Vous êtes sur la page 1sur 313

PIPING SUPPORT STANDARD

DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 1 de 16

PIPING SUPPORT STANDARD DRAWING

N del Contrato : DLG 0304


N del Proj. de SECL : SC2566

1 10 DEC 2014 IFC-1 For Construction T.J.Lee Y.Y.Hwang J.J.YANG

0 24 MAR 2014 IFC For Construction T.J.Lee Y.Y.Hwang J.J.YANG

Descripcin del Preparado Verificado Aprobado


Rev Fecha Estado
Estado por por por

Revisin del Documento Pgina: Total de 16 hojas (Incl. Cartula)


PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 2 de 16

RESUMEN DE REVISION DEL DOCUMENTO

Fecha de Seccin
Rev. Descripcin de Revisin
Revisin Revisada
A 10 MAY 2013 N/A Issue for Preliminary
Issued for Review
N/A
-YPFB comments reflected
B 17 SEP 2013
Appendix II
Support drawings revised
Appendix III
C 03 DEC 2013 N/A Issued for Review

0 24 MAR 2014 N/A Issued for Construction

1 10 DEC 2014 N/A Issued for Construction


PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 3 de 16

TABLA DE CONTENIDOS

1. GENERAL...5

1.1. Intent...........5

1.2. Codes and Standards..........................................................................................5

1.3. Units....................................................................................................................5

1.4. Related Specifications.........................................................................................6

1.5. Pipe Support Drawing.........................................................................................6

2. INSTALLATION REQUIREMENTS........................................................................6

2.1. General...........6

2.2. Notes for Pipe Support Works.............................................................................6

3. GENERAL INSTRUCTIONS FOR PIPE SUPPORT DETAILS..8

3.1. General....8

3.2. Shoe....9

3.3. Pipe Guide.........9

3.4. Pick-up Support..................11

3.5. Support Trunnion.....12

3.6. Maximum Loading on Paved Area....................................................................12

3.7. Hold-down....12

3.8. Spring Wedge......12

3.9. Dummy Support...12

3.10. Pipe Support Span............................................................................................13

4. RECOMMENDED METHODS FOR SUPPORT OF SMALL PIPE (1.1/2 AND


SMALLER) IN FIELD...............................................................15

4.1. Purpose.....15
PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 4 de 16

4.2. Pipe Support Spans.........................15

4.3. Permissible Overhang Variations......................................................................15

4.4. Miscellaneous Support...17

5. PAINTING.....17

APPENDIX
I- I. STANDARD COLLECTION OF STEEL BEAM & ANCHOR BOLT
I- II. STANDARD COLLECTION OF SUPPORT MATERIAL
I- III. SELECTION GUIDE OF SUPPORT ATANDARDS
II. PIPE SUPPORT STANDARD DRAWINGS
III. VESSEL SUPPORT STANDARD DRAWINGS
PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 5 de 16

1 GENERAL

1.1 Intent

This specification covers the minimum technical engineering requirements for the
design of pipe supports for the piping systems designed by Samsung Engineering
Co., Ltd. (hereinafter referred to as CONTRACTOR), and shall be used as the
general instructions for the Pipe Support Details. This specification shall generally
exclude piping systems furnished as a regular part of the manufacturer's
standardized equipment or package facility.

1.2 Codes and Standards

The design, fabrication, inspection and testing of support material shall be in


accordance with the applicable codes and standards and industry practice.

1.2.1 Codes
Comply with all applicable federal, state and local codes including:

ANSI American National Standards Institute


B.1.1 Unified Screwed Threads
B.18.2.1 Square and Hex Nuts
B.18.2.2 Square and Hex Bolts and Screws, including
Askew Head Bolts, Hex Cap Screws, and Lag
Screws
ASME American Society of Mechanical Engineering
B31.3 Chemical Plant and Petroleum Refinery Piping
ASTM American Society for Testing and Materials

1.2.2 Standards
Comply with the following standards:

MSS - Manufacturers Standardization Society


SP-58 - Pipe Hangers and Supports -- Materials, Design and Manufacture
SP-69 - Pipe Hangers and Supports Selection and Application
SP-89 - Pipe Hangers and Supports -- Fabrication and Installation Practices

1.3 Units

Unless otherwise specified, metric, Celsius and kilogram units shall be applied as
the measurement system for drawings and documents to be submitted.
However, nominal sizes of piping components shall be in accordance with inch
system, which abbreviation is (NPS).
PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 6 de 16

1.4 Related Specifications

PAU-DPI-C-SPC-00001 Piping Material Specification


PAU-EPI-C-SPC-00002 Insulation Specification
PAU-EPI-C-SPC-00003 Painting Specification

1.5 Pipe Support Drawings

Pipe support drawings are divided into two parts as follows;

(1) Selection Guide of Pipe Support.


These drawings shall be used in design office only to select the proper type of
support for the pipes.

(2) Pipe Support Details.


These details are to be used for the purpose of Bid, Fabrication and
Construction. The details are included with pipe support standard drawings and
vessel support standard drawings.

2 INSTALLATION REQUIREMENTS

2.1 General

2.1.1 All pipe support shall be provided for piping of 2" and larger. Supports will
be identified and located in the piping isometric drawing. For pipe size 1.1/2
and smaller, pipe support shall be installed in field based on the section 4,
with exceptions as follows.

(1) Lines with operating temperature of pipe is 400C or greater.


(2) Process pipe lines in refrigeration service, -43C and below, requiring
cold insulated supports.
(3) Piping connected to rotating equipment.
(4) Piping which requires supports from vessels.
(5) All of the piping with hot & cold cradles.
(6) Piping in services requiring Class 900 ANSI flange rating or higher.
(7) Plastic lines carrying process fluids.
(8) Other piping required by stress engineer.

2.1.2 Support shall be designed and installed to prevent electrolysis of galvanic


action at surface of piping.

2.2 Notes for Pipe Support Works

2.2.1 The welding shall be carefully done as indicated on the pipe support details.
For all the Stress Relieve line, weld points between main pipe and support
attachment in the case of dummy support or trunnion type support shall be
PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 7 de 16

stress-relieved.

2.2.2 The welded material to piping shall be compatible for pipe and attachment.
Consideration shall be given to the localized stresses induced in the piping
component by welding the integral attachment.

2.2.3 Support shoes shall be centered over supporting beams unless otherwise
indicated.

2.2.4 No clearance shall be allowed between the bottom of pipes or shoes and
the top of support beams unless otherwise noted. Where clearance exists,
it shall be adjusted with insert plates. Insert plates shall be equal to the
beams of the width and suitable length considering lateral movement of
piping, and welded to the beams at both ends.

U-bolts and U-bands shall never be installed before adjustment with insert
plates. Specially, U-bolts and U-bands shall be prohibited for the piping
having a big thermal growth 10mm and over, due to equipment expansion
or initial movements.

2.2.5 Hangers shall be adjusted to give tension consistent with the pipe weight
without causing excessive tension.

2.2.6 Where resting supports are designed to slide along foundation or


pavement, the mortar level shall be lower than the sliding surface. The
mating plate shall be inserted top of foundation. Sliding surface shall be
adjusted to be horizontal and smooth, without weld-spatter, and any other
obstructions.

2.2.7 Maintenance supports for use during shutdown will not be provided.

2.2.8 CONTRACTOR shall provide temporary supports for hydrostatic test if


necessary but all temporary supports shall be clearly marked and removed
prior to commissioning of system.
After remove of temporary support, visual check shall be done.

Welding of the temporary support with dissimilar material to the piping is


prohibited.

2.2.9 Anchors, Directional stops, hold-downs and guides shall not be voluntarily
1 added, deleted, or relocated in field without stress engineers approval.

2.2.10 All spring supports shall be installed with name plate facing to the
walkway side so that the name plate can be read.

