Vous êtes sur la page 1sur 6

IEEE Transactions on Power Delivery, Vol. 13, No.

4, October 1998 1475

ult Location Using Wavelets


Fernando H. Magnago and Ali Abur

Department of Electrical Engineering


Texas A&M University
College Station, TX 77843, U.S.A.

Abstract - This paper describes the use of wavelet transform for Among the limitations of the traveling wave methods, the
analyzing power system fault transients in order to determine the requirement of high sampling rate is frequently stated. Other
fault location. Traveling wave theory is utilized in capturing the stated problems include the uncertainty in the choice of sampling
travel time of the transients along the monitored lines between the window and problems of distinguishing between traveling waves
fault point and the relay. Time resolution for the high frequency reflected from the fault and from the remote end of the line.
components of the fault transients, is provided by the wavelet Recent developments in optical current transducers technology
transform. This information is related to the travel time of the enabled high sampling rate recording of transient signals during
signals which are already decomposed into their modal compo- faults [7]. Availability of such broad bandwidth sampling capa-
nents. Aerial mode is used for all fault types, whereas the ground bility facilitates better and more efficient use of traveling wave
mode is used to resolve problems associated with certain special based methods for fault analysis.
cases. Wavelet transform is found to be an excellent discriminant
for identifying the traveling wave reflections from the fault irre- The correlation based fault location method introduced in
spective of the fault type and impedance. EMTP simulations are [ 2 ] , is very effective as long as the width of the time window
used to test and validate the proposed fault location approach for to save the forward moving wave is properly selected. Since
typical power system faults. this selection depends on the fault location which is unknown,
Keywords: Power System Faults, Electromagnetic Transients, the window width selection remains an unresolved issue for the
Wavelet Transform, Fault Location, Traveling Waves. practical implementation of this method. Combined use of a
short and a long window has been proposed as one solution for
this problem in [4].
1 Introduction
In this paper, a different approach, based on the wavelet
Transmission line fault location has long been one of the primary transform of the fault transients, is presented. Wavelet transform
concerns of the power industry. Methods of locating power sys- possesses some unique features that make it very suitable for this
tem faults introduced so far, can be broadly classified under two particular application. It maps a given function from the time do-
categories: one based on the power frequency components, and main into time-scaling domain. The wavelet, the basis function
the other utilizing the higher frequency contents of the transient used in the wavelet transform, has bandpass characteristics which
fault signals. The latter is also referred to as traveling wave or makes this mapping similar to a mapping to the time-frequency
ultra high speed fault location method, due to its use of traveling plane. Unlike the basis functions used in Fourier analysis, the
wave theory and shorter sampling windows. wavelets are not only localized in frequency but also in time.
The use of traveling wave theory for fault detection was This localization allows the detection of the time of occurence
initially proposed by Dommel and Michels in [I], where a dis- of abrupt disturbances, such as fault transients. Fault generated
criminant was defined based on the transient voltage and current traveling waves appear a:; such disturbances superposed on the
waveforms in order to detect a transmission line fault. McLaren power frequency signals recorded by the relays. Processing these
et al. have later developed a correlation based technique where signals using the wavelet transform reveals their travel times
the cross correlation between stored sections of the forward and between the fault and the relay locations.
backward traveling waves were used to estimate the travel times
of transient signals from the relays to the fault point [2,3,4]. An
overview of traveling wave based fault location methods can be The potential benefits of applying wavelet transform for anal-
found in [ 5 , 6 ] . ysis of transient signals in power systems have been recognized
in the recent years. Robertson et al. present a comparative
overview of Fourier, short time Fourier and wavelet transforms,
PE-303-PWRD-0-12-1997 A paper recommended and approved by give examples of applying wavelet transform to analyze power
the IEEE Transmission and Distribution Committee of the IEEE Power system transients and extraction of their particular features in [8].
Engineering Society for publication in the IEEE Transactions on Power A similar overview along with application of wavelet transform
Delivery. Manuscript submitted July 28, 1997; made available for to detect and classify power quality disturbances, are given in [9].
printing December 12, 1997. Advantages of using wavelet transform for analyzing transients
and solution of linear time-invariant differential equations using
wavelet transform is demonstrated in [ 101. In this paper, another
useful application of the wavelet transform in solving the prob-
lem of fault location, will be presented. A brief introduction to
wavelet transform will be given before formulating the problem
and presenting the proposed solution method.

