEADS.
TBTS / CHARGE
INDICATOR TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LEO_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ28 QQ28
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED BLUE ORG (277V) LINE
WHITE RED BLUE/WHT
UNSWITCHED
YELLOW A.C. BLUE/WHT RED/WHT EMERGENCY BLK (120V)
YELLOW
BLUE Ballast BLUE/WHT
BLUE
RED BALLAST WHITE
COMMON
BLUE YELLOW WHT/BLK
BLUE

RED/BLK (+)
LAMP UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

*LAMP TEST ACCESSORY LEADS-REFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS
INDICATOR FOR PROPER POLARITY WIRING.
COMMON
*AC / EMERGENCY

4LRSB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ29 QQ29
ONE LAMP OSRAM PROGRAM START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
RED BLUE/WHT
UNSWITCHED
WHITE
A.C. RED/WHT EMERGENCY BLK (120V)
BLUE
BLUE
Ballast RED BALLAST WHITE COMMON
YELLOW WHT/BLK

RED/BLK (+)
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
*LAMP CONNECTOR
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

TBTS / CHARGE
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
COMMON INDICATOR FOR PROPER POLARITY WIRING.
*AC / EMERGENCY

1LOSB

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ30 QQ30
TWO LAMP OSRAM PROGRAM START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
ORG (277V)
WHITE RED BLUE/WHT UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW BLUE
YELLOW Ballast BLUE
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

TEST ACCESSORY LEADS-
TBTS/CHARGE REFER TO INSTALLATION
INDICATOR INSTRUCTIONS FOR PROPER
COMMON POLARITY WIRING.
*AC / EMERGENCY

2LOSB_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ31 QQ31
THREE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLU/WHT BLUE ORG (277V)
WHITE BLUE/WHT
UNSWITCHED
RED/WHT
A.C. RED RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast BLUE
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
YEL/BLK

RED/BLK (+)
SELECT PROPER VOLTAGE

VIOLET

VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
LAMP TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
*LAMP TBTS/CHARGE VARIOUS OPTIONS
INDICATOR
COMMON
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LISB_48ST_3_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ32 QQ32
TWO LAMP INSTANT START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLUE ORG (277V)
BLUE/WHT
UNSWITCHED
RED/WHT EMERGENCY BLK (120V)
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
BLACK BLUE
SELECT PROPER VOLTAGE

RED/BLK (+)
WHITE
A.C. UNIT

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
BLUE
RED
Ballast CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
TBTS / CHARGE AC POWER IS SUPPLIED.
*LAMP INDICATOR
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
*LAMP INSTRUCTIONS FOR PROPER
POLARITY WIRING.
BLUE ORG (277V)
BLUE/WHT
RED/WHT EMERGENCY BLK (120V)
RED BALLAST WHITE
YELLOW WHT/BLK

RED/BLK (+)

WHT/RED

UNIT
RED OR
CONNECTOR

TBTS / CHARGE
INDICATOR
COMMON
*AC / EMERGENCY

2LISBDUAL_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ33 QQ33
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE LINE
WHITE BLUE BLUE/WHT ORG (277V)
YELLOW RED RED/WHT
UNSWITCHED
YELLOW EMERGENCY
BLU/WHT A.C. RED
BROWN
RED BLK (120V)
YELLOW BALLAST WHITE
BLU/WHT
Ballast BROWN
WHT/BLK
COMMON
ORANGE
ORANGE SELECT PROPER VOLTAGE

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP TEST ACCESSORY LEADS-


REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
*LAMP TBTS / CHARGE POLARITY WIRING.
INDICATOR
COMMON
*AC / EMERGENCY

4LRSB_ISL_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ34 QQ34
TWO LAMP OSRAM PROGRAM START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
ORG (277V)
WHITE RED BLUE/WHT UNSWITCHED
A.C. BLUE RED/WHT EMERGENCY BLK (120V)
YELLOW
YELLOW Ballast BLUE
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
LAMP
UNIT

WHT/RED
CONNECTOR SELECT PROPER VOLTAGE

RED OR
*LAMP
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
TBTS / CHARGE TEST ACCESSORY LEADS-REFER
INDICATOR TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.
COMMON
*AC / EMERGENCY

2LOSB_D_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ35 QQ35
THREE LAMP OSRAM PROGRAM START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
ORG (277V)
WHITE BLUE/WHT BLUE/WHT UNSWITCHED
RED
RED
A.C. RED/WHT EMERGENCY BLK (120V)
BLUE
YELLOW Ballast BLUE
RED BALLAST WHITE COMMON
YELLOW YELLOW WHT/BLK
LAMP

RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR

RED OR
LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

TEST ACCESSORY LEADS-REFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS
INDICATOR FOR PROPER POLARITY WIRING.
COMMON
*AC / EMERGENCY

3LOSB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ36 QQ36
INSTALACION CON UNA SOLO LAMPARA DE ENCENDIDO INSTANTANEO (INSTANT START LAMP)

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
AZUL AZUL NARANJA (277V)
NEGRO AZUL/BLANCO LINEA SIN
INTERRUPTOR
BLANCO
BALASTRA ROJO/BLANCO BALASTRA DE NEGRO (120V)
ROJO ROJO EMERGENCIA BLANCO
NEUTRAL
AMARILLO BLANCO/NEGRO

ROJO/NEGRO(+)
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
CONNECTORES APROPIADO. CANCELAR CABLE
*LAMPARA DE ENCENDIDO NO USADO.
DE LA UNIDAD
NO ACOPLE LOS CONECTORES DE ENCENDIDO

ROJO O
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
CONECTAR LOS SIGUIENTES CABLES JUNTOS
AZUL/BLANCO Y ROJO/BLANCO.

INTERUPTOR DE PARA LA INSTALACION DEL INTERRUPTOR


DE PRUEBA OBSERVE LAS INSTRUCCIONES
PRUEBA E INDICADOR CONTENIDAS EN EL MANUAL DE INSTALCION.
DE CARGA OBSERVE POLARIDAD DEL ALAMBRADO.
NEUTRAL
*LAMPARA ENCENDIDO
INSTANTANEO OPERADA
EN FUNCION REGULAR (C.A.)
O EN EMERGENCIA

1LISB_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ37 QQ37
INSTALACION CON UNA SOLA LAMPARA DE ENCENDIDO RAPIDO (RAPID START LAMP)

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL AZUL
NARANJA (277V)
BLANCO AZUL AZUL/BLANCO LINEA SIN
ROJO BLANCO BALASTRA DE INTERRUPTOR
ROJO BALASTRA NEGRO (120V)
ROJO EMERGENCIA BLANCO
ROJO NEUTRAL
AMARILLO BLANCO/NEGRO

ROJO/NEGRO(+)
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
*LAMPARA CONNECTORES APROPIADO. CANCELAR CABLE
DE ENCENDIDO NO USADO.
DE LA UNIDAD
NO ACOPLE LOS CONECTORES DE ENCENDIDO

ROJO O
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
PARA LA INSTALACION DEL INTERRUPTOR
DE PRUEBA OBSERVE LAS INSTRUCCIONES
CONTENIDAS EN EL MANUAL DE INSTALCION.
INTERUPTOR DE OBSERVE POLARIDAD DEL ALAMBRADO.
PRUEBA E INDICADOR
NEUTRAL DE CARGA
*LAMPARA ENCENDIDO
RAPIDO OPERADA EN
FUNCION REGULAR (C.A.)
O EN EMERGENCIA

1LRSB_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ38 QQ38
INSTALACION CON DOS LAMPARAS DE ENCENDIDO INSTANTANEO

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL AZUL NARANJA (277V)
BLANCO AZUL/BLANCO LINEA SIN
BALASTRA ROJO/BLANCO BALASTRA DE NEGRO (120V)
INTERRUPTOR
ROJO EMERGENCIA BLANCO
ROJO AZUL NEUTRAL
AMARILLO
BLANCO/NEGRO
LAMPARA

ROJO/NEGRO(+)
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
CONNECTORES
*LAMPARA DE ENCENDIDO APROPIADO. CANCELAR CABLE
DE LA UNIDAD NO USADO.
NO ACOPLE LOS CONECTORES DE ENCENDIDO

ROJO O
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
CONECTAR LOS SIGUIENTES CABLES JUNTOS
AZUL/BLANCO Y ROJO/BLANCO.
PARA LA INSTALACION DEL INTERRUPTOR
DE PRUEBA OBSERVE LAS INSTRUCCIONES
INTERUPTOR DE CONTENIDAS EN EL MANUAL DE INSTALCION.
PRUEBA E INDICADOR OBSERVE POLARIDAD DEL ALAMBRADO.
NEUTRAL DE CARGA
*LAMPARA ENCENDIDO
INSTANTANEO OPERADA
EN FUNCION REGULAR (C.A.)
O EN EMERGENCIA

2LISB_2_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ39 QQ39
INSTALACION CON DOS LAMPARAS DE ENCENDIDO RAPIDO

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO ROJO AZUL
NARANJA (277V)
BLANCO ROJO AZUL/BLANCO LINEA SIN
ROJO/BLANCO BALASTRA DE INTERRUPTOR
AMARILLO BALASTRA AZUL NEGRO (120V)
ROJO EMERGENCIA BLANCO
AMARILLO AZUL NEUTRAL
AMARILLO BLANCO/NEGRO
LAMPARA

ROJO/NEGRO(+)
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
CONNECTORES APROPIADO. CANCELAR CABLE
*LAMPARA DE ENCENDIDO NO USADO.
DE LA UNIDAD

ROJO O
NO ACOPLE LOS CONECTORES DE ENCENDIDO
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
PARA LA INSTALACION DEL INTERRUPTOR
DE PRUEBA OBSERVE LAS INSTRUCCIONES
CONTENIDAS EN EL MANUAL DE INSTALCION.
INTERUPTOR DE OBSERVE POLARIDAD DEL ALAMBRADO.
PRUEBA E INDICADOR
DE CARGA
NEUTRAL
*LAMPARA ENCENDIDO
RAPIDO OPERADA EN
FUNCION REGULAR (C.A.)
O EN EMERGENCIA

2LRSB_D_5_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ40 QQ40
INSTALACION CON UNA SOLA LAMPARA DE ENCENDIDO RAPIDO

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL AZUL NARANJA (277V)
BLANCO AZUL AZUL/BLANCO LINEA SIN
INTERRUPTOR
ROJO/BLANCO BALASTRA DE NEGRO (120V)
AMARILLO BALASTRA ROJO
ROJO EMERGENCIA BLANCO
AMARILLO ROJO NEUTRAL
AMARILLO BLANCO/NEGRO
LAMPARA

ROJO/NEGRO(+)
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
CONNECTORES
*LAMPARA DE ENCENDIDO APROPIADO. CANCELAR CABLE
DE LA UNIDAD NO USADO.

ROJO O
NO ACOPLE LOS CONECTORES DE ENCENDIDO
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
PARA LA INSTALACION DEL INTERRUPTOR
DE PRUEBA OBSERVE LAS INSTRUCCIONES
CONTENIDAS EN EL MANUAL DE INSTALCION.
INTERUPTOR DE OBSERVE POLARIDAD DEL ALAMBRADO.
PRUEBA E INDICADOR
NEUTRAL DE CARGA
*LAMPARA ENCENDIDO
RAPIDO OPERADA EN
FUNCION REGULAR (C.A.)
O EN EMERGENCIA

2LRSB_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ41 QQ41
INSTALACION CON TRES LAMPARAS DE ENCENDIDO INSTANTANEO

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL AZUL
NARANJA (277V)
BLANCO AZUL/BLANCO LINEA SIN
INTERRUPTOR
BALASTRA AZUL ROJO/BLANCO BALASTRA DE NEGRO (120V)
ROJO EMERGENCIA BLANCO
ROJO AZUL NEUTRAL
AMARILLO BLANCO/NEGRO
LAMPARA

ROJO/NEGRO(+)
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
CONNECTORES
LAMPARA DE ENCENDIDO APROPIADO. CANCELAR CABLE
DE LA UNIDAD NO USADO.

ROJO O
*LAMPARA NO ACOPLE LOS CONECTORES DE ENCENDIDO
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
CONECTAR LOS SIGUIENTES CABLES JUNTOS
AZUL/BLANCO Y ROJO/BLANCO.
INTERUPTOR DE PARA LA INSTALACION DEL INTERRUPTOR
PRUEBA E INDICADOR DE PRUEBA OBSERVE LAS INSTRUCCIONES
DE CARGA CONTENIDAS EN EL MANUAL DE INSTALCION.
NEUTRAL OBSERVE POLARIDAD DEL ALAMBRADO.
*LAMPARA ENCENDIDO
INSTANTANEO OPERADA
EN FUNCION REGULAR (C.A.)
O EN EMERGENCIA

3LISB_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ42 QQ42
INSTALACION CON TRES LAMPARAS DE ENCENDIDO RAPIDO

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL/BLANCO AZUL
NARANJA (277V)
BLANCO AZUL/BLANCO AZU/BLANCO LINEA SIN
AZUL INTERRUPTOR
ROJO/BLANCO BALASTRA DE
AZUL BALASTRA ROJO NEGRO (120V)
AMARILLO ROJO EMERGENCIA BLANCO
NEUTRAL
ROJO
AMARILLO AMARILLO BLANCO/NEGRO
LAMPARA

ROJO/NEGRO(+)
SELECCIONAR CABLE DE VOLTAGE
CONNECTORES

BLANCO/ROJO
APROPIADO. CANCELAR CABLE
*LAMPARA DE ENCENDIDO NO USADO.
DE LA UNIDAD
LAMPARA NO ACOPLE LOS CONECTORES DE ENCENDIDO

ROJO O
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
PARA LA INSTALACION DEL INTERRUPTOR
DE PRUEBA OBSERVE LAS INSTRUCCIONES
CONTENIDAS EN EL MANUAL DE INSTALCION.
INTERUPTOR DE OBSERVE POLARIDAD DEL ALAMBRADO.
PRUEBA E INDICADOR
DE CARGA
NEUTRAL
*LAMPARA ENCENDIDO
RAPIDO OPERADA EN
FUNCION REGULAR (C.A.)
O EN EMERGENCIA

3LRSB_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ43 QQ43
INSTALACION CON CUATRO LAMPARAS DE ENCENDIDO INSTANTANEO

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL AZUL
NARANJA (277V)
BLANCO AZUL AZUL/BLANCO LINEA SIN
INTERRUPTOR
AMARILLO BALASTRA ROJO

ROJO/BLANCO BALASTRA DE NEGRO (120V)
ROJO EMERGENCIA BLANCO
AMARILLO ROJO NEUTRAL
AMARILLO BLANCO/NEGRO
LAMPARA

ROJO/NEGRO(+)
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
CONNECTORES APROPIADO. CANCELAR CABLE
LAMPARA DE ENCENDIDO NO USADO.
DE LA UNIDAD
LAMPARA NO ACOPLE LOS CONECTORES DE ENCENDIDO

ROJO O
DE LA UNIDAD HASTA QUE TODA LA
*LAMPARA INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.