2.2.11 Materials for pipe supports shall generally be applied as follows:

(1) All structural members used for supports shall be ASTM A-36 or equal.
PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 8 de 16

(2) All bolting material shall be ASTM A-193 or equal.


(3) Stainless steel bolts and nuts shall be used for S.S. and alloy piping
and corrosive environment areas.

2.2.12 Pipe Shoes

(1) Shoes are used on all hot insulated lines and cold insulted lines for 2
and larger
(2) Welded type shoes shall be used at locations where as directional
stop or fixed anchor is required.
(3) Clamp type shoes (type S8, S9 and S10) may be used for thin wall
pipe in case shoe welding is not permitted.
(4) Clamp type shoes (type S8, S9 and S10) may be used at resting
guide location of alloy steel pipe line and stress relieved piping with
approval of stress engineer.
(5) Cold insulated 1.1/2 and smaller lines shall be on support cradle
(type S50)

2.2.13 Rigid pipe supports should be utilized to maximum extent thus avoiding
the use of spring supports whenever design permits.

2.2.14 All safety valves and rupture discs of vapor services shall be checked for
thrust load.

2.2.15 High pressure control valve should be anchored at one side of connecting
pipe.

2.2.16 Lines connected to tanks subject to settlement shall have the first support
located at sufficient distances from the tank to avoid excessive pipe or tank
stresses. In case of large settlements, the lines shall be supported from the
tank or by adjustable or spring supports from grade.

3 GENERAL INSTRUCTIONS FOR PIPE SUPPORT DETAILS

3.1 General

3.1.1 This drawing shall be used for selection and application only. Details of
supports are shown on fabrication detail drawings.

3.1.2 All dimensions are in millimeters.

3.1.3 Deviations from this drawing shall be reviewed by stress engineer and
detailed on the piping drawing.
PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 9 de 16

3.2 Shoe

3.2.1 Shoes are required for all hot insulated lines.


(1) For expansion 75 and less, use 300 long shoes.
(2) For expansion 76 to 150, use 450 long shoes.
(3) For expansion 151 to 225, use 600 long shoes.
(4) For expansion 226 to 300, use 750 long shoes.

3.2.2 Shoe heights are selected by insulation thickness as follows;


(1) Shoe height (H) = 100 for insulation thickness 75 and less.
(2) Shoe height (H) = 150 for insulation thickness 76 to 125
(3) Shoe height (H) = 200 for insulation thickness 126 to 175
(4) Shoe height (H) = 250 for insulation thickness 176 to 225

3.3 Pipe Guide

3.3.1 Pipe guide spacing shall be as per the table below.


(1) Guide at horizontal lines.
Pipe Sized Max. Span(mm)
1.1/2 and smaller 8,000
2 to 6 16,000
8 to 18 24,000
20 & larger 32,000
Note; Consider wind pressure and other condition, stress engineer
places the required guides.

(2) Guide at vessel.


Maximum spacing of guides (h) (in meter)
Nom. Insul. Wind Wind Wind Wind Wind Wind
Pipe Thick. Press. Press. Press. Press. Press. Press.
2 2 2 2 2 2
Size mm 145kg/m 170kg/m 195kg/m 220kg/m 240kg/m 300kg/m
1 25 6.7 5.8 5.1 4.6 4.0 3.6
1.1/2 25 7.0 6.1 5.1 4.6 4.3 4.0
2 25 7.3 6.1 5.5 4.9 4.3 4.0
3 25 8.2 7.0 6.1 5.5 4.9 4.3
4 25 8.8 7.6 6.7 5.8 5.2 4.6
6 50 10.0 8.5 7.6 6.7 6.1 5.5
8 50 11.3 9.8 8.5 7.3 6.7 6.2
10 50 12.5 10.7 9.4 8.2 7.6 7.3
12 50 13.7 11.6 10.4 9.1 8.2 8.0
14 50 14.3 12.2 10.7 9.4 8.5 8.2
16 75 15.2 13.1 11.6 10.0 9.1 8.8
18 75 16.2 13.7 12.2 10.7 9.8 9.5
20 75 17.0 14.6 12.8 11.3 10.4 10.0
24 & larger 75 18.3 15.5 13.7 13.2 11.0 10.5
PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 10 de 16

For lines with insulation thickness larger than those shown, the reduced
guide spacing (H) may be found by the following formula;
D2
H h
D1
Where;
D1 = OD of pipe + twice the given insulation thickness from the above
table.
D2 = OD of pipe + twice the actual insulation thickness, as shown in the
nomenclature.

(3) Pipe guides shall not be placed closer than 1000 pipe diameter from a
directional change of pipe except where required by stress engineer.
i.e. 6 pipe: 10006 = 6000mm
4 pipe: 10004 = 4000mm
PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 11 de 16

3.4 Pick-Up Support

3.4.1 Supporting pipe is limited to operating temperature of 90C or below.


If operating temperature is higher than 90C, it is required approval of
1
stress engineer.

3.4.2 Pick-ups shall have supporting pipe limited to non heat traced and carbon
steel. Use of pick-ups on insulated, heat traced and non-carbon steel pipe
shall require approval by stress engineer.

3.4.3 Load shall be calculated by using following method.

L L 3 P
W 1 L2
2 1000

Where, W= Support load in kg


L1, L2, L3 = Pipe length in mm.
P= Unit weight of pipe including full of
water and insulation in kg/m.
Example: L1 = 3500, L2 = 900, L3 = 4500
Pipe = 2 SCH.80 with full of water and P = 9.4 kg/m
Therefore, 3500 4500 9.4
W 900
2 1000
46kg 130kg...Acceptable
Torsional moment = 46250/1000 =11.5kgm
<60kgm
(Acceptable)
PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 12 de 16

Max. allowable load on supporting pipe (kg and kgm)


Type of pick-up Max allowable
Supporting
Torsional
Pipe size PU1 PU2 PU3 Moment
3 65 65 100 40
4 130 130 200 60
6 & 8 130 430 500 80
10 thru 24 200 500 700 120

3.5 Support Trunnion

3.5.1 Approval of stress engineer is required if support load exceeds maximum


total load in the table.

3.5.2 Actual load must be calculated and transmitted to support design.

3.5.3 Trunnions shall be shop fabricated and shown on shop fabrication drawing.

3.6 Maximum Loading on Paved Area

Maximum loadings on paved area using concrete slab based on 100mm thick are
as follows;

(1) 1.5 ton maximum if base plate size is 200mm2.


(2) 2.0 ton maximum if base plate size is 300mm2.
(3) 2.5 ton maximum if base plate size is 400mm2.

Greater loads than above loadings require approval from civil engineer.

3.7 Hold-Down

Reciprocating compressor or pump piping subject to vibration shall be held down


by HD1, HD5, HD7, HD10, HD11, HD12, and HD13.

3.8 Spring Wedge

Use spring wedges (type SW1 to SW5) where required by vibration analysis on
pulsating lines, volume bottles and pulsation dampers at reciprocating pumps and
compressors.

3.9 Dummy Support

3.9.1 Dummy support shall be used by piping design, if pipe wall thickness is
equal or thicker than minimum STD. wall thickness.

3.9.2 If pipe wall thickness is thinner than STD. wall thickness, stress engineer
PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 13 de 16

should check to see whether reinforcement is required or not.

3.9.3 Dummy support size for pipe size 2 and smaller shall be the same size as
pipe size.

3.9.4 Dummy supports shall be shown on piping arrangement drawing together


with piping and shall be purchased and fabricated together with piping.

3.10 Pipe Support Span

The following pipe span is based on 15mm maximum deflection and 4Hz in
minimum natural frequency of the piping concerned.