0885-8977/98/$10.00 0 1997 IEEE


1476

at a distance x from bus A, this will appear as an abrupt injection


at the fault point. This injection will travei like a surge along the
Wavelet transform has been introduced rather recently in math- line in both directions and will continue to bounce back and forth
ematics, even though the essential ideas that lead to this devel- between the fault point, and the two terminal buses until the post
opment have been around for a longer period C P time.~ It is a fault steady state is reached. Hence, the recorded fault transients
linear transformation much like the Fourier transform, howev- at the terminals of the line will contain abrupt changes at intervals
er with one important difference: it allows time localization of commensurate with the travel times of signals between the fault
different frequency components of a given signal. Windowed to the terminals. Using the knowledge of the velocity oftraveling
Fourier transform also partially achieves this same goal, but with waves along the given line, the distance to the fault point can
a limitation of using a fixed width windowing function. As a be deduced easily. This is the essential idea behind traveling
result, both frequency and time resolution of the resulting trans- wave methods. Unlike the correlation based methods where the
form will be apriori fixed. In the case of the wavelet transform, forward and backward traveling wave components are computed
the analyzing functions, which are called wavelets, will adjust and used for the cross correlation, in the wavelet based approach,
their time-widths to their frequency in such a way that, higher the composite signal (voltage or current) at the relay location is
frequency wavelets will be very narrow and lower frequency directly analyzed.
ones will be broader. This property of multi resolution is partic- In three phase transmission lines, the traveling waves are
ularly useful for analyzing fault transients which contain local- mutually coupled and therefore a single traveling wave velocity
ized high frequency components superposed on power frequency does not exist. In order to implement the traveling wave method
signals. Thus, wavelet transform is better suited for analysis of in three phase systems, the phase domain signals are first decom-
signals containing short lived high frequency disturbances super- posed into their modal components by means of the modal trans-
posed on lower frequency continuous waveforms by virtue of this formation matrices. In this study, all transmission line models
zoom-in capability. are assumed to be fully transposed, and therefore the well known
Given a function f ( t ) , its continuous wavelet transform Clarke's constant and real transformation matrix given by:
(WT) will be calculated as follows:

where, a and b are the scaling (dilation) and translation (time is used. The phase signals are transformed into their modal com-
shift) constants respectively, andQ,I is the wavelet function which ponents by using this transformation matrix as follows:
may not be real as assumed in the above equation for simplicity.
The choice of the wavelet function (mother wavelet) is flexible Sinode = TSphase (4)
provided that it satisfies the so called admissibility conditions where, Smo& and Spha.ve are themodal and phase signals (voltages
P11. or currents) vectors respectively.
Wavelet transform of sampled waveforms can be obtained by Clarke's transformation is real and can be used with any
implementing the discrete wavelet transform which is given by: transposed line. If the studied line is untransposed, then an eigen-
vector based transformation matrix, which is frequency depen-
dent, will have to be used. This matrix should be computed at
a frequency equal or close to the frequency of the initial fault
transients.
where, the parameters a and b in Eq.( 1) are replaced by a; and Recorded phase signals are first transformed into their modal
ka?, k and m being integer variables. In a standard discrete components. The first mode (mode l), is usually referred to as the
wavelet transform, the coefficients are sampled from the contin- ground mode, and its magnitude is significant only during faults
having a path to ground. Hence, this component can not be used
uous WT on a dyadic grid, a0 = 2 and bo = 1, yielding a: = 1, for all types of faults. The second mode (mode 2), also known as
U;' i,
= etc. b = k x 2-',i being an integer variable. the aerial mode, however is present for any kind of fault. Accord-
Actual implementation of the discrete wavelet transform, in- ingly, the fault location problem is formulated based essentially
volves successive pairs of high-pass and low-pass filters at each on the aerial mode, making occasional use of the ground mode
scaling stage of the wavelet transform. This can be thought of signal for purposes of distinguishing between certain peculiar sit-
as successive approximations of the same function, each approx- uations, which will be discussed in the next section. Depending
imation providing the incremental information related to a par- on the existing communication scheme between the two ends of
ticular scale (frequency range), the first scale covering a broad the line, fault location problem can be solved in two different
frequency range at the high frequency end of the spectrum and the ways described below.
higher scales covering the lower end of the frequency spectrum
however with progressively shorter bandwidths. Conversely, the
first scale will have the highest time resolution, higher scales will Two ended sync ronized recording
cover increasingly longer time intervals. While, in principle any
admissible wavelet can be used in the wavelet analysis, we have Fault signals are recorded simultaneously at both ends of the
chosen to use the Daubechies4 [9],[12] wavelet as the mother line by two separate channels both of which are using the same
wavelet in all the transformations. time reference synchronized using Global Positioning Satellite
(GPS) receivers. The recorded waveforms will be transformed
into modal signals, after which the modal signals will be analyzed
using their wavelet transforms. Let t~ and t g correspond to the
lem times at which the modal signal wavelet coefficients in scale 1,
show their initial peaks for the signals recorded at bus A and
Consider a single phase lossless transmission line of length B respectively. Assuming that the recorded signals at the two
e, connected between buses A and B, with a characteristic ends of the line are fully synchronized, the delay between the
impedance 2, and traveling wave velocity of U . If a fault occurs fault detection times at the two ends, i.e. t d = t g - t A , can be
1477

