What is a hazardous area?
A hazardous area is a place where concentrations of flammable gases, vapors or dusts occur.
Electrical equipment installed in these environments is specifically designed and tested to ensure
they dont initiate an explosion caused by arcing contacts or high surface temperature of equipment.
step
The hazard level of the gases and dusts increases from gas groups IIA to IIC
and dust groups IIIA to IIIC/ The most severe in both cases being IIC and IIIC
2
STEP 2: What type of zone?
2
Examples of hazardous area zones
step
Zone 0
Zone 1
Zone 2
Zone Area in which an explosive gas-air mixture is continuously present or present for long
0 periods
Zone Area in which an explosive gas-air mixture is likely to occur for short periods in normal
1 operation
Zone Area in which an explosive gas-air mixture is not likely to occur, and if it occurs it will
2 only exist for a very short time due to an abnormal condition
Zone 20
Zone 21
Zone 22
DUST
Zone Area in which an explosive dust-air mixture is continuously present or present for long
20 periods
Zone Combustible or conductive dusts are present and is likely to occur for short periods in
21 normal operation
Zone Area in which an explosive dust mixture is not likely to occur, and if it occurs it will only
22 exist for a very short time due to an abnormal condition
3
3
STEP 3: Product selection
Series Selection
step
Protection Page
Product Series Description Zone(s)
Method No.
4
Series Selection
Protection Page
Product Series Description Zone(s)
Method No.
Types of protection
To protect installations from potential explosion a method of analysing and classifying a
potentially hazardous area is required
This is to ensure correct selection and installation of equipment to prevent explosion and
ensure safety of life.
Non-sparking
Ex n
IECEx 60079-15
5
HAE Certified IEC Ex workshop:
NHP supplies not only the Cortem range of hazardous area equipment, but
equally important, customer specific systems via our assembly workshop
located at our National Distribution and Manufacturing Centre in Melbourne.
In this workshop, accredited staff design, construct and inspect the Cortem
range according to the requirements of IECEx certification. It allows for
flexibility to produce custom solutions to suit your HAE requirements
including:
The NHPEx workshop enables both expeditious and effective solutions for
customers and operates under stringent quality assurance guidelines.
Distribution panels
Motor control
Control stations
Automation solutions.
6
Fluorescent Lighting:
EXEL Series
T
Zones 1, 2 and 21, 22 Wattage 1) Voltage Operation Mounting 2) rating Cat. No.
IECEx CES 07.0001 2 x M8
2 x 18 W 230 V Normal T5 EXEL218MAU
Ex ed IIC T5 moulded thread
Ex tb T95C 2 x M8
2 x 36 W 230 V Normal T5 EXEL236MAU
IP 66 moulded thread
Ambient Temp. / Temp. Class / 2 x M8
2 x 18 W 110/230 V Normal + Emergency 3) T5 EXEL218EF4AU*
Max Surface Temp. moulded thread
-40C +55C / T5 / 95C 2 x M8
2 x 36 W 110/230 V Normal + Emergency 3) T5 EXEL236EF4AU
moulded thread
1
) 1 x 18 W and 1 x 36 W options also available
2
) Brackets not included see page 9
3
) Exit lighting available on request
Note: Datasheet available on NHP Corporate Website. Lamps not included.
*Through wiring not available
EXEN Series
Great mechanical strength Shock and UV resistant (body and diffuser)
High protection against corrosion, dust, water Loop-in/ loop-out connection on both sides
and humidity Suitable for fluorescent tubes up to 2 x 36 W
Single-channel 230 V electronic ballast Through wiring
Opening and closing slide system controlled EOL ballast (end of life)
by an hexagonal wrench
Brass earthing plates
T
Zones 2 and 21, 22 Wattage 1) Voltage Operation Mounting 2) rating Cat. No.
