R407C
DB-AIRE II another milestone series offers a wide range of capacities in superior compact, stylish black themed
attractive furniture grade cabinets in Upflow/ Downflow configuration to provide room-based cooling, control of
perfect humidification and air filtration.
GENERAL INFORMATION
DB-Aire II units are precision environmental control High-low pressure cutout to protect compressor (for
systems that bring a new standard of compact, Air Cooled DX Systems).
flexibility and reliable performance to the computer Specially built with non screw fixed panels where no
room. Because room requirements differ, DB-Aire II special tools required, front access for easier service
offers a wide range of sizes and styles. and maintenance
TEFC motor with low speed belt driven DIDW
DB-AIRE II SYSTEMS centrifugal fan.
DBAIRE II comes in 2 systems under Air cooled DX Large faced area evaporator coil with hydrophilic fins.
and Chilled water system. The nominal capacity range
Deep pleated disposable filter of MERV8 (Ashrae
is 2 to 26TR (7 to 91kW) of cooling.
52.2). Stainless steel finned tabular type electric
heater.
COMPUTER COMFORT 3-way modulating valve provides accurate
Computer rooms require air which is clean and properly temperature control and dehumidification (for Chilled
distributed with precisely controlled temperatures and Water Systems).
humidity. Building HVAC systems simply are not Integrated control system within the unit with panel
designed to meet these demands. But, DB-Aire II units mounting 4.3 graphical color touch screen for
easily accomplish these goals with top-rated efficiency, temperature/ humidity/alarm control and monitoring.
24 hours per day 7 days a week! DB-Aire II units have
Vision 2020i connectivity to BMS for telemonitoring.
been designed to meet the demanding requirements of
the most advanced computer room. Supply air plenum box for upflow model (optional).
Although building HVAC systems cool your staff, they Steam generator humidifier (optional).
fall short of your computer's comfort need. And they are Floor water detection alarm (optional).
unable to provide the close humidity control required in VFD applied to regulate airflow thus reducing fan
a modern data processing centre. input power for energy saving (optional).
TABLE OF CONTENTS
Page No Page No
General Information ............................................................................................... 2 Dual Coils Option .................................................................................................. 12
Nomenclature ......................................................................................................... 3 Electrical Data ....................................................................................................... 13
DB-Aire II Monitoring/ Control ................................................................................. 4 Dimensional Data .................................................................................................. 14
Network Remote Monitoring (Optional) ................................................................... 6 Remote Air-Cooled Condensers ........................................................................... 15
DB-Aire II Design Features ..................................................................................... 7 Typical Wiring Schematic ...................................................................................... 16
Performance and Technical Data ............................................................................ 8 Guide Specifications ............................................................................................. 21
-2-
NOMENCLATURE
INDOOR UNIT
String 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
D B A D 0 2 P A U D B H G S K P S E V N 1 Q
11 DISCHARGE PLENUM OPTION (for Upflow model only) 14 LIQUID LINE SOLENOID VALVE OPTION
B = Discharge Plenum S = Liquid Line Solenoid Valve
N = Not Selected N = Not selected
12 HUMIDIFIER OPTION
13 HOT GAS BYPASS OPTION
H = Humidifier (water conductivity 125 to 350S/cm)***
G = Hot Gas Bypass
N = Not Selected
***Please consult factory for other water conductivity. N = Not Selected
D B R C 0 4 P A U A L Q
-3-
DB-AIRE II MONITORING/ CONTROL
Temperature Set Point 10 to 50C (50F- 122F)
Temperature Sensitivity 0.5 to 2.7C (1F- 5 F)
Humidity Set Point (40% - 70% RH)
Humidity Sensitivity (1% - 10% RH)
Temperature Alarm Set points
Humidity Alarm Set points
Unit Start Time Delay
Normal functions are monitored and displayed on the
display panel and include, in addition to the above set
points, the following:
Current Temperature (deg C or deg F)
VISION 2020i CONTROLLER Current Humidity (%RH)
The heart of the Environmental Control System is the Cooling Stages 1, 2 as applicable
microprocessor based DB5 controller, a member of Heating Stages 1, 2, 3
Vision 2020i family. The DB5 controller was developed Humidification
in compliance with the European RoHS directives. The Dehumidification
DB5 controller is designed with 32 bit, 44 MHz CPU,
2+2MB built-in flash memory, and built-in clock with ALARMS
battery as standard. The program and the parameters
2 Alarm conditions are also monitored on the display
are saved to FLASH-MEMORY and E PROM, meaning
panel and are enunciated by an audible alarm. The
all data is retained even in the event of power failures
alarm silence button will quiet the audible alarm but the
(without requiring a backup battery). DB5 controller
display will continue to indicate the alarm condition until
offers various add-on cards which allow supervisory
the problem is corrected.
communication to be so easy by just inserting an add-
on card into DB5 controller. The following alarms are standard:
Compressor High/Low Pressure
DBG5 TOUCH SCREEN DISPLAY High and Low Temperature
High And Low Humidity
The new DB-AIRE II is equipped with a 4.3 DBG5
color touch screen display as standard display panel. No Airflow
The color touch screen display has graphical resolution Filters Blocked
of 480 x 272 pixels, 65k colors with LED backlight. This Humidifier Failure
means the display panel will perform high quality Power Failure Restart
images and advanced functions are available for a Compressor Short Cycle
superior appearance. DBG5 display panel not only Temperature Sensor Error
monitors your data center's temperature, humidity, Humidity Sensor Error
airflow, and cleanliness, but also provides component Local Alarm Customer Input Alarm
run times, alarm history and an automatic self-test of Maintenance Due
the microprocessor on system start-up. Multiple
messages will be displayed by automatically scrolling With add-on optional sensors, the following alarm
from each message to the next. All of these messages status can be monitored:
are spelled out in English language on the touch screen Under the floor water detection
color display. Multiple alarms will be displayed No water flow
sequentially in order of occurrence. Smoke alarm and etc.