CONECTAR LOS SIGUIENTES CABLES JUNTOS


AZUL/BLANCO Y ROJO/BLANCO.
PARA LA INSTALACION DEL INTERRUPTOR
INTERUPTOR DE DE PRUEBA OBSERVE LAS INSTRUCCIONES
PRUEBA E INDICADOR CONTENIDAS EN EL MANUAL DE INSTALCION.
NEUTRAL DE CARGA OBSERVE POLARIDAD DEL ALAMBRADO.
*LAMPARA ENCENDIDO
INSTANTANEO OPERADA
EN FUNCION REGULAR (C.A.)
O EN EMERGENCIA

4LISB_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ44 QQ44
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK YELLOW BLUE LINE
WHITE YELLOW BLUE/WHT ORG (277V)
BLU/WHT BROWN RED/WHT
UNSWITCHED
BLU/WHT EMERGENCY
BLUE A.C. BROWN RED BLK (120V)
YELLOW BALLAST WHITE
BLUE
Ballast RED
WHT/BLK
COMMON
RED
SELECT PROPER VOLTAGE

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.
*LAMP TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
TBTS / CHARGE POLARITY WIRING.
INDICATOR
COMMON
*AC / EMERGENCY

3LRSB_ISL_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ45 QQ45
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BROWN BLUE LINE
WHITE BROWN BLUE/WHT ORG (277V)
YELLOW RED/WHT
UNSWITCHED
YELLOW BLUE
EMERGENCY
ORG A.C. BLUE RED BLK (120V)
YELLOW BALLAST WHITE
ORG
Ballast RED WHT/BLK
COMMON

RED
SELECT PROPER VOLTAGE

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

*LAMP TEST ACCESSORY LEADS-


REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
TBTS / CHARGE POLARITY WIRING.
INDICATOR
COMMON
*AC / EMERGENCY

3LRSB_ISL_4

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ46 QQ46
TWO BIAX LAMP RAPID START BALLAST

PURPLE
(+)
GREY (-)
BLACK SWITCHED OR
UNSWITCHED
LINE
WHITE BLUE BLUE ORG (277V)
YELLOW BLUE BLUE/WHT
UNSWITCHED
YELLOW A.C. RED/WHT EMERGENCY BLK (120V)
RED
BROWN
BROWN
Ballast RED
RED BALLAST WHITE COMMON
YELLOW WHT/BLK

RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
TEST ACCESSORY LEADS-
*LAMP REFER TO INSTALLATION
TBTS / CHARGE INSTRUCTIONS FOR PROPER
INDICATOR POLARITY WIRING.
COMMON
*AC / EMERGENCY

2BXLRSB_3_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ47 QQ47
FOUR LAMP RAPID START BALLAST WITH THREE LAMPS ONLY

SWITCHED OR
UNSWITCHED
BLACK BROWN BLUE LINE
WHITE BROWN BLUE/WHT ORG (277V)
YELLOW RED/WHT
UNSWITCHED
BLK/WHT YELLOW EMERGENCY
BLK/WHT A.C. BLUE
RED BLK (120V)
YELLOW BALLAST WHITE
ORG Ballast BLUE
WHT/BLK
COMMON

ORG RED
RED SELECT PROPER VOLTAGE

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

*LAMP TEST ACCESSORY LEADS-


REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
TBTS / CHARGE POLARITY WIRING.
INDICATOR
COMMON CONNECT WIRES TOGETHER.
*AC / EMERGENCY

4LRSB_ISL_5

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ48 QQ48
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK LINE
BLUE BLUE
WHITE ORG (277V)
BLUE BLUE/WHT UNSWITCHED
RED
RED
A.C. YELLOW RED/WHT EMERGENCY BLK (120V)
BRN Ballast YELLOW RED BALLAST WHITE
COMMON
BRN YELLOW WHT/BLK
LAMP

RED/BLK (+)
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

TEST ACCESSORY LEADS-
TBTS/CHARGE REFER TO INSTALLATION
INDICATOR INSTRUCTIONS FOR PROPER
COMMON POLARITY WIRING.
*AC / EMERGENCY

2LRSB_3_ISL

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ49 QQ49
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE LINE
ORG (277V)
WHITE BLUE BLUE/WHT
UNSWITCHED
BLU/WHT
BLU/WHT
A.C. RED/WHT EMERGENCY BLK (120V)
RED
YELLOW Ballast RED
RED BALLAST WHITE COMMON
YELLOW YELLOW WHT/BLK

RED/BLK (+)
LAMP
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
3 AC POWER IS SUPPLIED.
3 TEST ACCESSORY LEADS-
TBTS / CHARGE REFER TO INSTALLATION
INDICATOR INSTRUCTIONS FOR PROPER
COMMON POLARITY WIRING.
*AC / EMERGENCY

3LRSB_ISL_5

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ50 QQ50
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED BLUE ORG (277V) LINE
WHITE RED BLUE/WHT
UNSWITCHED
YELLOW A.C. BLUE/WHT RED/WHT EMERGENCY BLK (120V)
YELLOW
BROWN Ballast BLUE/WHT
BLUE
RED BALLAST WHITE
COMMON
BROWN YELLOW WHT/BLK
BLUE

RED/BLK (+)
LAMP UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

*LAMP TEST ACCESSORY LEADS-REFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS
INDICATOR FOR PROPER POLARITY WIRING.
COMMON
*AC / EMERGENCY

4LRSB_6_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ51 QQ51
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE LINE
ORG (277V)
WHITE BLUE BLUE/WHT UNSWITCHED
BLU/WHT RED/WHT
YELLOW EMERGENCY BLK (120V)
BLU/WHT
RED/WHT A.C. YEL/BLK
RED
YELLOW
BALLAST WHITE
COMMON
RED/WHT
BLU/BLK
Ballast YELLOW WHT/BLK
RED

RED/BLK (+)
RED/BLK
UNIT

WHT/RED
RED SELECT PROPER VOLTAGE

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP TEST ACCESSORY LEADS-


TBTS / CHARGE REFER TO INSTALLATION
INDICATOR INSTRUCTIONS FOR PROPER
*LAMP POLARITY WIRING.
COMMON
*AC / EMERGENCY

4LRSB_ISL

NOTES
For ballast #: OSRAM SYLVANIA QTP 4x32T8/UNV DIM-TCL

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


QQ52 QQ52
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK LINE
WHITE RED BLUE ORG (277V)
UNSWITCHED
YELLOW/BLK A.C. RED BLUE/WHT
BLK (120V)
EMERGENCY
YELLOW Ballast BLUE RED/WHT
RED WHITE
YELLOW BLUE BALLAST COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

TEST ACCESSORY LEADS-REFER
TBTS/ TO INSTALLATION INSTRUCTIONS
CHARGE INDICATOR FOR PROPER POLARITY WIRING.
COMMON
*AC / EMERGENCY
NOTE:
DIMMING WIRE IS NOT AFFECTED BY
THE EM BALLAST

2LRSB_420_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V1 V1
ONE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY
UNSWITCHED
RED
RED Ballast RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

RED/BLK (+)

BRN/WHT
BROWN
VIOLET
SELECT PROPER VOLTAGE
UNIT

WHT/RED
*LAMP LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LRSB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V2 V2
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY UNSWITCHED
YELLOW RED
YELLOW Ballast RED
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
LAMP

RED/BLK (+)

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
*LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
CHARGE LAMP OPERATION SECTION FOR
COMMON INDICATOR VARIOUS OPTIONS.
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LRSB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V3 V3
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
WHITE BLUE/WHT BLUE/WHT ORG (277V)
BLUE
BLUE
A.C. RED/WHT EMERGENCY UNSWITCHED
RED
YELLOW Ballast RED
RED BALLAST BLK (120V)
YELLOW YELLOW WHITE
COMMON

RED/BLK (+)

BRN/WHT
LAMP

BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
*LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
CHARGE LAMP OPERATION SECTION FOR
COMMON INDICATOR VARIOUS OPTIONS.
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LRSB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V4 V4
ONE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE
BLACK BLUE/WHT ORG (277V)
WHITE A.C. RED/WHT EMERGENCY
UNSWITCHED
RED Ballast RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

RED/BLK (+)

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
*LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION ISNTRUCTIONS
FOR PROPER POLARITY WIRING.

1LISB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V5 V5
TWO LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE
BLUE/WHT ORG (277V)
BLACK A.C. RED/WHT EMERGENCY
UNSWITCHED
WHITE Ballast RED RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

RED/BLK (+)

BRN/WHT
SELECT PROPER VOLTAGE

BROWN
VIOLET
LAMP
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
RED OR
*LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LISB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V6 V6
TWO LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY
UNSWITCHED
RED Ballast BLUE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
LAMP

BRN/WHT
RED/BLK (+)

BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMP OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LISB_160_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V7 V7
THREE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE/WHT ORG (277V)
A.C. BLUE RED/WHT EMERGENCY UNSWITCHED
RED Ballast BLUE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
LAMP

RED/BLK (+)

BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
CHARGE LAMP OPERATION SECTION FOR
COMMON INDICATOR VARIOUS OPTIONS.
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LISB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V8 V8
FOUR LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE BLUE/WHT ORG (277V)
YELLOW
A.C. RED RED/WHT EMERGENCY
UNSWITCHED
YELLOW
Ballast RED
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
LAMP SELECT PROPER VOLTAGE

RED/BLK (+)

BRN/WHT
BROWN
VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
LAMP INSTALLATION IS COMPLETE AND
*LAMP
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
CHARGE VARIOUS OPTIONS.
COMMON INDICATOR
*AC / EMERGENCY
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

4LISB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V9 V9
TWO LAMP SERIES LEAD BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE/WHT ORG (277V)
BRN OR YEL
A.C. RED/WHT EMERGENCY UNSWITCHED
BRN OR YEL Ballast RED
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
LAMP

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
CHARGE INSTALLATION IS COMPLETE AND
COMMON INDICATOR/LPTS AC POWER IS SUPPLIED.

*AC / EMERGENCY
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

2LSL_2LEO_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V10 V10
TWO LAMP INSTART START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE LINE
WHITE BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY UNSWITCHED
RED Ballast BLUE RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
*LAMP

RED/BLK (+)

BRN/WHT
BROWN
SELECT PROPER VOLTAGE

VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
RED OR
*LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LISB_2LEO_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V11 V11
ONE LAMP BIAX

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE
BLACK BLUE/WHT ORG (277V)
WHITE A.C. BLUE 4 RED/WHT EMERGENCY
UNSWITCHED
RED Ballast 5
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LPTS / CHARGE AC POWER IS SUPPLIED.
COMMON INDICATOR
*AC / EMERGENCY
LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS
4 CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
5 CAP UNUSED LEAD

1LBX_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V12 V12
ONE BIAX LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY
UNSWITCHED
RED
RED Ballast RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LPTS / CHARGE
INDICATOR AC POWER IS SUPPLIED.
COMMON
*AC / EMERGENCY LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATIONS SECTION FOR
VARIOUS OPTIONS.

1BXLRSB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V13 V13
ONE BIAX LAMP RAPID START BALLAST WITH DIMMING CONTROL

DIMMED HOT
SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY
UNSWITCHED
RED
RED Ballast RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LPTS / CHARGE
INDICATOR AC POWER IS SUPPLIED.
COMMON
*AC / EMERGENCY LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATIONS SECTION FOR
VARIOUS OPTIONS.

1BXLRSB_DM_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V14 V14
TWO COMPACT LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
BLUE BLUE/WHT ORG (277V)
WHITE
YELLOW
A.C. RED/WHT EMERGENCY
UNSWITCHED
RED
YELLOW
Ballast RED
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
LPTS / CHARGE
INSTALLATION IS COMPLETE AND
INDICATOR AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER


*LAMP TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS
COMMON
*AC / EMERGENCY

2BXLRSB_DM_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V15 V15
THREE LAMP INSTANT START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE/WHT ORG (277V)
A.C. BLUE RED/WHT EMERGENCY UNSWITCHED
RED Ballast BLUE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
LAMP
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.

*LAMP
DO NOT MATE CONNECTOR UNTIL
LPTS / CHARGE INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
COMMON INDICATOR
*AC / EMERGENCY LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

3LISB_2LEO_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V16 V16
THREE LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
WHITE BLUE/WHT BLUE/WHT ORG (277V)
BLUE
BLUE
A.C. RED/WHT EMERGENCY UNSWITCHED
RED
YELLOW Ballast RED
RED BALLAST BLK (120V)
YELLOW YELLOW WHITE
COMMON

VIOLET

BRN/WHT
BROWN
*LAMP
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
LPTS / CHARGE INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
COMMON INDICATOR
*AC / EMERGENCY LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.

3LRSB_2LEO_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V17 V17
THREE BIAX RAPID START BALLAST WITH DIMMING CONTROL

DIMMED HOT ORANGE OR PURPLE


SWITCHED OR
UNSWITCHED
RED LINE
BLACK BLUE
RED BLUE/WHT ORG (277V)
WHITE
BLUE
A.C. RED/WHT EMERGENCY
UNSWITCHED
BLUE Ballast RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
BLUE/WHT
BLUE/WHT

YELLOW
YELLOW

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*LAMP
LAMP

LPTS / CHARGE
LAMP

INDICATOR AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER


TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS

COMMON

*AC / EMERGENCY

3BXLRSB_DM_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V18 V18
THREE LAMP BIAX INSTANT START

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE
BLACK BLUE/WHT ORG (277V)
WHITE A.C. BLUE 4 RED/WHT EMERGENCY
UNSWITCHED
RED Ballast BLUE RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.

DO NOT MATE CONNECTOR UNTIL


INSTALLATION IS COMPLETE AND
LAMP

LPTS / CHARGE
*LAMP
LAMP

AC POWER IS SUPPLIED.
INDICATOR
LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS
4 CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

COMMON

*AC / EMERGENCY

3LBXIN_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V19 V19
FOUR LAMP INSTANT START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE BLUE/WHT ORG (277V)
YELLOW
A.C. RED RED/WHT EMERGENCY
UNSWITCHED
YELLOW
Ballast RED
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
LAMP

VIOLET
LAMP
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP DO NOT MATE CONNECTOR UNTIL
LPTS / CHARGE INSTALLATION IS COMPLETE AND
*LAMP AC POWER IS SUPPLIED.
INDICATOR
COMMON LAMP SELECTOR LEADSREFER
*AC / EMERGENCY TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

4LISB_2LEO_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V20 V20
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED BLUE LINE
WHITE RED BLUE/WHT ORG (277V)
YELLOW A.C. BLUE/WHT RED/WHT EMERGENCY UNSWITCHED
YELLOW
BROWN Ballast BLUE/WHT
BLUE
RED BALLAST BLK (120V)
BROWN YELLOW WHITE
BLUE COMMON

BRN/WHT
BROWN
VIOLET
LAMP UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
LAMP LPTS / CHARGE INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
INDICATOR
*LAMP LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
COMMON LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
*AC / EMERGENCY

4LRSB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V21 V21
FOUR LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
BLACK RED BLUE LINE
WHITE RED BLUE/WHT ORG (277V)
YELLOW A.C. BLUE/WHT RED/WHT EMERGENCY UNSWITCHED
YELLOW
BROWN Ballast BLUE/WHT
BLUE
RED BALLAST BLK (120V)
BROWN YELLOW WHITE
BLUE COMMON

BRN/WHT
BROWN
VIOLET
LAMP UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
*LAMP LPTS / CHARGE INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
INDICATOR
*LAMP LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
COMMON LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
*AC / EMERGENCY

4LRSB_2LEO_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V22 V22
TWO BIAX LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE
BLACK BLUE/WHT ORG (277V)
WHITE A.C. BLUE 4 RED/WHT EMERGENCY
UNSWITCHED
RED Ballast RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
*LAMP LPTS / CHARGE
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
INDICATOR
LAMP SELECTOR LEADS - REFER
LAMP TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS
4 CONNECT BLUE/WHT AND RED/WHT
WIRES TOGETHER
COMMON
*AC / EMERGENCY

2LISBX_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V23 V23
TWO LAMP BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
WHITE BLUE/WHT ORG (277V)
YELLOW
A.C. RED/WHT EMERGENCY UNSWITCHED
YELLOW Ballast BLUE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
LAMP
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
CHARGE INSTALLATION IS COMPLETE AND
COMMON INDICATOR/LPTS AC POWER IS SUPPLIED.