IECEx CES 12.0010 2 x M8
2 x 18 W 230 V Normal T5 EXEN218AU
Ex nA IIC T5/T4 Gc moulded thread
Ex tb IIIC T65C to T85C Db 2 x M8
IP 66 2 x 36 W 230 V Normal T5 EXEN236AU
moulded thread
Ambient Temp. / Temp. Class /
Max Surface Temp. 2 x M8
2 x 18 W 230 V Normal + Emergency 3) T5 EXEN218EF4AU*
-40C +40C / T5 / 65C moulded thread
-40C +50C / T5 / 80C 2 x M8
-40C +55C / T4 / 85C 2 x 36 W 230 V Normal + Emergency 3) T5 EXEN236EF4AU
moulded thread
1
) 1 x 18 W and 1 x 36 W options also available
2
) Brackets not included see page 9
3
) Exit lighting available on request
Note: Datasheet available on NHP Corporate Website. Lamps not included.
*Through wiring not available
7
Fluorescent Lighting:
FLFE Series
Aluminium alloy with low copper content FLFE fixtures have an Ex e internal terminal
Borosilicate glass tube heat resistant junction box which allows the connection with
an Ex e cable gland (not barrier)
Internal white painted aluminium reflector
EOL ballast (end of life)
Excellent CX coefficient, less wind resistance
and less accumulation of dust
Pendant Lighting:
8
Mounting Accessories:
G-258 G-0480
9
Flood Lighting:
EWL-80 Series
Equipped with cooling fins for better heat Simple installation and continuous illumination
dissipation even in the event of failure of some LEDs
High performance in terms of reliability, safety, EWL-80 fixtures have an Ex e internal terminal
efficiency and energy savings junction box which allows the connection with
Life-cycle of 100,000 hours, unalterable an Ex e cable gland (not barrier)
brightness and light quality 65 W LED plate designed to replace traditional
As lighting fixture, the LED plate can be 150 W metal halide lamps, 250 W mercury
accompanied by an optics that vary the focus lamps and 500 W incandescent lamps
Tiger Series
Ideal for lighting large areas Fast maintenance
High degree of protection IP 66 Anti-corrosion aluminium clips
Suitable for the use in all environments where Flat glass anti-light pollution
climatic conditions are extreme Suitable for lamps up to 400 W
10
Flood Lighting:
SLEE Series
Designed for lighting large indoor and outdoor Low copper content Aluminium alloy body
areas Accessories available for pole mounting and
High degree of mechanical protection IP 67 angled bracket mounting
Shock proof & temperature resistant tempered Reinforced supporting bracket for mounting
front glass on mobile structures available
Electrical connections made via an Ex e
enclosure
H Series
Intrinsically Safe LED hand & head lamps, ideal HHL Hand Held Lamp
for work in harsh conditions Survives a 2 meter drop test
Shock resistant body made from Polypropylene Lasts 1 meter underwater
Transparent unbreakable polycarbonate lens Built in carabineer clip
Neoprene gasket resistant to acids and HEL Head Lamp
hydrocarbons
Survives a 4 meter drop test
Water resistant
Adjustable head band
Zone 0, 1, 2
Luminous Discharge Weight
IECEx UL 07.0008
Flux Time Batteries (kg) T Rating Cat. No.
Ex ia I/IIC T4
IP 67 30 20 hours 2x AA 0.116 T4 HHL20
Ambient Temp. / Temp. Class
45 70 hours 2x D 0.448 T4 HHL70
-20C to +50C / T4 /
75 15 hours 3x AA 0.234 T4 HEL15
11
Terminal Boxes & Custom Assemblies:
Can be used either as junction boxes with/ Available with window on cover
without terminals or for installation of electrical Body and cover can be drilled and threaded by
equipment such as circuit breakers, signals, the NHPEx workshop according to customers
remote control switches, transformers specification
Note: More sizes available. Contact NHP for quote and for further information
12
EJB Series Motor Starters
Max
Enclosure Starting
Power (kW) Max Voltage Max Current Dissipated
Type Method
Power
2.2 kW 400 V 5A 140 W EJB-1A DOL
4 kW 400 V 9A 140 W EJB-1A DOL
5.5 kW 400 V 11 A 180 W EJB-3BA Reverse
5.5 kW 400 V 11 A 140 W EJB-1A DOL
7.5 kW 400 V 14 A 180 W EJB-3BA Reverse
7.5 kW 400 V 14 A 140 W EJB-1A DOL
Zone 1, 2 and 21, 22 11 kW 400 V 21 A 140 W EJB-1A DOL
IECEx TSA 06.0011
Ex d IIB + H2 T5/T6 15 kW 400 V 21 A 140 W EJB-1A DOL
Ex tD A21 IP 66/67 22 kW 400 V 40 A 350 W EJB-4A Star-Delta
Ambient temperature Contact NHP for quote and for further information
-20C +55C
Standard Motor Starters
Enclosure
Description Cat. No.