In addition, incomparable control settings will be
OPERATION identified on the display panel.
DBG5 touch screen panel makes interaction between
the user and the unit much easier by simplifying
HISTORICAL DATA
navigation between the various screens. Touch keypad In order to facilitate maintenance and service,
on the DBG5 panel allows unit on/off operation, menu component run times for fan motor, compressor
selection, operational information, diagnostics, operation, reheat stages, humidification and
historical data and trend graph. Multi-level authorization dehumidification can be recalled and displayed on the
password feature prevents unauthorized access. DBG5 display panel. The current temperature and
Another feature is that all menu programmed humidity, with the minimum and maximum readings for
information for basic system operation and alarm the last 24 hours of operation, can be recalled and
parameters is stored in a non-volatile EEPROM and displayed. The last ten alarms and hours since
FLASH-MEMORY where backup battery is not required. occurrence can also be recalled and displayed. The
historical data base is stored in FLASH-MEMORY with
PROGRAMMABLE FUNCTIONS/ does not required backup battery in the event of power
failure.
MONITORING
The user friendly touch screen color display permits DIAGNOSTICS
step-by-step programming and display of the following Automatic and manual diagnostic sequences simplify
functions: troubleshooting.
-4-
DB-AIRE II MONITORING/ CONTROL
-5-
DB-AIRE II MONITORING/ CONTROL
6.) SMS, short message service (with GSM SMS that service personnel can use to reset any
Modem) alarm or perform the necessary operations, without
Dunham-Bush has pay great attention to fitting the having to travel to the installation.
Vision 2020i controllers with the ability to
communicate important information directly by SMS
message. 7.) TREND
In fact, this is the best communication system for Trend is a building Automation System
sending data wherever and promptly. verywidespread in the Anglo-Saxon countries and in
general in Europe.
By simply connecting a GSM modem, the DB5
controllers not limited to send alarms and The DB5 controller is TREND compatible, through
information only, but also receive commands via the proper serial card. TREND deals with the
configuration and the supply of the interface card.
-6-
DB-AIRE II DESIGN FEATURES
-7-
PERFORMANCE AND TECHNICAL DATA
Sensible Heat Ratio (SHR) 0.74 0.76 0.81 0.83 0.82 0.80
Sensible Heat Ratio (SHR) 0.79 0.82 0.85 0.85 0.88 0.87
Sensible Heat Ratio (SHR) 0.83 0.85 0.89 0.89 0.89 0.87
Number of
1 1 1 1 1 1
Compressor(s)
Total Power Input
kW 3.4 3.4 4.7 5.2 6.5 10.2
(50Hz)
Total Power Input
Compressor kW N/A N/A 4.4 5.4 6.6 11.2
(60Hz)
Hot Gas; Liquid Lines,
Inch 5/8 ; 1/2 5/8 ; 1/2 5/8 ; 1/2 5/8 ; 1/2 7/8 ; 1/2 7/8 ; 5/8
50Hz
Hot Gas; Liquid Lines,
Inch N/A N/A 5/8 ; 1/2 5/8 ; 1/2 7/8 ; 1/2 7/8 ; 1/2
60Hz
PHYSICAL DATA
mm 1944 1944 1944 1944 1944 1944
Height H
(inch) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5)
mm 749 749 749 749 1464 1464
Width W
(inch) (29.5) (29.5) (29.5) (29.5) (57.6) (57.6)
mm 874 874 874 874 874 874
Depth D
(inch) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4)
kg 251 259 260 272 420 450
Weight
(lbs) (552) (570) (572) (598) (924) (990)
Notes: 1.) Add 457mm (18inch) to height of unit for Discharge Plenum (optional) Upflow Models only