3.10.1 Maximum pipe support span (carbon steel / alloy steel)

Empty With Full of Water


Pipe Pipe Wall Insul. Insul.
Size Thickness Bare Insul. Bare Insul.
Thk. Thk.
(m) (m) (m) (m)
(mm) (mm)
1/2 SCH.80 4.0 3.0 50 4.0 3.0 50
3/4 SCH.80 5.0 3.7 50 4.5 3.5 50
1 SCH.80 5.5 4.3 50 5.0 4.0 50
1.1/4 SCH.80 5.7 5.0 50 5.5 4.5 50
1.1/2 SCH.80 6.0 5.5 50 5.8 5.0 50
2 SCH.40 6.4 6.0 50 6.1 6.0 50
3 SCH.40 7.7 7.1 50 7.1 6.7 50
4 SCH.40 9.0 8.0 50 8.0 7.7 50
6 SCH.40 10.7 10.1 75 9.5 9.5 75
8 SCH.40 12.2 11.6 75 10.7 10.7 75
10 SCH.40 14.0 12.5 75 11.0 11.0 75
12 STD. 15.0 12.8 75 11.5 11.5 75
14 STD. 16.0 14.1 75 12.2 12.2 75
16 STD. 16.8 15.3 75 12.8 12.8 75
18 STD. 17.7 13.5 90 11.3 11.3 90
20 STD. 18.5 14.5 90 11.9 11.9 90
22 STD. 19.5 15.5 90 12.0 12.0 90
24 STD. 20.5 16.0 90 12.8 12.8 90

Note: Above table is based on temperature of 350C.


PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 14 de 16

3.10.2 Maximum pipe support span (stainless steel)

Empty With Full of Water


Pipe Pipe Wall Insul. Insul.
Size Thickness Bare Insul. Bare Insul.
Thk. Thk.
(m) (m) (m) (m)
(mm) (mm)
1/2 SCH.10S 2.9 2.1 50 2.8 2.0 50
3/4 SCH.10S 3.3 2.5 50 3.1 2.4 50
1 SCH.10S 3.7 2.9 50 3.5 2.8 50
1.1/4 SCH.10S 5.0 4.1 50 3.8 3.0 50
1.1/2 SCH.10S 5.4 4.3 50 4.3 3.5 50
2 SCH.10S 5.8 5.0 50 5.0 4.2 50
3 SCH.10S 6.5 6.0 50 6.0 5.0 50
4 SCH.10S 7.5 6.5 50 6.5 5.5 50
6 SCH.10S 8.0 7.0 75 7.0 6.0 75
8 SCH.10S 8.7 7.7 75 7.7 6.7 75
10 SCH.10S 9.3 8.3 75 8.3 7.3 75
12 SCH.10S 10.0 9.0 75 9.0 7.9 75
14 SCH.10S 10.5 9.5 75 9.5 8.5 75
16 SCH.10S 11.0 10.0 75 10.0 9.0 75
18 SCH.10S 11.5 10.5 90 10.5 9.5 90
20 SCH.10S 12.0 11.0 90 11.0 10.0 90
22 SCH.10S 12.5 11.5 90 11.5 10.5 90
24 SCH.10S 13.0 12.0 90 12.0 11.0 90

Note: Above table is based on temperature of 350C.

3.10.3 The values in the above tables do not apply when there are concentrated
loads between supports as in the case of flanges, valves, etc

4 RECOMMENDED METHODS FOR SUPPORT OF SMALL PIPE (1.1/2" AND


SMALLER) IN FIELD

4.1 Purpose

It is provided for field piping fabricator of contractor to prepare and install proper
support on the lines 1.1/2" and smaller.

4.2 Pipe Support Spans

All supports are based on insulated pipe with full of water.


PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 15 de 16

4.2.1 Guide Spacing

Vertical Guide Spacing Horizontal Guide Spacing Pipe Weights Full of


Line Size
MAX.(mm) MAX.(mm) Water (Kg/m)
3/4" 4000 6000 2.5
1" 4500 6000 3.7
1.1/2" 6000 6000 6.5
Note: Add 2.5 kg/m for insulated lines.

4.3 Permissible Overhang Variations


'A'

Point of support
'B'

Point of support
Plan view of piping

Dimension 'A' Dimension 'B'


Line Size
(mm) (mm)
3/4" 1200 1500 1800 2100 2400 2400 2100 1800 1500 1200
1" 1200 1500 1800 2100 2400 2400 2100 1800 1500 1200
1.1/2" 1500 1800 2100 2400 2700 2700 2400 2100 1800 1500
COL No. 1 2 3 4 5 1 2 3 4 5
To find permissible overhangs, match column number for dimension 'A' with
same column number for dimension B

'A'
'B'

Point of support
PIPING SUPPORT STANDARD
DRAWING

Rev. 1
PLANTAS DE AMONIACO Y UREA, N del DOC. PAU-EPI-C-STD-00001
CARRASCO Pgina 16 de 16

Plan view of piping

Dimension 'A' Dimension 'B'


Line Size
(mm) (mm)
3/4" 700 900 1000 1200 1300 3300 2500 1900 1300 900
1" 900 1000 1200 1300 1500 3000 2400 1800 1300 900
1.1/2" 900 1000 1200 1300 1500 4500 3900 3300 2500 2100
COL No. 1 2 3 4 5 1 2 3 4 5
To find Permissible overhangs, match column number for dimension 'A' with
same column number for dimension 'B'

Point of support

Isometric

Line Dimension 'A' Dimension 'B' Dimension 'C'


Size (mm) (mm) (mm)
3/4" 300 700 1000 1300 1800 3600 2900 1400 300 300 1500 700 1000 1700 1200
1" 400 800 1200 1700 2100 4200 2500 1500 1200 1700 1700 1200 1100 1000 800
1.1/2" 500 1000 1600 2100 2700 5400 3200 2100 1000 2100 2100 1500 1400 1600 1000
COL No. 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
To find permissible overhangs, match column number for dimension 'A' with same column
number for dimension B and C

4.4 Miscellaneous Support

On pipe support details, type MC1 ~ MC8 shall be used.

5 PAINTING

Unless otherwise specified, all pipe support steel and its bolting shall be painted.
APPENDIX I-I: STANDARD COLLECTION OF STEEL BEAM AND ANCHOR BOLT

STEEL BEAM (JIS) DIMENSION (mm)


I-SHAPE H-SHAPE CHANNEL ANGLE
CODE DIMENSION CODE DIMENSION CODE DIMENSION CODE DIMENSION
L25 25*25*5
L50 50*50*6
L65 65*65*6
L75 75*75*6
L90 90*90*7
H100x100 100*100*6*8 C100 100*50*5*7.5 L100 100*100*10
H125x125 125*125*6.5*9 C125 125*65*6*8
I150 150*75*5.5*9.5 H150x150 150*150*7*10 C150 150*75*6.5*10 L150 150*150*15
I200 200*100*7*10 H200x200 200*200*8*12 C200 200*90*8*13.5
I250 250*125*7.5*12.5 H250x250 250*250*9*14 C250 250*90*9*13
H300x300 300*150*10*15 C300 300*90*10*15.5
1 H350x350 350*350*12*19 C380 380*100*10.5*16
H400x400 400*100*13*21

ANCHOR BOLT
CODE DETAIL
M10 M10x120
M12 M12x120
M16 M16x140
M20 M20x170




























APPENDIX I-II: STANDARD COLLECTION OF SUPPORT MATERIAL










APPENDIX I- III : SELECTION GUIDE OF SUPPORT ATANDARDS (1/3)