*AC / EMERGENCY
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

2LMB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V24 V24
ONE LAMP MAGNETIC BALLAST

SWITCHED OR
UNSWITCHED
LINE
RED BLUE
BLACK BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY
UNSWITCHED
WHITE Ballast RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
CHARGE DO NOT MATE CONNECTOR UNTIL
INDICATOR/LPTS INSTALLATION IS COMPLETE AND
COMMON AC POWER IS SUPPLIED.
*AC / EMERGENCY LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

1LMB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V25 V25
ONE LAMP CIRCLINE RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
WHITE RED BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY
UNSWITCHED
Ballast BLUE
WHITE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
LPTS/CHARGE INSTALLATION IS COMPLETE AND
INDICATOR AC POWER IS SUPPLIED.
COMMON
*AC / EMERGENCY
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.

1LCRSB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V26 V26
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
WHITE BLUE/WHT BLUE/WHT ORG (277V)
BLUE
BLUE
A.C. RED/WHT EMERGENCY UNSWITCHED
RED
YELLOW Ballast RED
RED BALLAST BLK (120V)
YELLOW YELLOW WHITE
COMMON

RED/BLK (+)

BRN/WHT
LAMP

BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
*LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
CHARGE LAMP OPERATION SECTION FOR
COMMON INDICATOR VARIOUS OPTIONS.
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LRSB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V27 V27
ONE LAMP LAG BALLAST

SWITCHED OR
UNSWITCHED
RED LINE
BLACK BLUE
WHITE RED BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY UNSWITCHED
BLUE Ballast RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
*LAMP
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
DISCONNECT LAMP HOLDER INSTALLATION IS COMPLETE AND
LPTS / CHARGE AC POWER IS SUPPLIED.
INDICATOR
COMMON LAMP SELECTOR LEADS - REFER
*AC / EMERGENCY TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS

1LLAG_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V28 V28
ONE LAMP PRE-HEAT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY UNSWITCHED
Ballast RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
S

BRN/WHT
BROWN
VIOLET
PFC
CAPACITOR *LAMP
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.


DO NOT MATE CONNECTOR UNTIL
LPTS / CHARGE INSTALLATION IS COMPLETE AND
INDICATOR AC POWER IS SUPPLIED.
COMMON
*AC / EMERGENCY LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.

1LPHSB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V29 V29
ONE LAMP EMERGENCY ONLY

CAP OFF
LEADS

BLUE
BLUE/WHT ORG (277V)
RED/WHT EMERGENCY UNSWITCHED
RED BLK (120V)
BALLAST
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
*LAMP
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.

LPTS/
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
CHARGE INDICATOR
AC POWER IS SUPPLIED.
*AC / EMERGENCY CONNECT THE LAMP SELECTOR
LEADS

1LEO_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V30 V30
TWO LAMP EMERGENCY ONLY

CAP OFF
LEADS

BLUE
BLUE/WHT ORG (277V)
RED/WHT EMERGENCY UNSWITCHED
RED BLK (120V)
BALLAST
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
*LAMP
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.

LPTS/
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*LAMP CHARGE INDICATOR
AC POWER IS SUPPLIED.
*AC / EMERGENCY CONNECT THE LAMP SELECTOR
LEADS

2LEO_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V31 V31
ONE LAMP TRIAD BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE
BLACK BLUE/WHT ORG (277V)
WHITE A.C. RED/WHT EMERGENCY
UNSWITCHED
RED Ballast BLUE RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
CHARGE INSTALLATION IS COMPLETE AND
INDICATOR AC POWER IS SUPPLIED.
COMMON
*AC / EMERGENCY
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

1LTB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V32 V32
FULHAM WORKHORSE BALLAST

SWITCHED OR
UNSWITCHED
LINE
RED BLUE
BLACK BLUE/WHT ORG (277V)
RED
WHITE A.C. RED 4 RED/WHT EMERGENCY
UNSWITCHED
YELLOW Ballast RED 5
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP

LPTS / CHARGE
*LAMP
LAMP

AC POWER IS SUPPLIED.
INDICATOR
LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS
4 CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

5 CAP UNUSED LEAD


COMMON

*AC / EMERGENCY

FWB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V33 V33
THREE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE/WHT ORG (277V)
A.C. BLUE RED/WHT EMERGENCY UNSWITCHED
RED Ballast BLUE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
LAMP

RED/BLK (+)

BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
CHARGE LAMP OPERATION SECTION FOR
COMMON INDICATOR VARIOUS OPTIONS.
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LISB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V34 V34
THREE LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
WHITE BLUE/WHT BLUE/WHT ORG (277V)
A.C. BLUE RED/WHT EMERGENCY UNSWITCHED
YELLOW Ballast BLUE
RED
RED BALLAST BLK (120V)
YELLOW YELLOW WHITE
RED COMMON

BRN/WHT
BROWN
VIOLET
LAMP UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP

DO NOT MATE CONNECTOR UNTIL
LPTS / CHARGE INSTALLATION IS COMPLETE AND
*LAMP AC POWER IS SUPPLIED.
COMMON INDICATOR
*AC / EMERGENCY LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.

3LRSB_2LEO2_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V35 V35
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
WHITE BLUE/WHT BLUE/WHT ORG (277V)
A.C. BLUE RED/WHT EMERGENCY UNSWITCHED
YELLOW Ballast BLUE
RED
RED BALLAST BLK (120V)
YELLOW YELLOW WHITE
RED COMMON

BRN/WHT
BROWN
VIOLET
LAMP UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
*LAMP LPTS / CHARGE INSTALLATION IS COMPLETE AND
INDICATOR AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
COMMON TO INSTALLATION INSTRUCTIONS,
*AC / EMERGENCY LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.

3LRSB2_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V36 V36
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED/WHT BLUE LINE
WHITE RED/WHT BLUE/WHT ORG (277V)
A.C. BLUE RED/WHT EMERGENCY UNSWITCHED
YELLOW Ballast BLUE
RED
RED BALLAST BLK (120V)
YELLOW YELLOW WHITE
RED COMMON

BRN/WHT
BROWN
VIOLET
LAMP UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
*LAMP LPTS / CHARGE
INSTALLATION IS COMPLETE AND
INDICATOR AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
COMMON TO INSTALLATION INSTRUCTIONS,
*AC / EMERGENCY LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.

3LRSB3_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V37 V37
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
WHITE BLUE/WHT BLUE/WHT ORG (277V)
YELLOW/BLK RED/WHT RED/WHT EMERGENCY UNSWITCHED
YELLOW/BLK
YELLOW A.C. RED/WHT
BLUE
RED
YELLOW
BALLAST BLK (120V)
WHITE
YELLOW
Ballast BLUE COMMON

BRN/WHT
BROWN
VIOLET
RED
RED UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
LPTS / CHARGE INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP INDICATOR
LAMP SELECTION LEADSREFER
LAMP TO INSTALLATION INSTRUCTIONS,
COMMON LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
*LAMP

*AC / EMERGENCY

4LRSB2_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V38 V38
TWO COMPACT LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
RED BLUE/WHT ORG (277V)
WHITE
YELLOW
A.C. RED/WHT EMERGENCY
UNSWITCHED
BLUE
YELLOW
Ballast BLUE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
LPTS / CHARGE
INSTALLATION IS COMPLETE AND
INDICATOR AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER


*LAMP TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS
COMMON
*AC / EMERGENCY

2CLRSB2_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V39 V39
TWO COMPACT RAPID START BALLAST TWO LAMP OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
BLUE BLUE/WHT ORG (277V)
WHITE
YELLOW
A.C. RED/WHT EMERGENCY
UNSWITCHED
RED
YELLOW
Ballast RED
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP DO NOT MATE CONNECTOR UNTIL
LPTS / CHARGE
INSTALLATION IS COMPLETE AND
INDICATOR AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER


*LAMP TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS
COMMON
*AC / EMERGENCY

2BXLRSB2LEO_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V40 V40
TWO COMPACT RAPID START BALLAST TWO LAMP OPERATION

SWITCHED OR
UNSWITCHED
RED LINE
BLACK BLUE
RED BLUE/WHT ORG (277V)
WHITE
YELLOW
A.C. RED/WHT EMERGENCY
UNSWITCHED
BLUE
YELLOW
Ballast BLUE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP DO NOT MATE CONNECTOR UNTIL
LPTS / CHARGE
INSTALLATION IS COMPLETE AND
INDICATOR AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER


*LAMP TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS
COMMON
*AC / EMERGENCY

2BXLRSB2LEO2_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V41 V41
ONE LAMP CIRCLINE RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
WHITE RED BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY
UNSWITCHED
YELLOW
Ballast RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LPTS/CHARGE
INDICATOR AC POWER IS SUPPLIED.
COMMON
*AC / EMERGENCY LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS

1LCRSB_160F

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V42 V42
ONE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
WHITE RED BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY
UNSWITCHED
BLUE
BLUE Ballast RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
*LAMP
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
LPTS/CHARGE INSTALLATION IS COMPLETE AND
COMMON INDICATOR AC POWER IS SUPPLIED.
*AC / EMERGENCY LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS

1LRSB_160_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V43 V43
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
WHITE RED BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY
UNSWITCHED
YELLOW BLUE
YELLOW Ballast BLUE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
LAMP

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
LPTS/CHARGE INSTALLATION IS COMPLETE AND
COMMON INDICATOR AC POWER IS SUPPLIED.
*AC / EMERGENCY LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS

2LRSB_160_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V44 V44
TWO LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
WHITE RED BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY
UNSWITCHED
YELLOW BLUE
YELLOW Ballast BLUE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
*LAMP

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
LPTS/CHARGE INSTALLATION IS COMPLETE AND
COMMON INDICATOR AC POWER IS SUPPLIED.
*AC / EMERGENCY LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS

2LRSB_2LEO_1602

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V45 V45
THREE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED/WHT BLUE
WHITE BLUE/WHT ORG (277V)
BLACK/WHT
A.C. RED 4 RED/WHT EMERGENCY
UNSWITCHED
YELLOW Ballast BLUE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
(GRD)
UNIT

BRN/WHT
BROWN
VIOLET
SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP LPTS/CHARGE AC POWER IS SUPPLIED.
INDICATOR
*LAMP LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
COMMON LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS
*AC / EMERGENCY
4 CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

3LISB_160_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V46 V46
ONE LAMP RAPID START BALLAST WITH RELAY

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE BLUE/WHT BLK (120V)
A.C. RED/WHT EMERGENCY UNSWITCHED
RED
RED Ballast RED BALLAST
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT
*LAMP CONNECTOR
YELLOW
YELLOW LPTS / CHARGE
WHITE INDICATOR
RELAY
BLACK

COMMON

*AC / EMERGENCY

1LRSBWR_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V47 V47
ONE LAMP INSTANT START BALLAST WITH RELAY

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE/WHT BLK (120V)
A.C. RED/WHT EMERGENCY UNSWITCHED
RED
Ballast RED BALLAST
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT
*LAMP CONNECTOR
YELLOW
YELLOW LPTS / CHARGE
WHITE INDICATOR
RELAY
BLACK

COMMON

*AC / EMERGENCY

1LISBWR_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V48 V48
ONE LAMP RAPID START BALLAST WITH RELAY

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE BLUE/WHT BLK (120V)
A.C. RED/WHT EMERGENCY UNSWITCHED
RED
RED Ballast RED BALLAST
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT
*LAMP CONNECTOR
YELLOW
YELLOW LPTS / CHARGE
WHITE INDICATOR
RELAY
BLACK

COMMON

*AC / EMERGENCY

1LRSBWR_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V49 V49
TWO LAMP SERIES LEAD BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE/WHT ORG (277V)
BRN OR YEL
A.C. RED/WHT EMERGENCY UNSWITCHED
BRN OR YEL Ballast RED
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
LAMP

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
CHARGE INSTALLATION IS COMPLETE AND
COMMON INDICATOR/LPTS AC POWER IS SUPPLIED.

*AC / EMERGENCY
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

2LSL_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V50 V50
TWO LAMP SERIES LEAD BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE/WHT ORG (277V)
BRN OR YEL
A.C. RED/WHT EMERGENCY UNSWITCHED
BRN OR YEL Ballast RED
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
LAMP

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
CHARGE INSTALLATION IS COMPLETE AND
COMMON INDICATOR/LPTS AC POWER IS SUPPLIED.

*AC / EMERGENCY
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

2LSL_2LEO_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V51 V51
TWO BIAX LAMP INSTANT START BALLAST TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE
BLACK BLUE/WHT ORG (277V)
WHITE A.C. BLUE 4 RED/WHT EMERGENCY
UNSWITCHED
RED Ballast RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
*LAMP LPTS / CHARGE
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
INDICATOR
LAMP SELECTOR LEADS - REFER
LAMP TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS
4 CONNECT BLUE/WHT AND RED/WHT
WIRES TOGETHER
COMMON
*AC / EMERGENCY

2LISBX_2LEO_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V52 V52
TWO COMPACT RAPID START BALLAST TWO LAMP OPERATION

SWITCHED OR
UNSWITCHED
RED LINE
BLACK BLUE
RED BLUE/WHT ORG (277V)
WHITE
YELLOW
A.C. RED/WHT EMERGENCY
UNSWITCHED
BLUE
YELLOW
Ballast BLUE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP DO NOT MATE CONNECTOR UNTIL
LPTS / CHARGE
INSTALLATION IS COMPLETE AND
INDICATOR AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER


*LAMP TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS
COMMON
*AC / EMERGENCY

2BXLRSB2LEO2_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V53 V53
TWO LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY UNSWITCHED
YELLOW Ballast RED
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
LAMP

VIOLET
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
LPTS / CHARGE INSTALLATION IS COMPLETE AND
COMMON INDICATOR AC POWER IS SUPPLIED.
*AC / EMERGENCY LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

2LISBESI_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V54 V54
TWO LAMP INSTANT START BALLAST TWO LAMP OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY UNSWITCHED
YELLOW Ballast RED
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
*LAMP
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.

DO NOT MATE CONNECTOR UNTIL


INSTALLATION IS COMPLETE AND
LPTS / CHARGE
COMMON INDICATOR AC POWER IS SUPPLIED.
*AC / EMERGENCY LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

2LISBESI_2LEO_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V55 V55
THREE BIAX RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLUE LINE
BLACK BLUE
BLUE BLUE/WHT ORG (277V)
WHITE
YELLOW
A.C. RED/WHT EMERGENCY
UNSWITCHED
YELLOW Ballast RED RED BALLAST BLK (120V)
RED YELLOW WHITE
COMMON
RED/WHITE
RED/WHITE

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.