determined [13]. The distance between the fault point to bus A Insignificant coefficients will imply that the fault is in the remote
will then be given by: half of the line, and vice versa.
If the fault is determined to be in the near half ofthe line, then
X =
e - v, td td in Eq.(6) will simply be the time interval between the first two
2 peaks of the scale 1 WTCs for the aerial mode.
If the fault is suspected to be in the second half of the line,
where, then td in Eq.(6) will be replaced by:
e is the length of the line, x is the distance to fault from bus A,
and U, is the speed of the traveling waves for mode m. td = 2t - tx (7)
where:
3.2 Single ended recording t is the travel time for the entire line length, and e, is the time
interval between the first two peaks of aerial mode WTCs in
A more robust configuration that does not require remote end scale 1.
synchronization is when the fault location is determined based Figure 1 shows the flowchart for the proposed fault location
solely on the recorded signals at one end of the line. However, in algorithm based on the wavelet transform coefficients. Next
such a case, due to the lack of any other time reference, all time section contains results of simulations used to test this proposed
measurements will be with respect to the instant when the fault algorithm for various fault types and line configurations.
is first detected. Therefore, fault location calculations will be
based on the reflection times of the traveling waves from the fault Transducer
point. Unfortunately, for faults involving a ground connection, output
not only those reflections from the fault point, but also from the
remote end bus will be observed at the sending end of the line.
Proper algorithms should therefore be devised in order to dis-
tinguish between close-in and remote faults which may produce Transformation
similar reflection patterns for the grounded faults. The following
sections describe our proposed approach to accomplish this task.
Wavelet

3.2.1 Approach I: Ungrounded faults


It has long been observed that ungrounded faults such as line-to-
line or ungrounded three-phase, do not cause significant reflec-
L-r
Transformation

tions from the remote end bus during the fault transients. Thus,
by measuring the time delay between the two consecutive peaks
in the wavelet transform coefficients of the recorded fault signal
at scale 1, and taking the product of the wave velocity and half of
this time delay, the distance to the fault can easily be calculated
for these kinds of faults. The fault distance will be given by the YE
equation:
Ungrounded Fault

calculate the fault loc.


where, as in Section 3.2.1
x is the distance to the fault, v is the wave velocity (for the mode
used), and td is the time difference between two consecutive I
I r

peaks of the wavelet transform coefficients. Grounded Faull
Remote half of the line. Grounded Fault
3.2.2 Approach 11: Grounded faults Based on Scale 1 Mode 2 Near half of the line.
calculate td as in Eq. (7) Based OD Scale 1 Mode 2
When the fault involves a connection to ground, then sending end then calculate the fault calculate the fault loc.
signals may contain significant reflections from the remote end as in Section 3.2.1
bus in addition to the ones from the fault point. Also, depending I
on the location of the fault, the reflections from the remote end
may arrive before or after those reflected from the fault point. Figure 1: Flowchart of the proposed fault location algorithm
It can be easily verified by using the Lattice diagram method,
that the remote end reflections will arrive later than the fault
reflections if the fault occurs within half the length of the line,
close to the relay location. The opposite will be true if the fault
is situated in the second half of the line. It is observed that, in 4 Simulation results
the former case the ground mode wavelet transform coefficient
(WTC) for scale 1, shows significant peaks, while the latter case The ATFEMTP program [ 141 is used to calculate the transient
ground mode WTC for scale 1 remains insignificant below the signals in the power system. Figure 2 shows the system config-
chosen detection threshold. uration used in the simulations. The frequency dependent model
Therefore, first a decision is made on whether or not the is used to model the line [ 151. The relays are located at hushar A
fault is grounded, based on scale 2 WTCs of the ground mode and B for the double ended configuration and at busbar A for the
signals. If these coefficients are found significant, then the fault single ended configuration.
will be assumed to be a ground fault. Next decision will be made For this tower configuration, mode 2 (aerial mode) has a
on which half of the line the fault is actually located. This is propagation velocity of 1.8 182 x lo5 miles/sec. A sampling time
done by observing scale 1 WTCs of the ground mode signals. of l o p s is used. The system is simulated using double and single
1478
1 = 200 miles
c * Scale 1, mode 2 (aerial mode)