Type
Ex d 415 V DOL starter 7.5 kW EJB-1A EJB1A4DOL7
Ex d 415 V DOL starter 15 kW EJB-1A EJB1A4DOL15
Operators and equipment that can be used and Circuit breaker control
implemented include: Selector switch
Emergency stop (twist, key, guard, padlock) Automatic transfer switches
Pushbutton (illuminated, non-illuminated) Transformers
Indicators
13
Terminal Boxes & Control Stations:
Can be used either as junction boxes with/ Can be supplied with multipolar terminal
without terminals or for the installation of blocks or with modular terminal blocks
electrical equipment Can be drilled in the NHPEx workshop
Body and cover in copper free aluminium alloy according to customers specification
Available with window on cover
135 x 70 5 3 21 15 11 GUB-01
180 x 85 8 6 2x 22 2x 19 2x 15 GUB-02
Note: More sizes available. Contact NHP for quote and for further information
14
EFDC Series Control Stations
Suitable for control and signalling equipment Stainless steel bushing and push button shaft
Aluminium RAL 7035 epoxy paint Also available in a double unit allowing for
1 to 4 operators on a single enclosure up to 8 operators, contact NHP for further
information
Cylindrical housing in copper-free
aluminium alloy
Entries are 1 ISO 7/1 ( conical), for M20 entry use reducer (REGM3IF20B), for M25 use (REGM3IF25B)
15
Terminal Boxes:
AJB164420
16
SA...SS Series Terminal Boxes
Constructed from AISI 316L stainless steel Can be equipped with pilot lights, push
Suitable for electrical installations placed in buttons and measuring instruments
aggressive environments as increased safety Can be drilled by the NHPEx workshop
boxes according to customers specification
Can be supplied with multipolar or modular
terminal blocks
17
Terminal Boxes & Control Stations:
Built in GRP resin and they are suitable for Can be equipped with pilot lights, push
electrical installations as increased safety boxes buttons and measuring instruments
Can be supplied with multipolar or with Can be drilled by the NHPEx workshop
modular terminal blocks according to customers specification and in
accordance with certification
PJB164420
18
SA Series Control Stations
1
) Substitute first letter of Cat. No. denotes material
P = GRP
A = Aluminium
S = Stainless steel
19
20
Ex e Standard Control Stations
POSITION
1
POSITION
2
POSITION
3
P
3
-
4
R
Z(1)
-
1
G
Z(1)
-
5
2M
/
01
-
G
E-Stop
accessories
Series
G
=
Guard
P
=
GRP
P
=
Guard
with
padlock
A
=
Aluminum
S
=
Stainless
steel
Operator
Contact
Blocks(s)
Entry(s)
V
=
1NO
01
=
1
x
M20
bottom
W=
1NC
10
=
1
x
M20
top
Enclosure
size
Z
=
1NO+1NC
11
=
1
x
M20
top
and
bottom
1
=
Single
Gang
(110 x 110 x 80 ) X
=
2NO
02
=
1
x
M25
bottom
2=
Twin
Gang
Y
=
2NC
20
=
1
x
M25
top
(170 x 110 x 80 )
3=
Triple
Gang
(300 x 140 x 110 ) NOTE:
MAX
2
PER
P/BUTTON
22
=
1
x
M25
top
&
bottom
09
=
2
x
M20
bottom
Switch
contacts
configuration:
Switches(s)
Options
are
1Z
,
2Z
,
1I
,
2I
,
3I
,
4I
,
IC
,
2C
,
1W
,
2W
,
1M
,
2M
,
3M
,
4M
1
=
Momentary
Push-button
2=
38mm
Mushroom
Head
twist
to
release
3=
38mm
Mushroom
Head
key
operator
LED
Voltage
I
=
Control
Switch
1=
24V
ac/dc
4=
Indicator
5
=
Selector