2.) Add 32kg (71lbs)- Model 02 to 05; 51kg(112 lbs)-Model 07 to 13; 80kg(176 lbs)- Model 14 to 26 to weight of unit for Discharge Plenum (optional)- Upflow Model only
-8-
PERFORMANCE AND TECHNICAL DATA
Sensible Heat Ratio (SHR) 0.83 0.80 0.79 0.80 0.80 0.80 0.80
Sensible Heat Ratio (SHR) 0.89 0.86 0.84 0.86 0.86 0.86 0.85
Sensible Heat Ratio (SHR) 0.90 0.86 0.86 0.87 0.87 0.86 0.86
Number of
1 1 2 2 2 2 2
Compressor(s)
Total Power Input
kW 11.1 12.7 14.7 17.1 20.3 21.8 26.1
(50Hz)
Total Power Input
Compressor kW 12.3 13.0 16.3 17.9 22.2 24.2 26.9
(60Hz)
Hot Gas; Liquid Lines, 7/8(2); 7/8(2); 7/8(2); 7/8(2); 7/8(2);
Inch 7/8; 5/8 7/8; 5/8
50Hz 1/2(2) 1/2(2) 5/8(2) 5/8(2) 5/8(2)
Hot Gas; Liquid Lines, 7/8(2); 7/8(2); 7/8(2); 7/8(2); 7/8(2);
Inch 7/8; 5/8 7/8; 5/8
60Hz 1/2(2) 1/2(2) 1/2(2) 5/8(2) 5/8(2)
15/15 15/15 15/15 15/15 15/15
Fan Size 15/15 15/15
(Twin) (Twin) (Twin) (Twin) (Twin)
CFM 6,000 6,500 8,000 10,000 11,000 11,000 13,000
Air Volume
Fan & Motor (m3/h) (10,194) (11,043) (13,592) (16,989) (18,688) (18,688) (22,086)
(Indoor) External Static in H2O 0.5 0.5 0.5 0.5 0.5 0.5 0.5
Pressure (ESP) (Pa) (125) (125) (125) (125) (125) (125) (125)
Motor (Standard Hp 4.0 5.5 4.0 5.5 7.5 7.5 10.0
Single Coil) (kW) (3.0) (4.0) (3.0) (4.0) (5.5) (5.5) (7.5)
ft2 12.2 12.2 23.9 23.9 23.9 23.9 23.9
Face Area
(m2) (1.1) (1.1) (2.2) (2.2) (2.2) (2.2) (2.2)
Coil (DX) FPM 491 532 335 419 461 461 544
Face Velocity
(m/s) (2.5) (2.7) (1.7) (2.1) (2.3) (2.3) (2.8)
Condensate Drain O.D Inch 7/8 7/8 7/8 7/8 7/8 7/8 7/8
20" x 20" x 2" Qty N/A N/A N/A N/A N/A N/A N/A
Filters
(ASHRAE 52.5 20" x 20" x 4" Qty 4 4 6 6 6 6 6
MERV 8)
20" x 25" x 4" Qty N/A N/A 2 2 2 2 2
Reheat 3-Stages MBH 41.0 41.0 61.4 61.4 61.4 61.4 61.4
(Electric) (rated at 415V) (kW) (12.0) (12.0) (18.0) (18.0) (18.0) (18.0) (18.0)
lbs/hr 17 17 33 33 33 33 33
Capacity (max.)
Steam Humidifier (kg/hr) (8.0) (8.0) (15.0) (15.0) (15.0) (15.0) (15.0)
(Optional)
Power Input (max.) kW 6.0 6.0 11.3 11.3 11.3 11.3 11.3
PHYSICAL DATA
mm 1944 1944 1944 1944 1944 1944 1944
Height H
(inch) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5)
mm 1464 1464 2554 2554 2554 2554 2554
Width W
(inch) (57.6) (57.6) (100.6) (100.6) (100.6) (100.6) (100.6)
mm 874 874 874 874 874 874 874
Depth D
(inch) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4)
kg 460 474 735 754 802 823 835
Weight
(lbs) (1,012) (1,043) (1,617) (1,659) (1,764) (1,811) (1,837)
Notes: 1.) Add 457mm (18inch) to height of unit for Discharge Plenum (optional) Upflow Models only
2.) Add 32kg (71lbs)- Model 02 to 05; 51kg(112 lbs)-Model 07 to 13; 80kg(176 lbs)- Model 14 to 26 to weight of unit for Discharge Plenum (optional)- Upflow Model only
-9-
PERFORMANCE AND TECHNICAL DATA
CHILLED WATER SYSTEM @ WATER SUPPLY/ RETURN 7C/ 12C (44.6F/ 53.6F)
DBCD/U DBCD/U DBCD/U DBCD/U DBCD/U DBCD/U
Model
02 03 04 05 07 09
Total Cooling MBH 47.1 64.1 83.9 98.8 151.8 188.4
Capacity (kW) (13.8) (18.8) (24.6) (28.9) (44.5) (55.2)
Sensible Cooling MBH 33.9 42.9 57.6 69.0 106.1 130.8
Capacity (kW) (9.9) (12.6) (16.9) (20.2) (31.1) (38.3)
Return Air
80F/67F/50% RH Sensible Heat Ratio (SHR) 0.72 0.67 0.69 0.70 0.70 0.69
(27C/19C/50% RH)
GPM 10.5 14.3 18.7 22.0 33.8 41.9
Water Flow Rate
(m3/hr) (2.4) (3.2) (4.2) (5.0) (7.7) (9.5)
PSI 4.2 10.4 3.7 4.9 5.0 18.3
Water Pressure Drop
(kPa) (29.3) (71.4) (25.7) (34.1) (34.7) (125.8)
Total Cooling MBH 32.8 44.3 59.3 70.0 107.0 133.6
Capacity (kW) (9.6) (13.0) (17.4) (20.5) (31.4) (39.1)
