Académique Documents
Professionnel Documents
Culture Documents
where, dj is the j level wavelet coefficient and cj is the j level Fig. 1 illustrates the single line diagram of a 400-kV
scaling coefficient. transmission network simulated using ATP/EMTP [21], in
With the energy in the expansion domain is partitioned in which the processing is created by preprocessor program
time by k and in scale by j. This means that the energy of the ATPDraw [22]. This figure shows small part of 400 kV
distorted signal can be partitioned in terms of the expansion FinGrid network has been simulated and a fault scenario
coefficients [17]. The above method was implemented in a similar to that disturbances occurs on 29.6.2002 13:12:54
MATLAB program using the current details of the fault line (GMT) between OL-KA substations at a distance 112.2km
955
from OL substation. The TWR recorders that recorded the advantages over data from a single TWR. First, if several
fault signals are YL, AJ, ES, OL recorders. The minimum path TWRs are used, combining the observations will result in
for the TW has been calculated from Bus OL though OL-KA an improved estimate of the fault position. A statistical
line to BUS AJ. The fault is then calculated using two end advantage is gained by adding the N independent
method using the OL and AJ recordings. TW velocities can be observations (e.g., the estimate of the fault location or
determined based on the type and configuration of lines using faulty line is improved by a factor proportional to N),
line/cable constant (LCC) program of ATP/EMTP [22]. assuming the data are combined in an optimal manner.
This same result could also be obtained by combining N
observations from an individual TWR.
A second advantage involves using the relative placement
of multiple TWRs to improve the observation process. For
example, two TWRs that measure fault direction can be
coordinated to determine the position of a fault.
Broadening the baseline of physical observable lines can
result in significant improvements.
Fig. 2 shows the topology structure of the network. It is
evident that several important buses are un-monitored.
Adding three TWRs can render the network observable.
The proposed buses are UL, HY, and KM buses. This
proposal is under condition that there are no consequent
buses unobserved. Therefore, a TWR is suggested at HY
which is between unmonitored buses KA and KR.
Similarly, TWRs are added at busses UL and KM.
Existing TWR
Fig. 1. Test transmission system single line diagram.
Proposed TWR
Unmonitored
956
where t is the time arrivals at the k-th TWR and D(tk) is the Phase
maximum details power. currents Read
Fig. 3 can help to understand the proposed algorithm Recording
implementation where it can be summarized as follows:
1. The measured fault signals of each TWR are transformed to
the modal domain. Polarity Modal
2. For each TWR, the faulty transmission line is identified Identification Transformation
which has different polarity from other lines or using a
probabilistic-based selectivity technique [24]. Then, the
signals are sent to a central computer with the network
Applying DWT
configuration, circuit breaker status and protective relay
signals.
3. The aerial mode is processed using DWT using a suitable
mother wavelet and the details level is selected based on its Selecting Optimum Mother
energy content. Wavelet and Optimum Detail
4. The best nearest two TWR signals is selected based on their
received signal strength and arrival times.
5. If the number of triggered TWRs, CBs is greater than one, Determine Nearest 2 TWRs, CBs operated
calculate the minimum travel time of the signals from the
faulted line towards the nearest TWRs using Dijkstra
algorithm. Otherwise, single-end method is used.
6. If faulted line is located in the TW path (an intermediate bus If
between the two TWRs), the double-end method is used to Single End No
find the fault location using (9). Method No. of TWRs > 1
7. For each TWR signal, the first packet of the details' power
of fault signal is determined to find its arrival time using
Yes
(10). The time at maximum value of the delay profile is
recorded for both TWR signals to improve the accuracy.