SIZE
CATEGORY TYPE LOCATION INSULATION SUPPORT REMARK
RANGE
ANCHOR ANCHOR HOR./VERT. NO ~2 AS1
SUPPORT ANCHOR HOR./VERT. HOT ~2 AS2
ADJUSTABLE BAG1 ~
GROUND/PF. NO/HOT 2~42
GUIDE BAG7
ADJUSTABLE BAG51 ~
GROUND/PF. COLD 2~42
GUIDE BAG57
ADJUSTABLE BAR1 ~
GROUND/PF. NO/HOT 2~54
RESTING BAR8
ADJUSTABLE BAR51 ~
GROUND/PF. COLD 2~54
RESTING BAR58
GUIDE GROUND/PF. NO/HOT 2~42 BG1 ~ BG7
IF DISTANCE FROM
BSG1 ~
GUIDE PF. NO/HOT 2~32 TOP TO BOP IS 600
BSG6
& BELOW
BG51 ~
GUIDE GROUND/PF. COLD 2~42
BG57
BASE
BSG51 ~
SUPPORT GUIDE GROUND/PF. COLD 2~32
BSG56
RESTING GROUND/PF. NO/HOT 2~54 BR1 ~ BR8
IF DISTANCE FROM
RESTING PF. NO/HOT 2~54 BS1 ~ BS8 TOP TO BOP IS 600
& BELOW
BR51 ~
RESTING GROUND/PF. COLD 2~54
BR58
IF DISTANCE FROM
BS51 ~
RESTING PF. COLD 2~32 TOP TO BOP IS 600
BS56
& BELOW
ONLY SPRING
RESTING ELBOW NO/HOT 2 ~ 64 DS3
SUPPORT
ONLY SPRING
RESTING ELBOW COLD 2 ~ 64 DS53
SUPPORT
SELECT BY
RESTING HOR./VERT. ALL ~12 CN1 ~CN2 LENGTH AND MAX.
LOAD
SELECT BY
CANTILEVER
GUIDE VERT. ALL ~12 CN5 ~ CN6 LENGTH AND MAX.
SUPPORT
LOAD
SELECT BY
RESTING HOR. ALL 2~16 CN4 LENGTH AND MAX.
LOAD
COLD SHOE
RESTING HOR. COLD ~ 76 S50 ~ S54
SUPPORT
DIRECTIONAL
HOR. NO 2 ~ 72 DA1 ~ DA3
DIRECTIONAL ANCHOR
SUPPORT DIRECTIONAL DA1S ~
HOR. HOT/COLD 2 ~ 72
ANCHOR DA3S
ELBOW
DUMMY RESTING ELBOW ALL 2 ~ DS1 ~ DS2
SUPPORT
FLANGE APPLICABLE TO
RESTING FLANGE BOLT NO/HOT 1 ~ 16 FBS1
SUPPORT 150# ONLY
APPENDIX I- III : SELECTION GUIDE OF SUPPORT ATANDARDS (2/3)

SIZE
CATEGORY TYPE LOCATION INSULATION SUPPORT REMARK
RANGE
GUIDE HOR. NO 1"~76" G1 ~ G2
GUIDE HOR. ALL 1"~76" G3
GUIDE N/A COLD 1/2"~76" G52
GUIDE VERT. NO 1"~8" G6
GUIDE VERT. HOT 1"~8" G7
GUIDE SUPPORT GUIDE VERT. NO/HOT 10"~24" G8
GUIDE VERT. COLD ~24" G53~54
NON-LIFTING
TYPE,
GUIDE HOR. NO/HOT ~18" G4 / G5 CONFIRM BY
STRESS
ENGINEER
ANCHOR BRANCH NO/HOT ~1.1/2" GUS1 WELDING
GUSSET SUPPORT
ANCHOR BRANCH NO/HOT ~1.1/2" GUS2 CLAMP
HANGER HOR./ELBOW NO/HOT 1"~24" H1
HANGER HOR. COLD ~30" H51 ~ H52
SELECT BY
HANGER
HANGER SUPPORT HOR. ALL ~24" H2 / H5 LENGTH AND
TRAPEZE
MAX. LOAD
HANGER SELECT BY
HOR. ALL ~24" H3 ~ H4
TRAPEZE MAX. LOAD
ONLY TO BE
HOLD
N/A. NO ~36" HD1 APPLIED AT
DOWN
FIELD
HOLD
HOR./VERT. NO ~36" HD5
DOWN
HOLD
HOR./VERT. COLD ~36" HD51
DOWN
HOLD
HOR./VERT. TRACING ~36" HD7
ANTI VIBRATION DOWN
SUPPORT ONLY
HOLD HD10 ~
N/A. NO ~24" VERTICAL
DOWN HD13
RESTRICTION
ON STEEL
GUIDE HOR. NO/HOT ~8" GV4
STRUCTURE
ON STEEL
GUIDE HOR. NO/HOT 10"~18" GV5
STRUCTURE
ON EMBEDDED
GUIDE HOR. NO/HOT 10"~24" GV6
PLATE
TYPE SELECT
ANCHOR HOSE STATION NO/HOT ~1.1/2" HOS1 BY SITE
CONDITION
MISCELLANEOUS TYPE SELECT
SUPPORT GUIDE HOSE STATION NO/HOT ~1.1/2 HOS3 BY SITE
CONDITION
GROUND/PLAT
ANCHOR NO/HOT ~1.1/2" MCBS
FORM
APPENDIX I- III : SELECTION GUIDE OF SUPPORT ATANDARDS (3/3)

SIZE
CATEGORY TYPE LOCATION INSULATION SUPPORT REMARK
RANGE
SELECT BY
SITE
MC1 ~ MC2,
RESTING HOR. ALL ~4" CONDITION
MC6
AND MAX.
LOAD
SELECT BY
SITE
MISCELLANEOUS RESTING HOR. ALL ~6" MC3 ~ MC5 CONDITION
SUPPORT AND MAX.
LOAD
SELECT BY
RESTING HOR. ALL ALL MC7 ~ MC8
MAX. LOAD
SELECT BY
RESTING HOR. ALL ALL T1 ~ T3
MAX. LOAD
SELECT BY
RESTING HOR. ALL ALL T4
MAX. LOAD
ANCHOR PSV INLET NO/HOT ~24" PSV1
ANCHOR PSV INLET COLD ~24" PSV51
PSV SUPPORT
GUIDE PSV INLET NO/HOT ~24" PSV3
GUIDE PSV INLET COLD ~24" PSV53
CONFIRM BY
RESTING HOR. NO/HOT ALL PU1 ~ PU3 STRESS
ENGINEER
PICK-UP SUPPORT
CONFIRM BY
PU51 ~
RESTING HOR. COLD ~24" STRESS
PU53
ENGINEER
RESTING HOR./VERT. NO/HOT ~ 76" S1 ~ S4
SHOE CLAMP TYPE
RESTING HOR./VERT. NO ~ 26" S8 ~ S10
SHOE
SLIDING PLATE -195C AND
RESTING HOR. ALL 0"~76" SSP1
ABOVE
BASE -195C AND
RESTING ALL 2"~54" SSP2
SUPPORT ABOVE
RESTING HOR. ALL 10"~76" TSP1 -10C ~ 120C
BASE
RESTING ALL 2"~54" TSP2 -10C ~ 120C
SUPPORT
TRUNNION RESTING VERT. ALL 2"~72" ST1,STP1
SUPPORT RESTING VERT. ALL 2"~24" ST2,STP2
SELECT BY
ST3,ST4,
RESTING VERT. ALL ALL" STRESS
STP3,STP4
ENGINEER
ALL ALL NO/HOT ~24" UB1
1 U-BOLT
ALL VERT. COLD ~4" UB3
PAD RESTING HOR. NO ALL WP2
RISER CLAMP RESTING N/A. NO 3/4~4 RC1




SAMSUNG ENGINEERING CO. LTD. YPFB BOLIVIA PROJECT

PIPE SUPPORT LIST


SHEET
TYPE REV TITLE REMARKS
NO.