DO NOT MATE CONNECTOR UNTIL


INSTALLATION IS COMPLETE AND
*LAMP
LAMP

LPTS / CHARGE
LAMP

INDICATOR AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER


TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS

COMMON

*AC / EMERGENCY

3BXLRSB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V56 V56
ONE COMPACT LAMP EMERGENCY ONLY

CAP OFF
LEADS

BLUE
BLUE/WHT ORG (277V)
RED/WHT EMERGENCY UNSWITCHED
RED BLK (120V)
BALLAST
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
CHARGE AC POWER IS SUPPLIED.
INDICATOR
CONNECT THE LAMP SELECTOR
LEADS

*AC / EMERGENCY

1CLEO_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V57 V57
TWO COMPACT LAMP EMERGENCY ONLY

CAP OFF
LEADS

BLUE
BLUE/WHT ORG (277V)
RED/WHT EMERGENCY UNSWITCHED
RED BLK (120V)
BALLAST
YELLOW WHITE
COMMON
*LAMP

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*LAMP CHARGE INDICATOR AC POWER IS SUPPLIED.
CONNECT THE LAMP SELECTOR
LEADS

*AC / EMERGENCY

2CLEO_160_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V58 V58
ONE LAMP INSTANT START BIAX

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE
BLACK BLUE/WHT ORG (277V)
WHITE A.C. RED 4 RED/WHT EMERGENCY
UNSWITCHED
Ballast RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LPTS / CHARGE AC POWER IS SUPPLIED.
COMMON INDICATOR
*AC / EMERGENCY
LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS
4 CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

1LBX_160_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V59 V59
TWO LAMP SERIES LEAD BALLAST

SWITCHED OR
UNSWITCHED
RED LINE
BLACK BLUE
WHITE BLUE/WHT ORG (277V)
BROWN
A.C. RED/WHT EMERGENCY UNSWITCHED
BROWN Ballast BLUE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
LAMP

BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
CHARGE INSTALLATION IS COMPLETE AND
COMMON INDICATOR/LPTS AC POWER IS SUPPLIED.

*AC / EMERGENCY
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

2LSL_160_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V60 V60
TWO LAMP SERIES LEAD BALLAST

SWITCHED OR
UNSWITCHED
BLUE LINE
BLACK BLUE
WHITE BLUE/WHT ORG (277V)
RED A.C. RED/WHT EMERGENCY UNSWITCHED
RED Ballast BLUE
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
LAMP

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
4 DO NOT MATE CONNECTOR UNTIL
CHARGE INSTALLATION IS COMPLETE AND
COMMON INDICATOR/LPTS AC POWER IS SUPPLIED.

*AC / EMERGENCY
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
4 LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS

2LSL_160_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V61 V61
THREE LAMP RAPID START BALLAST WITH TWO LAMP OPERATION

SWITCHED OR
UNSWITCHED
BLACK RED/WHT BLUE LINE
WHITE RED/WHT BLUE/WHT ORG (277V)
A.C. BLUE RED/WHT EMERGENCY UNSWITCHED
YELLOW Ballast BLUE
RED
RED BALLAST BLK (120V)
YELLOW YELLOW WHITE
RED COMMON

BRN/WHT
BROWN
VIOLET
LAMP UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
*LAMP LPTS / CHARGE
INSTALLATION IS COMPLETE AND
INDICATOR AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
COMMON TO INSTALLATION INSTRUCTIONS,
*AC / EMERGENCY LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.

3LRSB3_160_2LEO

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V62 V62
TWO COMPACT RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
BLUE BLUE/WHT ORG (277V)
WHITE
YELLOW
A.C. RED/WHT EMERGENCY
UNSWITCHED
RED
YELLOW
Ballast RED
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
LPTS / CHARGE
INSTALLATION IS COMPLETE AND
INDICATOR AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER


*LAMP TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS

COMMON
*AC / EMERGENCY

2BXLRSB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V63 V63
FOUR LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
WHITE RED BLUE/WHT ORG (277V)
YELLOW
YELLOW
A.C. BLUE/WHT
BLUE/WHT
RED/WHT EMERGENCY
BLK (120V)
UNSWITCHED

BROWN Ballast BLUE


RED
YELLOW
BALLAST
WHITE
BROWN BLUE COMMON

RED/BLK (+)

BRN/WHT
BROWN
VIOLET
LAMP SELECT PROPER VOLTAGE
UNIT

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
*LAMP
LAMP SELECTION LEADSREFER
*LAMP TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS/ VARIOUS OPTIONS.
COMMON CHARGE INDICATOR
TEST ACCESSORY LEADS
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POSITIVE LEAD WIRING.

4LRSB_2LEO_2_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V64 V64
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK YELLOW BLUE LINE
WHITE YELLOW BLUE/WHT ORG (277V)
BLU/WHT BROWN RED/WHT
UNSWITCHED
BLU/WHT EMERGENCY
ORG A.C. BROWN
BLUE
RED BLK (120V)
YELLOW BALLAST
ORG
Ballast BLUE WHITE
COMMON
RED
RED SELECT PROPER VOLTAGE

RED/BLK (+)

BRN/WHT
BROWN
VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS-REFER


LAMP TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
*LAMP TBTS / CHARGE VARIOUS OPTIONS.
INDICATOR
COMMON TEST ACCESSORY LEADS-
REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

4LRSB3_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V65 V65
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY UNSWITCHED
YELLOW RED
YELLOW Ballast RED
RED BALLAST BLK (120V)
YELLOW WHITE
COMMON
LAMP

RED/BLK (+)

BRN/WHT
BROWN
VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
*LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
CHARGE LAMP OPERATION SECTION FOR
COMMON INDICATOR VARIOUS OPTIONS.
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LRSB_160_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V66 V66
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED BLUE LINE
WHITE RED BLUE/WHT ORG (277V)
BLUE ORG RED/WHT UNSWITCHED
BLUE
EMERGENCY
ORG BLK (120V)
BLU/WHT A.C. YELLOW
RED
YELLOW
BALLAST
WHITE
BLU/WHT
Ballast YELLOW
COMMON
BROWN

RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

BRN/WHT
BROWN
VIOLET
WHT/RED
BROWN LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP
LAMP SELECTOR LEADS-REFER
*LAMP TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3LRSB4_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V67 V67
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK YELLOW BLUE LINE
WHITE YELLOW BLUE/WHT ORG (277V)
BLU/WHT BROWN RED/WHT
UNSWITCHED
BLU/WHT EMERGENCY
ORG A.C. BROWN
BLUE
RED BLK (120V)
YELLOW BALLAST
ORG
Ballast BLUE WHITE
COMMON
RED
RED SELECT PROPER VOLTAGE

RED/BLK (+)

BRN/WHT
BROWN
VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS-REFER


LAMP TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
*LAMP TBTS / CHARGE VARIOUS OPTIONS.
INDICATOR
COMMON TEST ACCESSORY LEADS-
REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

4LRSB3_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V68 V68
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE LINE
WHITE BLUE BLUE/WHT ORG (277V)
ORG RED RED/WHT
UNSWITCHED
ORG EMERGENCY
BLU/WHT A.C. RED
BROWN
RED BLK (120V)
YELLOW BALLAST
BLU/WHT
Ballast BROWN WHITE
COMMON
YELLOW
YELLOW
SELECT PROPER VOLTAGE

RED/BLK (+)

BRN/WHT
BROWN
VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP LAMP SELECTOR LEADS-REFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
*LAMP VARIOUS OPTIONS.
INDICATOR
COMMON TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

4LRSB4_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V69 V69
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK YELLOW BLUE LINE
WHITE YELLOW BLUE/WHT ORG (277V)
BLU/WHT RED/WHT
UNSWITCHED
GREY EMERGENCY
BROWN A.C. BLU/WHT
BLUE
RED BLK (120V)
YELLOW BALLAST
BROWN
ORG
Ballast BLUE WHITE
COMMON
RED
ORG
RED SELECT PROPER VOLTAGE

RED/BLK (+)

BRN/WHT
BROWN
VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS-REFER


*LAMP TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS.
INDICATOR
COMMON TEST ACCESSORY LEADS-
REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3LRSB5_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V70 V70
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE LINE
BLK/YLW BLUE BLUE/WHT ORG (277V)
YELLOW RED/WHT UNSWITCHED
YELLOW
EMERGENCY
RED BLK (120V)
WHITE A.C. RED
RED
YELLOW
BALLAST
WHITE
BLU/WHT
Ballast COMMON
BROWN

RED/BLK (+)
SELECT PROPER VOLTAGE

BRN/WHT
BROWN
UNIT

VIOLET
WHT/RED
BROWN LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP
LAMP SELECTOR LEADS-REFER
*LAMP TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3LRSB4_160_1

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


V71 V71
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED/WHT BLUE LINE
WHITE RED/WHT BLUE/WHT ORG (277V)
ORG BLU/WHT RED/WHT
UNSWITCHED
ORG
YELLOW A.C. BLUE/WHT
BLUE
RED
YELLOW
EMERGENCY BLK (120V)
BALLAST
YELLOW
Ballast BLUE WHITE
COMMON
RED
RED
SELECT PROPER VOLTAGE

RED/BLK (+)

BRN/WHT
BROWN
VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
*LAMP
LAMP SELECTOR LEADS-REFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3LRSB6_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY1 YY1
ONE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE
ORG (277V)
BLACK BLUE/WHT UNSWITCHED
WHITE A.C. RED/WHT EMERGENCY BLK (120V)
RED Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
SELECT PROPER VOLTAGE

VIOLET

VIOLET
RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
*LAMP CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
5 TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS.
COMMON INDICATOR CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
*AC / EMERGENCY
5 TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

1LISB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY2 YY2
ONE LAMP RAPID START BALLAST FOR USE WITH OSRAM/DIMMING

VIOLET (+)
GREY (-)

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE BLUE/WHT
A.C. RED/WHT EMERGENCY BLK (120V)
UNSWITCHED
RED
RED Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
SELECT PROPER VOLTAGE

RED/BLK (+)
*LAMP
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS
INDICATOR
COMMON
*AC / EMERGENCY
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

1LRSB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY3 YY3
ONE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
WHITE RED BLUE/WHT ORG (277V)
A.C. RED/WHT
UNSWITCHED
BLUE
BLUE Ballast RED EMERGENCY
BALLAST
BLK (120V)
YELLOW WHITE
COMMON
WHT/BLK

RED/BLK (+)
*LAMP

VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS/CHARGE LAMPS OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

1LRSB_D_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY4 YY4
TWO LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE/WHT UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
RED Ballast BLUE
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LISB_2_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY5 YY5
TWO LAMP INSTANT START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE LINE
ORG (277V)
WHITE BLUE/WHT UNSWITCHED
A.C. RED/WHT
EMERGENCY
BLK (120V)
RED Ballast BLUE RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
*LAMP

VIOLET

VIOLET
SELECT PROPER VOLTAGE

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
*LAMP

RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMPS OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS
COMMON
CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LISB_2LEO_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY6 YY6
TWO LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE ORG (277V)
BLUE/WHT UNSWITCHED
BLACK A.C. RED/WHT EMERGENCY BLK (120V)
WHITE Ballast RED RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET
VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR

RED OR
LEAD. CAP UNUSED LEAD.

DO NOT MATE CONNECTOR UNTIL


INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER

TEST ACCESSORY LEADS-


REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LISB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY7 YY7
TWO LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE BLUE/WHT
UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW RED
YELLOW Ballast RED
RED BALLAST
WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
*LAMP

VIOLET

VIOLET
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.

DO NOT MATE CONNECTOR UNTIL


INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMPS OPERATION SECTION FOR
COMMON VARIOUS OPTIONS
*AC / EMERGENCY
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LRSB_2LEO_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY8 YY8
TWO LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
WHITE RED BLUE/WHT ORG (277V)
A.C. RED/WHT
UNSWITCHED
YELLOW BLUE
YELLOW Ballast BLUE
RED EMERGENCY
BALLAST
BLK (120V)
YELLOW WHITE
COMMON
WHT/BLK
*LAMP

RED/BLK (+)
SELECT PROPER VOLTAGE

VIOLET

VIOLET
*LAMP UNIT LEAD. CAP UNUSED LEAD.

WHT/RED

RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
TBTS/CHARGE VARIOUS OPTIONS
INDICATOR
COMMON TEST ACCESSORY LEADS-
REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LRSB_2LEO_D_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY9 YY9
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
ORG (277V) UNSWITCHED
WHITE BLUE BLUE/WHT
A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW RED
YELLOW Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMPS OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS
COMMON TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LRSB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY10 YY10
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
ORG (277V) UNSWITCHED
WHITE RED BLUE/WHT
A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW BLUE
YELLOW Ballast BLUE
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMPS OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS
COMMON TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LRSB_D_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY11 YY11
THREE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE/WHT UNSWITCHED
A.C. BLUE RED/WHT EMERGENCY BLK (120V)
RED Ballast BLUE
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP SELECT PROPER VOLTAGE

VIOLET

VIOLET
RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED

RED OR
LAMP CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*LAMP AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS.
COMMON INDICATOR CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
*AC / EMERGENCY
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3LISB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY12 YY12
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
ORG (277V)
WHITE BLUE/WHT BLUE/WHT UNSWITCHED
BLUE
BLUE
A.C. RED/WHT EMERGENCY BLK (120V)
RED
YELLOW Ballast RED
RED BALLAST WHITE COMMON
YELLOW YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR

RED OR
LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMPS OPERATION SECTION FOR
COMMON VARIOUS OPTIONS
*AC / EMERGENCY TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3LRSB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY13 YY13
FOUR LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE BLUE/WHT UNSWITCHED
YELLOW
A.C. RED RED/WHT EMERGENCY BLK (120V)
YELLOW
Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP SELECT PROPER VOLTAGE

RED/BLK (+)
VIOLET

VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
*LAMP LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS.
INDICATOR CONNECT BLU/WHT AND RED/WHT
COMMON WIRES TOGETHER
*AC / EMERGENCY TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

4LISB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY14 YY14
TWO LAMP INSTANT START BALLAST TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
WHITE BLUE/WHT
UNSWITCHED
A.C. RED RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
*LAMP

VIOLET

VIOLET
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP SELECTOR LEADSREFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMPS OPERATION SECTION FOR
COMMON VARIOUS OPTIONS
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LISFB2_80D_2LEO

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY15 YY15
TWO LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
WHITE BLUE/WHT
UNSWITCHED
A.C. RED RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
LAMP

VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMPS OPERATION SECTION FOR
COMMON VARIOUS OPTIONS
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LISFB2_80D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY16 YY16
ONE BIAX LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY
UNSWITCHED
RED
RED Ballast RED BALLAST BLK (120V)
WHITE
YELLOW COMMON
WHT/BLK

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
4
LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
TBTS/ CHARGE LAMP OPERATIONS SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY 4 TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

1BXLRSB_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY17 YY17
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED BLUE LINE
ORG (277V)
WHITE RED BLUE/WHT UNSWITCHED
YELLOW A.C. BLUE/WHT RED/WHT EMERGENCY BLK (120V)
YELLOW
BROWN Ballast BLUE/WHT
BLUE
RED BALLAST WHITE
COMMON
BROWN YELLOW WHT/BLK
BLUE

VIOLET
VIOLET
RED/BLK (+)
LAMP UNIT SELECT PROPER VOLTAGE

WHT/RED

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

*LAMP LAMP SELECTION LEADSREFER


TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

4LRSB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY18 YY18
THREE LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
WHITE ORG (277V) UNSWITCHED
BLUE/WHT BLUE/WHT
BLUE
BLUE
A.C. RED/WHT EMERGENCY BLK (120V)
RED
YELLOW Ballast RED
RED BALLAST WHITE COMMON
YELLOW YELLOW WHT/BLK
*LAMP

VIOLET

VIOLET

RED/BLK (+)
SELECT PROPER VOLTAGE
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
*LAMP CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS.
INDICATOR
COMMON TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3LRSB_2LEO_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY19 YY19
THREE LAMP
THREE LAMP INSTANT
INSTANT START
START BALLAST BALLAST
WITH TWO WITH OPERATION
LAMP EMERGENCY

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
BLUE/WHT
WHITE
A.C. BLUE RED/WHT EMERGENCY BLK (120V)
UNSWITCHED

RED Ballast BLUE


RED BALLAST WHITE COMMON
YELLOW WHT/BLK

RED/BLK (+)
LAMP

VIOLET

VIOLET
WHT/RED
UNIT SELECT PROPER VOLTAGE

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS/ LAMP OPERATION SECTION FOR
COMMON CHARGE INDICATOR VARIOUS OPTIONS.
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
TEST ACCESSORY LEADS
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POSITIVE LEAD WIRING.