Switch
2=
230V
ac
Z=
2
position
command
-
fixed
Colour
N
=
Black
(P/B
only)
R
=
Red
C=
3
position
command
-
B
=
Blue
fixed
G
=
Green
Y
=
Yellow
X=
3
position
command
C
=
Clear
(Indicator
only)
spring
return
to
B
from
A&C
R=
3
position
command
spring
return
to
B
from
A,
fixed
at
C
RSX=
3
position
command
spring
return
to
B,
fixed
at
C
W=
3
position
command
A31RZ1GZ4GI01 spring
return
to
B
from
C&A
M=
Command
with
spring
Note: Contact NHP for custom control stations in any size available (page 16-18) return
Plugs and Sockets:
PY / SPY Series
PY series sockets complete with interlocked If supplied with the plugs SPY are conceived
disconnection switch, can be used in all so as not to allow the coupling with standard
environments with potential explosive industrial type plugs
atmosphere Ring colour indicates the suitable power
voltage
Socket
(2 x 2P + E 50/60 200/250 PY216B SPY216B
ISO 7/1)
Socket
(2 x 1
3P + E 50/60 380/415 PY332R SPY332R
ISO 7/1)
32 2)
Plug
(1 x 1 3P + N
50/60 200/250 PY432B SPY432B
ISO 7/1) +E
3P + N
50/60 380/415 PY432R SPY432R
+E
1
) 16 A - Entries are 3/4 ISO 7/1 (conical), for M20 entry use adapter (REGM2IF20B),
for M25 use (REBIF25GM2B)
2
) 32 A - Entries are 1 ISO 7/1 (conical), for M20 entry use adapter (REGM3IF20B),
for M25 use (REGM3IF25B)
Note: For plugs, use PLG2B for 16 A & PLG3B for 32 A
21
Isolators:
CSC Series
16 2 0.84 CSC-216
16 3 0.86 CSC-316
16 4 0.88 CSC-416
EFSCO Series
22
Cable glands:
FAL series cable glands (double seal) are used for the direct insertion of armored cables into Ex d
equipment or enclosures placed in areas at risk of explosion. The cable glands can be installed easily
and the taper fit guarantees optimum earthling continuity.
FL series cable glands (double seal) are used for the direct insertion of non-armored cables into Ex d
equipment or enclosures placed in areas at risk of explosion. The cable glands can be installed easily
and the taper fit guarantees optimum earthling continuity.
Note: Banner glands also available. Contact NHP for quote and for further information
23
Adapters and Stopping Plugs:
RE Series
1 - M20 REGM3IF20B
1 - M25 REGM3IF25B
1 - M32 REBIF32GM3B
* REB = Adaptor
* Reducer * REG = Reducer
PLG Series - Ex d / Ex e / Ex tD
Stopping plugs
Metric
Zones 1, 2 and 21, 22
IECEx CES 10.0001X issue 0 Thread
Ex d IIC size Cat. No.
Ex e II
Ex tb IP 66/67 M16 PLG01IB
M20 PLG1IB
M25 PLG2IB
M32 PLG3IB
M40 PLG4IB
M50 PLG5IB
Conical
Thread
size Cat. No.
3/8 PLG01B
1/2 PLG1B
3/4 PLG2B
Note: Supplied for conical threads
1 PLG3B
11/4 PLG4B
1
1/2
PLG5B
Note: Adaptors and plugs available in all thread types and sizes. Contact NHP for quote and for further information
24
Intrinsically Safe Barriers:
4-20 mA / 1 TCD1020S
0-20 mA bus
Zones 0, 1, 2 and 20, 21, 22 2 TCD1020D
2 4-20 mA / 0-20 mA powered 20-30 V DC
Ex nA [Ex ia Ga] IIC T4
[Ex ia Da] IIIC + line & load
[Ex ia Ma] I 1 TCD1021S
AO fault detection
IECEx BVS 07.0027X
1-40 mA - fire/ 1 TCD1022S
smoke detector or loop
- loop powered AI/
1-40 mA
powered
AO isolator 2 TCD1022D
Digital Barriers
Channel
SIL Hazardous Area Safe Area Supply Per unit Cat. No.