1 AS1 0 ANCHOR FOR UNINSULATED PIPE 2" & SMALLER (ONLY FOR C.S)

2 AS2 1 ANCHOR FOR INSULATED PIPE 2" & SMALLER

3 BAG1 1 BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): PIPE SIZE 2" THRU 4"

4 BAG2 1 BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): PIPE SIZE 6" THRU 8"

5 BAG3 1 BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): PIPE SIZE 10" THRU 12"

6 BAG4 1 BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): PIPE SIZE 14" THRU 16"

7 BAG5 1 BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): PIPE SIZE 18" THRU 24"

8 BAG6 1 BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): PIPE SIZE 26" THRU 32"

9 BAG7 1 BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): PIPE SIZE 34" THRU 42"

BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 2"
10 BAG51 1
THRU 4"
BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 6"
11 BAG52 1
THRU 8"
BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 10"
12 BAG53 1
THRU 12"
BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 14"
13 BAG54 1
THRU 16"
BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 18"
14 BAG55 1
THRU 24"
BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 26"
15 BAG56 1
THRU 32"
BASE SUPPORT FOR ADJUSTABLE GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 34"
16 BAG57 1
THRU 42"

17 BAR1 1 BASE SUPPORT FOR ADJUSTABLE RESTING: PIPE SIZE 2" THRU 4"

18 BAR2 1 BASE SUPPORT FOR ADJUSTABLE RESTING: PIPE SIZE 6" THRU 8"

19 BAR3 1 BASE SUPPORT FOR ADJUSTABLE RESTING: PIPE SIZE 10" THRU 12"

20 BAR4 1 BASE SUPPORT FOR ADJUSTABLE RESTING: PIPE SIZE 14" THRU 16"

21 BAR5 1 BASE SUPPORT FOR ADJUSTABLE RESTING: PIPE SIZE 18" THRU 24"

22 BAR6 1 BASE SUPPORT FOR ADJUSTABLE RESTING: PIPE SIZE 26" THRU 32"

23 BAR7 1 BASE SUPPORT FOR ADJUSTABLE RESTING: PIPE SIZE 34" THRU 42"

24 BAR8 1 BASE SUPPORT FOR ADJUSTABLE RESTING: PIPE SIZE 44" THRU 54"

25 BAR51 1 BASE SUPPORT FOR ADJUSTABLE RESTING: FOR COLD PIPE SIZE 2" THRU 4"

26 BAR52 1 BASE SUPPORT FOR ADJUSTABLE RESTING: FOR COLD PIPE SIZE 6" THRU 8"

27 BAR53 1 BASE SUPPORT FOR ADJUSTABLE RESTING: FOR COLD PIPE SIZE 10" THRU 12"

28 BAR54 1 BASE SUPPORT FOR ADJUSTABLE RESTING: FOR COLD PIPE SIZE 14" THRU 16"

29 BAR55 1 BASE SUPPORT FOR ADJUSTABLE RESTING: FOR COLD PIPE SIZE 18" THRU 24"

30 BAR56 1 BASE SUPPORT FOR ADJUSTABLE RESTING: FOR COLD PIPE SIZE 26" THRU 32"

31 BAR57 1 BASE SUPPORT FOR ADJUSTABLE RESTING: FOR COLD PIPE SIZE 34" THRU 42"

32 BAR58 1 BASE SUPPORT FOR ADJUSTABLE RESTING: FOR COLD PIPE SIZE 44" THRU 54"

33 BG1 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): PIPE SIZE 2" THRU 4"

34 BG2 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): PIPE SIZE 6" THRU 8"
SAMSUNG ENGINEERING CO. LTD. YPFB BOLIVIA PROJECT

PIPE SUPPORT LIST


SHEET
TYPE REV TITLE REMARKS
NO.

35 BG3 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): PIPE SIZE 10" THRU 12"

36 BG4 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): PIPE SIZE 14" THRU 16"

37 BG5 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): PIPE SIZE 18" THRU 24"

38 BG6 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): PIPE SIZE 26" THRU 32"

39 BG7 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): PIPE SIZE 34" THRU 42"

40 BG51 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 2" THRU 4"

41 BG52 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 6" THRU 8"

42 BG53 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 10" THRU 12"

43 BG54 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 14" THRU 16"

44 BG55 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 18" THRU 24"

45 BG56 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 26" THRU 32"

46 BG57 1 BASE SUPPORT FOR GUIDE (2 OR 4 WAY): FOR COLD PIPE SIZE 34" THRU 42"

47 BR1 1 BASE SUPPORT FOR RESTING: PIPE SIZE 2" THRU 4"

48 BR2 1 BASE SUPPORT FOR RESTING: PIPE SIZE 6" THRU 8"

49 BR3 1 BASE SUPPORT FOR RESTING: PIPE SIZE 10" THRU 12"

50 BR4 1 BASE SUPPORT FOR RESTING: PIPE SIZE 14" THRU 16"

51 BR5 1 BASE SUPPORT FOR RESTING: PIPE SIZE 18" THRU 24"

52 BR6 1 BASE SUPPORT FOR RESTING: PIPE SIZE 26" THRU 32"

53 BR7 1 BASE SUPPORT FOR RESTING: PIPE SIZE 34" THRU 42"

54 BR8 1 BASE SUPPORT FOR RESTING: PIPE SIZE 44" THRU 54"

55 BR51 1 BASE SUPPORT FOR RESTING FOR COLD PIPE SIZE 2" THRU 4"

56 BR52 1 BASE SUPPORT FOR RESTING FOR COLD PIPE SIZE 6" THRU 8"

57 BR53 1 BASE SUPPORT FOR RESTING FOR COLD PIPE SIZE 10" THRU 12"

58 BR54 1 BASE SUPPORT FOR RESTING FOR COLD PIPE SIZE 14" THRU 16"

59 BR55 1 BASE SUPPORT FOR RESTING FOR COLD PIPE SIZE 18" THRU 24"

60 BR56 1 BASE SUPPORT FOR RESTING FOR COLD PIPE SIZE 26" THRU 32"

61 BR57 1 BASE SUPPORT FOR RESTING FOR COLD PIPE SIZE 34" THRU 42"

62 BR58 1 BASE SUPPORT FOR RESTING FOR COLD PIPE SIZE 44" THRU 54"

63 BS1 1 BASE SUPPORT FOR PIPE SIZE 2" THRU 4"

64 BS2 1 BASE SUPPORT FOR PIPE SIZE 6" THRU 8"

65 BS3 1 BASE SUPPORT FOR PIPE SIZE 10" THRU 12"

66 BS4 1 BASE SUPPORT FOR PIPE SIZE 14" THRU 16"

67 BS5 1 BASE SUPPORT FOR PIPE SIZE 18" THRU 24"

68 BS6 1 BASE SUPPORT FOR PIPE SIZE 26" THRU 32"


SAMSUNG ENGINEERING CO. LTD. YPFB BOLIVIA PROJECT

PIPE SUPPORT LIST


SHEET
TYPE REV TITLE REMARKS
NO.