3LISB_2LEO_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY20 YY20
FOUR LAMP INSTANT START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE BLUE/WHT UNSWITCHED
YELLOW
A.C. RED RED/WHT EMERGENCY BLK (120V)

YELLOW
Ballast RED
RED BALLAST WHITE COMMON
YELLOW WHT/BLK

RED/BLK (+)
LAMP

VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
LAMP

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*LAMP AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
TEST ACCESSORY LEADS
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POSITIVE LEAD WIRING.

4LISB_2LEO_80D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY21 YY21
THREE LAMP RAPID START BALLAST WITH DIMMING LEAD TWO LAMP EMERGENCY OPERATION

DIMMED HOT
SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
ORG (277V)
WHITE BLUE/WHT BLUE/WHT UNSWITCHED
BLUE
BLUE
A.C. RED/WHT EMERGENCY BLK (120V)
RED
YELLOW Ballast RED
RED BALLAST WHITE
COMMON
YELLOW YELLOW WHT/BLK
*LAMP

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.

RED OR
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3LRSB_DM_2LEO_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY22 YY22
ONE LAMP INSTANT START BALLAST WITH CHARGE INDICATOR AND TEST SWITCH

BLUE BLUE
ORG (277V) SWITCHED OR
BLACK BLUE/WHT
WHITE A.C. RED/WHT EMERGENCY BLK (120V) TEST SWITCH
UNSWITCHED
LINE
RED Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
SELECT PROPER VOLTAGE

VIOLET

VIOLET
RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
*LAMP CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
CHARGE VARIOUS OPTIONS.
COMMON INDICATOR CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
*AC / EMERGENCY
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

1LISB_CI_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY23 YY23
TWO LAMP EMERGENCY ONLY

BLUE ORG (277V)


BLUE/WHT UNSWITCHED
RED/WHT EMERGENCY BLK (120V)
RED WHITE
BALLAST COMMON
YELLOW WHT/BLK

RED/BLK (+)
VIOLET

VIOLET
WHT/RED
UNIT SELECT PROPER VOLTAGE
*LAMP

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*LAMP AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
*AC / EMERGENCY TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS.
CAP UNUSED LEADS.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LEO_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY24 YY24
ONE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE
ORG (277V)
BLACK BLUE/WHT UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
WHITE Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
SELECT PROPER VOLTAGE

VIOLET

VIOLET
RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
*LAMP CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS.
COMMON INDICATOR CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
*AC / EMERGENCY
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

1LISB_D_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY25 YY25
ONE LAMP LAG BALLAST

SWITCHED OR
UNSWITCHED
RED LINE
BLACK BLUE ORG (277V)
WHITE RED BLUE/WHT
UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
BLUE Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
DISCONNECT LAMP HOLDER INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON TEST ACCESSORY LEADS-REFER
*AC / EMERGENCY TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LLAG_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY26 YY26
ONE LAMP INSTANT START BALLAST WITH 347V CONVERTER

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE ORG (277V)
347 VOLT
BLACK BLUE/WHT CONVERTER UNSWITCHED
WHITE A.C. RED/WHT EMERGENCY BLK (120V)
RED Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.
*LAMP CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP SELECTOR LEADSREFER


TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS.
INDICATOR
COMMON CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

1LISB_347_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY27 YY27
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
ORG (277V) UNSWITCHED
WHITE BLUE BLUE/WHT
BLUE A.C. RED RED/WHT EMERGENCY BLK (120V)
YEL
RED
Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMPS OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS
COMMON TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LRSB_D_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY28 YY28
TWO BIAX LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
BLUE/WHT
UNSWITCHED
WHITE
RED
A.C. RED/WHT EMERGENCY BLK (120V)
BLUE
Ballast RED BALLAST WHITE COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
LAMP INDICATOR LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
COMMON
CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LISBX_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY29 YY29
TWO LAMP BALLAST

SWITCHED OR
UNSWITCHED
BLACK LINE
RED BLUE ORG (277V)
WHITE BLUE/WHT UNSWITCHED
YELLOW
A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW
Ballast BLUE
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET
VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR

RED OR
LEAD. CAP UNUSED LEAD.

DO NOT MATE CONNECTOR UNTIL


INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER

TEST ACCESSORY LEADS-


REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LMB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY30 YY30
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
ORG (277V) UNSWITCHED
WHITE BLUE BLUE/WHT
A.C. RED
RED/WHT EMERGENCY BLK (120V)
YELLOW
YELLOW
Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMPS OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS
COMMON TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LRSB_D_4

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY31 YY31
THREE LAMP RAPID START BALLAST WITH DIMMING LEAD

DIMMED HOT
SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
ORG (277V)
WHITE BLUE/WHT BLUE/WHT UNSWITCHED
BLUE
BLUE
A.C. RED/WHT EMERGENCY BLK (120V)
RED
YELLOW Ballast RED
RED BALLAST WHITE COMMON
YELLOW YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR

RED OR
LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMPS OPERATION SECTION FOR
COMMON VARIOUS OPTIONS
*AC / EMERGENCY TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3LRSBDL_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY32 YY32
FOUR U-BEND LAMP INSTANT START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE BLUE/WHT UNSWITCHED
YELLOW
A.C. RED RED/WHT EMERGENCY BLK (120V)
YELLOW
Ballast RED
RED BALLAST WHITE COMMON
YEL WHT/BLK

RED/BLK (+)
SELECT PROPER VOLTAGE

VIOLET

VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP*

LAMP*
LAMP

LAMP

LAMP OPERATION SECTION FOR


TBTS / CHARGE VARIOUS OPTIONS.
INDICATOR CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

COMMON
*AC / EMERGENCY

4ULISB_2LEO_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY33 YY33
FOUR LAMP BIAX FULLHAM WORKHORSE BALLAST

SWITCHED OR
UNSWITCHED
LINE
RED BLUE ORG (277V)
BLACK RED BLUE/WHT
UNSWITCHED
WHITE A.C. RED RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast RED RED BALLAST WHITE COMMON
YELLOW WHT/BLK
SELECT PROPER VOLTAGE

RED/BLK (+)
VIOLET

VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED

RED OR
CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
*LAMP
LAMP

LAMP

LAMP SELECTOR LEADS - REFER


LAMP

TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS
INDICATOR
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.

TEST ACCESSORY LEADS-REFER


TO INSTALLATION INSTRUCTIONS
COMMON FOR PROPER POLARITY WIRING.

*AC / EMERGENCY

4LBFWB_160

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY34 YY34
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE LINE
BLUE BLUE/WHT ORG (277V)
WHITE RED RED/WHT
UNSWITCHED
ORG A.C. RED RED
EMERGENCY BLK (120V)
BALLAST
ORG Ballast BROWN
BROWN
YELLOW WHITE
WHT/BLK
COMMON
BLU/WHT YELLOW
BLU/WHT SELECT PROPER VOLTAGE

VIOLET
VIOLET
YELLOW

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
CONNECTOR

RED OR
LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
*LAMP INDICATOR VARIOUS OPTIONS.
TEST ACCESSORY LEADS-
COMMON REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

4LRSB_D_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY35 YY35
THREE BIAX RAPID START BALLAST WITH DIMMING CONTROL

DIMMED HOT ORANGE OR PURPLE


SWITCHED OR
UNSWITCHED
RED LINE
BLACK BLUE ORG (277V)
RED BLUE/WHT
UNSWITCHED
WHITE
BLUE
A.C. RED/WHT EMERGENCY BLK (120V)

BLUE Ballast RED BALLAST WHITE COMMON


YELLOW WHT/BLK

VIOLET

VIOLET
BLUE/WHT

RED/BLK (+)
BLUE/WHT

YELLOW
YELLOW

UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*LAMP

AC POWER IS SUPPLIED.
LAMP
LAMP


LAMP SELECTOR LEADS - REFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.

TEST ACCESSORY LEADS-REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

COMMON
*AC / EMERGENCY

3BXLRSB_DM_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY36 YY36
TWO LAMP RAPID START BALLAST WITH DIMMING LEAD

DIMMED LEAD
SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
ORG (277V)
WHITE BLUE BLUE/WHT UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW RED
YELLOW Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
LAMP

VIOLET

VIOLET
UNIT

WHT/RED
CONNECTOR SELECT PROPER VOLTAGE

RED OR
*LAMP
LEAD. CAP UNUSED LEAD.

DO NOT MATE CONNECTOR UNTIL


INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
TBTS / CHARGE LAMP SELECTOR LEADSREFER
INDICATOR TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
COMMON VARIOUS OPTIONS
*AC / EMERGENCY TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LRSBDL_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY37 YY37
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE LINE
BLUE BLUE/WHT ORG (277V)
WHITE RED RED/WHT
UNSWITCHED
ORG A.C. RED RED
EMERGENCY BLK (120V)
BALLAST
ORG Ballast BROWN
BROWN
YELLOW WHITE
WHT/BLK
COMMON
BLU/WHT YELLOW
BLU/WHT SELECT PROPER VOLTAGE

VIOLET
VIOLET
YELLOW

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
CONNECTOR

RED OR
LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
*LAMP INDICATOR VARIOUS OPTIONS.
TEST ACCESSORY LEADS-
COMMON REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

4LRSB_D_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY38 YY38
THREE BIAX LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE ORG (277V)
BLACK BLUE/WHT
UNSWITCHED
WHITE A.C. BLUE
RED/WHT EMERGENCY BLK (120V)
RED Ballast BLUE
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
SELECT PROPER VOLTAGE

RED/BLK (+)
VIOLET

VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP LAMP SELECTOR LEADS - REFER


TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS
INDICATOR
*LAMP
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.

COMMON
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
*AC / EMERGENCY FOR PROPER POLARITY WIRING.

3LISBX_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY39 YY39
ONE LAMP EMERGENCY ONLY

BLUE ORG (277V)


BLUE/WHT UNSWITCHED
RED/WHT EMERGENCY BLK (120V)
RED WHITE
BALLAST COMMON
YELLOW WHT/BLK

RED/BLK (+)
VIOLET

VIOLET
WHT/RED
UNIT SELECT PROPER VOLTAGE
*LAMP

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*AC / EMERGENCY AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS.
CAP UNUSED LEADS.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LEO_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY40 YY40
TWO LAMP CIRCLINE FULHAM BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED BLUE ORG (277V) LINE
WHITE RED BLUE/WHT
UNSWITCHED
RED A.C. RED/WHT EMERGENCY BLK (120V)
RED Ballast YELLOW
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/BLK
LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP
LAMP SELECTOR LEADS - REFER
*LAMP
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.

TEST ACCESSORY LEADS-REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LCFB_80

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY41 YY41
ONE BIAX LAMP RAPID START BALLAST WITH DIMMING CONTROL

DIMMED HOT
SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE
WHITE BLUE BLUE/WHT ORG (277V)
A.C. RED/WHT EMERGENCY
UNSWITCHED
RED
RED Ballast RED BALLAST BLK (120V)
WHITE
YELLOW COMMON
WHT/BLK

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
TBTS/ CHARGE LAMP OPERATIONS SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

1BXLRSB_DM_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY42 YY42
ONE LAMP BIAX

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE ORG (277V)
BLACK BLUE/WHT
UNSWITCHED
WHITE A.C. BLUE
RED/WHT EMERGENCY BLK (120V)
RED Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS
COMMON
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER

CAP UNUSED LEAD


TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LBX_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY43 YY43
ONE LAMP CIRCLINE INSTANT START FULLHAM BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
WHITE RED BLUE/WHT
UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
Ballast YELLOW
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
VIOLET

VIOLET
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

TBTS/CHARGE LAMP SELECTOR LEADS - REFER


INDICATOR TO INSTALLATION INSTRUCTIONS,
COMMON LAMP OPERATION SECTION FOR
*AC / EMERGENCY VARIOUS OPTIONS.

TEST ACCESSORY LEADS-REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LCISB_80F_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY44 YY44
ONE LAMP CIRCLINE RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
WHITE RED BLUE/WHT
UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
Ballast BLUE
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TBTS/CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMP OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LCRSB2_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY45 YY45
ONE LAMP CIRCLINE RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
WHITE RED BLUE/WHT
UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
Ballast BLUE
WHITE
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP SELECTION LEADSREFER
TBTS/CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMP OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LCRSB_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY46 YY46
ONE LAMP MAGNETIC BALLAST

SWITCHED OR
UNSWITCHED
LINE
RED OR BLUE BLUE ORG (277V)
BLACK BLUE/WHT UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
WHITE Ballast RED BALLAST WHITE COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
UNIT

WHT/RED
SELECT PROPER VOLTAGE
*LAMP

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS/ TO INSTALLATION INSTRUCTIONS,
COMMON CHARGE INDICATOR LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS
*AC / EMERGENCY
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.

TEST ACCESSORY LEADS-REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LMB_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY47 YY47
ONE LAMP PRE-HEAT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
BLUE/WHT
UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
S

VIOLET

VIOLET
RED/BLK (+)
PFC
CAPACITOR UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR

RED OR
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMP OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LPHSB_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY48 YY48
ONE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
WHITE RED BLUE/WHT UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
BLUE
BLUE Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS/CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMPS OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LRSB_48ST_2_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY49 YY49
ONE LAMP TRIAD BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLUE BLUE ORG (277V)
BLACK UNSWITCHED
BLUE/WHT
WHITE A.C. RED/WHT EMERGENCY BLK (120V)
RED Ballast BLUE RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
VIOLET

VIOLET
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMP OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.

TEST ACCESSORY LEADS-REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LTB_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY50 YY50
TWO BIAX RAPID START

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
RED BLUE/WHT
UNSWITCHED
WHITE
YELLOW
A.C. RED/WHT EMERGENCY BLK (120V)
BLUE
YELLOW
Ballast BLUE
RED BALLAST WHITE COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER
*LAMP TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2BXLRSB2_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY51 YY51
TWO BIAX LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
BLUE BLUE/WHT
UNSWITCHED
WHITE
YELLOW
A.C. RED/WHT EMERGENCY BLK (120V)
RED
YELLOW
Ballast RED
RED BALLAST WHITE COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER
*LAMP TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2BXLRSB_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY52 YY52
TWO BIAX LAMP FULLHAM BALLAST TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
RED BLUE ORG (277V)
BLACK BLUE/WHT
UNSWITCHED
WHITE A.C. RED
RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast YELLOW BALLAST WHITE COMMON
RED WHT/BLK

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.