345 KV 1-x
9
:t
X

I
I( D-c------h 345 Kv

Figure 2: Schematic diagram of the simulated system

ended configurations under various kind of faults. Different type


of balanced and unbalanced faults at different locations along
the line and at different inception angles are simulated. Results
2t II
of single phase to ground, phase to phase and three phase to
ground faults for an inception angle of 108 degrees are reported 20 20 5 21 21 5 22 225 23
to illustrate the method. The modal signals are decomposed using time (ms)
the Daubechies4 wavelet where number 4 represents the number
ofwavelet coefficients. Only the first two scales, scale 1 and scale Figure 4: Single phase to ground fault at 120 miles from A. Peaks
2 of the WTC are used in the proposed fault location method. correspond to the predicted ones in Fig. 3.
In order to minimize the noise effect, we squared the wavelet
coefficients at each scale as also done in [9].
A lattice diagram illustrating the reflection and refraction of
traveling waves initiated by the fault transients, is shown in Fig- 5(a) and (b) show the WTC for scale 1, of the voltage transients
ure 3. On the left side of the figure, a line connecting buses A and recorded at bus A and B respectively.
B is drawn vertically. The line is 200 miles long. A single phase In this example, the first WTC peak at bus A occurs at tA =
to ground fault is assumed to occur at point F,120 miles from bus 20.15 ms, and at bus B at t B = 21 ms, yielding f d = 0.85 ms and
A. The horizontal axis starting from point F,represents the time. using Eq.(5):
A set of arrows are shown below the lattice diagram, indicating
the arrival times of various waves reflected from the fault as well 200- 1.81 x io5 x 0.85 x 1 0 - ~
x= = 22.99 miles.
as bus B. Mode 2 (aerial mode) is considered only. The travel 2
times from the fault to bus A, and from the fault to bus B are
designated by TI and T2 respectively. Given the traveling wave
velocity v 2 for mode 2, TI and T2 will be given by 120 mi I v 2 and Bus A: Scale 1, mode 2
80 mi 1 U:! respectively. 0 21
Figure 4 shows the WTC at scale 1 calculated for the example 7-

of Figure 3. Comparing the WTC peak times with the arrival


times of waveform reflections at bus A, it can be observed that
there is a one to one correlation between them. Simulation results
for both the two ended and single ended fault location approaches
will now be given.

T2 3T2 2Tl+T2 5T2 B u s B: Scale 1, mode 2


R
3 1 5 3 j

* ,
I I .** . .

time (ms)
A T1 T1+2TZ 3T1 T1+4T2

Figure 5: Three phase fault at 20 miles from A.

*Ilj The arrival time of the first transient peak depends on the
velocity of the line and the fault distance, it is independent of
the type of fault, hence the method applies to all type of faults
Figure 3: Lattice diagram for a single phase to ground fault at 120 provided the two terminal recordings are synchronized in time.
miles from A.
4.2 Single ended recording
4.2-1 Ungrounded faults:
4. ronized recording
Figure 6 shows the WTCs for an example of a phase to phase
Assuming synchronized recording of fault transients at both ends fault at 30 miles from A. It can be seen from the figure that mode
of the line, a three phase fault is simulated at 20 miles away from 1 (ground mode) signals are zero, therefore mode 1 WTCs can
bus A. Mode 2 (aerial mode) voltage signals are used only. Figure be used to identify this as an ungrounded fault.
1479

In this case, td will be directly obtained by measuring the time a)Scale 1, mode 2 c)Scale 1, mode 1
2 1.5r I
difference between the first two peaks in Figure 6(a) and using
Eq.(6) of Approach I described in section 3.2.1.

a)Scale 1, mode 2 c)Scale 1, mode 1


I
I
21 22 23
time (ms)
d)Scale 2, mode 1
5
Q)

A4
30 21 22 23 0
7
time (ms) time (ms) x 3
b)Scale 2, mode 2 d)Scale 2, mode 1 cu
2, I I
< 2
6
z1 0
20 21 22 23
time (ms) time (ms)

Figure 7: Phase to ground fault at 30 miles from A.


