AbstractWith the grid-connected mode turning into the isolation and voltage mode, a serious transient problem may occur on the
mode, the control strategy of micro-grid is changed into voltage output terminal voltage of utility interactive inverters. A new
control from current control. The control strategy with load voltage inverter system and its control algorithm for seamless transfer
in outer loop and inductance current in inner loop is able to make during intentional islanded operations in micro grid systems were
micro grid into isolation operation rapidly and steadily. In this proposed in [2]. A point of common coupling (PCC) seamless
paper, an accurate simulation model of micro grid connection transfer control strategy with adjustment of frequency and phase
operation with an LCL grid-connected filter is built based on the was presented in [3]. With dual-mode inverter, when in grid-
platform of MATLAB/SIMULINK. Then the simulation model connected operation and islanded operation, the traditional PV
works from grid-connected state to isolation state. In the isolation
control and v-f control strategies are applied to the micro grid
operation, an improved control strategy of load voltage in outer
system, respectively [4,5]. For other control strategies, in
loop and inductance current in inner loop is applied so as to get
more rapid dynamic response and comparatively better steady
islanded operation, the droop control is used in the micro grid
performance. Simulations and theoretical analysis fully verify that system in order to meet the demand of plug and play [6].
the proposed control strategy can safely guarantee the micro-grid Although the introduced control strategies meet the needs of
operates with the isolation state from the grid connection state very micro grid operation, their control algorithms are relatively
smoothly. complex. With the load voltage in the outer loop and the
inductance current in the inner loop, the proposed control
Keywords-islanded operation; voltage/current control; LCL grid- strategy is with simpler algorithm and good control performance.
connected filter If the control strategy is applied to micro gird, it will greatly
reduce the hardware costs.
I. INTRODUCTION In this paper, a micro grid connection model is analyzed
firstly, and then built on the basis of MATLAB/SIMULINK, in
Nowadays human beings are confronted with the increasingly which the LCL filter is employed for the grid-connection
serious energy and environment issues, and the utilization of new interface. Investigations indicate the LCL filter has a strong
energy sources has being promoting the development of ability to remove high-order harmonics. Based the grid-
distributed generation. In the form of micro grid, these distributed connected model, the micro grid turns into isolation state apart
power systems are connected with the large-scale power grid. away gird connection state with disconnecting from the large-
When the large-scale power grid breaks down, the micro grid is scale power grid. The micro grid uses the isolation control
in disconnection and would stay in the islanded mode. A control strategy with the load voltage in the outer loop and the
algorithm for utility interactive pulse width modulation (PWM) inductance current in the inner loop. Simulation shows that the
inverters to maintain a continuous, uninterrupted voltage across micro grid can provide the stable power supply to the load in the
critical and sensitive loads in the event of a fault on the grid was mode of isolated operation quickly. Comprehensive
proposed in [1]. Micro grid should go into intentional islanded investigations on the proposed control strategy demonstrate very
operation to back up private emergency loads when the main grid good dynamic and steady control performance.
is out of electric power. Conventional utility interactive inverters
which are normally operated in current mode must change their
operation into voltage mode to ensure stable supply voltage for II. GRID-CONNECTED MODEL OF MICRO GRID
emergency loads when intentional islanded operation occurs in The structure of the grid-connected model of micro grid is
micro grid systems. During the transition between current mode shown in Fig. 1. As is seen from this figure, L1 and L2 are the
Similar with the LCL filter, the block diagram of the LC filter
is drawn as Fig. 4, in which G4(S) and G5(S) are RL and sC,
respectively.
I 2 ( s) 1
G (s) = = 3 (2)
U i ( s ) s L1 L2C + s ( L1 + L2 ) Figure 5. Block diagram of the islanded operation control strategy.
292
C. Stability Analysis of Islanded Operation Control Strategy
According to Fig. 5, its signal flow diagram is illustrated as
a 0' > 0
Fig. 6.
'
a1 > 0
'
a 2 > 0
' (4)
a3 > 0
'
a 4 > 0
'
b1 > 0
Figure 6. Diagram of the signal flow.
Based on the signal flow diagram and the Mason Formula, its c ' > 0
open-loop transfer function is derived as 1
IV. SIMULATION RESULTS AND ANALYSIS
uL Gu ( s)Gi1 ( s )G1 ( s )G4 ( s )
GL ( s ) = = The models of the grid-connected operation and the islanded
uref u L 1 + G1 ( s )G4 ( s ) + G4 ( s)G5 ( s ) + G1 ( s )G42 ( s )G5 ( s)
(1) operation are built based on the platform of
R K K ' L s 2 + RL ( K P K I' + K P' K I ) s + RL K I K I' MATLAB/SIMULINK. In the grid-connected operation model,
= L P P 1
RL L1Cs 4 + ( L1 + RL2 C ) s 3 + RL s 2 the key parameters are chosen in the following: Udc = 400 V, ug =
And its closed-loop transfer function is got by 311 V (50 Hz), L1 = 2 mH, L2 = 1 mH, C = 2 F, Kp = 2.7, Ki =
100, and KC = 100. And in the islanded model, the key
RL K P K P' L1s 2 + RL ( K P K I' + K P' K I ) s + RL K I K I' parameters are: Udc = 400V, L1 = 2 mH, C = 2 F, R = 4.84 , Kp
GL* ( s) =
RL L1Cs + ( L1 + RL2 C ) s 3 + RL (1 + K P K P' L1 ) s 2 + RL ( K P K I' + K P' K I )s + RL K I K I'
4
= 91, Ki = 0.01, Kp = 30, and Ki = 1.
RL K P K P' L1s 2 + RL ( K P K I' + K P' K I ) s + RL K I K I' It can be seen from Fig. 7 that the grid-connected current is
=
a4' s 4 + a3' s 3 + a2' s 2 + a1' s + a0' under the condition of the same phase as the one of the grid
(2) voltage. In Fig. 8, the total harmonic distortion (THD) of the
where a4 is RLL1C, a3 is (L1+RL2C), a2 is RL(1+KPKp L1), a1 is grid-connected current by the fast Fourier transformation method
RL(KPKI +KPKI), and a0 is RLKIKI. (FFT) is 0.04 %. So in the case of grid-connected mode of the
micro grid, the system is able to suppress the harmonics well and
Its characteristic equation is expressed as to ensure a high in-grid power factor.
D( s ) = a '4 s 4 + a3' s 3 + a '2 s 2 + a1' s + a 0' (3)
It can be known that the control system is a fourth-order
linear system. And the stability conditions are derived based on
the Routh-Hurwitz stability criterion as shown in Table I.
293
V. CONCLUSION
In this paper, simulation models of the grid-connected
operation and the islanded operation are built in the platform of
MATLAB / SIMULINK. In the case of stand-alone mode of the
micro grid, the control strategy is not only able to provide the
stable voltage for the load, but also to filter out most harmonics
of the load voltage. In the switching process between the modes
of grid-connected and islanded, the proposed control strategy is
able to ensure the quality of the load voltage and current, which
are of less fluctuations and fewer harmonics. The results
demonstrate that the parameters are rational, and it also verified
that the proposed control strategies as effective.
Figure 9. Curves of the load voltage and current when in the islanded operation.
(iL is phase current, and uL is line voltage)
Figure 10. Diagram of the load voltage harmonic analysis with FFT algorithm
when in the islanded operation.