Sensible Cooling MBH 29.0 36.0 49.0 59.2 90.5 111.9
Capacity (kW) (8.5) (10.5) (14.4) (17.3) (26.5) (32.8)
Return Air
75F/62.5F/50% RH Sensible Heat Ratio (SHR) 0.88 0.81 0.83 0.85 0.85 0.84
(24C/17C/50% RH)
GPM 7.3 9.9 13.2 15.6 23.8 29.7
Water Flow Rate
(m3/hr) (1.7) (2.2) (3.0) (3.5) (5.4) (6.7)
PSI 2.3 5.5 2.1 2.7 2.7 10.1
Water Pressure Drop
(kPa) (15.8) (38.0) (14.3) (18.8) (18.8) (69.6)
Total Cooling MBH 26.8 35.9 48.1 57.0 86.9 108.9
Capacity (kW) (7.9) (10.5) (14.1) (16.7) (25.5) (31.9)
Sensible Cooling MBH 26.4 32.5 44.4 53.8 82.0 101.7
Capacity (kW) (7.7) (9.5) (13.0) (15.8) (24.0) (29.8)
Return Air
72F/60F/50% RH Sensible Heat Ratio (SHR) 0.99 0.91 0.92 0.94 0.94 0.93
(22C/16C/50% RH)
GPM 6.0 8.0 10.7 12.7 19.3 24.2
Water Flow Rate
(m3/hr) (1.4) (1.8) (2.4) (2.9) (4.4) (5.5)
PSI 1.6 3.9 1.4 1.9 1.9 7.1
Water Pressure Drop
(kPa) (11.1) (26.6) (9.9) (13.2) (13.2) (49.0)
Fan Size 10/8 10/8 10/8 10/8 15/15 15/15
CFM 1,500 1,500 2,000 2,500 4,000 5,000
Air Volume
(m3/h) (2,548) (2,548) (3,398) (4,247) (6,796) (8,495)
Fan & Motor
(Indoor) External Static in H2O 0.3 0.3 0.3 0.3 0.5 0.5
Pressure (ESP) (Pa) (75) (75) (75) (75) (125) (125)
Hp 1.0 1.0 1.0 2.0 2.0 3.0
Motor
(kW) (0.75) (0.75) (0.75) (1.5) (1.5) (2.2)
ft2 5.6 5.6 5.6 5.6 12.2 12.2
Face Area
(m2) (0.5) (0.5) (0.5) (0.5) (1.1) (1.1)
Coil FPM 270 270 360 450 327 409
Face Velocity
(Chilled Water) (m/s) (1.4) (1.4) (1.8) (2.3) (1.7) (2.1)
Condensate Drain
Inch 7/8 7/8 7/8 7/8 7/8 7/8
O.D
PHYSICAL DATA
mm 1944 1944 1944 1944 1944 1944
Height H
(inch) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5)
mm 749 749 749 749 1464 1464
Width W
(inch) (29.5) (29.5) (29.5) (29.5) (57.6) (57.6)
mm 874 874 874 874 874 874
Depth D
(inch) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4)
kg 205 212 219 229 365 374
Weight
(lbs) (451) (466) (482) (504) (803) (823)
Note: 1.) Add 457mm (18 inch) to height of unit for Discharge Plenum (optional) Upflow Models only
2.) Add 32kg (71lbs)- Model 02 to 05; 51kg(112 lbs)- Model 07 to 13; 80kg(176 lbs)- Model 14 to 26 to weight of unit for Discharge Plenum (optional)- Upflow Model only
- 10 -
PERFORMANCE AND TECHNICAL DATA
CHILLED WATER SYSTEM @ WATER SUPPLY/ RETURN 7C/ 12C (44.6F/ 53.6F)
Model DBCD/U 11 DBCD/U 13 DBCD/U 14 DBCD/U 16 DBCD/U 19 DBCD/U 22 DBCD/U 26
PHYSICAL DATA
mm 1944 1944 1944 1944 1944 1944 1944
Height H
(inch) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5)
mm 1464 1464 2554 2554 2554 2554 2554
Width W
(inch) (57.6) (57.6) (100.6) (100.6) (100.6) (100.6) (100.6)
mm 874 874 874 874 874 874 874
Depth D
(inch) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4)
kg 398 410 602 615 665 678 688
Weight
(lbs) (876) (902) (1,324) (1,353) (1,463) (1,492) (1,514)
Note: 1.) Add 457mm (18 inch) to height of unit for Discharge Plenum (optional) Upflow Models only
2.) Add 32kg (71lbs)- Model 02 to 05; 51kg(112 lbs)- Model 07 to 13; 80kg(176 lbs)- Model 14 to 26 to weight of unit for Discharge Plenum (optional)- Upflow Model only
- 11 -
DUAL COILS OPTION
Notes: 1.) Add 457mm (18inch) to height of unit for Discharge Plenum (optional) Upflow Models only
2.) Add 32kg (71 lbs)- Model 02 to 05; 51kg(112 lbs)-Model 07 to 13; 80kg(176 lbs)- Model 14 to 22 to weight of unit for Discharge Plenum (optional)- Upflow Model only
CONDENSER SELECTION
Selections are to be based on standard airflow rate and return air temperature of 24C / 17C (75F / 62.5F) or
lesser at sea level.