20 21 22 23
time (ms) time (ms)
on the td measurement of Eq.(7) per the flowchart of Figure 1.
Figure 6: Phase to phase fault at 30 miles from A. Calculations for the fault location are as follows:

td = 2 x 5.5 x x 200 - 0.32 x 1 0 - ~= 0.0019 ms.


4.2.2 Grounded faults:
1.9 x x 1.8182 x lo5
In the case of ground faults, it is observed that WTC contains X = = 172.72 miles.
the signatures of not only the reflections from the fault point, but 2
also those from the remote end bus. The former and the latter
reflections can not be distinguished and identified only based on
the aerial mode WTCs. In this case, a fault at distance x and a 4.3 Mutually coupled lines
fault at distance I - x will yield similar WTCs for the aerial mode
signals. However, the true fault location can be determined based Mutual coupling between lines mostly affect the ground mode
on the information provided by the ground mode WTCs. This signals, the effect on the aerial mode is not significant. In order
can be illustrated by the following example. to investigate the effect of mutual coupling on the fault location
Consider a single phase to ground fault at 30 miles from bus calculation, the test system shown in Figure 9 is considered.
A. The WTCs obtained for this case are shown in Figure 7. The It is noted that, since the ground mode WTCs are used on-
same type of fault occuring at 170 miles from bus A yields the ly to discriminate between different types of faults (unground-
WTCs shown in Figure 8. In these figures, subplots (a) and (b) ed, grounded near-end, grounded far-end) and not to obtain any
show the aerial mode WTCs at scales 1 and 2, while (c) and (d) time measurements, their strong mutual coupling to the parallel
are the ground mode WTCs at scales 1 and 2, respectively. lines will not hinder the fault location calculations. Aerial mode
Following the steps of the fault location algorithm given in WTCs are not significantly affected by the presence of mutually
Figure 1, the following results will be obtained: coupled lines, therefore the distance calculation based on the
proposed algorithm of Figure 1 remains valid for these cases.
Case 1: Fault at 30 miles from bus A. Simulation results support this claim. Comparing the aerial mode
WTCs obtained for the mutually coupled lines and those where
Figure 7(c) shows that mode 1 (ground mode) scale 1 WTCs mutual coupling is ignored, it is seen that they remain rather
are not zero. Hence, according to the flowchart in Figure 1 , fault insensitive to the existence of mutual coupling between lines.
distance should be calculated using Eq.(6) where td is simply
the difference between the first two peaks in Figure 7(c). The
calculated fault distance for this example is: 4.4 Series capacitor compensated lines
1.8182 x lo5 x 0.32 x Series compensation capacitors are known to affect the fault loca-
X = = 29.09 miles. tion methods that are based on effective impedance seen from the
2
sending end of the line. The proposed method, which is based on
Case 2: Fault at 170 miles from bus A. wavelet transform coefficients at low scales (scales 1and 2), will
reman unaffected by the presence of series capacitors since the
In this case mode 1 scale 1 WTCs are zero as shown in impedance modification at high frequencies (low scales) due to
Figure 8(c). Figure 8(d) however shows that scale 2 WTCs for the series capacitor will be negligible. Simulation results confirm
the same mode are not zero, indicating that the fault is a ground this observation. The wavelet transform coefficients obtained for
fault but it occured at a point closer to the remote end than the compensated and uncompensated line faults look almost identi-
sending end. Hence, the fault distance will be calculated based cal for all the simulated test cases.
1480
d)Scale 1, mode 2 c)Scale 1, mode 1 [2] S. Wajendra and P.G. McLaren, Traveling-Wave Tech-
101 1,
niques Applied to the protection of Teed Circuits: Prin-
ciple of Traveling Wave Techniques, IEEE Transactions
on Power Apparatus and Systems, Vol. PAS-104, no. 12,
pp.3544-3550, Dec. 1985.
[3] S. Rajendra, and P. G. McLaren, Traveling Wave Tech-
niques Applied to the Protection of Teed Circuits: - Multi -
Phase I Multi Circuit System, IEEE Transactions on Pow-
er Apparatus and Systems, Vol. PAS- 104, no. 12, pp.355 1-
time (ms) time (ms) 3557, Dec, 1985.
b)Scale 2. mode 2 d)Scale 2, mode 1
151 I 4, 1
[4] E. H. Shehab-Eldin, and P. G. McLaren, Traveling Wave
? I
aJ I Distance Protection - Problem Areas and Solutions, IEEE
Transactions on Power Delivery, Vol. 3, no. 3, pp. 894-902,
July 1988.
[5] Microprocessor Relays and Protection Systems, IEEE
Tutorial Course, 88EH0269-1-PWR.
161 G.B. Ancell, and N.C. Pahalawaththa, Effects of Fre-
quency Dependence and Line Parameters on Single End-
ed Traveling Wave Based Fault Location Schemes, ZEE
Figure 8: Phase to ground fault at 170 miles from A. Proceedings-C, Vo1.139, No.4, July 1992, pp.332-342.