69 BS7 1 BASE SUPPORT FOR PIPE SIZE 34" THRU 42"

70 BS8 1 BASE SUPPORT FOR PIPE SIZE 44" THRU 54"

71 BS51 1 BASE SUPPORT FOR COLD INSULATED PIPE SIZE 2" THRU 4"

72 BS52 1 BASE SUPPORT FOR COLD INSULATED PIPE SIZE 6" THRU 8"

73 BS53 1 BASE SUPPORT FOR COLD INSULATED PIPE SIZE 10" THRU 12"

74 BS54 1 BASE SUPPORT FOR COLD INSULATED PIPE SIZE 14" THRU 18"

75 BS55 1 BASE SUPPORT FOR COLD INSULATED PIPE SIZE 20" THRU 24"

76 BS56 1 BASE SUPPORT FOR COLD INSULATED PIPE SIZE 26" THRU 32"

77 BSG1 1 BASE SUPPORT GUIDE ( 2 OR 4 WAY) FOR PIPE SIZE 2" THRU 4"

78 BSG2 1 BASE SUPPORT GUIDE ( 2 OR 4 WAY) FOR PIPE SIZE 6" THRU 8"

79 BSG3 1 BASE SUPPORT GUIDE ( 2 OR 4 WAY) FOR PIPE SIZE 10" THRU 12"

80 BSG4 1 BASE SUPPORT GUIDE ( 2 OR 4 WAY) FOR PIPE SIZE 14" THRU 16"

81 BSG5 1 BASE SUPPORT GUIDE ( 2 OR 4 WAY) FOR PIPE SIZE 18" THRU 24"

82 BSG6 1 BASE SUPPORT GUIDE ( 2 OR 4 WAY) FOR PIPE SIZE 26" THRU 32"

83 BSG51 1 DIRECTIONAL BASE GUIDE FOR COLD INSULATED PIPE SIZE 2" THRU 4"

84 BSG52 1 DIRECTIONAL BASE GUIDE FOR COLD INSULATED PIPE SIZE 6" THRU 8"

85 BSG53 1 DIRECTIONAL BASE GUIDE FOR COLD INSULATED PIPE SIZE 10" THRU 12"

86 BSG54 1 DIRECTIONAL BASE GUIDE FOR COLD INSULATED PIPE SIZE 14" THRU 16"

87 BSG55 1 DIRECTIONAL BASE GUIDE FOR COLD INSULATED PIPE SIZE 18" THRU 24"

88 BSG56 1 DIRECTIONAL BASE GUIDE FOR COLD INSULATED PIPE SIZE 26" THRU 32"

89 CN1 0 CANTILEVER FOR PIPE SIZE 4" AND SMALLER

90 CN2 1 CANTILEVER FOR PIPE SIZE 12" AND SMALLER

91 CN4 0 CANTILEVER BRACKET FOR PIPE SIZE 2" THRU 16"

92 CN5 0 CANTILEVER GUIDE FOR VERTICAL PIPE SIZE 4" AND SMALLER

93 CN6 0 CANTILEVER GUIDE FOR VERTICAL PIPE SIZE 6" THRU 12"

94 DA1 1 DIRECTIONAL ANCHOR FOR UNINSULATED PIPE SIZE 2' THRU 10"

95 DA1S 1 DIRECTIONAL ANCHOR FOR PIPES 2' THRU 10" WITH SHOE

96 DA2 0 DIRECTIONAL ANCHOR FOR UNINSULATED PIPE SIZE 12" THRU 24"

97 DA2S 0 DIRECTIONAL ANCHOR FOR PIPES 12' THRU 24" WITH SHOE

98 DA3 0 DIRECTIONAL ANCHOR FOR UNINSULATED PIPE SIZE 26" THRU 72"

99 DA3S 0 DIRECTIONAL ANCHOR FOR PIPES 26' THRU 72" WITH SHOE

100 DA51-1 1 DIRECTIONAL ANCHOR FOR COLD INSULATED PIPE 2" THRU 10" (SHEET 1 OF 2) DELETED

101 DA51-2 1 DIRECTIONAL ANCHOR FOR COLD INSULATED PIPE 2" THRU 10" (SHEET 2 OF 2) DELETED

102 DA52-1 1 DIRECTIONAL ANCHOR FOR COLD INSULATED PIPE 12" THRU 24" (SHEET 1 OF 2) DELETED
SAMSUNG ENGINEERING CO. LTD. YPFB BOLIVIA PROJECT

PIPE SUPPORT LIST


SHEET
TYPE REV TITLE REMARKS
NO.

103 DA52-2 1 DIRECTIONAL ANCHOR FOR COLD INSULATED PIPE 12" THRU 24" (SHEET 2 OF 2) DELETED

104 DA53-1 1 DIRECTIONAL ANCHOR FOR COLD INSULATED PIPE 26" THRU 42" (SHEET 1 OF 2) DELETED

105 DA53-2 1 DIRECTIONAL ANCHOR FOR COLD INSULATED PIPE 26" THRU 42" (SHEET 2 OF 2) DELETED

106 DA54-1 1 DIRECTIONAL ANCHOR FOR COLD INSULATED PIPE 48" THRU 60" (SHEET 1 OF 2) DELETED

107 DA54-2 1 DIRECTIONAL ANCHOR FOR COLD INSULATED PIPE 48" THRU 60" (SHEET 2 OF 2) DELETED

108 DS1 0 DUMMY SUPPORT AT ELBOW FOR PIPE SIZE 2" THRU 24"

109 DS2 0 DUMMY SUPPORT AT ELBOW FOR PIPE SIZE 26" AND LARGER

110 DS3 1 DUMMY SUPORRT FOR BASE TYPE

111 DS53 0 DUMMY SUPPORT FOR BASE TYPE (FOR COLD INSULATION)

112 FBS1 0 FLANGE BOLT SUPPORT FOR PIPE SIZE 1" THRU 6"

113 G1 0 GUIDE FOR UNINSULATED PIPE SIZE 1" THRU 8"

114 G2 0 GUIDE FOR UNINSULATED PIPE SIZE 10" THRU 76"

115 G3 1 GUIDE FOR PIPE SIZE 1/2" THRU 76" WITH SHOE

116 G4 0 NON LIFTING GUIDE FOR PIPE SIZE 8" AND SMALLER WITH SHOE

117 G5 0 NON-LIFTING GUIDE FOR PIPE SIZE 10" THRU 18" WITH SHOE

118 G6 1 GUIDE FOR VERTICAL PIPING FOR UNINSULATED PIPE SIZE 1" THRU 8"

119 G7 1 GUIDE FOR VERTICAL PIPING FOR INSULATED PIPE SIZE 1" THRU 8"

120 G8 1 GUIDE FOR VERTICAL PIPING FOR PIPE SIZE 10" THRU 24"

121 G52 1 GUIDE FOR COLD INSULATED PIPE SIZE 1/2" THRU 76"

122 G53 0 GUIDE FOR VERTICAL PIPING FOR COLD PIPE SIZE THRU 4"

123 G54 0 GUIDE FOR VERTICAL PIPING FOR COLD PIPE SIZE 6" THRU 24"

124 GUS1 1 GUSSET FOR PIPE SIZE 1.1/2" AND SMALLER (WELDED)

125 GUS2 1 GUSSET FOR PIPE SIZE 1.1/2" AND SMALLER (CLAMPED)

126 GUS3 0 GUSSET FOR DOUBLE BLOCK DRAIN FOR PIPE SIZE 1.1/2" AND SMALLER

127 GUS5 0 GUSSET FOR DOUBLE BLOCK DRAIN FOR TEE CONNECTION 1.1/2" AND SMALLER

128 GV4 0 GUIDE FOR VIBRATION PIPING FOR PIPE SIZE 8" AND SMALLER

129 GV5 0 GUIDE FOR VIBRATION PIPING FOR PIPE SIZE 10" THRU 18"

130 GV6 0 GUIDE FOR VIBRATION PIPING FOR PIPE SIZE 10" THRU 24" (ON EMBEDDED PLATE)

131 H1 1 HANGER FOR PIPE SIZE 1" THRU 24"

132 H3 0 HANGER-TRAPEZE

133 H4 0 HANGER-TRAPEZE

134 H5 0 HANGER-TRAPEZE

135 H51-1 0 HANGER FOR COLD INSULATED PIPE SIZE 4" & SMALLER (SHEET 1 OF 2)

136 H51-2 0 HANGER FOR COLD INSULATED PIPE SIZE 4" & SMALLER (SHEET 2 OF 2)
SAMSUNG ENGINEERING CO. LTD. YPFB BOLIVIA PROJECT

PIPE SUPPORT LIST


SHEET
TYPE REV TITLE REMARKS
NO.