1 SPDT (relay)
Voltage free contact, 85-264 V 1 TCD1130S
+ 1 SPDT
proximity switch, AC or 100
(alarm or
line fault detection -350 V DC 2 TCD1130D
duplicator)
2 SPST (relay)
+ 2 SPST
2 TCD1032D
(alarm or
DI duplicator)
4 SPST (relay) 4 TCD1032Q
Voltage free contact,
2 proximity switch, 2 open 20-30 V DC
line fault detection collector + 2
open collec- 2 TCD1033D
tor (alarm or
duplicator)
4 open
4 TCD1033Q
collector
Loop powered Loop +
TCD5048S
control signal 20-30 V DC
NE solenoid
Bus powered
20-30 V DC TCD5049S
DO 3 control signal 1
F&G solenoid TCD5247S
Loop powered Loop +
NE 12W Ex d control signal 20-30 V DC TCD5280S
solenoid
25
Intrinsically Safe Barriers:
Analogue Barriers
Channel
SIL Hazardous Area Safe Area Supply Per unit Cat. No.
4-20mA, 2 trip Amp
4-20 mA, 2 wire TX
2 with 1 TCD5254S
active or passive
1 SPST (contact)
20-30 V
AI Source DC 1 TCD5011S
4-20 mA, 2-wire TX
only 2 TCD5011D
3 4-20 mA
4-20 mA, 2 wire TX Source 1 TCD5014S
active or passive or sink 2 TCD5014D
1 TCD5020S
20-30 V
AO 3 4-20 mA 4-20 mA
DC
2 TCD5020D
Digital Barriers
Hazardous Channel
SIL Area Safe Area Supply Per unit Cat. No.
1 TCD5030S
Zones 0, 1, 2 and 20, 21, 22 SPDT (relay)
1
Ex nA [ia Ga] IIC T4 Gc Voltage free TCD5030D
[Ex ia Da] IIIC contact, 2 SPST (relay) 2
[Ex ia Ma] I proximity
IECEx BVS 10.0072 X switch, line 1 open collector 1 TCD5031S
fault
3 detection, 2 open collectors 2
DI
20-30 V DC
isolated 1 open collector or 1
inputs TCD5031D
open collector + 1 open
1
collector
(alarm duplicator)
Voltage free 4 open collectors 4 TCD5231Q
contact,
2
proximity 8 open collectors 8 TCD5231E
switch
Loop powered control Loop +
TCD5048S
signal 20-30 V DC
NE solenoid
Bus powered control
20-30 V DC TCD5049S
signal
DO 3 1
F&G solenoid TCD5247S
Loop powered control Loop +
NE 12W 'Ex d' signal1 20-30 V DC
TCD5280S
solenoid
26
Limit Switches:
Ex position switches are used where moving parts of machines and industrial plants have to
be positioned, controlled and monitored. The various application fields, ranging from fine
mechanics to heavy-duty machinery, require different materials, electrical capacity and quality
criteria regarding construction and design.
Entry
Device Contacts bottom Cat. No.
Foot Switches:
Ex foot switches are used, amongst other things, in good lifts and service elevators to open the cabin
doors. Using these switches, operators do not have to lay down carried goods or materials to open the
lift cabin door and load the lift cabin.
Entry
Device Contacts bottom Cat. No.
Zones 1, 2 and 21, 22 Foot switch 1N/O + 1N/C 1 x M20 EEx GFS 1O/1S
Flameproof with guard 2N/C 1 x M20 EEx GFS 2O
Ex d IIC T5/T6
Combustible dust (DIP)
Ex tb IP 65
IECEx PTB 06.0098X
(EEx 14 contact)
27