Faulty line
VII. RESULTS No included in the
The new TWRs places are assigned to make the TW path,
transmission system as observable as possible. Implementing
the proposed algorithm enables accurate positioning of the Yes
majority of faults in the network assisted by breakers'
operation and other intelligent electronic devices' signals Double End Method
(IED). Some results are shown in Table I. This method is
sensitive to the travelling wave propagation velocity which
Fig. 3 the proposed fault locator implementation.
can be calculated using the switching disturbances or using
external faults for lines connected between each two TWRs. VIII. CONCLUSIONS
Using a ground resistivity of 2300 .m and the data of table II This work has successfully developed an economical fault-
and III for a horizontal transmission line configuration, the location scheme for transmission networks using minimum
propagation speed was found to be 291774 km/s. At least, two TWRs. DWT of the TW signals is used to extract arrival times
recordings are needed for an accurate fault location in meshed of fault traveling waves reflected from the fault point. The
networks. Simulation studies show that the errors are minimum path for the TW has been calculated and the fault is
symmetric along the transmission line. The exceptions are for then calculated using two end method using the appropriate
close-up faults and small fault inception angles. Practically, it fault recordings from the nearest TWR recorders. The method
is impossible to locate faults if the TW arrival time is less than shows a good results for long transmission lines in a meshed
the sampling time. In this case, high sampling frequency is network. Simulations show a good results when compared
needed which may not be possible due to the equipment with some practical events in the studied network. For close-
limitation. Other impedance based techniques can be adopted up, other fault location techniques can be combined with the
for such cases. Considering small inception fault angle, it is proposed method.
not possible to detect the TW as it may not has enough level to
be detected by the TWR.
957
IX. APPENDIX [2] F. S. Caralho and S. Carneiro,Detection of Fault Induced Transients in
E.H.V. Transmission Lines for the Development of a Fault Locator,
International Conference on Power Systems Transients- IPST 2003.
400kV [3] Y. G. Paithankar and M. T. Sant, A new algorithm for relaying and
fault location based on auto-correlation of travelling waves ,
400kV 400kV
Electric Power Systems Research, Volume 8, Issue 2, March 1985,
Pages 179-185.
I
UL I
HU
I
AJ
[4] Rajendra S, McLaren PG. Traveling-wave techniques applied to
F2
I protection of teed circuits: Principle of traveling wave techniques ,
IEEE Trans PAS, 1985, 104, Page(s): 3544-3550.
I
UL UL
I
OL
I [5] Rajendra S, McLaren PG. Traveling wave techniques applied to the
YL
I F1 protection of teed circuits: Multi phase/multi circuit system. IEEE Trans
PAS 1985; 104, Page(s): 3551-3557.
I
KA
400kV 400kV I 400kV [6] Christopoulos C, Thomas D, Wright A. Scheme, based on travelling-
KA
I
waves, for the protection of major transmission lines. IEEE Proc C 1988,
RA pp. 63-73.
KR
RA
RA
HY [7] Aurangzeb, M.; Crossley, P.A.; Gale, P.; Fault location using the high
400kV KR
IN
frequency travelling waves measured at a single location on a
KR
transmission line , Developments in Power System Protection, 2001,
Seventh International Conference on (IEE), 9-12 April 2001
F3
Page(s): 403 406.
I
ES
[8] Z. Galijasevic and A. Abur,'Fault Area Estimation via Intelligent
Processing of Fault-Induced Transients', IEEE TRANSACTIONS ON
I
KM
POWER SYSTEMS, VOL. 18, NO. 4, NOVEMBER 2003, pp. 1241-
1247.
TM [9] Robertson, D. C.; Camps, O. I.; Mayer, J. S. & Gish, W. B.: Wavelets
Fig. 4 ATPDraw circuit diagram of the simulated network. and electromagnetic power system transients, IEEE Transactions on
Power Delivery, Volume: 11 Issue: 2 , April 1996, Page(s): 1050 -1058.
TABLE I [10] A. Abur and F. H. Magnago, Fault location using wavelets, IEEE
Simulation Results for a Single-Phase earth faults Trans Power Delivery 1998; 13, Page(s): 1475-1480.