DX-System DBAD/U 02 DBAD/U 03 DBAD/U 04 DBAD/U 05 DBAD/U 07 DBAD/U 09
Model
Dual Coils
DBDD/U 02 DBDD/U 03 DBDD/U 04 DBDD/U 05 DBDD/U 07 DBDD/U 09
System
Total Heat Rejection MBH 46 51 60 73 101 151
(Nominal) (kW) (14) (15) (18) (21) (30) (44)
43C (110F) Ambient See Note 1 DBRC06 DBRC06 DBRC08 DBRC11 DBRC17 DBRC20
46C (115F) Ambient See Note 1 DBRC08 DBRC11 DBRC17 DBRC17 DBRC26 DBRC34
49C (120F) Ambient See Note 2 DBRC11 DBRC11 DBRC17 DBRC20 DBRC26 DBRC34
52C (125F) Ambient See Note 3 DBRC13 DBRC13 DBRC20 DBRC26 DBRC30 DBRC40
35C (95F) Ambient - DBRC13 DBRC17 DBRC17 DBRC20 DBRC20 DBRC26 DBRC30
37.8C (100F) Ambient - DBRC17 DBRC17 DBRC20 DBRC26 DBRC26 DBRC30 DBRC30
40.6C (105F) Ambient - DBRC20 DBRC26 DBRC26 DBRC26 DBRC34 DBRC34 DBRC34
43C (110F) Ambient See Note 1 DBRC26 DBRC30 DBRC34 DBRC40 DBRC44 DBRC44 DBRC44
46C (115F) Ambient See Note 1 DBRC40 DBRC44 DBRC44 DBRC30 x 2 DBRC30 x 2 DBRC40 x 2 DBRC40 x 2
49C (120F) Ambient See Note 2 DBRC40 DBRC44 DBRC44 DBRC30 x 2 DBRC34 x 2 DBRC40 x 2 DBRC44 x 2
52C (125F) Ambient See Note 3 DBRC44 DBRC44 DBRC26 x 2 DBRC30 x 2 DBRC34 x 2 DBRC44 x 2 DBRC44 x 2
- 12 -
ELECTRICAL DATA
o o o o
Return Air at 24 C/17 C/50 %RH (75 F/62.5 F/ 50 %RH)
Model DBCD/U 02 DBCD/U 03 DBCD/U 04 DBCD/U 05 DBCD/U 07 DBCD/U 09
Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS
380V/ 3Ph/ 50Hz 9.7 12 16 9.7 12 16 9.7 12 16 11.3 13 16 18.9 23 30 20.3 24 30
400V/ 3Ph/ 50Hz 10.0 12 16 10.0 12 16 10.0 12 16 11.5 14 16 19.6 24 30 20.8 25 30
415V/ 3Ph/ 50Hz 10.2 12 16 10.2 12 16 10.2 12 16 11.7 14 16 20.0 24 30 21.2 25 30
460V/ 3Ph/ 60Hz N/A N/A 9.1 11 16 9.8 12 16 18.1 22 30 19.2 23 30
o o o o
Return Air at 24 C/17 C/50 %RH (75 F/62.5 F/ 50 %RH)
Model DBCD/U 02 DBCD/U 03 DBCD/U 04 DBCD/U 05 DBCD/U 07 DBCD/U 09
Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS
380V/ 3Ph/ 50Hz 18.8 21 30 18.8 21 30 18.8 21 30 20.4 22 30 28.0 32 32 29.4 33 40
400V/ 3Ph/ 50Hz 18.7 21 30 18.7 21 30 18.7 21 30 20.2 22 30 28.2 32 40 29.5 33 40
415V/ 3Ph/ 50Hz 18.6 21 30 18.6 21 30 18.6 21 30 20.0 22 30 28.4 33 40 29.6 34 40
460V/ 3Ph/ 60Hz N/A N/A 16.7 19 20 17.4 19 30 25.6 29 40 26.7 30 40
Note : RLA - Rated Load Amps MCA - Minimum Circuit Amps MFS - Maximum Fuse Size
- 13 -
DIMENSIONAL DATA
DBAD DBAD DBAD DBAD DBAD DBAD DBAD DBAD DBAD DBAD DBAD DBAD DBAD
DOWN FLOW DX System
02 03 04 05 07 09 11 13 14 16 19 22 26
CW DBCD DBCD DBCD DBCD DBCD DBCD DBCD DBCD DBCD DBCD DBCD DBCD DBCD
Model
System 02 03 04 05 07 09 11 13 14 16 19 22 26
Dual Coils DBDD DBDD DBDD DBDD DBDD DBDD DBDD DBDD DBDD DBDD DBDD DBDD
-
System 02 03 04 05 07 09 11 13 14 16 19 22
mm 1944 1944 1944 1944 1944 1944 1944 1944 1944 1944 1944 1944 1944
Height H
(inch) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5) (76.5)
mm 749 749 749 749 1464 1464 1464 1464 2554 2554 2554 2554 2554
Width W
(inch) (29.5) (29.5) (29.5) (29.5) (57.6) (57.6) (57.6) (57.6) (100.6) (100.6) (100.6) (100.6) (100.6)
mm 874 874 874 874 874 874 874 874 874 874 874 874 874
Depth D
(inch) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4) (34.4)
H H H
- 14 -
REMOTE AIR-COOLED CONDENSERS
TECHNICAL DATA
DBRC 04 870 (34) 1 2030 (4300) 100 (220) 1 900 1075 220~240Vac, 1Ph, 50/60Hz.