137 H52-1 0 HANGER FOR COLD INSULATED PIPE SIZE 6" THRU 30" (SHEET 1 OF 2)

138 H52-2 0 HANGER FOR COLD INSULATED PIPE SIZE 6" THRU 30" (SHEET 2 OF 2)

139 HD1 0 HOLD-DOWN FOR UNINSULATED PIPE SIZE THRU 36" (FABRICATED AT FIELD)

140 HD5 0 HOLD-DOWN FOR UNINSULATED PIPE SIZE THRU 36"

141 HD7 0 HOLD-DOWN FOR INSULATED PIPE SIZE THRU 36"

142 HD10 1 HOLD-DOWN FOR UNINSULATED PIPE SIZE 1.1/2" THRU 3"

143 HD11-1 0 HOLD-DOWN FOR UNINSULATED PIPE SIZE 4" THRU 10" (SHEET 1 OF 2)

144 HD11-2 0 HOLD-DOWN FOR UNINSULATED PIPE SIZE 4" THRU 10" (SHEET 2 OF 2)

145 HD12 1 HOLD-DOWN FOR UNINSULATED PIPE SIZE 12" THRU 18"

146 HD13 1 HOLD-DOWN FOR UNINSULATED PIPE SIZE 20" THRU 24"

147 HD51 0 HOLD-DOWN FOR COLD INSULATED PIPE SIZE THRU 36"

148 HOS1-1 0 HOSE STATION SUPPORT (SHEET 1 OF 2)

149 HOS1-2 1 HOSE STATION SUPPORT (SHEET 2 OF 2)

150 MC1 1 MISCELLANEOUS SUPPORT

151 MC2 0 MISCELLANEOUS SUPPORT

152 MC3 0 MISCELLANEOUS SUPPORT

153 MC4 0 MISCELLANEOUS SUPPORT

154 MC5 1 MISCELLANEOUS SUPPORT

155 MC6-1 1 MISCELLANEOUS SUPPORT (SHEET 1 OF 2)

156 MC6-2 1 MISCELLANEOUS SUPPORT (SHEET 2 OF 2)

157 MC7 0 MISCELLANEOUS SUPPORT

158 MC8 0 MISCELLANEOUS SUPPORT

159 MC9 0 MISCELLANEOUS SUPPORT ADDED

160 MC10 0 MISCELLANEOUS SUPPORT ADDED

161 MC11 0 MISCELLANEOUS SUPPORT ADDED

162 MCBS 0 BASE SUPPORT FOR PIPE SIZE 1.1/2" & SMALLER

163 PSV1 1 ANCHOR AT PSV (HOT SERVICE)

164 PSV3 1 GUIDE AT PSV (HOT SERVICE)

165 PSV51 0 ANCHOR AT PSV (COLD SERVICE)

166 PSV53 0 GUIDE AT PSV (COLD INSULATION)

167 PU1 0 PICK-UP

168 PU2 0 PICK-UP

169 PU3 0 PICK-UP

170 PU51 0 PICK-UP FOR COLD INSULATION PIPE


SAMSUNG ENGINEERING CO. LTD. YPFB BOLIVIA PROJECT

PIPE SUPPORT LIST


SHEET
TYPE REV TITLE REMARKS
NO.

171 PU52 0 PICK-UP FOR COLD INSULATION PIPE

172 PU53 0 PICK-UP FOR COLD INSULATION PIPE

173 RC1 0 RISER CLAMP FOR PIPE SIZE 3/4" THRU 4"

174 S1 1 SHOE FOR PIPE SIZE 8" AND SMALLER

175 S2 1 SHOE FOR PIPE SIZE 10" THRU 18"

176 S3 1 SHOE FOR PIPE SIZE 20" THRU 36"

177 S4 1 SHOE FOR PIPE SIZE 38" THRU 76"

178 S8 1 CLAMP-ON SHOE FOR PIPE SIZE 8" AND SMALLER

179 S9 1 CLAMP-ON SHOE FOR PIPE SIZE 10" AND 18"

180 S10 1 CLAMP-ON SHOR FOR PIPE SIZE 20" THRU 28"

181 S50 1 COLD SUPPORT SHOE FOR PIPE SIZE THRU 1.1/2"

182 S51 1 COLD SUPPORT SHOE FOR PIPE SIZE 2" THRU 8"

183 S52 0 COLD SUPPORT SHOE FOR PIPE SIZE 10" THRU 18"

184 S53 0 COLD SUPPORT SHOE FOR PIPE SIZE 20" THRU 36"

185 S54 0 COLD SUPPORT SHOE FOR PIPE SIZE 38" THRU 76"

186 SSP1 0 S.S. SLIDE PLATE FOR ALL PIPE SIZE (TEMPERATURE -195 oC & ABOVE)

187 SSP2 0 S.S. SLIDE PLATE FOR BASE SUPPORTS (TEMPERATURE -195 oC & ABOVE)

188 ST1 0 DUMMY SUPPORT AT PIPE (DOUBLE) FOR PIPE SIZE 2" THRU 72"

189 ST2 0 DUMMY SUPPORT (SINGLE) AT PIPE FOR PIPE SIZE 2" THRU 24"

190 ST3 0 DUMMY SUPPORT (SINGLE) AT PIPE FOR PIPE SIZE 2" AND LARGER

191 ST4 0 DUMMY SUPPORT AT PIPE (DOUBLE) FOR PIPE SIZE 2" AND LARGER

192 STP1 0 DUMMY SUPPORT (DOUBLE) WITH PAD AT PIPE FOR PIPE SIZE 2" THRU 72"

193 STP2 0 DUMMY SUPPORT (SINGLE) WITH PAD AT PIPE FOR PIPE SIZE 2" THRU 24"

194 STP3 0 DUMMY SUPPORT (SINGLE) WITH PAD AT PIPE FOR PIPE SIZE 2" AND LARGER

195 STP4 0 DUMMY SUPPORT (DOUBLE) WITH PAD AT PIPE FOR PIPE SIZE 2" AND LARGER

196 SW1 0 SPRING WEDGE FOR PIPE SIZE 2" THRU 4"

197 SW2 0 SPRING WEDGE FOR PIPE SIZE 6" THRU 8"

198 SW3 0 SPRING WEDGE FOR PIPE SIZE 10" THRU 14"

199 SW4 0 SPRING WEDGE FOR PIPE SIZE 16" THRU 20"

200 SW5 0 SPRING WEDGE FOR PIPE SIZE 24" THRU 32"

201 T1 0 T-POST (DO NOT USE FOR GUIDE OR DIRECTIONAL STOP)

202 T2 0 T-POST (DO NOT USE FOR GUIDE OR DIRECTIONAL STOP)

203 T3 0 T-POST

204 T4 0 STANCHION
SAMSUNG ENGINEERING CO. LTD. YPFB BOLIVIA PROJECT

PIPE SUPPORT LIST


SHEET
TYPE REV TITLE REMARKS
NO.
TEFLON SLIDE PLATE FOR PIPE SIZES 10" AND LARGER (TEMPERATURE -10C TO
205 TSP1 0
120C)

206 TSP2 0 TEFLON SLIDE PLATE FOR BASE SUPPORTS (TEMPERATURE -10C TO 120C)

207 UB1 1 U-BOLT

208 UB2 1 U-BOLT FOR COLD INSULATED PIPE SIZE 1/2" THRU 24" (VERTICAL PIPE) DELETED

209 UB3 1 U-BOLT GUIDE FOR COLD INSULATED PIPE SIZE 1/2" THRU 4" (HORIZONTAL LINE)

210 WP1 0 COROSSION PROTECTION FOR UNINSULATED STAINLESS STEEL PIPE

211 WP2 1 BEARING PLATE TO BE USED ON UNINSULATED METALLIC PLATE


SAMSUNG ENGINEERING CO. LTD. YPFB BOLIVIA PROJECT

VESSEL SUPPORT LIST


SHEET
TYPE REV TITLE REMARKS
NO.