Faulted Actual Location from OL Estimated Location Error % [11] A. Abur and F. H. Magnago, Use of time delays between modal
Line from OL components in wavelet based fault location , International Journal of
% km Electrical Power & Energy Systems, Volume 22, Issue 6, August 2000,
OL-KA 20 % 32.6 32.6540 -0.1656 Pages: 397-403.
OL-KA 50 % 81.5 81.6586 -0.1946 [12] A. Elhaffar and M. Lehtonen, Multi-End Traveling Wave Fault
OL-KA 80 % 130.4 130.4298 -0.0229 Location based on Current Traveling Waves, 16th Power Systems
Computation Conference 2008, (PSCC2008), July14-18, 2008,
TABLE II Glasgow, Scotland.
Conductor data of a 400-kV transmission line [13] E. W.Dijkstra, A note on two problems in connection with graphs,
Ph skin Resistance Rout Numer. Math., vol. 1, pp. 269-271, 1959.
[/km DC] [cm] [14] Kai-Ping Lien, Chih-Wen Liu,Chi-Shan Yu,and Joe-Air Jiang,
1 0.374 0.05165 3.284 'Transmission Network Fault Location Observability with Minimal
2 0.374 0.05165 3.284 PMU Placement', IEEE Transactions nn Power Delivery, Vol. 21, No. 3,
July 2006, pp. 1128-1136.
3 0.374 0.05165 3.284
[15] Daubechies I. Ten lectures on wavelets , SIAM; 1992.
4 0.5 0.36 1.46 [16] M. Misiti, Y. Misiti, G. Oppenheim and J. Poggi, Wavelet toolbox user's
5 0.5 0.36 1.46 guide. Version 2. , The math works.
[17] A. M. Gaouda, M. M. A. Salama, M. R. Sultan, and A. Y. Chikhani,
TABLE III 'Application of Multiresolution Signal Decomposition for Monitoring
Tower configuration data of a 400-kV line Short-Duration Variations in Distribution Systems', IEEE Transactions
Ph Horiz Vtower Vmid Seperate NB on Power Delivery, Vol. 15, No. 2, April 2000,pp. 478-485.
[m] [m] [m] [cm] [18] L. M. Wedepohl, Application of matrix methods to the solution of
1 11 24 10 45 2 travelling wave phenomena in polyphase systems, Proc. IEE, vol. 110,
2 0 24 10 45 2 no. 12, pp. 2200-2212, Dec. 1963.
3 -11 24 10 45 2 [19] E. Clarke, Circuit Analysis of AC Power Systems, Symmetrical and
4 6 33 20 0 0 Related Components, Wiley, NewYork, 1943.
[20] Liang, J.; Elangovan, S; Devotta, J.B.X. "Application of Wavelet Transform in Travelling Wave
5 -6 33 20 0 0 Protection" International Journal of Electrical Power and Energy Systems, Vol. 22, 2000, 8, pp.
537-542.
[21] Alternative Transient Program, RuleBook, 1987.
[22] Prikler, L. and Hoildalen, H. ATPDraw users' manual, SINTEF Energy
Research AS, Norway, TR F5680, ISBN 82-594-2344-8, August 2002
X. ACKNOWLEDGMENT [23] C. Sidney Burrus, Ramesh A. Gopinath and Haitao Guo. Introduction to
The author gratefully acknowledges the valuable discussion Wavelets and Wavelet Transform, Prentice Hall, New Jersey (1997).
[24] Abdelsalam M. Elhaffar, Nagy I. Elkalashy, Naser G. Tarhuni,
and revision with Dr. N. Elkalashy, Power System Protection Mohamed F. Abdel-Fattah and Matti Lehtonen, Evaluation of
Group (PSPG), Electrical Engineering Department, Probabilistic-Based Selectivity Technique for Earth Fault Protection in
Minoufiya University,Egypt. MV Networks,28 June - 2 July 2009, Bucharest, Romania.
REFERENCES
[1] T. W. Stringfeild, D.J. Mahart and R.F.Stevens, Fault Location
Methods for Overhead Lines, AIEE Transactions, pp. 157-160, August
1957.
958