DO NOT MATE CONNECTOR UNTIL


*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

CONNECT BLUE/WHT AND RED/WHT
*LAMP WIRES TOGETHER
TBTS / CHARGE
INDICATOR LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LBXF_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY53 YY53
TWO LAMP CIRCLINE RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
WHITE RED BLUE/WHT
UNSWITCHED
WHITE
BLUE
A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW
YELLOW
Ballast YELLOW
YELLOW
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/BLK
CONNECTOR LEAD. CAP UNUSED LEAD.

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP *LAMP
LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LRSB_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY54 YY54
TWO LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE/WHT ORG (277V)
WHITE RED/WHT
UNSWITCHED
A.C. YELLOW EMERGENCY BLK (120V)

RED Ballast BLUE


RED BALLAST WHITE
COMMON
BLUE WHT/BLK

RED/BLK (+)
LAMP

VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.

DO NOT MATE CONNECTOR UNTIL


INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.

TEST ACCESSORY LEADS-REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LISB_80_3_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY55 YY55
TWO LAMP INSTANT START BALLAST TWO LAMP OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE/WHT
UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
*LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.

DO NOT MATE CONNECTOR UNTIL


INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.

TEST ACCESSORY LEADS-REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LISBESI_2LEO_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY56 YY56
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE
ORG (277V) UNSWITCHED
WHITE RED BLUE/WHT
A.C. BLUE RED/WHT EMERGENCY BLK (120V)
YELLOW
YELLOW
Ballast BLUE
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMPS OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS
COMMON TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

2LRSB_D_5

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY57 YY57
TWO LAMP INSTANT START BALLAST TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
WHITE BLUE/WHT
UNSWITCHED
A.C. RED RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
*LAMP

VIOLET

VIOLET
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMPS OPERATION SECTION FOR
COMMON VARIOUS OPTIONS
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.

TEST ACCESSORY LEADS-REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LISFB2_80_2LEO_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY58 YY58
TWO LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
WHITE RED BLUE/WHT
UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW BLUE
YELLOW Ballast BLUE
RED BALLAST WHITE COMMON
YELLOW WHT/BLK
*LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS/ TO INSTALLATION INSTRUCTIONS,
CHARGE INDICATOR LAMPS OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LRSB_2LEO_48ST_2_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY59 YY59
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK LINE
WHITE BLUE BLUE ORG (277V)
UNSWITCHED
YELLOW/WHT A.C. BLUE BLUE/WHT
BLK (120V)
EMERGENCY
YELLOW Ballast RED
RED/WHT
RED WHITE
YELLOW RED BALLAST COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS/ LAMPS OPERATION SECTION FOR
CHARGE INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

NOTE:
DIMMING WIRE IS NOT AFFECTED BY
THE EM BALLAST

2LRSB_2LEO_SYL_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY60 YY60
ONE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
WHITE RED BLUE/WHT UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
BLUE
BLUE Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS/CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMPS OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LRSB_48ST_2_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY61 YY61
TWO LAMP RAPID START BALLAST TWO LAMP OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
BLUE BLUE/WHT
UNSWITCHED
WHITE
A.C. RED/WHT EMERGENCY BLK (120V)
YELLOW RED
YELLOW Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
SELECT PROPER VOLTAGE

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS,
*LAMP TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON TEST ACCESSORY LEADS-REFER
*AC / EMERGENCY TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LRSB_80_2_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY62 YY62
TWO LAMP SERIES LEAD BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
UNSWITCHED
WHITE BLUE/WHT
BRN OR YEL A.C. RED/WHT EMERGENCY BLK (120V)
BRN OR YEL Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
SELECT PROPER VOLTAGE

VIOLET

VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
RED OR
*LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
TBTS/ VARIOUS OPTIONS
CHARGE INDICATOR
COMMON CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LSL_2LEO_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY63 YY63
TWO LAMP SERIES LEAD BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE/WHT
UNSWITCHED
RED
A.C. RED/WHT EMERGENCY BLK (120V)

RED Ballast BLUE


RED BALLAST WHITE COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
*LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS/ LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS
CHARGE INDICATOR
COMMON
CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LSL_80_2_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY64 YY64
TWO LAMP SERIES LEAD BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
WHITE BLUE/WHT
UNSWITCHED
BROWN
A.C. RED/WHT EMERGENCY BLK (120V)
BROWN Ballast BLUE
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET
VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
*LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS/ LAMPS OPERATION SECTION FOR
CHARGE INDICATOR VARIOUS OPTIONS
COMMON CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER.

TEST ACCESSORY LEADS-REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LSL_80_3_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY65 YY65
TWO LAMP SERIES LEAD BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE/WHT
UNSWITCHED
BRN OR YEL
A.C. RED/WHT EMERGENCY BLK (120V)

BRN OR YEL Ballast RED


RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP SELECT PROPER VOLTAGE

VIOLET

VIOLET
RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED

RED OR
*LAMP CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
TBTS/ VARIOUS OPTIONS
COMMON CHARGE INDICATOR CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.
*AC / EMERGENCY
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LSL_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY66 YY66
THREE BIAX RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLUE LINE
BLACK BLUE ORG (277V)
BLUE BLUE/WHT
UNSWITCHED
WHITE
YELLOW
A.C. RED/WHT EMERGENCY BLK (120V)

YELLOW Ballast RED RED BALLAST WHITE COMMON


RED YELLOW WHT/BLK

VIOLET

VIOLET
RED/WHITE
RED/WHITE

RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
*LAMP
LAMP
LAMP

LAMP SELECTOR LEADS - REFER


TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.

TEST ACCESSORY LEADS-REFER


TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

COMMON
*AC / EMERGENCY

3BXLRSB_80_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY67 YY67
THREE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE YELLOW ORG (277V)
WHITE BLUE/WHT
UNSWITCHED
A.C. BLUE
EMERGENCY BLK (120V)
RED/WHT
YELLOW Ballast BLUE
RED BALLAST WHITE
COMMON
BLUE WHT/BLK

RED/BLK (+)
LAMP

VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LISB2_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY68 YY68
THREE LAMP INSTANT START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE YELLOW ORG (277V)
WHITE BLUE/WHT
UNSWITCHED
A.C. BLUE
EMERGENCY BLK (120V)
RED/WHT
YELLOW Ballast BLUE
RED BALLAST WHITE
COMMON
BLUE WHT/BLK

RED/BLK (+)
LAMP

VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
LAMP CONNECTOR
DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LISB2_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY69 YY69
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE/WHT BLUE ORG (277V)
BLUE/WHT BLUE/WHT UNSWITCHED
WHITE

YELLOW
A.C. BLUE
BLUE
RED/WHT EMERGENCY BLK (120V)

YELLOW Ballast RED


RED
YELLOW
BALLAST WHITE
WHT/BLK
COMMON
RED

RED/BLK (+)

VIOLET
VIOLET
LAMP
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
LAMP
DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LRSB2_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY70 YY70
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED/WHT BLUE ORG (277V)
WHITE RED/WHT BLUE/WHT
UNSWITCHED
A.C. BLUE RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast BLUE
RED
RED BALLAST WHITE COMMON
YELLOW YELLOW WHT/BLK
RED

VIOLET

VIOLET
SELECT PROPER VOLTAGE

RED/BLK (+)
LAMP UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
RED OR
CONNECTOR
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
*LAMP
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS.
COMMON INDICATOR
TEST ACCESSORY LEADS-REFER
*AC / EMERGENCY TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LRSB3_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY71 YY71
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED/WHT BLUE ORG (277V) LINE
WHITE RED/WHT BLUE/WHT
UNSWITCHED
BLUE
BLUE
A.C. RED/WHT EMERGENCY BLK (120V)
RED
YELLOW Ballast RED
RED BALLAST WHITE COMMON
YELLOW YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LRSB4_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY72 YY72
THREE LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE/WHT BLUE ORG (277V)
WHITE BLUE/WHT BLUE/WHT
UNSWITCHED
A.C. BLUE RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast BLUE
RED
RED BALLAST WHITE COMMON
YELLOW YELLOW WHT/BLK
RED

RED/BLK (+)
VIOLET
VIOLET
LAMP UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*LAMP AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LRSB_2LEO2_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY73 YY73
THREE LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
BLACK RED/WHT BLUE ORG (277V) LINE
WHITE RED/WHT BLUE/WHT
UNSWITCHED
A.C. BLUE RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast BLUE
RED
RED BALLAST WHITE COMMON
YELLOW YELLOW WHT/BLK
RED

VIOLET

VIOLET
RED/BLK (+)
LAMP UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*LAMP AC POWER IS SUPPLIED.

LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
COMMON INDICATOR VARIOUS OPTIONS.
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LRSB_2LEO3_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY74 YY74
FOUR LAMP BIAX RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE ORG (277V) LINE
WHITE BLUE BLUE/WHT
UNSWITCHED
YELLOW RED RED/WHT EMERGENCY BLK (120V)
BLUE
RED A.C. RED
BROWN
RED
YEL
BALLAST WHITE
WHT/BLK
COMMON
BROWN
GRAY
Ballast BROWN

VIOLET

VIOLET
RED/BLK (+)
GRAY
UNIT SELECT PROPER VOLTAGE

WHT/RED
GRAY LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
*LAMP

TEST ACCESSORY LEADS-REFER


LAMP

LAMP

LAMP

TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

COMMON
*AC / EMERGENCY

4LBRSB_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY75 YY75
FOUR LAMP FULLHAM BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
RED BLUE/WHT
UNSWITCHED
WHITE
YELLOW
A.C. RED RED/WHT EMERGENCY BLK (120V)
Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
LAMP SELECT PROPER VOLTAGE

RED/BLK (+)
VIOLET

VIOLET
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
*LAMP LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS.
INDICATOR
COMMON CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

4LFB_80_2LEO_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY76 YY76
FOUR LAMP FULLHAM BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
BLUE/WHT
UNSWITCHED
WHITE RED
YELLOW
A.C. RED RED/WHT EMERGENCY BLK (120V)
Ballast RED
RED BALLAST WHITE COMMON
YELLOW WHT/BLK

RED/BLK (+)
LAMP

VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
LAMP

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*LAMP AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

4LFB_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY77 YY77
FOUR LAMP INSTANT START BALLAST WITH THREE LAMPS ONLY

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
BLUE BLUE/WHT
UNSWITCHED
WHITE
YELLOW
A.C. RED
RED/WHT EMERGENCY BLK (120V)

YELLOW
Ballast RED
RED BALLAST WHITE COMMON
YELLOW WHT/BLK
LAMP SELECT PROPER VOLTAGE

RED/BLK (+)
VIOLET

VIOLET
UNIT

WHT/RED
LEAD. CAP UNUSED LEAD.
LAMP

RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
CONNECT BLU/WHT AND RED/WHT
*AC / EMERGENCY WIRES TOGETHER
CAP UNUSED LEAD.
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

4LISB_80_2_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY78 YY78
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE/WHT BLUE ORG (277V)
WHITE BLUE/WHT BLUE/WHT
UNSWITCHED
YELLOW/BLK RED/WHT RED/WHT EMERGENCY BLK (120V)
YELLOW/BLK
YELLOW A.C. RED/WHT
BLUE
RED
YELLOW
BALLAST WHITE
WHT/BLK
COMMON
YELLOW
Ballast BLUE

RED/BLK (+)
SELECT PROPER VOLTAGE

VIOLET

VIOLET
RED
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
RED

RED OR
CONNECTOR
DO NOT MATE CONNECTOR UNTIL
LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
*LAMP TEST ACCESSORY LEADS-REFER
COMMON TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.
*AC / EMERGENCY

4LRSB2_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY79 YY79
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE ORG (277V) LINE
WHITE BLUE BLUE/WHT
UNSWITCHED
YELLOW RED RED/WHT EMERGENCY BLK (120V)
BLUE
RED A.C. RED
BROWN
RED
YELLOW
BALLAST WHITE
WHT/BLK
COMMON
BROWN
GRAY
Ballast BROWN

RED/BLK (+)
VIOLET

VIOLET
GRAY
UNIT SELECT PROPER VOLTAGE

WHT/RED
GRAY LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
*LAMP
COMMON
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
*AC / EMERGENCY FOR PROPER POLARITY WIRING.

4LRSB3_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY80 YY80
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED BLUE ORG (277V) LINE
WHITE RED BLUE/WHT
UNSWITCHED
YELLOW A.C. BLUE/WHT RED/WHT EMERGENCY BLK (120V)
YELLOW
BLUE Ballast BLUE/WHT
BLUE
RED BALLAST WHITE
COMMON
BLUE YELLOW WHT/BLK
BLUE

RED/BLK (+)
VIOLET

VIOLET
LAMP UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

*LAMP LAMP SELECTION LEADSREFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMP OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

4LRSB4_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY81 YY81
FULHAM WORKHORSE BALLAST

SWITCHED OR
UNSWITCHED
LINE
RED BLUE ORG (277V)
BLACK RED BLUE/WHT UNSWITCHED
WHITE A.C. RED RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast RED RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP

*LAMP
LAMP

AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS - REFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMP OPERATION SECTION FOR
VARIOUS OPTIONS
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.

CAP UNUSED LEAD.


COMMON
TEST ACCESSORY LEADS-REFER
*AC / EMERGENCY TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

FWB_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY82 YY82
ONE LAMP CIRCLINE RAPID START BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE BLUE/WHT
UNSWITCHED
A.C. RED/WHT EMERGENCY BLK (120V)
RED
Ballast RED
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
RED/BLK (+)
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
*LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.

LAMP SELECTION LEADSREFER
TBTS/CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMP OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

1LCRSB_80_2_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY83 YY83
ONE LAMP EMERGENCY BALLAST

SWITCHED OR
UNSWITCHED
LINE
BLUE
ORG (277V)
BLACK BLUE/WHT UNSWITCHED
WHITE A.C. RED/WHT EMERGENCY BLK (120V)
Ballast S RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
SELECT PROPER VOLTAGE

VIOLET

VIOLET
RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
*LAMP CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS.
COMMON INDICATOR TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
*AC / EMERGENCY FOR PROPER POLARITY WIRING.

1LEB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY84 YY84
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE LINE
BLUE BLUE/WHT ORG (277V)
WHITE RED RED/WHT
UNSWITCHED
ORG A.C. RED RED
EMERGENCY BLK (120V)
BALLAST
ORG Ballast BROWN
BROWN
YELLOW WHITE
WHT/BLK
COMMON
BLU/WHT YELLOW
BLU/WHT SELECT PROPER VOLTAGE

VIOLET
VIOLET
YELLOW

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
*LAMP INDICATOR VARIOUS OPTIONS.
TEST ACCESSORY LEADS-
COMMON REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3_LRSB_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY85 YY85
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK BLUE/WHT BLUE LINE
ORG (277V)
WHITE BLUE/WHT BLUE/WHT UNSWITCHED
RED
RED
A.C. RED/WHT EMERGENCY BLK (120V)
BLUE
YELLOW Ballast BLUE
RED BALLAST WHITE COMMON
YELLOW YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
*LAMP CONNECTOR

RED OR
LEAD. CAP UNUSED LEAD.
LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMPS OPERATION SECTION FOR
COMMON VARIOUS OPTIONS
*AC / EMERGENCY TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3LRSB_D_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY86 YY86
INSTALACION CON UNA SOLO LAMPARA DE ENCENDIDO INSTANTANEO (INSTANT START LAMP)

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
AZUL AZUL NARANJA (277V)
NEGRO AZUL/BLANCO LINEA SIN
INTERRUPTOR
BLANCO
BALASTRA ROJO/BLANCO BALASTRA DE NEGRO (120V)
ROJO ROJO EMERGENCIA BLANCO
NEUTRAL
AMARILLO BLANCO/NEGRO

ROJO/NEGRO(+)
VIOLETA

VIOLETA
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
CONNECTORES APROPIADO. CANCELAR CABLE
*LAMPARA DE ENCENDIDO NO USADO.
DE LA UNIDAD
NO ACOPLE LOS CONECTORES DE ENCENDIDO

ROJO O
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.

