Académique Documents
Professionnel Documents
Culture Documents
AbstractThis paper describes a new approach to fault location Ratio between the magnitudes of
for double-circuit transmission lines based on only the voltage data negative-sequence voltages at the local
of both ends of the faulted circuit. The ratio between the magni-
tudes of negative-sequence voltages measured at both ends of the and remote ends.
faulted circuit is utilized to estimate the fault location. Since only Fault location in the faulted circuit of the
the magnitudes are used, the data of both ends are not required to
double-circuit transmission line in per
be synchronized, which removes any concern about data synchro-
nization. Moreover, since only the voltage data are required, the er- unit.
rors caused by current transformers can be avoided. The proposed
method can effectively locate the single-phase-to-ground, double- I. INTRODUCTION
phase-to-ground, and phase-to-phase faults disregarding the fault
resistance and prefault conditions and without any need for fault
classification and phase selection. Unlike the iterative methods, the
proposed method is fully analytical and does not cause much com-
puting burden to the line relays. The accuracy and practicality of
D OUBLE-CIRCUIT transmission lines have been adopted
in modern power systems to increase the transmission
capacity and to enhance reliability and security. However,
the proposed method make it an attractive function to implement protecting double-circuit lines, in particular locating faults
in numerical relays.
on them, are always challenging due to the mutual coupling
Index TermsDouble-circuit transmission line, fault location, between zero-sequence components of the two circuits.
negative-sequence reactance, negative-sequence voltage magni- Whether they are for single-circuit or double-circuit transmis-
tude, unsynchronized measurement.
sion lines, there are two types of fault-location methods known
as one-end-based and two-end-based ones. The one-end-based
NOMENCLATURE methods [1], [2] may suffer from errors due to the variations
of source impedance, fault incidence angle, and loading condi-
tions while their major merit is that they need data of only one
and Negative-sequence reactance behind end [3]. To overcome the shortfalls of one-end-based methods,
relays and , respectively. two-end-based methods were introduced. They can be classified
Negative-sequence reactance of a into unsynchronized and synchronized ones. Unsynchronized
transmission line. methods do not need the data of both line ends to be synchro-
nized while data synchronization is the first step in the synchro-
and Negative-sequence voltage measured by nized methods.
relays and , respectively. Up till now, several methods have been proposed for fault
Negative-sequence voltage at the fault location on double-circuit transmission lines, most of which re-
point. quire data of both voltage and current [4][11]. The magnetic
saturation of current transformers (CTs) always presents chal-
and Negative-sequence capacitance and
lenges of having reliable current data and, thus, a strong desire
capacitive reactance of a transmission
for possible approaches based on only voltage data exists.
line, respectively.
Chen et al. [4] presented a fault-location method based on the
and Equivalent capacitance at the sending and
distributed line model. This method requires the phasor mea-
receiving ends, respectively.
surement units (PMUs) for synchronized data and continuous
monitoring of the line under normal operation. Funabashi et al.
Manuscript received June 09, 2013; revised October 30, 2013; accepted De- [5] presented two algorithms for multiterminal double-circuit
cember 04, 2013. Paper no. TPWRD-00660-2013. transmission lines based on impedance calculation and cur-
B. Mahamedi was with the School of Electrical, Mechanical and Mechatronic
rent diversion ratio. The synchronization for voltages and cur-
Systems, University of Technology Sydney, Ultimo NSW 2007, Australia. He
is now with the Iran Grid Management Company, Tehran IR-15175-648, Iran rents at all terminals is required. Kang et al. [6] developed a
(e-mail: behnam.mahaamedi@gmail.com). fault-location algorithm for untransposed double-circuit trans-
J. G. Zhu is with the School of Electrical, Mechanical and Mechatronic Sys-
mission lines based on the lumped parameter model of trans-
tems, University of Technology Sydney, Ultimo NSW 2007, Australia (e-mail:
jianguo.zhu@uts.edu.au). mission lines by ignoring the line shunt capacitances. This may
Digital Object Identifier 10.1109/TPWRD.2013.2294972 cause significant errors in long transmission lines. Besides, fault
0885-8977 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
MAHAMEDI AND ZHU: UNSYNCHRONIZED FAULT LOCATION BASED ON THE NEGATIVE-SEQUENCE VOLTAGE MAGNITUDE 3
where is the voltage between the fault point and the star
point of the Y connection in the negative-sequence circuit.