345 KV 345 Kv
[7] J. Blake, P. Tantaswadi, and R.T. de Carvalho, In-Line
Sagnac Interferometer Current Sensor, IEEE Trans. on
I \ PowerDelivery, Vol.11, No.1, January 1996, pp.116-121.
345 KV I 345 Kv
[SI D. C. Robertson, 0. I. Camps, J. S. Mayer, and W. B. Gish,

-
I

100 miles
I

100 miles
I
c
Wavelets and Electromagnetic Power System Transients,
IEEE Transactions on Power Delivery, Vol.11, No.2, pp.
1050-1058, April 1996.

Figure 9: Circuit diagram of the simulated system with mutually [9] S. Santoso, E. Powers, W. Grady, and P. Hoffmann, Pow-
coupled lines. er Quality Assessment via Wavelet Transform Analysis,
IEEE Transactions on Power Delivery, Vol.11, N0.2, pp.
924-930, April 1996.
5 [lo] 6. T. Heydt, and A. W. Galli, Transient Power Quality
Problems Analyzed Using Wavelets, IEEE Transactions
This paper presents a new, wavelet transform based fault loca- on Power Delivery, V01.12, No.2, pp. 908-915, April 1997.
tion method. Using the traveling wave theory of transmission [ 111 I. Daubechies, Ten Lectures on Wavelets, SIAM, Philadel-
lines, the transient signals are first decoupled into their modal phia, Pennsylvania, 1992.
components. Modal signals are then transformed from the time
domain into the time-frequency domain by applying the wavelet [12] MATLAB Users Guide, The Math Works Inc., Natick,
transform. The wavelet transform coefficients at the two lowest MA.
scales are then used to determine the fault location for various
types of faults and line configurations. The proposed fault loca- [ 131 A. Phadke, J. Thorp, ComputerRelayingfor Power System-
tion method is independent of the fault impedance and is shown s, John Wiley & Sons Inc., New York, 1988.
to be suitable for mutually coupled tower geometries as well as
series capacitor compensated lines. The method can be used both [ 141 Alternative Transients Program, Bonneville Power Admin-
with single ended and synchronized two ended recording of fault istration, Portland, Oregon.
transients. The fault location estimation error is related to the
sampling time used in recording the fault transient. Furthermore, [ 151 J. R. Marti, Accurate Modeling of Frequency Dependent
for grounded faults near the middle of the line, mode 1 signals Transmission Lines in Electromagnetic Transient Simula-
from the fault and from the far end become comparable increas- tions, IEEE Trunsactlons on Power Apparatus and Sys-
ing the error of the fault location algorithm. Simulation results tems, Vol. PAS-101, no. l,pp.147-155, Jan. 1982.
are given to demonstrate the performance of the method. Fernando N. Magnago obtained the B.S. degree from UNRC,
Argentinain 1990 and his M.S. degree from Texas A&M Univer-
sity, College Station, TX in 1997. He is currently a Ph.D. student
at Texas A&M University.
References
Ali Abur (SM90) received the B.S. degree from M E W , Turkey
H. W. Dommel, and J. M. Michels, High Speed Relaying in 1979, the M.S. and Ph.D. degrees from The Ohio State Uni-
using Traveling Wave Transient Analysis, IEEE Publica- versity, Columbus, OH, in 1981 and 1985 respectively. Since
tions NO. 78CH1295-5 PWR, paper no. A78 214-9, IEEE late 1985, he has been with the Dept. of Elect. Eng. at Texas
PES Winter Power Meeting, New York, January 1978, A&M University, College Station, TX, where he is currently an
pp.1-7. Associate Professor.

Vous aimerez peut-être aussi