CABLES SELECTOR DE LAMPARA - OBSERVE LAS


INSTRUCCIONES DE INSTALCION, SECCION DE
SELECCION, DE LAMPARA A OPERAR.
INTERUPTOR DE
PRUEBA E INDICADOR CONECTAR LOS SIGUIENTES CABLES JUNTOS
AZUL/BLANCO Y ROJO/BLANCO.
DE CARGA
NEUTRAL PARA LA INSTALACION DEL INTERRUPTOR
*LAMPARA ENCENDIDO DE PRUEBA OBSERVE LAS INSTRUCCIONES
INSTANTANEO OPERADA CONTENIDAS EN EL MANUAL DE INSTALCION.
EN FUNCION REGULAR (C.A.) OBSERVE POLARIDAD DEL ALAMBRADO.
O EN EMERGENCIA

1LISB_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY87 YY87
INSTALACION CON DOS LAMPARAS DE ENCENDIDO INSTANTANEO

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL AZUL NARANJA (277V)
BLANCO AZUL/BLANCO LINEA SIN
BALASTRA ROJO/BLANCO BALASTRA DE NEGRO (120V)
INTERRUPTOR
ROJO EMERGENCIA BLANCO
ROJO AZUL NEUTRAL
AMARILLO
BLANCO/NEGRO
LAMPARA

VIOLETA
VIOLETA
ROJO/NEGRO(+)
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
CONNECTORES
*LAMPARA DE ENCENDIDO APROPIADO. CANCELAR CABLE
DE LA UNIDAD NO USADO.
NO ACOPLE LOS CONECTORES DE ENCENDIDO

ROJO O
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
CABLES SELECTOR DE LAMPARA - OBSERVE LAS
INSTRUCCIONES DE INSTALCION, SECCION DE
SELECCION, DE LAMPARA A OPERAR.

INTERUPTOR DE CONECTAR LOS SIGUIENTES CABLES JUNTOS


AZUL/BLANCO Y ROJO/BLANCO.
PRUEBA E INDICADOR
NEUTRAL DE CARGA PARA LA INSTALACION DEL INTERRUPTOR
DE PRUEBA OBSERVE LAS INSTRUCCIONES
*LAMPARA ENCENDIDO CONTENIDAS EN EL MANUAL DE INSTALCION.
INSTANTANEO OPERADA OBSERVE POLARIDAD DEL ALAMBRADO.
EN FUNCION REGULAR (C.A.)
O EN EMERGENCIA

2LISB_2_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY88 YY88
INSTALACION CON DOS LAMPARAS DE ENCENDIDO INSTANTANEO CON OPERACION DE EMERGENCIA DE DOS LAMPARAS

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL AZUL NARANJA (277V)
BLANCO AZUL/BLANCO LINEA SIN
INTERRUPTOR
BALASTRA ROJO/BLANCO BALASTRA DE NEGRO (120V)
ROJO EMERGENCIA BLANCO
ROJO AZUL NEUTRAL
AMARILLO BLANCO/NEGRO

ROJO/NEGRO(+)
*LAMPARA

VIOLETA

VIOLETA
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
CONNECTORES APROPIADO. CANCELAR CABLE
*LAMPARA DE ENCENDIDO NO USADO.
DE LA UNIDAD

ROJO O
NO ACOPLE LOS CONECTORES DE ENCENDIDO
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
CABLES SELECTOR DE LAMPARA - OBSERVE LAS
INSTRUCCIONES DE INSTALCION, SECCION DE
SELECCION, DE LAMPARA A OPERAR.
INTERUPTOR DE
PRUEBA E INDICADOR CONECTAR LOS SIGUIENTES CABLES JUNTOS
DE CARGA AZUL/BLANCO Y ROJO/BLANCO.
NEUTRAL
PARA LA INSTALACION DEL INTERRUPTOR
*LAMPARA ENCENDIDO DE PRUEBA OBSERVE LAS INSTRUCCIONES
INSTANTANEO OPERADA CONTENIDAS EN EL MANUAL DE INSTALCION.
EN FUNCION REGULAR (C.A.) OBSERVE POLARIDAD DEL ALAMBRADO.
O EN EMERGENCIA

2LISB_2LEO_80_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY89 YY89
INSTALACION CON TRES LAMPARAS DE ENCENDIDO INSTANTANEO

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL AZUL
NARANJA (277V)
BLANCO AZUL/BLANCO LINEA SIN
INTERRUPTOR
AZUL ROJO/BLANCO BALASTRA DE
BALASTRA ROJO EMERGENCIA
NEGRO (120V)
BLANCO
ROJO AZUL NEUTRAL
AMARILLO BLANCO/NEGRO

VIOLETA

VIOLETA
LAMPARA

ROJO/NEGRO(+)
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
CONNECTORES
LAMPARA DE ENCENDIDO APROPIADO. CANCELAR CABLE
DE LA UNIDAD NO USADO.

ROJO O
*LAMPARA NO ACOPLE LOS CONECTORES DE ENCENDIDO
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
CABLES SELECTOR DE LAMPARA - OBSERVE LAS
INSTRUCCIONES DE INSTALCION, SECCION DE
SELECCION, DE LAMPARA A OPERAR.
INTERUPTOR DE
PRUEBA E INDICADOR CONECTAR LOS SIGUIENTES CABLES JUNTOS
DE CARGA AZUL/BLANCO Y ROJO/BLANCO.
NEUTRAL
PARA LA INSTALACION DEL INTERRUPTOR
*LAMPARA ENCENDIDO DE PRUEBA OBSERVE LAS INSTRUCCIONES
INSTANTANEO OPERADA CONTENIDAS EN EL MANUAL DE INSTALCION.
EN FUNCION REGULAR (C.A.) OBSERVE POLARIDAD DEL ALAMBRADO.
O EN EMERGENCIA

3LISB_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY90 YY90
INSTALACION CON CUATRO LAMPARAS DE ENCENDIDO INSTANTANEO

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL AZUL
NARANJA (277V)
BLANCO AZUL AZUL/BLANCO LINEA SIN
INTERRUPTOR
AMARILLO BALASTRA ROJO ROJO/BLANCO BALASTRA DE NEGRO (120V)
ROJO EMERGENCIA BLANCO
NEUTRAL
AMARILLO ROJO
AMARILLO BLANCO/NEGRO
LAMPARA

ROJO/NEGRO(+)
VIOLETA

VIOLETA
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
CONNECTORES APROPIADO. CANCELAR CABLE
LAMPARA DE ENCENDIDO NO USADO.
DE LA UNIDAD
LAMPARA
NO ACOPLE LOS CONECTORES DE ENCENDIDO

ROJO O
DE LA UNIDAD HASTA QUE TODA LA
*LAMPARA INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.

CABLES SELECTOR DE LAMPARA - OBSERVE LAS


INSTRUCCIONES DE INSTALCION, SECCION DE
SELECCION, DE LAMPARA A OPERAR.
INTERUPTOR DE CONECTAR LOS SIGUIENTES CABLES JUNTOS
PRUEBA E INDICADOR AZUL/BLANCO Y ROJO/BLANCO.
DE CARGA
NEUTRAL PARA LA INSTALACION DEL INTERRUPTOR
DE PRUEBA OBSERVE LAS INSTRUCCIONES
*LAMPARA ENCENDIDO CONTENIDAS EN EL MANUAL DE INSTALCION.
INSTANTANEO OPERADA OBSERVE POLARIDAD DEL ALAMBRADO.
EN FUNCION REGULAR (C.A.)
O EN EMERGENCIA

4LISB_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY91 YY91
INSTALACION CON UNA SOLA LAMPARA DE ENCENDIDO RAPIDO (RAPID START LAMP)

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL AZUL
NARANJA (277V)
BLANCO AZUL AZUL/BLANCO LINEA SIN
ROJO BLANCO BALASTRA DE INTERRUPTOR
ROJO BALASTRA NEGRO (120V)
ROJO EMERGENCIA BLANCO
ROJO NEUTRAL
AMARILLO BLANCO/NEGRO

ROJO/NEGRO(+)

VIOLETA

VIOLETA
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
*LAMPARA CONNECTORES APROPIADO. CANCELAR CABLE
DE ENCENDIDO NO USADO.
DE LA UNIDAD
NO ACOPLE LOS CONECTORES DE ENCENDIDO

ROJO O
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
CABLES SELECTOR DE LAMPARA - OBSERVE LAS
INSTRUCCIONES DE INSTALCION, SECCION DE
SELECCION, DE LAMPARA A OPERAR.
INTERUPTOR DE
PRUEBA E INDICADOR PARA LA INSTALACION DEL INTERRUPTOR
DE PRUEBA OBSERVE LAS INSTRUCCIONES
NEUTRAL DE CARGA CONTENIDAS EN EL MANUAL DE INSTALCION.
OBSERVE POLARIDAD DEL ALAMBRADO.
*LAMPARA ENCENDIDO
RAPIDO OPERADA EN
FUNCION REGULAR (C.A.)
O EN EMERGENCIA

1LRSB_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY92 YY92
INSTALACION CON DOS LAMPARAS DE ENCENDIDO RAPIDO CON OPERACION DE EMERGENCIA DE DOS LAMPARAS

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL AZUL NARANJA (277V)
BLANCO AZUL AZUL/BLANCO
LINEA SIN
INTERRUPTOR
ROJO/BLANCO BALASTRA DE NEGRO (120V)
AMARILLO BALASTRA ROJO EMERGENCIA BLANCO
ROJO NEUTRAL
AMARILLO ROJO
AMARILLO BLANCO/NEGRO

ROJO/NEGRO(+)
*LAMPARA SELECCIONAR CABLE DE VOLTAGE

VIOLETA

VIOLETA
BLANCO/ROJO
CONNECTORES APROPIADO. CANCELAR CABLE
*LAMPARA DE ENCENDIDO NO USADO.
DE LA UNIDAD NO ACOPLE LOS CONECTORES DE ENCENDIDO

ROJO O
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
CABLES SELECTOR DE LAMPARA - OBSERVE LAS
INSTRUCCIONES DE INSTALCION, SECCION DE
SELECCION, DE LAMPARA A OPERAR.
INTERUPTOR DE
PRUEBA E INDICADOR PARA LA INSTALACION DEL INTERRUPTOR
DE CARGA DE PRUEBA OBSERVE LAS INSTRUCCIONES
NEUTRAL CONTENIDAS EN EL MANUAL DE INSTALCION.
OBSERVE POLARIDAD DEL ALAMBRADO.
*LAMPARA ENCENDIDO
RAPIDO OPERADA EN
FUNCION REGULAR (C.A.)
O EN EMERGENCIA

2LRSB_2LEO_80_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY93 YY93
INSTALACION CON DOS LAMPARAS DE ENCENDIDO RAPIDO

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO ROJO AZUL
NARANJA (277V)
BLANCO ROJO AZUL/BLANCO LINEA SIN
ROJO/BLANCO BALASTRA DE INTERRUPTOR
AMARILLO BALASTRA AZUL NEGRO (120V)
ROJO EMERGENCIA BLANCO
AMARILLO AZUL NEUTRAL
AMARILLO BLANCO/NEGRO
LAMPARA

ROJO/NEGRO(+)

VIOLETA
VIOLETA
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
CONNECTORES APROPIADO. CANCELAR CABLE
*LAMPARA DE ENCENDIDO NO USADO.
DE LA UNIDAD

ROJO O
NO ACOPLE LOS CONECTORES DE ENCENDIDO
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
CABLES SELECTOR DE LAMPARA - OBSERVE LAS
INSTRUCCIONES DE INSTALCION, SECCION DE
SELECCION, DE LAMPARA A OPERAR.
INTERUPTOR DE
PRUEBA E INDICADOR PARA LA INSTALACION DEL INTERRUPTOR
DE CARGA DE PRUEBA OBSERVE LAS INSTRUCCIONES
NEUTRAL CONTENIDAS EN EL MANUAL DE INSTALCION.
*LAMPARA ENCENDIDO OBSERVE POLARIDAD DEL ALAMBRADO.
RAPIDO OPERADA EN
FUNCION REGULAR (C.A.)
O EN EMERGENCIA

2LRSB_D_5_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY94 YY94
INSTALACION CON TRES LAMPARAS DE ENCENDIDO RAPIDO

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL/BLANCO AZUL
NARANJA (277V)
BLANCO AZUL/BLANCO AZU/BLANCO LINEA SIN
AZUL INTERRUPTOR
ROJO/BLANCO BALASTRA DE
AZUL BALASTRA ROJO NEGRO (120V)
AMARILLO ROJO EMERGENCIA BLANCO
NEUTRAL
ROJO
AMARILLO AMARILLO BLANCO/NEGRO
LAMPARA

ROJO/NEGRO(+)
SELECCIONAR CABLE DE VOLTAGE

VIOLETA

VIOLETA
CONNECTORES

BLANCO/ROJO
APROPIADO. CANCELAR CABLE
*LAMPARA DE ENCENDIDO NO USADO.
DE LA UNIDAD
LAMPARA NO ACOPLE LOS CONECTORES DE ENCENDIDO

ROJO O
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.

CABLES SELECTOR DE LAMPARA - OBSERVE LAS


INSTRUCCIONES DE INSTALCION, SECCION DE
SELECCION, DE LAMPARA A OPERAR.
INTERUPTOR DE PARA LA INSTALACION DEL INTERRUPTOR
PRUEBA E INDICADOR DE PRUEBA OBSERVE LAS INSTRUCCIONES
DE CARGA CONTENIDAS EN EL MANUAL DE INSTALCION.
NEUTRAL
OBSERVE POLARIDAD DEL ALAMBRADO.
*LAMPARA ENCENDIDO
RAPIDO OPERADA EN
FUNCION REGULAR (C.A.)
O EN EMERGENCIA

3LRSB_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY95 YY95
INSTALACION CON UNA SOLA LAMPARA DE ENCENDIDO RAPIDO

LINE CON O
SIN INTERRUPTOR
PRINCIPAL
NEGRO AZUL AZUL NARANJA (277V)
BLANCO AZUL AZUL/BLANCO LINEA SIN
INTERRUPTOR
ROJO/BLANCO BALASTRA DE NEGRO (120V)
AMARILLO BALASTRA ROJO
ROJO EMERGENCIA BLANCO
AMARILLO ROJO NEUTRAL
AMARILLO BLANCO/NEGRO

VIOLETA
VIOLETA
LAMPARA

ROJO/NEGRO(+)
SELECCIONAR CABLE DE VOLTAGE

BLANCO/ROJO
CONNECTORES
*LAMPARA DE ENCENDIDO APROPIADO. CANCELAR CABLE
DE LA UNIDAD NO USADO.