Considering only the phasor magnitudes and dividing (5) by
(6) yields
(7)
(8)
(9)
(6) (10)
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
The equal capacitances given in (9) and (10) are parallel with TABLE I
the source reactances and , respectively. Thus, two new DIFFERENT FAULT CASES CONSIDERED FOR EVALUATION STUDIES
source reactances and will be formed by the parallel
combination of the source reactances and the equal capacitances
as
(11)
(12)
MAHAMEDI AND ZHU: UNSYNCHRONIZED FAULT LOCATION BASED ON THE NEGATIVE-SEQUENCE VOLTAGE MAGNITUDE 5
Fig. 5. Estimation errors for Case 1 based on the lumped and PI model. Fig. 8. Estimation errors for Case 4 based on the lumped and PI model.
Fig. 9. Estimation errors for Case 5 based on the lumped and PI model.
Fig. 6. Estimation errors for Case 2 based on the lumped and PI model.
Fig. 10. Estimation errors for Case 6 based on the lumped and PI model.
Fig. 7. Estimation errors for Case 3 based on the lumped and PI model.
Fig. 11. Estimation errors for Case 7 based on the lumped and PI model.
Fig. 14. Variation of for different fault locations.
Fig. 12. Estimation errors for Case 8 based on the lumped and PI model.
Fig. 15. Sensitivity factor to the source reactance behind the sending-end relay
for different fault locations based on the lumped model.
Fig. 13. Estimation errors for Case 9 based on the lumped and PI model.
TABLE II
MAXIMAL AND MEAN VALUES OF ABSOLUTE ERRORS FOR EACH FAULT CASE
BASED ON THE LUMPED AND PI MODELS
Fig. 16. Sensitivity factor to the source reactance behind the receiving-end
relay for different fault locations based on the lumped model.
MAHAMEDI AND ZHU: UNSYNCHRONIZED FAULT LOCATION BASED ON THE NEGATIVE-SEQUENCE VOLTAGE MAGNITUDE 7
APPENDIX
The parameters of the simulated system are given as follows.
The positive-, negative- and zero-sequence impedances be-
hind relay are
Fig. 18. Estimation errors for deviation of 10% in source reactances (case:
0.9 X and 0.9 X ).
The voltage of the source behind relay is
Fig. 19. Estimation errors for deviation of 10% in source reactances (case:
1.1 X and 0.9 X ).
The distributed model parameters of the double-circuit trans-
mission line:
The positive-, negative-, and zero-sequence impedances are
The mutual coupling capacitance between the zero-sequence [13] S. M. Brahma and A. A. Girgis, Fault location on a transmission line
circuits is using synchronized voltage measurements, IEEE Trans. Power Del.,
vol. 19, no. 4, pp. 16191622, Oct. 2004.
[14] Y. Liao, Fault location utilizing unsynchronized voltage measure-
ments during fault, Elect. Power Compon. Syst., vol. 34, no. 12, pp.
12831293, 2006.
[15] H. Saadat, Power System Analysis, 2nd ed. New York: McGraw-Hill,
2002.
[16] A. Apostolov, D. Tholomier, S. Sambasivan, and S. Richards, Protec-
tion of double circuit transmission lines, presented at the 60th Annu.
REFERENCES
Conf. Protect. Relay Eng., College Station, TX, USA, Mar. 2007.
[17] B. Mahamedi and J. G. Zhu, Fault classification and faulted phase
[1] T. Kawady and J. Stenzel, A practical fault location approach for
selection based on the symmetrical components of reactive power for
double circuit transmission lines using single end data, IEEE Trans.
single-circuit transmission lines, IEEE Trans. Power Del., vol. 28, no.
Power Del., vol. 18, no. 4, pp. 11661173, Oct. 2003.
4, pp. 23262332, Oct. 2013.