FLA @ 240V/50Hz = 1.4A;
FLA @ 240V/60Hz = 1.5A
DBRC 06 870 (34) 1 3210 (6800) 111 (244) 1 925 1110 2.0 1.9 1.8 1.7
DBRC 08 870 (34) 1 3210 (6800) 122 (268) 1 925 1110 2.0 1.9 1.8 1.7
DBRC 10 870 (34) 1 3210 (6800) 134 (295) 1 925 1110 2.0 1.9 1.8 1.7
DBRC 11 870 (34) 1 3210 (6800) 180 (400) 1 925 1110 2.0 1.9 1.8 1.7
DBRC 13 1683 (66) 2 6420 (13600) 190 (420) 2 925 1110 4.0 3.8 3.6 3.4
DBRC 17 1683 (66) 2 6420 (13600) 204 (450) 2 925 1110 4.0 3.8 3.6 3.4
DBRC 20 1683 (66) 2 6420 (13600) 265 (583) 2 925 1110 4.0 3.8 3.6 3.4
DBRC 26 2500 (98) 3 9630 (20400) 288 (634) 3 925 1110 6.0 5.7 5.4 5.1
DBRC 30 2500 (98) 3 9630 (20400) 320 (700) 3 925 1110 6.0 5.7 5.4 5.1
DBRC 34 2500 (98) 3 9630 (20400) 355 (780) 3 925 1110 6.0 5.7 5.4 5.1
DBRC 40 3308 (130) 4 12838 (27200) 380 (835) 4 925 1110 8.0 7.6 7.2 6.8
DBRC 44 3308 (130) 4 12838 (27200) 410 (900) 4 925 1110 8.0 7.6 7.2 6.8
- 15 -
TYPICAL WIRING SCHEMATIC
DBAD/U
- 16 -
TYPICAL WIRING SCHEMATIC
- 17 -
TYPICAL WIRING SCHEMATIC
- 18 -
TYPICAL WIRING SCHEMATIC
- 19 -
TYPICAL WIRING SCHEMATIC
DBRC
- 20 -
GUIDE SPECIFICATIONS
This specification describes requirements for precision 1 STANDARD FEATURES (ALL SYSTEMS,
air conditioning system. The system shall be designed INDOOR UNIT)
to maintain precised temperature and humidity
conditions for applications such as computer server 1.1 Cabinet
rooms, telecommunication facilities, clean rooms, The cabinet comprises an anodized aluminium
laboratories, etc. The precision environmental control frame of epoxy powder coated black color paint
system shall be factory assembled, DB-Aire II model with nylon corners and removable steel sheet
vertical floor mounted by Dunham-Bush Industries, panels. All panels shall be externally installed onto
Malaysia. the cabinet by using special stopper system
without using screws. The stopper system shall
DESIGN REQUIREMENTS also facilitate the removable of panels for
(A) Direct Expansion (DX) System additional ease of field installation, service and
The system shall have a total cooling capacity of maintenance on the system. All panels and access
_____MBH /_____kW and a sensible cooling doors shall be fabricated from sturdy heavy gauge
capacity of _____MBH /_____kW based on an of 1.0mm steel sheets with epoxy powder coated
o
entering air temperature of _____ F /_____ C
o oven baked black color paint to provide a durable
DB and _____ oF /_____oC WB. finish. All panels shall be of 25mm (1 inch) thick
single skin and lined with minimum 2lbs/ft3 density
The system shall be designed based on thermal and acoustical fiberglass insulation with
_____oF /_____oC DB ambient temperature. For fire resistant of Class O (BS 476 Part 6, 7). The
low ambient application, the system shall also be system shall be designed for front access only with
o o
designed to operate at _____ F/_____ C DB hinged and lock type full height doors.
ambient temperature.
The unit shall be supplied with 1.2 Filters
_____/_____/_____(Volt/Phase/Hz) electrical The system shall be provided with 2 inches (50mm)
service. deep (for model 02-05) or 4 inches (100mm) deep
The unit shall be of Upflow / Downflow (for model 07-26) extended surface pleated
configured model. disposable type filters rated for MERV8 efficiency
to ASHRAE 52.2 standard (equivalent to EU4).
(B) Chilled Water (CW) System Filters shall be withdrawable from the front of the
The system shall have a total cooling capacity of unit.
_____MBH /_____kW and a sensible cooling
capacity of _____MBH /_____kW based on an 1.3 Blower Assembly
entering air temperature of _____oF /_____oC Blowers shall be belt driven double-inlet-double-
o o
DB and _____ F /_____ C WB. width (DIDW), statically and dynamically balanced
The system shall be supplied with chilled water with multiple forward curved blades mounted on a
with an entering water temperature of _____oF / solid steel keyed shaft. Heavy-duty V-belt fan drive
o
_____ C and leaving water temperature (sized for 200% safety factor) with cast iron pulleys
_____oF /_____oC. keyed and secured to the blower shaft shall be
The unit shall be supplied with provided.