ROJO O
NO ACOPLE LOS CONECTORES DE ENCENDIDO
DE LA UNIDAD HASTA QUE TODA LA
INSTALCION ESTE COMPLETA Y LA LINEA DE
CORRIENTE ESTE ACTIVADA.
CABLES SELECTOR DE LAMPARA - OBSERVE LAS
INSTRUCCIONES DE INSTALCION, SECCION DE
SELECCION, DE LAMPARA A OPERAR.
INTERUPTOR DE
PRUEBA E INDICADOR PARA LA INSTALACION DEL INTERRUPTOR
DE CARGA DE PRUEBA OBSERVE LAS INSTRUCCIONES
NEUTRAL CONTENIDAS EN EL MANUAL DE INSTALCION.
*LAMPARA ENCENDIDO OBSERVE POLARIDAD DEL ALAMBRADO.
RAPIDO OPERADA EN
FUNCION REGULAR (C.A.)
O EN EMERGENCIA

2LRSB_D_SP

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY96 YY96
TWO LAMP LAG BALLAST

SWITCHED OR
UNSWITCHED
YELLOW LINE
BLACK BLUE ORG (277V)
WHITE YELLOW BLUE/WHT UNSWITCHED
BLK/WHT A.C. RED/WHT EMERGENCY BLK (120V)
BLUE Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
*LAMP SELECT PROPER VOLTAGE

RED/BLK (+)
VIOLET

VIOLET
LEAD. CAP UNUSED LEAD.
UNIT

WHT/RED
RED OR
DISCONNECT LAMP HOLDER CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER


DISCONNECT LAMP HOLDER TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
LPTS / CHARGE VARIOUS OPTIONS.
INDICATOR
COMMON TEST ACCESSORY LEADS - REFER
*AC / EMERGENCY TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LLAG_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY97 YY97
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED BLUE LINE
RED BLUE/WHT ORG (277V)
WHITE ORANGE RED/WHT
UNSWITCHED
BLUE A.C. ORANGE RED
EMERGENCY BLK (120V)
BALLAST
BLUE Ballast YELLOW
YELLOW
YELLOW WHITE
WHT/BLK
COMMON
BLU/WHT BROWN
BLU/WHT SELECT PROPER VOLTAGE

VIOLET
VIOLET
BROWN

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
*LAMP INDICATOR VARIOUS OPTIONS.
TEST ACCESSORY LEADS-
COMMON REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3_LRSB_D_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY98 YY98
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK YELLOW BLUE LINE
YELLOW BLUE/WHT ORG (277V)
WHITE BROWN RED/WHT
UNSWITCHED
BLU/WHT A.C. BROWN RED
EMERGENCY BLK (120V)
BALLAST
BLU/WHT Ballast BLUE
BLUE
YELLOW WHITE
WHT/BLK
COMMON
ORG RED
ORG SELECT PROPER VOLTAGE

VIOLET
VIOLET
RED

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
CONNECTOR

RED OR
LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
*LAMP INDICATOR VARIOUS OPTIONS.
TEST ACCESSORY LEADS-
COMMON REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

4LRSB_D_4

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY99 YY99
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK LINE
WHITE BLUE (A1) BLUE ORG (277V)
UNSWITCHED
GREEN (A4) A.C. BLUE (A2) BLUE/WHT
BLK (120V)
EMERGENCY
YELLOW (A3) Ballast RED (A6)
RED/WHT
RED WHITE
YELLOW (A5) RED (A7) BALLAST COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS/ LAMPS OPERATION SECTION FOR
CHARGE INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

NOTE:
DIMMING WIRE IS NOT AFFECTED BY
THE EM BALLAST

2LRSB_2LEO_SYL_D_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY100 YY100
THREE LAMP RAPID START BALLAST

SWITCHED OR
BLACK UNSWITCHED
LINE
WHITE BLUE (A1) BLUE ORG (277V)
YELLOW (A3) BLUE (A2) BLUE/WHT UNSWITCHED
GREEN (A4)
YELLOW (B3) A.C. BLUE (B1)
BLUE (B2)
RED/WHT EMERGENCY BLK (120V)
GREEN (B4)
YELLOW (B5)
Ballast RED (B6)
RED
YELLOW
BALLAST WHITE
WHT/BLK
COMMON
RED (B7)

RED/BLK (+)

VIOLET
VIOLET
LAMP
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
LAMP
DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LRSB5_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY101 YY101
THREE LAMP RAPID START BALLAST

SWITCHED OR
BLACK UNSWITCHED
LINE
WHITE BLUE (B1) BLUE ORG (277V)
YELLOW (A3) BLUE (B2) BLUE/WHT UNSWITCHED
GREEN (A4)
YELLOW (B3) A.C. BLUE (A1)
BLUE (A2)
RED/WHT EMERGENCY BLK (120V)
GREEN (B4)
YELLOW (B5)
Ballast RED (B6)
RED
YELLOW
BALLAST WHITE
WHT/BLK
COMMON
RED (B7)

RED/BLK (+)

VIOLET
VIOLET
LAMP
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
LAMP
DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LRSB6_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY102 YY102
TWO LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK LINE
WHITE BLUE (A1) BLUE ORG (277V)
UNSWITCHED
GREEN (A4) A.C. BLUE (A2) BLUE/WHT
BLK (120V)
EMERGENCY
YELLOW (A3) Ballast RED (A6)
RED/WHT
RED WHITE
YELLOW (A5) RED (A7) BALLAST COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS/ LAMPS OPERATION SECTION FOR
CHARGE INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

NOTE:
DIMMING WIRE IS NOT AFFECTED BY
THE EM BALLAST

2LRSB_2LEO_SYL_D_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY103 YY103
THREE LAMP RAPID START BALLAST TWO LAMP EMERGENCY OPERATION

SWITCHED OR
BLACK UNSWITCHED
LINE
WHITE BLUE (B1) BLUE ORG (277V)
YELLOW (A3) BLUE (B2) BLUE/WHT UNSWITCHED
GREEN (A4)
YELLOW (B3) A.C. BLUE (A1)
BLUE (A2)
RED/WHT EMERGENCY BLK (120V)
GREEN (B4)
YELLOW (B5)
Ballast RED (B6)
RED
YELLOW
BALLAST WHITE
WHT/BLK
COMMON
RED (B7)

RED/BLK (+)

VIOLET
VIOLET
*LAMP
UNIT SELECT PROPER VOLTAGE

WHT/RED
LEAD. CAP UNUSED LEAD.

RED OR
CONNECTOR
LAMP
DO NOT MATE CONNECTOR UNTIL
*LAMP INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS.
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

3LRSB_2LEO4_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY104 YY104
FOUR LAMP RAPID START BALLAST

SWITCHED OR
BLUE/WHT BLUE
UNSWITCHED
BLACK BLUE/WHT BLUE/WHT
LINE
RED/WHT
WHITE A.C. RED/WHT
BLUE RED/WHT EMERGENCY
ORG (277V)
UNSWITCHED
YELLOW Ballast BLUE RED BALLAST BLK (120V)
RED WHITE
YELLOW RED COMMON
YELLOW WHT/BLK
LAMP SELECT PROPER VOLTAGE

VIOLET

VIOLET
UNIT LEAD. CAP UNUSED LEAD.

RED/BLK (+)
LAMP

WHT/RED
CONNECTOR DO NOT MATE CONNECTOR UNTIL

RED OR
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.
*LAMP LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
TBTS / CHARGE
TEST ACCESSORY LEADS-REFER
INDICATOR TO INSTALLATION INSTRUCTIONS
COMMON FOR PROPER POLARITY WIRING.
*AC / EMERGENCY

4LRSB_D_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY105 YY105
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED BLUE ORG (277V) LINE
WHITE RED BLUE/WHT
UNSWITCHED
YELLOW A.C. BLUE/WHT RED/WHT EMERGENCY BLK (120V)
YELLOW
BROWN Ballast BLUE/WHT
BLUE
RED BALLAST WHITE
COMMON
BROWN YELLOW WHT/BLK
BLUE

RED/BLK (+)
VIOLET

VIOLET
LAMP UNIT

WHT/RED
SELECT PROPER VOLTAGE

RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
LAMP
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

*LAMP LAMP SELECTION LEADSREFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMP OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

4LRSB5_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY106 YY106
ONE LAMP RAPID START BALLAST FOR USE WITH OSRAM/DIMMING

VIOLET (+)
GREY (-)

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE BLUE/WHT
A.C. RED/WHT EMERGENCY BLK (120V)
UNSWITCHED
RED
RED Ballast RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
SELECT PROPER VOLTAGE

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.
*LAMP

WHT/RED
CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMPS OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

1LRSB_D_DIMMING_OSRAM

NOTES
FOR REVERSED REDS AND BLUES SEE YY107

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY107 YY107
ONE LAMP RAPID START BALLAST FOR USE WITH OSRAM/DIMMING

VIOLET (+)
GREY (-)

SWITCHED OR
UNSWITCHED
LINE
BLACK RED BLUE ORG (277V)
WHITE RED BLUE/WHT
BLUE
A.C. RED/WHT EMERGENCY BLK (120V)
UNSWITCHED

BLUE Ballast RED BALLAST WHITE


COMMON
YELLOW WHT/BLK

VIOLET

VIOLET
SELECT PROPER VOLTAGE

RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.
*LAMP

WHT/RED
CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMPS OPERATION SECTION FOR
INDICATOR VARIOUS OPTIONS
COMMON
*AC / EMERGENCY TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

1LRSB_D_DIMMING_OSRAM_A

NOTES
FOR REVERSED REDS AND BLUES SEE YY106

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY108 YY108
TWO LAMP RAPID START BALLAST FOR USE WITH OSRAM/DIMMING

VIOLET (+)
GREY (-)

SWITCHED OR
UNSWITCHED
LINE
BLACK
WHITE BLUE BLUE ORG (277V)
YELLOW/WHT A.C. BLUE BLUE/WHT
BLK (120V)
UNSWITCHED
EMERGENCY
YELLOW Ballast RED
RED/WHT
RED WHITE
YELLOW RED BALLAST COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS/ TO INSTALLATION INSTRUCTIONS,
CHARGE INDICATOR LAMPS OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LRSB_D_DIMMING_OSRAM

NOTES
FOR REVERSED REDS AND BLUES SEE YY109

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY109 YY109
TWO LAMP RAPID START BALLAST FOR USE WITH OSRAM/DIMMING

VIOLET (+)
GREY (-)

SWITCHED OR
UNSWITCHED
LINE
BLACK
WHITE RED BLUE ORG (277V)
YELLOW/WHT A.C. RED BLUE/WHT
BLK (120V)
UNSWITCHED
EMERGENCY
YELLOW Ballast BLUE
RED/WHT
RED WHITE
YELLOW BLUE BALLAST COMMON
YELLOW WHT/BLK
LAMP

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED

RED OR
*LAMP CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TBTS/ TO INSTALLATION INSTRUCTIONS,
CHARGE INDICATOR LAMPS OPERATION SECTION FOR
COMMON VARIOUS OPTIONS.
*AC / EMERGENCY
TEST ACCESSORY LEADS-REFER
TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

2LRSB_D_DIMMING_OSRAM

NOTES
FOR REVERSED REDS AND BLUES SEE YY108

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY110 YY110
FULHAM WORKHORSE BALLAST

SWITCHED OR
UNSWITCHED
LINE
RED BLUE ORG (277V)
BLACK RED BLUE/WHT
UNSWITCHED
WHITE A.C. RED RED/WHT EMERGENCY BLK (120V)
YELLOW Ballast RED

RED BALLAST WHITE
COMMON
YELLOW WHT/BLK

RED/BLK (+)
VIOLET

VIOLET
UNIT SELECT PROPER VOLTAGE

WHT/RED
RED OR
CONNECTOR LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP

*LAMP

AC POWER IS SUPPLIED.

LAMP SELECTOR LEADS - REFER
TBTS / CHARGE TO INSTALLATION INSTRUCTIONS,
INDICATOR LAMP OPERATION SECTION FOR
VARIOUS OPTIONS
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER.

CAP UNUSED LEAD.


COMMON
TEST ACCESSORY LEADS-REFER
*AC / EMERGENCY TO INSTALLATION INSTRUCTIONS
FOR PROPER POLARITY WIRING.

FWB_80_D_2

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY111 YY111
THREE LAMP INSTANT START BALLAST WITH TWO LAMPS ONLY

SWITCHED OR
UNSWITCHED
LINE
BLACK BLUE BLUE ORG (277V)
WHITE BLUE/WHT UNSWITCHED
A.C. BLUE RED/WHT EMERGENCY BLK (120V)
RED Ballast BLUE
RED BALLAST WHITE
COMMON
YELLOW WHT/BLK
SELECT PROPER VOLTAGE

VIOLET

VIOLET
RED/BLK (+)
UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
LAMP

RED OR
CONNECTOR DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
*LAMP AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS.
COMMON INDICATOR CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
*AC / EMERGENCY
TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3LISB_D_3

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY112 YY112
THREE LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED BLUE LINE
RED BLUE/WHT ORG (277V)
WHITE RED/WHT
UNSWITCHED
EMERGENCY
RED/VIO
A.C. YELLOW
RED
YELLOW BALLAST
BLK (120V)
WHITE
RED/BLK
RED/WHT Ballast YLW/BLK WHT/BLK
COMMON

YELLOW
BLUE SELECT PROPER VOLTAGE

VIOLET
VIOLET
RED/BLK (+)
BLUE UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
CONNECTOR

RED OR
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.

LAMP
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
*LAMP INDICATOR VARIOUS OPTIONS.
TEST ACCESSORY LEADS-
COMMON REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3_LRSB_D_4

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY113 YY113
FOUR LAMP RAPID START BALLAST

SWITCHED OR
UNSWITCHED
BLACK RED BLUE LINE
RED BLUE/WHT ORG (277V)
WHITE RED/WHT
UNSWITCHED
RED/VIO RED
EMERGENCY BLK (120V)
YELLOW
RED/BLK A.C. YLW/BLK
YELLOW BALLAST WHITE
WHT/BLK
COMMON
RED/WHT Ballast YELLOW
BLU/VIO SELECT PROPER VOLTAGE

VIOLET
VIOLET
RED/BLK (+)
BLUE
BLU/BLK UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
BLUE
CONNECTOR

RED OR
BLU/WHT
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.
LAMP LAMP SELECTION LEADSREFER
LAMP TO INSTALLATION INSTRUCTIONS,
TBTS / CHARGE LAMP OPERATION SECTION FOR
*LAMP INDICATOR VARIOUS OPTIONS.
TEST ACCESSORY LEADS-
COMMON REFER TO INSTALLATION
*AC / EMERGENCY INSTRUCTIONS FOR PROPER
POLARITY WIRING.

4_LRSB_D_5

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com


YY114 YY114
THREE LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION

SWITCHED OR
UNSWITCHED
BLACK BLUE BLUE LINE
WHITE ORG (277V) UNSWITCHED
BLUE BLUE/WHT
BLUE/WHT A.C. YELLOW
RED/WHT EMERGENCY BLK (120V)
BLUE/WHT
RED
Ballast YELLOW
RED BALLAST WHITE COMMON
YELLOW WHT/BLK
RED

VIOLET

VIOLET

RED/BLK (+)
SELECT PROPER VOLTAGE
*LAMP UNIT LEAD. CAP UNUSED LEAD.

WHT/RED
CONNECTOR

RED OR
*LAMP DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
LAMP AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
TBTS / CHARGE VARIOUS OPTIONS.
INDICATOR
COMMON TEST ACCESSORY LEADS-
*AC / EMERGENCY REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.

3LRSB_2LEO5_80_D

NOTES

phone (520)-294-3292 FAX (520) 741-2837 WEB www.iotaengineering.com