212 VCN1 0 VESSEL SUPPORT FOR CANTILEVER PIPE SIZE: 1.1/2 AND SMALLER

213 VCN2 0 VESSEL SUPPORT FOR CANTILEVER FOR SPRAY RING PIPES

214 VCN3-1 0 VESSEL SUPPORT FOR CANTILEVER FOR HOR. PIPING

215 VCN3-2 0 VESSEL SUPPORT FOR CANTILEVER FOR HOR. PIPING

VESSEL SUPPORT FOR CANTILEVER (UNINSULATED PIPE AT COLD VESSEL) PIPE SIZES :
216 VCN101 0
1.1/2" AND SMALLER

217 VCN102 0 VESSEL SUPPORT FOR CANTILEVER FOR SPRAY RING PIPES AT COLD VESSEL

218 VCN103 0 SUPPORT FOR CANTILEVER FOR UTILITY PIPES AT COLD VESSEL

219 VCN104-1 0 COLD VESSEL SUPPORT FOR CANTILEVER FOR HOR. PIPING

220 VCN104-2 0 COLD VESSEL SUPPORT FOR CANTILEVER FOR HOR. PIPING

221 VG1 0 VESSEL SUPPORT FOR GUIDE FOR UNINSULATED : PIPE SIZES 2" THRU 8"

222 VG2 0 VESSEL SUPPORT FOR GUIDE FOR INSULATED : PIPE SIZES 2" THRU 8"

223 VG3-1 0 VESSEL SUPPORT FOR GUIDE : PIPE SIZES 10" AND LARGER

224 VG3-2 0 VESSEL SUPPORT FOR GUIDE : PIPE SIZES 10" AND LARGER

225 VG51 0 VESSEL SUPPORT FOR GUIDE : PIPE SIZES 1/2" THRU 4"

226 VG52-1 0 VESSEL SUPPORT FOR GUIDE PIPE SIZES : 6" THRU 24"

227 VG52-2 0 VESSEL SUPPORT FOR GUIDE PIPE SIZES : 6" THRU 24"

228 VG53-1 0 VESSEL SUPPORT FOR GUIDE PIPE SIZES : 26" AND LARGER

229 VG53-2 0 VESSEL SUPPORT FOR GUIDE PIPE SIZES : 26" AND LARGER

VESSEL SUPPORT FOR GUIDE(UNINSULATED PIPE AT COLD VESSEL) PIPE SIZES : 1.1./2 "
230 VG101 0
THRU 8"

231 VG501 0 VESSEL SUPPORT FOR GUIDE(COLD INSULATED PIPING) PIPING SIZES : 1/2" THRU 4"

232 VG502 0 VESSEL SUPPORT FOR GUIDE(COLD INSULATED PIPING) PIPING SIZES : 6" THRU 24"

233 VG503 0 VESSEL SUPPORT FOR GUIDE(COLD INSULATED PIPING) PIPING SIZES : 26" AND LARGER

234 VH1-1 0 VESSEL SUPPORT FOR HANGER PIPE SIZES : 12" AND LARGER

235 VH1-2 0 VESSEL SUPPORT FOR HANGER PIPE SIZES : 12" AND LARGER

236 VH2-1 0 VESSEL SUPPORT FOR HANGER PIPE SIZES : 12" AND LARGER

237 VH2-2 0 VESSEL SUPPORT FOR HANGER PIPE SIZES : 12" AND LARGER

VESSEL SUPPORT FOR HANGER PIPE SIZES : 12" AND LARGER (MAX. LOAD 20 TON THRU
238 VH3-1 0
40 TON)
VESSEL SUPPORT FOR HANGER PIPE SIZES : 12" AND LARGER (MAX. LOAD 20 TON THRU
239 VH3-2 0
40 TON)

240 VH51-1 0 VESSEL SUPPORT FOR HANGER PIPE SIZES : 12" AND 14"

241 VH51-2 0 VESSEL SUPPORT FOR HANGER PIPE SIZES : 12" AND 14"

242 VH52-1 0 VESSEL SUPPORT FOR HANGER PIPE SIZES : 16" AND 18"

243 VH52-2 0 VESSEL SUPPORT FOR HANGER PIPE SIZES : 16" AND 18"

244 VH53-1 0 VESSEL SUPPORT FOR HANGER PIPE SIZES : 20" THRU 26"

245 VH53-2 0 VESSEL SUPPORT FOR HANGER PIPE SIZES : 20" THRU 26"
SAMSUNG ENGINEERING CO. LTD. YPFB BOLIVIA PROJECT

VESSEL SUPPORT LIST


SHEET
TYPE REV TITLE REMARKS
NO.

246 VH54-1 0 VESSEL SUPPORT FOR HANGER PIPE SIZES : 28"~40"

247 VH54-2 0 VESSEL SUPPORT FOR HANGER PIPE SIZES : 28"~40"

248 VR1 0 VESSEL SUPPORT FOR RESTING : 2" THRU 6"

249 VR2 0 VESSEL SUPPORT FOR RESTING : 8" THRU 10"

250 VR3-1 0 VESSEL SUPPORT FOR RESTING :12" AND LARGER

251 VR3-2 0 VESSEL SUPPORT FOR RESTING :12" AND LARGER

252 VR4-1 0 VESSEL SUPPORT FOR RESTING :12" AND LARGER

253 VR4-2 0 VESSEL SUPPORT FOR RESTING :12" AND LARGER

254 VR5-1 0 VESSEL SUPPORT FOR RESTING :12" AND LARGER

255 VR5-2 0 VESSEL SUPPORT FOR RESTING :12" AND LARGER

256 VR11-1 0 VESSEL SUPPORT FOR RESTING AT HOR. PIPING MAX. LOAD : 1500 KG AND SMALLER

257 VR11-2 0 VESSEL SUPPORT FOR RESTING AT HOR. PIPING MAX. LOAD : 1500 KG AND SMALLER

258 VR12-1 0 SUPPORT AT VESSEL CLIP DETAIL - TYPE A

259 VR12-2 0 SUPPORT AT VESSEL BRACKET DETAIL - TYPE A

260 VR13-1 0 SUPPORT AT VESSEL CLIP DETAIL - TYPE B

261 VR13-2 0 SUPPORT AT VESSEL BRACKET DETAIL - TYPE B

262 VR51 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 2" AND 3"

263 VR52-1 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 4" AND 6"

264 VR52-2 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 4" AND 6"

265 VR53-1 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 8" AND 10"

266 VR53-2 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 8" AND 10"

267 VR54-1 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 12" AND 14"

268 VR54-2 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 12" AND 14"

269 VR55-1 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 16" AND 18"

270 VR55-2 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 16" AND 18"

271 VR56-1 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 20" AND 26"

272 VR56-2 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 20" AND 26"

273 VR57-1 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 28" AND 40"

274 VR57-2 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 28" AND 40"

275 VR58-1 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 42"~60"

276 VR58-2 0 VESSEL SUPPORT FOR RESTING LINE SIZES : 42"~60"

VESSEL SUPPORT FOR RESTING LINE SIZES (UNINSULATED PIPE AT COLD VESSEL) : 4"
277 VR102-1 0
THRU 6"
VESSEL SUPPORT FOR RESTING LINE SIZES (UNINSULATED PIPE AT COLD VESSEL) : 4"
278 VR102-2 0
THRU 6"

279 VR501 0 VESSEL SUPPORT FOR RESTING (COLD INSULATED PIPING) PIPE SIZES : 2" THRU 6"
SAMSUNG ENGINEERING CO. LTD. YPFB BOLIVIA PROJECT

VESSEL SUPPORT LIST


SHEET
TYPE REV TITLE REMARKS
NO.

280 VR502 0 VESSEL SUPPORT FOR RESTING (COLD INSULATED PIPING) PIPE SIZES : 8" THRU 10"

281 VR503-1 0 VESSEL SUPPORT FOR RESTING (COLD INSULATED PIPING) PIPE SIZES : 12" AND LARGER

282 VR503-2 0 VESSEL SUPPORT FOR RESTING (COLD INSULATED PIPING) PIPE SIZES : 12" AND LARGER