_____/_____/_____ (Volt/Phase/Hz) electrical
service. 1.4 Motor Assembly
The unit shall be of Upflow / Downflow Motors shall be of totally enclosed fan cooled
configured model. (TEFC) with IP55 enclosure rating. Motors shall be
mounted to an adjustable motor frame. Motor
(C) Dual Coils (DX + CW) System pulleys shall be cast iron, keyed and secured to
the motor shaft.
The system shall have a total cooling capacity of
______MBH /______kW and a sensible cooling
1.5 Evaporator Air Discharge
capacity of _____MBH /_____kW based on an
entering air temperature of _____F /_____C
1.5.1 Up-Flow (Front Free Return)
DB and _____F /_____C WB.
The DX system shall be designed based on The system shall be configured for up-flow
_____F /_____ C DB ambient temperature. pattern with front free evaporator return air
For low ambient application, the system shall and top evaporator air discharge. The system
also be designed to operate at _____F/_____C shall be supplied with grilles on the cabinet
DB ambient temperature. doors for front return air configuration. Up-
flow systems are available with optional
The CW system shall be supplied with chilled
Discharge Plenum.
water with an entering water temperature of
______F / ______C and leaving water 1.5.2 Down-Flow (Top Free or Ducted Return)
temperature _____F /_____C.
The system shall be configured for down-flow
The unit shall be supplied with pattern with top free or ducted evaporator
_____/_____/______ (Volt/Phase/Hz) electrical return air and bottom evaporator air
service. discharge through the raised floor.
The unit shall be of Upflow / Downflow
configured model.
- 21 -
GUIDE SPECIFICATIONS
1.6 Electric Reheat High supply air temperature
The electric reheat shall be factory installed low High room humidity
watt density finned-tubular nickel plated element Low room humidity
heater with overheat safety controls. The electric No air flow/loss of air flow
reheat shall be of three equal stages giving a more Filter dirty
accurate controlled response to the room Sensor failure
requirement. Evaporator fan overload alarm
Customer interlock alarm
1.7 Electrical Circuits Unit/ Compressor running hours threshold
The system shall be provided with a factory exceeded
installed electrical enclosure as per local code LAN network disconnected alarm
requirements. Control voltage of the system shall High/Low refrigerant pressure alarm (DX
be 24Vac. The fan motor(s), compressor(s), models)
electric heaters, humidifier (if applicable) shall have Chilled water flow switch alarm (chilled
their own circuit breaker and contactor. The water models)
electrical circuit shall have provision for user to cut Humidity Alarms
off control power during fire / emergency shutdown Under floor water detector alarm (optional)
Smoke detector alarm (optional)
1.8 Control System Vision 2020i Controller
1.8.3 Master-Slave Sequencing Control
1.8.1 Controller and display When more than one unit is present in the
The unit shall be provided with Vision 2020i system, master-slave or duty-standby
control system with the following features, control of this group of units shall be done
The control algorithm and parameters by just connecting controller of each unit in
shall be stored in flash memory and serial and require no additional controller.
2
E PROM of the controller and shall retain 1.8.4 BMS communications and remote
even in the event of power failures, monitoring
without requiring a backup battery
4.3 graphical touch terminal with 65k ModBus RTU RS485 communication port
color display shall be a standard feature of the controller.
On top of that, the following options shall be
Built in memory for data logging
available for BMS communications and
Temperature and humidity controlled remote monitoring:
Configurable by user
ModBus TCPIP
Alarm status/display
BACnet TCPIP / PTP / MSTP
Analog input/output display
LONworks
Digital input/output status
GSM Modem
Remote start/stop input
SNMP
Digital input for customer input alarm
General alarm output (dry contact)
Self-diagnostics 2 DIRECT EXPANSION (DX) SPLIT SYSTEMS
Security password access with multiple WITH REMOTE OUTDOOR AIR COOLED
access level for advanced settings CONDENSER (DBRC MODELS)
Unit status display with following
information: 2.1 Scroll Compressor
Current room temperature and Compressor shall be mounted on the base via
temperature setpoint vibration isolators. Compressor shall be charged
Current room relative humidity and with polyolester oil and designed for use with
relative humidity setpoint R407C refrigerant.
System ON/OFF
Operating mode (cooling/ heating/ 2.2 Refrigeration Circuits
humidifying/ dehumidifying)
The refrigeration system shall be of the direct
1.8.2 Alarm Monitoring expansion type with one (Model 02-13) or two
When the system is in alarm condition, the (Model 14-26) hermetic scroll compressors
system shall activate an audible buzzer and complete with rotalock connections. All
visual alarm message on the terminal refrigeration circuit shall be pre-piped with copper
display. A digital output (dry contact) shall tubing and include expansion valve with external
be closed to indicate the alarm condition. equalizer, filter dryer, sight glass, refrigerant
The following alarm conditions shall be service valves, pressure fittings of manual reset
monitored by the controller: high pressure control/auto reset low pressure
High room temperature safety cutouts and charging/access ports in each
Low room temperature circuit.