[2] G. Song, J. Suonan, and Y. Ge, An accurate fault location algorithm
[18] O. Hevia, Alternative Transients ProgramComparison of
for parallel transmission lines using one-terminal data, Elect. Power
transmission line models. [Online]. Available: www.iitree-
Energy Syst., vol. 31, no. 23, pp. 124129, 2009.
unlp.org.ar/caue/Archivos/emodlin.pdf
[3] J.-A. Jiang, J.-Z. Yang, Y.-H. Lin, C.-W. Liu, and J.-C. Ma, An adap-
[19] D. Tziouvaras et al., Mathematical models for current, voltage and
tive PMU based fault detection/location technique for transmission
coupling capacitor voltage transformers, IEEE Trans. Power Del., vol.
lines part I: Theory and algorithms, IEEE Trans. Power Del., vol. 15,
15, no. 1, pp. 6272, Jan. 2000.
no. 2, pp. 486493, Apr. 2000.
[4] C. S. Chen, C. W. Liu, and J.-A. Jiang, A new adaptive PMU based
protection scheme for transposed/untransposed parallel transmission Behnam Mahamedi was born in Tehran, Iran, in
lines, IEEE Trans. Power Del., vol. 17, no. 2, pp. 395404, Apr. 2002. 1982. He received the B.Sc. degree in electrical
[5] T. Funabashi, H. Otoguro, Y. Mizuma, L. Dube, and A. Ametani, Dig- engineering from Iran University of Science and
ital fault location for parallel double-circuit multi-terminal transmis- Technology (IUST), Tehran, in 2005 and the M.Sc.
sion lines, IEEE. Trans. Power. Del., vol. 15, no. 2, pp. 531537, Apr. degree in electrical engineering from Shahid Be-
2000. heshti University (SBU), Tehran, in 2010.
[6] S. Kang, Y. Ahn, Y. Kang, and S. Nam, A fault location algorithm From 2012 to 2013, he was a Researcher with the
based on circuit analysis for untransposed parallel transmission lines, University of Technology Sydney (UTS), Sydney,
IEEE Trans. Power Del., vol. 24, no. 4, pp. 18501856, Oct. 2009. Australia, focusing on power system fault detection
[7] J. Izykowski, E. Rosolowski, and M. M. Saha, Locating faults in par- systems. Since 2008, he has been a Protection
allel transmission lines under availability of complete measurements at Engineer with the Iran Grid Management Company
one end, Proc. Inst. Elect. Eng., Gen., Transm. Distrib., vol. 151, no. (IGMC), Tehran. His research interests are power system protection, power
2, pp. 268273, Mar. 2004. system transients, and wavelet-transform applications in power systems.
[8] C. A. Apostolopoulos and G. N. Korres, A novel fault-location al-
gorithm for double-circuit transmission lines without utilizing line pa-
rameters, IEEE. Trans. Power. Del., vol. 26, no. 3, pp. 14671478,
Jul. 2011. Jian Guo Zhu (SM03) received the B.E. degree in
[9] N. Kang and Y. Liao, Double-circuit transmission-line fault location electrical engineering from Jiangsu Institute of Tech-
utilizing synchronized current phasors, IEEE. Trans. Power. Del., vol. nology, Zhenjiang, China, in 1982, the M.E. degree
28, no. 2, pp. 10401047, Apr. 2013. in electrical engineering from Shanghai University of
[10] C. A. Apostolopoulos and G. N. Korres, Accurate fault location al- Technology, Shanghai, China, in 1987, and the Ph.D.
gorithm for double-circuit series compensated lines using a limited degree in electrical engineering from the University
number of two-end synchronized measurements, Elect. Power Energy of Technology Sydney (UTS), Sydney, Australia, in
Syst., vol. 42, no. 1, pp. 495507, 2012. 1995.
[11] G. Song, J. Suonan, Q. Xu, P. Chen, and Y. Ge, Parallel transmission Currently, he is a Professor of Electrical En-
lines fault location algorithm based on differential component net, gineering and Head of the School of Electrical,
IEEE Trans. Power Del., vol. 20, no. 4, pp. 23962406, Oct. 2005. Mechanical, and Mechatronic Systems, UTS. His
[12] I. Zamora, A. J. Mazn, V. Valverde, E. Torres, and A. Dysko, Power research interests include electromagnetic and magnetic properties of mate-
quality and digital protection relays, presented at the Int. Conf. Renew. rials, electrical machines and drives, power electronics, and renewable energy
Energies Power Qual., Barcelona, Spain, 2004. systems.