- 22 -
GUIDE SPECIFICATIONS
2.3 Evaporator Coil 4.2 Discharge Plenum (Up-flow Units only)
The evaporator coil shall be of draw through air A discharge plenum box shall be provided for field
design for uniform air distribution. The evaporator installation on the top of the up-flow unit. The
coil shall be quality construction of seamless plenum box shall be 18 inches (457mm) high,
copper tube, mechanically bonded to hydrophilic insulated and painted to match the color of the
aluminium fins with galvanized coil plates. The coil indoor unit. The plenum box shall be fitted with
shall be factory leak and pressure tested to double deflection grilles for room discharge of
450psig (31 bar) and the refrigeration system shall conditioned air.
be sealed prior to shipment. A galvanized and
painted drain pan shall be provided to cover the 4.3 Steam Generating Humidifier
entire coil area. The drain pan shall be designed to Humidifier shall be factory installed inside the unit.
incorporate sloped gutter for complete condensate The humidification system shall be an electrode
removal. cylinder type, complete with fill valve, drain valve,
adjustable humidity output and automatic flush
2.4 Remote Outdoor Air Cooled Condenser (DBRC cycle activated on demand from the
Models) microprocessor control system.
The remote condenser shall be constructed from 4.4 Hot Gas Bypass (DX Systems only)
sturdy heavy gauge steel sheets with epoxy The refrigerant circuit(s) shall be provided with a
powder coated oven baked, factory standard beige hot gas bypass system for evaporator freeze-
color to provide a durable finish. protection and capacity modulation during low
The remote condenser shall include direct driven load conditions.
propeller fans, condenser coil, fan guard, thermally
protected rated IP55 motors, integral factory wired 4.5 Liquid Line Solenoid Valve (DX Systems only)
and tested control panel. The condenser coil shall A factory fitted liquid line solenoid valve shall be
be quality construction of seamless copper tube, provided for each refrigeration circuit as an option.
mechanically bonded to aluminium fins with
galvanized coil plates. The coil shall be factory 4.6 Double Skin Panels
leak and pressure tested to 450psig (31 bar) and All panels shall be provided with galvanized
the refrigeration system shall be sealed prior to internal skin.
shipment. 4.7 Insulflex Closed Cell Insulation
The evaporator and condenser sections shall ship All panels shall be single skin and lined with
with a dry-nitrogen holding charge ready for field Insulflex Closed Celled insulation (in lieu of
refrigerant charging. fiberglass insulation) with fire resistant of Class O
(BS476 Part 6) and Class 1 (BS476 Part 7).
3 CHILLED WATER (CW) SYSTEMS
4.8 Hydrophilic or Copper Fin for Condenser Coil
3.1 Chilled Water Coil (DBRC)
The evaporator coil shall be of draw through air Condenser coils shall be provided with hydrophilic
design for uniform air distribution. The chilled water or copper fins in lieu of aluminium.
coil shall be quality construction of seamless 4.9 Black Color Epoxy Powder Coating for
copper tube, mechanically bonded to hydrophilic Remote Condenser (DBRC)
aluminium fins with galvanized coil plates. The coil The remoter condenser DBRC shall be epoxy
shall be factory leak and pressure tested to powder coated oven baked black color paint in
450psig (31 bar) and sealed prior to shipment. lieu of standard beige color.
Copper pipe for brazed connection shall be
provided as standard. A galvanized and painted 4.10 Under Floor Water Detector
drain pan shall be provided to cover the entire coil A remote water leak detector shall be factory
area. The drain pan shall be designed to provided for field installation. When water leak is
incorporate sloped gutter for complete condensate detected, cooling mode of the unit is off.
removal.
4.11 Smoke Detector
3.2 Chilled Water Control A smoke detector shall be factory supplied at
The water circuit shall include 3-way forged brass units evaporator return air section. The unit shall
valve and modulating actuators. The shut down when smoke alarm is triggered.
microprocessor positions the valve in response to 4.12 Variable Frequency Drive (VFD) for Evaporator
room condition. Cooling capacity shall be Blower Motor
controlled by bypassing chilled water around the A variable frequency drive (VFD) for blower motor
coil. shall be factory installed to vary the blower motor
speed based on rooms requirement.
- 23 -
Malaysia China Europe
Lot 5755-6, Kidamai Industrial Park, No. 1 Dunham-Bush Road, United Kingdom
Bukit Angkat, Laishan District,
43000 Kajang, Yantai, 8 Downley Road,
Selangor Darul Ehsan, Shandong Province, Havant, Hampshire,
Malaysia China 264003 England PO9 2JD
Al Murad Tower, Office 506 2, Kallang Pudding Road #07-07, No. 57 Sovereign Drive
Al-Barsha 1, Mactech Industrial Building, Route 21 Corporate Park
P. O. Box # 30922, Singapore 349307 Irene, Pretoria
Dubai, UAE South Africa
Tel: 65-6842 2012
Tel: 971-4-451 9899 Fax: 65-6842 2013 Tel: 27-12-345 4202
Fax: 971-4-451 9881 Fax: 27-12-345 4203
info@dunham-bush.com
www.dunham-bush.com Products that perform...By people who care
Manufacturer reserves the right to change specifications without prior notice. M-S-0704A-0712